Home
        Operating Instructions - VEGADIF 65
         Contents
1.            Fig  36  Electronics and connection compartment    1 Spring loaded terminals for voltage supply  2 Ground terminal for connection of the cable screen    3 Cable gland to VEGABAR       36    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          5 Connect to power supply       Terminal compartment  for sensor connection    Wiring plan external  electronics    Switch on phase                                                                                        Fig  37  Connection of the sensor in the housing socket  1 Brown   2 Blue   3 Yellow   4 White   5 Shielding                                                                                           iaie Ce                   Fig  38  Wiring plan external electronics  1 Power supply    5 8 Switch on phase    After connecting VEGADIF 65 to power supply or after a voltage    recurrence  the instrument carries out a self check for approx  30  seconds       Internal check of the electronics       VEGADIF 65 e   4     20 mA    37    5 Connect to power supply       VEIEA          e Indication of the instrument type  the firmware as well as the  sensor TAGs  sensor designation    e Output signal jumps briefly  approx  10 seconds  to the set fault  current    Then the corresponding current is outputted to the cable  the value  corresponds to the actual level as well as the settings already carried  out  e g  factory setting         38    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN
2.           Fig  21  Measurement setup with interface measurement  Min  adjustment with  filing complete with density 0 8  max  adjustment with filling complete with  density 1 0    1 VEGADIF 65       24    VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VaEIEA          4 Mounting       In gases and vapours    In liquids    4 6 Differential pressure measurement     gt  Mount VEGADIF 65 above the measurement loop so that    condensate can drain off in the process cable                                         Fig  22  Measurement setup  differential pressure measurement in gases and  vapours    1    AUN    VEGADIF 65  Three fold valve block  Block valves   E g  filter    Mount VEGADIF 65 below the measurement loop so that the  effective pressure lines are always filled with liquid and gas  bubbles can bubble up to the process line    For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and  sediment        VEGADIF 65 e   4     20 mA    25    4 Mounting             In gases  vapours and  liquids                                                 Fig  23  Measurement setup  flow measurement in liquids    DaKR amp WNH gt      gt     E g  filter   Block valves  VEGADIF 65  Precipitator   Drain valves  Three fold valve block    Mount isolating diaphragm with capillaries on top or laterally on the    pipeline    In vacuum applications  Moun
3.        VEGADIF 65 e   4     20 mA    17    4 Mounting             In open vessels with  effective pressure line                                                    Fig  12  Measurement setup  flow measurement in liquids    Drain valves  Three fold valve block    1 Orifice or impact pressure probe  2 Block valves   3 VEGADIF 65   4 Precipitator   5   6    4 4 Level measurement     gt  Mount VEGADIF 65 below the lower measurement connection so  that the effective pressure lines are always filled with liquid     gt  Minus side is open to the atmospheric pressure       18    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604             In open vessels with  unilateral pressure  transmitter    In closed vessels with  effective pressure lines                                                                                   4 Mounting   gt  For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and  sediment   Patm  min    Pam A  v  x    Fig  13  Measurement setup  level measurement in the open vessel  1 VEGADIF 65  2 Minus side is open to the atmospheric pressure  3 Block valve  4 Precipitator  5 Drain valve   gt  Mount VEGADIF 65 directly to the vessel   gt  Minus side is open to the atmospheric pressure  min   COO     Patm  Fig  14  Measurement setup  level measurement in the open vessel  1 VEGADIF 65  2 Minus side is open to the atmospheri
4.     36236 EN 090604       VEEA       11 Supplement       11 Supplement    11 1 Technical data    General data   Pressure type  Measuring principle  Communication interface    Materials and weights    Differential pressure  Piezoresistive  IC bus    Material 316L corresponds to stainless steel 1 4404 or 1 4435    Materials  wetted parts      Process fitting with lateral flanges      Separating diaphragm        Seal        Closing screws    Internal transmission liquid    Materials  non wetted parts      Electronics housing        External electronics housing        Socket  wall mounting plate external  electronics housing        Seal between housing socket and wall  mounting plate        Seal ring  housing cover        Inspection window in housing cover for  indicating and adjustment module        Screws and nuts for lateral flange        Ground terminal        Connection cable with version IP 68   1 bar        Connection between IP 68 transmitter  and external electronics housing        Type plate support with IP 68 version on  cable    C22 8  316L  Alloy C276    316L  Alloy C 276  Tantalum  Alloy C 276 gold   rhodium coated    FKM  Viton   FKM cleaned from oil and grease   FKM for oxygen application  PTFE  PTFE for  oxygen application  NBR  copper  copper for oxy   gen application    316L    Synthetic oil  Halocarbon oil        Plastic PBT  polyester   Alu die casting powder   coated  316L    plastic PBT  Polyester   plastic PBT  Polyester     TPE  fixed connected    Silicon
5.     VEGADIF 65  Three fold valve block  Precipitator    1  5 Drain valves   2  4 Inlet valves   6  7 Vent valves on VEGADIF 65  A  BBlock valves    Proceed as follows     Fill the vessel to just above the lower tap   Fill measuring system with medium   Close valve 3  Separate plus and minus side   Open valve A and B  Open block valves   Vent plus side  probably empty minus side    Open valve 2 and 4  Discharge medium on the plus side    Briefly open valve 6 and 7  then close again  Fill the plus side  completely with the medium and remove air     Set measurement loop to operation  Now    Valve 3  6 and 7 are closed   Valve 2  4 A and B are open    Then carry out adjustment  see below        62    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          8 Setup       Installation for closed  vessels with steam layer    Prepare the adjustment       G     J                                         Fig  46  Preferred installation for closed vessels with steam overlay    I1 VEGADIF 65   ll Three fold valve block   lll Precipitator   IV Condensate vessel   1  5 Drain valves   2  4 Inlet valves   3 Breather valve   6  7 Vent valves on VEGADIF 65  A  BBlock valves    Proceed as follows     1 Fill the vessel to just above the lower tap  2 Fill measuring system with medium  Open valve A and B  Open block valves    Fill the minus effective pressure line on the height of the  condensation pot    3 For this purpose  vent instrument   Open valve 2 and 4  Discharge me
6.     gt    OK  and confirm with  OK    5 Select the requested application in the selection list  for example   Flow  and confirm with  OK      Unit of measurement In this menu item you select the adjustment unit as well as the unit for  the temperature indication in the display        42 VEGADIF 65 e   4    20 mA    vO9060 N3 9E29E    36236 EN 090604          6 Adjustment with the indicating and adjustment module PLICSCOM       me    To select the adjustment unit  in the example switching over from mbar  to bar   proceed as follows     1 Push the  OK  button in the measured value display  the menu  overview is displayed      gt  Basic adjustment  Display    Diagnostics  Service  Info       2 Confirm the menu  Basic adjustment  with  OK   the menu item   Unit  will be displayed     Unit  Unit of measurement  mbar Y    Temperature unit  cY       3 Activate the selection with  OK  and select  Units of measure   ment with    gt       4 Activate the selection with  OK  and select the requested unit with     gt    in the example bar      5 Confirm with  OK  and move to position correction with    gt     The adjustment unit is thus switched over from mbar to bar     Information   When switching over to adjustment in a height unit  for example for  level measurement   the density also has to be entered     Proceed as follows to enter the density   1 Push the  OK  button in the measured value display  the menu  overview is displayed     2 Confirm the menu  Basic adjustment  with  OK   
7.    gt    e g  to accept the actual measured value    0 0035 bar     Position correction  Accept current measured  value     gt  Accept  Edit       3 Confirm with  OK      Position correction  Offset     0 0035 bar  0 0000 bar       4 Move to min   zero  adjustment with    gt       The current measured value was corrected to 0  the corrective value is  available in the display as offset value with sign reversal        44    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          6 Adjustment with the indicating and adjustment module PLICSCOM       Zero adjustment with  differential pressure    bae    Span adjustment with  differential pressure     T    Min  adjustment with  level    If a known value should be taken over as position correction which is  not the current value  then you have to select the function  Edit  and  enter the requested value     Proceed as follows     1 Edit the bar value in the menu item  zero  with  OK      Zero adjustment  0 00      0 0000 bar  0 0000 bar       2 Set the requested value with     and    gt      3 Confirm with     and move to span adjustment with    gt      For an adjustment with pressure  simply enter the actual measured  value indicated at the bottom of the display     The zero adjustment is finished     Information    The zero adjustment shifts the value of the span adjustment  The span   i e  the difference between these values  however  remains un   changed     Proceed as follows     1 Edit the bar value i
8.   You can give your VEGADIF 65 additional protection against moisture  penetration by leading the connection cable downward in front of the  cable entry  Rain and condensation water can thus drain off  This  applies mainly to outdoor mounting as well as installation in areas  where high humidity is expected  e g  through cleaning processes  or  on cooled or heated vessels     The ventilation for the electronics housing is realised via a filter  element in the vicinity of the cable glands                                                                                            Fig  9  Position of the filter element  Upper row single chamber housing  lower  row double chamber housing    1 Filter element for ventilation of the electronics housing  2 Blind stopper    Information   Make sure that the filter element is always free of buildup during  operation  A high pressure cleaner must not be used for cleaning        14    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEBA          4 Mounting       Effective pressure lines    Vibrations    Temperature limits    Oxygen applications    A    Pure gas applications    You find general recommendations for wiring of effective pressure  lines in DIN 19210  Effective pressure lines for flow systems  or the  corresponding national or international standards  When wiring  effective pressure lines outdoors  keep in mind to use a suitable  antifreeze  e g  by using tube heat tracing  Wire effective pressure  lines with 
