Home

Prescient III Installation Manual

image

Contents

1. iof E EOL Connections Connections to SLU 05 Normally gt 2 Normally Normall nor gt Open Nemal desea ances I azg 332 Pressure in Low Pressure Pressure 5606828533559 3 g Switch Switch Switch o 2 2 e 3 d z 2 d z 2 po dl Fd 00 1 G O O OO OJO O O i M Fg JJ _ zl I t t ELE 2 at ee Se et oe RA 42142 Hu x x 5 5 5 GAS REL GAS ISO GAS LOW VALVE TRAPPED Panel Terminals PAGE 39 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION ISSUE amp DATE 0 02 02 12 12 4 Monitored Outputs Connection Diagram These Outputs are Reverse polarity monitored at 5VDC They are Active at 28 VDC Nominal Each Output can be configured independently for Volt Free contacts by removing the relevant links on the motherboard The volt free contacts are rated at 1 Amp 30 VDC maximum DO NOT SWITCH AC VOLTAGES THROUGH THESE CONTACTS Gas Released Output Fault Output Normally de energised Normally energised Relay Relay 1 Stage Shutdown Output a m Grut Norrnally de energised lt mA CSV to SOV D Relay Coil current
2. for any open or short circuit fault on the Gas Low input llluminates for any open or short circuit fault on the Gas Released input Illuminates for a fault on any Status Lamp Unit Illuminates when either the CONFIG 6 INPUTS or the CONFIG SLU DIL switch is in the ON position It indicates that the EEPROM on control board is write enabled llluminates for any open or short circuit fault on the Gas Released Signal output llluminates if the AC mains input voltage to the power supply is lost or is less than the required minimum for correct operation of the power supply llluminates for any of the faults described in section 3 11 The General Fault LED on the Display board also pulses for any of the above faults 3 14 Internal Buzzer The internal buzzer provides an audible indication to compliment the visual indications provided via the LEDs on the panel The buzzer has various modes as follows 1 Fault Indication Pulse 1 second On 3 seconds OFF The buzzer can be silenced 2 Alarm Indication Pulse 1 second On 1 second OFF The buzzer can be silenced 3 Buzzer Pulse End Of Delay Pulse Ya second On Y second OFF Optional The buzzer cannot be silenced PAGE 14 of 43 EQUIPMENT FIRECLASS Prescient lll PUBLICATION OMFCPRESSIN ISSUE No amp DATE 0 02 02 12 WRITTEN BY RKP CHECKED BY AP 3 15 Display Board General The left window displays the status of the F
3. PAGE 4 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 Figure 2 Motherboard Terminal Identification Part 1 Repeat Output Isolation Valve Abnormal Repeat Output Isolation Valve Closed 2 Repeat Output Actuators Disabled 0 Repeat Output Emergency Abort Activated 3 Panel in Manual DIL SW Selectable Repeat Output Emergence Hold Activated Panel in Auto DIL SW Selectable Repeat Output Manual Release Activated 1 Repeat Output Auxiliary Zone Fire Z2 AUX MR Repeat Output Zone 2 Fire Repeat Output Zone 1 Fire 21 Input Auto Manual Mode Select Switch 10K EOL 4K7 Manual Only Mode Status Input Gas Trapped in Manifold 10K EOL 680R Activation Remote Control Input 10K EOL 4K7 Sound Alarms 1K8 Silence Alarms 560R Reset System Status Input Isolation Valve Status 10K Abnormal 2K2 Open 680R Closed Input Emergency Hold Switch status Input Low 10K EOL 680R Activated 10K EOL 680R Gas Low DIL SW configurable for Normally closed operation Input Emergency Hold Switch 10K EOL 680R Activated Status Input Gas Released Pressure Switch 10K EOL 680R Activated Manual Release Input 21VDC 10K EOL 680R Activated DIL SW configurable for 3K9 EOL Auziliary Zone Inpu
4. REMOTE CONTROLS input status is displayed by two LEDs The red LED is normally off illuminating steady when the input registers a Sound Alarms The yellow LED is normally off pulsing for an open or short circuit fault the Remote Controls input 3 16 7 FIRE SOUNDER FAULT DISABLED This is a yellow LED which is normally off pulsing for an open or short circuit on either of the general sounder circuits illuminating steady when the general sounder circuits are disabled A separate fault LED for each sounder circuit is also provided on the control board inside the panel 3 17 Display Board Common Status Indications 3 17 1 POWER SUPPLY ON This is a green LED which is illuminated steady as long as there is a supply of power to the panel 3 17 2 GENERAL FAULT This is a yellow LED that is normally OFF The LED pulses for any fault on the panel 3 17 3 POWER SUPPLY FAULT This is a yellow LED that is normally OFF The LED pulses if there is a mains or battery failure 3 17 4 SYSTEM FAULT This is a yellow LED that is normally OFF The LED pulses if the CONFIG I S INPUTS or CONFIG SLU DIL switch is in the ON position The LED is steady if the microprocessor fails to execute the software correctly or internal memory corruption is detected Note The system is completely non functional and alternative fire detection measures should be implemented 3 17 5 EARTH FAULT This is a yellow LED that is normal
5. OUTPUTS Zi Z2 AUXMR 1 2 4V OV 24V OV A B 2 olo ejo eje e oje ojo ojo o EA INSI Panel Terminals side 2 Enclosure 12 6 Glossary 1st Stage Pre activated Fire condition on zone 1 or zone 2 in system Automatic with panel configured to double knock mode 2nd Stage Activated Pre discharge time delay running 3rd Stage Activated Pre discharge timer ended actuators activated Discharged Released Release of gas confirmed by signal from discharge pressure switch or when panel configured to No discharge pressure switch mode actuator activated PAGE 41 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRES3IN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 13 Mechanical Electrical amp Environmental Specification Mechanical Specification Size mm HxWxD 370mm X 325mm X 125mm Weight excluding batteries 4 85Kg Mains Input Specification Maximum Input current 1 6A Protection T5AH250V Warning Replace only with identical type amp rating 20mm fuse 5A HBC Anti surge approved to BS EN of BEAB or VDE approved fuse 60127 or equivalent Input Voltage 230V AC 10 15 Cable requirements Minimum of 1mm copper protected by a 5A fuse Panel Integrated Power Supply Output Specification Maximum Short Term Current Output I max b 4 8A Maximum Continuous Current I max a 1
6. PUBLICATION ISSUE amp DATE 0 02 02 12 8 Panel Installation The control panel must be installed by suitably qualified technicians familiar with the installation of fire detection amp extinguishing systems In addition it is recommended to refer to the following information 1 Current edition of the IEE wiring regulations 2 Current edition of BS5839 1 or the installation standards for the relevant country 3 Any site specific requirements 4 Any field device installation instructions 5 Any data sheet provided for the installation of Intrinsically Safe devices WARNING Head this section completely before commencing installation Prior to commencing installation of the control panel ensure that adequate precautions are taken to prevent damage to the sensitive electronic components on the control board due to electrostatic discharge You should discharge any static electricity you may have accumulated by touching a convenient earthed object such as an unpainted copper radiator pipe You should repeat the process at regular intervals during the installation process especially if you are required to walk over carpets The panel must be located in a clean dry position which is not subject to shock or vibration and at least 2 metres away from pager systems or any other radio transmitting equipment The operating temperature range is 5 C to 40 C maximum humidity is 95 8
7. Sounder Sounder ET 1 Sndr2 Test pi opa Coincidence M detection EN A 2 i Zone 2 Z2 Z2 Internal Ext Sndr Fault Fault Fire Disabled Auxili Aux Zone Aux Aux i gt P Extinguishin detection Zone Internal Disabled 5 Act 1 fit Act 2 fit Gas discharged Peleased dap e ju pressure switch bL Open amp short cct flt monitored Gas Low Lus 680 Ohm Ext Low Low pressure switch low weight Gas isolation Isolation Isolation ena valve Isol Valve Valve Valve Fault Open amp short cct flt Internal Valve Stuck Abnormal Abnormal Closed monitored I P e O 6800hms V Closed S D SD 5 0 Valve Closed Isol Valve 2 2 V Abnormal See valve Closed e wiring diag G Trapped in Internal Gas Trapped Manifold Fault Gas Trapped in Manifold Pressure nena 5 Outputs Switch isable Fault Panel Release e Internal Mar Fire Si i el aul i Ire ol Conventional panua Active Disabled NA Routing Fault Manual Release Ses O O Active Disabled Z Link configurable O Ps one nternal e SS e e Emergency EOS baut Open short cct fault Conventional Hol ctive Fau monitored powered at E Hold input L e L m OS when active Fault Si
8. This is a 2 digit numeric display It is normally blank When the pre discharge timer is running the remaining seconds left to discharge are displayed In CONFIG SLU mode the 2 digit display allows the SLU type codes to be programmed into the panel see section 4 2 3 3 19 Display Board User Controls The Display Board provides user controls via buttons behind the membrane of the display board All buttons except for TEST for Test Display are disabled until the ACCESS CONTROLS key switch is rotated to the ON position The panel acknowledges a button press by sounding the internal buzzer briefly The following controls are available 3 19 1 SILENCE ALARMS This button silences the general sounder circuits and or silences the extinguishing sounder circuit when possible Silencing of the extinguishing sounder circuit is inhibited until the panel enters the Gas Released condition or the Abort input is activated The attached yellow LED is normally OFF It pulses when it is possible to silence any of the sounder circuits and is illuminated steady to indicate silenceable sounder circuits have been silenced 3 19 2 RESOUND ALARMS This button allows previously silenced alarm circuits to be resounded 3 19 3 FIRE RESET This button controls the resetting of fault and fire conditions on the Fire Alarm section of the panel Faults common to the Fire section amp the Extinguishing section can also be reset with this bu
9. 100mA Voltage 9V to 30V D 2 1N4002S DIODES OR EQUIVALENT 2x 1N4002S DIODES OR EQUIVALENT 2x 1N4002S DIODES OR EQUIVALENT Fire Signal Output wired same as Gas Released Output FAULT SIG GAS REL SIG FIRE SIG P P or C P O 3RD STAGE P 0 P 1ST STAGE 230 STAGE Panel Terminals PAGE 40 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 0242 12 5 Remote Outputs amp SLU Communication Connection Diagram D 2 2 93 8 OR 2 Y BOLO p 8 c OS m i 8 of amp E Connections to SLU I D E T zT 1 5 8 a 8 E g 11 89 8 y o3 BH 9 g 8 B gm 5 2 282803 8 r 2 3 oo T b Eg og 8 RIS ao S S gt 5 03 93 gt m y o a 5 aJ o 5 M o gt 2 9 0 US 2 m E x 78 5 3 flo 2 2 or26 8 gt 82848 3 go oo 9 5 5 2 y ae sc S S gt 2 gt Z gt og 5 Ql e ele Ln a 3282 E P 210000 nm 8 28 28 amp 8 3 o 8 S858 Y Current II III Minimum 470R a Tm IS ndicators Maximum ALA ARA Ry 3 4 5 Connected to Panel Earth Bar amp SLU Termination Cable Shield 50
10. ENVIRONMENTAL 3 16 2 242 42211 15 SPECIFICATION 42 3164 ZONE LLL 14 CONSTRUCTION PRODUCTS DIRECTIVE 43 3 16 5 2 15 3 16 6 REMOTE SOUND ALARMS 16 3 16 7 FIRE SOUNDER FAULT DISABLED 16 Figures 3 17 1 16 ed FIGURE 1 ENCLOSURE DIMENSIONS 4 3 17 4 SYSTEM 16 FIGURES S MOTHERBOARD TERMINAL TDENTIEIGATION 8475 _ 16 PART 1 5 3476 FUSE FAILED D he aol 16 FIGURE 3 MOTHERBOARD TERMINAL IDENTIFICATION 3 17 7 FAULT SIGNAL FAULT DISABLED 16 PART uera 6 3 17 8 16 FIGURE 4 PRESCIENT BLOCK SCHEMATIC DIAGRAM 3 18 1 amp lada dira 7 3 18 2 16 5 222 15 3 18 3 MANUAL RELEASE ACTIVE 16 FIGURE 6 POWER SUPPLY CONNECTION DETAILS 23 3 18 4 SYSTEM ACTIVATED 16 3 18 5 GAS RELEASED 16 3 18 6 GAS RELEASED SIGNAL ACTIVE 16 3 18 7
11. Link ON or Volt Free Link OFF In the Monitored mode an open or short circuit fault on the field wiring illuminates the Circuit Fault LED on the display and the 3 Stage Shutdown Fault LED on the motherboard FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP In the Volt free mode clean contacts for Pole Normally Open amp Normally Closed are available rated at 1A 30VDC 3 10 4 Gas Discharged GAS REL SIG The Gas Discharged Relay is energised when the Gas Released Pressure Switch input is activated or when the actuator circuits are operated if the panel is configured for NO PRESSURE SWITCH A triple jumper link allows the output to be powered and monitored Link ON or Volt Free Link OFF In the Monitored mode an open or short circuit fault on the field wiring illuminates the Circuit Fault LED on the display and the Gas Released signal Fault LED on the motherboard In the Volt free mode clean contacts for Pole Normally Open amp Normally Closed are available rated at 1A 30VDC 3 10 5 Fire Signal FIRE SIG The Fire Signal Relay is energised when zones 1 2 or Aux zone detect a fire condition A triple jumper link allows the output to be powered and monitored Link ON or Volt Free Link OFF In the Monitored mode an open or short circuit fault on the field wiring illuminates the Fire Signal Fault LED on the display In the Volt free mode clean contacts for Pole Normally Open amp Nor
12. Operate on Pre discharge Timer Ended or Man Release in Immediate mode Act 2 Max O P 1 Amp Each Plant Shutdown O P has 1 x OP link configurable as fault monitored powered when active as per fire routing O P or 1 x V F C O relay contact rated 1 Amp 24 VDC 1st stage Plant Shutdown Active on any fire Z1 or gt Z2 in auto Man Rel or Gas Released P S signal 2nd stage Plant Shutdown Active on coincidence fire on Z1 and Z2 in auto Man Rel or Gas Released P S signal 3rd stage Plant Active on Actuators Shutdown operated if no gt Discharged Pressure Switch or Gas Released P S signal Fire Si inei Routing Operates on any fire Z1 Z2 Aux Zone Fault Si Routing _ Operates de energises on any fault including Valve bnormal but not Valve Closed Gas Released Operates on Gas P S Routing active or Actuator operated when No Discharge P S mode RP E Hold Active or Panel in Auto RP E Abort Active or Panel in Manual B Actuators Extinguishing DIL Switch Selectable RP Isol Valve Closed p gt RP Isol Valve Abnormal c lt RP Fire Z1 RP Fire Z2 RP Fire Aux Zone EL RP Manual Release Operated 24V AUX 250 Output y Operating for 10 Seconds after operation of Fire Reset switch Aux Reset PAGE 7 of 43 EQUIPMENT PUBLICATION OMFCPRESS3IN ISSUE No amp DAT
13. RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 0242 14 Construction Products Directive 0086 Control Equipment Ltd Hillcrest Business Park Cinder Bank Dudley West Midlands DY2 9AP United Kingdom 08 0086 CPD 517159 EN54 2 Control and indicating equipment for fire detection and fire alarm systems for buildings Provided options e Outputs to fire alarm devices e Output to fault warning routing equipment e Test condition EN54 4 Power supply equipment for fire detection and fire alarm systems for buildings EN 12094 1 Electrical automatic control and delay device Environmental class A 1 flooding zone CO high pressure CO low pressure inert gas Halocarbon Provided options e Extinguishing system delay e Reception of a signal representing the flow of extinguishing agent e Monitoring of status of components Low pressure low weight e Reception of signal from an emergency hold device e Separate monitoring of the status of non electrical disable device s e Input from auto manual selector switches e Transmission of a triggering signal to equipment within the fire extinguishing system Optical warning devices e Transmission of signals to equipment outside the fire extinguishing system e Reception of signal from an emergency abort device e Activation of alarm devices with different signals Response delay activated condition maximum 3s Response delay triggering
14. The internal buzzer pulses d The fault output operates Re connect the detector and check that the panel returns to quiescent Repeat step 6 and 7 on zone 2 and the auxiliary zone Check that the zone detection circuits are monitoring the wiring for short circuits correctly For each zone in turn place a wire link across the end of line device and check that after a few seconds a The appropriate yellow Zone fault LED pulses b The General fault LED pulses c The internal buzzer pulses d The fault output operates Remove the link and check that the panel returns to quiescent Remove the end of line device from the Manual Release Zone terminals in the panel and connect the field cabling After a few seconds observe that the panel returns to the quiescent condition Check that the Manual Release Zone circuit is monitoring the wiring for open circuits correctly PAGE 31 of 43 EQUIPMENT PUBLICATION ISSUE No amp DATE 0 12 13 14 15 OMFCPRESSIN 02 02 12 by disconnecting the End Of Line resistor at the end of the circuit and checking that after a few seconds a The yellow Manual Release Fault Disabled LED pulses b The General fault LED pulses c The internal FIELD MR FAULT LED illuminates steady d The internal buzzer pulses e The fault output operates Re connect the EOL resistor and check that the panel returns to quiescent Check that the Manual Release Zone circuit is m
15. These should be on separate zones and the zones should be varied each week unless all zones are always tested 1 Check that sounder circuits 1 amp 2 operate 2 Remove the test key from all manual call points and clear all detectors of smoke WRITTEN BY RKP CHECKED BY AP 3 Press the Fire Reset button 4 Operate the test lamps switch and observe that all indications operate for 5 seconds and the buzzer sounds 5 Test one hold abort and one auto manual switch if fitted These should be on separate SLUs and should be varied each week 6 Check that operation of the hold switch indicates a hold condition on the SLU 7 Check that operation of the abort switch indicates an abort condition on the SLU 8 Check that operation of the auto manual switch changes the panel from automatic amp manual to manual only operation as indicated at the SLU 9 Operate test lamps on each SLU and observe that all indicators operate 10 Enter details of the weekly test in the log book ENSURE THAT NO DISABLEMENTS REMAIN ON THE PANEL 9 3 Battery Replacement The useful life of the sealed lead acid standby batteries in this panel is three years The batteries must be replaced after this period In addition the batteries should be tested annually in line with the manufacturer s recommendations and replaced if necessary The batteries should be labelled with the date of installation PAGE 34 of 43 EQUIPMENT
16. 1 Important Safety Considerations For Batteries DANGER Batteries are electrically live at all times take great care never to short circuit the battery terminals WARNING Batteries are often heavy take great care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery Electrolyte is a highly corrosive substance and presents significant danger to yourself and to anything else it touches In case of accidental skin or eye contact flush the affected area with plenty of clean fresh water and seek immediate medical attention Valve Regulated Lead Acid VRLA batteries are low maintenance requiring no electrolyte top up or measurement of specific gravity FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP WARNING Only clean the battery case with a cloth that has been soaked or dampened with distilled water Do not use organic solvents such as petrol paint thinner benzene or mineral spirits or other materials that can substantially weaken the case Do not use a dry cloth as this will generate static electricity which in turn may lead to an explosion WARNING Avoid operating temperatures outside A the range of 15 C 5 F to 50 C 122 F for float standby applications The recommended normal operating temperature is 20 C HIGH TEMPERATURE will re
17. 16 of 43 EQUIPMENT PUBLICATION OMFCPRES3 IN ISSUE No amp DATE 0 02 02 12 indication is latching and must be manually reset via the Extinguishing Reset button 3 18 8 EMERGENCY HOLD ACTIVE This is a yellow LED that is normally OFF It indicates that the pre discharge delay timer has been reset amp held therefore the release of the extinguishing gas has been suspended The LED pulses if the Hold input is active when the pre discharge delay timer is not running The LED is illuminated steady if the Hold input is activated or a fault occurs on the input during the pre discharge delay timer running The pulsed amp steady indications are non latching and clear when the input clears 3 18 9 CIRCUIT FAULT This is a yellow LED that is normally OFF It pulses to indicate that one of the circuits related to the Extinguishing system has an open or short circuit fault A separate LED on the control board inside the panel will indicate which circuit is in fault 3 18 10 GAS LOW This is a yellow LED which is normally OFF It pulses while the Gas Low input is active clearing when the input is cleared 3 18 11 GAS TRAPPED IN MANIFOLD This is a yellow LED which is normally OFF It pulses while the Gas Trapped input is active clearing when the input is cleared 3 18 12 ISOLATION VALVE ABNORMAL This is a yellow LED which is normally OFF It pulses while the Isolation Valve monitors an abnormal value nominally 10
18. 3A Minimum Output Current I min 0A Voltage Output Mains On 26 5 28 6V 27 15V nominal Maximum Current Output Mains Failed 4 8A Voltage Output Mains Failed 28 3V 19V Max Ripple including switching spikes 07V full load battery disconnected Output voltage adjustment Factory set Output protection Electronic current limiting Common fault output Not available to user Mains failed fault output Not available to user Battery Specification Battery charger output Temperature compensated float charger 5A 28 25V 0 1V 5 C 26 78 V 0 1V 50 C Maximum internal resistance of battery amp charger circuit Ri max 0 35 Ohms Battery type 2 off POWERSONIC PS12120 Warning Replace only with identical battery 12V 12Ah Battery size mm Ww L 151 ee W 98 Ili H 94 H HT 100 Battery circuit protection Warning Replace only with identical type amp rating F6 15AL250V 20mm fast blow glass fuse of fuse Mains failed fault battery current 60mA Ancillary equipment current 160mA 20mA to 50mA for each zone in alarm Ancillary equipment current Alarm circuit current Solenoid circuit current Mains failed alarm battery current Environmental Specification Operating temperature 5 to 40 Operating humidity 596 to 9596 PAGE 42 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY
19. E od TRANSORB 6 VOLT Unpolarised Solbnoid Bell MN NOTE Diodes amp Terminal Blocks are not supplied with the Panel Polarised Electronic Sounder SNDR2 amp EXT SNDR ACT2 wired wired identically to ird to SNR ACT SE Pedal NDA E 1 DO Panel Terminals PAGE 368 of 43 resistor is fitted This resistor is in series with the solenoid coil WRITTEN BY RKP CHECKED BY AP Actuator Solenoid Alternative Connection of Solenoid if C1565 Board is not used EQUIPMENT PUBLICATION ISSUE No amp DATE FIRECLASS Prescient Ill OMFCPRESSIN 0 02 02 12 12 3 Monitored Inputs Connection Diagram 1 Valve Full n 2 Valve 41522 Isolation Valve is monitored for open circuit short circuit abnormal fully open Closed states Isolation Valve must be fitted with two SPDT limit switches SW1 operates when valve is fully open SW when valve is fully closed m Local terminal box may be required to accommodate monitoring resistors Vave Open 680R AW ate Valve Closed 2K2 AW 1 Valve Not Closed 2 Valve Fully Closed 1K8 4W WRITTEN BY RKP CHECKED BY AP SILENCE ALARMS 560R 4W 5 EOL EC ee 10K 4W EOL
20. EMERGENCY ABORT ACTIVE 16 Tables 3 18 8 EMERGENCY HOLD ACTIVE 17 3 18 9 17 318105 GAS LOW Leite etes 17 TABLE 1 RESET INHIBIT SETTINGS 13 3 18 11 GAS TRAPPED IN MANIFOLD 17 TABLE 2 CIRCUIT 18 3 18 12 ISOLATION VALVE ABNORMAL 17 TABLE FLOAT CHARGE VOLTAGES FOR 3 18 13 ISOLATION VALVE CLOSED 17 lt VRLA BATTERIES 23 3 18 14 MANUAL RELEASE FAULT DISABLED 17 3 18 15 EXTINGUISHING DISABLED 17 3 18 16 GAS RELEASED SIGNAL DISABLED 17 3 18 17 SHUTDOWN OUTPUTS DISABLED 17 3 18 18 SECONDS TO DISCHARGE 17 3 19 1 SILENCE 17 3 19 2 RESOUND ALARMS 17 3 19 8 17 3 19 4 EXTINGUISHING 17 3 19 5 SILENCE BUZZER 18 3 19 6 AUTO amp MANUAL MANUAL ONLY 18 PAGE 2 of 43 EQUIPMENT PUBLICATION OMFCPRESSIN ISSUE No amp DATE 0 02 0242 1 Introduction The FIRECLASS Prescient Ill Gas Extinguishing Control Panel is a stand alone panel intended for use with gas extinguishing systems It has been designed and approved to the Europ
21. LED pulses d The internal buzzer pulses e The fault output operates Remove the link amp check that the panel returns to quiescent FIRECLASS Prescient 16 17 18 19 20 21 22 23 24 WRITTEN BY RKP CHECKED BY AP Repeat steps 13 to 15 for alarm circuit 2 and the extinguishing alarm circuit Ensure that the Actuators are disconnected from the circuit cabling and are replaced with a suitable load as described above Remove the end of line device from the Actuator Circuit 1 terminals in the panel and connect the field cabling After a few seconds observe that the panel returns to the quiescent condition Repeat open circuit amp short circuit tests on actuator circuit 1 and check that the control panel reacts as follows a The Circuit fault amp General fault LEDs pulse b The appropriate Actuator Fault LED on the control board illuminates The internal buzzer pulses d The fault output operates Repeat Steps 18 and 19 on Actuator circuit 2 Any additional monitored circuits being used should also be connected in turn and checked for correct open short circuit fault monitoring by removing or short circuiting the EOL resistor on each circuit and checking that the correct fault indication is given on the panel Fault indications should clear once the EOL resistor is returned to normal Check that the MANUAL ONLY LED is illuminated If not press the AUTO amp MAN MANUAL
22. OFF ON OFF 9 ON OFF OFF ON OFF 10 OFF ON OFF ON OFF 11 ON ON OFF ON OFF 12 OFF OFF ON ON OFF 13 ON OFF ON ON OFF 14 OFF ON ON ON OFF 15 ON ON ON ON OFF 16 OFF OFF OFF OFF ON 17 ON OFF OFF OFF ON 18 OFF ON OFF OFF ON 19 ON ON OFF OFF ON 20 OFF OFF ON OFF ON 21 ON OFF ON OFF ON 22 OFF ON ON OFF ON 23 ON ON ON OFF ON 24 OFF OFF OFF ON ON 25 ON OFF OFF ON ON 26 OFF ON OFF ON ON 27 ON ON OFF ON ON 28 OFF OFF ON ON ON 29 ON OFF ON ON ON 30 OFF ON ON ON ON 30 ON ON ON ON ON 3 12 1 13 SILENCE ALARMS BEFORE RESET Switch OFF The panel can be reset from the alarm condition without first silencing the alarms A requirement of EN54 2 Switch ON The panel cannot be reset from the alarm condition until the alarms have been silenced A recommendation of BS5839 3 12 1 14 AUTO MANUAL OUTPUTS Switch OFF Open Collector Output 1 operates on Emergency Hold Active Open Collector Output 2 operates on Emergency Abort Active Switch ON Open Collector Output 1 operates when panel is in AUTO amp MANUAL mode Open Collector Output 2 operates when panel is MANUAL ONLY mode 3 12 1 15 CONFIG SLU When in the ON position allows the type code of any connected SLUs to be configured on the panel See section 4 2 3 for configuration details 3 12 1 16 3k9 EOL When in the ON position zones 1 2 Aux Zone amp Manual Release are monitored for a 3k9 End EQUIPMENT FIRECLASS Prescient PUBLIC
23. RKP CHECKED BY AP 3 12 1 2 PRE DISCHARGE DELAY 5S 10S 20S 40S These four switches allow the Pre discharge delay timer to be configured from 0 to 60 seconds in 5 second increments Any of the four switches in the ON position adds to the delay value up to a maximum of 60 seconds pun SW1 2 SW1 3 SW1 4 SW1 5 Seconds 58 10S 20S 40S 0 OFF OFF OFF OFF 5 ON OFF OFF OFF 10 OFF ON OFF OFF 15 ON ON OFF OFF 20 OFF OFF ON OFF 25 ON OFF ON OFF 30 OFF ON ON OFF 35 ON ON ON OFF 40 OFF OFF OFF ON 45 ON OFF OFF ON 50 OFF ON OFF ON 55 ON ON OFF ON 60 N A N A ON ON 3 12 1 3 SILENT ZONE TEST Switch OFF A fire alarm on any zone in Test Mode will operate the appropriate zonal fire indicator and the general sounder circuits for four seconds Switch ON A fire alarm on any zone in Test Mode will operate the appropriate zonal fire indicator but will NOT operate the general sounder circuits 3 12 1 4 BUZZER DISABLE Switch OFF The internal buzzer operates for any fire fault or display button operation Switch ON The internal buzzer only operates on operation of any display button Note This is not compliant with EN54 2 or EN12094 1 Provided for commissioning purposes only 3 12 1 5 LATCHED FAULTS Switch OFF All fault indications are non latching and clear once the fault clears Switch ON All fault indications are latching and requi
