Home

Operating Instructions TLON Manager V2.0.x

image

Contents

1. TLONDDE Server Select this alternative for a TLONDDE Server for a security management system NOTE Only valid for Unit_29 Number 29 Securimaster 1 43 connection Select this alternative only for Securimaster 1 43 NOTE Only valid for Unit_29 Number 29 Channel See chapter 6 1 Planning a Project Select a Channel in the list In this example select Channel_1 default Description A description of the node may be written here Max 64 characters divided on three rows 5 Click OK to save the settings and close the dialog box The following will be shown in the List View P TLON Manager 2 0 d So File Network AllUnits Show Help D x a Network Status Project System_xyz Path CNm db System_xyz Number Channel Status 0 Channel_1 No Response Unit_0 is now added on Channel_l Status No Response shows that this unit is not installed is not responding Add the wanted number of EBL512 EBL512 G3 units nodes the same way In this example add one more unit Node_1 14 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 7 1 Operating Instructions TLON Manager V2 0 x Ta TLON Manager 2 0 L arim File Network AllUnits Show Help D a x Ga Network Status Project System_xyz Path CNm db System_xyz List View Unit Number Channel Status Update Pacem Unit_0 0 Channel_1 No Response Unit_1 1 Channel_1 No Response Ready
2. a Select the unit to be removed and click the right mouse button to get a pop up menu Select Remove b Select the unit and click Remove fa 2 TLON Manager 2 0 S m e a File Network AllUnits Show Help D a x G Install Online Wink Status Update Replace Remove Move Offline Restart Detail Information Ready Properties Remove Channels In the Network menu select Channel The following dialog box displays 27 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 12 3 Operating Instructions TLON Manager V2 0 x fi a Create Channel Channel_3 TP FT 10 Z Channel_1 Select the Channel to remove and click Remove Remove Routers In the Network menu select Router The following dialog box displays w Create Router pa No Response Select the router to remove and click Remove 28 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 13 Operating Instructions TLON Manager V2 0 x Maintenance and troubleshooting 13 1 13 2 13 3 Some TLON information is saved in the TLON connection board 1590 5090 memory and some in the EBL512 EBL512 G3 Main board 1556 5010 memory If only the Main board 1556 5010 is replaced Do Update for the unit Select the unit right click and select Update in the pop up menu If the TLO
3. Level 1 Type Repeater This type should normally be selected No learning function All messages except faulty messages will go through Learning Router This type could be selected It learns after some time the messages that shall go through to the other channel Only the required messages and no faulty messages will go through Learns if a new unit is added to the channel Configured Router This type could be selected It has no learning function The programming is followed to 100 and no faulty messages will go through Bridge Not used in a TLON Network Permanent Repeater Not used in a TLON Network Permanent Bridge Not used in a TLON Network 19 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x Near Far A router must be installed between two Channels If there is only one Channel in the list see above required new channels must be added before a router can be added see chapter 8 Add a Channel page 18 E Create Router 7 pr re Name Router_1 Type Repeater Mi Near Channel_1 x Far Channei_2 M Name Type Near Far Status Add Remove Install Reset Update Replace Status A router has connections for one Near channel e g Lon A and one Far channel e g Lon B Select a channel in the drop down list respectively Near On Router_1 the channel where the TLO
4. a Create Channel j Name Channel_2 Type TP FT 10 x Existing Channel_1 aa Name Next Channel in order to be added Normally the default name is used but can be changed Type The type used with EBL512 EBL512 G3 units is TP FT 10 default If a fibre optic network is to be used via Fibre Optic Twisted Pair LonWorks Routers the type is FO 10 Other units may use other types of communication Existing A list of the existing Channels in the Project Add Click Add to add the Channel shown in the Name field e g Channel_2 Remove Removes deletes a selected Channel in the list Close Saves the data and closes the dialog box when the required number of channels is added l6 E g Channel_2_Backbone 18 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 9 Add a Router Regarding Routers in a TLON Network see chapter 6 1 Planning a Project page 8 Two or more Routers have to be connected via a Backbone net Use Channel_2 for the Backbone net In the Network menu select Router and the following dialog box displays r a Create Router il a Far Name Router_1 Type Repeater x Near l Channel_1 Channel_1 Name Default is Router_1 Write another name or add some information for the router e g Router_1 Building A
5. Application Key below and click the Finish gt button If the key is valid the additional credits encrypted within the key will be added Order Information PC Key BCB 465E O6FB C480 50 71D7 D287 C5C1 CSFE 8E71 DCAS 82E5 CCD4 DESE 61DD 948C CASB Serial Number Not Applicable Copy to Clipboard Application Key Cancel Click Copy to Clipboard Open your favourite email program or word processor and paste the clipboard contents the Request form into the email message or document Send that Request form together with your article number 5096 order to Order pewnf eu panasonic com If you order from Echelon directly fill in the requested information in the Request form before you send it to credits echelon com Application Key You will receive an Application Key via a return email Start the LNS Server Licence Wizard and proceed to the second dialog box containing the Copy to Clipboard button Copy the Application Key from the return email into the Application Key field Click Finish Request form example The Request form shall be send together with the article 5096 order NOTE If you order article number 5096 Panasonic ESN AB will fill in the requested information in the top part of the form If you order from Echelon directly fill in the requested information Here follows an example of a Request form generated by the LNS Server Licence Wizard 39 Panasonic Eco Soluti