9.   gt   and  OK    3 Confirm with  OK  and move to the menu overview with  ESC      For an adjustment with flow  simply enter the actual measured value  indicated at the bottom of the display     The max  adjustment is finished     For level measurement  a linearization is necessary for all vessels in  which the vessel volume does not increase linearly with the level   e g   in a cylindrical or spherical tank   and the indication or output of the   volume is requested     Respective linearisation curves are stored for these vessels  They  indicate the relation between the percentage level and the vessel  volume  By activating the suitable curve  the percentage vessel  volume is displayed correctly     The flow is proportional to the square of the pressure difference on the  orifice or the back pressure probe  To establish a linear relation  a root  extraction is necessary  VEGADIF 65 has this root extraction function   It is selected in the menu item  Linearization curve      Linearisation curve    linear       Enter the requested parameter via the appropriate keys  save your  settings and jump to the next menu item with the    gt   key     In some applications  small flow volumes should not be detected  With  the leak volume suppression  the flow value can be suppressed up to a  certain   value  The limit value is 50    This function is independent of  the selected linearisation function        VEGADIF 65 e   4     20 mA    47    6 Adjustment with the indicating and adjustmen
10.  090604          6 Adjustment with the indicating and adjustment module PLICSCOM       Function Configuration     T    Mount Dismount indicat   ing and adjustment  module    6 Adjustment with the indicating and  adjustment module PLICSCOM    6 1 Short description    The indicating and adjustment module is used for measured value  display  adjustment and diagnosis  It can be mounted in the following  housing versions and instruments     e All sensors of the plics   instrument family  in the single as well as  in the double chamber housing  optionally in the electronics or  connection compartment    e External indicating and adjustment unit VEGADIS 61    Note   You can find detailed information on adjustment in the operating  instructions manual  Indicating and adjustment module      6 2 Insert indicating and adjustment module    The indicating and adjustment module can be inserted into the sensor  and removed again at any time  It is not necessary to interrupt the  power supply     Proceed as follows     1 Unscrew the housing cover    2 Place the indicating and adjustment module in the desired position  on the electronics  you can choose any one of four different  positions   each displaced by 90       3 Press the indicating and adjustment module onto the electronics  and turn it to the right until it snaps in     4 Screw housing cover with inspection window tightly back on  Removal is carried out in reverse order     The indicating and adjustment module is powered by the sens
11.  27  4 8 External housing                       00008 27  4 9 Mounting control                     0 000408 28  5 Connect to power supply  5 1 Prepare the connection               00  000  29  5 2 Connection procedure               0 0000008  30  5 3 Single chamber housing                200048  33  5 4 Double chamber housing                  0045  34  5 5 Double chamber housing Ex d              004  35  5 6 Version IP 66 IP 68  1 bar    n n ananuna anaa 36  5 7 External housing with version IP 68               36  5 8 Switch on phase                 0 00  37  6 Adjustment with the indicating and adjustment module  PLICSCOM  6 1 Short description                       00040  39  6 2 Insert indicating and adjustment module            39  6 3 Adjustment system                     000008 41  2 VEGADIF 65    4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604              T     T    Contents  6 4 Setparameters                      00000408 42  6 5 Menu schematic       aaau uaaa 51  6 6 Saving the parameter adjustment data             55  7 Operating with PACTware and other adjustment programs  7 1 Connect the PC via VEGACONNECT              56  7 2 Parameter adjustment with PACTware             56  7 3 Saving the parameter adjustment data             57  8 Setup  8 1 Select the mode                      0000408 58  8 2 Flow measurement                   0 000008 58  8 3 Level measurement                0000000008  60  8 4 Density and interface measurement               64  8 5 Diff
12.  and possible transit  damage immediately at receipt  Ascertained transit damage or  concealed defects must be appropriately dealt with        Storage Up to the time of installation  the packages must be left closed and  stored according to the orientation and storage markings on the  outside    Unless otherwise indicated  the packages must be stored only under  the following conditions   e Not in the open  e Dry and dust free  e Not exposed to corrosive media  e Protected against solar radiation  e Avoiding mechanical shock and vibration  12 VEGADIF 65    4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604       VEEA       3 Product description       Storage and transport  temperature    e Storage and transport temperature see chapter  Supplement    Technical data   Ambient conditions   e Relative humidity 20     85         VEGADIF 65 e   4     20 mA    13    4 Mounting             Suitability for process  conditions    Moisture    Ventilation    be    4 Mounting  4 1 General instructions    Make sure that all parts of the instrument exposed to the process  in  particular the sensor element  process seal and process fitting  are  suitable for the existing process conditions  These include above all  the process pressure  process temperature as well as the chemical  properties of the medium     You can find the specifications in chapter  Technical data  or on the  type label     Use the recommended cables  see chapter  Connecting to power  supply   and tighten the cable gland   
13.  be saved        VEGADIF 65    4       20 mA    41    6 Adjustment with the indicating and adjustment module PLICSCOM VEIA             6 4 Set parameters    Introduction VEGADIF 65 has general adjustment parameters which are also used  for other measuring principles as well as instrument specific adjust   ment parameters  The general adjustment parameters are described  in the operating instructions manual  Indicating and adjustment  module      The instrument specific adjustment parameters are described in this  chapter     Information    If the adjustment limits of the adjustment parameters are exceeded   the message  Outside parameter limits  appears  The editing  procedure can be aborted with  ESC  or the displayed limit value can  be accepted with  OK      bale    Application VEGADIF 65 can be used for differential pressure  level as well as flow  measurement  The selection is made in the menu item  Application    Depending on the selected application  the adjustment is carried out  as zero span or min  max  adjustment     Proceed as follows to switch over to the application level or flow  measurement     1 Push the  OK  button in the measured value display  the menu  overview is displayed      gt  Basic adjustment  Display    Diagnostics  Service  Info       2 Confirm the menu  Basic adjustment  with  OK      Application    Differential pressure Y       3 Confirm the menu item  Application  with  OK    Warning   AN Note the warning   Output can change      4 Select with
14.  bilateral isolating diaphragm CSB is immediately  ready for operation     The VEGADIF 65 without isolating diaphragm or with unilaterial  isolating diaphragm CSS is ready for operation after opening a  possibly available block valve     Before you adjust VEGADIF 65 without isolating diaphragm or with  unilateral isolating diaphragm  the effective pressure lines must be  cleaned and the instrument filled with the medium     3  Valves 1  3  5  Configuration with 5 valves        60    VEGADIF 65    4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEBA          8 Setup       Installation for open  vessels    Prepare the adjustment          1X    y 3    Patm          NIB                  Fig  44  Preferred installation for open vessels      VEGADIF 65   ll Precipitator   1 Drain valve   6 7 Vent valves on VEGADIF 65  A Block valve    Proceed as follows     1 Fill the vessel to just over the lower tap    2 Fill measuring system with medium   Open valve A  Medium flows in    3 Vent instrument    Briefly open valve 6  then close it  Fill the measuring instrument  completely with the medium and remove air     4 Set measurement loop to operation  Now   Valve A open and valve 6 closed  Then carry out adjustment  see below        VEGADIF 65 e   4     20 mA    61    8 Set up             Installation for closed  vessels    Prepare the adjustment                   eo                      x   J  y             a1   Ax          Fig  45  Preferred installation for closed vessels    l  I  Ml
15.  in    If necessary  clean the differential pressure lines    with gases by  blowing out with compressed air   with liquids by rinsing 2    For this purpose close valve 2 and 4  i e  block the instrument     Then open valve 1 and 5 so that the effective pressure lines blow  out rinse     After cleaning  close valves 1 and 5   Remove air from instrument    Open valves 2 and 4  Medium flows in   Close valve 4  Minus side will be closed   Open valve 3  Equalisation plus and minus side    Briefly open valve 6 and 7  then close again  Fill the measuring  instrument completely with the medium and remove air    Arrangement with 5 valves        VEGADIF 65 e   4     20 mA    59    8 Setup       VEEA          Instructions    4 Carry out a position correction if the following conditions apply  If  the conditions are not fulfilled  then carry out the position  correction after step 6     Conditions   The process cannot be blocked     The pressure extraction positions  A and B  are at the same  geodesic height     5 Put measurement loop into operation   Close valve 3  Separate plus and minus side  Open valve 4  Connect minus side  Now   Valves 1  3  5  6 and 7 are closed    Valves 2 and 4 open  Valves A and B open  if available     6 Carry out position correction  if flow can be blocked  In this case   step 5 is deleted     Then carry out adjustment  see chapter  Set parameters      8 3 Level measurement    For level measurements  the VEGADIF 65 in all versions is used     VEGADIF 65 with