24. a gas extinguishing system The Prescient monitors one extinguishing area and one non extinguishing area for fire conditions and gives an appropriate audible and visual indication Zones 1 amp 2 are used for coincident detection in the extinguishing area and can be used to automatically release the extinguishing gas The Auxiliary zone only provides an alarm indication The Prescient also provides a facility for initiating the release of extinguishing gas manually The Prescient incorporates 5 Amp switch mode power supply with Power Factor correction 2 General Description The Prescient is housed a metal enclosure with a Manual Release facility mounted on the door The following functions are available on the front of the panel 1 Visual Indication of panel status via LEDs 2 Numerical Display for the Extinguishant Release Timer 3 Buttons for User Control 4 Manually operated Extinguishant Release unit The following functions are available inside the panel 1 Three fully monitored Detection circuits One fully monitored Manual Release circuit Two fully monitored General Sounder circuits One fully monitored Extinguishing Sounder circuit 5 Two fully monitored Actuator circuits PAGE 3 of 43 FIRECLASS Prescient OMFCPRESSIN 02 02 12 EQUIPMENT PUBLICATION ISSUE No amp DATE 0 6 Repeater outputs for i Zone 1 Fire Detected ii Zone 2 Fire Detec
25. accommodate two 12V batteries up to 12Ah capacity Larger sized batteries fitted in a separate enclosure are not permitted 6 2 Battery Replacement The useful life of the standby batteries in this panel is three years The batteries must be replaced after this time To ensure this when first installed the battery should be clearly labelled with the date of installation and scheduled replacement date 6 3 Battery Charging The battery charger voltage 15 set during manufacturing and should not require adjustment The output voltage can be verified by measuring the voltage across the battery terminals on the internal control board with the batteries connected The battery charger output should be 27 10V 0 05V 25 C Thermistor value 15k If the charger voltage requires adjustment use an insulated trimming tool to adjust the potentiometer SVR1 on the Power Supply see PSU layout diagram in Figure 6 for location See Table 3 for recommended charge voltages PAGE 22 of 43 FIRECLASS Prescient OMFCPRES3 IN EQUIPMENT PUBLICATION ISSUE No amp DATE WRITTEN BY RKP CHECKED BY AP 0 Earth Lead to Earth Bar 02 02 12 Figure 6 Power Supply Connection Details 240VAC IN Incoming Mains Cable Secured with a cable tie Qu Negative Temperature Coefficient Thermistor Input Connector Q E Thermistor to battery lead directly abov
26. circuit fault on the 274 Stage monitored Output SHUTDOWN 1 llluminates for an open or short FAULT circuit fault on the 1 Stage monitored Output ACTUATOR 2 llluminates for an open or short FAULT circuit fault on the Actuator 2 Output ACTUATOR 1 llluminates for an open or short FAULT circuit fault on the Actuator 1 Output EXT SNDER for an open or short FAULT circuit fault on the Extinguishing Sounder Output SNDER 2 llluminates for an open or short FAULT circuit fault on the General Sounder 2 Output SNDER 1 llluminates for an open or short FAULT circuit fault on the General Sounder 1 Output AUTO MAN llluminates for any open or short FAULT circuit fault on the Auto Manual Input FIELD MR FAULT PANEL MR FAULT ABORT FAULT HOLD FAULT GAS TRAPPED FLT ISOLATION VALVE FLT GAS LOW FAULT GAS RELEASED FLT SLU FAULT CONFIG ON GAS SIGNAL FLT MAINS FAULT BATT CHARGE FAULT llluminates for any open or short circuit fault on the Manual Release Zone Input for any open or short circuit fault on the Panel Mounted Manual Release llluminates for any open or short circuit fault on the Emergency Abort input for any open or short circuit fault on the Emergency Hold input llluminates for any open or short circuit fault on the Gas Trapped input for any open or short circuit fault on the Isolation Valve input
27. correct polarity Observe after 20 to 30 seconds that the control panel reacts as follows a The buzzer silences and the fault indications extinguish b The Power Supply On LED remains lit c The System Automatic amp Manual LED remains lit FIRECLASS Prescient 11 WRITTEN BY RKP CHECKED BY AP Position the Thermistor in free air space directly above the batteries Use a cable tie to secure the Thermistor to one of the battery leads Press the Test button on the display board and check that the control panel reacts as follows a All LEDs on the display board and the control board illuminate for 5 seconds b The internal buzzer sounds for 5 seconds Switch off the mains AC supply to the control panel and check that the control panel reacts as follows a The General fault LED on the display board pulses b The Power Supply fault LED on the display board pulses The internal buzzer in the control board sounds d The Fault Relay operates e The Mains Fault LED on the control board illuminates Restore the mains supply to the panel Remove the end of line device from the zone 1 terminals in the panel and connect the field cabling After a few seconds observe that the panel returns to the quiescent condition For each detector on zone 1 remove the detector from it s base and check that after a few seconds a The appropriate yellow Zone fault LED pulses b The General fault LED pulses c
28. for an open or short circuit fault on the Zone 1 input The LED is illuminated steady if the Zone 1 input is disabled or selected to the Test mode 3 16 4 ZONE2 The Zone 2 input status is displayed by two LEDs The red LED is normally off pulsing if a fire condition is detected on zone 2 illuminating steady when the alarm is accepted by operation of the Silence Alarms button The yellow LED is normally off pulsing for an open or short circuit fault on the Zone 2 input The LED is illuminated steady if the Zone 2 input is disabled or selected to the Test mode 3 16 5 AUXZONE output The LED is illuminated steady if the Fire The Aux Zone input status is displayed by two Signal output is disabled LEDs 3 16 3 ZONE 1 The Zone 1 input status is displayed by two LEDs The red LED is normally off pulsing if a fire condition is detected on zone 1 illuminating steady when the alarm is accepted by operation of the Silence Alarms button The red LED is normally off pulsing if a fire condition is detected on the aux zone illuminating steady when the alarm is accepted by operation of the Silence Alarms button The yellow LED is normally off pulsing for an open or short circuit fault on the aux zone input PAGE 15 of 43 EQUIPMENT PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 12 The LED is illuminated steady if the aux zone input is disabled or selected to the Test mode 3 16 6 REMOTE SOUND ALARMS
29. mode an open or short circuit fault on the field wiring illuminates the Circuit Fault LED on the display and the 1 Stage Shutdown Fault LED on the motherboard In the Volt free mode clean contacts for Pole Normally Open amp Normally Closed are available rated at 1A 30VDC 3 10 2 Second Stage Shutdown 2ND STAGE The Second Stage Shutdown Relay is energised when the panel enters the activated condition This occurs when the panel is in the AUTOMATIC amp MANUAL mode and a fire occurs on zone 1 and zone 2 or the Manual Release is operated in Auto or Manual mode The relay is also energised if the panel enters the 3 Stage condition see 3 10 3 A triple jumper link allows the output to be powered and monitored Link ON or Volt Free Link OFF In the Monitored mode an open or short circuit fault on the field wiring illuminates the Circuit Fault LED on the display and the 27 Stage Shutdown Fault LED on the motherboard In the Volt free mode clean contacts for Pole Normally Open amp Normally Closed are available rated at 1A 30VDC 3 10 3 Third Stage Shutdown 3RD STAGE The Third Stage Shutdown Relay is energised when the pre discharge delay timer ends amp the actuator circuits are operated The relay is also energised if the panel enters the discharged condition due to operation of the Gas Released Pressure Switch input see 3 10 4 A triple jumper link allows the output to be powered and monitored
30. panel should be set to the AUTOMATIC amp MANUAL mode and left on soak for 24 hours DO NOT CONNECT THE SOLENOID VALVES DURING THIS PERIOD After the panel has been successfully soak tested the SOLENOID VALVES may be connected to the actuator circuits and the panel can be locked and left in a fully operational state Do not arm the extinguishing system without authorization from the Site s designated Responsible Person authorised users must be given adequate instruction training on the operation of the extinguishing system prior to hand over PAGE 33 of 43 EQUIPMENT FIRECLASS Prescient PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 12 9 System Maintenance 9 1 Overview The Fire detectors amp Sounders should be tested weekly and a note made in the system logbook 1 The operation of manual call points and detectors should be carried out on a rotational basis so that all devices are checked at least once over a 3 month period Important Ensure that the extinguishing system is physically disabled by electrical or mechanical disconnection before carrying out any tests 2 To operate a manual call point use the Test key provided 3 To operate a detector use an approved Test Smoke 4 Check the operation of auxiliary items such as door closers 5 Re enable any disabled circuits after completing the tests 9 2 Weekly Test Routine Operate one manual call point and one detector
31. 0M Marinecallpoint MB600D Sounder Base with Diode e Thorn Grinnell 600RBA Relay Base UL Pe 612H ROR heat detector High performance optical detector 60 deg heat detector 90 deg c heat detector 4 BASE 7 5 00 o o o 1 1 1 6 BASE Series600base 1 1 1 NOTES 1 Detector quantities are based on the use of a 22uF capacitor as the end of line device except for intrinsically safe devices in which case the EOL is a 10k resistor 2 DIL switch option 3K9 EOL is selected then the maximum number of detectors per zone will be reduced In this case the maximum detector current in standby should not exceed 2 3mA As a general rule the quantities shown above should be halved 3 Detector models not listed above may be compatible if electrically similar to the above devices Consult your supplier for advice 4 All break glass units call points must have a resistor fitted to them to produce an alarm condition on the panel Any value between 100 Ohm and 680 Ohm is acceptable Please check with your supplier if you are not sure It is not permitted to connect more than 32 devices to any zone EN54 recommendation Zones 1 amp 2 should only have automatic detectors fitted The Manual Release circuit is not a detection zone and therefore should only have MCPs fitted PAGE 27 of 43 EQUIPMENT
32. 0R resistor illuminating the Emergency Abort Active LED on the display and stopping the Extinguishant release The active abort condition is latched until the input is cleared and the Extinguishing Reset button is pressed NOTE Use only LATCHING switches which need to be manually returned to the OFF position this is a requirement of EN 12094 1 2003 clause 4 27 2 NOTE If a SLU with an Abort switch is configured to transmit the Abort signal via the serial communications path a communication fault on this path will initiate the Abort condition as described above and the release of extinguishant will be aborted PAGE 10 of 43 EQUIPMENT PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 0242 3 10 Relay Contacts Other than the Auxiliary Reset Relay all Relay outputs can be configured as either powered and monitored outputs or Volt free relay contacts The factory default is powered and monitored outputs as required by EN54 2 1997 amp EN12094 1 2003 3 10 1 First Stage Shutdown 1ST STAGE The First Stage Shutdown Relay is energised when the panel enters the pre activated condition This occurs when the panel is in the AUTOMATIC amp MANUAL mode and a fire occurs on zone 1 or zone 2 The relay is also energised if the panel enters the 274 Stage or 3 Stage condition see 3 10 2 and 3 10 3 A triple jumper link allows the output to be powered and monitored Link ON or Volt Free Link OFF In the Monitored
33. 560 Reset Fire System amp Extinguishing System reset of the extinguishing system can be inhibited until the inhibit timer ends or Abort is operated When activated Resets all indications on the Fire Alarm section of the panel Only resets the indications on the Extinguishing section of the panel if the Reset Inhibit is inactive When deactivated no action 3 9 5 Gas Trapped This is a fully monitored input providing open amp short circuit fault monitoring The EOL device is a 10k resistor activated by a 680R resistor Activation illuminates the GAS TRAPPED MANIFOLD LED and raises the general fault condition 3 9 6 Auto Manual Lock Off Switch AUTO MANUAL The Auto Manual input is fully monitored for open amp short circuit faults The End Of Line device is a 10k resistor activated by a 4k7 resistor In the active state the panel is placed in Manual Only mode and the yellow Manual Only LED on the display board pulses Operation of the Auto Manual button on the display board has no effect while the input is active The input allows for the connection of Auto Manual Lock Off switches on SLUs Door Lock switches may also be connected via terminals on the SLUs The total number of Auto Manual switches amp Door Lock switches that can be connected is 14 This allows for 7 SLUs each with an auto manual Keyswitch and a door lock switch fitted See the SLU installation manual for more details 3 9 7 Low Press
34. ATION ISSUE amp DATE 0 02 02 12 WRITTEN BY RKP CHECKED BY AP Of Line device Allows backward compatibility when replacing older systems with this panel 3 12 1 17 LOW PRESSURE Switch OFF The Gas Low input monitors a normally open switch i e activated by a 680R resistor Switch ON The Gas Low input monitors a normally closed switch i e activated by disconnection of the 680R resistor 3 12 2 Link For Earth Fault Monitoring This is a single jumper link located at the bottom right of the control board J22 When present it allows the panel to monitor for earth faults on the cables coming into the panel If this link is REMOVED it physically isolates the internal control board from earth thus disabling the external earth fault monitoring facility 3 13 Fault LEDs SHUTDOWN 3 FAULT ABORT FAULT SHUTDOWN 2 FAULT HOLD FAULT SHUTDOWN 1 FAULT GAS TRAPPED FLT ACTUATOR 2 FAULT ISOLATION VALVE FLT ACTUATOR 1 FAULT GAS LOW FAULT EXT SNDER FAULT GAS RELEASED FLT SNDER 2 FAULT c3 SLU FAULT SNDER 1 FAULT CONFIG ON AUTO MAN FAULT GAS SIGNAL FLT FIELD MR FAULT MAINS FAULT PANEL MR FAULT BATT CHARGE FAULT Twenty two yellow LEDs are mounted on the control board to indicate the following faults SHUTDOWN 3 llluminates for an open or short FAULT circuit fault on the 3 Stage monitored Output SHUTDOWN 2 llluminates for an open or short FAULT
