1.    46    OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Supplement       Konformitatserklarung  declaration of conformity  Declaration de conformite   IEC 61508   IEC 61511    KROHNE GAS  Les Ors  26103 ROMANS    France    erkl  rt als Hersteller  dass die Vibrationsgrenzschalter  declares as manufacturer  that the vibrating level switches  d  clare en tant que fabricant que les d  tecteurs vibrants    OPTISWITCH 3100 C  3200 C  3300 C  mit   with   avec VB60C     R    T    N    Z  Ex     entsprechend der IEC 61508 f  r den Einsatz in sicherheitsinstrumentierten Systemen  geeignet sind  Die Sicherheitstechnische Kennzahlen sowie die Sicherheitshinweise im  Safety Manual sind zu beachten    siehe entsprechende Batriebsanleitung  Kapitel    Funktionale Sicherheit      according to IEC 61508 are suitable for safety instrumented systems  SIS   The safety  related characteristics as well as the instructions of the safety manual must be considered    see corresponding operating instruction  chapter    Functional Safety      conviennent    une utilisation dans les syst  mes de s  curit   instrument  s suivant la norme  IEC 61508  Les caract  nstiques techniques relatives a la s  curit   ainsi que les consignes de  s  curit   stipul  es dans le Safety Manual sont 4 respecter    voir la notice technique de mise en service au chapitre S  curit   fonctionnelle        Romans  21 10 2005  KROHNE GAS    G  aa She yh  Dr  Flarian Stengele  Geschaftsfihrer    Managing
2.    with NAMUR output    Supplement    51    Subject to change without notice    31358 EN 051207    
3.   Exchange instrument or return it for repair    7 3 Exchanging the electronics    In general  all oscillators of series VB60 can be interchanged  If  you want to use an oscillator with a different signal output  you  can download the corresponding operating instructions man   ual from our homepage under Downloads     opened if there is no explosive atmosphere present     es With EExd instruments  the housing cover must only be    Proceed as follows     1    2  3  4  5    Switch off power supply   Unscrew the housing cover   Lift the opening levers of the terminals with a screwdriver  Pull the connection cables out of the terminals    Loosen the two screws with a Phillips screwdriver  size 1     OPTISWITCH 3300 C   with NAMUR output 27    Maintenance and fault rectification    28    ie                Fig     1    15  Loosen the screws  Electronics module    2 Screws  2 pcs     6 Remove the old oscillator   7 Compare the new oscillator with the old one  The type label  of the oscillator must correspond to that of the old  oscillator  This applies particularly to instruments used in  hazardous areas    8 Compare the settings of the two oscillators  Set the  adjustment elements of the new oscillator to the settings of  the old oscillator    Information     Make sure that the housing is not rotated during the electronics  exchange  Otherwise the plug may be in a different position  later     9    10    11    12    13    14    15    Insert the oscillator carefully  Make sure that 
4.   option                50  C 50  C 100  C 10 200 250  C    58  F   122  F   212  F   302  F   392  F   482  F              Fig  18  Ambient temperature   Product temperature  1 Product temperature   2 Ambient temperature   3 Temperature range with temperature adapter    Density    40 OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207        Standard        adjustable    Electromechanical data    Cable entry plug        Single chamber housing    Spring loaded terminals    Adjustment elements    Mode switch      Min         max     Potentiometer for switching point adap   tation  Simulation key    Voltage supply    Supply voltage  standard characteris   tics    Open circuit voltage   Short circuit current    Electrical protective measures    Protection  Overvoltage category  Protection class    Supplement   gt 0 02 g cm    gt 0 0007 Ibs in       gt 0 008 g cm    gt 0 0003 Ibs in      e 1xcable entry M20x1 5  cable g 5     9 mm    1x blind stopper M20x1 5   or    e 1x closing cap 12 NPT  1x blind stopper  Yo NPT   or     e 1x plug  depending on the version   1x blind  stopper M20x1 5    for wire cross section up to 1 5 mm   0 0023 in      rising characteristics  High current when im   mersed     falling characteristics  Low current when im   mersed     0 02     0 1 g cm   0 0007     0 036 Ibs in      simulation of a line break between sensor and  processing unit    for connection to an amplifier acc  to NAMUR  IEC 60947 5 6  approx  8 2 V   Uo approx  8 2 V   l
5.  Director  Directeur g  n  ral          Fig  22  SIL declaration of conformity    OPTISWITCH 3300 C   with NAMUR output    47    Supplement    CE declaration of conformity          CE    Konformit  tserkl  rung    Declaration of conformity  D  claration de conformit      KROHNE    Krohne SAS   Les Ors BEA  F 26103 Romans Cedex    erkl  rt in alleiniger Verantwortung  daf  das Produkt   declare under  our sole responsibility that our product   d  clare sous sa seule  responsabilit   que le produit    OPTISWITCH 3100 C  OPTISWITCH 3200 C  OPTISWITCH 3300 C  mit NAMUR Ausgang   with NAMUR output    avec sortie NAMUR  VB60N     auf das sich diese Erkl  rung bezieht  mit den folgenden Normen     bereinstimmt   to which this declaration relates is in conformity   with the following standards   auquel se refere cette d  claration  est conforme aux normes    Emission   Emission   Emission     EN 61326   2004 Klasse B  Immission   Susceptibility   Immission     EN 61326   2004 einschlie  lich Anhang A  EN 61010   1   2002    gemal den Bestimmungen der Richtlinien   following the provision  of Directives   conform  ment aux dispositions des Directives    73 23 EWG  89 336 EWG    08 11 2005    Fig  23  CE declaration of conformity    48    OPTISWITCH 3300 C   with NAMUR output    ZOGLSO NA 8G   ELE    31358 EN 051207    OPTISWITCH 3300 C   with NAMUR output    Supplement    49    Supplement    50    OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    OPTISWITCH 3300 C