6. all the LNS Device credits Licensed credits are consumed and TLON Manager V2 0 has started to use Deficit credits this field will show the number of days 0 14 before the license will expire If the number of days 0 the LNS Server will cease to operate until new LNS Device credits Licensed credits are added Deficit credits As long as there are LNS Device credits Licensed credits this field will show 0 When all the LNS Device credits Licensed credits are consumed TLON Manager V2 0 will start to use Deficit credits This field will then show the number of Deficit credits being used 0 500 Licensed credits The number of LNS Device credits added Licensed type Always Standard Mode in TLON Manager 2 0 Max deficit credits The number of Deficit credits allowed If this number is exceeded the LNS Server will cease to operate until sufficient LNS Device credits are added Used credits The number of the LNS Device credits Licensed credits consumed This number does not include the number of Deficit credits currently being used 37 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 15 2 Operating Instructions TLON Manager V2 0 x How to order LNS Device credits Before the license will expire you should purchase additional LNS Device Credits Panasonic Electric Works Nordic AB s article number for additional LNS Device Credits is 5096 The article number 5096 corresponds to 50 LN
7. documentation etc Also a USB extension cable is supplied License for 64 credits per PC Ss SS L O The USB network interface D is via the Network connection cable Z connected to the modular RJ 45 connector in EBL512 EBL512 G3 The USB extension cable is normally used with the USB Network interface but can of course be used for the USB memory stick if required Credit LNS Device credit One credit is consumed for each Neuron ID number in the network e g each TLON connection board 1590 p c b no 9302 xx but not for the succeeding TLON connection board 5090 p c b no gt 9310 xx Routers will not consume any LNS Device credits How to check the LNS Device credits Licensed credits status and how to order new credits see page 36 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 3 Echelon LNS Server 3 1 Installation of the Echelon LNS Server Before installation be sure that no other application is running on your PC The USB Memory stick contains the Echelon LNS Server 3 27 the TLON Manager V2 0 x software the OpenLDV driver and documents Put the USB Memory stick in one of your PC s free USB ports lt USB drive gt LNS Server 3 27 OpenLDV x xx Operating instructions TLON Manager 2 0 x Select the LNS Server 3 27 folder Double click the Setup exe file name and follow the installation instructions Op
8. x 16 Revision history When possible the revised information is written in red font colour Revision 1 Revised added info in the following chapters 2 TLON Manager kit 5095 footnote 2 15 LNS Device credits The whole chapter is revised Revision 2 Company name etc revised TLON connection board 1590 is revised to 1590 5090 Revised added info in the following chapters 3 1 Info added 5 Info revised 6 1 Info added mixed system 6 1 2 Info and footnote added 6 2 Footnote added 7 Footnote added 13 Info deleted 13 3 Info added Revision 3 New chapter 5 about installation of the driver OpenLDV gt 4 00 which is necessary to support 64 bit Windows versions 45 This page has deliberately been left blank Panasonic Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 e Fax 46 0 40 697 70 99 E mail info pewnf eu panasonic com e Internet pesn panasonic se ISO 9001 NATIONAL ACCREDITATION OFCERTIACATION BODES
9. 361_ Rev 3 Operating Instructions TLON Manager V2 0 x 7 Create a New Project This example will show how to connect two EBL512 EBL512 G3 units CU00 and CU01 in a TLON network Start TLON Manager i e double click the EE icon on your PC s desktop i a File Network AllUnits Show Help D a x G Unit Number Channel Status Update Ready 1 Select New in the File menu rr Eron rg 2 File Network All Units Show Help Open Close X Delete Import Export 23 Copy Project A dialog box displays 11 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x Gi E Create New Project Name Path CAm db Browse Network Interface Name Type a name for the project Normally use the same name as the System Name in Win512 WinG3 e g System_xyz Max 23 characters Path The path will be automatically created when you type the name i e C lm db NOTE Do not change this data base path Network interface Engineered Mode This mode shall be selected when TLON Manager i e your PC is not connected to any TLON Network e g when creating a new Project in your office LON1 This is the TLON USB Network interface for TLON Manager 2 0 installed on your PC Select this interface LON1 when you shall connect TLON
10. 5R 1 1 8W 35 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x An example of an EBL512 network with three Routers connected via a Backbone net Four Channels are required Channel_2 Backbone net Router_1 Router_2 Router_3 l l l 512 512 512 l l l 512 512 512 l l l l l l Channel_1 Channel_3 Channel_4 Each Channel has to start and end with a termination resistor 105R 1 1 8W 36 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 15 Operating Instructions TLON Manager V2 0 x LNS Device credits 15 1 With every TLON Manager kit 5095 TLON Manager V2 0 comes a license with 64 LNS Device credits One LNS Device credit is consumed for each Neuron ID number in the network e g each TLON connection board 1590 p c b no 9302 xx but not for the succeeding TLON connection board 5090 p c b no gt 9310 xx Routers will not consume any LNS Device credits How many LNS Device credits remains Open any project in menu File select Open In menu Help select License status and the following dialog box opens License status Days remaining Sufficient credits Deficit credits 0 Licensed credits 64 License type Standard Mode Max deficit credits 500 Used credits 4 Days remaining As long as there are LNS Device credits Licensed credits this field will show Sufficient credits When
