Home

Installation and operating instructions electric shower

image

Contents

1. REPLACING THE COVER The power selector spindle must be aligned as shown fig 14 Make sure the temperature control is correctly positioned on the stabilising valve by temporarily placing the cover in position so that the splines engage and then rotate the temperature control fully anti clockwise Remove the cover and position the temperature control knob so that it points towards the No 1 position fig 15 Position the power selector to the STOP position fig 16 Replace the cover squarely to the backplate and guide into position so that the knobs locate correctly into the splined spindles Should any difficulty arise recheck the points above Secure the cover in position with the three retaining screws COMMISSIONING WARNING Before normal operation of the shower it is essential the following commissioning procedure is completed correctly The first operation of the shower is intended to flush out any remaining unit debris and to guarantee that the heater unit contains water before the elements are switched on This operation must be carried out with the flexible hose screwed to the outlet but without the showerhead attached Make sure the outlet of the flexible hose is directed to waste Before turning on the electric and mains water supplies to the shower make sure that the power selector is at the STOP position fig 17 and the temperature control is rotated fully cloc
2. After choosing the site for the shower use the backplate as a template and mark the two fixing holes fig 11 Drill and plug the wall An appropriate drill bit should be used If the wall is brick plasterboard or a soft building block appropriate wall plugs should be fitted T70si electric shower Screw bottom fixing screw into position leaving the base of the screw head protruding 6 mm out from the wall Hook the backplate over the bottom screw and fit the top fixing screw into position DO NOT fully tighten the screws at this stage as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed D amp ero 1 lI lL p TT e WARNING The outlet of the shower acts as a vent and MUST NOT be connected to anything other than the hose and showerhead supplied PLUMBING CONNECTIONS Plumbing to be carried out before wiring DO NOT use jointing compounds on any pipe fittings for the installation DO NOT solder fittings near the shower unit as heat can transfer along the pipework and can damage components Compression fittings MUST be used to connect to the inlet o
3. MAX PRESSURE Approved Fig 2 MIN PRESSURE RATED PRESSURE MODEL No 00000000 SERIAL No 00000000 Fig 3 Schematic of installation circuit Pull cord isolating switch RCD can be part of consumer unit Fuse or Consumer MCB Meter Incoming supply 80A or 100A L fuse main switch Meter tails Table A TN CIRCUIT PROTECTION unit cartridge rating MCB fuse 7 0kW 30 32A 30A 7 5kW 32A 35A 8 0kW 40A 35A 8 5kW 40A 45A 9 0kW 40A 45A 9 5kW 40 45A 45A 10 5kW 45A 45A 5 1 6 1 6 2 8 1 8 2 9 1 A 30mA residual current device RCD must be installed in all UK electric and pumped shower circuits This may be part of the consumer unit or a separate unit A 45 amp double pole isolating switch with a minimum contact gap of 3 mm in both poles must be incorporated in the circuit It must have a mechanical indicator showing when the switch is in the OFF position and the wiring must be connected to the switch without the use of a plug or socket outlet The switch must be accessible and clearly identifiable but out of reach of a person using a fixed bath or shower except for the cord of a cord operated switch and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower Where shower cubicles are located in any rooms other
4. 0870 067 3334 E mail technical tritonshowers co uk 1 2 1 3 1 4 1 5 1 6 b c 1 7 1 8 1 9 2 2 2 3 PLEASE READ THIS IMPORTANT SAFETY INFORMATION Products manufactured by Triton are safe and without risk provided they are installed used and maintained in good working order in accordance with our instructions and recommendations WARNING DO NOT operate shower if frozen or suspected of being frozen It must thaw out before using DO NOT operate the unit if the showerhead or spray hose becomes damaged DO NOT restrict flow out of shower by placing showerhead in direct contact with your body DO NOT operate the shower if water ceases to flow during use or if water has entered inside the unit because of an incorrectly fitted cover WARNING If restarting the shower immediately after stopping be aware that a slug of hot water will be expelled for the first few seconds GENERAL Isolate the electrical and water supplies before removing the cover Read all of these instructions and retain them for later use DO NOT take risks with plumbing or electrical equipment Isolate electrical and water supplies before proceeding with the installation The unit must be mounted onto the finished wall surface on top of the tiles Do not tile up to unit after fixing to wall Contact Customer Service see back pago if any of the following occur If it is intended to operate the shower at pressures a
