Operating Instructions Fire Alarm System EBL512
Contents
1. tested continue as above EPT H7 j If not scroll or push Return to logout NOTE If the control unit door is left open the output s for routing equipment fire brigade tx may be disabled if programmed so in Win512 A sensor in test mode will not be able to activate fault 94 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 Maintenance H8 30 1 Access code for maintenance Access code for access level 3 is required for menu H8 NOTE If login to level 2 was made with code for level 3 or 4 no code to access level 3 is required here Access According to chapter Access see page 57 Scroll to menu H8 Maintenance ACCEPT H8 A Access code _ When required see above enter the access code for level 3 Enter the code 4 digits Access code The digits are replaced in the display NO ACCESS The access code was not correct Try again Disable or r nable outputs for The access code was routing equipment ACCEPT S1 correct This is menu S1 Push A to accept or scroll to the following menus S2 S8 95 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 2 Disable or re enable outputs for routing equipment H8 S1 Outputs for routing equipment fire brigade tx fault tx can be disabled via this menu They stay disabled
2. ACC menu H8 Scroll or push Return to logout Bach fire alarm has to be individually reset 101 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 8 Synchronize the control units H8 S7 The control units have to be synchronized when e The following fault message is shown FAULT CU xx has wrong information e After Status Checking has been enabled in Win512 When using Win512 you can use the Synchronize toolbar button Access According to chapter Access code for maintenance see page 95 Scroll to menu S7 Synchronize the control units ACC Shall control units be synchronized 0 Push A to start the synchronisation Yes 0 No ACCEPT Synchronization will take about 30 sec Push Return at once for each CU Hit any key to return Shall control units be synchronized 0 Before a new syncro WSS ros NS AceRp TS nization wait until the a a E t syncronization is ready Push Return to menu S7 Synchronize the control units Scroll or push Return to Acc menu H8 Scroll or push Return to logout 6 Tf the control unit restart in conjunction with this fault the synchronization will happen automatically l Normally a syncronization is done in conjunction with the fault message above When the syncronization is ready the fault will be indicated as Serviced If a syncronization i
3. NOTE Service signal is only an information that the sensor has to be cleaned replaced soon See chapter Acknowledge SERVICE signal H8 S4 page 99 It is not possible to get a print out Access According to chapter Access see page 57 Scroll to menu H4 Present system status on display and printer ACCEPT H4 Disablement Printout Scroll to menu U7 Sensors activating S E Push A to accept Sensor XXXXXX needs service This is a list in which you can scroll Push Return to menu U7 If there are no sensors in the list menu U7 will be shown again Sensors activating S E signal Scroll or push Return to menu H4 Scroll or push Return to logout 77 Matsushita Electric Works Fire amp Security Technology AB MEW00442 26 8 Rev Show event log H4 U8 Operating Instructions EBL512 V1 44 x This is a list of events Types number of events in the list ete can be programmed From this menu it s also possible to get a print out Each event can be listed Via display See Alternative A below Via a print out See Alternative 1 below aa Scroll to menu H4 Scroll to menu U8 Alternative A Alternative 1 Write number of events to be printed e g 010 Present system status on display and ACCEPT H4 printer Disablement Printout l yes Show event log Printout l yes When A is pushed an event will be
4. Short circuit break on the connected cable equipment x 3 S3 Short circuit break on the connected cable equipment e Connected equipment may be stolen e Resistor s missing or not correct value see dwg 512 42 FAULT No reply techn no XXXXXX In spite of the control unit is communicating in both directions one or more units can not be found Check the unit s address DIL switch in the unit or with programming tool 3314 for sensors 3304 3308 Faulty unit not sensor Double break on the COM BS4 loop Single break gives the fault message FAULT Cut off When short circuit isolator 2370 is used Check the loop and the units connected on the isolated loop segment FAULT Output x techn no XXXXXX If the output is programmed for sounders alarm devices it is also indicated by LED Fault Sounder Check fuses F1 F8 on the output unit p c b Short circuit break on the connected wires Wrong no end of line resistor One or more connected units have been removed stolen FAULT Output unit techn no xxxxxx e Fault in the output unit RAM e Fault in the output unit EPROM e Fault in the output unit EEPROM site specific data Replace the output unit output unit p c b FAULT Presentation unit xxxxxx Display unit out of work Fault in the display unit EEPROM site specific data Download the data again or change the EEPROM and download the data again 42 Matsushita Elec
5. In certain premises a special environment can exist which can influence smoke detectors sensors and cause alarm It can be ions from plastics flour dust oil haze aerosols strong perfumes strong ventilation insecticides disinfecting sprays etc If many odd and unnecessary alarms occur the environment must be examined and perhaps other detector types have to be chosen Steam hot air Smoke and heat detectors are influenced by steam and hot air e g from an oven dry blower heater etc 108 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Exhausts Exhausts from cars trucks lift trucks lawn mowers etc influences smoke detectors sensors If windows and doors are open exhausts can slip in that way Lack of maintenance Smoke detectors sensors are influenced by their environment and becomes dirty In an analogue system e g EBL512 a Service signal is given when it s time to clean or exchange the smoke detectors sensors The alternative is to exchange detectors at even intervals to be on the safe side Change in activities or wrong choice of detector If the activities in the premises are altered the detector choice might also need altering Due to special environments see above an in appropriate detector type could have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another ty
6. Re enable control output 0 If more re enablements shall be done continue like 0 RU SU 1 S 2 R 3 RE 4 E above If not push Return to menu B6 Scroll or push Return to menu H2 Scroll or push Return to logout 66 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 7 Re enable non reset zone address H2 B7 This function is normally only used in the Swedish configuration Convention RUS in Win512 One or more alarm points have been reset when still in alarm status e g smoke in a sensor or activated manual call point To prevent an immediate new fire alarm these alarm points have been encapsulated indicated by LED Zone Detector not reset L6 and have to be re enabled before the can generate a new fire alarm Access According to chapter Access see page 57 Scroll to menu H2 Disable or r a Pl Scroll to menu B7 R nable non reset zone address ACCEPT Zone address 000 00 non reset If there are no zone addresses to re enable Re enable push ACC i menu B7 will be shown again If it s the correct zone address to re enable push A to accept If not scroll or write the wanted zone address and push A to accept R nable non reset zone address If more re enablements hall ti i ieee DT shall be done continue like above If not scroll or push Return to menu
7. Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x NOTE By reset restart the Fault tx output s will be activated The restart will last for up to 2 minutes During this 2 min period no fire alarm can be activated A fault is generated in the system and the following message will be shown in the display FAULT Restart CU nn code xx yyyyyyyyyy Date MM DD Time HH MM Regarding code xx and yy y see page 43 This fault is also indicated by LEDs Fault tx L19 and Fault L8 Also LED Fault System L12 can be lit After fault acknowledge menu H6 the LEDs will be turned OFF if there are no other faults NOTE After reset required disablements have to be done 56 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 22 Access To be able to use the key pad in the control unit to get access to the menu tree it is necessary to login with an access code for level 2 3 or 4 See also chapter Access levels page 17 Open the door in the control unit level 1 push the Access button P8 and continue as follows Access Access code _ Enter the code 4 digits Access code The digits are replaced in the display NO ACCESS The access code was not correct Try again Perform monthly test The access code was correct This is menu H1 Push A to accept to perform monthly
8. V1 44 x LED indicators on the Control Panel CP LED indicator Indicating Fault yellow Acknowledged fault s and or acknowledged but not corrected fault s Test mode yellow One or more zones are in test mode 10 Disabled yellow Something in the system is disabled L11 Power on green Power on i e the power supply rectifier and or battery are connected and working properly Fault System yellow System program SW is not running correct e g CPU memory fault Fault Sounder yellow One or more supervised outputs type 3 alarm device have generated fault Fault Power supply yellow Power supply fault s described in chapter Fault messages page 35 Fault tx yellow 1 One or more faults not acknowledged are generated in the system L8 L9 L L L L 12 13 14 15 L 2 Output s for fault tx routing equipment is are activated Key switch yellow The control unit door is open When a TLON see chapter Door open network is used one or more doors in the system are Key switch see page 25 open 17 Service yellow One or more sensors have reached the service level L18 Disabled Fire brigade tx Output s for fire brigade tx routing equipment yellow is are disabled via menu H8 S1 or open door L19 Disabled Fault tx yellow Output s for fault tx routing equipment is are disabled via menu H8 S1 or open door 20 Disabled Extinguish Output s for extinguishi
9. a TLON connection board is plugged in the control unit Some old types of control units not prepared for network connection have to be connected via a serial interface and a Gateway A network can be one channel FTT 10 or several channels connected via routers or repeaters Repeaters are used to increase the maximum cable length C U to C U in a network LonWorks A summing up name for the market of Echelon Corporation Inc technology Matsushita Electric Works Fire amp Security Technology AB MEW00442 2 14 2 15 2 16 2 17 2 18 2 19 Rev Operating Instructions EBL512 V1 44 x Router or Repeater is the same type of unit different configuration All network programming configuration are made with the PC program TLON Manager LED LED Light Emitting Diode Yellow green or red optical indicator lamp External Indicator LED A unit with an LED Connected to an ASB ADB CDB or a detector with a built in LED Lit when the built in LED is lit Display LCD LCD Liquid Crystal Display Display for presentation of fire alarms fault messages etc Normally alphanumeric characters and backlight Door open Key switch In most EBL512 configurations there is a door switch which is activated when the control unit door is opened In some configurations does a key switch replace this door switch The LED Key switch is indicating door open key switch in po
10. the paper within the printer remains there e Take the new paper roll tape the new paper to the old paper and place the paper roll on the printer e Push Paper feed button until the new paper comes out of the printer Cut off the paper and lock the inner door Close the control unit door Paper feed button is different in different configurations conventions The following alternatives are to be found An unsigned grey push button on the left side of the inner door An unsigned black push button P5 below the Silence P2 and Reset P3 buttons NOTE In English configuration this button P5 is green and signed Evacuate and has another function See chapter Control Unit page 12 106 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 34 Battery maintenance The batteries 2 x 12 V 24 Ah are normally placed in the control unit The control unit supervises the batteries and a fault will be activated if something goes wrong They are rechargeable sealed lead acid batteries and maintenance free but the producer s instructions are always to be followed The ambient temperature affects the battery capacity self discharge and life span It shouldn t be higher than normal room temperature For highest safety batteries used in fire alarm installations should never be older than four years 107 Matsushita Electric Works Fire amp Sec
11. until re enabled again via this menu Can be useful during an installation test period when only local alarm is required Disabled outputs are indicated by LEDs Disabled L10 and Disabled Fire brigade tx L18 and or Disabled Fault tx L19 Access According to chapter Access code for maintenance see page 95 Disable or r nable outputs for shee equipment ACCEPT S1 A Routing equipment for FIRE 1 FAULT 1 To move the cursor push gt Edit and h A 1 enabled 0 disabled ACCEPT pears oie to accept A Disable or r nable outputs for Scroll or push Return to routing equipment ACCEPT S1 return to H8 Scroll or push Return to logout 96 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 3 Disconnect COM loop H8 S2 Before physical connection disconnection of loop units etc to a loop or zone line the loop should be disconnected disabled i e no voltage on the loop to avoid damage on the units and control unit Don t forget to re connect the loop zone line again via menu H8 S3 BS4 loop require an Autronica interface board 1584 in the control unit DET8 loop require an 8 zones expansion board 1580 in the control unit Access According to chapter Access code for maintenance see page 95 Scroll to menu S2 Disconnect Disconnect type 0 O COM 1 BS4 Push 2 DET8 3 loop Unit ACCEPT 0
12. Change access code for daily duties ACCEPT H9 Access code _ New code Verify Enter the old code the Access code New code The digits are replaced new code and the new in the display 2 Verify code again H Incorrect access code NO change The code was not correct Try again Change access code for daily duties The code was correct and is now changed to the new ACCEPT H9 code Scroll or push Return to logout 104 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 32 Annual control The building occupier is highly recommended once a year to do some tests beside the monthly tests To avoid the Fault tx output s to be activated they can be disabled via menu H8 S1 or via an open door se chapter Door open Key switch page 25 Regarding the fault condition see chapters Fault page 35 and Fault messages page 35 NOTE Some faults may take a few minutes before they will be activated Each control unit should be tested as follows e Perform monthly test menu H1 e Remove one battery fuse F2 or F3 on the charger board 1557 The following fault message is to be shown FAULT Battery not connected CU xx NOTE xx is depending on control unit e Put back the fuse and acknowledge the fault Menu H6 e Remove fuse F5 not F1 F4 on the connection board 1555 The following fault mess
