1.      E1  1 flash The master has lost communication to the room sensor  The fault is corrected by re establishing the connection to the Room  Sensor and the fault condition will be automatically reset once correct communication is resumed  If the room sensor is  defective and has to be changed  or if it has been deliberately removed  it is necessary to make a HARD RESET   NOTE  If the  room sensor is of the WIRELESS type  the error fault message could be an indication that the power has failed  and that the  internal battery of the room sensor needs to be replaced     E2  2 flashes The internal sensor in the room sensor controller is defective  The fault can only be corrected by replacing the room sensor   Controller  Remember to make a HARD RESET after installing the new room sensor controller    E3  3 flashes The limit sensor on the room sensor controller is defective  Replace the faulty sensor  Reset is NOT required    E4  4 flashes Defective WLCT room controller  If a room controller operating a group of room sensors becomes defective  the remaining  room sensors will continue control within the maximum and minimum limits programmed into the Room controller    E5  5 flashes Two or more room controllers are trying to control this output  Check    AREA    setting on the room controllers    RESET    There are 2 different reset actions that can be used     RESET   If the     button is pressed for 5 seconds  a HARD RESET will be initiated   Indicated by all the red output LED  
2.      If a limit sensor is connected to the Room sensors   The lowest value of any Limit sensor is taken as the MIN Limit Temperature    The highest value of any Limit sensor is taken as the Max Limit Temperature     Channel 15  position F on the switch  Party and vacation function   Special function see FUNCTIONALITY     Supply water temperature sensor and mixing valve    Fig 11 Supply water temperature limit sensor  This feature is not available on the basic master   s version WLM2 1BA and WLM2 3BA  The limit sensor is directly connected to the master at the terminals marked limit sensor  Sensor    type ETF 1899A must be used   The temperature sensor should be placed on the supply water pipe to the underfloor heating        e system  If a limit sensor is installed  without a weather compensation module  WLOC  the master  f will control the maximum water temperature  The factory default setting is 55  C  but this value can     be changed via the displav   fra If a weather compensation module  WLOC  is added to the svstem  the master will varv the supplv  water temperature setting based on the outdoor temperature  A standard compensation curve  has been programmed at the factorv  If needed the curve can be changed  see separate USER  MANUAL  MASTER TVPE WLM2   Mixing valve actuator control  Control of a mixing valve actuator is possible using the digital masters WLM2 1FS and WLM2 3FS  The actuator must be 24Vac powered  max 6VA  and positioned via the 0 10V DC signal  and  sho
3.      It is possible to control a of a secondary heat source in a room  e g  a backup radiator   use the  spesial mode in the WLCT 2 Room controller  In addition to the primary underfloor heating output   this WLCT 2 room controller is able to control a second output as a boost function  witch will be  activated only if the temperature cannot be schieved by the underfloor heating within a preset time  period     e The WLCT 2 must be fixed in a convenient position for the user  but which is representative of the  room or area temperature   Connect the Room controller to the WLM master using the sensor controller bus   Set the channel number on Room controller to correspond with the output on the WLM master that  is connected to the underfloor heating actuator    e The next numerical output on the WLM master MUST be used for the secondary boost function     Note  To avoid overloading the WLM master  we recommend that the secondary output is used as a  signalling function for a remote relay   Please refer to the technical information     p  24    p  25    Commissioning mode     Supply temp        RESERVED  DEHUM    BR965A30b    X RELAY    COMMISSION MODE  LEARN MODE  BOILER TEST  INSTALL MODE    co   N      LO     ioe   N       LL  LL  O       Replacing equipment     Digital masters include a special    commissioning mode     which allows the temperature of the supply  water to be controlled to assist the drying out of a newly laid concrete floor     To start this function     Se
4.     The function of the relay is determined by the  setting of the DIP switches    The functions that the relay can perform  and the  appropriate DIP switch settings  are as follows     High limit zone valve     Cooling device module      Cooling device module  alternative       p  17    The X relay output is volt free as shown in fig 8a  If the relay is required to be used as aL  amp N switch   connect a link wire from mains L to C1  connect the device L to C2  and the device N to mains N     Boiler pump   Where a boiler primary pump is required to be switched on from the master  the relay output can be used  for this purpose  The relay will be activated 10 seconds after the UFH circulating pump has started     High Limit Zone Valve    This function is used where an additional protection is required to prevent boiler water entering the  underfloor system  when the system is off or when the supply water exceeds 65 C    An additional sensor  ETF 1899A  and a zone valve is connected as per attached pic     Cooling device module    The relay output can be used to provide a volt free signal to a heatpump  or to a K MOD switching  module where a chiller is utilized to provide the cooling water  The relay is on when there is a cooling  demand     Cooling device module alternative   The relay output is always on in cooling mode and off in heating mode        Thermal Actuators  Thermoheads     Fig 6    THERMAL ACTUATORS  L N L N L N L N L N L N L N L N    Q2 2 2 2 2 2 2 2 2 2 2 2 2 2
5.    57641 01 08  LJE        WLM2 WLTA WLTD       OJ ELECTRONICS    www oj dk taking comfort further       CONTENT    INSTALLATION MANUAL       p  2                 8 life  QU Sosa A AT A a    Quick Installation GUI Gives ncoenccecaadan  npeccehssnnbsiedetnseshnseensenanenaerace MEDRE Dep te PADLA PLE Ar AADI NONE EOE BOPITA T U sabie Page 3  Setting up the System  i en kB Ennen Page 5  Wireless  Systemi ONIY vaceonenn ct smut necena shee nes E A A E E E EE RE Page 5  Testing the Ea d pp a a E a a E a a a E a a A Page 6    Troubleshoot gesessen rie a E A d EEA ii    INSTRUCTIONS    WLM Underfloor Heating Controller       Page 10 Add On Module       sssssnnnnnnnnnnnnnnnnnnnn Page 31  Wiring didgraM sasagaran a Page 10 Configuring the Total System             000eeeeeee Page 31  DesCriptON ssri irka kin ki kd Page 13  Product programme        seeeennenzenznnzenzenzzz Page 13 Outdoor Compensation Module            Page 32  Technical data  s  riniizotonjeiakiibietjenzaiitttaazoi Page 13 Introduction iisireiisienziettibiekabii ba bkbbbi buri Page 32  EMViNOniMenll ic lt cepccckecinncepnctenseersacesueraereates Page 14 Mounting       Page 32  Recycling of obsolete appliances                   Page 14 Bus connection   Outdoor  Configuring of the total system                 6855 Page 14 compensation module                ccceeeeeeeeeees Page 32   Interconnection of WLM2 product                  Page 32   Installation  ms8s8s8ss ann Page 15  Electrical installation           eeaeee Pag
6.    E1  1 flash    E2  2 flashes    E3  3 flashes    E4  4 flashes    E5  5 flashes    E6  6 flashes    E7  7 flashes    E8  8 flashes    E9  9 flashes  E10  10 flashes  E11  11 flashes    One or more room sensors  room controllers  WLH  WLAC that are set to channel 0 or channel 15 are no longer sending data  to the master control  The fault is corrected by replacing the room sensor  The master will need to be HARD RESET  see below    NOTE  If the room sensor is of the WIRELESS type  the error fault message could be an indication that the power has failed   and that the internal battery of the room sensor needs to be replaced     One or more room sensors have been set to a channel number which does not exist in the system  For example  the message  will occur if the units are set to channels 9 14 and the required add on  AO  module are not found in the system  The error is  corrected by setting the channel number of the room sensor to a channel that does exist within the installed master add on  module system     Application sensor defect  The fault is corrected by changing the temperature sensor  If the sensor has been removed deliberately to  change the operation of the system  follow the HARD RESET instruction below     The outdoor compensation module  WLOC  is defective  The fault is corrected by changing the outdoor compensation module   If the module has been removed deliberately to change the operation of the system  follow the HARD RESET instruction below     The exter
7.   E     L  N  PE  Main supply  230V AC from    10 Amp fused  isolator       Boiler Demand       The master has a volt free relay output that can be used to control a boiler  or to open a    Fig  4  motorised valve     BR965A14a    A  To control a boiler that requires switching of the live supply  take a link from L  230V  to the  terminals marked BOILER   B1  Connect the boiler L to the terminal marked BOILER     B2   Connect the boiler N terminal to the N terminal on the master  and the boiler E to the master  terminal E   see fig  7A      B  To control a boiler that has a pair of dedicated terminals for remote switching  e g  by a Room  sensor   connect these terminals to B1 and B2 on the master  B1 and B2 terminals are    volt free     i so they can be used for both a 240V and a 24V circuit from the boiler     Main supply  230V AC from Boiler  10 Amp fused    isolator       as lee    BR965A33a        Main su pply  230V AC from  10 Amp fused  isolator    Motorised    Pump Output    ion panen    UFH   sr ef  ere     OUTPUT  BOILER   B1 B2 C1 C2   ojo       Volt free output  for boiler control  Secondary    Volt free pump  X output 230V         BR965A15b    C  To control a motorised valve     Many motorised valves have wires coloured BROWN and BLUE for power connections  In this  case BROWN goes to the terminal B2 under the heading BOILER and BLUE goes to the N  terminal of the master  Then a link from L  230V  to the terminals marked    Boiler B1     The boiler  relay will b