5. in accordance with this installation guide objects or substances of parts consequential loss of any kind with the appliance be isolated this includes consequential losses arising from unserviceable supply valves The cost of repair or replacement of pressure relief devices showerheads hoses riser rails and or wall brackets isolating switches electrical cable fuses and or circuit breakers or any other accessories installed at the same time overhaul modifications or loss or damage arising therefrom including the cost of repairing damage breakdown malfunction caused by corrosion furring pipe scaling limescale system debris or frost d Triton Showers Triton Road Nuneaton Warwickshire CV11 4NR Triton is a division of Norcros Group Holdings Limited Customer Service 0844 980 0750 Trade Installer Hotline F 0844 980 0730 Fax 0844 980 0744 www tritonshowers co uk E mail serviceenquiries tritonshowers co uk Extended Warranty AVAILABLE NOW Call 0844 980 0740 for more details TRITON reserve the right to change product specification without prior notice E amp OA TRITON SHOWERS 2009
6. is fitted with a thermal cut out safety device In the event of abnormal operation SG which could cause unsafe temperatures within the unit the device will disconnect the heating elements It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety device once the unit has been repaired temperature 705 electric shower CLEANING WARNING DO NOT use abrasive or solvent cleaning fluids DO NOT use abrasive or aggressive The shower unit riser rail hose etc should be cleaning products when cleaning the cleaned using a soft cloth and warm water shower as they may damage the unit Before cleaning turn off the unit at the isolation switch to avoid the shower being accidentally switched on IT IS IMPORTANT TO KEEP THE SHOWERHEAD CLEAN TO MAINTAIN THE PERFORMANCE OF THE SHOWER The hardness of the water will determine the frequency of cleaning For example if the shower is used every day in a very hard water area it may be necessary to clean the showerhead on a weekly basis 705 electric shower INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY filter CLEANING THE INLET FILTER It is recommended that the filter is periodically cleaned in order to maintain the performance of the shower It is essential that this operation is carried out by a competent person SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS The inlet f
7. the water supply permanently on to the shower unit but as with most electrical appliances the unit must be switched off at the isolating switch when not in use OPERATING THE SHOWER WARNING Before normal operation of the shower it is essential the following commissioning procedure is completed correctly To start the shower Turning the power selector to the red or blue symbol positions allows water to flow To stop the shower Switch the power selector to the STOP position and water will cease to flow WARNING If restarting immediately after stopping be aware that a slug of hot water will be expelled for the first few seconds To use the power selector The power selector has four positions STOP COLD ECONOMY and HIGH as shown in fig 21 STOP is to switch off the electric and water supply at the shower no flow or power used Blue symbol is for COLD water only Adjusting the temperature control at this setting will only alter the force of the water from the showerhead IT WILL NOT ALTER THE WATER TEMPERATURE Single red symbol is the ECONOMY setting for using less power during warmer months Temperature adjustment at this setting is via the temperature control Note If the stated flow rate required for the unit cannot be met due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the
8. unit Double red symbol is the HIGH setting which allows the highest flow achievable for your preferred temperature This setting should normally be regarded as optimum shower performance throughout the year Temperature adjustment at this setting is via the temperature control To adjust the shower temperature The water temperature is altered by increasing or decreasing the flow rate of the water through the shower via the temperature control Note The preferred number on ECONOMY will give a different temperature to the same number position on HIGH To decrease the shower temperature Turn the temperature control anti clockwise this will increase the flow of water through the shower and be indicated by the lower numbers To increase the shower temperature Turn the temperature control clockwise this will decrease the flow of water through the shower and be indicated by the higher numbers Note It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a few seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate CAUTION It is recommended that persons who may have difficulty understanding or operating the shower controls should not be left unattended whilst showering Special consideration should be given to young children and the less able bod