35. E 0 02 02 12 3 Functional Description Note Please refer to Section 10 for PCB Layout Diagram and Section 12 for Connection Diagrams 3 1 Detection Zones Zone 1 Zone 2 amp Aux Zone Three detection zone circuits are provided They are monitored for Open Circuit Fault Short Circuit Fault and Alarm Fire The End Of Line device is normally a 22uF capacitor or 10k resistor if set to Intrinsically Safe mode but can be configured for 3k9 resistor via a DIL switch on the motherboard A maximum of 32 devices may be connected on each zone the actual number is dependent on the type of detector used see section 7 Manual Call Points may only be connected to the aux zone In Automatic mode zones 1 and 2 are normally used together to produce First Stage pre activated and Second Stage activated fire alarms resulting in automatic extinguishant discharge Double Knock or Coincidence Zones The auxiliary detection zone only provides a general fire indication Operation of Fire Reset causes the power supply to all three zones to be disconnected for 4 seconds to reset any activated detectors The Display Board has Fire and Fault LEDs for each of the zones The Display Board also provides User Controls for disabling the monitoring of individual zones 3 2 Manual Release Facility MR amp Panel Mounted Call Point Two circuits are provided for operating the Manual Release facility 1 The fourth dete
36. EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 APPROVED ontrol quipment Limited Q FIRECLASS PRESCIENT FIRE ALARM amp GAS EXTINGUISHING CONTROL PANEL Application Installation Operation amp Maintenance Manual PAGE 1 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRES3IN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 CONTENTS 1 INTRODUCTION eere nnn 3 3 19 7 18 3 19 8 ENABLES 18 2 GENERAL 4 3 3 19 9 DISABLE nce emer oho ater 18 3 FUNCTIONAL DESCRIPTION 8 3 19 10 18 391 REMOTE CONTROLS 9 31941 SCROLL entree nte 18 3 9 2 REMOTE SOUND ALARMS A 9 4 PANEL OPERATION See 18 3 9 3 REMOTE SILENCE 9 4 2 1 DISABLE RE ENABLE TEST 19 3 9 4 REMOTE 9 4 2 2 CONFIGURE l S 20 19 3 9 5 GASIT RAPPE Dinner naa oet 9 4 2 3 CONFIGURE SLU STATUS LAMP UNITS 19 3 9 6 AUTO MANUAL LOCK OFF SWITCH 4 5 1 MANUAL ONLY MODE 20 9 4 5 2 AUTOMATIC amp MANUAL MODE 20 3 9 7 Low PRESSURE FA
37. FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 0242 10 PCB Layout Diagram E eds Connector Configuration Switch 1 Te ara SUNOD INOZ IIA WAN 119154 1531 3NOZ SOP AY DO 39uvHOS 3d Configuration Switch 2 AYT 30 Ly 525108 p 1 5 T 5 9 A Sv9 ox SUNOO OS 5 9 TINA OLD 13534 340498 SITY agave IvA roma aa mw an Fault Status LEDs ze uA xnv ZZ 12 Microcontroller Programming Header Manufacturer s Use Only se su asa srl 24V Battery Connector Internal Buzzer 3573 ABU 154 DC Power Supply Connector 0 2 OS BY 5 9 2107 Relay Output Configuration Links Remove links for Volt Free operation 55 Remove Link to Disable Earth Fault Monitoring AO ABZ No SIS 34H 70 d 4 2 wT ENT SS E 1 1 35 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRES3IN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 11 Panel Exploded View PSU EARTH CABLE MOTHERBOARD PCB CHASSIS EARTH CABLE MAINS TERMINAL BLOCK 3A15 FUSE MAINS TERMINAL LABEL 5A
38. IGNAL fault LED b Press the SCROLL button The cursor should move to the ZONE 1 fault LED c Press the ENABLE button The ZONE 1 amp ZONE 2 fault LEDs should clear with a cursor flash on ZONE 1 fault LED The TEST LED should also clear d Press the SELECT ON OFF button to switch off the flashing cursor Place the Auxiliary Zone into the One Man Test mode using the SELECT cursor as for zones 1 amp 2 Activate each detector amp call point in turn and check that the panel responds as in 24 above except that the AUX ZONE Fire LED operates instead of the ZONE 1 Fire LED Return the Auxiliary Zone to normal operation Operate the panel mounted Manual Release Point and check that the panel reacts as follows a The red Manual Release Active LED pulses b The red System Activated LED illuminates steady c The EXTINGUISHING SOUNDER circuit pulses d Actuator circuits 1 amp 2 operate The internal buzzer in the control panel sounds Activate the Pressure Switch input if fitted and check that the panel reacts as follows a The Silence Alarms LED pulses b The red Manual Release Active LED pulses The red System Activated LED illuminates steady d The Gas Released LED illuminates steady e The Gas Released Signal Active LED illuminates steady f The Gas Released Signal Relay activates g The EXTINGUISHING SOUNDER circuit is steady h Actuator circuits 1 amp 2 remain activated i The internal
39. ONLY button once so that the MANUAL ONLY LED illuminates Place zones 1 amp 2 into the One Man Test mode as follows a Press the SELECT ON OFF button The SELECT cursor should flash on the FIRE SIGNAL fault LED Press the SCROLL button The cursor should move to the ZONE 1 fault LED Press the TEST button The ZONE 1 amp ZONE 2 fault LEDs should illuminate steady with a cursor flash on ZONE 1 fault LED The TEST LED should also illuminate steady Press the SELECT ON OFF button to switch off the flashing cursor leaving the ZONE 1 amp ZONE 2 fault LEDs and the TEST LED illuminated steady Activate the first detector on zone 1 and check that the control panel reacts as follows The red ZONE 1 Fire LED illuminates steady b Sounder circuits 1 amp 2 operate c The internal buzzer in the control panel sounds After four seconds the panel should automatically reset resetting the detector and energising the RESET relay for 10 seconds PAGE 32 of 43 EQUIPMENT FIRECLASS Prescient lll PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 42 25 Repeat step 24 above for all detectors on zone 26 27 28 29 30 31 32 1 Repeat steps 24 and 25 for zone 2 checking that the red ZONE 2 Fire LED illuminates steady instead on the Zone 1 Fire LED Return zones 1 amp 2 to normal as follows a Press the SELECT ON OFF button The SELECT cursor should flash on the FIRE S
40. POWER SUPPLY KEYSWITCH MOUNTING NUT KEYSWITCH CONNECTOR MANUAL RELEASE CONNECTOR CHASSIS DOOR EARTH CABLE DISPLAY BOARD BACKBOX ENCLOSURE 8 WAY EARTH BAR INSERTS MEMBRANE KEYSWITCH NOTE TERMINAL BLOCK POSITION L H S CONNECTIONS 1 2 3 4 HALON BREAK GLASS UNIT BREAK GLASS LEAD COVER 10K RESISTOR PURSPEX PAGE 36 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRES3 IN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 12 Connection Diagrams 12 4 Zone Circuit Connection Diagram End Of Line Capacitor 22uF 35V MEO evel to anual Release switch SLU End Of Line 22uF 35V 3 4 2 Z g UT X OUT 2604 22 IN C Manual Call Point with 680R 0 5W resistor Detector Bases with optional Schottky Diode End Of Line resistor IN IN Detector Base with optional Schottky Diode Manual Release Call Point with 680R 1 W resistor Zone 2 wired identically to Zone oo eje ojo Panel Terminals PAGE 37 of 43 EQUIPMENT FIRECLASS Prescient PUBLICATION ISSUE amp DATE 0 02 02 12 12 2 Sounders amp Actuators Connection Diagram Actuator Solenoid End Of Line Resistor 10K 4W AA
41. To Discharge display 3 The Extinguishing System Reset Inhibit timer starts and the INHIBITED LED illuminates if configured to a non zero value 4 The Extinguishing Sounder circuit pulses 1 second on 1 second off The Extinguishing Sounders cannot be silenced The Extinguishing System cannot be reset while the Reset Inhibit timer is active up to 30 minutes When the pre discharge delay timer ends 1 The SECONDS TO DISCHARGE display clears 2 The 3 Stage Shutdown output operates 3 The actuator circuits operate 4 The Extinguishing Sounder circuit pulses 1 second on 1 second off When the Gas Released input is activated or when the actuator circuits are operated and the NO DISCHARGE PRESSURE SWITCH DIL switch is in the ON position 1 The Gas Released Signal output operates 2 The GAS RELEASED LED amp GAS RELEASED SIGNAL ACTIVE LED operate 3 The SILENCE ALARMS LED pulses 4 The Extinguishing Sounder circuit operates continuously 4 8 1 Emergency Hold Operation Operation of an Emergency Hold switch while the pre discharge delay timer is running will stop the pre discharge delay timer and reset it to the configured value The Extinguishing Sounder circuit will change to pulsing 1 second on 5 seconds off The timer will restart on release of the Emergency Hold switch amp the Extinguishing Sounder circuit will return to pulsing 1 second on FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP 1 secon
42. ULT GAS LOW 9 4 6 1 MANUAL ONLY MODE 20 3 9 8 EXTINGUISHING ISOLATION VALVE STATUS 4 6 2 AUTOMATIC 8 MANUAL MODE 20 ISO 10 4 8 1 EMERGENCY HOLD OPERATION 21 3 9 9 GAS RELEASED PRESSURE SWITCH GAS 4 8 2 EMERGENCY ABORT OPERATION 21 BEL iude eeepc 10 5 TECHNICAL SPECIFICATION rennen 21 3 9 10 EMERGENCY HOLD HOLD 10 3 9 11 EMERGENCY ABORT INPUT 10 6 STANDBY BATTERY REQUIREMENTS 22 3 10 1 FIRST STAGE SHUTDOWN 1ST STAGE 11 7 DETECTOR 24 3 10 2 SECOND STAGE SHUTDOWN 2ND STAGE 11 3 10 3 THIRD STAGE SHUTDOWN STAGE 11 8 PANEL INSTALLATION eene 28 3 10 4 Gas DISCHARGED GAS REL SIG 11 9 SYSTEM 34 3 10 5 FIRE SIGNAL FIRE SIG 11 2406 FAULT oe FAULT ae SUNT 11 10 PCB LAYOUT DIAGRAM 35 3 10 7 AUXILIARY RESET RESET 11 11 PANEL EXPLODED VIEW eren 36 3 12 1 FUNCTION SELECT SWITCH 12 8155 14 12 CONNECTION 5 37 e A rS 15 13 MECHANICAL ELECTRICAL amp
43. at detector PAGE 25 of 43 EQUIPMENT FIRECLASS Prescient Ill WRITTEN BY RKP PUBLICATION OMFCPRES3IN CHECKED ISSUE No amp DATE 0 02 02 12 Description Max per zone See notes 4451E Range 1 heat detector B401RSD Mountingbase 7610 1 lonisation detector 26 52 Mounting base PO100 Optical Smoke Detector PB100 PBD100 Common Diode Base seems 3 100 24V Relay Base ADT Tyco Thorn MF601 lonisation Detector CP210 MANUAL CALLPOINT Tyco H600 Fixed Temperature heat detector 2 Non Branded H902 H904 M300EX Detector base l S MUBEX MUBEXbase 1 M600D Series 600 Diode Base 7 MC600 Series 600 RelayBase 7 MF301 MF301EX MR301 MR301EX MD301 MD301EX MD303EX MD305EX M300 ConventionalBase O 601FEX MD631EX 601CH 601H R 601H F 601P 601PH Conv High Perform Optical Smoke 5B BASE 5BI BASE 5 isolatorbase MU601EX PAGE 26 of 43 5 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 0242 Description Max per zone T See notes MD611EX Heat detector IS M600 UnvesalBae MB600 Sounder Base 1 1 0 0 1 0 0 60158 7 SOUNDER BASE 6018BD________ DIODESOUNDERBASE CP26
44. buzzer in the control panel sounds Press the Silence Alarms button on the display board and check that the control panel reacts as follows a The Extinguishing sounders silence b The red Manual Release LED illuminates steady The Silence Alarms LED illuminates steady WRITTEN BY RKP CHECKED BY AP 33 Restore the panel mounted Manual Release point to normal Press the EXTINGUISHING SYSTEM RESET button to reset the panel 34 Operate the first device connected to the external Manual Release input and check that the panel reacts as in 30 above Restore the Manual Release device to normal and press the EXTINGUISHING SYSTEM RESET button to reset the panel 35 Repeat step 34 for all devices connected to the Manual Release input The primary functions of the panel have now been tested The Panel can now be configured for the specific requirements of the site via the internal DIL switches Once configured the panel functions should be tested to ensure correct configuration For any optional circuits in use i e GAS LOW ISOL VALVE GAS TRAPPED HOLD REMOTE CTRLS AUTO MANUAL 1 2 amp 3 Stage Shutdowns these should also be checked for open amp short circuit faults and for correct activation If Status Indicators are used then check that the correct indications are shown the status indicators and any switches fitted operate correctly Once all Panel functions have been fully tested the
45. cal detector SIH E CD Range ionisation detector PAGE 24 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRESSIN CHECKED BY AP ISSUE No amp DATE 0 02 0242 See notes YFB RL 4H5 Mountingbase 4 CDX Range mounting base YBN R4 Electronics Free Base o Z 5_ 7 CDX range mounting base with remote indicator diode YBO 5SK 7 CDXrange mounting base with remote indicator amp diode 4 CDX range mounting base no diode deg fixed temperature element YBN R A S 7 Electronics Free Base intrinsically Safe YBN R eSK Conventional head removal base _ 6 7 EHlecroicsfreebase YBO HeR Mounting base with relay YO 6 7 Mounting base with relay and Schottky diode 6 Mounting base with relay with non latch relay 14506587 005 Mounting base Diode version o Z o o Nittan 450 7 diode and resistor base _STB 4R_ Sensortec resistor 24 Sensottecrelaybase STEMS 7 SensorteciISbase TBA NewEvoutonbase 7015 Moutingbase y Mountingbase RB4 5451 Grade 1 he
46. cation becomes steady when the panel is in the Alarm Silenced condition 3 18 4 SYSTEM ACTIVATED This is a red LED that is normally OFF pulsing during the pre activated condition 1 Stage illuminating steady during the activated condition 299 Stage The LED remains illuminated until the Extinguishing System is reset 3 18 5 GAS RELEASED This is a red LED that is normally OFF It is illuminated steady when the panel is in the Gas Released condition This normally occurs when the GAS RELEASED input is activated but can be configured to occur as soon as the actuator circuits are energised via the NO DISCHARGE PRESSURE SWITCH DIL switch The LED remains illuminated until the Extinguishing System is reset 3 18 6 GAS RELEASED SIGNAL ACTIVE This is red LED which is normally off It is illuminated steady when the Gas Released output is active 3 18 7 EMERGENCY ABORT ACTIVE This is a yellow LED that is normally OFF It indicates that the release of extinguishing gas has been aborted The LED pulses if a fault occurs on the Abort input when the Extinguishing System is not in the pre activated or activated conditions a separate fault LED is also provided on the control board The pulsed indication is non latching and clears when the fault clears The LED is illuminated steady If the Abort input is activated at any time or a fault occurs on the input during the pre activated or activated conditions PAGE
