TA4 THERMAL ANEMOMETER OPERATING INSTRUCTIONS

image

Contents

1. PRESSZERO shown will be displayed briefly after BO OD te Imin the unit is switched ON nai Isec CJ CS3 oa Cee eli DT Battery cover This slides and snaps in at the rear of the case Telescopic probe and cable The telescopic probe gives an extended length of about 900mm With the coiled cable fully extended the maximum reach from the instrument case is approximately 2 metres Direction of flow indicator Align with the arrow head on the probe cap Velocity measuring thermistor Compensating and temperature measuring thermistor Range 0 800C Zeroing cap for velocity sensor Direction of flow arrow head on end of probe USING THE INSTRUMENT Switch ON the instrument Check for LOBAT low battery on the display If necessary change the battery cells before taking measurements Refer to section 2 Zero the instrument With the zeroing cap covering the velocity thermistor to isolate it from any air movement press zero When zeroed the display press zero will disappear For optimum accuracy it is necessary for the instrument to be rezeroed with the probe at the operating temperature and zero velocity At switch on either Metric or Imperial units will be displayed depending upon which was selected when last used To change the units from one to the other press the I M switch 4 5 4 6 47 4 8 4 9 4 10 To set a duct area press the vel vol area switch sequenti
2. to the temperature of the air inside the container Press Key 2 zero key the instrument will enter the input as the zero calibration point and will then display 5 00 m s 2 Place the probe tip in an air stream set to a velocity of precisely 5 00 m s and allow at least 10 seconds for the probe to stabilise to this condition Press key 2 the instrument will enter this as calibration data and then display 10 00 m s 3 Set the air stream velocity to 10 00 m s precisely allow 10 seconds to stabilise press key 2 and the instrument will then display 20 00 m s 4 Set the air stream velocity to 20 00 m s precisely allow 10 seconds to stabilise press key 2 and the instrument will then display 30 00 m s 5 Set the air stream velocity to 30 00 m s precisely allow 10 seconds to stabilise press key 2 and the instrument will then display Cal end The velocity calibration is now complete press key 2 to return to normal read mode A calibration accuracy check may now be performed if required WARNING ALTERING THE CALIBRATION WILL INVALIDATE AIRFLOW S RESPONSIBILITY FOR CALIBRATION UNDER WARRANTY The unit monitors each time the calibration is effected If the calibration routine is inadvertently entered then ABORT immediately by switching the instrument OFF and then retry SERVICE AND RECALIBRATION If a fault or the instrument s calibration is suspected it should be returned to Airflow Developmen
3. 1 4825 Fax 201 691 4703 AIRFLOW LUFTTECHNIK GmbH o s Praha Hostynska 520 108 00 Praha 10 Malesice Czech republic Telefon a fax 02 77 22 30
4. 1 5 volt AA size cells are required which may be either disposable or rechargeable types Either Standard or Alkaline disposable cells may be used but the Standard type will exhibit a relatively short life and are therefore not recommended Low battery condition is indicated by LOBAT appearing on the instrument display The cells must be replaced as soon as possible to maintain optimum accuracy The battery cells are accessible by means of the slide and snap in cover at the rear of the instrument case To remove the battery cover press firmly on the cover and slide it in the direction of the arrow A tape is now fitted in the battery compartment to ease the removal of the battery cells and the use of a small screwdriver will also assist Ensure that the battery cells are replaced with the correct polarity as indicated by the diagram in each cell compartment Rotate the cell slightly forwards and backwards to check that the cell is properly seated in the cell compartment DESCRIPTION OF THE INSTRUMENT Refer to FIG 1 instrument case Keypad area ON OFF slide switch On powering up initially all the display segments will be shown briefly on the display followed by a countdown from 9 down to 1 The display will then indicate either velocity or volume flow and temperature of the probe in the units previously selected vel This key sequentially selects on each key press either velocity vol volume or area display mo