8.   p  37    Programming 4 Event Clock Time and Temperature    For each event  the start time and required temperature needs l l  to be set  Press OK   V   button for 3 secs  to begin programming    For example  in the morning you wish the heating to start at  07 00 and the temperature to rise to 25  C  Press OK  v   button  for 3 seconds and the start time is displayed  Change this to    07 00 with the UP  A  or DOWN  17  button  Press OK  v   to i   S  Umie ane temperature  confirm    The temperature is now displayed  Change this to 25  C with the   UP  A  or DOWN  7  button  Press OK  v   button to confirm  N     Time and temperature    This action can now be repeated for the second  third and  fourth event     O     Time and temperature    These settings will be valid for days 1 5 showing on the display   To program the days 6 and 7  repeat the above  Days 6 and 7  are usually Saturday and Sunday  and only have two events   generally morning ON and evening OFF   q i       Time and temperature    The temperature can be set within the range of  5 to  35  C   It is also possible to select the heating OFF at that event by  reducing the setting to 5 C  and then pressing the  Y  once    more  l ix   Time and temperature    Note that when programming the   Sleep  time  event 4    please ensure that this time is before midnight  00 00         Time and temperature       p  38       Advanced Settings and Read out    Press both UP  A  and DOWN  V  buttons together for 3 seconds  INFO 
9.   see later   A WLM  master has 8 outputs and additional slave module 6 outputs  and can be connected creating a  system of 14 individual zones     Please note that channels 10 to 14 are marked as A through E on the selector     A Room sensor set for CH1 will activate the thermal actuator connected to output 1 on the master   The channel number can be selected without any power connected to the system  The channel of  the Room sensor can be changed afterwards if needed    If two Room sensors are placed in the same room and set to the same channel  the temperature  control will work according to the average temperature of both Room sensors     Channel 0    Each Room sensor is delivered with the switch in position 0 ensuring that it must be set to operate  correctly  Channel 0 can also be used for a Room controller controlling a group of Room sensors  where the control position should be somewhere central  e g  the kitchen  rather than in the area  where the Room sensors are installed  Setting it to Ch 0 means that times and temperatures are  set on the WLCT for the group  but that the WLCT will not control a specific output itself     Channels 1  14    A Room sensor set for channel 1 will activate the thermal actuator connected to output 1 on  the master  If several Room sensors are set to the same channel number  they will control in the  following way      The actual room temperature is calculated as an average      The room temperature set point is calculated as an average 
10.  2   ojololejololololojololejololejo        Capa Oupa oupas Culpa   THERMAL ACTUATORS       BR965A16a    These actuators are fitted to the underfloor heating manifolds and control the supply of water through the  various loops  The voltage of the thermal actuators  230V or 24V  must correspond to the master    Master type WLM 1BA and WLM 1FS are for 230 V thermal actuators  and master type WLM 3BA   and WLM 3FS are for 24V Thermal actuators  Up to 8 different zones can be controlled by the master   Connect the thermal actuators on the loop s  for each zone to the corresponding terminals on the master   Thermal actuators belonging to zone 1 must be connected to output terminal 1  and thermal actuators for  zone 2 must be connected to output terminal 2  etc  etc     Guideline   More than 1 head can be connected to a single terminal  provided that the heads are to be controlled by  the same room Room sensors    Connect the Brown wire to the L terminal  and the Blue wire to the N terminal  When the installation is  complete  check that the Room sensor in e g  room zone  1  operates the correct thermo actuator s  for  that room on the manifold  If the heads appear to be in the wrong position on the manifold  it may be  simpler to change them on the manifold  rather than reconnecting them on the master     External Switch  TIMER  for night setback    Fig 7 From factory the master is delivered with a jumper in the switch  timer terminals    amp  O  The day  temperature setpoint is d
11.  DIP 1 to deactivate Install mode    Switch off DIP 2 to deactivate boiler test     Set all temperature knobs to default positions  Room sensors  WLTA  WLTD  WLTM  WLTP  to zero  center position    Room controllers  WLCT  recommended to 21c     Set all override switches on WLTM and WLID room sensors to automatic position   clock symbol      oe    The system is now operating automatically     Factorv Default Settings     House temperature    Night temperature  Off temperature  Floor Limit temp high    Floor Limit temp low    Weather compensation   Outdoor temperature a       Max water temperature  Weather compensation   Outdoor temperature ee S    p  27    p  28    Error Indication       During normal operation the green power LED will be ON when the master control is energised  The red output Channel LED   s   1 to 8 on the master  and 9 to 14 on the add on module  will indicate if the channel output relay is ON OFF     An error   fault message is shown by flashing the green power LED or one of the 8 red output Channel LED   s  From the number of flashes  on any one LED  the problem can be diagnosed  and identified from the following     The error number will be indicated by the number of flashes  with a pause of less than a 1 2 second between the flashes  The indication will be followed  by a pause of 2 seconds  following which the sequence will be repeated  The failure code can also be seen in the service menu on WLM FS MASTERS     submenu 2      Flashing Power LED  green  
12.  a Turn onthe power supply     2  Set the clock on any WLCT room controller   a  If the hour digit is not flashing  press the small pinhole button with the clock symbol  otherwise    b  Adjust the hours and press OK   c  Adjust the minutes and press OK   d  Adjust the day number  1   Monday  and press OK     3  In addition to its own room  the WLCT room controller can be used to set the operating times and temperatures of other Room sensors   channels    To achieve this  do the following on the WLCT room controller   a  Enter the    InFo    menu by pressing the up and down button simultaneously for 4 seconds   b  Find the    ArEA    menu with the down button and press OK   c  The display shows    CH 1     channel 1      Press OK button     Select    On    if this channel  Room sensor  should be controlled by the WLCT room controller  or    OFF    if not     Now press OK button to get to the next channel  CH 2  and repeat this step until all required channels have been selected    On      d  After all channels are set up  find the    ESC    menu entry and press OK              1     Switch on DIP 3 to activate learn mode                       RESERVED    DEHUM 2  All wireless Room sensors now have to be initialized     EL   Analogue Room sensor  TA TD TM TP  by pressing the internal  COMMISSION MODE BE init button  Button learning mode  until a beep is heard   LEARN MODE Sa   Digital Room sensor  CT  by pressing the pin hole button with the    OIE EST clock symbol until a beep
13.  frost protection level of 5  C    NIGHT SETBACK  see also EXTERNAL SWITCH    The external switch or timer function on the master module allows the whole system to be changed from the DAY Setpoint to the NIGHT Setpoint   The external switch must have volt free contacts that are OPEN for NIGHT Setpoint  and CLOSED for DAY Setpoint  The factory fitted link wire is  removed when a remote switch timer is used     If aWLCT Room controller is employed in a part of the system  the external switch action of going to NIGHT Setpoint will override the Room  controller     Emergency program for room control     If a Room sensor controller is defective or if the communication to the unit is interrupted  an alarm will be triggered  Depending on the system  configuration the regulation will continue in one of the following ways      If there are several units on the same channel which have a room sensor  which is still intact   the regulation will continue as before  however  without contribution from the defective unit     If no valid room sensor controller is found  the system will run at constantly 20  ON     If an outdoor sensor is connected  the system will run 40  at 10  C  and Below  decreasing to 0  at 20  C  and above      The emergency program is only valid for channels with heat control  Channels with cooling control will always run at 100  OFF in connection with  a defective room sensor     Emergency program for supply limit sensor    lf the supply limit sensor is deffective  th