9. with a damaged or kinked shower hose or a blocked showerhead which can cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose while at the same time the temperature control must be at the minimum flow position Failure to follow this procedure may also cause the PRD to operate Make sure the shower is positioned over a bath or shower tray because if the PRD operates then water will eject from the bottom of the unit Should this happen turn off the electricity and water supplies to the shower at the isolating switch and stopvalve Contact Customer Service for advice on replacing the PRD WARNING The shower must not be positioned where it will be subjected to freezing conditions UN Shower unit can be mounted either Q side of riser rail or rear entry ji Height of showerhead and shower DOKN to suit user s Retaining ES requirement ring R Mains cold water i supply either top i side bottom de Showor unit 25 mm minimum must not N d be within ME I an area o 1 metre Outline of bath from base V or shower tray Fig 5 Diagrammatic view not to scale IMPORTANT The unit must be mounted on a flat surface which covers the full width and length of the backplate It is important that the wall surface is flat otherwise difficulty may be encountered when fit
10. MPORTANT When first installed the unit will be empty It is essential the unit should contain water before the elements are switched t is vital that the followed commissioning procedure is Failure to carry out this operation will result in damage to the unit and will invalidate the guarantee The following points will help you understand how the shower operates a The electric heating elements operate at a constant rate at your chosen power setting It is the rate of the water passing through the heater can which determines the water temperature The slower the flow the hotter the water becomes and the faster the flow the cooler the water b During winter the mains water supply will be cooler than in summer so the temperature of the shower will vary between seasons on any one setting of the temperature control At different times of the year you may have to adjust the position of the temperature control to maintain your desired temperature setting c The stabiliser valve minimises variations in shower temperature during mains water pressure changes If changes in shower temperature are experienced during normal use it will most likely to be caused by the water pressure falling near to or below the minimum level The drop in pressure may be due to water being drawn off at other points in the house while the shower is in use If pressure drops appreciably below the minimum the heating elements will automatically c
11. TRITON T70si electric shower Installation and operating instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180254Q February 2008 705 electric shower CONTENTS Page Important safety information sss 1 Introductio reet o REP D obo EI 2 Specifications crece tette totae cos ted ke bd 2 AdVice to Usels eerte deret ine dero 2 Main componerits s eoe coerente ehe ER 3 Electrical requiremiernts ee cnt ero re tren etes 4 Water requirements Siting of the shower Fitting the shower to the wall nee ttt renes 8 Plumbing connections nce ten tetro isi 10 Electrical corinectlons e rk 11 Replacing the CoV6r onere tede et 12 Comimlissiohilligi 1 55 1 sates cache E EE IEEE 13 Operating the shOWer ierit re bone rtr Deeper eio neis 14 Operating FUNCOMS serrar iet ete rp rodent 16 Gl aming ite p IPS RERO ON SERERE ENG EAE TEE ERR PK 17 Instructions for installers and service engineers only 18 Cleaning the inlet filter Spare parts iso ivo OR SEU Fault finding 3x deett ir De cra et e e rbi rv RES Guarantee Service policy etc 6 rettet rear cover To check the product suitability for commercial and multiple installations please contact Triton s specification advisory service before installation Telephone 0870 067 3767 Facsimile