16.  pressure                                                                                                                                         gt  Basic adjustment 1  Display  Diagnostics  Service  Info  Application abel Unit tf Position correction 1 2 Zero 1 3  Unit of measurement Offset CB 000 0       Differential pressure Y bar Y          Temperature unit  0 0035 bar 0 0000 bar  CTY 0 0000 bar 0 0000 bar  Max  adjustment 1 4 Damping TS Linearisation curve 1 6 Sensor TAG led  100 00    amp   gt  linear   T s zj 1s Horizontal cylindrical tank Sensor  0 5000 bar Spherical tank  0 0000 bar User programmable  Basic adjustment flow   gt  Basic adjustment D  Display  Diagnostics  Service  Info  Application 1 1  Unit 11 Position correction 1 2 Min  adjustment 1 3  Unit of measurement Offset    000 0       Flow V    bar        o  Temperature unit  0 0035 bar 0 0000 bar  Ly cY 0 0000 bar 0 0000 bar  Max  adjustment Damping 25  Linearisation curve 1 6 Leak volume suppression 1 7  100 00    gt  linear  m  1s Extracted by root Activated Y  0 5000 bar Bidirectionally linear  0 0000 bar Bidirectionally extracted by root  User programmable  Sensor TAG 1 8     Sensor             VEGADIF 65    4     20 mA 51    6 Adjustment with the indicating and adjustment module PLICSCOM             Basic setting level                                                              gt  Basic adjustment 1   Display  Diagnostics  Service  Info  a ee  Application 11 Unit pel Position correction 1 2 Min  adj
17.  service purposes     The VEGA DTM Collection and PACTware in the licensed  profes   sional version provide suitable tools for systematic project documen   tation and storage        VEGADIF 65 e   4     20 mA    57    8 Setup       VEIEA          Instructions    Installation for gases    8 Set up    8 1 Select the mode  The following modes can be adjusted on VEGADIF 65     e Flow measurement  e Level measurement  e Differential pressure measurement    8 2 Flow measurement    In flow measurement  normally VEGADIF 65 is used without isolating  diaphragm     Before adjusting VEGADIF 65  you have to clean the effective  pressure lines and the instrument must be filled with the medium                                   Fig  42  Preferred installation for gases    I1 VEGADIF 65   ll Three fold valve block   2 4 Inlet valves   3 Breather valve   6 7 Vent valves on VEGADIF 65  A  BBlock valves       58    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEBA          8 Setup       Installation for liquids    Prepare the adjustment                      eee  XA BX  6 7 7  l  Ill     Ill  Xa  2X Xi 5 x                         Y Y          Fig     I    I  Ml  1 5  2 4  3    43  Preferred installation for liquids    VEGADIF 65  Three fold valve block  Precipitator   Drain valves   Inlet valves   Breather valve    6 7 Vent valves on VEGADIF 65  A  BBlock valves    Proceed as follows     Close valve 3  Fill measuring system with medium   Open valves A  B  2  4  Medium flows
18.  so that  condensate can drain off in the process cable   Fig  10  Measurement setup  flow measurement in gases  1 VEGADIF 65  2 Three fold valve block  3 Block valves  4 Orifice or impact pressure probe  In vapours  gt  Mount VEGADIF 65 below the measurement loop   gt  Mount condensate vessels at the same height with the discharge  socket and at the same distance to VEGADIF 65   gt  For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and  sediment    gt  Fill the effective pressure lines to the height of the condensate  vessels before setup  16 VEGADIF 65    4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604          4 Mounting       In liquids                                                    Fig  11  Measurement setup  flow measurement in vapours    NOOA ODA    Condensate vessels   Orifice or impact pressure probe  Block valves   VEGADIF 65   Precipitator   Drain valves   Three fold valve block    Mount VEGADIF 65 below the measurement loop so that the  effective pressure lines are always filled with liquid and gas  bubbles can bubble up to the process line    For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and  sediment     Fill the effective pressure lines to the height of the condensate  vessels before setup
19. 0 15   of the set span       Turn down gt  1 1  0 15   of the set span x TD   100 mbar measuring cell       Turndown 1 1 upto4  1  0 075     0 05    of the set span       Turn down  gt  4 1   0 012   x TD   0 027  of the set span  Measuring cells  gt  500 mbar       Turndown 1 1 upto 15 1  0 075     0 05    of the set span       Turn down  gt  15  1   0 0015   x TD   0 053  of the set span    Reference accuracy   Isolating diaphragm versions    100 mbar measuring cell        Turn down1 1upto4 1  0 075     0 05    of the set span   influence of  the isolating diaphragm      Turn down  gt  4 1   0 012   x TD   0 027  of the set span   influence    of the isolating diaphragm    Measuring cells  gt  500 mbar        Turndown 1 1 upto 15 1  0 075     0 05    of the set span   influence of  the isolating diaphragm      Turn down  gt  15  1   0 0015   x TD   0 053  of the set span      influence of the isolating diaphragm    Influence of the product or ambient temperature    Applies to instruments in basic version with digital signal output  HART  Profibus PA  Foundation  Fieldbus  as well as to instruments with analogue current output 4     20 mA  Specifications refer  to the set span  Turn down  TD    nominal measuring range set span        Temperature range Measuring range Thermal changes of the zero  signal and the output span relat   ing to the adjusted span       10  Incl  non linearity  hysteresis and non repeatability        74 VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    
20. 36236 EN 090604          11 Supplement       Temperature range       Measuring range    Thermal changes of the zero  signal and the output span relat     ing to the adjusted span          VEGADIF 65 e   4     20 mA    75    VEE A Printing date           VEGA Grieshaber KG  Am Hohenstein 113  77761 Schiltach  Germany   Phone  49 7836 50 0  Fax  49 7836 50 201  E mail  info de vega com  www vega com    O CE  amp     All statements concerning scope of delivery  application    practical use and operating conditions of the sensors and   processing systems correspond to the information avail   able at the time of printing        VEGA Grieshaber KG  Schiltach Germany 2009       Subject to change without prior notice 36236 EN 090604    
21. 6236 EN 090604          9 Maintenance and fault rectification       Maintenance    Reaction when malfunc   tions occur    Causes of malfunction    Fault rectification    24 hour service hotline    Checking the 4    20 mA  signal    9 Maintenance and fault rectification  9 1 Maintain    When used in the correct way  no special maintenance is required in  normal operation     In some applications  product buildup on the separating diaphragms  can influence the measuring result  Depending on the sensor and  application  take precautions to ensure that heavy buildup  and  especially a hardening thereof  is avoided     9 2 Remove interferences    The operator of the system is responsible for taken suitable measures  to remove interferences     A maximum of reliability is ensured  Nevertheless  faults can occur  during operation  These may be caused by the following  e g      Sensor   Process   Power supply  Signal processing    The first measures to be taken are to check the output signals as well  as to evaluate the error messages via the indicating and adjustment  module  The procedure is described below  Further comprehensive  diagnostics can be carried out on a PC with the software PACTware  and the suitable DTM  In many cases  the causes can be determined  and faults rectified in this way     However  should these measures not be successful  call the VEGA  service hotline in urgent cases under the phone no   49 1805 858550     The hotline is available to you 7 days a week rou
22. GADIF 65 e   4     20 mA    55       7 Operating with PACTware and other adjustment programs Vela          7 Operating with PACTware and other  adjustment programs    7 1 Connect the PC via VEGACONNECT       VEGACONNECT directly  on the sensor                Fig  41  Connection of the PC via VEGACONNECT directly to the sensor    1 USB cable to the PC  2 VEGACONNECT  3 Sensor    7 2 Parameter adjustment with PACTware    Further setup steps are described in the operating instructions manual   DTM Collection PACTware  attached to each CD and which can also  be downloaded from our homepage  A detailed description is available  in the online help of PACTware and the VEGA DTMs     Note   Keep in mind that for setup of VEGADIF 65  DTM Collection in the  actual version must be used      T    All currently available VEGA DTMs are included as a DTM Collection  on a CD  They can be purchased for a token fee from the responsible  VEGA agency  In addition  the actual PACTware version is also  available on this CD     In addition  this DTM Collection incl  the basic version of PACTware  can be downloaded free of charge from the Internet  Move via www   vega com and  Downloads  to  Software         56 VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604          7 Operating with PACTware and other adjustment programs       7 3 Saving the parameter adjustment data    It is recommended to document or save the parameter adjustment  data  They are hence available for multiple use or
23. ICSCOM       VEIEA          Menu section    Menu item    Reset value       Decimal point indication    8888 8       Diagnostics    Service       Total sum counter    0 0000 10     gal       Part sum counter    0 0000 10   gal             Current output   characteristics 4   20 mA  Current output   failure mode  lt  3 6 mA  Current output   min  current 3 8 mA  Current output   max  current 20 5 mA             The values of the following menu items are not reset with  Reset                          Menu section Menu item Reset value  Basic settings Application no reset  Position correction no reset  Display Lighting no reset  Service Language no reset  Pointer    Optional settings    The min  and max  temperature or pressure values are each reset to    the actual value     Totalizer    The total and part sum counter are reset to zero     Additional adjustment and diagnosis options such as e g  scaling    simulation or trend curve presentation are shown in the following menu  schematic  You will find a detailed description of these menu items in  the operating instructions manual  Indicating and adjustment module         50    VEGADIF 65    4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604          VEEA 6  Adjustment wih the indicating and adi  justment with the indicating and adjustment module PLICSCOM       6 5 Menu schematic   J Information   1 Depending on the version and application  the highlighted menu    windows are not always available     Basic adjustment differential