6.  Hardware  fault toler   ance    60   up to  lt 90   SIL1 SIL2    90   up to  lt 99   SIL2 SIL3       9 2 Planning    The measuring system must be used acc  to the  application   The application specific limits must be maintained and the  specifications must not be exceeded    Acc  to the specifications in the operating instructions  manual  the current load of the output circuits must be  within the limits    It must be used only in products to which the materials of  the vibrating system are sufficiently chemically resistant     Note the following items for use as dry run protection system     Avoid buildup on the vibrating system  possibly smaller  proof test intervals   Avoid granulation size of the product  gt  15 mm    For the implementation of FMEDA  Failure Mode  Effects and  Diagnostics Analysis  the following assumptions form the  basis     Failure rates are constant  wear of the mechanical parts is  not taken into account   Failure rates of external power supplies are not included  Multiple errors are not taken into account   The average ambient temperature during the operating  time is  40  C  104  F    The environmental conditions correspond to an average  industrial environment   The service lift of the components is between 8 to 12 years   IEC 61508 2  7 4 7 4  remark 3    The processing unit can interpret  fail low  and  fail high   failures as interferences and output a suitable fault signal    OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 0512
7.  information    Due to agitators  vibrations or similar  the level switch can be  subjected to strong lateral forces  For this reason  do not use  an overly long extension tube for OPTISWITCH 3300 C  but  check if you can mount a short level switch on the side of the  vessel in horizontal position     Extreme vibration caused by the process or the equipment  e   g  agitators or turbulence in the vessel e g  from fluidization   can cause the extension tube of OPTISWITCH 3300 C to  vibrate in resonance  This leads to increased stress on the  upper weld joint  Should a longer tube version be necessary   you can provide a suitable support or guy directly above the  tuning fork to secure the extension tube     This measure applies particularly to applications in Ex areas   Make sure that the tube is not subjected to bending forces  through this measure     If OPTISWITCH 3300 C is mounted in the filling stream   unwanted switching signals may be generated  Mount OPTI   SWITCH 3300 C at a location in the vessel where no disturbing  influence from e g  filling openings  agitators  etc  can occur     This applies particularly to instrument types with long  extension tube     OPTISWITCH 3300 C   with NAMUR output 11    Mounting    Lock fitting    Socket    Material cone    12       7 OUO S  OVS eN                                        Fig  3  Inflowing material    OPTISWITCH 3300 C can be mounted with a lock fitting for  height adjustment  Take note of the pressure information of the 
8.  lock fitting     The vibrating element should protrude into the vessel to avoid  buildup  For that reason  avoid using mounting bosses for  flanges and screwed fittings  This applies particularly to use  with adhesive products     Material cones can form in solids silos which can change the  switching point  Please keep this in mind when installing the  sensor in the vessel  We recommend selecting an installation  location where the tuning fork detects an average value of the  material cone     The vibrating element must also be mounted at a location that  takes the arrangement of the filling and emptying apertures  into account     To compensate measurement errors in cylindrical vessels  caused by the material cone  the sensor must be mounted ata  distance of d 6 from the vessel wall     OPTISWITCH 3300 C   with NAMUR output    LOcLSO NA 8SEL       31358 EN 051207                            ole                            Mounting          Fig  4  Filling and emptying centered    OPTISWITCH 3300 C   with NAMUR output    13    Mounting    Flow    14                         Fig  5  Filling in the center  emptying laterally  1 OPTISWITCH 3300 C   2 Emptying opening   3 Filling opening    If there is movement within the product  the tuning fork of  OPTISWITCH 3300 C should be mounted in such a way that  the surfaces of the fork are parallel to the product movement     OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Baffle protection against fall   ing rock
9.  that  the tuning fork is at the height of the requested switching point     Use the recommended cable  see chapter  Connecting to  power supply   and tighten the cable gland     You can give your OPTISWITCH 3300 C additional protection  against moisture penetration by leading the connection cable  downward in front of the cable entry  Rain and condensation  water can thus drain off  This applies mainly to mounting  outdoors  in areas where moisture is expected  e g  by  cleaning processes  or on cooled or heated vessels                 Fig  2  Measures against moisture penetration    Do not hold OPTISWITCH 3300 C on the vibrating element   Especially with flange and tube versions  the sensor can be  damaged by the weight of the instrument     Remove the protective cover just before mounting     The process fitting must be sealed if there is gauge or low  pressure in the vessel  Before use  check if the seal material is  resistant against the measured product and the process  temperature     The vibrating level switch is a measuring instrument and must  be treated accordingly  Bending the vibrating element will  destroy the instrument     OPTISWITCH 3300 C   with NAMUR output    ZO LS0 NJ 8GE LE    31358 EN 051207    A    Agitators and fluidization    Inflowing material    2    Mounting    Warning   The housing must not be used for screwing in  Tightening can  cause damages on the locking piston of the housing     To screw in  use the hexagon above the thread     4 2 Mounting
10.  the dangerous failures  Therefore the  stated values in chapter  Safety relevant characteristics  can  deteriorate     The processing unit must correspond to the SIL level of the  measuring chain     The adjustment of the mode on the NAMUR amplifier acc  to  IEC 60947 5 6 must be selected in such a way that its  switching condition takes on safe condition if there is an input  current  lt  1 2 mA     9 3 Setup    The prevailing plant conditions influence the safety of the  measuring system  Therefore note the mounting and installa   tion instructions of the appropriate operating instructions  manual  Mainly important is the correct setting of the mode   min  max       OPTISWITCH 3300 C   with NAMUR output    Z0 LONG    31358 EN 051207    Functional safety    9 4 Reaction during operation and in case of  failure    e The adjustment elements must not be modified during  operation    e Incase of modifications during operation  you have to take  note of the safety functions    e Occurring fault signals are described in the appropriate  operating instructions manual    e Incase of detected failures or fault signals  the entire  measuring system must be switched out of service and the  process held in a safe condition by means of other  measures    e An electronics exchange is easily possible and described  in the operating instructions manual    e  f due to the detected failure  the electronics or the  complete sensor is interchanged  the manufacturer must  be informed  incl  a f
