Home

Installation Manual - Electricianforum.co.uk

image

Contents

1. etm Ceiling Acceptable here NEVER HERE Top of detector acceptable here NOTE Measurements shown are to the closest edge of the detector Wall Smoke detectors should always be installed in accordance with NFPA 72 the National Fire Alarm Code Smoke detectors should always be located in accordance with e Paragraph 2 2 1 1 1 of NFPA 72 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including basements and excluding crawl spaces and unfinished attics In new construction a smoke detector also shall be installed in each sleeping room e Paragraph 2 2 1 1 2 of NFPA 72 Split level arrangement Smoke detectors are required where shown Smoke detectors are optional where a door is not provided between living room and recreation room Qr Smoke Detector is designed to use Eveready Energizer E91 Alkaline Batteries Do not use other brands of batteries with the Smoke Detector Using brands other than the Eveready Energizer will void UL approval and may affect the system s operation 28 LIMITED WARRANTY Digital Security Controls Ltd warrants the original purchaser that for a period of twelve months from the date of purchase the product shall be free of defects in materi als and workmanship under normal use During the warranty period Digital Security Controls Ltd shall a
2. To restore the keypad defaults perform the following 1 Enter 8 Installers Code 2 Press 99 NOTE This does not affect the PC5132 portion of the keypad Testing amp Mounting S E Cc T 0 N 5 5 1 Test the Reception of Wireless Devices It is very important to test the proposed placement of each wireless device before it is mounted Following these steps will test the placement of the wireless motion detectors WLS904P WLS914 wireless smoke detectors WLS906 wireless glassbreak detectors WLS912 and wireless door window contacts WLS907 WLS925L based on the signal strength between the RF5501 433 and the device NOTE You cannot test the Wireless Keys WLS909 WLS919 in this mode See section 5 2 for instructions on testing these devices You cannot run a placement test on the RF Jam Detect zone 1 Temporarily place the device you want to test in the place you want to mount it Ata system keypad enter 8 Installer Code Enter programming section 904 Enter the 2 digit zone number for the device to be tested Activate the device being tested until a result is displayed on the keypad or sounded by the keypad or bell WLS904P L 433 WLS91 4 433 Remove the detector from its backplate wait for 1 2 seconds then reattach the detector to its backplate WLS906 433 Remove the detector from its backplate wait for 5 seconds then reattach the detector to its backplate Or hold a magnet near the raised
3. the display will look like this 12 Program For information on programming the rest of your security system please refer to your system s Installation Manual 2 2 Function Key Options The function keys are programmed in sections 1 to 5 By default the 5 function keys on the keypad are programmed as Stay Arm 03 Away Arm 04 Chime 06 Sensor Reset 14 and Quick Exit 16 You can change the function of each key on every keypad Please see your system s nstallation Manual for instructions on programming the keys and a complete list of all the function key options available for your system 2 3 Clock Options The RF5501 433 will display the current time after 30 seconds of no key presses To set the correct time and date for the system please refer to your system s nstruction Manual You can change how the keypad displays the time with the following options To change the clock options 1 Enter 8 Installer Code 2 Enter 000 to go to keypad programming 3 Enter section 6 to go to clock options 4 To turn any of the options on or off press 1 2 or 8 NOTE If the Time does not display on keypad option is selected make sure that the Keypad displays time when zones are open option is also selected 1 ON Time displays on keypad OFF Time does not display on keypad 2 ON Clock display is in AM PM format e g 08 00 AM OFF Clock display is in 24 hour format e g 20 00 3 ON Keypad do
4. LCD5501Z keypad that presents system status using an LCD style display with fixed messages With the addition of the receiver portion the control panel will now support up to 32 zones The RF5501 433 is compatible with the following DSC security systems e PC5010 all versions PC1555 MX 1565 v2 3 amp higher e PC5008 v2 3 amp higher e PC5015 all versions Power608 v2 3 amp higher e PC580 585 v2 3 amp higher e PC5020 all versions NOTE Control panels previous to version 2 3 support 8 wireless zones Only one RF5501 keypad can be connected per system If more keypads are required please select other DSC compatible keypads for the system being installed Specifications and Features e Maximum Current Draw 220 mA with back lighting boost on and both PGMs drawing maximum current of 50 mA each e Frequency 433 92 mHz e Voltage 12V e Zones receiver can receive signals from up to 32 wireless zones e Supervisory programmable supervisory window 4 to 24 hours e Location can be wired up to 1000ft 305m from the main panel with 22 gauge wire for longer wire runs thicker gauge wire must be used e The wiring used in this circuit connection shall be insulated with PVC TFE PTFE FEP neoprene or polymide e Compatibility The RF5501 433 can be connected to the following panels PC5010 PC5015 PC5020 PC5008 PC 1555 1565 PC580 585 e Connects to control panel via 4 wire Keybus e One keypad zone input e Optional t
5. enabled Disabled Option 7 Zone 23 Supervision enabled Disabled L__ Option 8 Zone 24 Supervision enabled Disabled 26 PROGRAMMING WORKSHEETS 85 Zone Device Supervision Options 25 32 Default ON Option ON Option OFF Option 1 Zone 25 Supervision enabled Disabled Option 2 Zone 26 Supervision enabled Disabled L_ Option 3 Zone 27 Supervision enabled Disabled Option 4 Zone 28 Supervision enabled Disabled Option 5 Zone 29 Supervision enabled Disabled Option 6 Zone 30 Supervision enabled Disabled Option 7 Zone 31 Supervision enabled Disabled L__ Option 8 Zone 32 Supervision enabled Disabled 90 Other Options Default Option ON OFF OFF 1 5 For Future Use ON 6 Keypad Zone Enabled PGM2 Enabled OFF 7 RF Jam Detect Disabled RF Jam Detect Enabled OFF 8 Global Placement Test Individual Placement Test RF Jamming Detection 93 RF Jam Detect Zone Default 00 Lt 1 Select an unused zone that will be set to the tamper state when a jamming signal is detected Valid entries 01 32 00 No RF Jam tone selected 27 Guidelines for Locating Smoke Detectors N A P P E D l x A Experience has shown that all hostile fires in family living units generate smoke to a greater or lesser extent Experiments using typical fires in family living units indicate that de precede detectable levels of heat in most cases In existing homes NFPA smoke de
6. line on the outer rim Then remove the magnet WLS907 433 WLS925L 433 Open and close the contact by moving the magnet away from the unit If the unit is attached to a door or a window open and close the door or window to activate the device WLS912L 433 Press and hold the test mode tab for 5 seconds Release the test mode tab The keypad will display the test result 6 Read the test results at the keypad GN BEN Result LED Keypad LCD Keypad Buzzer Bell Good Light 1 On Steady Good 1 Beep Squawk Bad Light 3 On Steady Bad 3 Beeps Squawks Activate the device until you get 3 good results in a row Wait 10 seconds between each test on the same device You may mount wireless devices where results were good Devices indicating a bad result must be moved to another location You may only have to move the device a few inches to correct a bad result NOTE Do not mount any device where a bad test result was indicated If several wireless devices produce BAD test results you may need to move the RF5501 433 to a better location 7 To test another device press once then repeat steps 4 6 Continue to test the devices until both the RF5501 433 and the devices are in good locations 8 To exit installer programming press twice TES TING amp MOUNTING 5 2 Test WLS909 amp WLS919 Reception The wireless key WLS909 cannot be tested using the module placement test described above To ensure that the RF550