12. above 9kW it is advisable to contact the local electricity supply company 1 1 The electrical rating of the shower is shown on the rating label Fig 2 within the unit 2 Before making any sort of electrical connection within the installation make sure that no terminal is live If in any doubt switch off the whole installation at the mains supply and remove the correct fuse 3 shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outlet lighting circuit or cooker circuit 3 1 The electrical supply must be adequate for the loading of the unit and existing circuits 4 Check your consumer unit main fuse box has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or Miniature Circuit Breaker MCB necessary for the shower Fig 3 4 1 If your consumer unit has a rating below 80A or if there is no spare fuse way then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower 4 2 You will need to contact the local electricity company They will check the supply and carry out what is necessary 5 For close circuit protection DO NOT use a rewireable fuse Instead use a suitably rated Miniature Circuit Breaker MCB or cartridge fuse see Table A Shepperton Park p TRI Triton Road Nuneaton Warwickshire CV11 4NR MODEL 230 240V
13. bove the maximum or below the minimum stated If the unit shows a distinct change in performance If the shower is frozen If it is intended to operate the shower in areas of hard water above 200 ppm temporary hardness a scale inhibitor may have to be fitted For advice on the Triton Scale Inhibitor contact Triton Customer Service The showerhead must be cleaned regularly with descalent to remove scale and debris otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the Pressure Relief Device in the unit to operate This product is not suitable for mounting into steam rooms or steam cubicles PLUMBING The plumbing installation must comply with Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700 The supply pipe must be flushed to clear debris before connecting to the shower unit DO NOT solder pipes or fittings within 2 4 2 5 2 6 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 10 300mm of the shower unit as heat can transfer along the pipework and damage components DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can DO NOT use excessive force when making connections to the flexible hose or showerhead finger tight is sufficient All plumbing connections must be completed b
14. cable can be surface clipped hidden or via 20 mm conduit Note Conduit entry can only be from rear Route the cable into the shower unit and connect to the terminal block fig 13 as follows Earth cable to terminal marked E Neutral cable to terminal marked N Live cable to terminal marked L IMPORTANT Fully tighten the terminal block screws and check that no cable insulation is trapped under the screws Loose connections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall in accordance with IEE regulations The use of connections within the unit or other points in the shower circuit to supply power to other equipment i e extractor fans pumps etc will invalidate the guarantee DO NOT switch on the electricity supply until the cover has been fitted 1 Terminal block 6 Solenoid valve 2 Thermal cut out main 7 Element 3 Thermal cut out outlet 8 Element 4 Microswitches 9 Neon 5 Start Stop button Xe 2 TT T a Fig 13 _ Terminal block Note The elements on UK models are to 240V specification and will give a lower kW rating if the voltage supply is below 240V 705 electric shower Selector spindle Fig 14
15. e mains stopvalve is fully open and there are no other restrictions in the supply while shower is in use or see 4 2 4 4 2 4 Fit pump to give minimum pressure see rating label Contact Customer Service for advice 4 3 1 Readjust flow rate to give reduced flow 4 3 2 Select HIGH power 4 4 1 Have unit checked by suitably qualified electrician or contact Triton Customer Service Problem Symptom 5 Shower varies from normal temperature to cold during use FAULT FINDING Cause 5 1 Water pressure has dropped below minimum required Action Cure 5 1 1 Wait until the water pressure resumes to normal 6 Pressure relief device has operated water ejected from PRD tube 6 1 Blocked showerhead 6 2 Twisted blocked flexible shower hose 6 3 Showerhead not removed while commissioning 6 1 1 Clean or replace blocked sprayplate in showerhead and then fit new PRD 6 2 1 Check for free passage through hose Replace the hose if necessary and fit new PRD 6 3 1 Fit new PRD Commission unit with showerhead removed Note Identify cause of operation before fitting new PRD unit When fitting a new PRD follow the commissioning procedure It is advised all electrical maintenance repairs to the shower should be carried out by a suitably qualified person 3M eEmICEDOIICV UK SERVICE POLICY In the event of a product fault or complaint occurring the following procedure should be followed 1 Telep