13. Scroll to menu H2 Disable or r o S Scroll to menu B3 Disable control output Disable control unit Write C U No and push 0 RU4 2265 or SU4 2262 2263 1 S0 S3 2 R0 R1 or 3 Relay board 1581 4 1583 board output Extinguishing system O RU SU 1 S 2 R 3 RE 4 ES not shown in Swedish RUS convention Push A to accept A le 00 0000 control output 0 Depending on the ACCEPI chosen type 0 1 2 3 resp 4 the following f Write the data Push A will be shown E to accept ACCEE relay board 0 output 0 ACCEE output for extinguishing board CU 00 ACCEPT A Disable control unit 00 Type 0 If more disablements shall be done continue O RU SU 1 S 2 R 3 RE 4 ES ACCEPT like above If not push Return to menu B3 Scroll or push Return to menu H2 Scroll or push Return to logout 63 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 4 Re enable zone H2 B4 Disabled zones are listed in menu H4 U1 From this menu it s also possible to get a print out Re enabling via this menu has higher priority than automatic re enabling When all zones have been re enabled The LED Disabled will be turned OFF if there are no other disablements in the system Access According to chapter Access see page 57 Scr
14. Technology AB MEW00442 2 9 2 10 2 11 2 12 2 13 Rev Operating Instructions EBL512 V1 44 x Control Unit C U C LE Control Unit C U Control and Indicating Equipment Unit to which the alarm points are connected e g EBL512 Indicates fire alarm fault condition etc Fire Brigade Panel amp Control Panel see below included or not included Printer included or not included Fire Brigade Panel FBP Unit intended for fire alarm presentation etc for the fire brigade personnel Can be a part of the control unit front adhesive or a separate unit an external FBP In the ext FBP a printer can be included or not included Control panel CP A part of the control unit front adhesive intended for the building occupier service personnel etc to communicate with the control unit system System Several control units connected via a TLON network co operating control units Network TLON LonWorks Echelon Node TLON Conn board Gateway Channel Router Repeater Brief explanations to the words expressions to be found in connection with a network See also separate TLON Technical description TLON TeleLarm Local Operating Network a LonWorks based network for communication between several control units nodes The protocol is LonTalk and the transmission works with doubly terminated bus topology Echelon FTT 10 To connect a control unit to the network
15. accept Start Sensor 000000 Write the sensor s techn number and push A to accept E g 000001 Sensor 000001 Value YYY This is a list in which A you can scroll Push Return to return to Start Sensor Write a new techn number or push Return to menu US Show sensors week average valu Scroll or push Return to menu H4 Scroll or push Return to logout 26 5 1 Reset of a sensor week average value If a sensor is replaced without having generated a service signal its sensor week average value has to be set to the default value otherwise the new clean sensor will inherit the old sensor s value In menu H4 US5 when you see the specified sensor week average value push Fault acknowledged to reset it to the default value See also chapter Acknowledge SERVICE signal H8 S4 page 99 NOTE Authorised service personnel only must do the reset to default value Used incorrectly it can cause nuisance fire alarms gt The first sensor week average value is calculated 10 minutes after SSD download amp restart Until then the default value for that specific sensor type is shown 75 Matsushita Electric Works Fire amp Security Technology AB MEW00442 26 6 Rev Operating Instructions EBL512 V1 44 x Show sensors momentary values H4 U6 Each sensor s actual sensor value can be listed Via display See Alternative A below Via a print out See Alternative 1 below ei
16. access code for programming H5 A10 For security reasons the default code should be changed Access According to chapter Access code for programming H5 see page 81 a to menu A10 E access code for programming ACCEPT Al E wea i So Enter the old code the Access code New code The digits are replaced new code and the new Verify in the display code again Incorrect access code NO change The code was not correct Try again Change access code for programming The code was correct and ACCEPT A10 is now changed to the new code Scroll or push Return to H5 Scroll or push Return to logout 91 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 28 Acknowledge FAULTS H6 LEDs Fault tx L19 and Fault L8 are lit and resp outputs are activated There is a fault message shown in the FBP display s More than one fault is indicated in the display by the text More faults If a fault is automatically corrected before being acknowledged it is indicated in the display by the text Serviced NOTE The fault still has to be acknowledged in menu H6 In menu H6 are all faults listed not acknowledged and acknowledged but not corrected faults All faults fault status are stored in the event log and can be listed see chapter Show event log H4 U8 page 78 When all faults are the LED Fault
17. configuration Scroll or push Return to menu H4 Scroll or push Return to logout 79 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 Programming H5 When commissioning an installation power on and programming a control unit a system menu H5 is used to get certain information and help Only authorised personnel have access to level 4 menus Access code for level 4 is required Via a PC and Win512 access code for level 5 you can e download backup of site specific data e download of SW settings configurations C U amp system data e create and download the user definable text messages shown in the alphanumeric display in the C U ext FBP and in the Display units Via a PC and TLON Manager you can do the TLON network programming configuration TLON Manager is used for programming of network data addresses etc NEWTEXT DOS based older program could be used to create download the user definable text messages shown in the Display units connected to the COM loops 5 Connected to the D connector J1 on the main board 1556 5 Connected to the modular connector J2 on the main board 1556 80 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 1 Access code for programming H5 When commissioning an installation you have to be authorised
18. displayed NOTE No or very small current consumption could not be presented correctly precisely Access According to chapter Access code for programming H5 see page 81 Scroll to menu A6 Display current consumption on COM BS4 loop ACCEPT A6 Select type of loop 0 0 COM 1 BS4 Select type of loop Push A to accept ACCEPT Display current consumption on Write loop number board COM loop 0 unit 00 number 0 3 and control or 1 we AN unit number Push A to Display current consumption on BS4 loop accept 0 board 0 unit 00 ACCEPT p Current consumption on COM loop 0 control unit 00 is xxxx mA Current consumptio n BS4 loop 0 board 0 unit 00 is xxxx mA Display curre mption on Scroll or push Return to COM BS4 loop ACCEPT A6 H5 Scroll or push Return to logout 58 An Autronica interface board 1584 is required in the control unit 87 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 8 Display statistics for COM loop H5 A7 Pollings are the number of pollings questions sent out to the units on the COM loop by the control unit Parity are received parity faults number and faults in relation to pollings Bit are received bit faults number and faults in relation to pollings Answer are received answer faults or no answers number and faults in relation to
19. documentation valid for that HW 52 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 20 EBL512 settings download EBL512 settings are normally factory made before delivery On site it is possible to download the following e The number of addresses max loop units e Convention different functions facilities country depending e Language If you wish to download new EBLS512 settings a PC and Win512 is used Before download the PC has to be connected to the D connector J1 in the control unit main board 1556 in question 1 Start Win512 2 Set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart by setting jumper JP4 RESET momentarily in position approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 The Win512 settings dialog box shows default settings in the different fields Click the Read button to see the actual settings Then write the new settings in the fields respectively 6 Start the downloading The buzzer will now be silenced 7 When the download is ready in the Win512 log view it will be shown Download ready 8 Click the Read button to verify the new settings 9 Reset jumper JP1 BOOT position OFF and do a reset restart see paragraph 2 above Regarding the reset restart see chapt
20. open door in one or more external FBPs should be indicated by the LED Key switch or not Disable outputs for routing equipment Fire brigade tx and Fault tx In Win512 the following can be programmed No disabling Output s for routing equipment Fire brigade tx and Fault tx are not disabled by an open door or Disable if any door in the system is open Output s for routing equipment Fire brigade tx and Fault tx are disabled when a door in a control unit is open Disabled outputs for routing equipment are indicated by the LED Disabled Fire brigade tx Disabled L18 and Fault tx Disabled L19 2 No choice between control unit and any control unit in the system Only valid for control unit doors not ext FBP doors 25 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 12 Technical number Presentation number 12 1 Technical number for COM loop units The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also used to identify which unit has generated a fault 000 127 The address on the COM loop Avoid address 000 Start at 001 Don t have to be in sequence The connections on the COM loop don t have to be in sequence The address is set on DIL switches in each unit With a programming tool 3314 in sensor types 3xxx 0 3 COM loop number 00 29 The control
21. shown Control unit 00 29 BS4 board 0 3 and if required BS4 loop 0 3 27 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 12 3 Presentation number For each fire alarm point input a presentation number NNN NN has to be programmed This number is shown in the FBP display s to identify the point zone generating fire alarm It is also used to disable re enable fire alarm points zones and in control conditions expressions to activate the programmable outputs 00 99 The address within the zone 01 99 00 Zone number only will be displayed for one or more conventional detectors connected to a zone interface ADB or 8 zones expansion board input 000 999 Zone number normally 001 999 Together with the zone number and the address a user definable 40 character text message can be displayed if programmed gt Presentation number is also shown in the display units connected to the COM loops 28 Matsushita Electric Works Fire amp Security Technology AB MEW00442 13 Operating Instructions EBL512 V1 44 x Alarm types 13 1 In case of a fire sensors conventional smoke and or heat detectors manual call points or programmable inputs can generate fire alarm When somebody break into a key cabinet it will also generate a fire alarm The sensors can generate three types of fire alarm Pre alarm Fir
22. system CU xx 1583 German FBP interface board Short circuit cut off on the wires from the extinguishing system equipment connected to the 1583 board in control unit No xx FAULT Wrong type of input unit xxxxxx The input unit is not the same type as programmed Change the programming or the input unit FAULT Wrong type of sensor XXxXXxXx The sensor mounted in the sensor base is not the same type as programmed Change the programming or the sensor 45 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x FAULT Wrong type of unit no XXXXXX The output unit is not the same type as programmed Change the programming or the output unit High Current loop x BS4 board x CU xx BS4 1584 Autronica interface board The current consumption is gt 60 mA on the BS4 loop High Voltage on BS4 Board x CU xx BS4 1584 Autronica interface board The BS4 loop voltage is gt 16V normally it is 14V 0 1V No connection loop x BS4 Board x CU xx BS4 1584 Autronica interface board Cut off break on the BS4 loop This is indicating a single break on the loop Communication has to be performed in both directions to find all units Each 10 minutes an attempt is made to comm in one direction again Short circuit loop x 1 Board x CU xx BS4 1584 Autronica interface board Short circuit or current consum
23. test or EPT H1 scroll to the following menus H2 H9 Explanations Action in the table use push button key e g signed Access Text in display in the table what is shown in the display in the control unit Use Tt and to scroll between the main menus H1 H9 Use A to accept Some main menus have sub menus Use 1 and 4 to scroll between the sub menus e g B1 B9 Use A to accept If instead of a menu identification e g B1 the letter L is shown it means that it is a List Use 1 and to scroll in the list Use lt and gt to move the cursor in a menu Use Return to return from a sub menu to the main menu H1 H9 Use Return to logout from a main menu H1 H9 There will be an automatic logout 10 minutes after the last action i e if the key pad a push button is not being used for 10 min 57 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 23 Perform monthly test H1 The control unit and the installation should be tested on a regular basis If one twelfth of the alarm points are tested each month the whole installation will be tested after one year In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test If a real fire alarm is generated by an alarm point not in test mode the normal fire alarm functions will be activated i e outp
24. xx ASFO lt gt CU Short circuit on the COM loop x one two three or four short 43 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x circuit isolators 2370 ASF are connected on the loop Check the specified and isolated segment on the loop e g CU lt gt ASFO between the control unit and short circuit isolator number 0 Each 10 minutes an attempt is made to re enable the isolated segment again FAULT Short circuit loop x CU xx Short circuit on COM loop x short circuit isolator is not connected on the loop Check the loop NOTE As long as there is a short circuit the COM loop is disabled Each 10 minutes an attempt is made to re enable the loop again FAULT Short circuit x DI Board x CU xx DET8 1580 8 zones expansion board This is indicating a short circuit on input x zone line on the 1580 board The wires cable may have been damaged NOTE As long as there is a short circuit the zone is disabled Each 10 minutes an attempt is made to re enable the zone again FAULT Site specific data no x CU xx Some external influence has caused a fault in the Site Specific Data Can also be shown after downloading Site Specific Data This is very serious Call for service personnel engineer immediately e No 1 SSD downloaded data from PLAN512 Win512 e No 2 SSW data which is changed during operation sensor
25. 0442 18 Operating Instructions EBL512 V1 44 x Programming SSD download 18 1 18 2 The PC program Win512 is used for programming download of the site specific data SSD When the control units is running power supplied and when required the TLON network programming configuration is done the SSD download can start The PC has to be connected to the D connector J1 in the control unit main board 1556 Start Win512 Now you have to be authorised i e you have to log on to the control unit Single Control Unit Start the downloading from Win512 After the downloading an automatic reset restart will take place see chapter Reset Restart page 55 Control Units in a TLON network The PC should be connected to one control unit from which the SSD for all control units can be downloaded In Win512 you select the control unit s to which the SSD should be downloaded Start the downloading from Win512 After the downloading in the selected control unit an automatic reset restart will take place in that control unit see chapter Reset Restart page 55 If you select two or more control units the PC has to be connected to a control unit that shall have no SSD downloaded or to the control unit that has the highest number address because after the downloading to a control unit an automatic reset restart will take place in that control unit and the downloading will start in the next selected