11. 0008 Ibs in   can be measured  It is possible to adapt the  instrument for products with lower density  gt 0 008 g cm      gt 0 0003 Ibs in         OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Product description    On the electronics module you will find the following indicating  and adjustment elements     signal lamp for indication of the switching condition  yellow   potentiometer for adaptation to the product density   Mode switch to select the switching condition  reverse  characteristics    Simulation key    3 4 Storage and transport    Packaging Your instrument was protected by packaging during transport   Its capacity to handle normal loads during transport is assured  by a test acc  to DIN 55439     The packaging of standard instruments consists of environ   ment friendly  recyclable cardboard  In addition  the sensor is  provided with a protective cover of cardboard  For special  versions PE foam or PE foil is also used  Dispose of the  packaging material via specialised recycling companies     Storage and transport tem  e  perature    Storage and transport temperature see  Supplement      Technical data   Ambient conditions     Relative humidity 20     85      OPTISWITCH 3300 C   with NAMUR output 9    Mounting    Switching point    Moisture    Transport    Pressure Vacuum    Handling    10    4 Mounting  4 1 General instructions    In general  OPTISWITCH 3300 C can be mounted in any  position  The instrument must be mounted in such a way
12. 07    Low demand mode    High demand mode    Safe condition    Functional safety    e The communication via the IIC bus interface is only used  for default scaling and for service purposes    e The repair time  exchange of the measuring system  after a  fail safe error is eight hours  MTTR   8 h    e Inthe mode with the lowest demand rate  the reaction time  of a connected control and processing unit to dangerous  detectable errors is max  1 hour     If the demand rate is only once a year  then the measuring  system can be used as safety relevant subsystem in  low  demand mode   IEC 61508 4  3 5 12      If the ratio of the internal diagnostics test rate of the measuring  system to the demand rate exceeds the value 100  the  measuring system can be treated in the way it is executing a  safety function in the mode with low demand rate  IEC 61508 2   7 4 3 2 5      Corresponding characteristics is the value PFDa    average  Probability of dangerous Failure on Demand   It is dependent  on the test interval Tproor between the function tests of the  protective function     For number values see paragraph  Safety technical charac   teristics      If the  low demand rate  does not apply  the measuring system  as safety relevant part system in  high demand mode  should  be used  IEC 61508 4  3 5 12      The fault tolerance time of the complete system must be higher  than the sum of the reaction times or the diagnostics test  periods of all components in the safety chain     Correspond
13. 300 C is a sensor for level detection     Detailed information on the application range of OPTISWITCH  3300 C is available in chapter  Product description      2 3 Warning about misuse    Inappropriate or incorrect use of the instrument can give rise to  application specific hazards  e g  vessel overfill or damage to  system components through incorrect mounting or adjustment     2 4 General safety instructions    OPTISWITCH 3300 C is a high tech instrument requiring the  strict observance of standard regulations and guidelines  The  user must take note of the safety instructions in this operating  instructions manual  the country specific installation standards   e g  the VDE regulations in Germany  as well as all prevailing  safety regulations and accident prevention rules     2 5 CE conformity    OPTISWITCH 3300 C is in CE conformity with EMC  89 336   EWG   fulfils the NAMUR recommendation NE 21 and is in CE  conformity with NSR  73 23 EWG      Conformity has been judged acc  to the following standards     e EMC       Emission EN 61326  1997  class B       Susceptibility EN 61326  1997 A1  1998    e LVD  EN 61010 1  2001    OPTISWITCH 3300 C   with NAMUR output 5    For your safety    2 6 SIL conformity    OPTISWITCH 3300 C fulfills the requirements for functional  safety acc  to IEC 61508  You will find further information in  chapter  Functional safety      2 7 Safety information for Ex areas    Please note the Ex specific safety information for installation  and operat
14. Asd   Asu   DCp Diagnosis coverage DCD   Agd  Ada   Adu        OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Dry run protection Mode switch is set to  min     36 FIT safe detected failure  155 FIT safe undetected failure    dangerous detected failure   dangerous undetected failure   Safe Failure Fraction   Diagnosis coverage DCs   Agq  Aga   Agu   Diagnosis coverage DCD   Agd  Ada   Adu        General data  TDiagnosis Diagnosis test period 100 sec  MTBF   MTTF   MTTR 1 56x10   h    max  useful life of the measuring system for the safety approx  10 years  function       Single channel architecture    Architecture 1001D   Overfill SIL2  Safety Integrity Level     protection  HFT   0  Hardware Fault Tolerance     Mode switch is set to  max     PFDavg  Tproof   1 year  lt  0 020 x 10    Tproot   5 years  lt  0 100 x 107  Tproor   10 years  lt  0 200 x 107    PFH  1 h   lt  0 047 x 10   h    Architecture 1001D   Dry run SIL2  Safety Integrity Level   protection       HFT   0  Hardware Fault Tolerance     Mode switch is set to  min     PFDavg  Tproor   1 year  lt  0 023 x 107  Tproof   5 years  lt  0 114 x 107       Tproor   10 years  lt  0 228 x 10      PFH  1 h   lt  0 052 x 10    h       OPTISWITCH 3300 C   with NAMUR output 37    Functional safety    Time dependent process of  PFDavg    Architecture 1002    38    The time dependent process of PFDayg reacts in the time  period up to 10 years virtually linear to the operating time  The  above values only 
15. Fault signal    Necessary processing system    Supplement    316L  316L  Klingersil C 4400  316L  316L    plastic PBT  Polyester   Alu die casting pow   der coated  stainless steel 316L    NBR  stainless steel housing   silicone  Alu   plastic housing     316L    1500 g  53 oz   1950 g  69 oz   2300 g  81 oz   approx  2000 g m  21 5 oz ft     0 3   6m 1    20 ft     two wire NAMUR output     gt  2 2 mA uncovered  lt  1 0 mA covered   lt  1 0 mA uncovered  gt  2 2 mA covered   lt  1 0 mA    NAMUR processing system acc  to IEC  60947 5 6  EN 50 227 DIN 19234     Modes  NAMUR output adjustable to falling or rising characteristics     OPTISWITCH 3300 C   with NAMUR output    Min     max     rising characteristics  High current when im   mersed     falling characteristics  Low current when im   mersed     39    Supplement    Ambient conditions    Ambient temperature on the housing  40      80  C   40      176  F   Storage and transport temperature  40      80  C   40      176  F     Process conditions    Parameter level of solids  Process pressure  1     16 bar   100     1600 kPa   14 5     232 psi        50  C OC 50  C 100  C 150  C 200  C 250  C    58  F   32  F   122  F   212  F   302  F   392  F   482  F           Fig  17  Process pressure   Product temperature  1 Product temperature  2 Process pressure    OPTISWITCH 3300 C of 316L  50      150  C   58      302  F   Process temperature  thread or flange  50      250  C   58      482  F   temperature  with temperature adapter  