7. of reasons some of which follow The smoke detectors may have been improperly installed or posi tioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every fire is different in the amount of smoke produced and the rate of burning Smoke detectors cannot sense all types of fires equally well Smoke detectors may not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits children playing with matches or arson Even if the smoke detector operates as intended there may be cir cumstances when there is insufficient warning to allow all occu pants to escape in time to avoid injury or death E Motion Detectors Motion detectors can only detect motion within the designated ar eas as shown in their respective installation instructions They can not discriminate between intruders and intended occupants Motion detectors do not provide volumetric area protection They have mul tiple beams of detection and motion can only be detected in unob structed areas covered by these beams They cannot detect motion which occurs behind walls ceilings floor closed doors glass parti tions glass doors or windows Any type
8. system does not have partitions enter 1 for the first digit 1st digit Enter O for Global Keypad 1 8 for keypad partition Enter 1 for Partition 1 Keypad Enter 2 for Partition 2 Keypad 2nd digit Enter 1 to 8 for Slot Assignment 5 Press the key twice to exit programming 6 After assigning all keypads perform a supervisory reset by entering 8 Installer s Code 902 The panel will now supervise all assigned keypads and enrolled modules on the system To review which modules the control panel is currently supervising 1 Enter 8 Installer s Code 2 Enter 903 to display all modules On the RF5501 433 keypad 1 and 17 will scroll on the keypad to indicate that the RF5501 433 is present on the system 1 designates the keypad section and 17 is used to show the receiver section is also supervised If using an LCD5501Z keypad scroll until the module name appears on the display 3 To exit press If both modules do not show on the keypad one of the following conditions may be present e the keypad is not connected properly to the Keybus e there is a problem with the Keybus wiring run e the keypad does not have enough power 1 6 Downloading This product has an integrated RF5501 433 v5 0 receiver When downloading to this keypad please select the PC5132 433 v5 0 file DLS2002 and greater must be used in order to have the capability of downloading to this keypad 1 7 Compatible Wireless Devices Please refer
9. the following at any system keypad 1 Enter 8 Installer Code to enter Installer Programming 2 Enter 804 to enter the RF5501 Module Programming 3 Enter sections 82 85 Enable and disable zone supervision by turning on off the corresponding zone toggle option 4 To exit press 4 4 Jamming Signal Detection The RF5501 433 receiver detects jamming signals that can prevent the receiver from properly receiving transmissions from enrolled devices When jamming signals are detected the panel can report a jamming trouble condition in one of two ways By default the panel will report an RF Jam Trouble General System Tamper on the PC5010 13 O T HER PROGRAM MIN G Toturn OFF jamming signal detection 1 Enter 8 Installer Code to enter Installer Programming 2 Enter 804 to enter the PC5132 Module Programming 3 Turn ON section 90 option 7 4 To exit press The RF5501 433 can also be programmed to indicate the jamming trouble condition with the RF Jam Zone For RF Jam Zone to work you must select an unused zone to be used as the RF Jam Detect zone When the receiver detects an attempt to jam the RF signal the RF Jam Detect zone will be violated and the system will generate a tamper signal When the jamming signal is gone the RF Jam Detect zone closes and the system sends a tamper restore signal To enable RF jamming detection 1 Enter 8 Installer s Code 2 Enter programming section 8
10. to television or radio reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Re orient the receiving antenna Relocate the alarm control with respect to the receiver Move the alarm control away from the receiver Connect the alarm control into a different outlet so that alarm control and receiver are on different circuits If necessary the user should consult the dealer or an experienced radio television technician for additional suggestions The user may find the following booklet prepared by the FCC helpful How to Identify and Resolve Radio Television Interference Problems This booklet is available from the U S Government Printing Office Washington D C 20402 Stock 004 000 00345 4 IC 160A RF550143 The term IC before the radio certification number only signifies that Industry Canada technical specifications were met A DSC erkl rer herved at denne komponenten overholder alle viktige krav samt andre bestemmelser gitt i direktiv 1999 5 EC Por este meio a DSC declara que este equipamento est em conformidade com os requisitos essenciais e outras determina es relevantes da Directiva 1999 5 EC DSC bekr ftar h rmed att denna apparat uppfyller de v sentliga kraven och andra relevanta best mmelser i Direktivet 1999 5 EC Con la presente la Digital Security Controls Ltd dichiara che ques
11. 04 3 Enter section 93 Enter the 2 digit number of the RF Jam Detect zone 01 to 32 in the programming section 4 Disable supervision for the RF Jam detect zone by turning the relevant option off in section 82 83 84 or 85 See section 4 3 for more information 5 RF jamming detection is now enabled To exit Installer programming press NOTE A jamming condition will be indicated as RF Jam Zone if section 93 is pro grammed regardless of the RF Jam indicates Trouble option section 90 option 7 4 5 Receiver Software Default Returning the receiver programming to factory default settings is a quick way to remove all the enrolled devices from the system and reset all the programming in section 804 NOTE Performing this procedure will not change any programming sections except 804 Resetting the control panel to factory default settings will not return the RF5501 433 to factory default settings To restore the PC5132 portion of the RF5501 433 programming to the factory default settings perform the following 1 Enter 1 8 Installers Code 2 Enter programming section 996 3 Enter the Installer s Code followed by 996 again Press The software for the receiver section will be restored to its factory default settings For instructions on restoring the default programming of the control panel or any other connected module see your system nstallation Manual 4 6 Keypad Software Default
12. 1 433 is receiving transmissions from these devices conduct the following tests WLS909 WLS919 Use the function keys to arm and disarm the system at several different points in the installation If these devices do not operate from all points in the installation you will need to move the RF5501 433 receiver Moving the RF5501 433 higher will usually improve the reception If you move the RF5501 433 repeat the tests described in sections 5 1 and 5 2 on all the wireless devices Continue to test the devices until you have found satisfactory locations for the RF5501 433 and the WLS904P WLS906 and WLS907 devices and there is good reception between the RF5501 433 and the WLS909 device Mount the Wireless Devices If you have conducted the placement test described in section 5 1 and got 3 Good results in a row for each device you can mount the wireless devices See the Installation Sheet for each device for mounting instructions Additional Notes S E Cc T 0 N 6 6 1 Trouble Conditions The control panel always watches for possible trouble conditions If a trouble condition occurs the keypad Trouble light will turn on and the keypad will beep Press 2 to display the trouble conditions The following trouble conditions apply to the receiver portion identified as the PC5132 by the panel and or any enrolled devices For a description of all troubles please see your system nstallation Manual The following trouble con
13. 3 Instruction Sheet for walk test instructions Programming Worksheets S E C T 0 N 8 000J Keypad Programming 1 Enter 8 Installer s code 2 Enter 000 to go to keypad programming 0 Keypad Enrollment Valid entries are 01 88 e g enter 11 for partition 1 slot 1 Default 11 1st digit Enter O for Global Keypad Enter 1 for Partition 1 Keypad Enter 2 for Partition 2 Keypad etc 2nd digit Enter 1 to 8 for Slot Assignment Slot u a i 1 5 Function Key Assignments 1 Key 1 2 Key2 3 Key3 4 Key 4 5 Key 5 Defaults 03 04 06 14 16 Stay Away Chime Reset Exit l l l l I l 6 RF5501 433 Keypad Options Default Option On Off ON I 1 Local Clock Display Enabled Display Disabled ON I 2 Local Clock Displays AM PM Displays 24 hour Time OFF __ 3 Open Zones Override Clock Display Do Not Override Clock OFF __ 4 _ For Future Use OFF L 5 _ Alarms Not Displayed While Armed Always Displayed While Armed OFF __ 6 Door Chime Enabled for Zone Openings Door Chime Disabled OFF __ 7 Door Chime Enabled for Zone Closings Door Chime Disabled OFF 8 For Future Use 7 Emergency Key Options Default Option On Off ON L I 1 F Key Enabled F Key Disabled ON L I 2 A Key Enabled A Key Disabled ON L I 3 P Key Enabled P Key Disabled OFF __ 4 7 For Future Use OFF L i 8 Low Temperature Alert Enabled Low Temperature Alert Disabled PROGRAMMING WORKSHEETS Door Chime