16. efore making the electrical connections ELECTRICAL The installation must comply with BS 7671 Requirements for electrical installations IEE wiring regulations building regulations or any particular regulations as specified by the local Electrical Supply Company This appliance MUST be earthed In accordance with The Plugs and Sockets etc Safety Regulations 1994 this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system Make sure all electrical connections are tight to prevent overheating Fuses do not give personal protection against electric shock A 30mA residual current device RCD MUST be installed in all UK electric and pumped shower circuits This may be part of the consumer unit or a separate unit Switch off immediately at isolating switch if water ceases to flow during use Other electrical equipment i e extractor fans pumps must not be connected to the circuits within the unit Switch off at isolating switch when not in use This is a safety procedure recommended with all electrical appliances As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage INTRODUCTION This book contains all the necessary fitting and operating instructions for your Triton electric shower Please read them care
17. f the shower Note An additional stopvalve complying with Water Regulations MUST be fitted in the mains water supply to the shower as an independent means of isolating the water in order to carry out maintenance or servicing IMPORTANT Before completing the connection of the water supply to the inlet of the shower flush out the pipework to remove all swarf and system debris To do this connect a hose to the pipework and turn on the mains water supply long enough to clear the debris to waste Procedure Turn off water supply either at the mains stopvalve or the isolating stopvalve Connect the mains water supply to the inlet of the shower via 15 mm copper stainless steel or plastic pipe using a 15 mm x 15 mm compression fitting Note The inlet fitting is designed to enter a compression fitting only DO NOT use push fit connectors as full engagement cannot be guaranteed DO NOT use excessive force when making these connections Make sure the backplate is square on the wall and tighten the two retaining screws which hold it to the wall Turn on the mains water supply and check for leaks in the pipework connection to the shower IMPORTANT Using a suitable sealant always seal around the incoming pipework to prevent water entering the wall Note At this stage no water can flow through the unit ELECTRICAL CONNECTIONS SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS Fig 12 shows a schematic wiring diagram The
18. fully The shower installation MUST be carried out by a suitably qualified person and in the sequence of this instruction book Care taken during the installation will ensure a long trouble free life from your shower SPECIFICATIONS Electrical Nominal power rating at 240V 7kW 30A MCB rating 8kW 40A MCB rating 8 5kW 40 MCB rating 9kW 40A MCB rating 9 5kW 40A MCB rating Water Inlet connection 15 mm diameter Outlet connection 7 BSP male thread Nominal power rating at 230V 6 4kW 30A MCB rating 7 4kW 40A MCB rating 7 8kW 40A MCB rating 8 3kW 40A MCB rating 8 7kW 40A MCB rating Entry Points Water top bottom back left or right Cable top bottom back left or right Materials Backplate cover controls showerhead ABS Sprayplate Acetal Elements Minerally insulated corrosion resistant metal sheathing Dimensions mm Height 300 Width 208 Depth 110 Standards and Approvals Splashproof rating IPX4 Complies with the requirements of current British and European safety standards for household and similar electrical appliances Complies with requirements of the British Electrotechnical Approvals Board BEAB Meets with Compliance with European Community Directives CE Replacement parts can be ordered from Customer Service See spare parts for details and part numbers ADVICE TO USERS I
19. hone Customer Service on 0844 980 0750 having available your details including post code the model number and power rating of the product together with the date of purchase 2 Basedon information given over the telephone a Triton Customer Service Advisor will attempt to diagnose the fault and confirm whether a site visit from a qualified service engineer is required 3 All products attended to by a Triton service engineer must be installed in full accordance with the Triton installation guide applicable to the product Every product pack contains an installation guide however they can also be bought via our Customer Service Spares Department 4 Our engineer will require local parking and if a permit is required this must be available to the engineer on arrival at the call 5 Itis essential that you or an appointed representative who must be over 18 years of age is present for the duration of the service engineer s visit If the product is in guarantee you must produce proof of purchase 6 Where a call under the terms of guarantee has been booked and the failure is not product related i e scaling and furring incorrect water pressure pressure relief device operation or electrical plumbing installation fault a charge will be made A charge will also be issued if nobody is at home when the service engineer calls or adequate parking permit is not available 7 If the product is no longer covered by the guarantee an up front