16. Operating Instructions    OPTISWITCH 3300 C  with NAMUR output       Variable area flowmeters   Vortex flowmeters   Flow controllers   Electromagnetic flowmeters  Ultrasonic flowmeters   Mass flowmeters   Level measuring instruments  Communications engineering  Engineering systems  amp  solutions    Switches  counters  displays and recorders    Heat metering  Pressure and temperature       Contents    Contents  1 About this document  11  FUNCION AE OE rte OE e 5  12 Target group             0 2 eee 5  13 Symbolism use  5  2 For your safety  2 1 Authorised personnel  6  2 2 Appropriate use naaa aaaea 6  23 Warning about misuse                    6  2 4 General safety instructions                 6  2 5 CE confOFMItY        SES SE SS Se aee 6  2 6 SIL confOrmitYy        EE EES SEE SE Se 7  2 7 Safety information for Ex areas              7  3 Product description  3 1 Configuration        EES SS SE Se See 8  3 2 Principle of operation                     8  3 3 Adjustment       SES SS eee eee 9  3 4 Storage and transport  10  4 Mounting  4 1 General instructions                  05  11  4 2 Mounting information                 46  12  5 Connecting to power supply  5 1 Preparing the connection                  18  5 2 Connection procedure          uaa aaa 18  5 3 Wiring plans  signal chamber housing         19  6 Setup  6 1 General  22  6 2 Adjustment elements                  0  22  6 3 Function chat    23  6 4 Recurring function test                06  24  7 Maintenance and fau
17. UR output 3    About this document    EI Pme    d    1 About this document    1 1 Function    This operating instructions manual has all the information you  need for duick setup and safe operation of OPTISWITCH 3300  C  Please read this manual before you start setup     1 2 Target group    This operating instructions manual is directed to trained  personnel  The contents of this manual should be made  available to these personnel and put into practice by them     1 3 Symbolism used    Information  tip  note  This symbol indicates helpful additional information     Caution  warning  danger   This symbol informs you of a dangerous situation that could  occur  Ignoring this cautionary note can impair the person and   or the instrument     Ex applications  This symbol indicates special instructions for Ex applications     List  The dot set in front indicates a list with no implied sequence     Action  This arrow indicates a single action     Sequence  Numbers set in front indicate successive steps in a procedure     OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    For your safety    2 For your safety    2 1 Authorised personnel    All operations described in this operating instructions manual  must be carried out only by trained and specialist personnel  authorised by the operator  For safety and warranty reasons   any internal work on the instruments must be carried out only  by personnel authorised by the manufacturer     2 2 Appropriate use  OPTISWITCH 3
18. apply to the Tproor interval  after which a  recurring function test must be carried out                       1 5 10 Tproot          Fig  16  Time dependent process of PFDavg     1 PFDayg   0   2 PFDayvg after 1 year   3  PFDavg after 5 years   4 PFDayg after 10 years    Multiple channel architecture  SIL3  Safety Integrity Level     HFT   1  Hardware Fault Tolerance        If the measuring instrument is used in double channel  architecture  the safety relevant characteristics of the selected  structure of the measuring chain must be calculated specifi   cally for the selected application acc  to the above failure rates    A Common Cause Factor must be taken into account     The measuring system can be used in a diversitary redundant  as well as a homogeneous redundant structure     1  Numbers see in the above charts     OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    10 Supplement    10 1 Technical data    General data  Material 316L corresponds to 1 4404 or 1 4435    Materials  wetted parts    Process fitting   Thread   Process fitting   Flange   Process seal   Tuning fork   Extension tube   43 mm    1 7 in     Materials  non wetted parts    Housing    Seal ring between housing and  housing cover    Ground terminal    Weights    with plastic housing   with Aluminium housing  with stainless steel housing  Extension tube    Sensor length    Output variable    Output  Current consumption    Falling characteristics  max    Rising characteristics  min    
19. ase of    OPTISWITCH 3300 C   with NAMUR output 21    Setup    Characteristics reversal  2     Simulation key  3     Signal lamp  6     22    very light solids  turn the potentiometer completely to the left      0 008 g cm  or  gt 0 0003 Ibs in    By doing this  OPTISWITCH  3300 C will be more sensitive and light solids can be detected  more reliably     For instruments detecting solids in water  these values are not  applicable  The potentiometer is preset and must not be  changed     The characteristics reversal can be carried out with the DIL  switch  You can choose between falling characteristics  switch  position max   and rising characteristics  Switch position min     You can have the requested current outputted     Modes    e min    rising characteristic curve  High current when  immersed   e max    falling characteristics  Low current when immersed     The NAMUR output can be switched over to falling or rising  characteristics  See also Function chart      The simulation key is located in a recess on the upper side of  the oscillator  Push the simulation key with a suitable object   screwdriver  pen  etc       When the key is pushed  line break between sensor and  processing unit is simulated  The signal lamp on the sensor  extinguishes  The measuring system must signal failure and  take on safe condition when the key is pushed     Keep in mind that the connected instruments are activated  during operation  By doing this  you can check the correct  function of the me