14. E oeei aien ia 12 MOWING NE A A Co WinMe cese ei r A Ea eE Ee E Oa ae EEDE 1 4 Applying Power a 1 5 Enrolling the Keypad irrist roeie p eR a E eei aeii 4 16 Downloadihg asic 2 kine aim iel kyn A e aaa ini EEE E ei aE kemi aR 5 1 7 CompatibleWirelessDevices AM M m gt e gt e gt e gt Zm gt Z m tnt 5 Ng NN SE deeds 5 Section 2 Keypad Programming 6 2 1 Programming the Keypad ser sekeri epi kii ghee 24 tide Binay EEN E eE EEE 6 22 FuUNnetion KEY O ehil pk e A e e 6 20 WCIOCK OPHION Sek De ak a R le ala ee aes 6 2 4 Alarms Displayed While Armed Option m m 7 2 5 Emergency Fire Auxiliary Panic Key Options 7 26 DOOR CAMS 84 0 gh Esecek amaaa terete E e adama 7 27 gt EOW Temperat Alem e e naam e cette tet e nes testeins 8 Section 3 Receiver Programming 9 Enroll Ge Program DEVICES e ari sma catty ee e adayan m earns ra galan 9 3 1 l dentifiedWirelessKeys sm9 3 2 Enroll Wireless Devices USING ZONE Sise sansi na paya sa am sey a mia 9 3 3 A Note About Electronic Serial Numbers 10 3 4 Enroll Wireless Devices Using Zones sa 1O 3 5 RF5501 433 PGM Outputs eze dd 3 6 Deleting Wireless Devices aii Section 4 Other Programming 12 AA Program ZOneSand Partitions nneresnerispeisnan ne E E many 12 4 2 Enable Receiver Supervision 212 4 3 Enable Supervision of Wireless Zones se 19 44 RF Jam Ditet ZONE relay den dalan a i aa aaa sean all u
15. Sound Programming 1 Enter 8 Installer s code 2 Enter 2 digit zone number 01 32 then select door chime sound option 1 4 Repeat for each zone that is to sound a chime Zone Location 1 2 3 4 4 Beeps Bing bing Ding dong Alarm tone default 01 021 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 l NOTE Options 5 8 are for future use and must be OFF 20 PROGRAMMING WORKSHEETS Zone Location 1 2 3 4 4Beeps Bing bing Ding dong Alarm tone default 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 99 Keypad Default 2 PROGRAMMING WORKSHEETS 804 Wireless Expansion Programming PC5132 portion e 6 digit entry is required See Section 3 1 A note on Electronic Serial Numbers for details on programming 6 digit serial numbers e When enrolling devices with a 5 digit entry please use the 5 digit serial number printed on the de
16. WARNING Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer Installation Manual RF55O 1 433 DLS2002 and higher version 5 O WARNING Please Read Carefully Note to Installers This warning contains vital information As the only individual in contact with system users it is your responsibility to bring each item in this warning to the attention of the users of this system System Failures This system has been carefully designed to be as effective as pos sible There are circumstances however involving fire burglary or other types of emergencies where it may not provide protection Any alarm system of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons Some but not all of these reasons may be E Inadequate Installation A security system must be installed properly in order to provide adequate protection Every installation should be evaluated by a se curity professional to ensure that all access points and areas are cov ered Locks and latches on windows and doors must be secure and operate as intended Windows doors walls ceilings and other build ing materials must be of sufficient strength and construction to pro vide the level of protection expected A reevaluation must be done during and after any construction activity An evaluation by the fire a
17. amper version e Five programmable function keys e Ready green Armed red and Trouble yellow status lights e Upto 2 open collector type PGM outputs e Low temperature zone option see section 2 7 2 1 Installation S E Cc T l fe N 1 1 Unpacking The RF5501 433 package includes the following parts 1 One RF5501 433 keypad Two 5 6K Ohm resistor Four mounting screws One keypad inner door label One set of Fire Auxiliary and Panic key labels One LCD5501Z User Sheet One RF5501 433 Installation Manual 2 Mounting You should mount the keypad where it is accessible to designated points of entry and exit Once you have selected a dry and secure location perform the following steps to mount the keypad 1 2 3 Remove the keypad backplate by loosening the screw located at the base of the unit Secure the keypad backplate to the wall in the desired location Use the screws provided Before attaching the keypad to its backplate complete the keypad wiring as described in the next section Ensure the mounting location is o 1 1 Dry Central to the proposed placement of all wireless devices Far from sources of interference including electrical noise computers televisions electric motors in appliances and heating amp air conditioning units large metal objects such as heating ducts and plumbing which may shield the antenna 3 Wiring Before beginning to wire the unit ensure that all power AC t
18. cient Time There may be circumstances when the system will operate as in tended yet the occupants will not be protected from the emergency due to their inability to respond to the warnings in a timely manner If the system is monitored the response may not occur in time to protect the occupants or their belongings E Component Failure Although every effort has been made to make this system as reliable as possible the system may fail to function as intended due to the failure of a component E Inadequate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance The complete system should be tested weekly and immediately after a break in an attempted break in a fire a storm an earthquake an accident or any kind of construction activity inside or outside the premises The testing should include all sensing devices keypads consoles alarm indicating devices and any other operational de vices that are part of the system E Security and Insurance Regardless of its capabilities an alarm system is not a substitute for property or life insurance An alarm system also is not a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Table of Contents u A 8 amp amp E O F O V G V Introduction 2 Section 1 Installation 3 1i e FE E
19. d must first obtain an authorization number Digital Security Controls Ltd will not accept any shipment whatsoever for which prior authorization has not been obtained Products which Digital Security Controls Ltd determines to be repairable will be repaired and returned A set fee which Digital Security Controls Ltd has predetermined and which may be revised from time to time will be charged for each unit repaired Products which Digital Security Controls Ltd determines not to be repairable will be replaced by the nearest equiva lent product available at that time The current market price of the replacement product will be charged for each re placement unit FCC COMPLIANCE STATEMENT CAUTION Changes or modifications not expressly approved by Digital Security Controls Ltd could void your authority to use this equipment This equipment generates and uses radio frequency energy and if not installed and used properly in strict accordance with the manufacturer s instructions may cause interference to radio and television reception It has been type tested and found to comply with the limits for Class B device in accordance with the specifications in Subpart B of Part 15 of FCC Rules which are designed to provide reasonable protection against such interference in any residential instal lation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference
20. ditions apply to the RF5501 433 and or any enrolled devices General System Tamper This trouble is generated when the RF5501 433 plastic cover is removed and or if there is a jamming condition present General System Supervisory This trouble will be indicated if the panel loses communication with any module connected to the Keybus The event buffer will log a detailed description of the event Device Low Battery This trouble is generated when a wireless device exhibits a low battery condition Press 7 one two or three times to view which devices are experiencing battery failure An LED keypad will indicate battery failure using zone lights 1 to 8 Zone Tamper This trouble is generated when an enrolled wireless device is removed from its mounting location Zone Fault Each wireless zone will send a supervisory signal every 64 minutes If the receiver does not receive a signal within the time programmed for the Wireless Supervisory Window it will generate a zone fault Tamper Switches Removing the RF5501 433 from its mounting location will cause a general system tamper Wireless Zone Low Battery Transmission Within the supervisory transmission the device will indicate the status of the battery If a battery is low the system will indicate a Device Low Battery trouble The system will delay reporting the event to the central station for the number of days programmed for Zone Low Battery Transmission Delay in section 370 This wi
21. ease refer to your System Installation Manual for available PGM outputs NOTE If the RF5501 433 is connected to the PC580 5PC85 PC 1555 PC 1565 P 48 P 6B all versions PC5010 v1 x P832 v1 x or the WSS5010 1 0 2 1 the RF5501 PGM outputs cannot be programmed to follow main panel PGM outputs 1 or 2 2 Activate for a programmable amount of time when a signal is received from a wireless key programmed with output option 31 or 32 RF5501 PGM pulse and the PGM output programming section 70 or 71 is programmed with option 15 RF5501 PGM pulse The amount of time that the PGM outputs can be programmed to remain on is programmed in sections 72 and or 73 The default activation time is 5 seconds 3 Toggle state when a signal is received from a wireless key programmed with option 31 or 32 and the PGM output programming section 70 or 71 is programmed with option 16 RF5501 PGM toggle 3 6 Deleting Wireless Devices To remove a wireless device from the system follow the guideline for adding a wireless device Program the ESN as 000000 The wireless device for the zone will be removed Now that you have enrolled all the wireless devices you willneed to program the system to work properly with the devices See section 4 for more information Other Programming S E Cc T l 0 N 4 4 1 Program Zones and Partitions Now that you have enrolled the wireless devices you should complete all zone programming on the system Although the exact p
22. es not display time when zones are open OFF Keypad displays time when zones are open 5 When you are finished programming the clock options press to exit NOTE Ona PC5020 v3 2 and higher if a Loss of Clock trouble 5 is present on the system the display will be as shown 6 KEYPAD P ROGRAMMING 2 4 Alarms Displayed While Armed Option You can disable the display of alarms on the keypad when the system is armed The display of alarms is enabled by default To disable the display of alarms when the system is armed turn off section 6 option 5 1 Enter 8 Installers code 2 Enter 000 to go to keypad programming 3 To turn the display of alarms on or off enter section 6 4 Turn option 5 on or off 5 ON Alarms not displayed while system is armed OFF Alarms are always displayed while system is armed 5 When you are finished press to exit 2 5 Emergency Fire Auxiliary Panic Key Options You can enable or disable the Fire Auxiliary and Panic keys at each keypad These keys are enabled by default Please see your systems Installation Manual for more information on these keys and their options To turn any of the emergency keys on or off on the keypad 1 Enter 8 Installer s code 2 Enter 000 to go to keypad programming 3 Enter section 7 4 To turn the emergency key options on or off press 1 2 or 3 1 ON Fire key enabled OFF Fire key disabled 2 ON Auxil
23. he zone input disabled see section 90 the keypad will report an alarm condition If the environment becomes less than 6 C Once the temperature is greater than 8 C the zone will restore depending on zone type and panel status Enter 8 Installer Code Enter 000 Enter Section 7 Press 8 to enable disable temperature sensor 8 ON Low Temperature Alert enabled OFF Low Temperature Alert disabled Receiver Programming S E C T l N 3 Enroll amp Program Devices This section describes how to enroll and program e wireless devices using zones WLS904PL 433 WLS906 433 WLS907 433 WLS912L 433 WLS914 433 and WLS925L 433 e wireless keys WLS909 433 WLS919 433 For more information on these devices read the instruction sheet included with each device 3 1 Identified Wireless Keys Reporting by the system of openings closings by individual wireless keys and command output 7 activation by wireless key buttons may be supported on certain control panels To do this the system will reserve access codes 17 32 for wireless keys 01 16 respectively You must program one access code for each wireless key using 115 access code programming for this feature to work correctly NOTE Program these access codes on the system after you have connected the RF5501 433 to the Keybus see section 2 4 Refer to your system nstallation Manual for information on access code programming Opening Closing By Wireless Key Repor
24. iary key enabled OFF Auxiliary key disabled 3 ON Panic key enabled OFF Panic key disabled 5 When you are finished press to exit 2 6 Door Chime Options You can program the RF5501 433 keypad to sound a tone when any zone is opened or closed There are two parts to the RF5501 433 door chime programming e Program if the RF5501 433 will chime when zones are opened and or closed e Program the type of sound the RF5501 433 will make when an individual zone is opened or closed For the door chime feature to work you will also need to turn on the Door Chime attribute for each zone that will trigger the chime This programming is done in the control panel software Refer to your control panel s Installation Manual for more information Door Chime on Zone Openings Closings You can program each RF5501 433 keypad to sound a door chime when zones are opened and or when they are closed By default RF5501 433 keypads are programmed to sound door chimes on both zone openings and closings To change the door chime opening closing settings at each RF5501 433 keypad 1 Enter 8 Installer s code 2 Enter 000 to go to keypad programming 3 Enter section 6 4 To turn the options on or off press 6 or 7 7 KEYPAD PROGRAM MIN G 6 ON Door Chime Enabled for Zone Openings OFF Door Chime Disabled for Zone Openings 7 ON Door Chime Enabled for Zone Closings OFF Door Chime Disabled for Zone Closings 5 When you a
25. iately conduct a complete system test to ensure that the system operates as intended E Failure of Replaceable Batteries This system s wireless transmitters have been designed to provide several years of battery life under normal conditions The expected battery life is a function of the device environment usage and type Ambient conditions such as high humidity high or low tempera tures or large temperature fluctuations may reduce the expected battery life While each transmitting device has a low battery moni tor which identifies when the batteries need to be replaced this moni tor may fail to operate as expected Regular testing and maintenance will keep the system in good operating condition MB Compromise of Radio Frequency Wireless Devices Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the radio path or delib erate jamming or other inadvertent radio signal interference E System Users A user may not be able to operate a panic or emergency switch pos sibly due to permanent or temporary physical disability inability to reach the device in time or unfamiliarity with the correct operation It is important that all system users be trained in the correct opera tion of the alarm system and that they know how to respond when the system indicates an alarm E Smoke Detectors Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number
26. le from an existing system you will have to disable supervision of the PC5132 NOTE Deleting all devices from the RF5501 433 or defaulting the RF5501 433 will cause a PC5132 supervisory fault To disable PC5132 supervision 1 Disconnect the RF5501 433 from the Keybus 2 Enter 8 Installer Code 3 Enter 902 The control panel will clear all supervision and re scan the system for connected modules The scan will take approximately one minute 4 To exit press To review which modules the control panel is currently supervising 1 Enter 8 Installer Code 2 Enter 903 to display all modules On LED keypads light 17 will indicate that the PC5132 is present on the system On LCD keypads scroll until the module name appears on the display 3 To exit press T H E R PROGRAM MIN G If the PC5132 portion of the RF5501 433 module does not show on the keypad one of the following conditions may be present e the module is not connected properly to the Keybus e there is a problem with the Keybus wiring run e the module does not have enough power e no devices have been enrolled on the RF5501 433 4 3 Enable Supervision of Wireless Zones NOTE for PC5010 v1 x control panels only For UL Listed installation Double EOL resistors must be enabled in the PC5010 for the wireless zones to be supervised If normally Closed or Single EOL resistors are selected the PC5010 will not be able to supervise the wireless de