20. ied WARNING After any servicing of mains water supply always flush out the pipework to remove any debris Always make sure the unit is started on COLD in order to purge any air in the pipework WARNING This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance T70si electric shower OPERATING FUNCTIONS Power on indicator fig 22 When the electricity supply to the shower is switched on at the isolating switch the power indicator will light Low water pressure cut out If the water pressure falls below the minimum required for correct operation of the shower power will be switched off to the heating elements preventing any maintained temperature rises water will continue to flow Power will automatically be restored when adequate water pressure returns Overheat cut out During normal operation if an overheat temperature is sensed power to the elements will be reduced Water will continue to flow When the temperature has cooled sufficiently power to the elements will be automatically restored to the previous setting at the time of interruption Safety cut out The unit
21. ilter is situated inside the solenoid inlet fig 23 To access the filter remove the cover and disconnect and remove the compression fitting Also depending on the incoming pipework arrangements if there is not enough slack in the pipework it could mean the removal of the unit from the wall When cleaning the filter DO NOT use a sharp object as it will cause damage It is preferable to use an old toothbrush or similar 705 electric shower Ref Description N A ws 10 11 Can assembly 7kW 8kW 8 5kW 9kW 9 5kW Terminal block Switching module assembly c w actuator amp m switches Solenoid valve assembly Thermal cut out main Stabiliser valve assembly Outlet pipe amp wiring assy Pressure Relief Device Cover assembly c w knobs Power neon Insert trim cover Insert trim backplate SPARE PARTS Part No 84500430 84500450 P07810700 84500550 P07810701 22011410 82500210 83300450 22009860 82600820 85000250 82800450 84800010 82300980 7052245 7052244 Problem Symptom 1 Shower inoperable no water flow FAULT FINDING IMPORTANT Switch off the electricity at the mains supply and remove the circuit fuse before attempting any fault finding inside the unit Cause 1 1 In
22. it is intended to operate the shower at pressures above the maximum or below the minimum stated contact Triton Customer Service for advice Fig 4 shows a typical system layout Do not use jointing compounds on any pipe fittings for the installation SITING OF THE SHOWER FOR EASE OF SERVICING THE UNIT MUST ALWAYS BE MOUNTED ON THE SURFACE OF TILED WALLS NEVER TILE UP TO THE UNIT Refer to Fig 5 for correct siting of shower Position the unit where it will not be in direct contact with water from the showerhead Position the shower unit vertically Allow enough room between the ceiling and the shower to access the cover top screws Note Water Regulations shower hose connections requires the showerhead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25 mm above the spill over level of the relevant bath shower tray or other fixed appliance The use of the supplied soap dish will in most cases meet this requirement but if the showerhead can be placed within a bath basin or shower tray then a double check valve or similar must be fitted in the supply pipework to prevent back flow Pressure relief safety device A pressure relief device PRD is designed into the shower unit which complies with European standards The PRD provides a level of appliance protection should an excessive build up of pressure occur within the shower Do not operate the shower
23. iton guarantee this product against all mechanical and electrical defects arising from faulty workmanship or materials for a period of two years for domestic use only from the date of purchase provided that it has been installed by a competent person in full accordance with the fitting instructions Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge so long as it has been properly maintained and operated in accordance with the operating instructions and has not been subject to misuse or damage This product must not be taken apart modified or repaired except by a person authorised by Triton This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially This guarantee does not affect your statutory rights What is not covered 1 Repair costs for damage caused by foreign Total loss of the product due to non availability Compensation for loss of use of the product or Call out charges where no fault has been found Call out charges where the water supply cannot The cost of routine maintenance adjustments TRITON STANDARD GUARANTEE Breakdown due to a use other than domestic use by you or your resident family b wilful act or neglect c any malfunction resulting from the incorrect use or quality of electricity gas or water or incorrect setting of controls d failure to install