26. 5 External Indicator LED 9 2 16 Display LCD 9 2 17 Door open Key switch 9 2 18 SSD Site Specific Data 9 2 19 SW Software System program 9 3 Overview 10 3 1 The EBL512 system 10 3 1 1 Expansion boards 10 33122 Printer 10 3 2 SW versions 10 3 3 Documents 11 3 4 Applications 11 3 5 PCSW 11 4 Control Unit 12 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 5 LED indicators and push buttons 14 6 Access levels 17 6 1 Access level 1 17 6 2 Access level 2 18 6 3 Access level 3 19 6 4 Access level 4 20 6 5 Access level 5 20 7 Normal operation 21 8 Push button Silence 22 8 1 Silence before a fire alarm 22 8 2 Silence during a fire alarm 22 9 Alarm device on Alarm device off 23 10 Controls ON Controls OFF 24 11 Door open Key switch 25 11 1 LED Key switch 25 11 2 Disable outputs for routing equipment Fire brigade tx and Fault tx 25 12 Technical number Presentation number 26 12 1 Technical number for COM loop units 26 12 2 Technical number for BS4 loop units 27 12 3 Presentation number 28 13 Alarm types 29 13 1 Pre alarm 29 13 2 Fire alarm 30 13 2 1 Alert annunciation 31 13 2 2 2 zone address dependence 31 13 3 Heavy smoke alarm 31 14 Key cabinet 32 14 1 Key cabinet alarm 32 14 2 Key cabinet opened in conjunction with a fire alarm 32 14 2 1 Restori
27. BP to see which alarm point s having generated fire alarm In the display LCD 2x40 alphanumeric characters is on the first row displayed the zone number and the 12 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x address within the zone On the second row is shown a user definable text message if programmed Required fire brigade personnel manoeuvres can be performed from the FBP The CP is used to communicate with the system e g for commissioning monthly tests or maintenance The CP has several system status LEDs A keypad is used to get access to the system a menu tree with main and sub menus and for different manoeuvres Access codes for different access levels are required 13 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 5 LED indicators and push buttons LEDs and push buttons vary according to type and configuration convention country language f D L3 Extinguishing red Output s for extinguishing equipment activated L4 Ventilation yellow Output s for fire smoke ventilation equipment activated L5 Fire brigade tx red Output s for fire brigade tx routing equipment activated L6 Zone Detector not An alarm point has been reset while still in alarm status i e reset it is non reset isolated and has to be re enabled Silence y
28. COM loop 1 BS4 loop 2 Expansion board 1580 3 A ddr zone interface 2226 2335 Push A to accept A j t 2 10 Write the required numbers Push A to Depending on the chosen type 0 1 2 or 3 the following will be shown accept input technical no 000000 ACCEPT type 0 O COM LED Disabled indicates loop Unit ACC disconnected loops etc Continue to disconnect or push Return to menu S2 Scroll or push Return to return to menu H8 Scroll or push Return to logout 97 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 4 Re connect Loop H8 S3 Disconnected disabled loops zone lines are indicated by LED Disabled and listed in menu H4 U1 BS4 loop require an Autronica interface board 1584 in the control unit DET8 loop require an 8 zones expansion board 1580 in the control unit Access According to chapter Access code for maintenance see page 95 Scroll to menu S3 Re connect Loop Re connect type 0 O COM 1 BS4 Push 2 DET8 3 Loop Unit ACCEPT 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 Push A to accept A t 0 Write the required numbers Push A to Depending on the accept chosen type 0 1 2 or 3 the following will be shown input technical no 000000 ACCEP
29. FN Ai Matsushita Electric Works i Fire amp Security Technology AB Operating Instructions MEW00442 Revision Fire Alarm System EBL512 V1 44 x Author Jan Pettersson Date 2003 09 09 Checked by Mikael Ostergren S class Public Approved by Rutger Palsson Bp Number of pages 111 L Product Documentation Manuals Doc MEW00442 doc This page has deliberately been left blank Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Table of contents 2 1 22 2 2 1 Smoke detector 2 2 2 Sensor 2 2 3 Analog detector 2 2 4 Analog Sensor Base ASB 22 5 Conventional detector 2 2 6 Conventional Detector Base CDB PROS Addressable Detector Base ADB 2 2 8 Addressable 2 2 9 Old detector 2 2 10 External line Conventional zone line 2 2 11 ADB input Addressable zone interface Introduction Definitions Explanations MFSTech Alarm points CmAAANINAINANINANNANINANINANINANINIDDADADADADAAHR A 2 3 Output unit 2 4 Output Control output 25 Short circuit isolator 2 6 Display unit 2 7 COM loop 2 8 BS4 loop 2 9 Control Unit C U C I E 2 10 Fire Brigade Panel FBP 2 11 Control panel CP 2 12 System 2 13 Network TLON LonWorks Echelon Node TLON Conn board Gateway Channel Router Repeater 8 2 14 LED 9 2 1
30. H2 Scroll or push Return to logout 67 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 8 Control on Control off H2 B8 Outputs programmed as type 0 control general type 1 fire ventilation and or type 2 extinguishing system can be disabled all at the same time Control off means that even if the control condition expression for resp output is fulfilled the outputs will not be activated Control off is indicated by LED Disabled and is shown in menu H4 U1 Don t forget to re enable the outputs again i c Control on via menu H2 B8 Access According to chapter 8 P Access see page 57 Scroll to menu H2 Disable or r Scroll to menu B8 Control on Control off Control off 0 7 Push 1 or 0 and push A to accept Control on Control off Scroll or push Return to menu H2 Scroll or push Return to logout 5 Also the Extinguish equipment output on the German FBP interface board 1583 68 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 9 Alarm device on Alarm device off H2 B9 Outputs programmed as type 3 alarm device sounder can be disabled all at the same time Alarm device off means that even if the control condition expression for resp output is fulfilled the outputs will not be activat
31. MM e Ifmore than one fault is activated the text More faults is added after the time e Ifa fault has been corrected before it has been acknowledged the text Serviced is added after the time Faults and disablements are indicated by a 2 sec beep when an open control unit door is being closed If a fault can not be corrected it is important to contact service personnel engineer immediately 16 1 Fault messages Below follows a list of all fault messages in alphabetical order CU xx have no contact with CU xx e Check the TLON network cable connections e Faulty TLON connection board 1590 e No power supply to the control unit Double addresses on techn no XXXXXX 37 In Win512 fault latching or not fault latching can be selected Fault latching the faults always have to be acknowledged Not fault latching corrected faults will automatically be removed from the fault list menu H6 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Two or more units connected to a BS4 loop 1584 board have been given the same address Check the units FAULT 1581 Relay board x CU xx 1581 8 relays expansion board Fault on no communication to 1581 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1582 printer board x CU xx 1582 External FB
32. P interface board e Fault on no communication to 1582 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 e Fault on connected unit s FAULT 1583 Extinguishing system CU xx 1583 German FBP interface board e Fault in the extinguishing system equipment connected to the 1583 board in control unit No xx FAULT 1583 GFBP interface board CU xx 1583 German FBP interface board e Fault on no communication to 1583 board in control unit No xx Check address setting and connections on the board Check programming Win512 e Check the fuses F1 and F2 on the 1583 board FAULT ASF COM loop x control unit xx ASF 2370 Addressable short circuit isolator This message is only shown when the control unit works in Sensitive fault detection mode menu H5 A2 A short circuit shorter faster than the time delay for an ordinary fault has occurred on the COM loop Could be used for commissioning maintenance purposes 36 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Battery not connected CU xx Also indicated by LED Fault Power supply Batteries 2 x 12 V are missing or not correctly connected Fuse es F2 F3 on the charger board 1557 is are blown Other battery fuse is blown e g when the batteries are placed outside the control unit Battery outpu
33. T t type 0 0 COM Continue to re connect or 3 Loop Unit ACC push Return to menu S2 LED Disabled will be turned off if there are no other disablements in the system Re connect Loop Scroll or push Return to return to menu H8 Scroll or push Return to logout 98 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 5 Acknowledge SERVICE signal H8 S4 See chapter Sensors activating SERVICE signal H4 U7 page 77 When service signal from a sensor is acknowledged the sensor is given a default sensor value for a new clean sensor i e first replace the sensor then acknowledge the service signal NOTE Ifa sensor is replaced without activating service signal it has to be reset to the default sensor value See chapter Reset of a sensor week average value page 75 Access According to chapter Access code for maintenance see page 95 Scroll to menu S4 Acknowledge SERVIC ACCEPT S4 A Sensor xxxxxx needs service If there are no sensors to acknowledge menu S4 will be shown again If it s the correct sensor to acknowledge push Fault acknowledge and you will return to menu S4 If not scroll or write the wanted sensor and push Fault acknowledge and you will return to menu S4 or push Return to S4 Fault acknowledge The service signal for that sensor is now acknowledged and _ I
34. access code to level 4 If login to level 2 was made with code for level 4 no code is required here Access According to chapter Access page 57 Perform monthly test EPT H1 Scroll to menu H5 Programming EPT H5 Access code _ If login was made with code for level 4 no code is needed Enter code for level 4 Access code The digits are replaced 4 digits in the display NO ACCESS The access code was not correct Try again Calibration of monitored outputs The access code was correct This is menu H5 A1 Push A to accept scroll or push ACCEPT Al return to menu H5 81 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 2 Calibration of monitored outputs H5 A1 The voltage outputs SO S3 in each control unit are monitored supervised as well as the outputs 0 3 in each output unit type 2262 and 2263 A calibration has to be performed to ensure the function When all alarm devices sounders etc have been connected including required resistors and when the SSD download is ready calibration has to be done as follows Access According to chapter Access code for programming H5 see Calibration of monitored outputs ACCEPT Al Calibration in process Please wait Calibration of monitored outputs Calibration is ready Scroll or push Return to H5 Scroll or push Return to log
35. age is to be shown FAULT monitored output 0 CU xx NOTE xx is depending on control unit e Put back the fuse and acknowledge the fault When output units type 2262 2263 are installed e Remove the battery fuse F3 on the rectifier p c b The following fault message is to be shown FAULT Battery output unit xxxxxx NOTE xxxxxx is depending on output unit and control unit e Put back the fuse and acknowledge the fault e Remove fuse F8 on the output p c b The following fault message is to be shown FAULT Output 3 techn no XXXXXX NOTE xxxxxx is depending on output unit and control unit e Check the manual call points the glass Take required measures Use the manual call point alarm test key e Check some control outputs Are they activated according to programmed control expressions 105 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 33 Changing paper in the printer When the paper roll is almost empty a red line appears on one edge of the paper Change the paper roll before it s completely empty Always have a spare paper roll on site Change the paper roll as follows e Read all instructions before changing the paper roll e Open the control unit door Unlock the metal inner door by removing the screw placed on top to the left of the inner door Open the inner door e Remove the old paper roll carefully cut the paper so that
36. ators 2370 ASF are connected on the loop Communication has to be performed in both directions to find all units The break is to be found in the specified segment e g 38 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x ASF 3 lt gt CU between short circuit isolator number 3 and the control unit Each 10 minutes an attempt is made to comm in one direction again FAULT Cut off ET8 board x CU xx DET8 1580 8 zones expansion board This is indicating a break or missing end of line resistor on input x zone line on the 1580 board A detector may have been removed stolen from its base FAULT DET8 board x CU xx DET8 1580 8 zones expansion board Fault on the 1580 board lt minus CU xx Earth fault is detected Check all cables for damage etc The function of the control unit can not be guaranteed Call for service personnel engineer Barth fault output unit xxxxxx Check all cables connected to the output unit FAULT external FBP x board x CU xx The control unit can not communicate with the ext FBP or data converter Check the connections Check the cable break Check address DIL switch in the ext FBP Is correct address set Several ext FBPs have the same address Faulty ext FBP External fuses control unit xx 39 Matsushita Electr
37. be acknowledged see chapter Acknowledge FAULTS H6 page 92 100 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 7 Activate address in alarm mode H8 S6 One or more alarm points addresses can be set in alarm status Fictitious zone addresses can not be used and address 00 can only be used for a conventional zone line e g an exp board 1580 input NOTE All outputs standard and programmable which would have been activated by a real fire alarm from the same alarm point will be activated by this manual alarm as well The LED in the detector base ext LED will not be lit Access According to chapter Access code for maintenance see page 95 Scroll to menu S6 Activate address in alarm mode ACCEPT lect zone 000 address 00 ACCEEF Write the zone and lect zone 123 address 45 Push A to accept address ACCEPT activate the fire alarm Alarm No 001 123 45 Normal fire alarm presen Information text if programmed tation in the display s in the whole system Select zone 000 address 00 The fire alarm shown in ACC the display will be reset After that another alarm point can be activated i e continue as above Select zone 000 One more alarm point can be activated i e continue as above If not push Return to menu S6 Activate address in alarm mode Scroll or push Return to
38. ccess see page 57 eae Lo Push 1 for an automatic print out Push A for presentation in the Present system status on display and printer ACCEPT H4 Disablement Printout Scroll to menu U4 Activated 2 zone address dependent zone address Printout l yes display When A is pushed zone amp address will be shown in the display e g ALARM zone XXX address XX co incidence Return Activated 2 zone address dependent zone address Printout l yes This is a list in which you can scroll If there are no alarms if Return is pushed and after the last print out menu U4 will be shown again Scroll or push Return to menu H4 Scroll or push Return to logout gt When two or more zones dependent on each other are in alarm status fire alarm will be activated in the system When two or more units zone addresses dependent on each other are in alarm status fire alarm will be activated in the system 74 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 5 Show sensors week average values H4 U5 Each sensor s week average sensor value can be listed It is not possible to get a print out Access According to chapter Scroll to menu H4 Present system status on display and printer ACCEPT Disablement Printout l yes Scroll to menu U5 Show sensors week average valu Push A to