20. asuring system     Control lamp  LED  for indication of the switching condition     e yellow   High current  gt   2 2 mA  e dark   Low current  lt   1 mA  e yellow  flashing    Failure  lt   1 mA    6 3 Function chart    OPTISWITCH 3300 C level switch  The following chart provides an overview of the switching  conditions depending on the adjusted mode and level     OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    SIL    Setup    Note    Select the mode setting on the NAMUR amplifier in such a way  that the switching output takes on safe condition if there is a  fault signal  I  lt   1 0 mA      Level Signal current   Control lamp  Sensor    Falling characteris   gt   2 2 MA  tics max     Falling characteris   tics max                       Rising characteris   tics min        Rising characteris   tics min              Failure    flashes       6 4 Recurring function test  Acc  to IEC 61508     In mode A  overfill protection   OPTISWITCH 3300 C is  qualified for use in measuring chains of stage SIL2 acc  to IEC  61508  redundant  stage SIL3      The following instrument combinations meet the requirements  acc  to SIL     OPTISWITCH 3300 C  e Oscillator VB E60N    OPTISWITCH 3300 C   with NAMUR output 23    Setup    Recurring function test    Simulation key on the elec   tronics module    24    The recurring function test acc  to IEC 61508 can be carried  out by pushing the simulation key on the electronics module or  by briefly   gt  2 seconds  interruptin
21. ault description      9 5 Recurring function test    The recurring function test serves to reveal potential danger   ous errors that are otherwise not discernible  The function of  the measuring system must be checked at adequate intervals     The operator is responsible for choosing the type of test and  the intervals in the stated time frame  The time frame depends  on the PFDayg value acc  to the chart and diagram in section   Safety related characteristics      In high demand rate  no recurring function test is arranged in  IEC 61508  A proof of the functional efficiency is seen in the  more frequent demand of the measuring system  In double  channel architectures it is useful to proof the redundancy by  recurring function tests in appropriate intervals     The test must be carried out in a way that verifies the flawless  operation of the safety functions in conjunction with all system  components     This is ensured by a controlled reaching of the response height  during filling  If filling up to the response height is not possible   then a response of the measuring system must be triggered by  a suitable simulation of the level or the physical effect     The methods and procedures used during the tests must be  stated and their suitability must be specified  The tests must be  documented     OPTISWITCH 3300 C   with NAMUR output 35    Functional safety    Recurring function test when  using the measuring system  as overfill protection    Overfill protection    36    If 
22. e seal  ring must completely encircle the cable    10 Screw the housing cover back on    The electrical connection is finished        A   gt              Fig  8  Connection steps 5 and 6    5 3 Wiring plans  signal chamber housing    The following illustrations apply to the non Ex as well as to the  EEx d version     OPTISWITCH 3300 C   with NAMUR output    oO    ZO SO NA 8GE     31358 EN 051207    Housing overview    Electronics and connection  compartment  single chamber  housing    Wiring plan    Connecting to power supply                Fig  9  Material versions  single chamber housing  Plastic   Aluminium   Stainless steel   Filter element for pressure compensation    KON A          VB60N     EI  1234  min  NAMUR IEC 60947 5 6            X    Simulation          Fig  10  Electronics and connection compartment  single chamber housing  Potentiometer for switching point adaptation   DIL switch for characteristics reversal   Simulation key   Ground terminal   Terminals   Control lamp    CO D P Go h   A    For connection to an amplifier acc  to NAMUR  IEC 60947 5 6   EN 50227   For further information see Technical data in the  Supplement     Further information you will find in the Technical data in the  Supplement  Ex technical data are specified in the attached  safety instructions manual     OPTISWITCH 3300 C   with NAMUR output 19    Connecting to power supply    20          Fig  11  Wiring plan  single chamber housing    External simulation key       In addition to the 
23. ed     d OPTISWITCH 3300 C signals  covered  when the vibrating  element is not submerged  overfill protection     d OPTISWITCH 3300 C signals  uncovered  when the  vibrating element is submerged  dry run protection       Supply voltage too low   gt  Check the power supply    Electronics defective     gt  Push the characteristics reversal switch  If the instru   ment then changes the mode  the instrument may be  mechanically damaged  Should the switching function  in the correct mode still be faulty  return the instrument  for repair      gt  Push the characteristics reversal switch  If the instru   ment then does not change the mode  the oscillator  may be defective  Exchange the oscillator      gt  Check if there is buildup on the vibrating element  and if  SO  remove it       Unfavourable installation location     gt  Mount the instrument at a location where no dead  zones or mounds can form in the vessel     26 OPTISWITCH 3300 C   with NAMUR output    Z0 LONG    31358 EN 051207    Maintenance and fault rectification     gt  Check if the vibrating element is covered by buildup on  the socket       Wrong characteristics selected     gt  Set the correct characteristics on the characteristics  reversal switch  overfill protection  dry run protection    Wiring should be carried out acc  to the quiescent  current principle    Signal lamp flashes yellow      Failure on the electronics     gt  Exchanging the electronics    Signal lamp flashes yellow    instrument defective     gt
24. en exposed to strong external vibration or  changing products     Solid detection in water   If OPTISWITCH 3300 C was ordered for solid detection in  water  the tuning fork is set to the density of water  In air or if  immersed in water  density  1 g cm     0 036 Ibs in   OPTI   SWITCH 3300 C signals uncovered  Only if the vibrating  element is also covered with solids  e g  sand  sludge  gravel  etc   will the sensor signal covered     Fault monitoring  The electronics of OPTISWITCH 3300 C continuously mon   itors the following criteria     e Correct vibrating frequency  e Line break to the piezo drive    If one of these faults is detected  the electronics signals it via a  defined current to the signal conditioning instrument  The  connection cable to the vibrating element is also monitored     The tuning fork is piezoelectrically energised and vibrates at its  mechanical resonance frequency of approx  150 Hz  When the  tuning fork is submerged in the product  the vibrating  amplitude changes  This change is detected by the integrated  oscillator and converted into a switching command     OPTISWITCH 3300 C with NAMUR electronics can be  connected to different NAMUR amplifiers depending to your  requirements  The specifications for NAMUR amplifiers are  available in the Technical data     The exact range of the power supply is stated in the Technical  data in the Supplement     3 3 Adjustment    3    With the factory setting  products with a density of  gt 0 02 g cm    gt 0 