5. 2 x 1 25 in 360 gm 12 7 Oz Four 1 5 volt AA type Alkaline Standard or Rechargeable cells Approximately 15 hours using Alkaline battery cells Accuracy is at ambient conditions of 20 C and 1013 mb 68 F and 30 in Hg CE Marking The unit complies with the EEC Directive on Electromagnetic Compatibility EMC 89 336 EEC Applied Harmonised Standards EN50081 1 Radiated Emissions and EN50082 1 Radiated and ESD Immunities The statements and opinions contained in this document are made and expressed in good faith Whilst every effort has been made to provide reliable information Airflow Developments Limited do not hold themselves responsible for possible errors of an editorial or other nature however caused Should you require a more detailed specification for a product described herein please contact our Sales Department In view of our continuous programme of improvement we reserve the right to change the specification for any model or item described in this publication AIRFLOW AIRFLOW DEVELOPMENTS LIMITED Lancaster Road Cressex Business Park High Wycombe Buckinghamshire HP12 3QP England Telephone 01494 525252 443821 Facsimile 01494 461073 E mail info airflow co uk WWW hitp Awww airflow co uk airflow AIRFLOW LUFTTECHNIK GmbH Postfach 1208 D53349 Rheinbach Germany Telefon 02226 9205 0 Telefax 02226 9205 11 AIRFLOW TECHNICAL PRODUCTS inc 23 Railroad Avenue Netcong N J 07857 USA Telephone 201 69
6. 9021045 B 297 SPECIALISTS IN AIR MOVEMENT TECHNOLOGY imenom NS STS TR OR ET PORTICO AE SAP CAESAR ARP ITA BSR STE DSTI TE SE CE SE PPL ELIE TSE SOA ASI LE CELLS EET LEE CE EN LEST Aa E A TI TRIE PORT POEL ECE OP AEA GE TAT PAA AP AERIS EGNOS TA4 THERMAL ANEMOMETER OPERATING INSTRUCTIONS Please read these instructions carefully before using the instrument Shortform instructions are on the back of the instrument 3 1 3 2 3 2 INTRODUCTION The TA4 is a battery powered hand held instrument with a digital LCD display capable of measuring the velocity volume flowrate and temperature of air by means of a thermal probe The unit allows the airstream area to be entered for volume measurement Measurements may be displayed in either Metric or Imperial units as selected from the keyboard After selection this will be remembered by the instrument until reselected from the keyboard The attached thermal anemometer probe has a tip diameter of 8mm and is therefore suitable for measurements at grilles slot diffusers and in small ducts where large access holes are not acceptable The velocity sensor in the probe is compensated for variations in airstream temperature by means of a second thermistor which also senses and displays the actual airstream temperature in either metric or imperial units consistent with the units selected for velocity BATTERY INFORMATION The TA4 instrument is supplied without battery cells fitted Four
7. ally until area is displayed followed by its current setting in either m or ft2 depending upon the units previously selected for velocity volume Area units are automatically converted when using the I M switch Increment or decrement the area to its required value by means of the area or area key Note that holding either of these keys down will increment or decrement the duct area at an increasing rate dependent upon how long the key is held down Reselect velocity or volume flowrate mode by means of the Vel Vol Area key Extend the telescopic probe axially by pulling on the smallest section taking care not to damage or stress the probe tip and ensure that the cable slides freely into the handle end of the probe Remove the zeroing cap and ensure that the direction of flow indicator on the probe handle is aligned with the flow arrow on the probe cap Offer the probe head into the airstream pointing the arrow or direction of flow indicator if the head is inside a duct into the airstream in the direction of flow and read the velocity and temperature of the airstream To use the probe inside ducting a 9 5mm 3 9 diameter minimum hole is required in the duct wall If a duct traverse is required it may help to use the joints between the telescopic tubes as markers to determine the probe head position When closing down the the telescopic probe ensure that the cable slides