39. control unit Regarding the automatic reset restart see chapter Reset Restart page 55 3 Access code for level 5 should be entered via the PC Win512 4 Tt is recommended to select only one control unit at a time but of course it is depending of the SSD quantity number of COM loop units texts outputs etc and up to three control units are normally okay NOTE After the automatic reset restart of a control unit a number of faults could be generated This will cause heavy traffic on the network which could affect the SSD downloading to other control units Downloading is performed in a consecutive order i e 0 1 2 3 4 29 amongst the selected control units 50 Matsushita Electric Works Fire amp Security Technology AB MEW00442 18 3 18 3 1 18 3 2 Rev Operating Instructions EBL512 V1 44 x User definable text messages download When a fire alarm an addressable alarm point is activated the presentation number Zone amp Address will be shown on the first row in the control unit s and the ext FBP s alphanumeric display On the second row will be shown a user definable text message if programmed The user definable text message will also be printed out when a printer is available See also chapter Fire alarm page 30 User definable text messages can also be shown in Display units connected on the COM loops The texts up to 40 alphanumeric characters are created an
40. d downloaded via Win512 See Planning Instructions chapter User definable text messages An older DOS based PC program NEWTEXT could also be used see Planning Instructions chapter Display units addressable See also Win512 help Download in Control unit The user definable text messages which are to be displayed in the control unit s ext FBP s alphanumeric display could be downloaded in one control unit for the whole the system A specific addressable alarm point will have the same user definable text message in all control units ext FBPs If a specific addressable alarm point has no individual text a default alarm text could be displayed This default text could be different in the different control units Download in Display unit The user definable text messages which are to be displayed in the Display units connected on the COM loops are to be downloaded in each Display unit A specific addressable alarm point can have different user definable text message in the different Display units If a specific addressable alarm point has no individual text a default alarm text could be displayed This default text could be different in the different Display units 4 Ext FBPs are connected to a control unit and they will display the same texts that will be displayed in the control unit they are connected to 51 Matsushita Electric Works Fire amp Security Technology AB MEW00442 19 Opera
41. d I Scroll to menu H4 Scroll to menu U6 Alternative A E g 000001 A Alternative 1 Present system status on display and printer ACCEPT Disablement Printout l yes Show sensors momentary values Printout l yes Start Sensor 000000 Sensor 000001 Value YYY Start Sensor 000000 End Sensor 293127 According to chapter Access see page 57 Push A for display presentation or Push 1 for print out Write the sensor s techn number and push A to accept This is a list in which you can scroll Push Return to return to Start Sensor Write a new techn number or push Return to menu U6 Scroll or push Return to menu H4 Scroll or push Return to logout Write the start and end sensors techn numbers Push A to accept start the print out Automatic return to menu U6 E g 000001 003127 WAM Show sensors momentary value Printout l yes 76 Scroll or push Return to menu H4 Scroll or push Return to logout Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 7 Sensors activating SERVICE signal H4 U7 A sensor s week average value is below or over the service level resp for this type of sensor Service signal is indicated by LED Service L17 Menu H4 U7 is a list of the sensor s activating service signal It is not possible to get a print out
42. dar and clock H3 70 26 Present system status on display and printer H4 71 26 1 Disablement H4 U1 71 26 2 Disablement by time channel H4 U2 72 26 3 Show open doors H4 U3 73 26 4 Activated 2 zone address dependent H4 U4 74 26 5 Show sensors week average values H4 US5 75 26 5 1 Reset of a sensor week average value 75 26 6 Show sensors momentary values H4 U6 76 26 7 Sensors activating SERVICE signal H4 U7 77 26 8 Show event log H4 U8 78 26 9 Show configuration H4 U9 79 27 Programming H5 80 27 1 Access code for programming H5 81 27 2 Calibration of monitored outputs H5 A1 82 27 3 Sensitive fault detection mode H5 A2 83 27 4 Direction for communication on COM loop H5 A3 84 27 5 Show information about site specific data H5 A4 85 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 6 Display current consumption in unit H5 A5 86 27 7 Display current consumption COM BS4 loop H5 A6 __ 87 27 8 Display statistics for COM loop H5 A7 88 27 9 Select unit on COM loop to use for triggering H5 A8 89 27 10 Change access code for PC communication H5 A9 _ 90 27 11 Change access code for programming H5 A10 91 28 Acknowledge FAULTS H6 92 29 Perform ZONE TEST test mode H7 93 30 Maintenance H8 95 30 1 Access code for maintenance 95 30 2 Disable or re enable outputs for routing equipment H8 S1 96 30 3 Disconnect COM l
43. e alarm and Heavy smoke alarm see below The control unit can handle up to 130 pre alarms and fire alarms No more alarms will be generated until one or more of the 130 alarms is are reset Pre alarm Pre alarm is a programmable option Win512 and will not be activated if not programmed A sensor generates pre alarm for a lower offset level than the offset level for fire alarm Pre alarm could be used when early alarm actions are required but no activation of alarm devices routing equipment etc e g computer soft power off In case of a pre alarm the following will happen e The buzzer in the control unit sounds 0 8 sec each 4 sec 0 8 4sec e Output s programmed for pre alarm is are activated e LEDs Fire L1 are blinking e On the first row in the control unit s display the presentation number is shown for the first pre alarm Example pre alarm zone 123 address 45 Pre alarm 123 45 e Ifmore than one pre alarm are generated the LEDs Alarms queued L2 are blinking and the pre alarms will be automatically scrolled each five seconds Pre alarm is automatically reset see chapter Alarm reset page 33 Pre alarm offset lt fire alarm offset and is programmable in WinS12 and is valid for the whole system Regarding the BS4 exp board 1584 for Autronica devices BS4 loops pre alarm can also be generated by detector s connected to address units And output s progra
44. e key cabinet has been opened a fault message is shown in the display as follows FAULT Key box control unit No Date MM DD Time HH MM This key cabinet fault message is to be acknowledged the same way as a normal fault see chapter Fault acknowledge page 47 When the key cabinet fault is acknowledged the LED Fault L8 will be turned OFF if the key cabinet is closed and if there are no other faults in the system Zone Detector not reset Normally used only in Swedish config convention LED Zone Detector not reset is lit indicating that one or more alarm points have been reset while still in alarm status i e it is non reset isolated and has to be re enabled via menu H2 B7 NOTE Zone Detector not reset Encapsulated 34 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 16 Fault In case of a fault condition the following has happened will happen in the control unit e The buzzer in the control unit sounds steady ON e Output s for routing equipment Fault tx is are activated e Output s for fault is are activated e LED Fault tx L19 is lit e LED Fault L8 is lit e LEDs Fault System L12 Sounder L13 and or Power supply L14 may be lit as well e A fault message incl date and time is shown in the display Example fault message FAULT No reply unit 001067 Date MM DD Time HH
45. eavy smoke alarm A sensor generates heavy smoke alarm for a higher offset level than the offset level for fire alarm Heavy smoke alarm could be used for automatic activation of smoke ventilation etc In case of a heavy smoke alarm the following will happen e Output s for heavy smoke alarm is are activated e Each heavy smoke alarm is printed Heavy smoke the same information as for the fire alarm generated by the same sensor and time Heavy smoke alarm is reset when the fire alarm is reset see chapter Alarm reset page 33 LED Acknowledge is indicating that the push button Acknowledge has been activated A busy system can cause a time delay up to 10 seconds before the fire alarm is acknowledged Heavy smoke alarm offset gt fire alarm offset and is programmable in Win512 and is valid for the whole system 32 Normal Fire alarm is always generated before a heavy smoke alarm can be generated for the same sensor 3 And output s programmed for this specific heavy smoke alarm When printer is available e g control unit 1549 31 Matsushita Electric Works Fire amp Security Technology AB MEW00442 14 Operating Instructions EBL512 V1 44 x Key cabinet 14 1 14 2 14 2 1 One of the programmable inputs 10 I3 in the control unit can be used to connect a key cabinet The fire brigade uses a key cabinet to store a key for the building locks Key cab
46. ected A TLON connection board 1590 is required in each control unit When the 1590 board is on place and the cables connected for each control unit do as follows 1 Take away the rectifier fuse F1 and a battery fuse F2 or F3 on the charger board 1557 2 Connect the batteries to the charger board 1557 3 Connect the rectifier to the mains 230 V AC 4 Replace the rectifier fuse F1 and the battery fuse F2 or F3 on the charger board 1557 5 LED Power on on the control panel indicate that the 24 V DC power supply rectifier and or battery is okay 6 An automatic reset restart will now take place see chapter Reset Restart page 55 When all control units are running power supplied the TLON network programming configuration has to be done before the site 38 The TLON connection board is to be mounted on the main board 1556 Cable connections are to be made on the connection board 1555 T B P1 48 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 17 2 1 specific data SSD can be downloaded see chapter Programming SSD download page 50 TLON network programming configuration A PC is connected to the modular connector J2 in the control unit main board 1556 The PC program TLON Manager is used see separate TLON network documentation 49 Matsushita Electric Works Fire amp Security Technology AB MEW0
47. ed Alarm device off is indicated by LED Disabled and is shown in menu H4 U1 Don t forget to re enable the outputs again i e Alarm device on via menu H2 B9 NOTE This function is not the same as for push button Silence See chapter Push button Silence page 22 This function has higher priority than Silence Access According to chapter Access see page 57 Scroll to menu H2 Scroll to menu B9 larm device on Alarm device o ACCE m device off 0 or Push 1 or 0 and push A to accept alarm device on 1 1 m device on Alarm device o Scroll or push Return to ACCE menu H2 Scroll or push Return to logout 69 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 25 Set calendar and clock H3 The RTC component has a built in battery Normally date day of the week and time don t have to be set except when the control unit is powered for the first time The clock may have to be corrected so that the time stamps for fire alarms faults etc will be correct In this menu is also the SW system program version shown NOTE If you only want to see the SW version push Return instead of A to return to menu H3 because then there will be no changes of the time Access see page 57 Scroll to menu H3 Set calendar and clock EPT H3 Date YY MM DD Time hh mm ss Here is the SW
48. ed objects reached Disconnection not performed ACCEPT Don t forget to re enable via menus H2 B4 B6 or use automatic re enablement for zones and alarm points Disablements are indicated by LED Disabled L10 Disablements and faults are indicated by a 2 sec beep when an open control unit door is being closed NOTE Don t re enable a zone and then disable the same zone immediately Re enabling takes about 2 seconds normally and up to 15 seconds All alarm points have to among other things be reset before they can be re enabled 60 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 1 Disable zone H2 B1 When a whole zone is disabled all alarm points within the zone are disabled excl addressable manual call points Disabled zones are listed in menu H4 U1 From this menu it s also possible to get a print out Access According to chapter Access see page 57 Scroll to menu H2 Disable or r Disable Write zone number e g Disable 3 Push A to accept 001 Automatic re enabling 0 0 No Push 1 for aut re enabling and accept or Time HH MM i change the time max 24 hours Push A to accept LED Disabled will light up lt is current time 3 hours If more disablements shall be done continue like above If not push Return to menu B1 Scroll or push Return to menu H2 Sc
49. edged faults and or acknowledged but not corrected faults the LED Fault will be lit and corresponding output s activated The list in menu H6 shows a maximum of 120 faults not acknowledged faults and or acknowledged but not corrected faults When a fault is acknowledged and corrected it will be removed from the list and a new fault can be shown Corrected faults are shown in the event log menu H4 U8 47 Matsushita Electric Works Fire amp Security Technology AB MEW00442 17 Operating Instructions EBL512 V1 44 x Commissioning an installation 17 1 17 2 Before you connect the power supply to a control unit all other cable connections should be made Check once more that they are correct Single Control Unit 1 Take away the rectifier fuse F1 and a battery fuse F2 or F3 on the charger board 1557 2 Connect the batteries to the charger board 1557 3 Connect the rectifier to the mains 230 V AC 4 Replace the rectifier fuse F1 and the battery fuse F2 or F3 on the charger board 1557 5 LED Power on on the control panel indicate that the 24 V DC power supply rectifier and or battery is okay 6 An automatic reset restart will now take place see chapter Reset Restart page 55 7 The site specific data SSD can now be downloaded see chapter Programming SSD download page 50 Control Units in a TLON network In a TLON network there are two or more control units conn
50. ellow The sounders alarm devices are silenced by the push button Silence L3 L5 can be individually programmed to indicate when it s normal trigger condition is met or when a programmable input is activated e g L5 will be turned on when an input is activated by a TX output Push buttons on the Fire Brigade Panel FBP Push button Operation function P1 Scroll red Used when LEDs Alarms queued are lit to scroll browse through the queued alarms P2 Silence yellow Used to silence the sounders i e to reset resp outputs LED Silence indicates silenced sounders P3 Reset red Resets the fire alarm displayed in the LCD When more than one fire alarm is generated LEDs Alarms queued are lit Each fire alarm has to be individually reset P4 Lamp test green To test all the LEDs on the FBP and the CP P5 Evacuate green Manual activation of sounders alt Paper feed gt Normally only used in Swedish configuration convention Has a special function in some configurations conventions 7 Not used in all configurations conventions If not used it s black and has no function Normally only used in Brittish Standard convention In B S Marine application convention it has the function Paper feed Otherwise it s black and has no function or the function Paper feed 14 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512