25. es which meet the specific requirements of  the safety technology  e g      e Mode  max  for overfill protection   e Mode  min  for dry run protection   The measuring system is qualified in both modes to meet the  following requirement degree acc  to IEC 61508 2    e SIL2 with architecture 1001D  single channel    e SIL3 with architecture 1002D  double channel redundant     With a special factory setting  the measuring system is also  suitable for detection of solids in water  See operating  instructions manual      The safety function of this measuring system is the detection  and signalling of the condition of the vibration element  The  safe condition depends on the mode       e In mode  max   condition  covered   e In mode  min   condition  Uncovered     e IEC 61508 1   2   4      Functional safety of electrical electronic programmable  electronic systems    The failure limit values for a safety function  depending on the  SIL class  of IEC 61508 1  7 6 2     Safety integrity level   Low demand mode High demand mode    PFDavg     gt  10   up to  lt 10   gt  10   up to 108     gt  10  up to  lt 10    gt  10   up to  lt 107        gt  10   up to  lt 107  gt  10   up to  lt 10       gt  10   up to 107  gt  10   up to  lt 10      OPTISWITCH 3300 C   with NAMUR output 31    Functional safety    General instructions and re   strictions    Assumptions    32    Safety integrity of the hardware for safety relating subsystems  of type B  IEC 61508 2  7 4 3     Safe failure fraction
26. g the cable to the sensor   The correct sequence of the switching conditions must be  monitored on the switch amplifier as well as on the connected  systems  Neither must the sensor be removed nor a response  triggered by filling the vessel  This applies to OPTISWITCH  3300 C with NAMUR oscillator VB E60N     You can carry out the function test with the outputted current  values also directly with a safety PLC or a process control  system     In applications in conjunction with the NAMUR electronics  module VB E6ON  a function test can be carried out  Hence the  integration time must be set to 0 5 s  OPTISWITCH 3300 C  has an integrated simulation key  The simulation key is  lowered on the electronics module  Push the simulation key for   gt  2 seconds     If OPTISWITCH 3300 C is connected to an SPLC  you have to  interrupt the connection cable to the sensor for  gt  2 seconds     After releasing the simulation key or briefly interrupting the  connection cable to the sensor  you can check the complete  measuring system on correct function  A switching procedure  is simulated during the test           VmA  2 2 ere D  1 ee 2   3 45 t s          Fig  14  Flow chart of the function test  1 Full signal  2 Empty signal    Check if the switching conditions occur in the correct  sequence and the stated time period  If this is not the case   there is a fault in the measuring system  Keep in mind that    OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Test proced
27. ing characteristics is the value PFH  failure rate      For number values see paragraph  Safety technical charac   teristics      The safe condition depends on the mode and is stated in the  following chart     The characteristics min max must be set acc  to the mode  see  Function chart      N Overfill protection Dry run protection  Safe condition  uncovered     Output current in safe 0 4     1 MA  condition       OPTISWITCH 3300 C   with NAMUR output 33    Functional safety    Fault description    Configuration of the process   ing unit    Mounting and installation    34    Overfill protection Dry run protection    Interference current  Fail  Low     Interference current  Fail  High        A safe failure exists if the measuring system goes to the  defined safe condition without being required by the process or  the interference current outputs  Fail low  or  Fail high      H the internal diagnostics system detects an error  an  interference current of  lt  1 mA will be outputted     A dangerous undetected failure exists if the measuring system  switches neither to the defined safe condition  nor to failure  mode when the process requires it     If the measuring system delivers output currents of  fail low  or   fail high   it can be assumed that there is a failure somewhere     The processing unit must therefore interpret such currents as  failure and output a suitable fault signal     If this is not the case  the appropriate shares of the failure rates  must be assigned to
28. ion in Ex areas  These safety instructions are part of  the operating instructions manual and come with the Ex   approved instruments     OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    3 Product description  3 1 Configuration    Scope of delivery The scope of delivery encompasses     e OPTISWITCH 3300 C level sensor  e Documentation      this operating instructions manual      Supplementary instructions manual  Plug connector for  level sensors    optional      Ex specific safety instructions  with Ex versions   if  necessary further certificates    Components OPTISWITCH 3300 C consists of the following components     e Housing cover  e Housing with electronics  e process fitting with tuning fork    0 OUO 9 1                                        Poe                Fig  1  OPTISWITCH 3300 C   with plastic housing  1 Housing cover    2 Housing with electronics  3 Process fitting          3 2 Principle of operation    Area of application OPTISWITCH 3300 C is a level sensor with tuning fork for level  detection     OPTISWITCH 3300 C   with NAMUR output 7    Product description    Physical principle    Power supply    It is designed for industrial use in all areas of process  technology and is preferably used for bulk solids     Typical applications are overfill and dry run protection  Thanks  to its simple and robust measuring system  OPTISWITCH  3300 C is virtually unaffected by the chemical and physical  properties of the solid     It functions even wh