14.  is heard   INSTALL MODE       BR965A30b                  N      LO  T   ip   N       ic  O    3  Switch off DIP 3 to de activate learn mode        Button learning mode    TESTING THE SYSTEM     Oo ARO NA    Switch on DIP 3 to activate learn mode    power light will blink quickly    Each red channel light on the master should now be lit if a Room sensor is present on that  Channel     Switch off DIP 3 to de activate learn mode again     power light stops blinking   Turn all adjustable temperature settings on the Room sensors to minimum     Switch on DIP 1 on the master to activate install mode  Install mode will be active for 2 hours    Pumps  boiler  mixing valve and actuators should now be off     Turn the temperature setting on the adjustable Room sensor in room 1 to maximum  The red  channel 1 light should be lit and the actuator on output nr  1 will be activated  and will open  after 1 3 minutes  depending on the type of actuator    Important  If the Room sensor is of a wireless type a delay of up to 5 minutes may occur  before the channel light becomes illuminated      Check that the UHF pump is running and the mixing valve  only FS master  opens    Repeat step 6 on all rooms     Boiler test function   Switch on DIP 2   This closes the boiler start relay contacts for 1 minute     1 0  To end all tests       Switch off DIP 1 to deactivate install mode   Switch off DIP 2 to deactivate boiler test     Set all temperature knobs to default positions  Room sensors  TA TD TM T
15.  s 1 8  lighting in sequence   This reset  will remove from the system any room sensor unit with a defective input sensor  or a defective AO module  The fault message will be reset but the  defective items will no longer participate in the system  Once a defective unit is replaced  the new unit will automatically be recognised by the master  control and become part of the system  To erase the identity of the defective component from the master memory a HARD RESET must be performed  Hard resets do not alter the temperature settings already programmed into the master control     FACTORY RESET   If the      button is pressed for more than 15 seconds  a total factory reset will be initiated  This is indicated through flashes of channel LEDs 1 3  5  and 7 alternating with channel LEDs 2  4  6 and 8  while the    y    button is pressed     A factory reset will put all programmed temperature settings back to the factory defaults  It will also remove all room sensors Controllers from the  master memory  and reset the system to accept only those room sensors Controllers that are functioning correctly     DEFAULT SETTINGS  amp  SPECIAL FUNCTIONS  The master control has the following default temperature settings   For the master with display  the setpoints can be altered on the display    DAY SETPOINT 21  C  NIGHT SETPOINT 18  C  OFF  FROST PROTECTION  SETPOINT oC  MAX LIMIT 27  C  MIN LIMIT 17  C  MAX SUPPLY WATER TEMP 55  C    p  30    Each Room sensor with manual adjustment is capabl
16.  to local regulations     Configuring the Total System    Each master module is capable of controlling 8 heating zones  each of which may use one or more         loops of piping  with one or more thermal actuators   S These zones are referred to later in this instruction as channels 1 to 8  If vou wish to control more  D than 8 zones  it is necessary to install ADD ON  AO  modules  each of which can provide another 6  x outputs  The first AO module then controls channels 9 to 14   CEC Green  Power supply connected  5 Red  Night setback active  Q Red flashing  Indicates error  LO      O X Main boiler  primary  pump is running  if installed   m    CS Secondary UFH pump is running     Boiler enable signal is activated    1  8 Zone 1 to 8 indicating heating is on       INSTRUCTIONS    Installation       Fit the WLM master to a suitable wall  It will generally be found more convenient if the unit is within 0 8 metre  of the manifold  as most thermal actuators are supplied with 1m cables  Cables can be run on the surface  into the terminals using either the cable releases in the cover or by pressing out the cable entries in the lower  part of the cover     Electrical Installation            Fig  3 PLEASE ENSURE THAT ALL WIRING IS CARRIED OUT IN ACCORDANCE WITH LOCAL  ELECTRICAL REGULATIONS     When wiring is completed  fit the cover on the master using the screws provided     BR965A13a    Mains supply  WLM requires a 230V AC mains supply connected to the terminals marked L  N   amp
17. 00 shaendabsexdtecnbieserdeneas Page 24 Waterline ROOM sensors     sssenennnnnnnn Page 42  2 step NGAUNG ixxi ua iii or Page 24  grigal fl ai e vies nn a e Page 42  Commissioning mode iii ka ti   ib Page 25 SUP cc i di Page 43  Replacing equipment    neennnnnnnn Page 25 Setting of Room Temperature               0   000  Page 44  Guidelines and special features                      Page 26 Setting of Room sensor Operating Mode          Page 44  Factory default settings                 ceceee eee eens Page 27 Limit Sensor   WLTD and WLCT                05  Page 45  Error indication  essar Page 28    QUICKGUIDES    p  3    QUICK INSTALLATION GUIDE               WLM2 Master AO Module          BR965A21a    WLM2 Master AO Module                AO Module Cable       Channel 1                                                    Manifol                      WLM2 Master    WLRC 19                                  We recommend the preparation of an area schedule chart on the backside of the user manual before  commencing the installation  This identifies piping circuits to specific rooms and enables the correct  allocation of a channel number in the WLM system     Mount the Master and AO modules in the correct way on the wall in accordance with electrical  regulations     Connect the AO module  using the special cable included in the box           Mount the Room sensors controllers in the rooms  and set the channel switches to correspond with  the number of the actuator controlling that 
18. BR965A18a    SENSORS CONTROLLERS CONNECTED IN STAR SENSORS CONTROLLERS CONNECTED IN BUS MODE     DAISY CHAIN   MASTER  MASTER    SENSOR CONTROLLER  BUS       SENSORS CONTROLLERS    CONNECT   TO  ANDLTO L Fig 1 O       BR935A03A    Fig 11    Room sensors   Wireless setup     BR939A17B       Button learning mode    Channel  selector    Fig 13       Button learning mode    Where wireless Room sesors controllers  WLTx 29  are being used is necessary for the WLM master to     learn    that the Room sensors controllers are communicating correctly     To achieve this   1  On master  switch on DIP 3 to activate learn mode   2  All wireless Room sensors controllers now have to be initialized   Room sensors  WLTA  WLTD  WLTM  WLITP  by pressing the internal init button   Button learning mode  until a beep is heard   see fig  12   Room controllers  WLCT  by pressing the pin hole button with the clock symbol until a beep is  heard   see fig  13     3  Switch off DIP 3 to de activate learn mode     p  20    Setting up Which Room sensor Should Work With Which Thermal Actuator    Fig 10    BR939A01C       Channel  selector    Each Room sensor can be selected to operate a specific output which in turn controls the thermal  actuators on the manifold  Under the front cover of the Room sensor  a selector can be accessed   and the number of its output  its CH channel  can be set with a screwdriver   See fig 10  Up to   14 channels can be set on the selector  and there are two auxiliary channels 
19. Be Bd ji  DR  No No  1 2 L N  LI Timer   w volt free contacts   Open contacts  for night setback        Thermoheads    RESERVED  DEHUM    BR965A30b    X RELAY    COMMISSION MODE  LEARN MODE  BOILER TEST  INSTALL MODE         N      LO   lt   O  N  s     TA  O    ON       Wiring diagram WLM2   BA    Fuse     OUTPUT  C1 C2    SUPPLY BOILER Kouru  tlie    Volt free output  for boiler control    Main supplv    Secondary  230V AC from Volt free pump  10 Amp fused X output 230V  isolator Max 6A    2 wire low voltage bus    between the sensor controllers     Connect   to  and Lto L  Thermostats can be wired as  conventional Star or as Bus    NB  Remember the voltage of the Thermal actuators connected mode  Daisy chain      230V or 24V must correspond to the master  See instruction for further  explanation     THERMAL ACTUATORS  Output 1  Output2   Output3   Output 4 Output 6   Output7   Output 8 c  SUPPLV  DISP   SENSOR    ololololelelejelejelelejelejeje eere  aoeeoe  jelelelelejaleja    SENSOR SENSOR CONTROLLER  Output 8 BUS  THERMAL ACTUATORS             g  No No  1 2 LN  Thermoheads L  Timer   DX wivolt free contacts     Open contacts  for night setback       Outdoor  compensation  module  lf  fitted     BR965A27A    NETWORK BUS    NETWORK BUS    ADD ON MODULE    WIRELESS RECEIVE    Wiring diagram WLM2   AO    a  al     PE    Main supply  230V AC from  10 Amp fused  isolator    Secondary  pump  230V   Max 6A    NB  Remember the voltage of the Thermal actuators  230V or 24V must c
20. P  to zero  center position    Room controllers  CT  recommended to 21  C     Set all override switches on TM and TD Room sensors to automatic position  clock symbol      11  The system is now operating automatically     NB  Other important settings can be found in the User manual on the pages shown bellow     Off temperature  frost protection  page 7  Minimum  amp  Maximum floor temperatures page 7  Maximum supply water temperature page 8  Weather compensation page 8       p  7    TROUBLESHOOTING     Problem    Channel light is not coming on    When in Learn mode      When in Install mode  when the Room  sensor is activated  set to maximum      The actuator on the manifold has not  opened after 3 minutes     UFH Pump not starting in install mode       Possible cause  amp  solution    Make sure the power light is fast blinking  If not then put DIP 3 to ON position     2 wire bus may be incorrectly connected  Voltage at each Room sensor should not be  lower than 4 0V  check for    amp    continuity and short circuits     For wireless Room sensors  please check that the batteries have been inserted correctly   Has the init button been pressed     For wireless Room sensor check that the WLRC 19  receiver  is correctly connected    For channel 9 14  is the AO module correctly connected to the Master    Make sure the Room sensor in that room is set to the correct channel number     The channel selector on the Room sensor may be slightly out of position  try rotating and  the set i