47. ction zone is used as a Manual Release zone It is monitored for Open Circuit Fault Short Circuit Fault and Alarm The End Of Line device is usually a 10k resistor but can be configured for 3k9 resistor via a DIL switch on the motherboard It gives a Second Stage alarm in both automatic and manual modes and initiates the Extinguishant release sequence when activated This zone must only have manually operated devices connected to it e g Manual Call Points The power supply to this zone is not switched off during panel Reset 2 Manual Release Call Point is mounted on the door of the panel and is monitored by a separate circuit for open amp short circuit faults The connection for the call point is on the rear of the display board The Display Board has Activated and Fault LEDs for the Manual Release facility common to both FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP circuits Individual fault LEDs are provided on the motherboard inside the panel The Manual Release facility can be disabled resulting in both circuits being disabled 3 3 General Alarm Circuits SNDR1 amp SNDR2 Two fully monitored general alarm circuits are provided They are monitored for Open Circuit and Short Circuit faults They are rated at 0 5A electronically fused 28VDC each The End Of Line device is a 10k resistor 3k9 can also be used The Fire Sounder Fault Disabled LED on the display flashes for any fault condition
48. d off The Hold output will operate while the Hold switch is operated 4 8 2 Emergency Abort Operation Operation of an Emergency Abort switch or a fault on the Emergency Abort input will abort the extinguishant release The pre discharge delay timer will be cancelled the Extinguishing System Reset Inhibit will be cancelled the actuator circuits will be de energised the Extinguishing Sounder circuit will be silenced amp the Abort output will operate The Abort condition will remain until the Extinguishing System is reset 5 Technical Specification Mains supply voltage 230VAC 10 15 Mains supply frequency 50 60Hz Power supply output voltage 19 0 28 3V ripple 0 7V maximum Maximum power supply output 5A Alarm current Mains failed 160mA 20mA to 50mA for each zone in alarm Ancillary equipment current Alarm circuit current Solenoid circuit current Mains Failed current 60mA Ancillary equipment current Integral charger output Quiescent 5A minus mains failed current Integral charger output Alarm 5A minus Alarm current Maximum Auxiliary 24VDC supply 1 0A Alarm circuit rating 3 at 0 5A each electronically fused Actuator circuit rating 2 at 1A each electronically fused Internal Battery size 2 x 12Ah Sealed lead acid Enclosure Dimensions 370 high x 325 wide x mm 125 dee
49. d the INHIBITED LED illuminates 11 The Extinguishing Sounder circuit pulses 1 second on 1 second off In this state the buzzer can be silenced only sounder circuits 1 amp 2 can be silenced and re sounded if necessary the fire condition can be reset by operation of the FIRE RESET button 4 7 Manual Release Condition The Manual Release facility is available in the AUTOMATIC amp MANUAL mode and in the PAGE 20 of 43 EQUIPMENT PUBLICATION OMFCPRESSIN ISSUE No amp DATE 0 02 0242 MANUAL ONLY mode When Manual Release is initiated the following occurs 1 MANUAL RELEASE LED pulses 2 The MANUAL RELEASE output operates 3 The SYSTEM ACTIVATED LED illuminates steady activated condition 4 The 1 Stage Shutdown amp 274 Stage Shutdown outputs operate 5 The pre discharge delay timer starts 6 The Extinguishing System Reset Inhibit timer starts and the INHIBITED LED illuminates 7 The Extinguishing Sounder circuit pulses 1 second on 1 second off In this state the buzzer can be silenced 4 8 Activated Condition The activated condition normally occurs when the Manual Release is activated see section 4 7 or when zones 1 amp 2 register a fire condition and the panel is in the Automatic amp Manual mode see section 4 6 2 During this condition 1 The 1 Stage Shutdown 8 2 Stage Shutdown outputs operate 2 The pre discharge delay timer starts and the time to discharge is counted down on the Seconds
50. d the Type Code digit will flash 5 Press the SCROLL button to change the Type Code to the desired value valid values 12 3 The configuration is stored immediately in EEPROM 6 Press ENABLE to switch between flashing the first amp second digits address change or type code change 7 Press SELECT ON OFF to switch off the edit mode the edit mode is automatically switched off if no buttons are pressed for 60 seconds PAGE 19 of 43 EQUIPMENT PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 12 8 Move the CONFIG SLU DIL switch on the control board to the OFF position NOTE The SLU configuration is stored in EEPROM and is retained when the panel has no power 4 3 Panel Quiescent State The panel will be in the quiescent state when the POWER SUPPLY ON LED is on steady either the AUTOMATIC 8 MANUAL LED or the MANUAL ONLY LED is on steady and no other indications are present on the display board or the control board 4 4 Auxiliary Fire Condition If a fire condition is detected on the Auxiliary zone the following occurs The FIRE LEDs pulse The AUX ZONE FIRE LED pulses The SILENCE ALARMS LED pulses The FIRE SIGNAL output operates and the red FIRE SIGNAL LED operates The AUX ZONE FIRE output operates Sounder circuits 1 amp 2 operate In this state the buzzer can be silenced both sounder circuits can be silenced and re sounded if necessary and the fire condition can be reset by operation
51. duce battery service life In extreme cases this can cause Thermal Runaway resulting in high oxygen hydrogen gas production battery swelling Batteries are irrecoverable from this condition and should be replaced LOW TEMPERATURE will prolong battery life but reduce output capacity Do not incinerate batteries If placed in a fire the batteries may rupture with the potential to release hazardous gases and electrolyte VRLA batteries contain substances harmful to the environment Exhausted batteries must be recycled Return them to the battery manufacturer or take them to your Council waste disposal site for appropriate disposal 8 2 Electrical Safety The volt free relay contacts provided within the panel must not be used to directly switch any voltage that exceeds 50VAC or 75VDC Please also refer to relay rating data This equipment requires a 230V AC supply All installation work should be carried in accordance with the recommendations of BS5839 Part 1 and the current edition of the IEE regulations by suitably qualified and trained personnel Must Be Earthed gt 2 Q m gt gt THIS PANEL MUST BE EARTHED electrically conductive parts of this installation must be bonded to the protective earth for safety PAGE 268 of 43 EQUIPMENT PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 0242 8 3 Cable Recommendations All external connections except for mains po
52. e battery use cable tie T ere N a m Mains er Terminal Voltage Block Adjust Connection to Mounted on 5 Control Board the Enclosure 281 backbox 9 Output 5A Power Supply Unit Mounted on Internally Wired 7 Mains Cable vio Wire H to Chassis Table 3 Float Charge Voltages for Powersonic VRLA batteries Ambient Float Charge Voltage Temperature Charger ser voltage 2x12V Batteries in series 102 14 28 32 28 42V 27 84 28 44V 0 32 F 27 82 27 92V 27 60 28 20V 10 50 F 27 45 27 55V 27 36 27 96V 20 68 27 20 27 30 27 12 27 72 25 77 27 10 27 20V 27 00 27 60V 30 86 27 03 27 13V 26 88 27 48V 40 C 104 F 26 91 27 01V 26 64 27 24V 50 C 122 F 26 84 26 94V 26 40 27 00V PAGE 23 of 43 EQUIPMENT FIRECLASS Prescient WRITTEN BY RKP PUBLICATION OMFCPRES3IN CHECKED BY AP ISSUE No amp DATE 0 02 02 12 7 Detector Compatibility The panel will operate with the following types of devices See notes 45681 007 7 Series20 30mountingbase o o EA AA O SEU IEEE Orbis Class A1R Heat detector with SensAlert amp FasTest amp ORB HT 11013 APO Orbis Class A EE ORB HT 11002 APO Orbis Class A2S Heat detector with SensAlert amp FasTest ORB HT 11014 Apo Orbis Class 25 Heat detector with SensAlert a
53. ean Standard EN 12094 1 2003 as well as the relevant parts of EN54 2 1997 amp EN54 4 1997 The Prescient also incorporates the relevant recommendations of the British Code of Practice BS7273 1 2000 The Prescient is fully compliant with the mandatory requirements of EN54 parts 2 and 4 along with the following options with requirements 1 EN54 2 1997 Clause 7 8 Outputs to fire alarm devices sounders 2 EN54 2 1997 Clause 7 9 Outputs to fire alarm routing equipment 3 EN54 2 1997 Clause 8 9 Output to fault warning routing equipment 4 EN54 2 1997 Clause 10 Test condition The Prescient provides the following compulsory functions of BSEN 12094 1 2003 as listed in clause 4 3 2 1 a Reception amp processing of at least one input triggering signal from an f d a s Fire detection Zones 1 amp 2 and an input triggering signal from manual triggering device s connected directly to the e c d Manual Release input 2 b Transmission of the extinguishing signal Actuator circuits 1 amp 2 3 c Activation of Alarm devices Extinguishing Sounder circuit 4 d Indication of each condition unambiguously LEDs amp internal buzzer 5 e Transmission of the information of the incorrect status of components and of the information of the fault warning condition Fault Signal Output 6 f Transmission of the information of the released condition Gas Released Output The Prescient provides the follow
54. eet for actual current or coil resistance should be connected in place of the solenoid to simulate the presence of the solenoid coils The solenoid coils should be connected only at the end of the commissioning process The commissioning engineer should also be aware of any additional equipment connected to the panel and the consequences of the operation of that equipment during the commissioning process Make sure that the ACCESS CONTROLS Keyswitch is in the position before operating any of the buttons on the display board ALL internal DIL switches should be in the OFF position at the start of the commissioning process detailed below 1 Turn ON the mains supply to the panel and observe that the control panel reacts as follows a The green Power illuminates display b The yellow Manual Only LED illuminates Supply On LED display c The yellow General Fault LED flashes display d The yellow Power Supply Fault LED flashes display e The yellow Batt Charge Fault LED is illuminated control board f The internal buzzer sounds control board g The Auxiliary Fault Relay operates No other indications should be present at this time if there are identify the fault and rectify it by checking the following a That no field wiring is connected b That the EOL devices are connected correctly in the panel terminals each monitored circuit 2 Connect the batteries to the control board observing
55. equired by 54 2 1997 clause 10 1 c 3 19 11 SCROLL This button has no function unless the Circuit Select Cursor is ON Depending on the current mode operation of the button will move the flashing cursor through the available circuit LEDs or in SLU CONFIGURATION mode will change either the SLU number digit or the SLU TYPE CODE digit to the next value See section 4 2 for details 4 Panel Operation 4 1 Circuit Configuration Options Table 2 lists the available operating modes for configurable circuits Table 2 Circuit Modes Test Intrinsically Circuit Disabled Mode Safe Zone 1 Y See Y Zone 2 Y Note 1 Y Auxiliary Zone Field Manual N A Y Release Group Panel Operation Manual N A Release Sounder 1 Group Sounder 2 Operation Group Extinguishing Operation Sounder Group Actuator 1 Operation ZEE 8 Ra Actuator 2 N A Fire Signal Y N A Fault Signal Y N A N A Gas Released Y N A N A Signal Shutdown 1 G N A N A Shutdown 2 Shutdown 3 N A N A Note 1 Zones 1 amp 2 are placed into Test mode together but are cleared individually safety feature N A Not Available Feature available without additional configuration 4 2 Circuit Select Cursor The Circuit Select Cursor is a rapidly flashing fault disablement LED for the selected circuit The curso
56. faults Switch ON The actuator circuits are only monitored for open circuit faults Used for open circuit fault monitoring of the solenoid coil without a series end of line resistor 3 12 1 11 RESET INHIBIT PERIOD Five switches allow the Extinguishing System Reset Inhibit timer to be configured from 0 to 30 minutes in 1 minute increments Any of the five switches in the ON position adds to the timer value up to a maximum of 30 minutes See Table 1 3 12 1 12 CLEAR ACTUATORS AFTER 1 MIN Switch OFF The actuator circuits are energised until the Extinguishing System is reset Switch ON The actuator circuits are only energised for 1 minute and then are de energised NOTE This facility is only to be used where the actuators connected to the actuator circuits remain activated when the power is removed and require manual resetting This facility is not intended to control the gas discharge period It is only provided as a means to reduce current consumption during gas discharge PAGE 13 of 43 Table 1 Reset Inhibit Settings Reset Inhibit SW2 2 SW2 3 SW2 4 SW2 5 SW2 6 Length 2min 4min 8min 16min minutes 0 OFF OFF OFF OFF OFF 1 ON OFF OFF OFF OFF 2 OFF ON OFF OFF OFF 3 ON ON OFF OFF OFF 4 OFF OFF ON OFF OFF 5 ON OFF ON OFF OFF 6 OFF ON ON OFF OFF 7 ON ON ON OFF OFF 8 OFF OFF
57. g Ini E Emergency JE Abort 11978 1 x Vol Free Change Routing Fault Conventional Abort Active Fault feed PAG QU Abort input gt O Rated 1 Amp 24VDC e Auto ntema Internal Gas Rel Auto Manual amp Manual Signal Conventional Lock Off Manual Only Fault fas Rel Sig i Routing _ Auto Manual e Routing Fau Active Disabled switch input gt e e o To Status Indicator RS485 serial Controller data SLU Gas Released SLU Gas Manual SLU SLU Faul Gas Auto SLU q t lt Timer Hold SLU Open collector O Ps each rated 50 mA Release Aborted SLU Release Disabled SLU 24V AUX 1A Output Release Count Down SLU lt OV AUX 1A Output 1A Fused 4 1 Remote oun RCI Alarms Faul Active aut Max O P 0 25A Fused Remote Input Es Soun arms xtinguishing 4 1 x V F C O relay contact 1K8 Silence Alarms Reset t Rated 1 Amp 24VDC 560R Reset Panel ae d steady while Extinguisnini Reset is Inhibite Open amp short circuit monitored output Gen Sndr 1 3 Continuous for fire on Z1 72 Aux Zone Also for Remote Sound Alarm Gen Sndr 2 MaxO P 0 5A f Pulsed when Z1 amp Z2 in alarm In auto or Man Release active Ext Sndr Continuous on actuator p gt activation or discharge Pressure SW signal active Max O P 0 5A Act 1