51. er ACCEPT board number 0 3 loop number and address Push CU 00 BS4 Board 0 Loop 0 j A l A to accept Address 00 or Select type of loop 0 Select type of loop Push A to accept or push 0 COM 1 BS4 Return to menu A8 Select unit on COM loop to use for Scroll or push Return to trigging ACCEPT A8 H5 Scroll or push Return to logout 89 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 10 Change access code for PC communication H5 A9 As a protection against unauthorised personnel programming the system an access code level 5 for PC connection Win512 is required For security reasons the default code should be changed NOTE This code require eight 8 digits Access According to chapter Access code for programming H5 see page 81 Scroll to menu A9 Change access code for PC communication ACCEPT A9 A Access code _ The digits are replaced New code x x x x Verify 2a Ae in the display Incorrect access code NO change The code was not correct Try again Change access code for PC communication The code was correct and ACCEPT A9 is now changed to the new code Scroll or push Return to H5 Scroll or push Return to logout 90 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 11 Change
52. er Reset Restart page 55 Follow the same procedure in each control unit 44 To change the Max loop units a separate download password is required This password is in conjunction with a Key eight digits and is available from the producer if you are authorized The Key is shown in Win512 and the procedure is described in the Win512 help S In old control units a separate CPU board 1526 could be found Regarding connections jumpers and LEDs see documentation valid for that HW 53 Matsushita Electric Works Fire amp Security Technology AB MEW00442 20 1 Rev Operating Instructions EBL512 V1 44 x Control Units in a TLON network All control units connected to a TLON network should have the same convention The number of addresses could vary and the language if required For download of new EBL512 settings in each control unit follow the procedure above 54 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 21 Reset Restart Reset restart will reset delete all activated fire alarms faults and disablements FFD When required make notes of the disablements before reset restart so that they can be disabled again after the reset restart Remaining fire alarms and faults will be activated again Reset restart can be performed as follows Action Data etc which Data etc which will be deleted not will be deleted Contr
53. es expansion board 1581 8 relays expansion board 1582 External FBP interface board 1583 German FBP interface board 1584 Autronica interface board four BS4 loops Regarding the expansion boards see the EBL512 Planning Instructions Printer In control unit 1548 it is possible to mount a 1558 Printer SW versions Due to continual development and improvement different SW versions could be found When installing a new control unit in a system with older control units you may have to update the SW in the old control units Max two 1582 boards per C U 3 Max one 1583 board per C U 1583 board is not possible to use in Swedish convention Max four 1584 boards per C U 10 Matsushita Electric Works Fire amp Security Technology AB MEW00442 3 3 3 4 3 5 Rev Operating Instructions EBL512 V1 44 x Documents The following documents are available e Planning instructions incl drawings e Operating instructions Normally information that is found in one document is not to be found in another document i e the documents complements each other Applications The EBL512 system is intended for small medium and large installations The intelligent control units offer the system designer and end user a technically sophisticated range of facilities and functions Programming PC SW Win512 and commissioning of the control unit system is very easy Start with one control unit and then
54. f more service signal the next sensor will be shown in the display acknowledgements shall be done continue like Sensor xxxxxx needs service above If not push Return to menu S4 Acknowledge S E Scroll or push Return to EPT S4 menu H8 Scroll or push Return to logout 99 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 6 Safe shut down of control unit H8 S5 It s not recommended to power off a control unit without doing a safe shut down This is because data can get lost Safe shut down also put the CPU at rest NOTE By reset restart and power off the Fault tx output s will be activated Before a Safe shut down see chapter Reset Restart page 55 Access According to chapter Access code for maintenance see page 95 Scroll to menu S5 Safe shut down of control unit ACCEPT S5 A Shut down control unit 00 0 1 Yes 0 No ACCE 2 Write the C U number Ready for shut down break the power Count down from 300 I yes and tate seconds starts y Automatic restart within 300 seconds A Disconnect the power supply mains and battery When the power supply is connected again or if powered all time after 300 seconds there will be an automatic reset restart FAULT Restart CU xx code xx After restart power on there will be a fault activated This fault has to
55. ic Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Also indicated by LED Fault Power supply The fault is to be found in the external power supply blown fuses etc Board x CU xx BS4 1584 Autronica interface board Check for blown fuse on the 1584 board The fuse is not replaceable The board has to be replaced FAULT Fuse COM loop x CU xx The fuse is not replaceable The main board 1556 has to be replaced FAULT Fuse DET8 board x CU xx DET8 1580 8 zones expansion board Check for blown fuse on the 1580 board FAULT fuse for board 1582 no x CU xx 1582 External FBP interface board Check for blown fuses on the 1582 board FAULT Fuse output unit t no XXXXXX Also indicated by LED Fault Power supply Fuse F9 on the output unit p c b is blown FAULT ID presentation unit XXXXXX The presentation display unit is not the same type as programmed Change the programming or the presentation unit FAULT input no 0 tech no xxxxxx Detector mounted in an ADB 2330 faulty removed detector or Ext line input to an ADB 2330 break on a wire or wrong no end of line resistor or Zone interface 2335 2226 break on a wire or wrong no end of line resistor 40 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x or Zone interface 2226 No ext
56. inet alarm If the key cabinet is opened before a fire alarm e g if somebody break into a key cabinet a fire alarm will be generated see chapter Alarm reset page 30 Example Key cabinet alarm xx control unit number larm No 001 KEY xx larm from keybox This alarm will also generate a fault message indicated by LED Fault L8 Fault tx output s will not be activated Key cabinet opened in conjunction with a fire alarm The fire brigade personnel can open the key cabinet in case of a fire alarm No alarm or fault will be generated when the key cabinet is opened i e no key cabinet alarm Restoring the key after a fire alarm When all fire alarms in the system are reset see chapter Alarm reset page 33 the key has to be restored in the key cabinet within 5 minutes If not a fault will be generated 35 Inputs I0 I3 have a 1 5 seconds delay of activation 32 Matsushita Electric Works Fire amp Security Technology AB MEW00442 15 Operating Instructions EBL512 V1 44 x Alarm reset 15 1 15 2 15 3 Pre alarm reset Pre alarm is automatically reset i e when the sensor value offset for pre alarm is below the pre alarm level Fire alarm reset e The fire alarm shown in the FBP display s on the first row to the left will be reset when the push button Reset P3 is pushed NOTE The push button has to be in reset position for a minimum of 0 5 sec e Output s
57. ire alarm has to be individually reset see chapter Alarm reset page 33 Via Win512 it is possible to change the fire alarm offset level A special access code is required 7 And output s programmed for this specific fire alarm 8 Only the ten latest fire alarms will be displayed in the ext FBPs When printer is available e g control unit 1549 30 Matsushita Electric Works Fire amp Security Technology AB MEW00442 13 2 1 13 2 2 13 3 Rev Operating Instructions EBL512 V1 44 x NOTE Up to 120 fire alarms can be stored In case of more alarms they will not be registered until one or more of the 120 alarms are reset Alert annunciation Indications print outs actions etc as for a normal fire alarm except output s for routing equipment fire brigade tx which will not be activated The fire alarm has to be acknowledged and reset within an acknowledge time and an investigation time respectively otherwise the output s for routing equipment fire brigade tx will be activated See EBL512 Planning instructions for more information Acknowledgement and reset of the fire alarm is normally done on a 2235 display unit or an alert annunciation controller 2232 2 zone address dependence LEDs Fire L1 are blinking but there is no fire alarm shown in the FBP display s To see which zone alarm point is in alarm status see chapter Activated 2 zone address dependent H4 U4 page 74 H
58. lding occupier Service personnel Service commissioning engineer Service Installation handling monthly tests etc Service maintenance Service commissioning the system etc Code to connect a PC i e for Win512 Access level 5 Access code for level 5 is commissioning required engineer The access codes can be changed To change a code you have to know the valid code or use a code for a higher access level 6 1 Access level 1 After the door has been opened LED Key switch is lit the user fire brigade personnel will be able to use the push buttons keypad to Scroll browse through the queued alarms Silence the sounders alarm devices Reset fire alarm s Perform lamp LED test Start the sounders Get access after login to certain menus functions in the system 12 Not in all configurations conventions 3 Normally only used in English configuration convention Normally the fire brigade personnel have no access code 17 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 6 2 Access level 2 From access level 1 the user can login to access level 2 which gives access to the following menus U2 Disablement by time channel U4 Activated 2 zone address dependent zone address 5 Show sensors week average values U U 6 Show sensors momentary values S Normally only in Swedish c
59. mm ACCEPT hh hour mm minute Show information about Scroll or push Return to H5 Scroll or push Return to logout site specific data EPT A4 7 Logical Name as written in Win512 dialog box System tab System Data 85 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 6 Display current consumption in unit H5 A5 System shows the total current consumption including the charging current on the 24V side for the whole control unit Charging shows the charging current NOTE System current gt 3 8 A is presented as gt 3800 mA Charging current lt 100 mA can not be correctly presented n e Scroll to menu A5 Display current consumption in unit ACCEPT A5 From which control unit shall current consumption be displayed 00 ACCEPT Current consumption control unit 00 System xxxx mA Charging xxxx mA Display current consumption in unit ACCEPT A5 86 According to chapter Access code for programming H5 see page 81 Write control unit number Push A to accept Scroll or push Return to H5 Scroll or push Return to logout Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 7 Display current consumption COM BS4 loop H5 A6 The current consumption an average value for each COM loop and BS4 loop can be
60. mmed for this specific pre alarm 29 Matsushita Electric Works Fire amp Security Technology AB MEW00442 13 2 Operating Instructions EBL512 V1 44 x Fire alarm A sensor generates fire alarm for an offset level that can normally not be changed In case of a fire alarm the following will happen e The buzzer in the control unit sounds 0 8 sec each 0 8 sec 0 8 0 8sec e Output s for routing equipment Fire brigade tx is are activated e Output s for sounders type 3 alarm devices is are activated e Output s for fire alarm is are activated e LEDs Fire L1 are blinking e On the first row in the FBP display s the presentation number is shown for the first fire alarm On the second row is a user definable text message shown if programmed Example fire alarm zone 123 address 45 Alarm No 001 123 45 User definable text messag e Ifmore than one fire alarm are generated the LEDs Alarms queued L2 are blinking To scroll through the alarms use push button Scroll P1 Example more than one fire alarm Alarm No 001 123 45 Last No 011 555 User definable text message for 123 45 e The alarms are stored in a circular buffer and when scrolling from the last to the first alarm the LEDs Alarms queued will be turned off for three seconds e Each fire alarm is printed zone address user definable text message if programmed and time Each f
61. n to logout 71 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 2 Disablement by time channel H4 U2 A list of all disablements by time channel s in the system From this menu it s also possible to get a print out Access According to chapter Access see page 57 Scroll to menu H4 Present system status on display and printer ACCEPT H4 Disablement Printout l yes Scroll to menu U2 Disablement by time channel Push 1 for an automatic rint out of all Printout l yes Pr disablements in the system Push A for presentation in the display When A is pushed the disablements will be shown in the This is a list in which you display e g can scroll If there are no isabl ts if Return Zone XXX address XX disabled disablement ee i h fter the last by eime channet is pushed and after the las print out menu U2 will be shown again Disablement by time channel Scroll or push Return to menu H4 Scroll or push Printout l yes Return to logout 72 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 3 Show open doors H4 U3 The LED Key switch L16 is lit to indicate that one or more doors are open See chapter Door open Key switch page 25 Menu H4 U3 is a list of all open doors and from this menu it s also possible to get a pri
62. ng equipment is are disabled via time channel or menu H2 B3 or B8 5 L In Brittish Standard Marine application convention Door open 10 It is programmable if also the ext FBP open door s should be indicated and if it should indicate for each control unit individually or the whole system Tt is programmable if open door should disable the output s 15 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Keypad push buttons on the Control Panel CP Key push button Operation function eos af Numeric keys for the figures 0 9 gt Left right keys to move the cursor in a menu Up down keys to scroll between the menus ce Clear deletes just written data Be a Kooi imena Pae E E E a i O Ps Acces To peaos 0 tne menu ee Gria aoee oda P9 Retun To leave a menu one step up and to stop input of data 16 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 6 Access levels The control unit has five access levels which are adapted to different kind of users Access level 1 Open door Fire brigade personnel Fire alarm handling key is needed Access level 2 Access code for level 2 or 3 or 4 is required Access level 3 Access code for level 3 or 4 is required Access level 4 Access code for level 4 is required Bui