24. Operating Instructions    VEGADIF 65  4   20 mA       Document ID   36236          Ap  ota          Differential pressure                         Contents VEIA    Contents  1 About this document  Tl RUNCORN a i d ae aaa A tcl a Ps 4  1 2  Targat group i e ieee alee tate Ha toate Coach 4  1 3 Symbolism used                     0000008 4  2 For your safety  2 1 Authorised personnel                    000408 5  2 2 Appropriate use        eee 5  2 3 Warning about misuse                     04  5  2 4 General safety instructions                       5  2 5 Safety label on the instrument                   6  2 6 CEconformity  iiia a iie aa E a aa a A 6  2 7 Fulfillment of NAMUR recommendations            6  2 8 Safety instructions for Ex areas                  6  2 9 Safety instructions for oxygen applications          6  2 10 Environmental instructions                      6  3 Product description  3 1 Configuration        2 2    ee eee 7  3 2 Principle of operation                     004  8  3 3 Operation          0 00000 000 cee eee 12  3 4 Packaging  transport and storage                 12  4 Mounting  4 1 General instructions                      0004  14  4 2 Special application conditions                   15  4 3 Flow measurement                   00 00008 16  4 4 Level measurement                    000008 18  4 5 Density and interface measurement               23  4 6 Differential pressure measurement                25  4 7 Wall or tube mounting                     04 
25. Prepare the adjustment                      eee  XA BX  6 7 7  l  Ill     Ill  Xa  2X Xi 5 x                         Y Y          Fig  48  Preferred installation for liquids    I    I  Ml    VEGADIF 65  Three fold valve block  Precipitator    1 5 Drain valves   2 4 Inlet valves   3 Breather valve   6  7 Vent valves on VEGADIF 65  A  BBlock valves    Proceed as follows     4     Close valve 3  Fill measuring system with medium   Open valves A  B  2  4  Medium flows in     If necessary  clean the differential pressure lines    with gases by  blowing out with compressed air   with liquids by rinsing        Close valve 2 and 4  block the instrument  Open valve 1 and 5   Close valve 1 and 5   For this purpose  vent instrument    Open valves 2 and 4  Medium flows in   Close valve 4  Minus side will be closed   Open valve 3  Equalisation plus and minus side    Briefly open valve 6 and 7  then close again  Fill the measuring  instrument completely with the medium and remove air    For this purpose  set measurement loop to operation    Arrangement with 5 valves        VEGADIF 65 e   4     20 mA    65    8 Setup    VEIEA             Close valve 3  Separate plus and minus side  Open valve 4  Connect minus side   Now    Valves 1  3  5  6 and 7 are closed      Valves 2 and 4 open   Valves A and B open  if available     Then carry out adjustment  see chapter  Set parameters      5     Valves 1  3  5  Configuration with 5 valves        66    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    3
26. a monotonic decrease of at least 10       In case of strong vibrations at the application position  the instrument  version with external electronics should be used     Higher process temperatures often mean also higher ambient  temperatures for electronics and connection cable  Make sure that the  upper temperature limits stated in chapter  Technical data  for the  environment of the electronics housing and connection cable are not  exceeded     4 2 Special application conditions    Oxygen and other gases can be explosive with oils  grease and  plastics so that the following provisions must also be taken     e All components of the plant  such as e g  measuring instruments  must be cleaning according to the requirements of BAM   DIN 19247    e Depending on the materials used  a certain max  temperature and  pressure must not be exceeded in oxygen applications    Danger    Instruments for oxygen applications must be unpacked just before  mounting  After removing the protective cover of the process fitting  the  label  O   will be visible on the process fitting  Penetration of oil   grease and dirt should be avoided  Danger of explosion     In addition  VEGA offers oil and grease free instruments for special  applications such as e g  pure gas  There are no special restrictions in  respect to the process conditions        VEGADIF 65 e   4     20 mA    15                                              4 3 Flow measurement  In gases  gt  Mount VEGADIF 65 above the measurement loop
27. a safety data  sheet outside on the packaging   e Please ask the agency serving you for the address of your return  shipment  You can find the respective agency on our website  www vega com under   Company   VEGA worldwide        VEGADIF 65 e   4     20 mA    69    10 Dismounting             10 Dismounting  10 1 Dismounting steps    Warning    Before dismounting  be aware of dangerous process conditions such  as e g  pressure in the vessel  high temperatures  corrosive or toxic  products etc     Take note of chapters  Mounting  and  Connecting to power supply   and carry out the listed steps in reverse order     10 2 Disposal    The instrument consists of materials which can be recycled by  specialised recycling companies  We use recyclable materials and  have designed the electronics to be easily separable     WEEE directive 2002 96 EG   This instrument is not subject to the WEEE directive 2002 96 EG and  the respective national laws  Pass the instrument directly on to a  specialised recycling company and do not use the municipal collecting  points  These may be used only for privately used products according  to the WEEE directive     Correct disposal avoids negative effects to persons and environment  and ensures recycling of useful raw materials     Materials  see chapter  Technical data     If you have no possibility to dispose of the old instrument  professionally  please contact us concerning return and disposal        70    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E
28. arameter adjustment data into the  Indicating and adjustment module as well as downloading parameter  adjustment data into the sensor  A detailed description of the function       48 VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          6 Adjustment with the indicating and adjustment module PLICSCOM       Reset    is available in the operating instructions manual  Indicating and  adjustment module      The following data are loaded or downloaded with this function     Measured value presentation  Application   Adjustment   Damping   Linearisation curve   Leak volume suppression  Sensor TAG   Displayed value   Display unit   Scaling   Current output   Unit of measurement  Language   The following safety relevant data are not uploaded or downloaded     e HART mode  e PIN    Copy sensor data    Copy sensor data        Basic adjustment  The reset  Basic adjustment  resets the values of the following menu  items to the reset values  see chart         Menu section       Basic settings    Menu item Reset value  Unit of measurement bar  Temperature unit   C    Zero Min  adjustment Measuring range begin       Span Max  adjustment Measuring range end                Density 1 kg l  Density unit kg l  Damping 1s  Linearisation linear  Sensor TAG Sensor       Display    Displayed value Differential pressure    Display unit Mass kg    Scaling 0 00 to 100 0                VEGADIF 65    4     20 mA    49    6 Adjustment with the indicating and adjustment module PL
29. be noted  Furthermore the valid  national regulations  implementation instructions and memorandums  of the BG  professional assoc   must be noted     2 10 Environmental instructions    Protection of the environment is one of our most important duties  That  is why we have introduced an environment management system with  the goal of continuously improving company environmental protection   The environment management system is certified according to DIN  EN ISO 14001     Please help us fulfil this obligation by observing the environmental  instructions in this manual     e Chapter  Packaging  transport and storage   e Chapter  Disposal        VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604          3 Product description       3 Product description    3 1 Configuration    Scope of delivery The scope of delivery encompasses   e VEGADIF 65 differential pressure transmitter  e Depending on the version ventilation valves and or closing screws  e Optional accessory  e Documentation    this operating instructions manual   Operating instructions manual 27835  Indicating and adjust   ment module PLICSCOM   optional    Supplementary instructions manual 31708  Heating for in   dicating and adjustment module   optional    Operating instructions 36133   solating diaphragm CSB    optional    Operating instructions 36134   solating diaphragm CSS    optional    Supplementary instructions manual  Plug connector for con   tinuously measuring sensors   optional    Ex specific  Sa
30. c pressure   gt  Mount VEGADIF 65 below the lower measurement connection so  that the effective pressure lines are always filled with liquid   gt  Connect minus side always above the max  level       VEGADIF 65 e   4     20 mA    19    4 Mounting VEIA     gt  For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and  sediment                 max     min                          Fig  15  Measurement setup  level measurement in closed vessel    Block valves  VEGADIF 65  Precipitator   Drain valves  Three fold valve block    AUN    In closed vessels with  gt  Mount VEGADIF 65 directly to the vessel  unilateral pressure  transmitter    NY    Connect minus side always above the max  level     gt  For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and  sediment        20 VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604          4 Mounting       In closed vessels with  bilateral pressure trans   mitter       i    In closed vessels with  steam layering with ef   fective pressure line       max     min                                Fig  16  Measurement setup  level measurement in closed vessel    Block valve  Precipitator  Drain valve  VEGADIF 65    AwWDM       gt  Mount VEGADIF 65 below the lower isolating dia
31. cell is used as sensor element  The process  pressures are transmitted via separating diaphragms and filling oils to  the resistance measuring bridge  semi conductor technology   The  differential pressure dependent change of the bridge voltage is  measured  further processed and converted into a corresponding  output signal        10    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604          3 Product description       Power supply    The configuration of the measuring cells differs depending on the  measuring range                                               Fig  7  Metallic measuring cell 10 mbar and 30 mbar   p   and p   process    pressures   1 Measuring element   2 Silicone diaphragm   3 Separating diaphragm   4 Filling oil   5 Integrated overvoltage arrester                      kyo  OQ    Po                               Fig     A wWDM      8  Metallic measuring cell from 100 mbar   p   and p   process pressures    Measuring element   Overload diaphragr Middle diaphragm  Filling oil   Separating diaphragm    Two wire electronics 4     20 mA for power supply and measured  value transmission on the same cable     The supply voltage range can differ depending on the instrument  version  The exact range is stated in chapter  Technical data      The background lighting of the indicating and adjustment module is  powered by the sensor  A certain level of operating voltage is required  for this  You can find the exact voltage specifications in chapter   Te