21. aces  real wood  are used  The sensor should be positioned where it can  read the true temperature of the floor and should alwavs be within the heated area    Min  temperature limitation is used to keep a floor surface warm  irrespective of room temperature   For example  water on tiled bathrooms or pool areas with drv more quickiv if the floor surface is kept  warm  The sensor should be positioned where it can read the true temperature of the floor and should    alwavs be within the heated area     For easv replacement we recommend that all floor sensors are mounted in a tube which is placed  between 2 heating pipes  The inner end of the tube should be sealed  and the sensor cable brought  back to the wall edge  If required  the sensor cable can be extended up to 50 m with a standard    installation cable     WLTM  Use of external room sensor    A remote room sensor can be used instead of the built in sensor bv connecting the jumper across the  two pin bridge on the printed circuit board under the  Room sensor cover  From factory the jumper is    parked    on one pin  Location of jumper see fig  3     Technical Data  Wireless   Supply Voltage Batteries  2 x AAA Alkaline 1 5 V    Distance to master                Max 30 m  PNnClOsSuiles       dec ene See Sees ees ceed IP 21  Ambient temperature range         O to 40  C    868 MHz  Up to 30 m inside   Up to 100 m outside    Communication frequency           Communication distance       Batteries  Wireless    The Room sensors u
22. and   to       Interconnection of WLM2 products     p  32    For easy installation  interconnections between master modules  master and add on modules  and  master and wireless receivers  are made by pre wired plug in connectors  RJ45  For connecting  WLM2 add on modules to WLM2 masters  a plug in connector is provided with the add on module   A WLRC wireless receiver is also connected to a WLM2 master  using the plug in connector provided  with the receiver    For connecting a WLM2 master to another master  a plug in connector kit is available     INSTRUCTIONS    Waterline Wireless System       Product Programme Technical Data  WLRC 19 Receiver Supply Voltage               24 V from Master  Distance to master   vt ritwiz onzznate   Max 3 m  Enclosure auaa IP 21  Ambient temperature range           O to 40  C  Communication Frequency            868 MHz  Communication distance       Up to 30 m inside     G0 Sede ESH OE eee E Up to 100 m outside    Connection of Master and Receiver    WLM2 Master       Blue   Red   Brown Yellow    The receiver is connected to the master or the add on module using the included cable        WLRC 19         O    i                                         Max distance between the master add on module and receiver is 3 m  Up to 5 receivers can be  connected  The wiring of the master  add on module and receiver can be made in either a daisv  chain or in parallel     ogg O            Do not place the receiver inside a metal box  In case of communicatio
23. and from Room sensors     Master is in cooling mode     Incorrect connection  see master wiring diagram for correct connection   Valve actuator assembly is incorrect   Actuator is faulty     Check what happens if sensor and or outdoor module is missing     Valve may be oversized   Supply Limit sensor may be subject to heat migration     Upstream water temperature is excessively high    these problems may be corrected by changing PI settings     please refer to the main manual     p 9    Room is too cold    After running for at least 48 hours     Room is too hot   After running for at least 48 hours     The Room sensor is placed in a position that does not represent the general temperature in  the room  E g  mounted on external wall or near an extraneous heat source     If the room is controlled bv a CT Room sensor  check that the time and temperatures are set  correctly     If the Room sensor has got an override switch  TM or TD   the switch may be set in the    off     or    night    position     For rooms with floor sensors  the maximum floor limit setting could be preventing the room  reaching the desired temperature     Insufficient heating capacity of the system     Bad insulation creating large heat loss     This could be caused by draughts within the wall cavities     The Room sensor is placed in a position that does not represent the general temperature in the  room     If the room is controlled by a CT Room sensor  check that the time and temperatures are set  correc
24. atures  For example wooden floor constructions which should not be  allowed to exceed a maximum of 27  C  The value can be set from 5  C up to 55  C  The value can also be set to OFF  adjust the  temperature to 55  C and push button up once more     Low limitation is used where the temperature of the floor is required never to fall below the minimum set temperature  Example in  kitchens or bathrooms with tiles  The value can be set from 5 C up to 55  C  The value can also be set to OFF  adjust the  temperature to 5  C and push button down once more   Remember the max limit temperature must be set higher than the min limit  temperature    The limit temperatures defined in the room controller will be valid for all the room sensors with limit sensor  type WLTD 19  which  are part of the area allocated to the WLCT unit     The maximum allowable floor temperature setting is shown  Use  the UP  A  or DOWN  V  button to increase or reduce  and OK    V   button to accept     The display will now show Loli  Press OK  V   button to continue     The minimum allowable floor temperature setting  Use the UP  A   or DOWN  V  button to increase or reduce and OK  V   button to  accept     You can select either   C or   F scale  and 12 or 24 hour clock as  follows     Press UP  A  or DOWN  V  button to change settings  Confirm    the required scale with the OK button   V   button     Adaptive function   This function enables the thermostat to calculate when it needs to switch ON so that the re
25. d Special Features    POWER UP RECOMMENDATIONS  When all connections are complete  we recommend to use the quick guide  setting up svstem     Svstem check   Correct operation of the system can be checked using a special    Install Mode      This enables the installer to individually test and prove each output     Testing the system     1  Switch on DIP 3 to activate learn mode    power light will blink quickly  2  Each red channel light on the master should now be lit if a sensor controller is present on that  channel     3  Switch off DIP 3 to de activate learn mode again     power light stops blinking   4  Turn all adjustable temperature settings on the sensor controller to minimum   5 Switch on DIP 1 on the master to activate install mode  Install mode will be active for 2 hours     Pumps  boiler  mixing valve and actuators should now be off   6  Turn the temperature setting on the adjustable sensor controller in room 1 to maximum   The red channel 1 light should be lit and the actuator on output nr  1 will be activated  and will  open after 1 3 minutes  depending on the type of actuator   Important  If the sensor controller is of a wireless type a delay of up to 5 minutes may occur before  the channel light becomes illuminated    Check that the UHF pump is running and the mixing valve  only FS master  opens    Repeat step 2 on all rooms   Boiler test function   Switch on DIP 2   This closes the boiler start relay contacts for 1 minute   10  To end all tests     Switch off
26. e 15 Waterline Wireless System                  Page 33  Boiler demand    enennenenznnnenzenennnna Page 15 Product Programme E ccd  A e hoe Lee A Page 33  Pump OULDUE ai iedecaccchdaeddwesecdeatedccwsaauanas Page 16 Connection of Master and Receiver                Page 33  Free relay function  X DUTPUT i  s s s Page 16 POSION kasba iniedi Page 33  Thermal actuators j  0icctaponatva sienna inpejzbi nie Page 17 META sci EEA A NT Page 33  External switch for night setback                    Page 18 To set up the system            ccccecesecseeeeeeeees Page 33  Room sensors   Bus connection                    Page 18  Room sensors   Wireless setup            0000    Page 19 Type WLCT        cccceesceeeeeeeeneeeeeneenes Page 34  Setting up which Room sensor controller ROOUCHOM    icscacnccmecerka e Page 34  should work with wich thermal actuator            Page 20 Getting started ns cnnaunsicracscoanmenttonemeerenanens Page 34  Supply water temperature sensor Daily Use of the room SeNnSOl              e0eeeeeee Page 36  and MIXING VANS 3  xx active cored anda ae kima d die Page 21 Programming 4 Event Clock Time   and Temperature            ssssee en enennnnnna Page 37   Creating a Network         ssssnnnnanzannnnnz Page 22 Advanced Settings and Read out                   Page 38  Using cooling function misinreszsjnzesiissenzzzonjona Page 23 Reset to factory Settings   room controllers       Page 41  Domestic hot water control          s eee Page 23  Radiator CONU Olas  lt nd lt 0n
27. e energised after a delay of 10 sec after the start of the main pump     Basic versions without display  Type WLM2 1BA and WLM2 3BA The boiler relay will stop if  there is no heat demand measured by the Room sensors     Versions with display  Type WLM2 1FS and WLM2 3FS   These units have supply water temperature control  and the boiler relay will be ON once the  control valve has reached 20  open  and will remain on as long as a heat demand exists        The master has an output for the underfloor circulating pump  secondary pump   The output will be  energised after a 180 sec  delay when any connected room sensor calls for heat  The delay is to  allow time for the thermal actuator to start opening     The 230v AC pump can be connected directly to terminals L and N under the heading    Sec  UFH  Pump     Connect the pump E  Earth  terminal to E  earth  on the master  The maximum pump load  must not exceed 4 amps   230v at start up  There is an overrun period of 1 minute after the demand  for heat from the room sensor disappears    Delay times  Secondary UHF pump 180 sec   X output  configured as main pump  190 sec        Fig  8a SEC    OUTPUT UFH   PUMP   L ce    Volt free output  for boiler control    Secondary  Volt free pump  X output 230V  Max 6A       BR965A15b    All WLM master have a relay which can be    utilized for a number of different purposes  To control         p Boiler pump  The relay is a volt free output and is positioned    on the PCB as shown on the drawing