27. less Key 09 Wireless Key 02 Wireless Key 10 Wireless Key 03 Wireless Key 11 Wireless Key 04 Wireless Key 12 Wireless Key 05 Wireless Key 13 Wireless Key 06 Wireless Key 14 Wireless Key 07 Wireless Key 15 Wireless Key 08 Wireless Key 16 24 PROGRAMMING WORKSHEETS Entry Description 00 ull No Operation 09 PC5208 PGM9 01 ain Panel PGM1 10 PC5208 PGM10 02 ain Panel PGM2 11 PC5204 PGM11 03 PC5208 PGM3 12 PC5204 PGM12 04 PC5208 PGM4 13 PC5204 PGM13 05 PC5208 PGM5 14 PC5204 PGM14 06 PC5208 PGM6 15 PC5102 PGM Pulse local 07 PC5208 PGM7 16 PC5102 PGM Toggle local 08 PC5208 PGM8 70 RF5501 PGM1 Output Option Default 01 PGM1 Output Option 1 1 RF5501 433 Output Options 71 RF5501 PGM2 Output Option Default 02 PGM2 Output Option 1 _1 72 RF5501 PGM1 Output Activation Time Default 00 PGM1 Output Activation Time Minutes Default 05 PGM1 Output Activation Time Seconds 73 RF5501 PGM2 Output Activation Time Default 00 PGM2 Output Activation Time Minutes Default 05 PGM2 Output Activation Time Seconds NOTE Sections 72 and 73 have a valid minimum programmable value of 00 minutes 01 seconds and a valid maximum programmable value of 99 minutes 99 seconds Supervision 81 Wireless supervisory Window Default 96 111 The window is programmed in 15 minute increments The default programming is 96 x 15minutes which is equal
28. ll prevent unnecessary reporting of the event if the user has been instructed on how to replace batteries 6 2 Jamming Signal Detection The RF5501 433 receiver detects jamming signals that can prevent the receiver from properly receiving transmissions from enrolled devices See section 4 4 Jamming Signal Detection for information on jamming signal detection programming 6 3 Replacing Batteries in Wireless Devices 1 Remove the cover of the device from its backplate This creates a tamper condition on the zone 2 Refer to the battery installation instructions on the Installation Sheetof each component Be sure to note the proper orientation of the batteries as you install them 3 When the fresh batteries are in place re attach the cover to the backplate The tamper is restored and the zone sends a battery trouble restoral signal to the receiver The battery trouble is now clear and the device should function normally NOTE When batteries in one device need to be replaced the batteries in all devices should be replaced at the same time Troubleshooting S E Cc T l fe N 7 1 When enter the 2 digit zone number when adding a wireless device the keypad gives me a long beep You cannot enter ESNs unless the RF5501 433 is properly connected to the Keybus See sections 1 amp 3 for instructions on setting up and wiring the RF5501 module 2 have entered the ESN for the device but when violate the device the zone does not sho
29. mance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty will be credited or replaced at DSC s option Products not covered by this warranty or otherwise out of warranty due to age misuse or damage shall be evaluated and a repair estimate shall be provided No repair work will be performed until a valid purchase order is received from the Customer and a Return Merchandise Authorisation number RMA is issued by DSC s Customer Service Digital Security Controls Ltd s liability for failure to repair the product under this warranty after a reasonable number of attempts will be limited to a replacement of the product as the exclusive remedy for breach of warranty Under no circumstances shall Digital Security Controls Ltd be liable for any special incidental or consequen tial damages based upon breach of warranty breach of contract negligence strict liability or any other legal theory Such damages include but are not limited to loss of profits loss of the product or any associated equipment cost of capital cost of substitute or replace ment equipment facilities or services down time purchaser s time the claims of third parties including customers and injury to property The laws of some jurisdictions limit or do not allow the disclaimer of consequential damages If the laws of such a jurisdiction apply to any claim by or against DSC the limi
30. more information on zone assignment consult your system Installation Manual 9 ENROLL amp PROGRAM DEVICES 5 The device is now enrolled on the system Record the serial number and the assigned zone number in the programming worksheets in the back of this manual 6 Continue with steps 3 5 until you have enrolled all wireless devices 7 To exit press NOTE The devices will not work properly until you complete zone and partition program ming see section 4 3 3 A Note about Electronic Serial Numbers Anelectronic serial number ESN is printed on the back of each wireless key ESNs are used to enroll the wireless keys with the RF5501 433 receiver In order to reduce the occurrence of wireless keys with the same serial number 6 digit serial numbers are now printed on the back of each wireless key The 6 digit serial numbers include hexadecimal digits For instructions on programming hexadecimal numbers see your system Installation Manual Section 4 Howto Program NOTE 6 digit serial numbers are only supported on the following control panels PC5020 P 8 PC501X v2 0 amp higher P832 DL v2 0 and higher PC 1555 MX P 6B MX PC580 585 and P 48 The P WLS909 433 and P WLS919 433 keys have both a 5 digitand a6 digit serial number printed on them When connecting the RF5501 433 toa PC5010v1 xorP 832v1 x panel enter 5 digit serialnumbers only When connecting the RF5501 433 toaPC5020 P 8 PC5015v2 x and higher P832DL v2
31. mulan apatite alak 13 45 Receiver Software Default waco cas sesscceseven cca sas a Bran maa adr a A 14 4 6 Keypad Software Default s s 00048110 00 deer ialerlan ese damar akan sel ass disi 14 Section 5 Testing amp Mounting 15 51 Testtiheplacementofwirelessdevices 15 52 TestWLS9O9SandWwWwl1Ss9i9Reception 16 Section 6 Additional Notes 17 6 1 Trouble Conditions serada as eves anan nama can el a ape ating Baldan my gelem aga 17 6 2 ReplacingBatteresinWirelessDevices 17 6 3 ReplacingBatteresinWirelessDevices 17 Section 7 Troubleshooting 18 Section 8 Programming Worksheets 19 Appendix A Guidelines for Locating Smoke Detectors 28 1 Introduction D U Cc T N Zone s Trouble display open 1 azminin options seu OPE N 12345678 Memory Aiarm s in memory D 2 OO say Clock and AM Bypass Zone s bypassed zone Fire alarm s in memor 4 5 6 ome 2 display Ai ram Keypad Hee j A 4 O aime pa PM rogi Installer s programming 15 DO O Ores TE ok A LAR M Stay Away Chime Door chime is on p lt L I 0 di 4 IL 5 Zone s Sim EE ANS NA in alarm armed armed I inStay in Away 1 n mode mode EH Flashing Trouble AC Failure Introduction The RF5501 433 keypad combines a standard PC5132 receiver with an
32. n buttons Default functions have been assigned but you may program other functions if desired After the functions are programmed when you press and hold one of the four buttons for one second the system will execute the programmed function For systems using partitions PC5020 P 8 PC501X P832 P832DL only All wireless keys assigned to Partition 1 will have the four functions programmed in section 61 Allwireless keys assigned to Partition 2 8 will have the four functions programmed in section 62 68 For example iffunction button 1 in Section 61 is programmed for Stay arming then pressing the first button on wireless keys assigned to Partition 1 will Stay arm Partition 1 NOTE Wireless keys will not work when the partition they are assigned to is being accessed for zone bypassing or programming 1 Ata system keypad enter 8 Installer s Code 2 Enter programming section 804 3 Enter programming section 61 to 68 for partitions 1 to 8 4 For each of the 4 function buttons enter the 2 digit number of the function you want to select See the programming worksheets in the back of this manual for a list of function key options 5 Record your programming choices in the worksheets in the back of the manual 6 To exit press 3 5 RF5501 433 PGM Outputs The RF5501 433 has two on board open collector PGM outputs Each of these can be individually programmed to 1 Follow main panel PGM outputs 1 to 14 NOTE Pl