32. chnical data         VEGADIF 65 e   4     20 mA    11    3 Product description       VEIEA          Packaging    Transport    Transport inspection    The optional heating requires its own operating voltage  You can find  details in the supplementary instructions manual  Heating for indicat   ing and adjustment module      This function is generally not available for approved instruments     3 3 Operation  VEGADIF 65 can be adjusted with different adjustment media     e with indicating and adjustment module   e with the suitable VEGA DTM in conjunction with an adjustment  software according to the FDT DTM standard  e g  PACTware and  PC    3 4 Packaging  transport and storage    Your instrument was protected by packaging during transport  Its  capacity to handle normal loads during transport is assured by a test  according to DIN EN 24180     The packaging of standard instruments consists of environment   friendly  recyclable cardboard  For special versions  PE foam or PE foil  is also used  Dispose of the packaging material via specialised  recycling companies     Caution    Instruments for oxygen applications are sealed in PE foil and provided  with a label  Oxygen  Use no Oil   Remove this foil just before  mounting the instrument  See instruction under  Mounting      Transport must be carried out under consideration of the notes on the  transport packaging  Nonobservance of these instructions can cause  damage to the device     The delivery must be checked for completeness
33. dium  Open valve 3  Equalisation plus and minus side    Briefly open valve 6 and 7  then close again  Fill the measuring  instrument completely with the medium and remove air    4 For this purpose  set measurement loop to operation  Close valve 3  Separate plus and minus side       VEGADIF 65 e   4     20 mA    63    8 Setup             Instructions    Installation for gases    Open valve 4  Connect minus side  Now   Valve 3  6 and 7 are closed  Valve 2  4 A and B are open   Then carry out adjustment  see chapter  Set parameters      8 4 Density and interface measurement    For density and interface measurements  VEGADIF 65 with bilateral  isolating diaphragm CSB is used     VEGADIF 65 in this version is immediately ready for operation     8 5 Differential pressure measurement    For differential pressure measurements  VEGADIF 65 without isolating  diaphragm or with bilateral isolating diaphragm CSB is used     VEGADIF 65 with bilateral isolating diaphragm CSB is immediately  ready for operation     Before adjusting VEGADIF 65 without isolating diaphragm  the  effective pressure lines must be cleaned and the instrument filled with  medium                                   Fig  47  Preferred installation for gases      VEGADIF 65   Il Three fold valve block   2  4 Inlet valves   3 Breather valve   6  7 Vent valves on VEGADIF 65  A  BBlock valves       64    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEBA          8 Setup       Installation for gases    
34. downloads  go to  Software   Select under  plics  instruments and sensors  the suitable instrument series  Load the zip  file via the right mouse key with  Save target as  e g  on the desktop of  your PC  Extract all files available in the zip file  e g  to the desktop        Connect the sensor to power supply and provide connection from PC  to the instrument via VEGACONNECT  Start PACTware and provide  connection to the sensor  e g  via the VEGA project assistant  Close  the parameter window of the sensor  as far as open     Go in the PACTware menu bar to   nstrument data    Additional  functions  and  Update instrument software      PACTware checks now the actual hardware and software version of  the sensor and displays the data  This procedure lasts approx  60 s     Push the button   Update software  and select the previously  extracted hex file  Then the software update can be started  Further  files are installed automatically  Depending on the sensor  this  procedure lasts approximately 1 h     9 5 Instrument repair  If a repair is necessary  please proceed as follows     You can download a return form  23 KB  from our Internet homepage  www vega com under   Downloads   Forms and certificates   Repair  form      By doing this you help us carry out the repair quickly and without  having to call back for needed information     e Print and fill out one form per instrument   e Clean the instrument and pack it damage proof   e Attach the completed form and  if need be  also 
35. e  Aluminium plastic housing   NBR  stain   less steel housing    Polycarbonate  UL 746 C listed    PN 160  hexagon screw ISO 4014 M12 x 90 A4   PN 420  hexagon nut ISO 4032 M12 A4 bs    316Ti 316L  PE  PUR  FEP    PUR    PE hard       Halocarbon oil generally with oxygen applications  not with vacuum and  absolute pressure measuring range  lt  1 barabs        VEGADIF 65 e   4     20 mA    71    11 Supplement Vela             Max  torque screws mounting strap 30 Nm  Max  torque screws socket external housing 5 Nm  3 688 lbf ft   Weight approx  4 2     4 5 kg  9 26     9 92 lbs   depending on    process fitting       Output variable       Output signal 4   20mA   Signal resolution 1 6 pA   Failure signal output current mA value unchanged 20 5 mA  22 mA   lt  3 6 mA   adjustable    Max  output current 22 mA   Load see load diagram under Power supply   Fulfilled NAMUR recommendations NE 43    Dynamic behaviour output  Run up time  lt 20s       100               63   H ey          ty Lt t             Fig  49  Presentation of the dead time t  and the time constant tp    The following specified total dead time applies to the 4     20 mA current output                 Dead time  lt  150 ms   Rise time  lt  100 ms  10     90      Step response time  lt  250 ms  ti  O s  10     90      Version  nominal measuring range Dead time t  Time constant t2  Basic version 10 mbar and 30 mbar measuring cell 100 ms 250 ms   Basic version 100 mbar 100 ms 180 ms   Basic version 500 mbar 100 ms 180 
36. e internal ground terminal  connect the  outer ground terminal with potential equalisation       30    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEIA 5 Connect to power supply    11 Tighten the compression nut of the cable entry  The seal ring must  completely encircle the cable    12 Screw the housing cover on  The electrical connection is finished                             Fig  27  Connection steps 6 and 7    IP 68 version with exter  Proceed as follows     nal housing  1 Loosen the four screws on the housing socket with an Allen key    size 4       VEGADIF 65 e   4     20 mA 31    5 Connect to power supply    VEEA             bae    2 Remove the housing socket from the mounting plate    ail                                                       ia                       Le    Fig  28  Components of the external housing                   1 Screw  2 Wall mounting plate  3 Cable gland    3 Loop the connection cable through the cable entry on the housing  base        Information    The cable gland can be mounted in three positions each displaced by  90    Simply exchange the cable gland against the blind plug in the  suitable thread opening     4 Connect the wire ends as described under  Single Double  chamber housing  according to the numbering    5 Connect the screen to the internal ground terminal  connect the  outer ground terminal above on the housing to potential equal   isation   6 Tighten the compression nut of the cable entry  The seal ring mu
37. e update or send the instrument for repair      E041  e Hardware error   gt  Exchange instrument or return instrument for repair    Depending on the failure reason and measures taken  the steps  described in chapter  Set up  must be carried out again  if necessary     9 3 Exchanging the electronics module    In case of a defect  the electronics module can be exchanged by the  user against an identical type  If no electronics module is available on  side  the module can be ordered for the VEGA agency serving you     The sensor serial number is required to order an exchange electronics   You will find this number on the type label of VEGADIF 65 or on the  delivery note     9 4 Software update    The software version of VEGADIF 65 can be determined as follows        Fault message can also appear if the pressure is higher than the nominal  range        68    VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604          9 Maintenance and fault rectification       Load sensor software to  PC    Prepare update    Load software into sen   sor    e via the type label of the electronics  e via the indicating and adjustment module  e via PACTware    You can view all software histories on our website www vega com   Make use of this advantage and get registered for update information  via e mail     The following components are required to update the sensor software     Sensor   Power supply  VEGACONNECT   PC with PACTware   Current sensor software as file    At  www vega com 
38. erential pressure measurement                64  9 Maintenance and fault rectification  9 1      Maintains 2 8 cio8 a fee eet 67  9 2 Remove interferences              000000008  67  9 3 Exchanging the electronics module                68  9 4 Software update                  2 2 eee eee  68  9 5 Instrument repair                0 000000 0 ee  69  10 Dismounting  10 1 Dismounting steps                       0004  70  10 2 Disposal irnayna   aia e eae ee ee iS ett aes 70  11 Supplement  11 1 Technical data            0 00     00 022 cee eee 71    Supplementary documentation    Information     Sup  with    plementary documents appropriate to the ordered version come  the delivery  You can find them listed in chapter  Product    description      Inst    Tip     ructions manuals for accessories and replacement parts    To ensure reliable setup and operation of your instrument  we offer  accessories and replacement parts  The corresponding instructions  manuals are       27720   External indication VEGADIS 61    34296   Protective cover  e 36132   Electronics module DF60 for VEGADIF 65       VEGADIF 65 e   4     20 mA    1    About this document    VEEA             1 About this document    1 1 Function    This operating instructions manual provides all the information you  need for mounting  connection and setup as well as important  instructions for maintenance and fault rectification  Please read this  information before putting the instrument into operation and keep this  manua
39. fety instructions   with Ex versions   Certificate  Oil and grease free for oxygen applications   with  respective versions    if necessary  further certificates    Components The following illustration shows the components of VEGADIF 65                                            Fig  1  VEGADIF 65 in basic version    1 Housing cover  optionally with integrated indicating and adjustment module  2 Housing with electronics   3 Process components with measuring cell   The components are available in different versions        VEGADIF 65 e   4     20 mA    3 Product description    VEIEA             Type label    Application area    The type label contains the most important data for identification and  use of the instrument     Sensor type   Article number instrument   Ex approval   Technical data  Measuring range  process pressure  process  temperature  signal output  voltage supply  protection  protection  class   e Order number  serial number instrument   e Hardware and software version   e Article numbers  documentation    The serial number allows you to access the delivery data of the  instrument via www vega com   VEGA Tools  and  serial number  search   In addition to the type label outside  you can also find the  serial number on the inside of the instrument     3 2 Principle of operation    VEGADIF 65 is a differential pressure transmitter for measurement of  flow  level  differential pressure  density and interface  Measured  products are gases  vapours and liquids     F