58. he panel needs to know the type of SLU connected and the address of the SLU The configuration process is as follows 1 Move the CONFIG SLU DIL switch on the control board to the ON position The CONFIG ON LED on the control board will illuminate the buzzer will sound the SYSTEM FAULT LED will illuminate and the SELECT ON OFF LED will pulse The two digit display for SECONDS TO DISCHARGE will show SLU address 1 for the first digit and the type code of that SLU on the second digit SLU address 1 set to Type code 0 no SLU with address 1 SLU address 1 set to Type code 1 SLU address 1 set to Type code 2 SLU address 1 set to Type code 3 SLU address 1 set to Type code 4 Note If a SLU is configured to use the panel circuits for switch monitoring the SLU will automatically be configured as an indication only unit The panel must therefore be configured for a type 1 SLU at the corresponding address 2 Press the SELECT ON OFF button The first digit will pulse SLU address and the buzzer will silence indicating that the SLU edit mode is active 3 Press the SCROLL button to change the SLU address value The second digit will show the Type code set for the selected address The SLU address digit will change in sequence 12 5 landthenbackto l 4 When the first digit displays the address of the SLU to be configured press the ENABLE button The SLU address digit will go steady an
59. ing optional functions of BSEN 12094 1 2003 as listed in clause 4 3 2 1 g Extinguishing system delay 2 h Reception of a signal representing the flow of extinguishing agent Discharged 3 i Monitoring of status of components a Low pressure low weight 4 j Reception of signal from an emergency hold device 5 k Separate monitoring of the status of non electrical disable device s Isolation valve 6 n Input from auto manual selector switches 7 0 Transmission of a triggering signal to FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP equipment within the fire extinguishing system b Optical warning devices Status indicators 8 q Transmission of signals to equipment outside the fire extinguishing system Shut downs 9 r Reception of signal from an emergency abort device 10 u Activation of alarm devices with different signals 2 stage sounders The Environmental Class as defined by clause 4 2 is Class A temperature range 5 to 40 Deg C The Prescient is fully compliant with the relevant recommendations of BS 7273 1 2000 The following safety critical aspects have been addressed 1 6 1 2 Avoidance of accidental discharge 2 6 4 3 A single short circuit in connections shall not cause an extinguishant release 3 6 4 4 Protection against over voltages which could cause an extinguishant release Prescient Ill integrates the functions of a fire alarm system and
60. ire Alarm The Display board is connected to the internal control board via a 16 way ribbon cable and polarised ribbon socket A polarised 16 way header is provided on the main control board at position J1 The Display is divided into three windows for clarity User Controls are positioned in the central window with status LEDs in the left amp right windows section of the panel as well as indications which are common to both the Fire Alarm section and the Extinguishing section The right window is dedicated to displaying the status of the Extinguishing section of the panel See Figure 5 for details Figure 5 Display FIRE STATUS COMMON STATUS SOUNDER TEST EXTINGUISHING STATUS ISOLATION VALVE CLOSED MANUAL RELEASE FAULT DISABLED EXTINGUISHING DISABLED GAS RELEASED SIGNAL DISABLED SHUTDOWN OUTPUTS DISABLED 88 SECONDS DISCHARGE 3 16 Display Board Fire Status Indications 3 16 1 FIRE These two red LEDs are normally off pulsing for a fire alarm on zones 1 2 or aux zone The LEDs are illuminated steady if the general sounders are silenced during the fire alarm 3 16 2 FIRE SIGNAL The Fire Signal output status is displayed by two LEDs The red LED is normally off illuminating steady when the Fire Signal output is active The yellow LED is normally off pulsing for an open or short circuit fault on the Fire Signal The yellow LED is normally off pulsing
61. k load to indicate valve stuck between open amp closed clearing when the input is cleared 3 18 13 ISOLATION VALVE CLOSED This is a yellow LED which is normally OFF It pulses while the Isolation Valve monitors a Closed value nominally 680R load clearing when the input is cleared 3 18 14 MANUAL RELEASE FAULT DISABLED This is a yellow LED which is normally OFF It pulses if the Manual Release zone input is in fault or the internal circuit to the door mounted Manual Release is in fault clearing when the fault is cleared A separate fault LED for each circuit is also illuminated on the internal control board The Manual Release Fault Disabled LED is illuminated steady when the Manual Release facility is disabled 3 18 15 EXTINGUISHING DISABLED This is a yellow LED which is normally OFF It is illuminated steady when the Actuators are disabled Note When the actuators are disabled the Extinguishing Sounder circuit is automatically disabled FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP 3 18 16 GAS RELEASED SIGNAL DISABLED This is a yellow LED which is normally OFF It is illuminated steady when the Gas Released Signal output is disabled 3 18 17 SHUTDOWN OUTPUTS DISABLED This is a yellow LED which is normally OFF It is illuminated steady when the shutdown outputs are disabled All three 1 Stage 2 Stage amp 3 Stage shutdown outputs are disabled together 3 18 18 SECONDS TO DISCHARGE
62. ld Reset 560 ohms green blue brown gold ii Valve monitoring resistors Valve open 2k2 ohms red red red gold Valve closed 680 ohms blue grey brown gold 3 x End of Line Capacitors 22uF v Spare 20mm mains fuse T5AH250V vi Spare 20mm battery fuse F6 3A250V vii 2 x cable ties viii 2 x C1565 actuator suppression units ix A set of battery leads Red Black and Blue ix Disconnect the display ribbon cable from the internal control board by pulling firmly but gently on the ribbon cable connector Disconnect the Earth wire from the chassis at the top left of the chassis Remove the control panel chassis complete with power supply amp control board from its fixings by undoing the screws located on the chassis The bottom left amp right screws need to be removed completely the top left amp right Screws can just be slackened The chassis can then be pushed upwards and removed Rest the chassis in the bottom of the enclosure and disconnect the internal mains cables from the terminal block at the top right of the enclosure Remove the chassis and place the complete chassis unit safely to one side Do not remove the control board or the power supply unit from the chassis Place the empty enclosure against the wall mark and fix using the single fixing hole in the upper section of the enclosure Level the enclosure and complete the fixing operation using the remaining tw
63. ly OFF The LED pulses if there is a low resistance to earth on any of the field cables 3 17 6 FUSE FAILED This is a yellow LED that is normally OFF The LED pulses if either of the electronic fuses on the two auxiliary 24V supply outputs are activated due to excessive loading 3 17 7 FAULT SIGNAL FAULT DISABLED The is a yellow LED which is normally off pulsing for an open or short circuit fault on the Fault Signal output The LED is illuminated steady if the Fault Signal output is disabled FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP 3 17 8 SOUNDER TEST This is a yellow LED which is normally off illuminating steady when the three sounder circuits are in the TEST mode 3 18 Display Board Extinguishing Status Indications 3 18 1 AUTO amp MANUAL This is a yellow LED that is illuminated steady if the actuators can be operated both automatically via a fire alarm on zones 1 amp 2 and manually via manual release 3 18 2 MANUAL ONLY This is a yellow LED that is illuminated steady if the actuators can only be operated manually via manual release The LED pulses if an AUTO MANUAL switch in the field is set to Manual 3 18 3 MANUAL RELEASE ACTIVE This is a red LED that is normally off pulsing if manual release is activated either by operation of the Manual Release Call Point on the front of the panel or via the operation of a manual release unit connected to the Manual Release Zone input The indi
64. mally Closed are available rated at 1A 30VDC 3 10 6 Fault Signal FAULT SIG The Fault Signal Relay is a fail safe relay and is normally energised It is de energised for any fault condition on the panel A triple jumper link allows the output to be powered and monitored Link ON or Volt Free Link OFF In the Monitored mode an open or short circuit fault on the field wiring illuminates the Fault Signal Fault LED on the display In the Volt free mode clean contacts for Pole Normally Open amp Normally Closed are available rated at 1A 30VDC 3 10 7 Auxiliary Reset RESET The Auxiliary Reset Relay is a single pole change over relay and is energised briefly when the panel is in Fire Reset mode The relay is energised for 10 seconds This is to allow ancillary equipment such as Beam Detectors to be reset The relay has no powered and monitored mode and only volt free contacts for Pole Normally Open amp Normally Closed are available rated at 1A 30VDC PAGE 11 of 43 EQUIPMENT FIRECLASS Prescient PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 12 3 11 Internal Standby Batteries Terminals are provided to allow connection of one set of internal standby batteries The Charger Circuit is monitored for the following Battery or associated wiring disconnected e Battery fuse blown e Low battery voltage 15 7V 0 4V e Battery and interconnection resistance is 0 350 or higher 3 12 Func
65. mergency Hold Active LED on the display and resetting amp holding the pre discharge delay timer NOTE If more than three Emergency Hold switches connected to the Hold input are operated simultaneously then a short circuit fault will be detected If this occurs while the Pre discharge timer is running then the Timer will still be reset and held until all switches are released Use only non latching switches which return to open contacts when the switch is released NOTE If a SLU with a Hold switch is configured to transmit the Hold signal via the serial communications path a communication fault on this path will initiate the condition as described above and the release of extinguishant will be inhibited 3 9 11 Emergency Abort Input ABORT This is a fully monitored input providing open amp short circuit fault monitoring The EOL device is a 10k resistor An open or short circuit fault is indicated by the Circuit Fault LED on the display and an Abort Fault LED on the motherboard In addition the Abort Active LED will pulse if the system is not in the Activated or Discharged condition clearing when the fault is cleared If a fault occurs on the input during the Activated or Discharged condition then the fault indication is still given but the Abort Active LED is illuminated steady and the Abort condition is latched until reset This fault condition prevents the Extinguishant release The input is activated by a 68
66. momentary activation during normal movement of the valve between open and closed positions See Connection Diagram in section 12 3 for details NOTE The healthy state for the input is VALVE OPEN and therefore if the input is not used the input should have a 2k2 resistor fitted 3 9 9 Gas Released Pressure Switch GAS REL This is a fully monitored input providing open amp short circuit fault monitoring The EOL device is a 10k resistor An open or short circuit fault is indicated by the Circuit Fault LED on the display and a Gas Released Fault LED on the motherboard The input is activated by a 680R resistor illuminating the Gas Released LED on the display the Extinguishing sounder circuit the Gas Released Signal amp all three shutdown outputs 3 9 10 Emergency Hold HOLD This is a fully monitored input providing open amp short circuit fault monitoring The EOL device is a 10k resistor An open or short circuit fault is indicated by the Circuit Fault LED on the display and a Hold Fault LED on the motherboard If a fault occurs on the input during the Activated or Discharged condition then the fault indication is still given but the Hold Active LED is illuminated steady and the Hold condition is established until FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP the fault is removed This fault condition prevents the Extinguishant release The input is activated by a 680R resistor illuminating the E
67. mp FasTest amp 32 Flashing LED ORB HT 11003 APO Orbis Class BR Heat detector with SensAlert amp FasTest Orbis Class BR Heat detector with SensAlert amp FasTest amp ORB HT 11015 APO Flashing LED ORB HT 11004 APO Orbis Class BS Heat detector with SensAlert amp FasTest ORB HT 11016 APO Orbis Class BS Heat detector with SensAlert amp FasTest amp Flashing LED ORB HT 11005 APO Orbis Class CR Heat detector with SensAlert amp FasTest Orbis Class CR Heat detector with SensAlert amp FasTest amp 32 11017 0108 0852 ORB HT 11006 APO Orbis Class CS Heat detector with SensAlert 8 FasTest ORB HT 11018 APO Orbis Class CS Heat detector with SensAlert amp FasTest amp Flashing LED ORB OP 12001 APO Orbis Optical detector with SensAlert FasTest amp DirtAlert Orbis Optical detector with SensAlert FasTest amp DirtAlert 32 120 Orbis Optical de 13001 Orie MO sereo detector with SensAlert FasTest amp Orbis multi sensor detector with SensAlert FasTest amp 32 ORB OH 13003 APO DirtAlert amp Flashing LED BERGEN ORB MB 00001 APO TimeSaverBase ORB MB 00002 APO TimeSaver Base LX without continuity checking link ORB MB 00003 APO TimeSaver Diode Base OLX DB 00007 APO Diode Base LX without continuity checking ORB RB 00004 APO TimeSaver Relay Base SLK E CD Range opti