28. e hot water take off pipe immediately above the storage    A cylinder  Use the fixing strap to mount it tight to the surface   ma The WLCT HW must be fixed in convenient position for the user  H ser Ta uror e Connect the hot water controller WLCT2 HW to the WLM2 master using the sensor controller bus        REMOTE SENSOR  FOR HOT WATER    p  23 ae    e Connect the hot water sensor to the controllers sensor terminals   e Connect the hot water zone valve to an output on the WLM master and set the channel number  on the hot water controller to the corresponding number     Note  When the WLCT HW calls for heat it does not start the circulation pump on the under floor  heating system       Radiator control     It is possible to control a radiator circuit room temperature with a special Room controller  WLCT R  to  ensure optimum energy saving    The Room controller measures the temperature in the room  and a zone valve is then controlled via the  WLM master  which in turn activates the boiler on demand     e The WLCT R must be fixed in a convenient position for the user  but which is representative  of the room or area temperature   Connect the Room controller to the WLM master using the sensor controller bus   Connect the radiator zone valve to an output on the WLM master and set the channel number  on the Room controller to the corresponding number     Note  When the WLCT R calls for heat it does not start the circulation pump on the under floor heating  system    2 step heating
29. e of increasing or decreasing the preset DAY  amp  NIGHT setpoints on the master by     4C for  the heating zone which it is controlling     The Room controller WLCT has its own DAY  amp  NIGHT temperature settings that can be set separately  and if manual Room sensors are attached to  its  group  these will operate to the same settings as the WLCT  but still with the possibility of local  4  C adjustment     CHANNEL 15 OPERATION  It is possible to override all the automatic functions of the master control  and the Room controllers with a single function  This action is used for  holiday periods  e g  to set the whole system under a frost protection mode   or to temporarily override all the temperature control of the system     It is achieved by using the any WLTM Room sensor  as this has the override selector  If the cover is removed and the channel selector is set to F   channel 15   that Room sensor will cease to operate its own output channel but will instead operate all the output channels of the system     Using the WLTM Room sensor  the slide selector on the right side can be used for as follows    Auto will allow the whole system to operate to the automatic settings    DAY will keep the whole system working to the DAY Setpoint  but only for those Room sensors that are set for auto    NIGHT will keep the whole system working to the NIGHT Setpoint  but only for those Room sensors that are set for either auto or day   OFF will turn the whole system OFF  but still under a
30. e system will run at constantly 20  on for the valve     If an outdoor sensor is connected  the system will run 40  at 10  C  and Below  decreasing to 0  at 20  C  and above      Exercise of valves  If no automatic on off sequence of valves or pumps occurs over a 72 hour period  an exercise of these components will take place  The actuators  will be activated for 3 minutes  The pumps will be started for 10 secs during that period  and the mixing valve  if fitted will be opened and closed        INSTRUCTIONS  Add On Module       Configuring the Total System       WLM2 Master AO Module                AO Module Cable       p  31    Each master module is capable of controlling 8 heating zones  each of which may use one or more  loops of piping  with one or more thermal actuators  These zones are referred to as channels 1 to  8  If you wish to control more than 8 zones  it is necessary to install an ADD ON  AO    modules  each of which can provide another 6 outputs     The first AO module then controls channels 9 to 14   Connection of master and add on module    Connect the AO module  using the special cable included in the box   Mains supply from 230V fused isolator    INSTRUCTIONS  Outdoor Compensation Module  Type WLOC 19           Introduction       Mounting    x jk    BR939A09A       The masters WLM2 1FS and WLM2 3FS are supplied already prepared for weather compensation  and simply by adding the outdoor compensation module on the 2 wire bus and using the water  temperature s
31. efaulted to 20  C and the night temperature to 15  C  These default settings can  be changed if the master has a display  The current operating set point of the master can be changed  from the day temperature into night temperature  and vice versa by using an input from an external  switch or timer  The input must be a volt free switch  and will need to open circuit for night temperature  and close circuit for day temperature  When the external switch or timer is used to switch to night  setback  this will override any time settings in a WLCT Room controller  including any Room sensors that    are part of a group allocated to that Room controller     BR965A17a    Timer    w volt free contacts   Open contacts   for night setback       Room sensors   Bus Connection       Only OJ Room sensors type WLxx that are prepared for 2 wire communication can be used  Standard  installation cable  maximum 2 x 0 25 mm  can be used  The Room sensors can be connected in the  conventional star wiring format  or in a bus connected mode  Daisy chain  see fig 10   fig 11  The  master has 4 sets of terminals marked Room sensor BUS that can be used for connecting the 2 wire  signal from the Room sensors    There are 4 identical sets of terminals for convenient installation  Any Room sensor can be connected  to any pair of terminals  The total length of the 2 wire system can be up to 300 m with a maximum  length of 100mbetween any 2 Room sensors    Remember to connect   to   and  to      ae  BUS    
32. ensor on the supply water side  you have a control system for weather compensation   Preset values are programmed at the factory  but these values can easily be adjusted according to  local needs via the display on the master  See the user manual    Master with display type WLM    for  changing of the default factory settings    The outdoor compensation module is mounted under the roof eaves  alternative 2 3 m above ground  level  Direct sunlight or any other direct heating source such as air ventilation must be avoided  The  outdoor compensation module is mounted vertically with the cable entry downwards     BUS CONNECTION   Outdoor Compensation Module    WLOC          BR965A22a    Only OJ Outdoor Compensation Modules type WLOC 19 that are prepared for 2 wire  communication can be used    Standard installation cable  minimum 2 x0 25 mm2 can be used  The outdoor compensation module  can be connected in the conventional star wiring format  or in a bus connected mode  Daisy chain    The master has 4 sets of terminals marked Room sensor BUS that can be used for connecting the  2 wire signal from the Room sensors and the outdoor compensation module    There are 4 identical sets of terminals for convenient installation  Any Room sensor   outdoor  compensation module can be connected to any pair of terminals  The total length of the 2 wire  system can be up to 300 m with a maximum length of 100 m between any 2 Room sensors   outdoor  compensation module  Remember to connect   to   
33. ent dee cetera Volt free signal  Max 4A  Main pump  free relay  missierek nce ik e i Volt free signal  Max 4A  OG NI je l reene 230V AC  50Hz Max  4A  Thermal actuators    WEM2  TBA ee een e ee ROE eee Tere eet eer eer nee eee ee ee eee 8 x 230V   WEM2 A eect care ga ect eee eiateneg a 8 x 230V   Max  2A per output  Max  5A in total   WEM2 39BA anon ae er eet One a eel eee eee ree ee eel eee ee aera a ere 8 x 24V   cat Poe S  ee ne ne ee ee ere ne eee ee ee ee ee Cee eee en eee ee ae 8 x 24V   Max  10VA per output  Max  35VA in total  Optional External Switch  Timer  for night setback           seen nnennen Open terminals for NSB   Closed terminals for day operation   Room sensor Bus 2 wire low voltage       Lee bus signal from Room sensors  Additional data for WLM2 1FS  amp  WLM2 3FS  not applicable to the basic version   Application sensor and Limit SENSOF               ccsseceeeeeeeees NTC type ETF 1899A for water temperature  Control signal for mixing valve actuator cadensstaeasicacdecsbeesentdmedesnascusais rael 0 10V DC  Power supply for mixing valve actuator            s sssessssssrrnsrsrrrrresrrrrrrnrnrrerernrrnsnrntneennnne 24V AC  Max 6VA    Environment    Please help us to protect the environment by disposing of the packaging in accordance with the  national regulations for waste processing     Recycling of obsolete appliances    Appliances with this label must not be disposed off with the general waste  They must be collected  separately and disposed off according
34. et the clock and day  and define the room sensors  rooms  that should belong to the area        The room controller has a pin button marked R  see fig  1   allowing you  at any time  to reset the room  controller to the factory settings  These are listed at the end of this manual with space for you to record  your own weekly schedule        Getting Started  Buttons       Adjustment  down    BR939B01A    Adjustment Reset to Pin button  up factory adjust of  setting clock       p  34    Time and  temperature    Day number   4 event symbol  Xt Wake TY   Out    C Night f4 Home       Setting the room controller into operation    First time power is connected the clock and day will be flashing and must be set  If you need to  adjust the time of the thermostat at a later date  insert a pin into the hole marked     see fig  1   for setting of time and day  Adjustment should be made for change in summer and winter time     Press the UP  A  or DOWN  V  buttons to select  the correct hours and press OK button  vV       Press the UP  A  or DOWN  V  buttons to select  the correct minutes and press OK button   V       Then press the UP  A  or DOWN  V  button to  select the correct day and press OK  V   button        AREA SETUP   see page 40    p  35       Daily Use of the room sensor    4 Event Clock Mode    4 event clock mode   automatic mode     Comfort mode     e NV X 5 secs     Manual mode     p  36    The day has been split into 4 events describing a typical day  When the room   senso