29. lt rectification  TA DONICE esre ehh eee EE Oe 27  7 2 Fault rectification        n    naaa aaa aaa aaa 27  7 3 Exchanging the electronics                 28  7 4  Instumentrepaif        SEE SEE SES eee 30  8 Dismounting  8 1 Dismounting steps    EN    OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Contents  8 2 Disposal    anaua ae Mew dew w EE DES 31  9 Functional safety  9 1 General  32  9 2 Planning    33  98 DSWD  nak oan eed ee DOE ER DEE N ea Di 35  9 4 Reaction during operation and in case of failure 36  9 5 Recurring function test                 5  36  9 6 Safety related characteristics                37  10 Supplement  10 1 Technical data  40  10 2 Dimensions       EES SE SS eee a 44  10 3 Certificates        cower ER ER oe Row oe eS 47    Supplementary operating instructions manuals    Information    OPTISWITCH 3300 C is available in different versions   Depending on the selected version  supplementary operating  instructions manuals will also be included in the scope of  delivery  The supplementary operating instructions manuals  are listed in section  Product description      Operating instructions manuals for accessories and  replacement parts   Tip    We offer accessories and replacement parts to enable reliable  use and operation of your OPTISWITCH 3300 C  The  corresponding operating instructions manuals are     e Operating instructions manual  Oscillator   e Operating instructions manual  Lock fitting     OPTISWITCH 3300 C   with NAM
30. reverse order     With Ex instruments  the housing cover may only be opened if  there is no explosive atmosphere present     8 2 Disposal    OPTISWITCH 3300 C consists of materials which can  recycled by specialised recycling companies  We have  purposely designed the electronic modules to be easily  separable     WEEE directive 2002 96 EG   This instrument is not subject to the WEEE directive 2002 96   EG and the respective national laws  in Germany  e g   ElektroG   Pass the instrument directly on to a specialised  recycling company or use the municipal collecting points  They  may only be used for privately used products acc  to the  WEEE directive     Correct disposal avoids negative effects to persons and  environment and ensures recycling of useful raw materials     Materials  see  Technical data     If you cannot dispose of the instrument properly  please  contact us about disposal methods or return     OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Validity    Area of application    Safety function    Relevant standards    Safety requirements    Functional safety    9 Functional safety  9 1 General    This safety manual applies to measuring systems consisting of  OPTISWITCH 3300 C vibrating level switches and integrated  oscillator VB6GON  The instrument corresponds to a subsystem  of type B     The sensor software must correspond at least to version 1 00  or higher     The measuring system can be used for level detection of  powders and granul
31. s    Mounting             Fig  6  Orientation of the tuning fork in case of flow  1 Marking with screwed version  2 Direction of flow    In applications such as grit chambers or settling basins for  coarse sediments  the vibrating element must be protected  against damage with a suitable baffle     OPTISWITCH 3300 C   with NAMUR output 15    Mounting    16             Fig  7  Baffle protection against damages    OPTISWITCH 3300 C   with NAMUR output    LOG LONG    31358 EN 051207    Note safety instructions    Take note of safety  instructions for Ex Ex   applications    Select power supply    Select connection cable    Select connection  cable for Ex applica   tions    EI       2    Connecting to power supply    5 Connecting to power supply  5 1 Preparing the connection    Always observe the following safety instructions   e Connect only in the complete absence of line voltage    In hazardous areas you should take note of the appropriate  regulations  conformity and type approval certificates of the  sensors and power supply units     Connect the power supply acc  to the following diagrams  Take  note of the general installation regulations  As a rule  connect  OPTISWITCH 3300 C to vessel ground  PA   or in case of  plastic vessels  to the next ground potential  On the side of the  instrument housing there is a ground terminal between the  cable entries  This connection serves to drain off electrostatic  charges  In Ex applications  the installation regulations for  hazardou
32. s areas must be given priority     The data for power supply are stated in the Technical data in  the Supplement     OPTISWITCH 3300 C is connected with standard cable with  round cross section  An outer cable diameter of 5    9 mm   0 2     0 35 in  ensures the seal effect of the cable entry     If cable with a different diameter or wire cross section is used   exchange the seal or use an appropriate cable connection     In hazardous areas  only use approved cable connections for  OPTISWITCH 3300 C     Take note of the corresponding installation regulations for Ex  applications     5 2 Connection procedure    With Ex instruments  the housing cover may only be opened if  there is no explosive atmosphere present    Proceed as follows    1 Unscrew the housing cover    2 Loosen compression nut of the cable entry    OPTISWITCH 3300 C   with NAMUR output 17    Connecting to power supply    18    3 Remove approx  10 cm  4 in  of the cable mantle  strip  approx  1 cm  0 4 in  insulation from the ends of the  individual wires    4 Insert the cable into the sensor through the cable entry    5 Lift the opening levers of the terminals with a screwdriver   see following illustration     6 Insert the wire ends into the open terminals according to  the wiring plan    7 Press down the opening levers of the terminals  you will  hear the terminal spring closing    8 Check the hold of the wires in the terminals by lightly  pulling on them    9 Tighten the compression nut of the cable entry  th
33. test key on the electronics module  you can  connect an external modulator to start the test procedure   Connect the modulator acc  to the following wiring plan     Terminals 3 and 4 are already bridged     For additional information see  Recurring function test                        Ad    1 2 3 4             Fig  12  Wiring plan   External simulation key    1 NAMUR amplifier  2 Bridge  3 External simulation key    OPTISWITCH 3300 C   with NAMUR output    ZO LONG    31358 EN 051207    Function Configuration    Switching point adaptation  1     Setup    6 Setup    6 1 General    The numbers in brackets refer to the following illustrations     On the electronics module you will find the following indicating  and adjustment elements     Potentiometer for switching point adaptation  1   DIL switch for mode adjustment   min max  2   Simulation key  3    Signal lamp  6     6 2 Adjustment elements          VB60N     m  1234  min X    NAMUR IEC 60947 5 6            Simulation             Fig  13  Oscillator VB 60N   NAMUR output  Potentiometer for switching point adaptation  DIL switch for characteristics reversal  Simulation key   Ground terminal   Terminals   Control lamp    Om D P UNS    You can adapt the switching point to the solid with the  potentiometer  The switching point is preset and covered by a  label  It must only be modified in special cases     The factory setting of the potentiometer of OPTISWITCH 3300  C is mid position   gt 0 02 g cm   or  gt 0 0008 Ibs in    In c