8. des area J This is a dual function key In either Velocity or Volume modes this key allows the units to be changed sequentially between Metric and Imperial on each key s press In Area mode the lower case option is selected which allows the area airstream area to be incremented on each key press or by holding the key down The rate of change of duct area will progressively increase the longer this key is held down This is a dual function key After power up initialisation or when either Velocity or Volume flow modes have been selected this key allows the unit to be zeroed zero see section 4 3 area In Area mode this key allows the airstream area to be decremented J on each key press or by holding the key down The rate of change of the duct area will progressively increase the longer the key is held down 210 DIRECTION ajn jia OF FLOW SLOW onorr a a as 3 3 DISPLAY _ Haoni A ie y L i m 3 9 zeRoina cap Pt al Oc fal ied Uk ea ai JPF o L Ea i 31 INSTAUMENT CASE a l 3 7 VELOCITY 2 at THERMISTOR _ o iN i a 4 8 TEMPERATURE 3 2 KEYPAD AREA MEASURING AND I COMPENSATING see LN THERMISTOR 36 DIRECTION OF FLOW INDICATOR tens 4 4 BATTERY COVER cn 4 5 TELESCOPIC ON REAR OF CASE PROBE AND CABLE 3 3 3 6 3 8 3 9 4 1 4 2 4 3 4 4 Display B g g AY oma J LOBAT All the character segments as
9. e Function Code The code entered at this point will govern which SETUP function is chosen Assuming that the keys are numbered as follows Top key 1 middle key 2 and bottom key 3 then the function key codes are as given in the following table CODE FUNCTION PURPOSE o 21132 Calibration mode Push button calibration of apaci ai or velocity 11332 HELP routine To assist in fault diagnosis Each code keypress must be made within 15 seconds of each other or the instrument will revert to its normal read mode Each valid key press will result in a segment bar appearing at the bottom of 7 3 7 4 the display lf a non valid code is entered the instrument will revert to its normal read mode HELP Routine Code 11332 The unit will display HELP for a period of two seconds and will then display all the display segments as shown in section 3 3 with Press Zero shown flashing check that all the display segments are present Pressing the Zero key will move the unit through a series of internal tests The unit will display PASS if it is functioning satisfactorily or display an error message if a test has failed The significance of each error message is as follows Lobat Low battery condition or fault in low battery circuitry The HELP routine will not proceed while this prevails Change the batteries and retry Error 1 The eeprom read
10. elocity interspersed with areas of low a n SEE 7 1 7 2 velocity The transitions between these areas are highly turbulent and there may even be some reversed flow If maximum accuracy is required it is advisable to make up a short length of test ducting which is just larger than the overall dimensions of the grille This duct can be of any convenient rigid material such as stiff cardboard and it should have a length of about twice the diagonal measurement of the grille The duct should be placed over the grille and sealed to the wall with adhesive tape Measurements of flow can now be conducted as already described at the unobstructed end of the test duct Ensure that the cross sectional area of the duct not the grille is entered in the TA4 CHECKING THE INSTRUMENT The TA4 instrument is provided with a SELF TEST routine called HELP and a CALIBRATION routine which may be accessed from the SETUP mode The calibration is a pushbutton procedure with the calibration data being stored in non volatile memory Calibration is in metric units only For optimum accuracy perform a Temperature calibration prior to a Velocity Calibration SETUP Mode The SETUP mode is entered as follows With the instrument switched OFF Hold down any key while switching the instrument ON The following messages will be sequentially displayed SETUP then V This is the instrument s software version number which may change then Cod
11. f the reduced velocity at the duct walls A more precise method is shown in BS1042 Part 2 the Log Tchebycheff method The positions for siting the probe for circular or rectangular ducts or apertures is shown in the following figures Position of alternative measuring points and traverse lines relative to side lengths for rectangular ducts No of 0 321D gt 0 6790 gt traverse Ines 0 865D lt _ _0 968D 6 10 061 0 235 0 437 0 563 0 765 0 939 0 053 0 203 0 366 0 5 0 634 0 797 lt ni 0 947 i Log Tchebycheff Rule for Rectangular Ducts Log Linear rule for traverse points on 3 diameters in a circular duct Distance between measuring stations l Should not exceed 200mm Note Should difficulty in access make it impossible to traverse on more than two diameters these should be mutually at right angles and the number of points on each line must be increased to 10 The spacing should be as follows 0 019D 0 0770 0 153D 0 217D 0 361D 0 639D 0 783D 0 847D 0 923D 0 9810 The previous procedure is satisfactory for use in ducts and unobstructed apertures however significant errors may occur if the aperture is covered by a grille particularly if this is of the type having adjustable direction vanes or dampers The airstream issuing from such a grille is invariably very disturbed consisting of many small areas of high v