24. ixed fee will be charged before the site visit 8 Should proof of purchase not be available on an in guarantee call or should the service engineer find that the product is no longer under guarantee the engineer will charge the same ixed price and the customer will be expected to pay the engineer before he leaves If payment is not made on the day an administration charge will be added to the fixed charge 9 debt is outstanding from a previous visit or from any other riton purchase Triton reserves the right to withhold service until he debt has been settled 10 Triton takes the health safety and wellbeing of its employees very seriously and expects customers to treat all staff members with respect Should any employee feel threatened or receive abuse either verbally or physically Triton reserves the right to withhold service and will support the employee with a legal prosecution Replacement Parts Policy Availability It is the policy of the manufacturer to maintain parts availability for the duration of production and a period of five years thereafter in accordance with industry standards Spare parts are available via our website www tritonshowers co uk or by telephoning Triton Customer Service Spares Department Payment should be made by credit debit card excluding American Express or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or money order J Tr
25. kwise to 10 the minimum flow position fig 18 Note Failure to turn the temperature control to 10 may cause the PRD to operate Turn on the mains water supply to the shower at the isolating stop valve and then turn on the electric supply to the shower at the isolating switch The power indicator will light Switch the power selector to the COLD position fig 19 and wait until water starts to flow from the flexible hose Slowly rotate the temperature control fully anti clockwise to 1 the maximum flow position fig 20 It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is being dispersed from the shower When a smooth flow of water is obtained rotate the temperature control from 1 to 10 several times to release any trapped air within the unit Once flushing out has been completed stop the water flow by turning the power selector to the STOP position Fit the showerhead to the flexible hose and place in the showerhead holder The shower is now ready for normal operation fe power Fi a 19 3 g stop M a FK puce I C 0 1 Fig 18 NN A A 8 j i ug power VN o Fig 19 E 8 S i 2 C temperature S TRITON T70si Economy Temperature control temperature Note In normal use it is in order to leave
26. nstalled in an insulated wall trunking wall 6 mm 6 mm 6 mm 32A 38A 46A 10 mm 10 mm 10 mm 43A 52A 63A 16 mm 16 mm 16 mm 57A 69A 85A Clipped direct or buried in a In conduit non insulated M Note Cable selection is dependent on derating factors A Mains electric supply via double pole switch V Isolating stopvalve Mains water supply Separate permanently connected supply from consumer unit Fig 4 Diagrammatic view not to scale J WATER REQUIREMENTS The installation must be in accordance with Water Regulations Bylaws To ensure activation of the heating elements the shower must be connected to a mains water supply with a minimum running pressure of 100kPa 1 0 bar at a minimum flow rate of eight litres per minute nine litres per minute for the 9 5kW rated model For all units the maximum static pressure must be no greater than 1000kPa 10 bar If in any doubt the pressure should be checked Note If the stated flow rate is not available it may not be possible to achieve optimum performance from the unit throughout the year The water supply can be taken from a cold water storage cistern provided there is a minimum head of ten metres Minimum head is the vertical distance from the base of the cistern to the showerhead It must be an independent supply to the shower only If