35. gs which are used by all non Room sensors  that are connected to the system  In Master WLM2 1BA  amp  WLM2 3BA  the DAY temperature setting  is fixed at 21  C and the NIGHT temperature is fixed at 15  C     In Master WLM2 1FS 8 WLM2 3FS  the DAY  NIGHT and OFF default temperatures are adjustable  through the display     Automatic switching between DAY and NIGHT temperatures is done by either connecting a separate  timing device to the master  or using a WLCT Room controller and allocating other Room sensors as  part of its group  It is possible to have two or more Room controllers in the system  with each one  having its own group of non Room controllers     Setting of Room sensor Operating Mode    Fig  3 Room sensors type WLTM 19 29 and WLTD 19 29 have a slide switch  see fig  4  for selecting the mode  of operation of the controller  Four different modes can be selected  Auto  Dav  Night and OFF        Auto  The controller will follow the temperature settings of the master  or if the Room sensors  belongs to a zone group using a WLCT Room controller  it will follow the automatic sequence of  temperatures and timings set in the WLCT     BR939A08B    Slide      Day  It will control the room temperature according to the  DAY  setting defined in the master  switch  typically 21  C         Night  It will control the room temperature according to the  NIGHT  setting defined in the master   typically 17  C      Adjustment    knob   OFF  It will control the room temperature accordi
36. he humidity sensor WLH the system limits the formation of condensation on floor  surfaces due to high humidity    e The WLH must be fixed in a room that represents the general humidity level in the building  and  connected to the sensor controller bus  more than one WLH can be used if necessary e g  on  separate floors of the building   Where more than one humidity sensor is used  the master will take  the reading of the sensor detecting the highest humidity level for the controlling action     e lf a dehumidifier is being used it can be connected via a relay using number 1 output on the master  and setting DIP 7 to    on       Note  This output gives either 24Vac or 230Vac depending on the WLM2 master type  Channel  number 1 cannot be used for Room controller control in this situation     e When cooling is enabled the cooling set point will be pre determined by the master and will  override any settings in any Room controller to ensure optimum energy efficiency    The cooling set point will be  3C above the master day set point     Domestic hot water control        It is possible to control the domestic hot water temperature with a special Room controller  WLCT   HW to ensure optimum energy saving    A hot water sensor is connected to the Room controller and measures the temperature in the storage  cylinder    A zone valve is then controlled via the WLM2 master  which in turn activates the boiler on demand     BUS  L    BR965A32a    e Install the hot water senser  ETF  on th
37. is displayed   Continue pressing the UP A  button until you reach one of the desired sub menus  PRO  Hi Li  Scal  and ArEA  For explanations  see  below  Select the sub menu with the OK  v   button     INFO   Information  The values of the actual measured room temperature and the floor temperature can be seen   The floor temperature is only shown if a floor sensor is installed     Press UP  A  or DOWN  V  button to show the different  Software version    a  j i readouts     Room temperature            gt    eat  Floor temperature       _  gt     No changes can be made here  Use the OK   v   button to end     PRO   4 event sequence   It is possible to change the factory event sequence of Days 1 5   4 event  and days 6  amp  7     2 event  Days 1 to 5 are usually Monday to  Friday  whilst days 6  amp  7 are usually Saturday  amp  Sunday  An EVENT is either an ON or an OFF operation  You can select from the  following sequences which are displayed in the form of a code     4 events 5 days  2 events 2 days indicated by Code 4 52    4 events 6 days  2 events 1 days indicated by Code 4 61    4 events 7 days indicated by Code 4 70    2 events 7 days indicated by Code 2 70    2 events 5 days  2 event 2 days indicated by Code 2 52    Select the required sequence with the OK   v   button     Hi Li   Floor sensor  Max and min allowed temperature of the floor surface   A limit sensor can be connected to the room controller    Max limitation is used for safety to prevent high floor temper
38. n problems it mav be necessarv  to move the location of the receiver  or to add an additional receiver        Connect the receiver to the master  and the svstem will reconfigure itself for wireless operation     To set up the svstem  See Quickguide          p  33    INSTRUCTIONS  Type WLCT    Introduction    The room controller type WLCT is part of the underfloor heating system type WLM  The room controller  can be set to control one single room  or it can be set as a master to control a group of room sensors   rooms zones   Here after referred to as area    All the room sensors that are part of that area will follow the times and temperatures programmed into  the room controller  For example  if the temperature programmed in the room controller is 22  C  all the  room sensors  rooms  belonging to that area will then also be controlled at 22  C  Depending on the types  of room sensors used you can adjust the temperature   or  4  C in different rooms  giving a possible room  setpoint of  18 to  26  C     The room controller can be programmed to work at different temperatures during the day allowing lower  temperatures during times that the room is unoccupied  Lower temperatures will lower your energy  costs without reducing the comfort  All room sensors that are part of the area will follow any new time or  temperatures programmed in the room controller     When it leaves the factory  the room controller has a preset program suitable for most installations  You  only need to s
39. nal Supply limit sensor  type ETF 1899A  is defective  The fault is corrected by changing the temperature sensor  If the  sensor has been removed deliberately to change the operation of the system  follow the HARD RESET instruction below     Internal overheating  The master has its own internal safety temperature protection system  The problem is corrected by  improving the ventilation around the master module     Defective internal overheat sensor  The Master will control as normal  however the protection against internal over heating is no  longer active  The fault can only be corrected by replacing the master module     The communication to the AO module has been lost  The fault is corrected by re establishing the connection to the AO module  or by changing the AO module if it is defective   or if it has been deliberately removed  with a HARD RESET     Indicates total number of input units exceeded  Please refer to factory or your local service engineer   No connection to wireless receiver  type WLRC 19     Step 2 on 2 step controller  WLCT X9 2  is used by another room sensor controller     Only one error fault condition can be shown at a time  If more than one error occurs  they will be prioritised in the shown sequence  E1  2  3         p  29    Flashing output LED  red      The appropriate output channel LED can flash  indicating that the room sensor or room contoller on that channel has a fault error  The failure code can  also be seen in the service menu  Submenu 2a 
40. ng to the  OFF  setting defined in the master   typically 5  C   This setting is intended to be a frost protection    mode and is used if the room is  to be left unoccupied for long periods        WLTM 19 29  amp  WLTD 19 29 are recommended for guest rooms and other infrequently used rooms  as  they allow simple override of the automatic timing sequence     p  44    Limit Sensor   WLTD and WLCT    LIMIT SENSOR  MAX 50m    Jumper mounted  max  limitation  Jumper removed  min  limitation       Button learning mode    Channel  selector    p  45    BR939A17B    Room sensors controllers with a limit sensor have a mechanical jumper on the printed circuit board  allowing the limitation to be set for MIN  or MAX  temperature control  If set for MAX   it will have a  temperature setting of 27  C  Set for MIN   it has a setting of 17  C  These temperature are fixed when  used with masters WLM 1BA or WLM 3BA unless the Room sensor has been allocated to a zone  group controlled by a WLCT Room controller  In this case  the limit settings can be increased or  decreased bv accessing the Room controller  The limits then set will applv to all relevant Room sensors  with limit sensors belonging to that group  If the master WLM 1FS or WLM 3FS is used  the limit  settings can be changed through the programming buttons on the master     Mounting of limitation sensor    Max  temperature limitation is used to protect the floor area from becoming too warm  This mav be  required if special floor surf