11. C Ins The Project name will be the same as the folder name You may use this name or change it 24 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 11 6 Export Used when you want to export a Project You will get a copy of the Project in another folder From this folder it is possible to copy the project Export can also be used if you want a backup of the project or want to use the Project in another PC Select Export and the following dialog box displays E Export Select Project Charie _0 Charie_1 TLON_2_0 System _xyz Select the Project to export Click OK F Browse For Folder Choose a folder to Exprot the project to 1 Computer 4 amp Local Disk C J ACLTWIN d Corel jpg J dell di Downloads dJ DVD_VIDEO_RECORDER D hp B inetpub 4 PY Im a l db Ii Sustem wer Bme C Gam Find and select the folder to which the Project is to be exported As default TLON Manager suggests C im db The File name Project name will be the same as the folder name You may use the current name or change it Click OK The project will now be copied to the selected folder NOTE It is not possible to upload data from the TLON Network to TLON Manager 25 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 11 7 Copy proj
12. Environment Variables Check in User variables that the Path is C LonWorks bin If not add it At the Date of issue or the Date of rev x 0 Operating Instructions TLON Manager V2 0 x MEW01361 i e this document in PDF format Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 5 Echelon OpenLDV driver 5 1 Installation of the Echelon OpenLDV driver An older version of the driver OpenLDV 3 4 was automatically installed during the installation of Echelon LNS Server 3 27 Before installation of the new driver OpenLDV gt 4 00 uninstall the old driver OpenLDV 3 4 The USB Memory stick contains the Echelon LNS Server 3 27 the TLON Manager V2 0 x software the OpenLDV driver and documents Put the USB Memory stick in one of your PC s free USB ports lt USB drive gt LNS Server 3 27 OpenLDV x xx fie Operating instructions TLON Manager 2 0 x Select the OpenLDV x xx folder Double click the _OpenLDVXxx exe file name and follow the installation instructions Connect the USB Network interface U10 to an available USB port The installation of the USB driver should start automatically If a Windows Update dialog box tells you to install the driver choose any of the three Windows Update options at your preference Click Next to continue Select Install the software automatically Recommended Click Next to continue A dialog box ap
13. Interfaces and select one normally LON1 a Open Project Project 11 Click OK 2 TLON Manager 2 0 g ma File Network AllUnits Show Help D x amp Project System_xyz Path CNm db System_xyz 12 In this example we have no Routers and only one Channel i e Channel_1l Routers have to be installed before EBL512 EBLS512 G3 units 13 Select a unit click Install and the following window will be displayed Install Unit Install the Unit must be attached Click Yes and the following dialog box displays 16 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 14 15 16 17 Operating Instructions TLON Manager V2 0 x E a Waiting for Service message Activate Service Pin Type of Unit EBL512 EBL512 G3 Neuron ID 7 Start installation automatically when service message is received ok Cancel Activate service pin is blinking In the EBL512 EBL512 G3 unit that is intended to be number zero CU00 shunt momentarily the Service pins in EBL512 JP 3 on the main board 1556 in EBL512 G3 JP 1 for Network no 0 or JP 2 for Network no 1 on the main board 5010 A Neuron ID number will be transmitted and for a second shown in the Neuron ID field Since the check box Start installation automatically when service message is received
14. Manager i e your PC to a TLON Network PCCLONI1 This is the TLON Network interface PCMCIA card for TLON Manager 1 x shown only if installed on your PC Must not be used for TLON Manager 2 0 2 Click OK to save the settings and close the dialog box In the TLON Manager 2 0 window is now displayed the Project System_xyz and the Path C lm db System_xyz Normally only one interface is installed but if also TLON Manager 1 x is installed LON1 might be used for that interface 12 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x r aS TLON Manager 2 0 T _ a Se File D x Network AllUnits Show Help System_xyz CNim db System_xyz In this example no Channels have to be added Now the EBL512 EBL512 G3 units have to be added In the Network menu select Unit or click Add The following dialog box displays amp a9 Create Unit Encim Name Unt _0 Number 0 Type EBL512 EBL512G3 Channel Channel_1 Name Use the default name or type a name Max 14 characters Number The number can be 00 29 i e CU00 CU29 Normally use the same number as in the name Type EBL512 EBL512 G3 Select this alternative for an EBL512 EBL512 G3 unit 13 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x
15. N Manager PC is to be connected often Unit_0 on Channel_1 On any other router the channel nearest Router_1 Far On Router_1 the Backbone net channel Channel_2 On any other router the channel on the other side of the router respectively Click Add to have the router shown in the list List field A list of the existing Routers in the Project Name The name of the router Type Type of router Near Near Channel Far Far Channel Status No response CnfgBypass Online Offline Add Adds the Router Type and Channels to the list List field Remove Removes deletes the selected router in the Name column 20 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 9 1 Operating Instructions TLON Manager V2 0 x Install Installs the selected Router in the Name column A dialog box Install displays See chapter Installation of Routers below Reset Sends a reset message that will clear some statistics and configuration data Update Updates the selected router See Update below Replace When an existing Router has to be replaced you do not have to remove delete the existing Router and then add a new Router Replace will start the same procedure as for Install See chapter Installation of Routers below Status The status for the selected Router in the Name column will be shown in the Status column Close Will save and close the dialog box Installation of Rout