27. terrupted power supply 1 2 Unit malfunction Action Cure 1 1 1 Blown fuse or circuit breaker Check supply Renew or reset fuse or circuit breaker If it fails again consult a qualified electrician 1 1 2 Power cut Check other appliances and if necessary contact local Electricity Supply Co 1 2 1 Have unit checked Ring Customer Service 2 Water too hot 2 1 Not enough water flowing through the shower 2 2 Blockage in supply 2 3 Increase in ambient water temperature 2 1 1 Increase flow rate via temperature control 2 1 2 Blocked showerhead clean or replace blocked sprayplate in showerhead 2 2 1 Check if stop valves are fully open Check if blockage in inlet filter 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select economy power 3 Water temperature cycling hot cool at intervals 3 1 Heater cycling on outlet thermal cut out 3 1 1 See Water too hot causes 2 1 2 2 and 2 3 and their appropriate action cures If it continues contact Triton Customer Service 4 Water too cool or cold 4 1 Too much flow 4 2 Water pressure below minimum required see rating label 4 3 Reduction in ambient water temperature 4 4 Electrical malfunction or safety cut out operated 4 1 1 Reduce flow rate via temperature control 4 2 1 Is water supply mains or tank fed 4 2 2 If tank fed replumb to mains water supply or see 4 2 4 4 2 3 f mains fed make sure that th
28. than bathrooms all socket outlets in those rooms must be protected by a 30mA RCD The current carrying capacity of the cable must be at least that of the shower circuit protection see Table B To obtain full advantage of the power provided by the shower use the shortest cable route possible from the consumer unit to the shower It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand voltage drop and cable size there is a maximum permissible circuit length The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit The current rating will be reduced if the cabling is bunched with others surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30 C Under these conditions derating factors apply and it is necessary to select a larger cable size 9 2 9 3 In the majority of installations the cable will unavoidably be placed in one or more of the above conditions This being so it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation In any event it is essential that individual site conditions are assessed by a competent electrician in order to determine the correct cable size and permissible circuit length Table B Twin and earth PVC insulated cable Current carrying capacity I
29. ting the cover and subsequent operation of the unit may be impaired TRITON T70si FITTING THE SHOWER TO THE WALL WARNING Check there are no hidden cables or pipes before drilling holes for wall plugs Use great care when using power tools near water The use of a residual current device RCD is recommended Note The control knobs are an integral part of the cover DO NOT attempt to remove them Unscrew the two top and one bottom retaining screws fig 6 and lift the cover from the backplate Entry positions for the mains water and electric cable are from the top bottom either side or from the back Note Deviations from the designated entry points will invalidate product approvals If bottom entry has been chosen fit the appropriate cut out in the top of the backplate fig 7 If top entry has been chosen fit the appropriate cut out in the bottom of the cover fig 8 If side entry is required the cover will have to be cut out Carefully remove the appropriate area by using a knife or junior hacksaw fig 9 If installing a feed pipe from the back or bottom the centre of the inlet valve to the wall surface is 20 mm fig 10 Note If entry is from the back the nut of the compression fitting will be partially behind the surface of the wall fig 10 This area MUST be left clear when plastering over the pipework in order to make the nut accessible for future adjustments
30. ut out If ever the water becomes too hot and you cannot obtain cooler water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cover and backplate and possibly damage the sealing rubber T70si electric shower MAIN COMPONENTS Fig 1 Inside unit fig 1 1 Top cable pipe entry 1 2 Wall screw fixings 3 Cover screw fixings hae 4 Thermal safety cut out main 5 Power selector assembly 6 Can and element assembly 7 Pressure switch assembly 8 Stabilising valve 9 Terminal block 10 Earth connection fis 11 Solenoid valve 12 Water inlet NI 13 Outlet temperature limiter i 14 Pressure relief device 15 Shower outlet N g L NOTE Not all wires are shown for reasons of clarity X A ELECTRICAL REQUIREMENTS WARNING THIS APPLIANCE MUST BE EARTHED The installation supply cable and circuit protection must conform with BS 7671 IEE wiring regulations and be sufficient for the amperage required The following notes are for guidance only 1 The shower must only be connected to a 230 240V ac supply If you are installing a shower with a kilowatt rating

Download Pdf Manuals

image

Related Search

Related Contents

StarTech.com 1 ft Mini DVI to DVI-D & HDMI Splitter Cable - M/F  Screen settings  BTouch - Swissvoice.net  ASUS X72JR-TY123V notebook  FS-ー 。。c 型式 FS・50A  03-Jan-2015 17:28    Samson 65 User's Manual      

Copyright © All rights reserved.
Failed to retrieve file