41. o set the Room sensors into learning mode   Standard Room sensors without display  Remove the front cover and push the little leaning mode  button for approx  2 sec until the Room sensor give a little    bib      Room controller with display  Press the clock symbol for 2 sec until it says    init      The Room sensors will now transmit its unique code in the next 30 seconds  and the system has  been set up     To set up the system for the Master to receive signals from the Room sensors    Wireless only    To set the master into learning mode set DIP X to    on       The master will now look for new Room sensors that also are in learning mode  Remember to set  DIP X back to  off    RF LEARNINGMODE   will be shown in the masters with display     Setting of Room Temperature    If the WLTM 19 or WLTD 19 Room sensor has been allocated to a WLCT controlled area  then when  AUTOMATIC mode has been chosen with the built in slide switch  the temperature settings will be as  programmed in the WLCT Room controller and not in the master  but the same local  4  C adjustment  is available     On the Master WLM2 1FS and WLM2 3FS  if the temperature setting is changed  then the default  temperature for all the rooms is changed  but each WLTA  WLTM or WLTD Room sensor is locally  adjustable with its own adjustment knob  With this knob the temperature setting from the Master can  be increased or decreased by 4  C for that specific room     The master is supplied with default temperature settin
42. oders again should be set in sequence from 1   to 9    This numbering can be continued for up to 15  strings     All masters are interconnected using special cable  via the RJ45 socket 1 or 2    The last master of the first string must be connected  to the first master of the second string etc  etc     An FS master can be used as the    network  controlling master    for central mixing control of  supply water and boiler switching     Switching between cooling and heating can be done  for the whole network on the    network controlling  master    using the WLAC 1 interface module  connected to the thermostat bus     Using cooling functions    In addition to controlling heating  all WLM2 masters have the ability to control the system for cooling     e To enable the cooling function an interface module WLAC and humidity sensor WLH have to be  connected    e On BA masters it is also necessary to install a sensor  ETF 1899  on the return water pipework  from the floor for dewpoint control     e The WLAC must be fixed in a convenient position for the user  and connected to the sensor   controller bus as shown in the picture  pic     e lIfa BMS system in being used for the heating cooling decision  the volt free BMS signal should  be connected to WLAC but the slider switch on the right side of the WLAC must be set to the  heating position  in this situation the BMS signal has priority and we recommend that the slider  toggle be removed to avoid incorrect overriding     e By using t
43. orrespond to the master     THERMAL ACTUATORS    THERMAL ACTUATORS    Thermoheads    2 wire low voltage bus  between the sensor controllers   Connect   to  and Lto L  Thermostats can be wired as  conventional Star or as Bus  connected mode  Daisy chain    See instruction for further  explanation     SENSOR CONTROLLER  51 52 53  54    21 22  23 24  SENSOR CONTROLLER       Outdoor  compensation  module  If  fitted     BR965A28a    MASTER MODULE    WIRELESS RECEIVE    Description    Product Programme    Technical Data    Type WLM underfloor heating controller is suitable for connecting multiple room Room sensors and  electric actuators  thermoheads  for an underfloor or radiator based heating system    Room sensors requiring a 230 V or 24V live  amp  neutral must NOT be connected    Only OJ Room sensors type WLxx that are prepared for 2 wire or wireless communication  can be used     Product Thermo Heads Type   Master for 8 zones 230V AC WLM2 1BA  basic system   Master for 8 zones with display 230V AC WLM2 1FS  full system   Master for 8 zones 24V WLM2 3BA  basic system   Master for 8 zones with display 24V WLM2 3FS  full system   Add on module for 6 zones 230V AC WLM2 1AO   Add on module for 6 zones 24V WLM2 3AO    TECHNICAL DATA    Power Supply ie id i a eer nee eer rn tre 230V AC  10  15   50 HZ  Max load pumps and Thermal actuators asissivinjaboiijaria te ikekiznzkkonnanaj kai bii ig   Bena   ikbba za tabdanajiiini  inkirttt  j 10A  Boiler relay sipini erea en areeee tee acc
44. quired temperature is reached at the set  time  With a start time of 07 00 therefore  the thermostat may switch ON as early as 06 00 so that the desired temperature of 25  C is  achieved by 07 00  Without this function set  the thermostat will start to heat at the time you set     Press the DOWN  V  button to switch between on and off     Press OK   V   button to confirm        p  39    p  40       ArEA    Group of rooms    The rooms that are to be set as part of the WLCT area will follow the temperature settings of the room controller   example  an area could be the living room kitchen  and children   s rooms having a high room temperature during afternoon and ear  evening  and a lower temperature during the early part of the day and at night  Each room sensor will have a channel number   designated CH1  CH2 etc  The appropriate channel number of any room sensor is determined by the numbered output on the master  control which is actually switching the valve actuator for that area     For example  a system may have the kitchen room sensor operating master output   4  and the childrens room sensor operating  master output  5  If the WLCT room controller is then situated in the living room  and operating output  1  then the WLCT need   be programmed to control outputs 1  4   amp  5   Each room sensor will have been set to operate its appropriate output ch   see separate instructions     To do this  enter the ArEA sub menu   and press OK  V  button  CH 1 will be displayed  use 
45. r is in this 4 event mode it will change the temperature to the required level  automatically at the programmed times  As standard the room sensor has 5 days  with 4 events  two ON   s and two OFF   s   and 2 days with 2 events  one ON and one  OFF   For programming see page 17  Please  see page 18   PRO   4 event sequence  to alter the daily event sequence     In automatic mode  the clock function symbol        and one of the 4 event symbols   if A   A  C  will be  indicated  Programming page 17     Temporary override   To temporarily override any temperature in the 4 event schedule program  press the UP  A  button once  to show  the temperature in the display  and press UP  A  or DOWN  V  again to increase or decrease the temperature   The display will flash for 5 seconds  and will then revert to the time  The override will operate until the next  programmed event when the thermostat will resume the automatic programme     Cancel comfort mode  temporary override   To cancel the temporary override  press the OK   V   button twice     Permanent override    During holidays  the scheduled 4 event program can be overridden    Press the OK   V   button  and then the UP  A  or DOWN  V  button until the override temperature is set  The set  temperature will remain in the display and the unit will now operate to this temperature permanently     Cancel manual mode  To cancel the permanent override state press the OK   v   button once  and the unit will resume automatic function      
46. room    For hardwired Room sensors controllers now connect the 2 wire bus to the master or the AO module   maintaining continuity of positive   and negative   connections    For wireless Room sensors controllers now insert the batteries     NB  For Room sensors with floor temperature limiting sensors  please refer to separate instructions  included with Room sensors controllers     If the Room sensors controllers are of wireless type connect the receiver  WLRC 19  using the special  cable enclosed with the receiver     Bae EE    Red   Brown Yellow       p  4    WLM2 Master       Thermal  Actuators  4 5 6 7                                                             Manifold                   FLOW DIAGRAM WLM2 Master    Power  supplv           Connect the actuators to the channel outputs on the master in accordance with the pipe manifold  layout  please refer to the area schedule     Actuator no  1 on the manifold to output no  1 on the master    Actuator no  2 on the manifold to output no  2 on the master    cic                    Outdoor module WLOC 19  FS Master only    Install on north facing wall  away from direct sunlight   Connect into 2 wire Room sensor bus or direct to master  maintaining continuity of positive   and    negative   connections             Connect 230 240Vac power  UFH circulating pump and boiler in accordance with electrical regulations      For FS masters  connect the mixing valve and water flow temperature sensors           SETTING UP THE SYSTEM    1
47. se 2 x AAA batteries type  Alkaline  A lifetime of 1 2 years is expected  The  Room sensors are equipped with a low battery  alarm giving a little bip each 5 minutes in case   of low battery  If a Room sensor is defective or if  the communication to the unit is interrupted  an  alarm will be triggered on the master  and the room  will be heated at constantly 20  as safety  The  alarm can be overruled in the next 24 hours  On  the Room controller press the clock symbol for 2  sec  On the other Room sensors remove the front  cover and press the little learning mode button for  2 seconds     59   6 4 amp  4    OJ ELECTRONICS A S  STENAGER 13B  DK 6400 SONDERBORG  DENMARK    T  45 73 12 13 14  F  45 73 12 13 13  OjJ OJ DK  WWW OJ DK    OJ ELECTRONICS UK  CRUSADER PARK  WARMINSTER  WILTSHIRE  BA12 8SP  UNITED KINGDOM    T  44 01985 213 003  F  44 01985 213 310  SALES OJUK CO UK  WWW OJUK CO UK    ON    OJ ELECTRONICS    taking comfort further    