33. nd or police department is highly recommended if this service is available E Criminal Knowledge This system contains security features which were known to be ef fective at the time of manufacture It is possible for persons with criminal intent to develop technigues which reduce the effectiveness of these features It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it does not provide the protec tion expected E Access by Intruders Intruders may enter through an unprotected access point circum vent a sensing device evade detection by moving through an area of insufficient coverage disconnect a warning device or interfere With or prevent the proper operation of the system M Power Failure Control units intrusion detectors smoke detectors and many other security devices reguire an adeguate power supply for proper opera tion If a device operates from batteries it is possible for the batter ies to fail Even if the batteries have not failed they must be charged in good condition and installed correctly If a device operates only by AC power any interruption however brief will render that de vice inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a security system After a power interruption has occurred immed
34. nsor Reset Panic Alarm For Future Use RF5501 PGM1 Pulse k 0 Quick Exit RF5501 PGM2 Pulse Sensor Reset can be used when the RF5501 433 is connected to the PC5010 Command outputs are not available for PC5010 software v1 x 23 PROGRAMMING WORKSHEETS Wireless Key Options Partition 1 Wireless Key Options 61 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 2 Wireless Key Options 62 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 3 Wireless Key Options 63 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 4 Wireless Key Options 64 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 5 Wireless Key Options 65 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 6 Wireless Key Options 66 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 7 Wireless Key Options 67 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 Partition 8 Wireless Key Options 68 Function Key 1 03 Function Key 3 27 Function Key 2 04 Function Key 4 30 69 Wireless Keys 1 16 Partition Assignments Default 01 Wireless Key 01 LL Wire
35. of tampering whether in tentional or unintentional such as masking painting or spraying of any material on the lenses mirrors windows or any other part of the detection system will impair its proper operation Passive infrared motion detectors operate by sensing changes in temperature However their effectiveness can be reduced when the ambient temperature rises near or above body temperature or if there are intentional or unintentional sources of heat in or near the detec tion area Some of these heat sources could be heaters radiators stoves barbeques fireplaces sunlight steam vents lighting and so on E Warning Devices Warning devices such as sirens bells horns or strobes may not warn people or waken someone sleeping if there is an intervening wall or door If warning devices are located on a different level of the residence or premise then it is less likely that the occupants will be alerted or awakened Audible warning devices may be inter fered with by other noise sources such as stereos radios televi sions air conditioners or other appliances or passing traffic Au dible warning devices however loud may not be heard by a hear ing impaired person E Telephone Lines If telephone lines are used to transmit alarms they may be out of service or busy for certain periods of time Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect E Insuffi
36. ransformer and battery is disconnected from the control panel Connect the four Keybus wires from the control panel red black yellow green to the keypad terminals R B Y G Consult the diagram below RFS501 433 NOTE P and Pp are open collector programmable outputs Refer to the control panel manual for proper hook up diagram Po is also the zone input terminal when programmed see section 90 DEOL is supported by this keypad Lo Red Bik Yel Grn Pi P2Z You can connect a device such as a door contact to the Z terminal of the RF5501 433 This eliminates the need to run wires back to the control panel for the device To connect the zone run one wire from the device to the Z terminal and the other wire from the device to the B black terminal For powered devices run the red wire to the R positive terminal and the black wire to the B negative terminal When using end of line supervision connect the zone according to one of the configurations outlined in your system s Installation Manual 3 4 Each PGM output is an open collector switch to ground That is MERSOL SA when the PGM output is activated by the RF5501 433 the terminal will switch to ground P1 can sink up to 50 mA of current to activate LEDs or a small buzzer Connect the positive side of the LED or 2 ve rr buzzer to AUX the negative side to P1 If more than 50 mA of c
37. re finished press to exit Door Chime Sounds You can program the RF5501 433 keypad to make different door chime sounds for individual zones or groups of zones Each RF5501 433 keypad can make any of four door chime sounds for each zone that triggers the door chime e 4 quick beeps default sound e Bing Bing tone e Ding Dong tone e Alarm tone NOTE For a zone to be able to trigger the door chime sound the Door Chime zone attribute must also be enabled in the control panel programming Please see your control panel Installation Manual To change the door chime sounds 1 Enter 8 Installer Code 2 Enter to go to door chime sound programming 3 Enter a 2 digit number for the zone you want to program 01 82 4 Turn one of the following options on by pressing 1 2 3 or 4 1 4 quick beeps default sound 21 Bing Bing tone 3 Ding Dong tone 4 Alarm tone NOTE Ensure that only one of the above options is turned on If more than one is on the keypad will sound the first option that is enabled If none of the options are selected the keypad will not make any sound when the zone is opened or closed 5 To program the door chime sound for another zone repeat steps 3 and 4 6 When you are finished programming the door chime sounds press to exit 2 7 Low Temperature Alert The RF5501 433 keypad is capable of detecting a low temperature environment Once enabled and t
38. rogramming required varies de pending on which control panel the RF5501 433 is connected to you should check that the following programming areas are completed correctly for each wireless zone e Enable zones and or assign zones to one or more partitions programming sections 2011 1209 2011 1265 for PC5020 e Program the definition for each zone programming sections 0011 0041 NOTE WLS906 wireless smoke detectors must be assigned to zones defined as Delay 24 hr fire wireless 87 or Standard 24 hr fire wireless 88 for proper supervision e Enable the wireless zone attribute for each wireless zone PC580 585 PC 1555 1565 PC5008 PC5010 v2 0 and higher PC5020 PC5015 v2 2 and higher only programming sections 101 132 See your system Installation Manual for more information on each of the above programming sections 4 2 Enable PC5132 Supervision The control panel will supervise the PC5132 receiver portion of the RF5501 433 via the Keybus after at least one device has been enrolled on the module see section 3 2 Enrolling Wireless Devices To activate module supervision after you enroll the first device s 1 Exit and then re enter Installer Programming 2 Enter programming section 902 Wait approximately 1 minute 3 To exit press The system will generate a General System Supervisory trouble if the module is removed from the Keybus If you need to remove the PC 5132 portion of the RF5501 433 modu