63. ng the key after a fire alarm 32 15 Alarm reset 33 15 1 Pre alarm reset 33 15 2 Fire alarm reset 33 15 3 Heavy smoke alarm reset 33 15 4 Key cabinet alarm reset 34 15 5 Zone Detector not reset 34 16 Fault 35 16 1 Fault messages 35 16 2 Fault acknowledge 47 17 Commissioning an installation 48 17 1 Single Control Unit 48 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 17 2 Control Units in a TLON network 48 17 2 1 TLON network programming configuration 49 18 Programming SSD download 50 18 1 Single Control Unit 50 18 2 Control Units in a TLON network 50 18 3 User definable text messages download 51 18 3 1 Download in Control unit 51 18 3 2 Download in Display unit 51 19 New system program SW version download 52 19 1 Control Units in a TLON network 52 20 EBLS12 settings download 53 20 1 Control Units ina TLON network 54 21 Reset Restart 55 22 Access 57 23 Perform monthly test H1 58 24 Disable or re enable H2 60 24 1 Disable zone H2 B1 6l 24 2 Disable zone address H2 B2 62 24 3 Disable control output H2 B3 63 24 4 Re enable zone H2 B4 64 24 5 Re enable zone address H2 B5 65 24 6 Re enable control output H2 B6 66 24 7 Re enable non reset zone address H2 B7 67 24 8 Control on Control off H2 B8 68 24 9 Alarm device on Alarm device off H2 B9 69 25 Set calen
64. nt out Access According to chapter Access see page 57 Scroll to menu H4 Present system status on display and printer ACCEPT H4 Disablement Printout Scroll to menu U3 Show open doors Push 1 for an automatic rint out of all open Printout p P doors Push A for presentation in the display When A is pushed open doors will be shown in the This is a list in which you display e g can scroll If there are no Desk open Gus Open doors if Return is pushed and after the last print out menu U3 will be shown again Show open doors Scroll or push Return to menu H4 Scroll or push Printout l yes Return to logout 73 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 4 Activated 2 zone address dependent H4 U4 2 zone dependency Win512 dialog box System When only one zone is in alarm status the LEDs Fire L1 are flashing but there is no fire alarm presentation in the FBP display s or display units 2 unit dependent Win512 COM loop unit dialog box When only one zone address alarm point unit is in alarm status the LEDs Fire are flashing but there is no fire alarm presentation in the FBP display s In menu H4 U4 this 2 zone or 2 unit dependent zone address in alarm status is shown From this menu it s also possible to get a print out Access According to chapter A
65. ol unit power OFF and SSw SSD SSI then power ON again FFD SW RESET jumper JP4 on the FFD SSD SSI main board 1556 SW SSW Reset command from Win512 FFD SSD SSI or TLON Manager SW SSW FFD SSD SSI SW SSW Automatically after download FFD SSD SSI of site specific data SSD via a SW SSW Automatically due to external disturbance PC amp Win512 Safe shut down Safe shut down of control unit menu H8 S5 will save the SSW data in a Flash ROM which saves the data although the control unit has no power supply Before the first Safe shut down this memory is empty After each Safe shut down the latest SSW data is saved The control unit RAM working memory will then read the saved data when the power supply returns FFD Fire alarms faults and disablements SSW Sensor week average values access codes monitored output calibration values log buffers and in some conventions the alarm counter SSD Site specific data i e all the installation programming downloaded from Win512 SSI EBL512 settings downloaded from Win512 SW Software i e the control unit system program 4 Reset restart affects the control unit where it is performed and that control unit s data in a system two or more control units in a TLON network 47 See Safe shut down below 48 See Safe shut down below 4 If this happens often call for service personnel engineer 55 Matsushita Electric Works Fire amp
66. oll to menu H2 Disable or r oo 4 If there are no zones to re enable menu B4 will be shown again If it s the correct zone to re enable push A to accept If not scroll or write the wanted zone and push A to accept If more re enablements Soa Bi shall be done continue like above If not scroll or push Return to menu H2 Scroll or push Return to logout 64 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 5 Re enable zone address H2 B5 Disabled alarm points zone addresses are listed in menu H4 U1 From this menu it s also possible to get a print out Re enabling via this menu has higher priority than automatic re enabling When all alarm points have been re enabled The LED Disabled will be turned OFF if there are no other disablements in the system Access According to chapter Access see page 57 Scroll to menu H2 Disable or r Oo a nable zone address nable zone 000 Address If there are no zone addresses to re enable menu B4 will be shown again If it s the correct zone address to re enable push A to accept If not scroll or write the wanted zone address and push A to accept nable zone address If more re enablements shall be done continue like EPT B5 above If not scroll or push Return to men
67. onds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM Push A to stop the test mode WAN Monthly test is completed The LED Test mode is ACCEPT turned OFF Perform monthly test Scroll or push Return to logout EPT H1 Some regulations say that the fire alarm routing equipment Fire alarm tx also should be tested If the equipment don t have this test possibility it can only be done by generating a real fire alarm NOTE If the control unit door is left open the output s for routing equipment fire brigade tx may be disabled if programmed so in Win512 A sensor in test mode will not be able to activate fault 59 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 Disable or re enable H2 A whole zone one or more alarm points within a zone and or control outputs can be disabled via menus H2 B1 B3 This possibility can be used when a temporary disablement is wanted e g when the premises are being restored etc Pre alarms and fire alarms from the disabled alarm points will be disabled Faults will not be disabled Addressable manual call points can not be disabled Up to 100 alarm points zones and or outputs can be disabled It is not possible to exceed the limit A warning message will be shown Max disconnect
68. onfiguration convention When a TLON network is used one or more doors in the system could be open It is programmable if also ext FBP open door s should be indicated and if it should indicate for each control unit individually or the whole system See also chapter Door open Key switch page 25 18 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 6 3 Access level 3 From access level 2 the user can login to access level 3 which gives access to the following menus normally used by service personnel Same menus as in access level 2 plus the following brigade tx amp Fault tx S4 Acknowledge service signal 17 Tf code for access level 3 or 4 has been used to login to access level 2 new login to access level 3 is not required 19 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 6 4 Access level 4 From access level 2 the user can login to access level 4 which gives access to the following menus normally used by a Service Commissioning Engineer A4 Show information about site specific data 6 5 Access level 5 Used by Service Commissioning Engineer when a PC is to be connected to the control unit i e when Win512 is to be used for backup downloading site specific data downloading SW settings configurations C U and system data on line statu
69. oop H8 S2 97 30 4 Re connect Loop H8 S3 98 30 5 Acknowledge SERVICE signal H8 S4 99 30 6 Safe shut down of control unit H8 S5 100 30 7 Activate address in alarm mode H8 S6 101 30 8 Synchronize the control units H8 S7 102 30 9 Change access code for maintenance H8 S8 103 31 Change access code for daily duties H9 104 32 Annual control 105 33 Changing paper in the printer 106 34 Battery maintenance 107 35 How to avoid unnecessary nuisance fire alarms 108 36 Information regarding radioactive radiation source110 37 Revision history 111 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 1 Introduction EBL512 Operating Instructions is a document intended to be used by the end user and the fire brigade personnel as well as service commissioning engineer Due to continual development and improvement different SW versions are to be found This document is valid for SW version 1 44 x Since the EBL512 control unit c i e is produced for many countries the look the texts the functions etc may vary Products Consists of one or more parts HW according to a Product Parts List A product has e atype number e g 1548 e an article number often the type no and sometimes is a country code added e g 1548SE e a product name e g EBL512 control unit 128 addresses without printer HW A HW e g a printed circuit board has e atype n
70. out ACCEPT Al 82 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 3 Sensitive fault detection mode H5 A2 To increase the possibilities to detect faults during the commissioning it is possible to use the Sensitive fault detection mode The time delay for each fault will be reduced NOTE Don t forget to turn off this mode after the commissioning Access According to chapter Access code for programming H5 see page 81 Scroll to menu A2 Sensitive fault detection mode ACCEPT A2 Sensitive fault detection mode 0 Push A or 1 and A to accept ON is indicated by LED Fault This mode is ON until turned OFF in this menu A2 off Sensitive fault detection mode Scroll or push Return to H5 Scroll or push Return to logout or ACCEPT A2 1 a AN 83 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 4 Direction for communication on COM loop H5 A3 To make trouble shooting easier e g during the commissioning it is possible to lock the communication on a COM or BS4 loop in one direction The communication direction is automatically changed two times per 24 hours to ensure that the wires are okay NOTE The locking only works as long as you see the text in the menu A3 i e when you log out or if you are automatically logged
71. out the communication direction will be reset to the normal direction for that time Access According to chapter Access code for programming H5 see page 81 Scroll to menu A3 Direction for communication on COM BS4 loop ACCEPT A3 Select type of loop 0 0 COM 1 BS4 Push A or 1 and A to accept ON is indicated by LED Fault This mode is ON until turned OFF in this menu A2 ACCEPT Write loop number board number and control unit number Push A to accept or Lock direction on BS4 loop 0 Board 0 CU 00 1 we MAS COM loop is currently communicati May be B direction A direction ACCE instead Push A to change direction Push Return When you have selected a BS4 loop the to finish back to menu text in this menu will still be COM loop A3 Direction for communication on Scroll or push Return to H5 Scroll or push COM BS4 loop ACCEPT A3 Return to logout 84 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 5 Show information about site specific data H5 A4 The site specific data SSD is downloaded via a PC and Win512 Access According to chapter Access code for programming H5 see page 81 Scroll to menu A4 Show information about site specific data EPT A4 57 Name XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX YY year MM month DD day Downloaded YY MM DD hh
72. pe of detector can solve certain problems Bear also in mind that the coverage area can be different for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via Win512 which can be used e Alarm delay for smoke detectors sensors can be used e Two zone or two unit dependent fire alarm activation can be used e Inan installation with addressable detectors sensors e g EBLS512 the affected detectors can be individually disabled or whole zones when the work is in progress Bear in mind that the smoke spreads and consideration must be taken to adjacent detectors zones Disablements can be done automatically via a time channel built in or external or via menu H2 B1 B3 e If there is a personnel alarm organisation on site alert annunciation can be used e Pre alarm from smoke sensors can be used 109 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 36 Information regarding radioactive radiation source The installation might contain smoke sensors detectors of the ionization type They contain a small radioactive radiation source Americium 241 When the sensor detector gets dirty and when service signal has been activated in the system contact your local dealer for cleaning replacement of the sensors detectors Metal objects must absolutely not be st
73. pollings Access According to chapter Access code for programming H5 see page 81 Scroll to menu A7 Display statistics for COM loop ACCE For which CU 00 and COM loop 0 s Write control unit and loop statistics be displayed ACC number Push A to Pollings 1234567 Parity 000000 00 0 Bit 000000 00 0 Answer 000000 00 0 Display statistics for COM loop Scroll or push Return to ACCEPT A7 H5 Scroll or push Return to logout 88 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 27 9 Select unit on COM loop to use for triggering H5 A8 This function is used by service engineer and by R amp D for troubleshooting On the pin respectively you will get a pulse to trig an oscilloscope etc COM loop Main board 1556 JP2 upper pin Each unit not giving a correct answer Main board 1556 JP2 lower pin When a specific unit is being polled BS4 loop Autronica interface board 1584 BY3 left pin When a specific unit is being polled Autronica interface board 1584 BY3 right pin 0 V BS4 board Autronica interface board 1584 Access According to chapter Access code for programming H5 see page 81 Scroll to menu A8 amp Select unit on COM loop to use for trigging ACCEPT A8 A Select type of loop 0 Select type of loop Push A t t 0 COM 1 BS4 i cae Loop 0 Address 000 Write control unit numb
74. power supply FAULT Key box control unit xx The key cabinet has been opened without a prior fire alarm i e a break into the cabinet or The key cabinet has not been closed within 5 minutes after reset of all fire alarms in the system FAULT L C mixed loop x CU xx The two wires L resp C have been mixed alternated Check so that the wire connections are correct according to drawing 512 41 FAULT LON board 1590 control unit xx 1590 TLON connection board No communication connection with the TLON network FAULT Low batt cap control unit xx Also indicated by LED Fault Power supply Battery voltage lt 21 9 V load resistor connected The battery is presumably too old FAULT Low main PWS control unit xx Also indicated by LED Fault Power supply Mains voltage below 187 V AC e Blown fuse 230 V AC or no voltage Rectifier voltage below 21 V DC e Fuse F1 on the charger board 1557 is blown FAULT monitored output x CU xx If the output is programmed for sounders alarm devices it is also indicated by LED Fault Sounder x 0 SO Short circuit break on the connected cable equipment and or blown fuse F5 or F6 on the connection board x 1 S1 Short circuit break on the connected cable equipment and or blown fuse F7 or F8 on the connection board 41 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x x 2 S2
75. programmed for this fire alarm is are reset If more than one fire alarm is activated i e LEDs Alarms queued L2 are lit the next fire alarm in the queue is now shown in the display on the first row to the left It has to be reset the same way as the first one NOTE If the sounders have been silenced LED Silence L7 is lit Push Silence P2 to return to normal state LED Silence will be turned OFF When all fire alarms are reset LEDs Alarms queued are turned OFF and the display is empty All outputs for fire alarm have been reset The key has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the FBP display s as follows FAULT Key box control unit No Date MM DD Time HH MM Indications and activations are the same as for any other fault see chapter Fault page 35 Heavy smoke alarm reset If a heavy smoke alarm has been activated it will be reset at the same time as the corresponding fire alarm is reset and resp output s will be reset If there is a fault condition e g caused by the fire a fault message will now be shown in the display 33 Matsushita Electric Works Fire amp Security Technology AB MEW00442 15 4 15 5 Rev Operating Instructions EBL512 V1 44 x Key cabinet alarm reset Key cabinet alarm is reset the same way as a fire alarm see above To inform the user that th
