        OPERATING INSTRUCTIONS FOR: M15n – Jockey Pump Controller
         Contents
1.  stop     Visual  Motor Running goes out   Volt free  Motor Running not indicating   When the Mode Switch is set to Auto and system pressure is above Pressure Switch set point     The pump will remain stopped until the system pressure falls below Pressure Switch set  point     METRON ELEDYNE CONTROL SYSTEMS  M15n   Jockey Pump Controller  MOTOR OVERLOAD    Motor running with excessive current due to a motor fault or a supply phase missing     After a delay depending upon the degree    of overload  Overload unit trips and the motor stops   Visual  Motor Running goes out    Motor Overload   Volt free  Motor Running not indicating    Motor Overload     Set the mode switch to Off     The controllers Mode Switch can be switched back to Auto after the fault has been rectified   and if necessary the Overload unit has been reset     Note  For Dual Motor controllers  visuals and volt frees are Motor Overload 1 and Motor  Overload 2 respectively     OPTIONS    e ANTI CONDENSATION HEATER   Ambient temperature below thermostat set point  The heater warms     Ambient temperature above thermostat set point  The heater cools     e MOTOR HEATER    The Motor Heater supply is only available when the motor is NOT running     e PRESSURE SWITCH  e Standard  Danfoss Type RTS or Allen Bradley of stainless steel type   e Alco  Type FF444   VDAF     e Standard as above with Manual Drain Handle  MDV     METRON ELEDYNE CONTROL SYSTEMS  M15n   Jockey Pump Controller    TABLE OF CONTENTS  SECTION PAGE  C
2. AUTION 1  GENERAL 1  ENERGISING THE SYSTEM 1  MANUAL CONTROL 2  AUTOMATIC CONTROL 2  MOTOR OVERLOAD 3  OPTIONS 3    HUBBELL    
3. METRON ELEDYNE CONTROL SYSTEMS  M15n   Jockey Pump Controller  OPERATING INSTRUCTIONS FOR     M15n     Jockey Pump Controller       CAUTION    In order to avoid risk of personal INJURY or damage to the control equipment  READ THIS  MANUAL VERY CAREFULLY  If after reading these instructions doubt exists  do not  hesitate to contact Metron Eledyne for further clarification  In the interests of safety pay  special attention to the CAUTION notes listed below     If work has to be carried out on the motor or control equipment  ensure the control equipment  is ISOLATED AND LOCKED OFF from the A C mains supply before work commences  If  possible use a temporary label which draws attention to this fact  Label suggestion  Caution  ENGINEER WORKING ON EQUIPMENT        The control system operates automatically from the pressure switch  and may start the motor  at any time  Ensure all concerned are aware of this condition by means of an appropriate  label  prominently displayed in the motor area  Label suggestion  WARNING MOTOR MAY  START AT ANY TIME     In order to avoid the risk of serious electric shock  NEVER energise the control system with  the access door open unless absolutely necessary  Care must be taken when dealing with the  pressure switch  which has control circuit voltage at the switch contacts when the panel is  energised        If the access door to the interior of the panel has to be opened when the panel is energised   BEWARE of the three phase motor supply and the sin
4. gle phase control circuit supply  This  warning cannot be stressed enough    GENERAL   The Metron Eledyne Jockey Pump Electric Motor Controller type M15n is designed for  across the line or Star   Delta starting of electric driven pumps  The unit is self contained and  self monitoring  with volt free outputs to facilitate remote monitoring  It also has the option  to control dual motors  with a Motor 1   2 Selector Switch    ENERGISING THE SYSTEM    Ensure that the controller is connected in accordance with the circuit diagram     Set the Mode switch to off   Close the AC isolator     Visual  Control Circuit Healthy     Volt free  Control Circuit Healthy indicating     METRON ELEDYNE CONTROL SYSTEMS  M15n   Jockey Pump Controller    MANUAL CONTROL  Set Mode switch to Hand   Visual     Volt free     Turn the mode switch to the off position     Visual     Pump starts    Motor Running    Motor Running indicating   Pump stops immediately     Motor Running goes out     Volt free  Motor Running not indicating     AUTOMATIC CONTROL    Set the Delay Start Timer T1  the Auto Stop  Minimum Run  Timer T2  and the Pressure  Switch set point to suit the site operating conditions     Set Mode Switch to Auto     Visual  Auto Mode    Volt free  Auto Mode    If pressure falls below Pressure Switch set point  Pump starts    Visual  Motor Running    Volt free  Motor Running indicating     When pressure rises above the set point of the Pressure Switch and the delay time set by T2  the motor will
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
warnung - Victor Technologies  Texte complet - Société Provancher  GHS 開発ガイドライン 適合宣言 実施ガイド  Origin Storage 250GB TLC SATA 2.5"  Instrukcja obsługi HB 5010  Untitled    Delaney 515T-VI-US26 Instructions / Assembly    PH-16CWQFS(F)    Copyright © All rights reserved. 
   Failed to retrieve file