39. s Ltd must first obtain an authorization number Digital Security Controls Ltd will not accept any shipment whatsoever for which prior authorization has not been obtained Conditions to Void Warranty This warranty applies only to defects in parts and workman ship relating to normal use It does not cover damage incurred in shipping or handling damage caused by disaster such as fire flood wind earth quake or lightning damage due to causes beyond the control of Digital Se curity Controls Ltd such as excessive voltage mechani cal shock or water damage damage caused by unauthorized attachment alterations modifications or foreign objects damage caused by peripherals unless such peripherals were supplied by Digital Security Controls Ltd defects caused by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any other abuse mishandling or im proper application of the products Items Not Covered by Warranty In addition to the items which void the Warranty the following items shall not be covered by Warranty i freight cost to the repair centre ii products which are not identified with DSC s product label and lot number or serial number iii products disassembled or repaired in such a manner as to adversely affect perfor
40. t its option repair or replace any defective product upon return of the product to its factory at no charge for labour and materials Any replacement and or repaired parts are warranted for the remainder of the original warranty or ninety 90 days whichever is longer The original purchaser must promptly notify Digital Security Controls Ltd in writing that there is defect in material or workmanship such written notice to be received in all events prior to expiration of the warranty period There is absolutely no warranty on software and all software products are sold as a user license under the terms of the software license agreement included with the product The Customer assumes all responsibility for the proper selection installation operation and maintenance of any products purchased from DSC Custom products are only warranted to the extent that they do not function upon delivery In such cases DSC can replace or credit at its option International Warranty The warranty for international customers is the same as for any customer within Canada and the United States with the exception that Digital Security Controls Ltd shall not be responsible for any customs fees taxes or VAT that may be due Warranty Procedure To obtain service under this warranty please return the item s in question to the point of purchase All authorized distributors and dealers have a warranty program Anyone returning goods to Digital Security Control
41. tations and disclaimers contained here shall be to the greatest extent permitted by law Some states do not allow the exclusion or limitation of incidental or consequential damages so that the above may not apply to you Disclaimer of Warranties This warranty contains the entire warranty and shall be in lieu of any and all other warranties whether expressed or implied including all implied warranties of merchantabil ity or fitness for a particular purpose and of all other obli gations or liabilities on the part of Digital Security Con trols Ltd Digital Security Controls Ltd neither assumes responsibility for nor authorizes any other person purport ing to act on its behalf to modify or to change this war ranty nor to assume for it any other warranty or liability concerning this product This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario Canada WARNING Digital Security Controls Ltd recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to but not limited to criminal tampering or electrical dis ruption it is possible for this product to fail to perform as expected Out of Warranty Repairs Digital Security Controls Ltd will at its option repair or re place out of warranty products which are returned to its fac tory according to the following conditions Anyone returning goods to Digital Security Controls Lt
42. tector be installed outside each sleeping area and on each addi ectable quantities of smoke Standard 72 requires that a ional story of the family unit On smooth ceilings detectors may be spaced 9 1m 30 feet apart as a guide Other spacing may be required depending on ceiling height air movement the presence of jois Consult National Fire Alarm Code NFPA 72 CAN ULS S553 M86 or standards for installation recommendations Do not locate smoke detectors at the top of peaked or gabled ceilings locations may prevent the unit from detecting smoke Avoid areas with turbulent air flow such as near doors fans or windows the detector may prevent smoke from entering the unit Do not locate detectors in areas of high humidity Do not locate detec 41 F Bedroom Bedroom Bedroom won Living Room e e Bedroom Hall Bedroom Me ition Ri 07 Recreation Room Basement O Smoke detectors for better protection SPLIT LEVEL ARRANGEMENT Smoke detectors for minimum protection s uninsulated ceilings etc other appropriate national he dead air space in these Rapid air movement around ors in areas where the temperature rises above 38 C 100 F or falls below 5 C Family Room o Bedroom o Dining Room Kitchen Living Room o T Bedroom Bedroom O O O O Bedroom Bedroom o Living Dining Room Pal Room Basement
43. ting NOTE The Identified Wireless Key Closing option is only available with the PC5020 P 8 PC501X v2 0 and higher P832 DL v2 0 and higher PC1555 MX P 6B MX PC580 585 v2 0 and higher P 48 v2 0 and higher by turning section 015 option 4 off To enable the reporting of openings and closings by identified wireless keys e Make sure the control panel is v2 0 or higher e Program a valid access code for each key e Program a closing and opening reporting code for each key s access code e Turn off the Quick Arm option in section 015 option 4 of the control panel programming To ensure that an unidentified wireless key cannot disarm the system turn off section 017 option 1 in the control panel programming This option is available in control panels with software version 2 1 or higher 3 2 Enroll Wireless Devices Using Zones Enroll wireless devices which use zones universal transmitters motion detectors smoke detectors and panic pendants 1 Ata system keypad enter 8 nstaller s code to go the installer s programming section 2 Enter programming section 804 3 Enter the 2 digit number corresponding to the zone the device is to occupy 01 to 32 NOTE Hardwired and wireless devices cannot be assigned to the same zone PC5108 zone expander modules occupy zones in 2 groups of 4 e g zones 9 12 and zones 13 16 None of the zones assigned to a PC5108 module may be used for wireless devices For
44. to 24 hours Valid entries are 16 96 equal to 4 24 hours 25 PROGRAMMING WORKSHEETS 82 Zone Device Supervision Options 1 8 Default ON Option ON Option OFF Option 1 Zone 01 Supervision enabled Disabled Option 2 Zone 02 Supervision enabled Disabled Option 3 Zone 03 Supervision enabled Disabled Option 4 Zone 04 Supervision enabled Disabled e i Option 5 Zone 05 Supervision enabled Disabled Option 6 Zone 06 Supervision enabled Disabled Option 7 Zone 07 Supervision enabled Disabled Ei Option 8 Zone 08 Supervision enabled Disabled 83 Zone Device Supervision Options 9 16 Default ON Option ON Option OFF Option 1 Zone 09 Supervision enabled Disabled Option 2 Zone 10 Supervision enabled Disabled Option 3 Zone 11 Supervision enabled Disabled Option 4 Zone 12 Supervision enabled Disabled Option 5 Zone 13 Supervision enabled Disabled Option 6 Zone 14 Supervision enabled Disabled Option 7 Zone 15 Supervision enabled Disabled Option 8 Zone 16 Supervision enabled Disabled 84 Zone Device Supervision Options 17 24 Default ON Option ON Option OFF Option 1 Zone 17 Supervision enabled Disabled Option 2 Zone 18 Supervision enabled Disabled Option 3 Zone 19 Supervision enabled Disabled L__ Option 4 Zone 20 Supervision enabled Disabled Option 5 Zone 21 Supervision enabled Disabled Option 6 Zone 22 Supervision
45. to prodotto conforme ai requisiti essenziali ed altre disposizioni rilevanti relative alla Direttiva 1999 05 CE Por la presente DSC declara que este equipo cumple con los requisitos requeridos por la Directiva 1999 5 EC Hierdurch erkl rt DSC da dieses Ger t den erforderlichen Bedingungen und Vorrausetzungen der Richtlinie 1999 5 EC entspricht A a tov nap vtos n DSC dnAdver tt avti n ovoKev eivat G HYOVN HE TI OVOLMINS amartijaeic ko pe Ohec tis 4Ahes oyetiK c avapop s mg O nyia 1999 5 EC Hierbij verklaart DSC dat dit toestel in overeenstemming is met de eisen en bepalingen vanrichtlijn 1999 5 EC Par la pr sente DSC d clare que cet article est conforme aux xigences essentielles etautres relevantes stipulations de la directive 1999 5 EC DSC vakuuttaa laitteen t ytt v n direktiivin 1999 5 EC olennaiset vaatimukset Hereby DSC declares that this device is in compliance with the essential requirements and other relevant provisions of Directive 1999 5 EC The complete R amp TTE Declaration of Conformity can be found at www dsc convintl ritedirect htm 2002 Digital Security Controls Ltd Toronto Canada gt www dsc com Technical Support 1 800 387 3630 Printed in Canada 29034573 R001 Direct all comments con cerning this publication to pubs dscltd com