12. freely back through the probe Always switch OFF when not in use to extend battery life WHERE TO USE THE INSTRUMENT Checking the air velocity or volume flowrate over large areas When measuring velocity or volume flowrate over a large area a number of readings must be taken spaced to give an even coverage of the whole area The average of these readings will give the mean velocity over the whole area or the mean volume flowrate It should be noted that quite large variations in readings may be observed and in general the larger the number of readings taken the more accurate the mean velocity or the mean volume flowrate will be The mean velocity or mean volume flowrate the sum of all the readings taken the number of readings taken 5 2 Use on grilles Avoid intrusion of the arm and hand into the face area of the grille The blockage effect would cause artificially high velocity over the remainder of the grille leading to incorrect readings The telescopic probe can be useful in avoiding this problem Better measuring conditions can be obtained on grilles with adjustable direction vanes if the vanes are temporarily straightened before taking measurements This should not significantly affect the flowrate so long as any built in dampers are not accidently disturbed The instrument is suitable for both supply and extract grilles and the procedure is the same for both POSSIBLE SOURCE OF ERRORS The above method ignores the effects o
13. ts for repair or recalibration to original standards In any event it is good practice to have the instrument checked at least once a year If an instrument is not working correctly or requires recalibration contact your nearest Airflow Agent or U K Service Department on High Wycombe 01494 525252 International 44 1494 525252 Airflow Developments operate an Instrument Hire Service for the convenience of customers having equipment repaired or recalibrated If you intend to take advantage of this facility please contact our service department to make arrangements prior to returning your instrument 9 SPECIFICATION PARAMETER METRIC IMPERIAL Velocity Range 0 30 m sec O 6 000 ft min Accuracy 3 of reading 1 digit or 3 of reading 1 digit or 0 06 m s 1 digit 12 ft min 1 digit whichever is the greater whichever is the greater Volume Flow Range 0 2 700 m sec 0 999 999 ft min Accuracy 3 of reading 1 digit or 3 of reading 1 digit or 0 06 x input Area m sec 12 x input Area ft min 1 digit whichever is the 1 digit whichever is the greater greater Temperature Range 0 80 C 32 176 F Probe Accuracy 1 C 1 digit 2 F 1 digit Airflow Area Range 0 008 90 m 0 08 900 f Ambient Operating Temperature 10 to 50 C 14 to 122 F Indicator unit Storage Temperature 20 to 60 C 4 to 140 F 185 x 92 x 30 mm 7 25 x 3 6
14. write function is not satisfactory Error 2 The reference voltage is incorrect or the internal oscillator is faulty Error 3 The probe is missing or incorrectly connected Note if either of these two messages appear please contact Airfow Service Department immediately Calibration routine Function code 21132 entered The instrument will display CAL TEMPERATURE Calibration Routine Specialised equipment is required for temperature calibration for information please contact Airflow Developments Limited Airflow Lufttechnik GmbH or Airflow Technical Products Inc VELOCITY Calibration Routine For velocity calibration a stable air flow is required with a setting resolution of 0 2 of reading and a velocity accuracy better than 0 5 of reading Airflow can supply an Open Jet Wind Tunnel together with associated instrumentation suitable for this purpose please contact Airflow Sales Department for details To select VELOCITY calibration press key1 1 On entry to the velocity calibration routine 00 00 m s will be displayed and a counter which decrements from 9 down to 0 The unit will ignore any keypress while the counter is displayed To set the zero for optimum performance it is preferable that the probe tip is totally enclosed in a container rather than the Zeroing Cap to shield the probe tip from surrounding draughts Allow 20 to 30 seconds for the probe tip to fully stabilise

Download Pdf Manuals

image

Related Search

Related Contents

PlanIT 3.1 User Manual  Preparación de tampones con FlexAct® BP  User Manual Power and Harmonics Analyzer Model PQ3350  HoMedics AR-45 Downloadable Instruction Book  Indesit FIM 21 KB BK  Flash EF-610 DG ST  SonicWALL ViewPoint Network Card User Manual  Samsung SGH-Z300 Benutzerhandbuch  HE200CGM100 - Logic, Inc.  Samsung YP-U2Q User Manual  