16. N connection board 1590 5090 is replaced Do Replace and Update for the unit There are a number of functions that are useful for network maintenance and troubleshooting The most common are described below Install The unit will be installed in the network see chapter Installation of a Project page 15 and chapter Installation of Routers page 21 Online The selected unit can be set Online if the status is CnfgBypass Offline Wink With Wink you can check that the EBL512 EBL512 G3 unit corresponds to the selected unit in TLON Manager 2 0 A not connected node not installed etc cannot receive a wink message There are two ways to send a wink message a Select the unit and click the right mouse button to get a pop up menu Select Wink b Select the unit and click Wink 29 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 13 4 13 5 Operating Instructions TLON Manager V2 0 x File Network AllUnits Show Help D x Network Status Project Charie _0 Path C ns Chardie _0 List View Add Unit Number Channel Status Update aa Node_0 0 Channel_1 CrfgOnline Node_1 1 Channel_1 CrfgOn ioa Install Install Online Update all Status All Online Update Replace Remove Move o Offline Restart Detail Information Properties EBL512 In the selected EBL512 unit node the wink message turns on the buzzer and all the front LEDs for app
17. Panasonic Operating Instructions MEW01361 Revision 3 TLON Manager V2 0 x Author Jan Pettersson Date of issue 2010 12 23 Date of rev 2013 02 08 This page has deliberately been left blank Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x Table of contents Introduction 3 1 1 Definitions 3 2 TLON Manager kit 5095 4 3 Echelon LNS Server 5 3 1 Installation of the Echelon LNS Server 5 4 Installation of TLON Manager 6 5 Echelon OpenLDV driver 7 sH Installation of the Echelon OpenLDV driver 7 6 Project 8 6 1 Planning a Project 8 6 1 1 EBL512 network 8 6 1 2 EBL512 G3 network 9 6 1 3 Channels 9 6 1 4 Routers 9 6 1 5 EBL512 EBL512 G3 units nodes 9 6 2 Planning Creating a project 10 7 Create a New Project 11 7 1 Installation of a Project 15 8 Add a Channel 18 9 Add a Router 19 9 1 Installation of Routers 21 10 Add a Unit 23 11 File menu 24 11 1 New 24 11 2 Open 24 11 3 Close 24 11 4 Delete 24 11 5 Import 24 11 6 Export 25 11 7 Copy project 26 11 8 Exit 26 12 Remove 27 12 1 Remove EBL512 EBL512 G3 units nodes 27 12 2 Remove Channels 27 12 3 Remove Routers 28 13 Maintenance and troubleshooting 29 13 1 Install 29 13 2 Online 29 13 3 Wink 29 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 13 4 Status 30 13 5 Update 30 13 5 1 Update all 31 13 6 Replace 31 13 7 Remove 31 13 8 Move 31 13 9 Offline 31 13 10 Res
18. S Device Credits It is also possible to order LNS Device Credits directly from Echelon In your Start menu you will find a program group Echelon LNS Utilities Start the program LNS Server Licence Wizard V LNS Server License Wizard Welcome to the LNS Server License Wizard The information below show s the current credit usages for the LNS Server License To purchase additional credits enter an amount below then Click Next gt to continue LNS Server Credit Info Credit Order Max pa Enter number of credits Credits to add Credits p4 Available Keep used credits recommended we cme In the Credit Order frame enter the number of LNS Device Credits you want to add purchase i e normally 50 Then click Next gt 38 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 15 3 15 4 Operating Instructions TLON Manager V2 0 x WV LNS Server License Wizard To complete this order send an order form by fax or email to the Echelon License Administrator Generate your order form by clicking the Copy to Clipboard button then opening your favorite word processor or email program and pasting to the document Fill the blanks then print and fax in the form to 1 408 790 3833 or email it to credits echelon com If you are not ready to enter the Application Key click the Cancel button and rerun the Vizard when you have it Once your order is processed you will receive back an Application Key Enter the
19. The window shows the Project System_xyz with two units Unit_O and Unit_1 on Channel_1 8 This project is now created and can be closed in menu File select Close and later installed see Installation of a Project below Installation of a Project The TLON Network cable installations have to be finished and the EBL512 EBL512 G3 units connected to the TLON Network NOTE In a Project with Routers they have to be installed before the EBL512 EBL512 G3 units see chapter Installation of Routers page 21 Plug the TLON USB network interface cable into any of the EBL512 EBL512 G3 units on Channel_1 The modular connector RJ 45 J2 in EBL512 J10 Network no 0 and J11 Network no 1 in EBL512 G3 are to be used 9 Start TLON Manager In the File menu select Open One TLON connection board 1590 5090 is required in each EBL512 unit In EBL512 G3 one 1590 5090 board per TLON Network From now on it is recommended to use the same Channel at all times It is situated close to the connector J1 for PC Win512 connection i e below and to the right of the keypad on the EBL512 front Situated down to the right on the main board 5010 15 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x al Open Project 10 Click to see the list of Projects and select one e g System_xyz Click to see the list of Network
20. btain a total cable length that is two times the normal cable length for one Channel In rough outline there are three types of networks a Up to six EBL512 units nodes on one Channel i e no Router b Up to twelve EBL512 units nodes and one Router i e one Router and two Channels One Router can also be used in order to obtain a total cable length that is two times the normal cable length for one Channel c Up to thirty EBL512 units nodes and a number of Routers connected to each other via a Backbone net Make a schematic drawing of the network i e a drawing showing all the EBL512 units nodes cables Channels and required Routers The fire alarm system s installation drawings can be useful as well as the planning made with Win512 e g system name control unit numbers cables etc For safety reasons it is recommended to place all the Routers and the backbone net together in a locked cabinet room See also chapter Examples page 35 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 6 1 2 Operating Instructions TLON Manager V2 0 x EBL512 G3 network Redundant network For safety reasons the EBL512 G3 units have the possibility to use two TLON connection boards type 1590 5090 in order to get two parallel TLON Networks Network no O and 1 i e a redundant network Normally TLON Network no 0 is used for communication and TLON Network no 1 is in a supervised quiescent state TLON Ne