40. ion of the cable screen  3 Spring loaded terminals for voltage supply  Wiring plan ae  an g       7 N  7 N  Jo         Ge  l    FORO         doa ro l    if 2 j  cz                Fig  32  Wiring plan  double chamber housing  1 Voltage supply Signal output       34 VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEIA 5 Connect to power supply    5 5 Double chamber housing Ex d                                                                                                                                                                   Connection compart   ment  1    1E  4      i 2      2  er eee    Fig  33  Connection compartment double chamber housing Ex d  1 Spring loaded terminals for power supply and cable screen  2 Ground terminal for connection of the cable screen  Wiring plan                                                                   Fig  34  Wiring plan double chamber housing Ex d  1 Voltage supply Signal output       VEGADIF 65 e   4     20 mA 35    5 Connect to power supply       5 6 Version IP 66 IP 68  1 bar             Wire assignment  con   nection cable                Fig  35  Wire assignment  connection cable    1 brown     and blue     to power supply or to the processing system    2 Shielding    5 7 External housing with version IP 68       Electronics and connec        tion compartment for  power supply                   Display                                                                                                         
41. l accessible in the immediate vicinity of the device     1 2 Target group    This operating instructions manual is directed to trained qualified  personnel  The contents of this manual should be made available to  these personnel and put into practice by them     1 3 Symbolism used    Information  tip  note  This symbol indicates helpful additional information     Caution  If this warning is ignored  faults or malfunctions can   result    Warning  If this warning is ignored  injury to persons and or serious  damage to the instrument can result    Danger  If this warning is ignored  serious injury to persons and or  destruction of the instrument can result     Ex applications  This symbol indicates special instructions for Ex applications     List  The dot set in front indicates a list with no implied sequence     Action  This arrow indicates a single action     Sequence  Numbers set in front indicate successive steps in a procedure        VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604          2 For your safety       2 For your safety    2 1 Authorised personnel    All operations described in this operating instructions manual must be  carried out only by trained specialist personnel authorised by the plant  operator     During work on and with the device the required personal protective  equipment must always be worn     2 2 Appropriate use    VEGADIF 65 is a differential pressure transmitter for measurement of  flow  level  differential pressure  density a
42. low measurement                                                       Fig  2  Flow measurement with VEGADIF 65 and effective pressure transmitter   Q   flow  Ap   differential pressure  Ap   p1   Po    1 Orifice  2 Dynamic pressure probe       VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEA 3 Product description    Level measurement                                                                                  ms  a      i   a ee eb                       Fig  3  Level measurement with VEGADIF 65  Ap   differential pressure  p    density of the medium  g   acceleration of gravity    1 Basic version with effective pressure lines  2 Version with flange isolating diaphragm  3 Version with capillaries and cell isolating diaphragms    Differential pressure measurement                                           Fig  4  Differential pressure measurement with VEGADIF 65    1    Filter  2  VEGADIF 65       VEGADIF 65 e   4     20 mA 9    3 Product description             Functional principle    Density measurement                                           Fig  5  Density measurement with VEGADIF 65  h   defined mounting distance   Ap   differential pressure  p   density of the medium  g   acceleration of gravity    1 VEGADIF 65    Interface measurement       ia  8  Ir                                2   a             Fig  6  Interface measurement with VEGADIF 65  1 VEGADIF 65    2 Liquid with highest density  3 Liquid with lowest density    A metallic measuring 
43. lso take note of new  regulations        VEGADIF 65 e   4     20 mA    2 For your safety       VEIEA          2 5 Safety label on the instrument    The safety approval markings and safety tips on the device must be  observed     2 6 CE conformity    This device fulfills the legal requirements of the applicable EC  guidelines  By attaching the CE mark  VEGA provides a confirmation  of successful testing  You can find the CE conformity declaration in the  download area of www vega com     2 7 Fulfillment of NAMUR recommendations    With respect to compatibility  the NAMUR recommendation NE 53 is  fulfilled  This applies also to the corresponding indicating and  adjustment components  VEGA instruments are generally upward and  downward compatible     e Indicating and adjustment module for sensor software    The parameter adjustment of the basic sensor functions is independ   ent of the software version  The range of available functions depends  on the respective software version of the individual components     2 8 Safety instructions for Ex areas    Please note the Ex specific safety information for installation and  operation in Ex areas  These safety instructions are part of the  operating instructions manual and come with the Ex approved  instruments     2 9 Safety instructions for oxygen applications    For instruments in oxygen applications the special instructions in  chapters  Storage and transport    Mounting  as well as  Technical  data  under  Process conditions must 
44. minal  The ground terminal on the  outside of the housing must be connected to the potential equalisation   low impedance      If potential equalisation currents are expected  the connection on the  processing side must be made via a ceramic capacitor  e  g  1 nF   1500 V   The low frequency potential equalisation currents are thus  suppressed  but the protective effect against high frequency interfer   ence signals remains     Take note of the corresponding installation regulations for Ex  applications  In particular  make sure that no potential equalisation  currents flow over the cable screen  In case of grounding on both sides  this can be achieved by the use of a capacitor or a separate potential  equalisation     5 2 Connection procedure    Proceed as follows     Unscrew the housing cover    2 If an indicating and adjustment module is installed  remove it by  turning it slightly to the left     3 Loosen compression nut of the cable entry    4 Remove approx  10 cm of the cable mantle  strip approx  1 cm  insulation from the individual wires    5 Insert the cable through the cable gland into the sensor    6 Lift the opening levers of the terminals with a screwdriver  see  following illustration    7 Insert the wire ends into the open terminals according to the wiring  plan   8 Press down the opening levers of the terminals  you will hear the  terminal spring closing   9 Check the hold of the wires in the terminals by lightly pulling on  them    10 Connect the screen to th
45. ms                   72 VEGADIF 65 e   4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604                11 Supplement             Version  nominal measuring range Dead time t  Time constant t2  Basic version  3 bar 100 ms 180 ms  Basic version 16 bar and 40 bar 100 ms 180 ms       ranges    Isolating diaphragm version  all nominal measuring    Damping  63   of the input variable     Depending on the isolat   ing diaphragm       0     999 s  adjustable       Depending on the isolating  diaphragm          Input variable       Measured value    Nominal range    Lower measurement  limit    Differential pressure  flow and level derived from it    Upper measuring limit    Smallest adjustable  span       10 mbar  1 kPa      10 mbar   1 kPa      10 mbar   1 kPa     0 25 mbar  25 Pa        30 mbar  3 kPa   100 mbar  10 kPa   500 mbar  50 kPa     3 bar  300 kPa      30 mbar   3 kPa    100 mbar   10 kPa    500 mbar   50 kPa      3 bar   300 kPa      30 mbar   3 kPa    100 mbar   10 kPa    500 mbar   50 kPa      3 bar   300 kPa     0 3 mbar  30 Pa   1 mbar  100 Pa   5 mbar  500 Pa     30 mbar  3 kPa        16 bar  1600 kPa      16 bar   1600 kPa      16 bar   1600 kPa     160 mbar  16 kPa        40 bar  4000 kPa         40 bar   4000 kPa         40 bar   4000 kPa           400 mbar  40 kPa        Reference conditions and actuating variables  similar to DIN EN 60770 1     Reference conditions according to DIN EN 61298 1   18      30   C   64      86   F         Temperature      Relative h
46. n the menu item  span  with  OK      Span adjustment  100 00    amp        DP    0 5000 bar  0 0000 bar       Information    When the instrument is not yet adjusted  then the display pressure for  100   corresponds to the nominal measuring range of the sensor  in  the above example 500 mbar      2 Set the requested value with    gt J and  OK    3 Confirm with  OK  and move to the menu overview with  ESC      For an adjustment with pressure  simply enter the actual measured  value indicated at the bottom of the display     The span adjustment is finished     Proceed as follows     1 Edit the   value in the menu item  Min  adjustment  with  OK         VEGADIF 65 e   4     20 mA    45       6 Adjustment with the indicating and adjustment module PLICSCOM VEIA          Max  adjustment with    level    Min  adjustment with  flow    Pio    0 00      0 0000 bar  0 0000 bar       2 Setthe requested value with     and    gt      3 Confirm with  OK  and edit the requested bar value    4 Set the requested bar value with     and    gt      5 Confirm with     and move to max  adjustment with    gt      For an adjustment with filling  simply enter the actual measured value  indicated at the bottom of the display     The min  adjustment is finished     Proceed as follows   1 Edit the   value in the menu item  Max  adjustment  with  OK      100 00      0 5000 bar  0 0000 bar       Information    When the instrument is not yet adjusted  then the display pressure for  100   corresponds to the n