76. ption gt 167mA on the BS4 loop short circuit isolator is not connected on the loop Check the loop NOTE As long as there is a short circuit the BS4 loop is disabled Each 10 minutes an attempt is made to re enable the loop again User programmable text External fault Programmable input is used for an external fault see fault message 46 Matsushita Electric Works Fire amp Security Technology AB MEW00442 16 2 Operating Instructions EBL512 V1 44 x Fault acknowledge The LEDs Fault tx and Fault are lit A fault message date and time are shown in the FBP display s After the time may be shown More faults more than one fault is generated in the system If Fault latching is selected in Win512 after the time may be shown Serviced the fault is already corrected e Login according to chapter Access page 57 e Use menu H6 access level 2 for fault acknowledge see chapter Acknowledge FAULTS H6 page 92 e All faults have to be individually acknowledged Use or 4 keys to scroll e Ifa fault has been corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged e When a fault is corrected and acknowledged it will disappear from the list H6 e When all faults have been acknowledged the LED Fault tx will be turned off and output s for routing equipment Fault tx is are reset e As long as there are faults not acknowl
77. push button Silence is pushed during a fire alarm the following will happen e LEDs Fire and Alarms queued L2 changes from blinking to steady ON e the buzzer in the control unit will be turned OFF e activated outputs programmed for sounders type 3 alarm devices will be turned OFF In case of a new fire alarm or if the push button Silence is pushed again the buzzer and the sounders i e the outputs will automatically be turned ON and LEDs Fire and Alarms queued starts blinking If the push button Silence is pushed during a fault condition the following will happen e the buzzer in the control unit will be turned OFF It will be turned OFF until the push button Silence is pushed again or a fire alarm is activated 19 In some configurations conventions e g Swedish RUS Brittish Standard and B S Marine application is this function not valid 2 When more than one fire alarm is activated 22 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 9 Alarm device on Alarm device off Via menu H2 B9 all outputs programmed for sounders type 3 alarm devices can be turned OFF disabled In case of a fire the sounders will remain turned OFF not sound They will be turned OFF disabled until they are turned ON re enabled again via menu H2 B9 Alarm device OFF is indicated by LED Disabled L10 23 Ma
78. roll or push Return to logout 61 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 2 Disable zone address H2 B2 Every addressable alarm point connected to the COM loop can be individually disabled Disabled alarm points zone addresses are listed in menu H4 U1 From this menu it s also possible to get a print out Access According to chapter Access see page 57 Scroll to menu H2 le or Scroll to menu B2 Disable zone address 000 Address Write zone number and L 001 Address Push A to accept address e g 001 01 Automatic re enabling 0 0 No 1 Yes Push 1 for aut re Pies HASNN ere enabling and accept or change the time max 24 hours Push A to accept LED Disabled will light up lt is current time 3 hours le zone 000 Address 00 If more disablements mee shall be done continue like above If not push Return to menu B2 Scroll or push Return to menu H2 Scroll or push Return to logout 62 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 3 Disable control output H2 B3 Every control output can be individually disabled Disabled outputs are listed in menu H4 U1 From this menu it s also possible to get a print out Access According to chapter Access see page 57
79. s checking etc 18 Tf code for access level 4 has been used to login to access level 2 new login to access level 4 is not required 20 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x T Normal operation When the control unit system is in normal operation i e no fire alarm no fault no disablement no service signal not in test mode and no open doors etc only the LED Power on L11 is to be lit 21 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Operating Instructions EBL512 V1 44 x 8 Push button Silence 8 1 8 2 In the control unit on the FBP there is a push button P2 Silence and an LED L7 Silence In some configurations conventions this button could have special function s Silence before a fire alarm If the push button Silence is pushed before a fire alarm fault the following will happen e LEDs Silence and Disabled L10 will light up steady ON e the buzzer in the control unit will be disabled e outputs programmed for sounders type 3 alarm devices will be disabled If case of a fire alarm the buzzer and the sounders will remain turned OFF not sound In case of a fault the buzzer will remain turned OFF not sound To reset this function push Silence once more The LEDs will be turned OFF indicating a normal state Silence during a fire alarm If the
80. s done via Win512 i e normally no fault message there is no syncronization ready indication The syncronization time is depending on the amount of data faults disablements etc stored If a new syncronization is started before a syncronization is ready the syncronization will start from the beginning again 102 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 30 9 Change access code for maintenance H8 S8 For security reasons the default code should be changed Access According to chapter Access code for maintenance see page 95 Scroll to menu S8 Change access code for maintenance ACCEPT S8 Access code _ New code Verify Enter the old code the Access code New code The digits are replaced new code and the new in the display 5 Verify code again 2 Incorrect access code NO change The code was not correct Try again Change access code for maintenance The code was correct and is now changed to the new ACCEPT S8 code Scroll or push Return to menu H8 Scroll or push Return to logout 103 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 31 Change access code for daily duties H9 For security reasons the default code should be changed Access According to chapter Access see page 57 Scroll to menu H9
81. shown in the display e g ALARM zone 123 address 45 MM DD HH MM XX How many events shall be printed 000 ACC How many events shall be printed 010 ACC Show event log Printout l yes 5t See EBL512 Planning Instructions and Win512 78 According to chapter Access see page 57 Push A for display presentation or Push 1 for print out This is a list in which you can scroll Push Return to menu U8 XX in the example control unit number XX 99 Win5 12 Push A to start print out After the last print out menu U8 will be shown again Scroll or push Return to menu H4 Scroll or push Return to logout Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 9 Show configuration H4 U9 In menu H4 U9 the EBL512 settings made in Win512 are shown Number of addresses that can be used 128 256 or 512 Convention i e different functions in different countries etc Language for the texts presented in the display on the print outs It is not possible to get a print out Access According to chapter Access see page 57 Scroll to menu H4 Present system status on display and Disablement Printout l yes Scroll to menu U9 Show configuration Push A to accept A Max number of allowed loop units xxx Push Return to menu Language nnnnnnnnnn Conv ccccccccce U9 Return Show
82. sition access SSD Site Specific Data This data is unique for each installation All alarm points presentation numbers user definable text messages programmable outputs etc are programmed configured in the PC program Win512 and has to be downloaded in EBLS12 SW Software System program The SW makes the control unit the microprocessor work It is factory downloaded but a new version can be downloaded in EBL512 on site Matsushita Electric Works Fire amp Security Technology AB MEW00442 3 Operating Instructions EBL512 V1 44 x Overview 3 1 3 2 The EBL512 system EBL512 is a microprocessor controlled intelligent fire alarm system intended for analog addressable smoke detectors as well as conventional detectors and manual call points Programmable control outputs and output units are available Up to 512 addresses can be connected to each control unit c 1 e Regarding alarm points outputs display units etc see chapter Definitions Explanations page 6 EBLS512 is available in several types versions and configurations It can be connected to a TLON network a system with up to 30 independent control units Each control unit has total access to all information EBL512 is designed according to the European standards EN 54 part 2 and 4 Expansion boards In the control unit c i e it is possible to mount up to six expansion boards The following types are available 1580 8 zon
83. t unit XXXXXX Also indicated by LED Fault Power supply Check the output unit battery connections fuse F3 on the power supply board in the output unit Board x CU xx 1584 Autronica interface board Fault on the 1584 board FAULT Charging control unit xx Also indicated by LED Fault Power supply e Loss of mains i e no 230 V AC the fault is activated after five hours the time could vary depending on convention e Blown fuse 230 V AC FAULT Charging output unit xxxxxx Also indicated by LED Fault Power supply Loss of mains i e no 230 V AC the fault is activated after five hours the time could vary depending on convention Check 230 V AC fuses and fuses F1 F5 on the output unit rectifier p c b FAULT Configuration on control unit xx Fault in the SSI EBL512 settings downloaded from Win512 FAULT CU xx did not get an ACK The communication between control units isn t correct Make sure that all control units are programmed Win512 and programmed in the 37 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x TLON network TLON Manager NOTE Programmed control units have to be connected running FAULT CU xx has wrong information Control units have data stored which is not the same in all control units The control units have to be synchronised via menu H8 S7 NOTE Programmed control units have
84. ting Instructions EBL512 V1 44 x New system program SW version download 19 1 SW download is normally factory made before delivery Latest SW version is then downloaded Due to continual development and improvement different SW versions could be found If you wish to download a new software system program version a PC and Win512 is used Before download the PC has to be connected to the D connector J1 in the control unit main board 1556 in question 1 Start Win512 2 Set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart by setting jumper JP4 RESET momentarily in position approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 Start the downloading The buzzer will now be silenced 6 When the download is ready in the Win512 log view it will be shown Download ready 7 Reset jumper JP1 BOOT position OFF and do a reset restart see paragraph 2 above Regarding the reset restart see chapter Reset Restart page 55 Follow the same procedure in each control unit Control Units in a TLON network All control units connected to a TLON network should have the same SW version For download of new SW in each control unit follow the procedure above 8 In old control units a separate CPU board 1526 could be found Regarding connections jumpers and LEDs see
85. to be connected running FAULT CU xx too high current consumption The control unit current consumption is over 2 5A and because of this the battery charging is turned off Normally this fault only appears when starting up expanding a system FAULT Cut off COM loop x CU xx This is indicating a single break on the loop Communication has to be performed in both directions to find all units May also be shown after a short circuit on the loop when short circuit isolators are used communication in both directions A double break will give the message FAULT No reply NOTE Communication in both directions lasts for about ten minutes when a new attempt to communicate in one direction is performed If the break remains a new ten minutes period starts and so on If the fault is acknowledged and the break is corrected during a ten minutes period it will not disappear from the list until the end of the ten minutes period loop x CU xx CU lt gt ASFO loop x CU xx ASF 0 lt gt ASF 1 xx ASF 1 lt gt ASF 2 loop x loop xx ASF 2 lt gt ASF 3 FAULT f loop xx ASF 3 lt gt CU FAULT f loop xx ASF 2 lt gt CU FAULT Cu loop U xx ASF 1 lt gt CU G C C G C C FAULT Cu loop x U xx ASF 0 lt gt CU This is indicating a single break on the COM loop x when one two three or four short circuit isol
86. tor Conventional detector with a closing contact short circuit no alarm resistor or detector with two breaking contacts External line Conventional zone line Input to an ADB an addressable zone interface or expansion board intended for one or more conventional alarm points End of line resistor in the last alarm point ADB input Addressable zone interface Unit with an input ext line conventional zone line intended for one or more conventional alarm points End of line resistor in the last alarm point Output unit Addressable unit with programmable control outputs To be connected to a COM loop see below Output Control output Defined or programmable function Relay or supervised monitored voltage output in the C U or an output unit Short circuit isolator Addressable unit for automatic disconnection of a part of a COM loop see below in case of a short circuit on the loop Display unit Addressable unit for fire alarm presentation incl user definable text messages if programmed Connected to a COM loop see below COM loop Loop a cable with two wires to which all the addressable MFSTech units can be connected It starts in the C U and it returns back to the C U BS4 loop Loop a cable with two wires to which all the addressable Autronica BS100 units can be connected It starts in the C U EBL512 and it returns back to the C U Matsushita Electric Works Fire amp Security
87. tric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x FAULT Restart CU nn code xx yyyyyyyyyy Control unit restart reset has occurred nn Control unit number 00 29 xx 00 Power On Reset Power supply connected xx 01 Watchdog Reset xx 02 Accidental jump to reset vector xx 03 External reset caused by external watchdog user e g after SSD download or RESET jumper JP4 on the main board 1556 has been used xx 4 16 Unexpected interrupt If xx 01 02 or 04 16 appear often call for service personnel engineer yy y memory address before restart FAULT ROM memory control unit xx A fault in control unit xx SW This is very serious Call for service personnel engineer immediately FAULT RS232 comm in gateway CU xx Gateway GW512 is are installed in the system No not correct communication on the RS232 line between GW512 and the EBL1000 2000 Main Control Unit number xx sub control unit number for the GW512 FAULT Sensor techn no XXXXXX e The sensor is removed from its sensor base e Faulty sensor FA Sh circ loop CU xx CU lt gt ASFO FA Sh circ loop CU xx ASFO lt gt ASF1 FAULT Sh circ loop CU xx ASF1 lt gt ASF2 FAULT Sh circ loop CU xx ASF2 lt gt ASF3 FAULT Sh circ loop x CU xx ASF3 lt gt CU FA Sh circ loop x CU xx ASF2 lt gt CU FAULT Sh circ loop x CU xx ASF1 lt gt CU FAULT Sh circ loop x CU
88. tsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 10 Controls ON Controls OFF Via menu H2 B8 all control output types 0 control general 1 fire ventilation 2 extinguishing system can be collective turned OFF disabled They will be turned OFF disabled until they are turned ON re enabled again via menu H2 B8 Controls OFF is indicated by LED Disabled L10 Also the Extinguish equipment output on the German FBP interface board 1583 24 Matsushita Electric Works Fire amp Security Technology AB MEW00442 11 Operating Instructions EBL512 V1 44 x Door open Key switch 11 1 11 2 A key is used to open the control unit door to get access to the system see chapter Access levels page 17 Door open is indicated by LED Key switch L16 see below Door open can disable output s for fire alarm and fault routing equipment respectively LEDs Fire brigade tx Disabled and Fault tx Disabled indicate this respectively See below LED Key switch In Win512 the following can be programmed Door in any control unit in the system LED Key switch is indicating door open in one or more control units in the system or Door in control unit LED Key switch is indicating door open in the same control unit as the LED is situated Indication open door external FBP In both cases above could be chosen if an
89. tx will be turned off Corresponding outputs will be reset When all faults are acknowledged and corrected serviced LED Fault will be turned off Corresponding outputs will be reset Also see chapter Fault page 35 Access see page 57 Scroll to menu H6 Acknowledge FAULTS EPT H6 FAULT XXXXXXXX This is a list in which Date MM DD Time HH MM See comments you can scroll If the fault is corrected the text Serviced is shown To acknow ledge the fault shown in the display push Fault acknowledged Fault acknowledged FAULT XXXXXXXX The fault is now acknow Date MM DD Time HH MM Acknowledged ledged If when it is corrected it s no more shown in this list Scroll to find more faults to be acknowledged or push Return to menu H6 Return Acknowledge FAULTS Scroll or push Return EPT H6 to logout 92 Matsushita Electric Works Fire amp Security Technology AB MEW00442 29 Rev Operating Instructions EBL512 V1 44 x Perform ZONE TEST test mode H7 Normally zones are tested during the monthly test menu H1 Via this menu it s possible to perform the zone test only In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test If a real fire alarm is generated by an alarm point not in test mode the normal fire alarm functions will be activated i e outputs sounders routing equipment fire brigade tx etc will be acti
90. u H2 Scroll or push Return to logout 65 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 24 6 Re enable control output H2 B6 Disabled outputs are listed in menu H4 U1 From this menu it s also possible to get a print out When all control outputs have been re enabled The LED Disabled will be turned OFF if there are no other disablements in the system Access According to chapter Access see page 57 Scroll to menu H2 Disable or r Disable zone Scroll to menu B6 Re enable control output Re enable control outpu 0 RU4 2265 or SU4 2262 2263 1 S0 S3 2 R0 R1 or 3 Relay board 1581 4 1583 board output Extinguishing system O RU SU 1 S 2 R 3 RE 4 E 4 ES not shown in Swedish RUS convention Push A to accept A Re enable 00 0000 output 0 If there are no outputs to Depending on the ACCEPT L re enable menu B6 will be chosen type 0 1 2 3 TEE i it 00 S0 shown again resp 4 the following ee will be shown re enable push A to If it s the correct output to t 00 RO accept If not scroll or ACCEPT L write the wanted output nable co it 00 relay board 0 and push A to accept output 0 ACCEP Re enable output for extinguishi system on 1583 board CU 00 ACC
91. uck into the sensor detector Static electricity may destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive waste They shall be packed in chock absorbing material to make a stable parcel PLEASE NOTE Damaged sensors detectors shall also be packed in a sealed packet whose surface must not be contaminated that is not be soiled with loose radioactive dust 110 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 37 Revision history Revision 111 This page has deliberately been left blank This page has deliberately been left blank NAIS Matsushita Electric Works U Fire amp Security Technology AB Citadellsvagen 23 SE 211 18 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 Home page www mfstech com
92. umber e g 1556 e an article number often the type no and sometimes is a country code added e g 1556SE e aproduct name e g Main Board 128 addr e ap c b number e g 9261 3A and could have a configuration e g CFG 1 a revision e g REV 2 e sometimes a SW SW A SW has e aversion number e g V1 44 1 e sometimes additional information such as Convention different functions facilities Language Number of addresses etc Matsushita Electric Works Fire amp Security Technology AB MEW00442 2 Operating Instructions EBL512 V1 44 x Definitions Explanations 2 1 2 2 2 2 1 2 2 2 2 2 3 2 2 4 2 2 5 2 2 6 2 2 7 Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document MFSTech Matsushita Electric Works Fire amp Security Technology AB Alarm points Units which can generate fire alarm in the control unit i e a sensor a conventional detector a manual call point etc Smoke detector Two types of analog and conventional smoke detectors are available photo electric optical and ionization Sensor Sensor Analog detector Analog detector Contains an A D converter The Control Unit pick up the digital values sensor values for each detector individually All evaluations and decisions are then made in the C U Analog detectors are addressable an address setting tool is used for detector types 3x
93. unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager Regarding DIL switch address setting see dwg 512 71 26 Matsushita Electric Works Fire amp Security Technology AB MEW00442 12 2 Rev Operating Instructions EBL512 V1 44 x Technical number for BS4 loop units Autronica interface board 1584 four BS4 loops is required in the control unit The technical number NNNNNN is used when programming all units connected to the BS4 loops Technical number is also used to identify which unit has generated a fault NN N N NN 01 99 The address on the BS4 loop Don t have to be in sequence The connections on the BS4 loop don t have to be in sequence The address is set on DIL switches in each unit 0 3 BS4 loop number 4 7 Board number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager NOTE In the technical number for unit connected to a BS4 loop the board number 4 Autronica interface board 0 the board number 5 Autronica interface board 1 the board number 6 Autronica interface board 2 and the board number 7 Autronica interface board 3 in the control unit In fault messages for Autronica interface boards the following information is
94. urity Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 35 How to avoid unnecessary nuisance fire alarms We all realise when life buildings production facilities etc shall be saved it is of utmost importance that an initial fire is detected as soon as possible That s why more and more automatic fire alarm systems are installed In an automatic fire alarm installation especially if smoke detectors sensors are used everybody in the building needs to be informed how to avoid so called unnecessary nuisance fire alarms To avoid trouble and unnecessary expenses there are a couple of things to bear in mind Here are some advice and tips Tobacco smoke The detectors sensors can not sense the difference between smoke and smoke They can not separate tobacco smoke from smoke from a fire Intensive tobacco smoking in connection with bad ventilation can cause a fire alarm Welding grinding cutting sawing amp drilling These kind of jobs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting amp candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of combustion products caused by cooking frying grilling toasting etc Warning Be careful when there are smoke detectors sensors near such activity Special environments
95. uts sounders routing equipment fire brigade tx etc will be activated NOTE If the control unit door is left open the output s for routing equipment fire brigade tx may be disabled if programmed so in Win512 There will be an automatic test mode exit one hour after the latest tested alarm point See also chapter Perform ZONE TEST test mode H7 page 93 Access According to chapter Perform monthly test EPT H Check that all LEDs light up The buzzer in the C U sounds and all dots in the display are shown for 3 seconds When printer is available it will print out Zone to be set in TEST MODE Te 2a 2 eE eee Stake best Write zone numbers Zone to be set in TEST MODE Push A to start the test oo 003 001 002 003 004 Start test E mode Zones are set in test mode LED Test mode L9 Ses a will light up Zone in TEST MODE Perform the tests When ready push A 001 002 003 004 End test to be continued 58 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Perform the tests as quickly as possible since the output for routing equipment fire brigade tx is disabled also the parts of the zones in test mode not visible for the test personnel are disabled In the tested alarm point the LED will light up and the LEDs Fire L1 in the C U will light up about ten sec
96. values access codes etc FAULT Subsystem control unit xx Gateway GW512 is are installed in the system One or more faults in the EBL1000 2000 system The fault s is are individually presented in the EBL1000 2000 system xx sub control unit number for the GW512 FAULT Supply external equipment CU xx Also indicated by LED Fault Power supply The fault is to be found in the external power supply connected to input in control unit xx 44 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x FAULT Supply for external FBP CU xx Also indicated by LED Fault Power supply Check the fuses F2 and F4 on the connection board 1555 Monitored output S2 is also supplied via F2 and F4 FAULT Supply for routing equipm CU xx Also indicated by LED Fault Power supply Check the fuses F1 and F3 on the connection board 1555 Monitored output S3 is also supplied via F1 and F3 FAULT Systemcomm in gateway CU xx Gateway GW512 is are installed in the system No not correct communication on the system loop between GW512 and the EBL1000 2000 Main Control Unit due to e cable connection fault e no not correct programming of the GW512 Sub Control Unit in the EBL1000 2000 system Xx EBL512 control unit number FAULT To low voltage control unit xx Also indicated by LED Fault Power supply System voltage lt 21 V DC FAULT Wire to exting
97. vated NOTE If the control unit door is left open the output s for routing equipment fire brigade tx may be disabled if programmed so in Win512 There will be an automatic test mode exit one hour after the latest tested alarm point Access According to chapter 8 p Access see page 57 Scroll to menu H7 Write zone numbers e g 001 002 003 004 Perform ZONE TEST be set in TEST MODE 2 2 Start tes Zone to be set in TEST MODE Push A to start the test mode 001 002 003 004 Start test Zones are set in test mode LED Test mode L9 wait will light up Zone in TEST MODE Perform the tests When 001 002 003 004 End test ACCE IA DUS hs Perform the test as quickly as possible since the output for routing equipment fire brigade tx is disabled also the parts of the zones in test mode not visible for the test personnel are disabled In the tested alarm point the LED will light up and the LED Fire L1 in the C U will light up about ten seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM Push A to stop the test mode Continues on next page 93 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x Perform ZONE TE If more zones are to be
98. version shown e g VER 1 41 x Weekday W 1 M ER VVVVVVVVVVVVV The time shown is the time when A was pushed for menu H3 Push A to accept or change the date time and or weekday The clock starts from the date time etc shown in the display NOTE Push Return instead of A when no changes are to be done Set calendar and clock Scroll or push Return to l t BET H3 98 70 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 26 Present system status on display and printer H4 Printer is factory mounted in control unit 1549 Printer 1558 is an option for control unit 1548 26 1 Disablement H4 U1 A list of all disablements in the system From this menu it s also possible to get a print out Access According to chapter Scroll to menu H4 Present system status on display and printer ACCEPT H4 Disablement Push 1 for an automatic rint out of all Printout l yes p disablements in the system Push A for presentation in the display When A is pushed the disablements will be shown in the This is a list in which you display e g can scroll If there are no i ts if Return Zone XXX address XX disabled cele Sars is pushed and after the last print out menu U1 will be shown again Disablement Scroll or push Return to printout teyesj menu H4 Scroll or push Retur
99. when required add more units The TLON network makes it possible to install the control units in one building or in many buildings PC SW Win512 is used for programming and commissioning of one or more control units e download backup of site specific data e download of SW settings configurations C U amp system data e create and download the user definable text messages shown in the alphanumeric display in the C U ext FBP and in the Display units TLON Manager is used for programming of network data addresses etc NEWTEXT DOS based older program could be used to create download the user definable text messages shown in the Display units connected to the COM loops 11 Matsushita Electric Works Fire amp Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 4 Control Unit Figure 1 EBL512 Control Unit 1548 1549 The look may vary according to configuration country etc The control unit c 1 e is housed in a grey metal cabinet The door has a Plexiglas ahead of the FBP part see Figure 1 When the door is open you fully see the front adhesive the Fire Brigade Panel FBP and Control Panel CP see Figure 2 L7 P2 P3 P4 P5 Pi P6 P8 P9 Figure 2 Front adhesive FBP upper black part and CP lower grey part in EBL512 The look may vary according to configuration English config in figure The fire brigade personnel use the F
100. xx and a DIL switch in the ASB see below for detectors 2xxx An analog detector has to be plugged in an ASB Analog Sensor Base ASB A sensor is plugged in an ASB which is connected to a COM loop see below Sensor Base types 2xxx have a DIL switch for COM loop address setting Conventional detector Detector with two states normal or fire alarm The detector contains a closing contact and a series alarm resistor Some types are plugged in an ADB see below or a CDB see below Some types are also available as addressable to be connected to a COM loop see below Normally plugged in a CDB see below connected to a conventional zone line with end of line resistor Conventional Detector Base CDB A conventional detector is plugged in a CDB connected to an external line an addressable zone interface conventional zone line etc Addressable Detector Base ADB A conventional detector is plugged in an ADB connected to a COM loop see below Matsushita Electric Works Fire amp Security Technology AB MEW00442 2 2 8 2 2 9 2 2 10 2 2 11 2 3 2 4 2 5 2 6 2 7 2 8 Rev Operating Instructions EBL512 V1 44 x Addressable A unit with a built in address device i e each unit is individually identified handled and indicated in the control unit The unit can consequently be an addressable zone interface to which one or more conventional alarm points can be connected Old detec
Download Pdf Manuals
Related Search
Related Contents
FANTEC MM-CH36US 4:00 pm Room 212 A 49502 Custom Set and Layers SATURNO ALCOR ALTAIR - Electric gates MSL 05_04_11 - Advance Lifts, Inc. Gigabyte GA-M52L-S3P AM2+, ATX, DDRII TBG 50LX PN ME. TBG 80LX PN ME. TBG 110LX PN ME. TBG ProxPoint Reader Installation Manual CTC 950 C – Bedienungsanleitung (PDF|4 MB) Coby CX244 Copyright © All rights reserved.