21. ect Used when you want a copy of an existing Project but with a new name This is useful when a new similar Project is to be created Select Copy project and the following dialog box displays Ia Copy Project arim Select Project Charie _0 Charie_1 TLON_2_0 System_xyz Select the Project to copy Click OK The following dialog box displays a a Select Path andSaveas E ME OO afd gt Computer gt Local Disk C Im db gt Organize v New folder Name Date modified Attribut Sil F Favorites Recently Changed Ji System yz 2010 12 14 13 34 D J Public J TLON2 0 2010 12 13 15 30 D EE Desktop E Recent Places m G Libraries Documents d Music E Pictures E Videos Filename copy_System_xyz X Save as type Z Hide Folders Save Cancel E Select a folder accept the file name or write another Click Save and the project will be copied 11 8 Exit Select Exit to close TLON Manager 2 0 NOTE First close the project 26 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 12 12 1 12 2 Operating Instructions TLON Manager V2 0 x Remove Everything added to the network i e EBL512 EBL512 G3 units Channels Routers etc may also be removed deleted NOTE After removing something you have to Update all Remove EBL512 EBL512 G3 units nodes There are two ways to remove a node
22. er Installation of a Project page 15 NOTE When all the EBL512 EBL512 G3 units nodes have been installed it is very important that you click Update all and All Online as described in the example After that it is recommended to restart each EBL512 EBL512 G3 unit 23 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 11 File menu TLON a TI File Network All Units L New EF Open Close X Delete Import Export 5a Copy Project Exit 11 1 New Creates a new Project Se chapter Create a New Project page 11 11 2 Open Opens an existing Project in TLON Manager s common data base Select a project in the list select a Network Interface and click OK 11 3 Close Closes the project that is open 11 4 Delete Deletes an existing Project in TLON Manager s common data base In the list select the project to be deleted and click OK 11 5 Import To be able to open a Project that for example has been copied from another PC or to be able to open an old Project when a new version of TLON Manager has been installed the Project has to be imported to TLON Manager s common database Select Import and the following dialog box displays F a Import Find and select the folder Project to be imported As default TLON Manager 2 0 saves all projects in C im db As default TLON Manager 1 x saves all projects in
23. erating Instructions TLON Manager V2 0 x MEW01361 i e this document in PDF format Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 4 Installation of TLON Manager Before installation be sure that no other application is running on your PC Before installation of this version V2 0 x uninstall any other version of TLON Manager V2 X x The USB Memory stick contains the Echelon LNS Server 3 27 the TLON Manager V2 0 x software and documents Put the USB Memory stick in one of your PC s free USB ports lt USB drive gt LNS Server 3 27 re OpenLDV x xx i Operating instructions z TLON Manager 2 0 x Select the TLON Manager 2 0 x folder Double click the Setup exe file name and follow the installation instructions Click Finish to finish the TLON Manager installation The program will normally be installed in the following folder C Program Files Panasonic Electric Works Nordic AB TLON Manager 2 0 x It is recommended to send a Shortcut to the desktop NOTE After a program installation it is always recommended to restart the PC It is also recommended to check that the path is correct Do as follows could vary depending on the type of Windows that is used In Windows Explorer use the right mouse button and click My Computer in the menu select System Properties In System Properties open the Advanced System Settings tab and click
24. ers The TLON Network cable installations have to be finished and the Routers have to be power supplied and connected to the network Plug the TLON USB network interface cable into any of the EBL512 EBL512 G3 units on Channel_1 The modular connector RJ 45 J2 in EBLS512 J10 Network no 0 and J11 Network no 1 in EBL512 G3 are to be used Start TLON Manager In the File menu select Open Select Project and Network Interface normally LON1 and click OK 3 In menu Network select Router N 17 From now on it is recommended to use the same Channel at all times 8 Tt is situated close to the connector J1 for PC Win512 connection i e below and to the right of the keypad on the EBL512 front 1 Situated down to the right on the main board 5010 21 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 4 In the dialog box select a Router in the Name column and click Install The following dialog box will be displayed f Install Router Install the Router must be attached Click Yes A dialog box displays E a Waiting for Service message gt Sto Activate Service Pin When manual entry of the Neuron ID Enter the near router side s Neuron ID Neuron ID Start installation automatically when service message is received _ Canc V Activate service pi
25. for latest restart of the unit Transaction Timeouts Shows the number of messages sent but not acknowledged by all other nodes in the network The number should be 0 after the unit has been installed The number may increase if new units are installed Reset the value and all the others by clicking Reset Transmission Errors After a reset of values by clicking Reset Must not increase during a 10 minutes interval Test Shall normally be Good Properties Select a unit and click the right mouse button to get a pop up menu Select Properties The following dialog box displays 33 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 0 EBL512 EBL512 G3 Channel_1 002268500900 Alfa For explanation of Name Number Unit Number etc see the above chapter Click OK to save and close the dialog box 34 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 14 Examples Some examples of TLON Networks Two networks with eight EBL units System EBL512 System EBL512 G3 gt 6 units i e one Router Redundant network is required i e two networks Channel_1 and Channel_2 Channel_1 512 512 G3 l I l 512 512 G3 l I 512 512 G3 l I 512 512 G3 l I l Router_1 512 G3 l I l 512 512 G3 l I 512 512 G3 l I 512 512 G3 l 512 Each Channel has to start and end with a termination resistor 10