47. nd interface     You can find detailed information on the application range in chapter   Product description      Operational reliability is ensured only if the instrument is properly used  according to the specifications in the operating instructions manual as  well as possible supplementary instructions     For safety and warranty reasons  any invasive work on the device  beyond that described in the operating instructions manual may be  carried out only by personnel authorised by the manufacturer  Arbitrary  conversions or modifications are explicitly forbidden     2 3 Warning about misuse    Inappropriate or incorrect use of the instrument can give rise to  application specific hazards  e g  vessel overfill or damage to system  components through incorrect mounting or adjustment     2 4 General safety instructions    This is a high tech instrument requiring the strict observance of  standard regulations and guidelines  The user must take note of the  safety instructions in this operating instructions manual  the country   specific installation standards as well as all prevailing safety  regulations and accident prevention rules     The instrument must only be operated in a technically flawless and  reliable condition  The operator is responsible for trouble free  operation of the instrument     During the entire duration of use  the user is obliged to determine the  compliance of the required occupational safety measures with the  current valid rules and regulations and a
48. nd the clock  Since  we offer this service world wide  the support is only available in the  English language  The service is free of charge  only the standard  telephone costs will be charged     Connect a handheld multimeter in the suitable measuring range  according to the wiring plan     4    20 mA signal not stable   e Level fluctuations     gt  Set the integration time via the indicating and adjustment  module or PACTware       20 mA signal missing  Wrong connection to power supply    Check connection according to chapter  Connection steps   and if necessary  correct according to chapter  Wiring plan     ves       VEGADIF 65 e   4     20 mA    67       9 Maintenance and fault rectification VEIA                     Fault messages via the  indicating adjustment  module    Reaction after fault rec   tification    e No power supply    gt  Check cables for breaks  repair if necessary   e Operating voltage too low or load resistance too high   gt  Check  adapt if necessary      Current signal greater than 22 mA or less than 3 6 mA  e electronics module or measuring cell defective   gt  Exchange instrument or return instrument for repair    In Ex applications  the regulations for the wiring of intrinsically safe  circuits must be observed         013    no measured value available     gt  Exchange instrument or return instrument for repair      E017  e Adjustment span too small   gt  repeat with modified values      E036    no operable sensor software   gt  Carry out a softwar
49. nominal load  with a sensor current of 20 5 mA or 22 mA in case of  fault message    e Influence of additional instruments in the circuit  see load values in  chapter  Technical data      The instrument is connected with standard two wire cable without  screen  If electromagnetic interference is expected which is above the  test values of EN 61326 for industrial areas  screened cable should be  used     Use cable with round cross section  A cable outer diameter of 5     9mm   0 2     0 35 in  ensures the seal effect of the cable gland  If you are  using cable with a different diameter or cross section  exchange the   seal or use a suitable cable gland     On the instrument with cable entry   2 NPT and plastic housing there is  a metallic 1   2  threaded insert moulded into the plastic housing        VEGADIF 65 e   4     20 mA    29    5 Connect to power supply    VEIEA             A    Cable screening and  grounding    Select connec   tion cable for Ex Ex  applications    Single Double chamber  housing    Caution    No grease should be used when screwing the NPT cable gland or  steel tube into the threaded insert  Standard grease can contain  additives that corrode the connection between threaded insert and  housing  This would influence the stability of the connection and the  tightness of the housing     If screened cable is necessary  connect the cable screen on both ends  to ground potential  In the sensor  the screen must be connected  directly to the internal ground ter
50. ominal measuring range of the sensor  in  the above example 500 mbar      Set the requested value with    gt   and  OK     Edit the requested mbar value with  OK     Set the requested value with     and    gt      Confirm with  OK  and move to the menu overview with  ESC      a kW DY    For an adjustment with filling  simply enter the actual measured value  indicated at the bottom of the display     The max  adjustment is finished     Proceed as follows     1 Edit the bar value in the menu item  Min  adjustment  with  OK      Min  adjustment  0 00      0 0000 bar  0 0000 bar       2 Set the requested bar value with     and    gt     3 Confirm with     and move to max  adjustment with    gt       For an adjustment with flow  simply enter the actual measured value  indicated at the bottom of the display        46    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          6 Adjustment with the indicating and adjustment module PLICSCOM       Max  adjustment with  flow    be    Linearisation curve    Leak flow volume sup   pression with flow    The zero adjustment is finished     Proceed as follows     1 Edit the bar value in the menu item  Max  adjustment  with  OK      Max  adjustment  100 00         DP    0 5000 bar  0 0000 bar       Information    When the instrument is not yet adjusted  then the display pressure for  100   corresponds to the nominal measuring range of the sensor  in  the above example 500 mbar      2 Setthe requested mbar value with  
51. or  an  additional connection is not necessary        VEGADIF 65 e   4     20 mA    39    6 Adjustment with the indicating and adjustment module PLICSCOM Vela              T                   Fig  39  Insert indicating and adjustment module    Note    If you intend to retrofit the instrument with an indicating and adjustment  module for continuous measured value indication  a higher cover with  an inspection glass is required        40    VEGADIF 65    4    20 mA    vO9060 N3 9E29E    36236 EN 090604       VaEIEA       6 Adjustment with the indicating and adjustment module PLICSCOM       Key functions    Adjustment system    6 3 Adjustment system                                  Fig  40  Indicating and adjustment elements    1 LC display  2 Indication of the menu item number  3 Adjustment keys    e  OK  key       Move to the menu overview      Confirm selected menu      Edit parameter      Save value    e    gt   key to select        menu change       list entry       Select editing position  e     key        Change value of the parameter  e  ESC  key        interrupt input       jump to the next higher menu    The sensor is adjusted via the four keys of the indicating and  adjustment module  The LC display indicates the individual menu  items  The functions of the individual keys are shown in the above  illustration  Approx  10 minutes after the last pressing of a key  an  automatic reset to measured value indication is triggered  Any values  not confirmed with  OK  will not
52. phragm   gt  The ambient temperature should be the same for both capillaries  Information     Level measurement is only ensured between the upper edge of the  lower and the lower edge of the upper pressure transmitter         gt     max                       min           See              Fig  17  Measurement setup  level measurement in closed vessel  1 VEGADIF 65     gt  Mount VEGADIF 65 below the lower measurement connection so  that the effective pressure lines are always filled with liquid     gt  Connect minus side always above the max  level       VEGADIF 65 e   4     20 mA    21    4 Mounting    VEIEA             In closed vessels with  steam layering with uni   lateral pressure trans   mitter     gt  The condensate vessel ensures a constant pressure on the minus     gt     side    For measurements in products with solid content such as e g  dirty  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and    sediment           max     min                        x                               Fig  18  Measurement setup in closed vessel with superimposed steam    OaAUNSa    Y    Condensate vessel    Block valves  VEGADIF 65  Precipitator   Drain valves    Three fold valve block    Mount VEGADIF 65 directly to the vessel    Connect minus side always above the max  level    The condensate vessel ensures a constant pressure on the minus    side    For measurements in products with solid content such as e g  dirt
53. py sensor data 4 7       Copy sensor data              PIN    Enable     4 8                VEGADIF 65 e   4     20 mA    53    6 Adjustment with the indicating and adjustment module PLICSCOM    VEIEA             Info    Basic adjustment 5   Display  Diagnostics  Service    gt  Info    ne       Sensor type 5 1    Serial number  12345678          Date of manufacture  21  March 2009    Software version  1 01    5 2    Last change using PC    21  March 2009    5 3 Sensor characteristics 5 4    Display now              54    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604       VEEA       6 Adjustment with the indicating and adjustment module PLICSCOM       6 6 Saving the parameter adjustment data    It is recommended noting the adjusted data  e g  in this operating  instructions manual and archive them afterwards  They are hence  available for multiple use or service purposes     If VEGADIF 65 is equipped with an indicating and adjustment module   the most important data can be read out of the sensor into indicating  and adjustment module  The procedure is described in the operating  instructions manual   ndicating and adjustment module  in the menu   item  Copy sensor data   The data remain there permanently even if  the sensor power supply fails     If it is necessary to exchange the sensor  the indicating and adjustment  module is inserted into the replacement instrument and the data are  written into the sensor under the menu item  Copy sensor data         VE
54. st  completely encircle the cable    7 Attach the mounting plate again and tighten the screws    The electrical connection of the sensor to the external housing is  hence ready     D The connection cable is already preconfectioned  If necessary  shorten it to  the requested length  cut the breather capillaries clean  Remove approx   5 cm of the cable mantle  strip approx  1 cm insulation from the ends of the  individual wires  After shortening the cable  fasten the type plate with sup   port back onto the cable        32    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          5 Connect to power supply       Electronics and connec   tion compartment    Wiring plan    5 3 Single chamber housing           o  o  o      Display    1 2  JOQ             Fig  29  Electronics and connection compartment  single chamber housing    1 Spring loaded terminals for voltage supply  2 Ground terminal for connection of the cable screen    Le s N  7 4  20mA o  N  Z ko     Display                                                                           Fig  30  Wiring plan  single chamber housing  1 Voltage supply Signal output       VEGADIF 65 e   4     20 mA    33    5 Connect to power supply Vela    5 4 Double chamber housing                                                                                  Connection compart   ment  Fig  31  Connection compartment double chamber housing  1 Plug connector for VEGACONNECT  I C interface   2 Ground terminal for connect