34. the function test proves negative  the entire measuring  system must be switched out of service and the process held  in a safe condition by means of other measures     In the double channel architecture 1002D this applies  separately to both channels     If the measuring system is used as overfill protection  the proof  of the function is ensured by a simple function test which can  be triggered and monitored manually or by a connected control  system     This function test is triggered by interrupting the supply cable  for at least two seconds  then a switch on procedure follows as  described in the operating instructions manual     If the test is carried out this way  make sure that the vibrating  element is not covered     If the evaluation is made by a control system  the correct  sequence of the current change must be checked and  documented     9 6 Safety related characteristics    The failure rates of the electronics and the vibrating system  were determined by an FMEDA acc  to IEC 61508  Basis for  the calculations are component failure rates acc  to SN 29500   All values relate to an average ambient temperature of  40  C   104  F  during operation  The calculations are further based  on the instructions stated in chapter  Planning      Mode switch is set to  max     safe detected failure  1 FIT   failure 10  h   safe undetected failure   Aga dangerous detected failure   Agu dangerous undetected failure    SFF Safe Failure Fraction  DCs Diagnosis coverage DCs   Asa  
35. the plug is in  the correct position     Screw in and tighten the two screws with a Phillips  screwdriver     Insert the wire ends into the open terminals according to  the wiring plan    Close the opening levers of the terminals  you will hear the  terminal spring closing    Check the hold of the wires in the terminals by lightly  pulling on them    Check the tightness of the cable entry  The seal ring must  completely encircle the cable     Screw the housing cover back on    OPTISWITCH 3300 C   with NAMUR output    Z0 LS0 NJ 8GE LE    31358 EN 051207    The electronics exchange is finished     7 4 Instrument repair  If a repair is necessary  please proceed as follows     You can download a return form from our Internet homepage    http   www krohne mar com fileadmin media lounge PDF   Download Specimen_e pdf     By doing this you help us carry out the repair quickly and  without having to call back for needed information     e Print and fill out one form per instrument   e Clean the instrument and pack it damage proof   e Attach the completed form and possibly also a safety data  sheet to the instrument    OPTISWITCH 3300 C   with NAMUR output 29    Dismounting    30    8 Dismounting  8 1 Dismounting steps    Warning    Before dismounting  be aware of dangerous process con   ditions such as e g  pressure in the vessel  high temperatures   corrosive or toxic products etc     Take note of chapters  Mounting  and  Connecting to power  Supply  and carry out the listed steps in 
36. ure    1  Low Current   approx  3 s     2  High Current   approx  1 5 s     3  Return to the actual op   erating condition    Setup    connected instruments are activated during the function test   By doing this  you can check the correct function of the  measuring system      after releasing the simulation key     Sensor cur    Level relay   Level relay   Signal lamp   Signal lamp   Signal    rent    approx  1  mA    mA    amplifier     amplifier     amplifier     amplifier   lamp    overfill pro    dry run overfill pro    dry run sensor  tection protection   tection protection    energized currentless    approx  2 2   currentless   energized  N l 7  pox       Note   Mode B  dry run protection  is not permitted  when used in  meas  chains acc  to IEC 61508     With the stated current values you can carry out the function  test directly via a safety PLC or a process control system     OPTISWITCH 3300 C   with NAMUR output 25    Maintenance and fault rectification    7 Maintenance and fault rectification    7 1 Service    When used as directed in normal operation  OPTISWITCH  3300 C is completely maintenance free     7 2 Fault rectification    OPTISWITCH 3300 C offers maximum reliability  Nevertheless  faults can occur during operation  These may be caused by the  following  e g      e Sensor   e Process   e Power supply   e Signal processing    Fault rectification The first measure is checking the output signal  In many cases   the reasons can be determined and faults rectifi
37. y approx  8 2 mA    IP 66 IP 67  III  Il    2  Depending on the version M12x1  acc  to DIN 43650  Harting  Amphenol   Tuchel  7 8  FF    OPTISWITCH 3300 C   with NAMUR output    41    Supplement    Approvals    ATEX II 1G  1 2G  2G EEx ia IIC T6   ATEX Il 1 2 D IP66 T    ATEX II 1 2G  2G EEx d IIC T6  ATEX II 1 2 D IP66 T 9    3  Deviating data with Ex applications  see separate safety instructions   4  See temperature statements in the safety instructions manual    42 OPTISWITCH 3300 C   with NAMUR output    ZO LONG     KROHNE    Supplement    10 2 Dimensions    OPTISWITCH 3300 C5         69mm   116mm                    69mm  2 23 32    4 916       2 23 32      77mm o 84mm         3 1 32    3 5 16                4 13 32     4 39 64     4 31 64      M20x1 5   Ye NPT    M20x1 5   Yo NPT                         Fig  19  Housing versions   1 Plastic housing   2 Stainless steel housing  3 Aluminium housing    5 All dimensions in mm  inch      31358 EN 051207    OPTISWITCH 3300 C   with NAMUR output 43    Supplement    Ad     1 19 64                  43mm  1 11 16         150mm  5 29 39                     Fig  20  OPTISWITCH 3300 C   Threaded version G1 2A  L   Sensor length  see Technical data    OPTISWITCH 3300 C   with NAMUR output    Z0 LONG    31358 EN 051207    178mm  7 1 64            Fig  21  Temperature adapter    OPTISWITCH 3300 C   with NAMUR output       o 34mm  1 11 39            Supplement       45    Supplement    10 3 Certificates    SIL declaration of conformity 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  RS-230 BGO - Terraplus  入園のしおり - 社会福祉園 宇治福祉園ホームページ  Betriebsanleitung  SERVICE MANUAL - Aire Acondicionado Mitsubishi Electric    Kambrook KSG220 Kitchen Grill User Manual  BEDIENUNGSANLEITUNG  Programmation des zones  313388D, Merkur Displacement Pump, Repair/Parts    Copyright © All rights reserved. 