26. he following payment methods and fill in the information for the requested method Credit Card minimum order of 50 credits Type of credit card American Express MasterCard Visa Name on the credit card Credit card number Expiration date Authorized by Billing Address Street 1 Street 2 City Providence State Postal Zip Code Country Purchase Order minimum order of 50 credits Purchase Order Number Authorized by Billing Address Street 1 42 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x Street 2 City Providence State Postal Zip Code Country No charge evaluation development test support production training or replacement credits check all that apply By submitting an order for free credits you agree that you will use these free credits only for the authorized purposes that you have checked below and you agree that you will provide Echelon with information as reasonably requested by Echelon to verify that the use of these LNS Device Credits is limited to the authorized uses There is no minimum order size maximum order size is indicated below Evaluation use LNS Device Credits used for evaluation purposes Limited to 500 free credits per company per year Internal development and test use LNS Device Credits used for the development and testing of devices that will solely will be used for develo
27. is marked TLON Manager will automatically start binding the node in the database The EBL512 EBL512 G3 Unit_0 is now created and installed in the network When the binding process is completed the Status will be CnfgBypass until all units are Online see below Do the same for the EBL512 EBL512 G3 Unit_1 In this example are now all units installed Click Update all TLON Manager will now re connect and update all the units installed in the network The Network information will now also be saved in each EBL512 EBL512 G3 unit one by one Some information will be saved in the TLON connection board 1590 5090 memory and some in the Main board 1556 5010 memory When all nodes are updated click All Online It is highly recommended to restart each EBL512 EBL512 G3 unit e g in menu All Units select Restart 14 Tf the check box is un marked you will have to click OK to continue The time is depending on the number of nodes S To check this you can select the EBL512 EBL5S12 G3 unit and click Wink The buzzer in the EBL512 EBL512 G3 unit respectively shall sound for approx one second 17 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 8 Add a Channel Regarding Channels in a TLON Network see chapter 6 1 Planning a Project page 8 In the Network menu select Channel and the following dialog box displays E
28. k two Projects have to be created and installed The Projects have to be identical but with different Project names One has to be installed for Network no 0 and one installed for Network no 1 8 One TLON connection board 1590 5090 is required in each EBL512 unit In EBL512 G3 one 1590 5090 board per TLON Network Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 6 2 Operating Instructions TLON Manager V2 0 x Planning Creating a project Here follows a rough overview Create a New Project File New Add required Channel s Network Channel Add required Router s Network Router Add the nodes Network Unit or Click Add Normally EBL512 EBL512 G3 units or TLONDDE Server or Securimaster 1 43 connection Installation All the network data will be downloaded to the units EBL512 EBL512 G3 etc Installation order 1 Routers Router Install 2 Nodes Node Install Update all Click Update all All network data will be updated and saved in all the units i e all the units will get information about all other units NOTE In EBL512 EBL512 G3 some data will be saved in the TLON connection board 1590 5090 and some data in the Main board 1556 4556 Wink Click Wink This is a way to check if a unit is correctly connected and installed in the network The buzzer will sound for a second in the unit respectively 10 Panasonic Eco Solutions Nordic AB MEWOI
29. n is blinking On the specified Router push the Service button A Neuron ID number will be transmitted and for a second shown in the Neuron ID field Since the check box Start installation automatically when service message is received is marked TLON Manager will automatically start binding the router in the database The Router_1 is now created and installed in the network When the binding process is completed the Status will be CnfgOnline When all Routers are installed click Update all TLON Manager will now re connect and update all the routers installed in the network When all the Routers are installed the EBL512 EBL512 G3 units can be installed see chapter Installation of a Project page 15 20 Tf the check box is un marked you will have to click OK to continue 22 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 10 Add a Unit Regarding EBL512 EBL512 G3 units nodes in a TLON Network see chapter Planning a Project EBL512 EBL512 G3 units nodes page 8 In the Network menu select Unit or click Add The following dialog box displays a9 Create Unit Name Unit_2 Number 2 Type EBL512 EBL512G3 Channel Channel_1 7 The dialog box and the following actions are described in the example in chapter Create a New Project page 13 and continues in chapt
30. oject page 15 Replace When a TLON connection board 1590 5090 is replaced in an EBL512 EBL512 G3 unit select the unit and click Replace After that you have to Update see above Remove The selected unit will be removed deleted from the project See chapter 12 Remove page 27 Move A node can be moved from one Channel to another In the dialog box that opens specify the New location Channel and click OK NOTE The Channels have to added before Offline The selected unit can be set Offline CnfgBypass if the status is Online Restart You can restart a unit in the network with the restart command Ina TLON Network this command works only with EBL512 EBL512 G3 units Select the unit and click the right mouse button to get a pop up menu Select Restart The following dialog box displays Restart Unit 31 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 13 10 1 13 11 Click Yes to restart the unit Restart All units You can restart see above all the units in a TLON Network In the menu All units select Restart The following dialog box displays Are you sure you want to restart the Network Click Yes to restart the unit Detail Information This command asks a unit in the Network a series of questions which will be presented in a dialog box Select a unit and click the right mouse bu