46. to the Instruction sheets of the following devices for more information The RF5501 433 v5 0 can receive signals from the following devices e WLS904L 433 Motion Detector e WLS912L 433 Glass Break Detector e WLS904PL 433 Pet Immune PIR e WLS914 433 Pet Immune PIR e WLS906 433 Smoke Detector e WLS909 433 Wireless Key e WLS907 433 Universal Transmitter e WLS919 433 Wireless Key e WLS907T 433 Low Temperature Sensor WLS925L 433 Mini Door Window Contact 1 8 Batteries The wireless devices are designed to use only specific brands and types of batteries Please see the appropriate instruction sheet for detailed information on the battery brands and types NOTE Do not use brands of batteries other than those specified Using any other brand may affect system operation Keypad Programming S E Cc T l N 2 2 1 Programming the Keypad There are several programming options available for the RF5501 433 keypad These are described below Record all your programming choices in the programming worksheets included in this manual Programming the RF5501 433 is similar to programming the rest of the system When you are in the RF5501 433 programming sections the keypad will display which options are turned on along the top of the display To turn an option on or off press the number corresponding to the option on the number pad The numbers of the options that are currently turned ON will be displayed For example if options 1 and 2 are on
47. urrent is required a relay must be used Please refer to diagram as 1 4 Applying Power Once all wiring is complete apply power to the control panel E 5 COM NC NO 1 Connect the battery leads to the battery 2 Connect the AC transformer For more information on control panel power specifications see the control panel Installation Manual NOTE Do not connect the power until all wiring is complete and unit is securely mounted 1 5 Enrolling the Keypad Once all wiring is complete you will need to enter a 2 digit number that tells the system the partition and slot assignment of the keypad If your system has partitions you will also need to assign the keypad to a partition 1st digit The slot assignment 2nd digit tells the panel which keypad slots are occupied The panel can then generate a fault when a keypad supervisory signal is not present There are eight available slots for keypads RF5501 433 keypads are always assigned to slot 1 by default You will need to assign each keypad to its own slot 1 to 8 NOTE The RF5501 433 enrolls as two modules 1 keypad section of the RF5501 433 17 receiver section of the RF5501 433 Enter the following at each keypad installed on the system 1 Enter Installer Programming by pressing 8 Installer s Code 2 Press 000 for Keypad Programming 3 Press 0 for Partition and Slot Assignment 4 Enter a two digit number to specify the partition and slot assignment NOTE If your
48. vice Zone Serial Numbers Default 000000 01 Zone 1 02 Zone 2 03 Zone 3 04 Zone 4 05 Zone 5 06 Zone 6 07 Zone 7 08 Zone 8 09 Zone 9 10 Zone 10 11 Zone 11 12 Zone 12 13 Zone 13 14 Zone 14 15 Zone 15 16 Zone 16 22 17 Zone 17 18 Zone 18 19 Zone 19 20 Zone 20 21 Zone 21 22 Zone 22 23 Zone 23 24 Zone 24 25 Zone 25 26 Zone 26 27 Zone 27 28 Zone 28 29 Zone 29 30 Zone 30 31 Zone 31 32 Zone 32 PROGRAMMING WORKSHEETS Wireless Key Serial Numbers Default 000000 41 Key 01 49 Key 09 42 Key 02 50 Key 10 43 Key 03 51 Key 11 44 Key 04 52 Key 12 45 Key 05 53 Key 13 46 Key 05 54 Key 14 47 Key 07 55 Key 15 48 Key 08 56 Key 16 Wireless Key Function Key Options Key Description Key Description Null Key 1 Reactivate Stay Aways For Future Use For Future Use Stay Arm 7 3 Command Output 3 Away Arm For Future Use 9 No Entry Arm 7 4 Command Output 4 Chime ON OFF For Future Use 1141 System Test Disarm OFF Five Use Fire Alarm 1 Command Output 1 Auxiliary Alarm 7 2 Command Output 2 Se
49. vices If a wireless device stops sending a supervisory signal the unit stops functioning the panel will not indicate a supervisory trouble condition unless Double EOL resistors are used In addition all hardwire zones must be wired for Double EOL resistors For more information refer to your PC5010 v1 x Installation Manual NOTE PC5010 v2 0 and higher PC5015 v2 2 and higher PC5020 PC5008 PC 1555 1565 PC580 585 only For wireless supervision to work you must enable the wireless zone attribute on all wireless zones sections 101 to 132 option 8 ON NOTE The RF Jam Detect zone must have the supervision option disabled Wireless Supervisory Window Each wireless zone will send a supervisory signal every 64 minutes If the receiver does not receive a signal within the time programmed for the Wireless Supervisory Window it will generate a supervisory fault To program the wireless supervisory window 1 Enter 8 Installer Code to enter Installer Programming 2 Enter 804 to enter into Receiver Programming 3 Enter sections 81 4 Enter the time period for the supervisory window The window is programmed in 15 minute increments The default programming is 96 x15minutes which is equal to 24 hours Valid entries are 16 96 equal to 4 24 hours 5 To exit press Disable Enable Zone Supervision All wireless zones have supervision enabled by default To disable supervision for any zone enter
50. w open on the keypad Check the following e Ensure the ESN has been entered correctly e Ensure that the zone is enabled for the partition if partition programming is used e Ensure that the wireless zone is not assigned to a zone used by PC5108 modules an on board zone or a keypad zone Ensure that the zone is programmed for something other than Null Operation and that the wireless zone attribute is turned on 3 When I try a module placement test get no result or Bad results Check the following see sections 5 1 and 5 2 for more information on testing devices e Verify that you are testing the correct zone e Verify that the correct ESN was entered when the device was enrolled e Verify that the device is in range of the RF5501 433 Try testing the device in the same room as the receiver e Confirm that the RF5501 433 is properly connected to the Keybus e Check that you are testing the zone correctly e Check that the batteries are working and installed correctly e Look for large metal objects that may be preventing the signal from reaching the RF 501 433 The device must be located where consistent Good results are obtained If several devices show Bad results or if panic pendants and wireless keys operate inconsist ently move the receiver 4 The LED on the motion detector does not turn on when walk in front of the unit The LED is for walk test purposes only See your WLS904 433 WLS904P L 43
51. x and higher PC5010 v2 0 and higher P832 v2 0 and higher PC1555 MX P 6B MX PC580 585 or P 48 panel enter the 6 digit serial number 3 4 Enroll amp Program Wireless Keys For wireless keys to work on the system you need to enroll them and then program the function buttons if the default values are not the functions desired Wireless keys are not assigned to zones and require no zone programming You can enroll up to 16 wireless keys on the system Enroll Wireless keys 1 At a system keypad enter 8 Installer s Code to go to the installer s programming section 2 Enter programming section 804 3 Enter a 2 digit number 41 56 to program the wireless key serial number These numbers correspond to wireless key numbers 01 16 4 Enter the key s ESN The entry must be six digits 5 The key is now enrolled on the system Record the serial number and the assigned slot number in the programming worksheets in the back of this manual 6 Repeat steps 3 5 until all wireless keys have been enrolled 7 PC5020 P 8 PC501X P832 P832DL only By default all wireless keys are assigned to Partition 1 To assign keys to different partition see programming section 69 NOTE A wireless key can only be assigned to one partition 8 To exit press ENROLL amp PROGRAM DEVICES Program the P WLS909 433 or P WLS919 433 Function Buttons P WLS909 433 and P WLS919 433 wireless keys have four programmable functio

Download Pdf Manuals

image

Related Search

Related Contents

Asrock E3C224-4L  DOSSIER DE PRESSE - Agglomération Côte Basque  Franke Pilatus  INSECTICIDE 101    ロープ用  NOBLEX  7. Управление  A. Preparation before using the winch B. Reminders of the winch  Dell GX1 User's Manual  

Copyright © All rights reserved.
Failed to retrieve file