48. t DIP 4 to    on       This will set the supply water temperature at 23c for three days and will fully open all the manifold  actuators    Then for a further four days the water will be supplied at the maximum supply water temperature    as set in the WLM master menu  and during this period the manifold actuators will remain fully open     When the WLM master is operating the commissioning function this is indicated by the output  LED   s flashing in rotation and with the word    commissioning    flashing in the display    The commissioning function time periods are paused if the power supply is interrupted   Should you need to restart the commissioning from the beginning  switch DIP 4 to    OFF    and  back to    ON       To de activate the function switch DIP 4 to    OFF        Note  This function conforms to BS EN 1264 part 4     Replacing a faulty sensor controller     OnRwWN 4    Identify the sensor controller to be changed by the blinking output LED   Switch OFF power to the master   Change the sensor controller    Switch ON power to the master   Set the master into learnmode and set DIP 3 to ON    On wireless sensor controller now press the button on the sensor controller     On hardwired sensor controller go to step 7   7  Check that the corresponding output LED has changed from blinking to permanently ON   8  Reset the DIP 3 to OFF     For any other changes in the system use the quick guide and start the install sequence from the  beginning     p  26    Guidelines an
49. t again   Master is not in install mode     after 2 hours the master automatically de activates install    mode     please reset the DIP 1     Make sure the Room sensor in that room is set to the correct channel number   two Room  sensors could be crossed over     Check the red channel light is illuminated   The actuator for the room is not connected to the correct output on the master   Bad electrical connection between actuator and terminals     Actuator may be faulty or manually locked     Bad electrical connection between pump and terminals   Install mode is not activated     Pump may be faulty     p  8    Output relay for Main pump  Cooling  High  limit valve or other attached device     Boiler does not fire   LED lit      LED not lit     Mixing valve does not operate correctiv   When in install mode      Valve cvcles between open and closed in  normal operating mode     Incorrect connection to device  output relav has volt free contacts  see master wiring diagram for  correct connection     Bad electrical connection between terminals and attached device   Install mode is not activated     Attached device may be faulty     Incorrect connection to device  output relay has volt free contacts  see master wiring diagram for  correct connection     Bad electrical connection between terminals and attached device   Install mode is not activated     Attached device may be faulty     Timing sequence delay is activated  FS master only   mixing valve not open above 20   No heat dem
50. t and mode switch Auto  Day  Night  OFF  WLTD 19 29 Room sensor with adjustment  mode switch Auto  Day  Night  OFF and limit sensor  WLCT2 19 29 Room controller with 4 event clock    Mounting of Room sensor fig  2   The Room sensor is used for comfort temperature control in rooms  The Room sensor is mounted  on an internal wall with free air circulation about 1 6 m above the floor  Draught  direct sunlight  or  any other direct heating source must be avoided     Wired Room sensors   Only OJ Room sensors type WLxx that are suitable for 2 wire communication can be used   Standard installation cable  minimum 2 x 0 25 mm2 can be used  The Room sensors can be  connected in the conventional star wiring format  or in a bus connected mode  Daisy   chain   The master has 3 sets of terminals marked Room sensor BUS that can be used   for connecting the 2 wire signal from the Room sensors  There are 3 identical sets of  terminals for convenient installation  Any Room sensor can be connected to any pair of  terminals  The total length of the 2 wire system can be up to 300 m with a maximum length of  100 m between any 2 Room sensors  Remember to connect   to   and   to         Wireless Room sensors  Insert batteries     BR939A17B       Button learning mode       Channel  selector       Button learning mode    p  43    Setting up which Room sensor should work with which thermal actuator   Each Room sensor can be selected to operate a specific output which in turn controls the thermal  actua
51. the OK  v  button and then the UP  A   button to change the setting to ON  Press OK  V  and CH 2 is displayed  Use the UP  A  button until CH4 is displayed  press OK  V    and change to ON  Repeat this for CH 5  All three room sensors will now operate under the control of the WLCT room controller     In total up to 14 Channels can be programmed in this way  and it is possible to have more than a single room controller  each  own sub room sensors operating to its schedule and temperatures     Set the Channels   Rooms  Ch  to ON if they should follow the  settings of this clock thermostat     In total 14 channels   rooms can be controlled     ESC   Escape  Press OK  v   button to end programming and to return to  scheduled programme     Reset to fatctory Settings   room controllers    Factory reset        J Press the pin button R for 3 secs  and the thermostat returns to    factory settings   R Remember to set time  day and area        Factory settings    4 event time and temperature    onines  mer    ponsa ez f  temperature  aa ie  temperature       p  41    INSTRUCTIONS    Waterline Room sensors    p  42       Introduction  Fig 1    Fig 2    To remove front Ba           BR939A04B             1 6m             BR939A05A                MASTER    Room sensors  connected in star       MASTER       Room sensors connected  in chain  Daisy Chain     Product programme   WLTP 19 29 Room sensor tamper proof   WLTA 19 29 Room sensor with adjustment   WLTM 19 29 Room sensor with adjustmen
52. tly     If the Room sensor has got an override switch  TM or TD   the switch may be set in the    day     position     For rooms with floor sensors  the minimum floor limit setting could be increasing the room  temperature above the desired setting     Solar gain or extraneous heat source        INSTRUCTIONS  WLM Underfloor Heating Controller    Wiring diagram WLM2   FS    Fuse     OUTPUT  SUPPLY BOILER  M    Volt free output  for boiler control    Main supply Secondary  230V AC from Volt free pump  10 Amp fused X output 230V  isolator Max 6A       oO       2 wire low voltage bus AT   L   between the sensor controllers  LO   Connect   to   and Lto L     Thermostats can be wired as ag   x conventional Star or as Bus a   NB  Remember the voltage of the Thermal actuators 2 connected mode  Daisy chain    230V or 24V must correspond to the master  ul See instruction for further NETWORK BUS  explanation   THERMAL ACTUATORS   Output 1   Output2 f Output3   Output4   Output5   Output6   Output7   Output 8   ETWORKBUS    SENSOR CONTROLLER f     SUPPLY MIXING VALVE 0 10V    elolojolololololololololelolelel lolololejolelolelejo    ojolejololololololejolejolelolo  lololololololejolejo    APP     La SENSOR CONTROLLER  EXT SWITCH  SENSOR MIXING VALVE 24 VAC    P    Mixing Valve    Actuator  Outdoor  compensation  module  If  fitted     ADD ON MODULE    WIRELESS RECEIVE    EY EY EEI II II  Output 1   Output2 f Output3   Output4   Output5   Output6   Output7   Output 8  THERMAL ACTUATORS    
53. tors on the manifold  Under the front cover of the Room sensor  a selector can be accessed   and the number of its output  its CH channel  can be set with a screwdriver  Up to 14 channels can be  set on the selector  and there are two auxiliary channels with special functions  A WLM master has 8  outputs and additional slave modules each with 6 outputs can be connected creating a system of 14  individual zones     Please note that channels 10 to 14 are marked as A through E on the selector     A Room sensor set for CH1 will activate the thermal actuator connected to output 1 on the master   The channel number can be selected without any power connected to the system  The channel of the  Room sensor can be changed afterwards if needed  If two Room sensors are placed in the same  room and set to the same channel  the temperature control will work according to the average  temperature of both Room sensors     Channel 0    Each Room sensor is delivered with the switch in position 0 ensuring that it must be set to operate  correctly  Channel 0 can also be used for a Room controller controlling a group of Room sensors  where the control position could be somewhere central  e g  the kitchen  rather than in the area where  the Room sensors are installed  Setting it to Ch 0 means that times and temperatures are set on the  WLCT for the group  but that the WLCT will not control a specific output itself     Channel 15  F    Special function  Further instructions in the user manual     T
54. uld be configured so that it closes the valve if there is no heating demand  OVdc signal   The  control signal can be reversed to 10 OV via the master menu system if required   eee Control action of the mixing valve actuator is P     and the parameters can be    changed if required in the master menu system     Please contact the supplier for further instructions     p  21    INSTRUCTIONS       Creating a Network    Cirkulation pump control of each string    String 2             _      __    ON   N NN  BAFS    WLM BA FS f   WLM BA FS f IWLM    a     String 1          _____    f N NN NN   i A WLM BA FS   IWLM BA FSf   WLM BA FS         Network communication                    Boiler    WLM2 Master 1 WLM2 Master 2    Master Cable    p  22    BR965A31a    BR 0965 A01    In large buildings with more than 14 zones where  multiple manifolds are utilized  it is possible to use  multiple masters to create a single network     One master must be defined as the    network  controlling master    by setting both encoders to zero   see pic      Subsequent masters  up to nine  should be  connected as a    string     where they will all use a  common pump     If more than one pump is used  a separate string  should be created for each pump    se drawing below     On the first string all left hand encoders must be set  to 1  and the right hand encoders should be set in  sequence from 1 to 9    On the second string of masters all left hand  encoders should be set to 2  and the right hand  enc
    