31. ons Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x YOU MUST FILL IN ALL THE BLANK FIELDS IN THE TOP PART OF THE FOLLOWING FORM SELECT ONE OF THE BILLING OPTIONS BY FILLING IN A CHECKBOX IN THE BOTTOM PART OF THE FORM AND FILL IN THE BLANK FIELDS IN THE SELECTED BILLING OPTION IF YOU ARE ORDERING NO CHARGE CREDITS YOU MUST FILL IN ONE OF THE CHECKBOXES EXPLAINING THE REASON FOR THE ORDER A BLANK FIELD IS A FIELD WITH A COLON AT THE END OF THE LINE IF ANY OF THIS INFORMATION IS MISSING YOUR ORDER WILL BE DELAYED TO Echelon License Administrator Email credits echelon com Fax 1 408 790 3833 FROM Name Company Address 1 Address2 Country Phone Fax Email SUBJECT Order for LNS r Device Credits LNS Turbo Edition PRS FAS 2g K K K K K K K K K K K K K K K K K KK K K K K K K K K K K K K K K K K K K K os KK 2 2K K K K 2 2 K ok xK xK NOTE This order form is for ordering LNS Device Credits kA LNS Device Credits are software keys that authorize 40 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x an LNS Server to Commission or Recover additional devices ne xK xK This form CANNOT be used to order LonMaker Credits Consult the LonMaker documentation for instructions for ordering LonMaker Credits an xK xK EE Also this form CANNOT be used to register the LNS EE Ap
32. ort for connection to the TLON Network Unit A physical device connected to the network e g an EBL512 or an EBL512 G3 unit containing a TLON connection board 1590 5090 Node A logical part of the network E g a unit see above Channel A physical part of the network i e the wires to which the units nodes are connected Compare with a COM loop and the connected loop units In system EBL512 up to six units nodes can be used per Channel Each side of a Router is a Channel Two or more Routers are connected via a Backbone net one Channel without other units In system EBL512 G3 with redundant network two parallel networks are Routers normally not required but can be used when a longer network cable is required longer than the max length for one Channel or for extra security reasons Router Repeater Normally a repeater will forward all valid data and a router will forward all valid data based on its destination address It is normally the same unit configured as a repeater or as a router In a TLON Network it doesn t matter because all valid data will be forwarded Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x 2 TLON Manager kit 5095 The TLON Manager kit 5095 contains the following gt U10 USB Network interface type 75010R Network connection cable C USB Memory stick containing Echelon LNS Server the PC program TLON Manager V2 0 x
33. pears Click Finish i Operating Instructions TLON Manager V2 0 x MEW01361 i e this document in PDF format Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 6 Operating Instructions TLON Manager V2 0 x Project 6 1 6 1 1 Normally often the network planning is carried out in your office Afterwards during the commissioning on site the TLON network installation can be performed As an alternative the planning and the installation can be carried out at the same time on site TLON network installation download of the project network data to the network units EBL512 EBL512 G3 and Routers Planning a Project A TLON Network can consist of two or up to thirty EBL512 EBL512 G3 units In an EBL512 TLON Network are normally for safety reasons Routers used see below In an EBL512 G3 TLON Network can one TLON Network with or without Routers be used or two parallel TLON Networks i e a redundant network see below It is possible to have one TLON Network with a mix of EBL512 and EBL512 G3 units i e a mixed system In such a case the EBL512 units have to have the software version 2 7 x and the EBL512 G3 units have to have the software United version 2 7 x EBL512 network For safety reasons it is recommended not to have more than six nodes on one Channel To get one more Channel a Router has to be added i e one Router per six EBL units A Router can also be added in order to o
34. plication Developer s Kit product If you have x licensed the LNS Application Developer s Kit oe ka product consult the documentation for instructions ces on how to register the product kE xK xK KEKE K K K K K K K K K K K K K K K K K KK K K K K K K K K K K K K K K K K K K K K KK K 2s K K K 2k 2k K K K K K Please process the following order Number of LNS Device Credits ordered ADD 50 Number of LNS Device Credits to be delivered if less than the quantity ordered Product LNS Device Credits Model Number 34400 Price Each Total Amount Following are the list prices These prices are subject to change Contact your distributor for current and local pricing Your distributor may also provide you with an alternate mailing address for this order List price US 1 50 Price for authorized free uses No charge see agreement below The following PC key value is filled in automatically by the LNS 41 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x Server License Wizard when you generate an LNS Device Credit order as described in the product documentation You should always use the order form generated by the software and send the form by email or fax if email is not available to ensure that there are no errors in transcribing the PC key value PC Key DBCB A65E 06FB C480 50 71D7 D287 C5C1 C5FE 8E71 DCAS5 82E5 CCD4 DE8E 61DD 9A8C CA8B Select one of t
35. pment or that will be shipped in the unconfigured state Limited to 500 free credits per device type per year Support use LNS Device Credits used by a support engineer to provide support to a customer The customer must have paid for the LNS Device Credits used for the customer s devices Limited to 500 free credits per support engineer per year 43 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0 x Production use LNS Device Credits used for manufacturing test Devices must be shipped in the unconfigured state Limited to 1 free credit per manufactured device shipped in the unconfigured state Training use LNS Device Credits used solely for training Any devices installed during training must not be used in a production or operational system Limited to 500 free credits per class Replacement use LNS Device Credits used to replace LNS Device Credits that were lost due to a PC hardware or software failure Limited to the number of credits that were lost as a result of the failure Your LNS Device Credits will be sent to you by email or fax as an Application Key a series of numbers and letters When you receive the Application Key run the LNS Server License Wizard again enter the Application Key on the second page of the wizard and then click Finish 44 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 Operating Instructions TLON Manager V2 0