68. o fixing holes in the lower section of the enclosure The fixing holes are suitable for 5mm diameter screws imperial size 10 Use stainless steel or plated screws the installation wiring into the enclosure using the cable entry knockouts provided at the top of the enclosure FIRECLASS Prescient 10 11 12 13 14 15 16 17 18 WRITTEN BY RKP CHECKED BY AP Do not connect any field wiring at this time When all installation wiring is complete check all the wiring to ensure that it is free from short circuits open circuits earth faults crossed connections etc Connect a 22uF end of line capacitor across the terminals of the last device in each of the three zone wiring runs Check that any Manual Call Points on the aux zone are fitted with an activation resistor in the range 100 Ohms to 680 Ohms Connect a 10k EOL resistor across the terminals of the last device on the Manual Release zone Connect a 10k EOL resistor across the terminals of the last device in each of the alarm wiring runs Connect a 10k EOL resistor across the terminals of the last device in each of the solenoid wiring runs If you are using the C1565 monitoring and suppression board instead of the end of line resistor then note that only one board can be used on each circuit Connect a 10k EOL resistor across the terminals of the last device for any additional monitored input or output circuits being
69. of outputs maximum 1s PAGE 43 of 43
70. of the FIRE RESET button 4 5 Single Extinguishing Zone Fire Condition 4 5 1 MANUAL ONLY MODE If a fire condition is detected on either zone 1 or zone 2 while the panel is in the MANUAL ONLY mode the following occurs 1 The FIRE LEDs pulse 2 The ZONE 1 FIRE or ZONE 2 FIRE LED pulses 3 The SILENCE ALARMS LED pulses 4 The FIRE SIGNAL output operates and the red FIRE SIGNAL LED operates 5 The ZONE 1 FIRE or ZONE 2 FIRE output operates 6 Sounder circuits 1 amp 2 operate In this state the buzzer can be silenced both sounder circuits can be silenced and re sounded if necessary and the fire condition can be reset by operation of the FIRE RESET button 4 5 2 AUTOMATIC amp MANUAL MODE If a fire condition is detected on either zone 1 or zone 2 while the panel is in the AUTOMATIC amp MANUAL mode the following occurs 1 The FIRE LEDs pulse 2 The ZONE 1 FIRE or ZONE 2 FIRE LED pulses 3 The SILENCE ALARMS LED pulses 4 The FIRE SIGNAL output operates and the red FIRE SIGNAL LED operates 5 The ZONE 1 FIRE or ZONE 2 FIRE output operates 6 Sounder circuits 1 amp 2 operate Tomo own FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP 7 The SYSTEM ACTIVATED LED pulses pre activated condition 8 The 1 Stage Shutdown output operates In this state the buzzer can be silenced both sounder circuits can be silenced and re sounded if necessary the fire condition can be reset by operati
71. on of the FIRE RESET button and the extinguishing pre activated condition can be reset by operation of the EXTINGUISHING SYSTEM RESET button 4 6 Two Extinguishing Zones Fire Condition 4 6 1 MANUAL ONLY MODE If a fire condition is detected on both zone 1 and zone 2 while the panel is in the MANUAL ONLY mode the following occurs 1 The FIRE LEDs pulse 2 The ZONE 1 FIRE and ZONE 2 FIRE LEDs pulse 3 The SILENCE ALARMS LED pulses 4 The FIRE SIGNAL output operates and the red FIRE SIGNAL LED operates 5 The ZONE 1 FIRE amp ZONE 2 FIRE outputs operate 6 Sounder circuits 1 amp 2 operate In this state the buzzer can be silenced both sounder circuits can be silenced and re sounded if necessary and the fire condition can be reset by operation of the FIRE RESET button 4 6 2 AUTOMATIC amp MANUAL MODE If a fire condition is detected on both zone 1 and zone 2 while the panel is in the AUTOMATIC amp MANUAL mode the following occurs 1 The FIRE LEDs pulse 2 The ZONE 1 FIRE and ZONE 2 FIRE LEDs pulse 3 The SILENCE ALARMS LED pulses 4 The FIRE SIGNAL output operates and the red FIRE SIGNAL LED operates 5 The ZONE 1 FIRE amp ZONE 2 FIRE outputs operate 6 Sounder circuits 1 amp 2 operate 7 The SYSTEM ACTIVATED LED illuminates steady activated condition 8 The 1 Stage Shutdown 8 2 Stage Shutdown outputs operate 9 The pre discharge delay timer starts 10 The Extinguishing System Reset Inhibit timer starts an
72. onitoring the wiring for short circuits correctly by placing a wire link across the Manual Release zone end of line device and checking that after a few seconds a The yellow Manual Release Fault Disabled LED pulses b The General fault LED pulses The internal FIELD MR FAULT LED illuminates steady d The internal buzzer pulses e The fault output operates Remove the link and check that the panel returns to quiescent Remove the end of line device from the Alarm Circuit 1 terminals in the panel and connect the field cabling After a few seconds observe that the panel returns to the quiescent condition Check that the alarm circuit is monitoring the wiring for open circuits correctly Remove the EOL resistor from the last device on the circuit and check that after a few seconds a The Fire Sounder Fault LED for on the Display pulses b The appropriate yellow alarm fault LED on the control board illuminates C The General fault LED pulses d The internal buzzer pulses e The fault output operates Replace the EOL resistor amp check that the panel returns to quiescent Check that the alarm circuits are monitoring the wiring for short circuits correctly Place a wire link across the EOL resistor in the last device on the circuit and check that after a few seconds a The Fire Sounder Fault LED on the Display pulses b The appropriate yellow alarm fault LED on the control board illuminates The General fault
73. or and then pressing ENABLE or DISABLE as required ENABLE I S DISABLE Normal The process is as follows 1 Move the CONFIG 1 6 INPUTS DIL switch on the control board to the ON position The CONFIG ON LED on the control board will illuminate the buzzer will sound the SYSTEM FAULT LED will illuminate and the SELECT ON OFF LED will pulse The fault disabled LEDs for any circuits already set to 1 5 mode will illuminate 2 Press the SELECT ON OFF button The Select Cursor will appear on the ZONE 1 fault LED and the buzzer will silence 3 Press the SCROLL button to move the cursor to the required circuit fault disabled LED The cursor will move in sequence through the relevant circuits and will then return to the ZONE 1 fault LED 4 Press the ENABLE or DISABLE button as required to ENABLE 1 6 or DISABLE 1 6 5 Repeat steps 3 amp 4 for any additional circuits 6 Press SELECT ON OFF to switch off the cursor the cursor is automatically switched off if no buttons are pressed for 60 seconds 7 Move the CONFIG 1 5 INPUTS DIL switch on the control board to the OFF position FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP NOTE The I S configuration status is stored in EEPROM and is not lost when power to the panel is lost WARNING The use of capacitors intrinsically safe zones is dangerous and carries a risk of explosion 4 2 3 Configure SLU Status Lamp Units If SLUs are used with the panel t
74. p Weight excluding 4 85kg batteries Cable Size Accepted 1 0mm to 2 5mm CSA by Terminals Cross Sectional Area Maximum Detectors per Zone 32 dependant on type amp EOL monitoring device not allowed on Manual Release Zone Maximum Call Points Per Zone No Limit not allowed on zones 1 amp 2 PAGE 21 of 43 EQUIPMENT PUBLICATION ISSUE amp DATE 0 02 02 12 The charger output is designed for charging Powersonic Valve Regulated Sealed Lead Acid batteries which are characterised by a reducing charge current when charged from constant potential source It will not provide the maximum charging current when the other power supply outputs are fully loaded The panel requires two 12V batteries connected in series to produce 24V CONNECTING ONLY ONE 12 VOLT BATTERY OR INCORRECT CONNECTION OF THE BATTERIES WILL PERMANENTLY DAMAGE THE PANEL AND THE BATTERY The battery charger circuit is temperature compensated and relies on a Thermistor mounted near the batteries to ensure that the correct charging voltage is maintained The Thermistor type has been chosen to fit the profile of the Powersonic VRLA batteries Use of batteries by another manufacturer is not recommended A WARNING A fuse protects the internal power supply always replace this with the correct type and rating T5AH250V 20mm fuse 5A HBC Anti surge approved to BS EN 60127 o
75. pendent on SLU type 1 Emergency Abort Activated Emergency Hold Activated Gas Released Auto amp Manual Manual Only Extinguishing Disabled Local Fault Seconds Remaining to Discharge fully functional SLU only The SLU can provide the following controls dependent on SLU type 1 Manual Release 2 Emergency Abort 3 Emergency Hold 4 Auto amp Manual Manual Only The controls on the SLU can be transmitted via the serial data link or hard wired via conventional circuits on the panel see 3 9 below 3 9 Remote Inputs 3 9 1 Remote Controls This is a fully monitored input providing open amp short circuit fault monitoring Silence Alarms Re WD FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP sound Alarms and Panel Reset The EOL device is a 10k resistor 3 9 2 Remote Sound Alarms Non latching 4 7 activate general sounders When activated steady Remote Sound Alarms indication and continuous operation of general sounders When deactivated Remote Sound Alarms indication clears and general sounders stop 3 9 3 Remote Silence Alarms Single Operation 1k8 silence active sounders silencing of extinguishing sounders is inhibited until the Discharged condition is active When activated same operation as pressing the Silence Alarms button When deactivated no action 3 9 4 Remote Reset Single Operation
76. r equivalent 6 Standby Battery Requirements 6 1 Battery Capacity Calculation The usual requirement for standby batteries is 24 Hours standby plus 30 Minutes in Alarm Use the following as a guideline when calculating your requirements 24 Hours Standby Battery Mains Standby Failed X Time current H Ah A Mains Failed current is 0 060A plus ancillary equipment e g if a Status Indicator draws 0 030A then the total Mains Failed current is 0 090A Therefore over 24 hours the battery requirement is 0 090 X 24 z 2 16Ah 30 Minutes Alarm Alarm Alarm De Battery Curent X Time X rating Capacity A H Factor Required 1 5 Ah FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP Alarm current is 0 160A plus the detector current plus alarm and solenoid current plus ancillary equipment e g if one detector is in alarm and draws 0 0304 and the alarm load is 1 0 and the actuator load is 1 0A and a Status Indicator draws 0 040A then the total Alarm current is 2 23A Therefore over 30 Minutes the battery requirement is 2 23 X 0 5 x 1 5 z 1 67Ah Therefore the total Battery requirement is 2 16Ah 1 67Ah 3 83Ah Use batteries with a rating of at least 25 more than the capacity required This is to allow for deterioration of the batteries during use So the minimum battery capacity required in this example is 1 25 x 3 83 4 79Ah Note that the enclosure will only
77. r flashes rapidly for 0 5 seconds then switches off for 1 second During the OFF period the LED will display the current status for the selected circuit PAGE 18 of 43 EQUIPMENT PUBLICATION OMFCPRESSIN ISSUE No amp DATE 0 02 0242 i e OFF if circuit is normal ON if in Test or Disabled pulsing if the circuit is in fault 4 2 1 Disable Re enable Test To disable re enable or test any of the circuits in Table 2 the required circuit is selected by moving the Circuit Select Cursor and then pressing ENABLE DISABLE or TEST as required The process is as follows 1 Press the SELECT ON OFF button The Select Cursor will appear on the FIRE SIGNAL fault LED 2 Press the SCROLL button to move the cursor to the required circuit fault disabled LED The cursor will move in sequence through the relevant circuits and will then return to the FIRE SIGNAL fault LED 3 Press ENABLE to return a circuit to normal operation press DISABLE a circuit press TEST to place a circuit into Test mode 4 Repeat steps 2 amp 3 for any additional circuits 5 Press SELECT ON OFF to switch off the cursor the cursor is automatically switched off if no buttons are pressed for 60 seconds NOTE Any circuits in Disabled or Test modes are cleared to the normal mode after power to the panel is lost 4 2 2 Configure I S Zones To configure circuits to 1 5 operation the required circuit is selected by moving the Circuit Select Curs
78. re a manual reset via the FIRE RESET and or EXTINGUISHING SYSTYEM RESET buttons 3 12 1 6 INSTANT MANUAL RELEASE Switch OFF Operation of Manual Release starts the Pre discharge delay timer Switch ON Operation of Manual Release bypasses the Pre discharge delay timer amp operates the actuator circuits immediately WRITTEN BY RKP CHECKED BY AP EQUIPMENT FIRECLASS Prescient PUBLICATION OMFCPRES3 IN ISSUE No amp DATE 0 02 02 12 3 12 1 7 BUZZER PULSES AT END OF DELAY Switch OFF No change in the state of the internal buzzer during the last five seconds of the Pre discharge delay timer Switch ON The internal buzzer pulses during the last five seconds of the Pre discharge delay timer 3 12 1 8 ZONES 1 amp 2 SINGLE KNOCK Switch OFF If the system is set to Auto amp Manual mode a fire condition on both zones 1 amp 2 is required to start the pre discharge delay timer Switch ON If the system is set to Auto amp Manual mode a fire condition on either zone 1 or zone 2 will start the pre discharge delay timer 3 12 1 9 NO DISCHARGE PRESSURE SWITCH Switch OFF The Panel only indicates SYSTEM DISCHARGED when the GAS REL input is activated via a Discharge Pressure switch Switch ON The panel indicates SYSTEM DISCHARGED as soon as the actuator circuits are activated 3 12 1 10 ACTUATOR S C DISABLE Switch OFF The actuator circuits are monitored for open amp short circuit