55. t VEGADIF 65 below the measure     ment loop     gt  The ambient temperature should be the same for both capillaries             pe ey                   Fig  24  Measurement setup  differential pressure measurement in gases   vapours and liquids    1    2  3  4    Isolating diaphragm with bolting  Capillaries   E g  filter   VEGADIF 65       26    VEGADIF 65 e   4    20 mA    t09060 NJ 9EZ9E    36236 EN 090604    VEEA          4 Mounting       4 7 Wall or tube mounting       Mounting arrangement                            Boe ee    i          Fig  25  Mounting arrangement    Strap for tube mounting  Mounting bracket  Ventilation valve   Fixing screws  VEGADIF 65   PTFE seal   3 fold valve block   Oval flange adapter  Screw    ODANAGT AWD    4 8 External housing    Wall mounting 1 Mark the holes according to the following drilling template  2 Depending on the mounting surface  fasten the wall mounting    plate with 4 screws       VEGADIF 65 e   4     20 mA    27    4 Mounting                90 mm  3 54    70 mm  2 76         8mm   0 32            3mm  12                     JS                            z 208  o we    110 mm  4 33    93 mm  3 66         C                                        1 an   5             Fig  26  Drilling template   wall mounting plate    Mount the wall mounting plate so that the cable entry of the socket  housing points downward  The socket housing can be displaced by  180   to the wall mounting plate     4 9 Mounting control  Check the following af
56. t module PLICSCOM Vela             The square root bidirectional square root characteristics is very steep  at the zero point  This means that small changes in the measured  differential pressure cause big changes in the output signal  The leak  volume suppression stabilises the signal output     Total amounts counter The VEGADIF 65 has two internal totalizers  For both you can adjust  and subtotalizer with volume or mass as count function as well as separately the unit   flow    Proceed as follows   1 Select  for example  menu item  Part sum counter      Part sum counter  0 0000 10     gal   Modify settings   2 Activate the function  Modify settings   with  OK     Part sum counter   gt  Effective pressure transmitter    Unit  Ea  qo          3 Confirm with  OK   Effective pressure transmitter      Part sum counter     gt  Mass flow     gt  Volume flow  Without unit       Select the requested variable with    gt J and confirm with  OK    5 Select calibration unit of the effective pressure transmitter with      gt    for example m  s and confirm with  OK      Part sum counter  0      0000    m s   100      0000  m s        O    Edit with  OK  and set the requested values with     and    gt       Confirm with  OK  and jump back to the indication of the part sum  counter     The setting of the part sum counter is hence terminated  the counting  function is activated     N    The procedure of the total sum counter is the same     Copy sensor data This function enables uploading p
57. ter mounting the instrument     e Did you tighten all screws   e Closing screws and ventilation valves closed       28    VEGADIF 65    4    20 mA    vO9060 N3 9E29E    36236 EN 090604          5 Connect to power supply       Note safety instructions    be    Take note of  safety instruc   tions for Ex ap   plications    Select power supply    Selecting connection  cable    Cable gland 1   2 NPT    5 Connect to power supply  5 1 Prepare the connection    Always keep in mind the following safety instructions     e Connect only in the complete absence of line voltage  e  f overvoltage surges are expected  overvoltage arresters should  be installed    Tip   We recommend using VEGA overvoltage arresters B63 48 and  USB 62 36G X     In hazardous areas you should take note of the appropriate  regulations  conformity and type approval certificates of the sensors  and power supply units     Power supply and current signal are carried on the same two wire  cable  The voltage supply range can differ depending on the  instrument version     The data for power supply are specified in chapter  Technical data      Provide a reliable separation between the supply circuit and the mains  circuits according to DIN VDE 0106 part 101  The VEGA power supply  units VEGATRENN 149AEx  VEGASTAB 690  VEGADIS 371 as well  as all VEGAMETs meet this requirement     Keep in mind the following additional influences on the operating  voltage     e Output voltage of the power supply unit can be lower under  
58. the menu item   Units of measurement  will be displayed     3 Activate the selection with  OK  and select the requested unit with     gt    in the example m      4 Confirm with  OK   the submenu  Density unit  appears     Unit of measurement    Density unit     gt  kg dm   pef       5 Select the requested unit  e g  kg dm  with    gt   and confirm with   OK   the submenu  Density  appears        VEGADIF 65 e   4     20 mA    43    6 Adjustment with the indicating and adjustment module PLICSCOM    VEIEA             Unit of measurement    Density  0001000  kg dm        6 Enter the requested density value with    gt   and      confirm with   OK  and move to position correction with    gt       The adjustment unit is thus switched over from bar to m     Proceed as follows to select the temperature unit      gt  Activate the selection with  OK  and select  Temperature unit    with    gt        gt  Activate the selection with  OK  and select the requested unit with      gt    e g    F     gt  Confirm with  OK      The temperature unit is hence switched over from   C to   F     Position correction The position correction compensates the influence of the installation  position of the instrument on the measured value  In this menu item   the offset value as well as the current measured value are displayed     Proceed as follows     1 Activate in the menu item  Position correction  the selection with     OK      Position correction  Offset    0 0000 bar  0 0035 bar       2 Select with 
59. umidity      Air pressure    Determination of characteristics    Characteristics    Position of the measuring cell    Span   Diaphragm material  Filling oil   Material  lateral flanges    Influence of the installation position basic    version    45     75      860     1060 mbar 86     106 kPa  12 5     15 4 psig     Limit point adjustment according to IEC 61298 2    linear    constant  in the range  horizontal  1      based on the zero point    316L  Alloy C276  gold rhodium plated  Monel    Silicone oil  316L   lt  4 mbar        8  Instrument is rotated vertically to the diaphragm axis   9 For instruments with inert oil  the value doubles        VEGADIF 65 e   4     20 mA    73       11 Supplement VEIA    A position dependent zero point shift can be corrected  see also chapter  General installation  instructions  and  Installation instructions  isolating diaphragm systems             Deviation determined according to the limit point method according to IEC 607701     Applies to digital interfaces  HART  Profibus PA  Foundation Fieldbus  as well as to analogue  current output 4     20 mA  Specifications refer to the set span  Turn down  TD  is the ratio nominal  measuring range set span     Reference accuracy   all versions    This applies to the characteristics extracted by root  The accuracy data of VEGADIF 65 are  entered with factor 0 5 in the accuracy calculation of the flow    Reference accuracy   Basic version    10 mbar  30 mbar measuring cell        Turn down 1  1  
60. ustment 1 3  Unit of measurement Offset    000 0   A  Level V Em    V m   i   Temperature unit  0 0035 bar 0 0000 bar  CY 0 0000 bar 0 0000 bar  Max  adjustment 1 4 Damping 15 Linearisation curve 1 6 Sensor TAG TZ  100 00   a    gt  linear  A   E 1s   Horizontal cylindrical tank E Sensor  0 5000 bar Spherical tank  0 0000 bar User programmable  Display  Basic adjustment 2   gt  Display  Diagnostics  Service  Info  Displayed value 2 1 Displayed value Y 2 1 Display unit 2 2 Scaling 2 3  0  0 0  Differential pressure Y Scaled Volume V l  IF 100     100 0                Lighting 2 4    Switched off Y             52    VEGADIF 65    4    20 mA    vO9060 N3 9E29E    36236 EN 090604    VEEA          6 Adjustment with the indicating and adjustment module PLICSCOM       Diagnostics       Basic adjustment 3  Display    gt  Diagnostics  Service    Info          Pointer 3 1  p min    5 8 mbar   p max   167 5 mbar   T min    12 5   C   T max    85 5   C    Sensor status    OK    3 2    Trend curve    Start trend curve     3 3    Total sum counter 3 4  0 0000 10    gal    Modify settings        Part sum counter 3 5   0 0000 10    gal            _ Modify settings     Service       Basic adjustment 4  Display  Diagnostics   gt  Service  Info          Current output 4 1    Output mode  4 20 mA Y       Fail mode   lt  3 6 mA Y  Min  current  3 8 mA Y  max  current  20 5 mA Y    Simulation    Start simulation Y    4 2    Reset    Select reset V    4 3       Language 4 4    Deutsch V          Co
61. y  liquids  the installation of separators and drain valves is  recommended to enable collection and removal of debris and    sediment        22    VEGADIF 65    4     20 mA    t09060 NJ 9EZ9E    36236 EN 090604          4 Mounting       Density measurement        i       max     min                             Fig  19  Measurement setup in closed vessel with superimposed steam    1 Condensate vessel  2 Block valve   3 Precipitator   4 Drain valve   5  VEGADIF 65    4 5 Density and interface measurement    Density and interface measurement are carried out in level measure   ment mode     gt  Mount VEGADIF 65 below the lower isolating diaphragm    gt  The ambient temperature should be the same for both capillaries  Information     The density measurement is only ensured with constant level   Homogeneous density distribution is a prerequisite        VEGADIF 65 e   4     20 mA    23    4 Mounting             Interface measurement    e  1             0 3m                                  Fig  20  Measurement setup with density measurement  Density 1 and h   0 3 m  means Ap   30 6 mbar  With density change  e g  measured Ap   36 7 mbar  corresponds to density 1 2  measured Ap   24 5 mbar corresponds to density  0 8    1 VEGADIF 65     gt  Mount VEGADIF 65 below the lower isolating diaphragm   gt  The ambient temperature should be the same for both capillaries  Information     Interface measurement is ensured only when the filling level is  constant              0 3m               
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
User's Manual  MARINE & SCIENCES - La Rose des Vents  Gegenees V 1.1.0  Yamaha LS9-16/LS9-32 V1.1 Supplementary Manual  Flat_light_manual_download  User Manual  取扱説明書  取扱説明書 - 山田照明  Fortinet FortiOS 3.0 User's Manual  Assembly and operating instructions 取扱説明書取扱    Copyright © All rights reserved. 
   Failed to retrieve file