36. rox 1 sec EBL512 G3 Network no 0 In the selected EBL512 G3 unit node the wink message turns on the buzzer and the front LED Test mode for approx 0 4 sec EBL512 G3 Network no 1 In the selected EBL512 G3 unit node the wink message turns on the buzzer and the front LED Test mode for approx 2 sec Status The status for the selected unit will be updated i e no change no change of the status Update Normally you update a unit i e the network configuration data is downloaded to the physical unit after it has been installed see chapter Installation of a Project page 15 Update can also be used when you suspect that the configuration data in a unit is incorrect When a TLON connection board 1590 5090 is replaced and or the Main board 1556 5010 is replaced in an EBL512 EBL512 G3 unit the unit have to be updated Select the unit and click the right mouse button to get a pop up menu Select Update After Update the information is 30 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 13 5 1 13 6 13 7 13 8 13 9 13 10 Operating Instructions TLON Manager V2 0 x OK 0 Update OK 0 unsuccessful attempts OK 1 Update OK after 1 unsuccessful attempt OK 2 Update OK after 2 unsuccessful attempts NG Update not good Update all All the units in the Network can be updated see above with only one command Click Update all See also chapter Installation of a Pr
37. tart 31 13 10 1 Restart All units 32 13 11 Detail Information 32 13 12 Properties 33 14 Examples 35 15 LNS Device credits 37 15 1 How many LNS Device credits remains 37 15 2 How to order LNS Device credits 38 15 3 Application Key 39 15 4 Request form example 39 16 Revision history 45 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 1 Operating Instructions TLON Manager V2 0 x Introduction 1 1 TLON Manager is an installation and maintenance tool for the TLON Network used for fire alarm systems EBL512 and EBL512 G3 TLON Manager 2 0 will replace TLON Manager 1 X x since that program needs a PCMCIA card as a network interface New Laptop PCs normally don t have any PCMCIA card slot Both programs can be used with both EBL systems and projects created in TLON Manager 1 X x can be opened in TLON Manager 2 0 which uses a USB network interface and has been updated to be more user friendly This Operating Instruction describes how to install the PC program TLON Manager V2 0 x At the Date of issue or the Date of rev x 0 It also describes how to create a new TLON project how to install it and the maintenance of a TLON network It is not a complete description of the TLON Manager Basic knowledge of windows and windows applications are required as well as knowledge of the fire alarm system respectively Definitions USB network interface type 75010 An Echelon network interface to be plugged in a laptop PC s USB p
38. tton to get a pop up menu Select Detail Info The following dialog box displays ft a Detaillnfo Unit_0 ype EBL512 EBL512 G3 Program ID 544C4F4E4D495000 Status CrfgOnline Update 1 1 Neuron ID 002268500900 Channel Channel_1 Location 000000000000 Unit Number 0 Description Alfa Model 0 Self Info TLON node software 6 Software Reset The dialog box contains a lot of information and a deeper knowledge of the TLON Network is required to be able to understand some of it The information of interest for the average user is explained below In case of no contact the information is No contact with node 32 Panasonic Eco Solutions Nordic AB MEWOI361_ Rev 3 13 12 Operating Instructions TLON Manager V2 0 x Name The name given to the unit when it was created Type The type given to the unit when it was created see page 13 If an old project is opened in TLON Manager 2 0 x the type shown here might be different than the type given to the unit when it was created Status Shows the status of the unit The normal status is CnfgOnline Neuron ID The TLON connection board 1590 5090 Neuron ID number Channel Shows the Channel the unit is installed on e g Channel_1 Unit Number The number given to the unit when it was created Description The Description given in the Create unit dialog box if any Last reset cause Shows the reason
39. twork no 1 will be used for communication only in case of a fault condition cut off or short circuit on TLON Network no 0 If a redundant network is used there is no need for Routers if not a cable length longer than the normal cable length for one Channel is required see b above Channels Two or more EBL512 EBL512 G3 units nodes are physically connected to each other via a network cable In the LonWorks vocabulary this is called a Channel Compare with a COM loop and connected loop units In a network type a there is only one Channel i e Channel_1 No Channel has to be added Channel_1 is default In a network type b there is one Channel on each side of the Router i e Channel_1 and Channel_2 Channel_2 has to be added In a network type c there is one Channel for each Router and one Channel for the Backbone net between the Routers i e Channel_1 Channel_2 Channel_3 and so on Required numbers of Channels have to be added How to add Channels to the Project see chapter Add a Channel page 18 Routers After the Channels have been added the Routers have to be added to the Project if it is a type b or c network See chapter Add a Router page 19 Use Channel_2 for the Backbone net EBL512 EBL512 G3 units nodes After the Channels and the Routers have been added the EBL512 EBLS512 G3 units nodes have to be added to the Project see chapter Add a Unit page 23 7 Tn a redundant networ

Download Pdf Manuals

image

Related Search

Related Contents

CARDIO-M ECG  Manual de uso  Samsung U4 Инструкция по использованию  Manuel de l`utilisateur  Kodak Auto-Focus Camera User's Manual  Stand construction and safety at the Helsinki Fair  Oster 137299 User's Manual  Empleo y Cuidado - Manuales de Mecánica  UC75 / UC75-MC - Real time controller for multi  Download_[PDF:2.54MB]  