79. s on the General Alarm Circuits Individual fault LEDs are provided on the motherboard inside the panel Both circuits can be disabled as a group Note The circuits are reverse polarity monitored The PCB terminals are marked for the active polarity Ensure that all connected devices are polarised 3 4 Extinguishing Alarm Circuit EXT SNDR One fully monitored extinguishing alarm circuit is provided monitored for Open Circuit and Short Circuit faults It is rated at 0 5A electronically fused 28VDC The End Of Line device is a 10k resistor 3k9 can also be used The Circuit Fault LED on the display flashes for any fault condition on the Extinguishing Alarm Circuit with an individual fault LED on the motherboard inside the panel The circuit can be disabled by disabling the extinguishing system the Actuators are also disabled at the same time Note The circuit is reverse polarity monitored The PCB terminals are marked for the active polarity Ensure that all connected devices are polarised 3 5 Actuator Circuits ACT1 amp ACT2 Two fully monitored actuator circuits are provided They are monitored for Open Circuit and Short Circuit faults short circuit fault indication can be disabled They are rated at 1A fused 28VDC each The End Of Line device is a 10k resistor 3k9 can also be used The Circuit Fault LED on the display flashes for any fault condition on either Actuator Circuit with individual fault LEDs on
80. scent OV when activated Extinguishing Sounder Circuit 1 2V in quiescent 24V when activated 1 3 8V in quiescent OV when activated Fire Sounder Circuit 2 1 2V in quiescent 24V when activated 3 8V in quiescent OV when activated Fire Sounder Circuit 1 1 2V in quiescent 24V when activated 3 8V in quiescent OV when activated SLU 2 Wire RS485 Data Connection Connect A at panel to A at SLU Connect B at panel to B at SLU 1 Amp 24V DC Power Supply Output Primarily for use with SIUS 250mA 24V DC Power Supply Output Primarily for use with Repeat Outputs PAGE 6 of 43 Third Stage Relay Volt Free or Powered Terminals C Normally Closed or 24V out P Pole O Normally Open or OV out Second Stage Relay Volt Free or Powered Terminals Ch Closed or 24V out Pole O Normally Open or OV out First Stage Relay Volt Free or Powered Terminals C Normally Closed or 24V out P Pole O Normally Open or OV out EQUIPMENT PUBLICATION ISSUE No amp DATE 0 FIRECLASS Prescient OMFCPRES3 IN 02 02 12 WRITTEN BY RKP CHECKED BY AP Figure 4 Prescient Block Schematic Diagram Open amp short cct flt monitored input die J Zone 1 71 21 Internal General General e
81. sly disabled circuit set a zone for intrinsically safe operation or move the cursor between SLU number and SLU type code digits See section 4 2 for details 3 19 9 DISABLE This button has no function unless the Circuit Select Cursor is ON Depending on the current mode operation of the button can disable a circuit or clear a zone from intrinsically safe operation See section 4 2 for details 3 19 10 TEST When the Circuit Select Cursor is OFF this button operates the Test Display feature sounding the internal buzzer and illuminating all the LEDs on the Display and internal control board for five seconds When the Circuit Select Cursor is ON depending on the current mode operation of the button can place the selected circuit into test mode See section 4 2 for details NOTE Important safety feature When either zone 1 or zone 2 is placed into the Test mode the panel will automatically set both zone 1 amp zone 2 into test mode see Table 2 The panel display will show that BOTH zone 1 amp 2 are in the Test mode The Test mode for zones 1 amp 2 is linked because the zones are usualy used as coincidence detection zones covering the same area Testing detectors on either zone 1 or zone 2 could inadvertently activate detectors on the other zone The clearing of the Test mode is not linked i e each zone is individually removed from the TEST mode This allows the engineer to test each zone individually if desired as r
82. t 21VDC 22uF EOL 680R Activated Detectors amp Call points allowed DIL SW configurable for 3K9 EOL Detector Zone 2 Input Protected Area Zone 21VDC 22uF EOL 680R Activated Fire Detectors only DIL SW configurable for 3K9 EOL Detector Zone 1 Input Protected Area Zone 21VDC 22uF EOL 680R Activated Fire Detectors only DIL SW configurable for 3K9 EOL AUX ZONE CIRCUITS PAGE 5 of 43 FIRECLASS Prescient Ill OMFCPRESSIN 02 02 12 EQUIPMENT PUBLICATION ISSUE No amp DATE 0 WRITTEN BY RKP CHECKED BY AP Figure 3 Motherboard Terminal Identification Part 2 Reset Relay Volt FreeTerminals C Normally Closed P Pole O Normally Open Fault Relay Volt Free or Powered Terminals de ES E Normally Closed or 24V out Pole 2 Normally Open or OV out T 5 e Fire Relay Volt Free or Powered o Terminals D Si Ld Closed or 24V out ya a 4 Normally Open or OV out gt Y C e Z 1ST STAGE 2ND STAGE 3RD STAGE Gas Released Relay Volt Free or Powered Terminals Closed or 24V out ot Pole Normally Open or OV out lt S Actuator Circuit 2 1 2V in quiescent 24V when activated 3 8V in quiescent OV when activated ACT2 Actuator Circuit 1 1 2V in quiescent 24V when activated 3 8V in quie
83. ted iii Auxiliary Zone Fire Detected iv Manual Release Activated v Extinguishing System Disabled vi Isolation Valve Closed vii Isolation Valve Abnormal viii Emergency Hold Activated configurable for auto amp manual mode Emergency Abort Activated configurable for manual only mode 7 Two Auxiliary 24VDC supply outputs 8 RS485 communication link to drive external Status Lamp Units 9 Fully monitored inputs for Gas Discharged Pressure Switch i Gas Low Pressure Switch iii Gas Isolation Valve iv Gas Trapped In Manifold WRITTEN BY RKP CHECKED BY AP v Emergency Hold Switch vi Emergency Abort Switch vii Manual Only Lock Off Switch viii Remote Controls Switches Sound alarms Silence Alarms Reset 10 Fully Monitored Outputs Configurable for Volt Free operation for i First Stage Shutdown ii Second Stage Shutdown iii Third Stage Shutdown iv Auxiliary Fire Signal v Auxiliary Fault Signal vi Gas Released Signal 1 Volt Free Relay Contacts for Auxiliary Equipment Reset Terminals for Internal Standby Batteries Site Configuration DIL Switches Fault indication LEDs Internal Buzzer Figure 1 Enclosure Dimensions p 325 00 mm gt 4 00 126 00 a O O E O Y
84. the motherboard inside the panel Both circuits can be disabled by disabling the extinguishing system the Extinguishing Alarm circuit is also disabled at the same time Note The circuits are reverse polarity monitored The PCB terminals are marked for the active polarity Ensure that all connected devices are polarised PAGE 8 of 43 EQUIPMENT PUBLICATION OMFCPRESSIN ISSUE No amp DATE 0 02 0242 3 6 Repeater Outputs Z1 Z2 AUX MR OUTPUTS 1 2 3 4 5 Each repeater output consists of an Open Collector transistor driver capable of sinking up to 50mA The following outputs are provided Z1 Zone 1 Fire Z2 Zone 2 Fire AUX Auxiliary Zone Fire MR Manual Release Activated OUTPUT 1 Emergency Hold Activated configurable for auto amp manual mode OUTPUT 2 Emergency Abort Activated configurable for manual only mode OUTPUT 3 Actuators Extinguishing Disabled OUTPUT 4 Isolation Valve Closed OUTPUT 5 Isolation Valve Abnormal 3 7 Auxiliary 24VDC Supply The panel provides two auxiliary 24Vdc power supply outputs for connection to ancillary equipment 1 AUX 250 24V OV This output is rated at 250mA electronically fused 24 Volts D C 2 AUX 1A 24V OV This output is rated at 1A electronically fused 24 Volts D C 3 8 Status Lamp Unit The panel communicates with the Status Lamp Units SLU via two wire RS485 serial data The following indications can be provided de
85. tion Enable Disable Switches Two sets of DIL switches and one jumper link are available on the motherboard to allow the panel to be configured for additional site specific functions 3 12 1 Function Select Switch 5 1 9 CONFIG I S INPUTS PRE DISCHARGE DELAY 55 om PRE DISCHARGE DELAY 10S sm PRE DISCHARGE DELAY 205 gj PRE DISCHARGE DELAY 405 og SILENT ZONE TEST BUZZER DISABLE LATCHED FAULTS eg INSTANT MANUAL RELEASE sm BUZZER PULSES AT END OF DELAY m ZONES 1 amp 2 SINGLE KNOCK NO DISCHARGE PRESSURE SWITCH L P ACTUATOR S C DISABLE 1 MIN om 2 RESET m 4MIN INHIBIT om 8MIN PERIOD om 16 MIN CLEAR ACTUATORS AFTER 1 MIN og SILENCE ALARMS BEFORE RESET OUTPUT 1 AUTO 2 MANUAL sm CONFIG SLU 2m 3K9 EOL GAS LOW This consists of two sets of 12 way DIL switches providing the following options 3 12 1 1 CONFIG 1 5 INPUTS When in the ON position enables zones 1 2 Aux zone and Manual Release input to be individually configured for standard or intrinsically safe monitoring The circuits need to be configured for I S monitoring if Galvanic Isolators or Zener Barriers are connected 1 5 zones will then be monitored for a 10k EOL resistor and different monitoring limits due to the I S barrier isolator series load See section 4 2 2 for configuration details PAGE 12 of 43 WRITTEN BY
86. tton 3 19 4 EXTINGUISHING RESET This button controls the resetting of fault and active conditions on the Extinguishing section of the panel Faults common to the Fire section amp the Extinguishing section can also be reset with this button The resetting of the Extinguishing system can be inhibited up to 30 minutes once the extinguishing system has been activated and the accompanying yellow LED is illuminated steady to PAGE 17 of 43 WRITTEN BY RKP CHECKED BY AP EQUIPMENT FIRECLASS Prescient PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 12 indicate that the Extinguishing System Reset is inhibited 3 19 5 SILENCE BUZZER This button silences the internal buzzer during any fault or alarm condition The accompanying yellow LED is illuminated steady to indicate that the buzzer has been silenced Any new fault or alarm will restart the buzzer and clear the LED 3 19 6 AUTO amp MANUAL MANUAL ONLY This button toggles the panel status between Automatic amp Manual and Manual Only modes If any Field Auto Manual switch is in the Manual Only position then this button has no effect the Manual Only LED will be flashing 3 19 7 SELECT ON OFF This button toggles the Circuit Select Cursor On and OFF See section 4 2 for more details 3 19 8 ENABLE This button has no function unless the Circuit Select Cursor is ON Depending on the current mode operation of the button can re enable a previou
87. ure Fault GAS LOW This is a fully monitored input providing open amp short circuit fault monitoring The EOL device is a 10k resistor activated by a 680R resistor Activation illuminates the GAS LOW LED and PAGE 9 of 43 EQUIPMENT PUBLICATION OMFCPRES3IN ISSUE No amp DATE 0 02 02 12 raises the general fault condition An open or short circuit fault is indicated by the Circuit Fault LED on the display and a Gas Low Fault LED on the motherboard The input is configurable for normally open or normally closed operation via a DIL switch on the motherboard 3 9 8 Extinguishing Isolation Valve Status ISO VALVE This is a fully monitored input providing open amp short circuit fault monitoring The EOL device is a 10k resistor giving an ISOLATION VALVE ABNORMAL indication An open or short circuit fault is indicated by the Circuit Fault LED on the display and a Isolation Valve Fault LED on the motherboard Three states are possible on the input 1 Valve Closed Activated by a 680R resistor flashing the Valve Closed LED on the display board amp pulsing the internal buzzer 2 Valve Open Activated by a 2k2 resistor no indication is given on the panel as this is the healthy state for the input 3 Valve Abnormal Activated by the 10k EOL resistor flashing the Valve Abnormal LED on the display board amp raising a general fault indication A 2 second delay is applied to the abnormal condition to avoid
88. used Place the chassis in the bottom of the enclosure and Re connect the internal mains cables to the mains terminal block Ensure that the Earth lead to the Earth Bar is connected to the Mains Terminal block Re connect the Earth lead to the chassis and refit the chassis on the four mounting screws Reconnect the display ribbon cable to the motherboard Connect 230VAC mains to the mains terminal block provided inside the enclosure ensuring that the mains supply is isolated at the source The mains cable must be secured inside the enclosure using a Cable Tie see Figure 6 DO NOT TURN THE MAINS ON An appropriate lockable double pole disconnect device shall be provided as part of the building installation This device must have a minimum contact gap of 3mm The mains supply should be protected by a 5A fuse Use only mains cable compliant to BS6004 BS6500 or equivalent within the following limits Conductor Cable Diameter Diameter Minimum 4 0mm 1 0mm 0 8mm Maximum 8 0mm 2 25mm 4 0 2 PAGE 30 of 43 EQUIPMENT PUBLICATION ISSUE No amp DATE 0 OMFCPRESSIN 02 02 12 8 5 Commissioning Procedure NOTES In order to avoid accidental operation of the solenoid valves during commissioning the solenoid valves should remain disconnected during the commissioning process A suitable load resistor typically 47R 20W providing a 0 6A load check manufacturer s datash
89. wer to the panel must be made using shielded fire resistant cable such as FP200 The shield of each cable must be connected to the earth bar inside the enclosure The maximum cable core size permitted is 2 5mm CSA cross sectional area The total end to end resistance of any core should not exceed 20 Ohms addition connection to the Status Lamp Units SLUs should be made via data grade fire resistant cable The total cable length for all SLUs should not exceed 2000 metres FIRECLASS Prescient WRITTEN BY RKP CHECKED BY AP Cable Cross Maximum CIRCUIT sectional Cable Run Area Zone 1 0mm 350 metres Zone 1 5mm 600 metres Alarm Actuator 1 0mm 200 metres Alarm Actuator 1 5mm 350 metres Mains cable compliant to BS6004 BS6500 or equivalent must be used for connection to the Power Supply Cable up to 4mm CSA may be used PAGE 29 of 43 EQUIPMENT PUBLICATION ISSUE No amp DATE 0 OMFCPRESSIN 02 02 12 8 4 Installation Procedure 1 Unpack the Control panel If the panel door is locked locate the panel keys usually fixed to the top of the panel and open the door Locate the small plastic bag containing the installation spares as follows i 22 x End of Line Resistors 10k ohms colour code brown black orange gold ii Remote controls switch resistors Sound alarms 4k7 ohms yellow purple red gold Silence alarms 1 8 ohms brown grey red go

Download Pdf Manuals

image

Related Search

Related Contents

Simon Son AF def BN  Kodak M577 User's Manual  Version1  S.Ha.R.K. User Manual Volume III S.Ha.R.K. MODULES Written by  取扱説明書  

Copyright © All rights reserved.
Failed to retrieve file