Fire Systems Installation Manual
Contents
1. G installation helpline 0844 412 1777 Book commissioning 01509 232651 Sounders visual CLY400 Xenon beacon Diameter Depth Alarm Positive Alarm Negative Terminate screens to 5amp connector block or similar not to building earth Di kd Fixing centres 50 60mm apart Use designated gland entries top and bottom when used externally or IP rating is required CLY408 LED beacon and sounder Diameter Depth Alarm Positive Alarm Negative Terminate screens to 5amp connector block or similar not to building earth kd Fixing centres 50 60mm apart Switch setting 00010 provides 1st tone sweeping with 2nd tone continuous CLY408D IP65 beacon and sounder Diameter Depth Alarm Positive Alarm Negative Terminate screens to 5amp connector block or similar not to building earth Fixing centres 50 60mm apart Use designated gland entries top and bottom when used externally or IP rating is required Switch setting 00010 provides 1st tone sweeping with 2nd tone continuous installation helpline 0844 412 1777 Z FA4 Multi message voice sounder een width Depth Loop Positive Loop Negative Screen Terminate screens to 5amp connector block or similar not to building earth See pages 28 amp 29 for wiring details Fixing diameter of 60mm P44 rating Z FC3 S Voice Sounder c w Beacon weight width Depth
2. 300mm gt Trunking 100mm deep Strip light 150mm deep Detectors should be mounted twice the depth of any obstructions such as beams ductwork or light fittings less than 250mm in depth n If lt 300mm If gt 10 of consider as ceiling height f reaching the consider as 4 ceiling a wall 7 7 Z Partitions or racks within Structural beams greater 300mm of ceiling to be than 10 of ceiling height to treated as full height be treated as wall Applies to point detection and beam detection lt 1m gt a Detectors should be mounted minimum of 1 metre away from a forced ventilation system Book commissioning 01509 232651 K Complying with BS 5839 Pt 1 800mm l ta Ceiling void nr lt lt lt lt 11 1 y1y 1 11 ero Er re o ee EEE RE Rack Rack 500mm clear space to be maintained below each detector Flue y Accommodation A detector should be mounted within 1 5m away from a vertical shaft such as a lift at each level A detector should also be fitted at the top of the shaft Excludes L4 L5 amp P2 gt Areas ch 450mm 350mm not covered Beams not to run closer than 500mm to any wall partition or obstruction installation helpline 0844 412 1777 Any area covered by automatic detection that contains a horizontal void of 800mm or more in height automatic fire detection should also be provided in the void Sn ii lt p 10
3. Adria ZKEY2 Keyswitch man pan 2 position surface key switch labelled plant isolate control with normal and isolate as selectable functions using a normally open going closed switch Rated 230Vac 5amp but typically used with Z745 Z740 or Z45D CLY495B 24Vdc relay Width 110mm 110mm kd Ol DO 3 3 Kai Surface mounted top side or bottom cable entry Relay has a 24Vdc coil and double pole change over contacts rated 230Vac 5amp 2 5amp for inductive loads L Cima Installation helpline 0844 412 1777 Z841 Class change unit a ih ren Surface mounted only The unit requires 230Vac and link to Z740 Z45D or to the panel The box will not accept a 20mm gland cable entry possible top bottom left or rear Z2000 Conventional beam detection Oo m Ines om O me om Additional information from the installation helpline 0844 412 1777 See diagram on page 24 lt i s an OU el CLY517 Conventional IP MCP wm mm oam Used typically in cold stores with interface to addressable loop Surface mounting only with surface rd cable installation Bottom 20mm glands used to retain SES Clymer Book commissioning 01509 232651 G Z440 Rotating beacon Diameter 120mm 200mm kd 230Vac unit mounted in an up right position for IP rating and effective use Th
4. Tx and Rx must be securely mounted to either main structural steels or brickwork only Internal connections Connection Loop Loop Loop 24V 24V Earth screen Conventional 72000 Z45D Z45D Z45D Supply Supply Addressable ZLP2000 Contact installation helpline for advice on system architecture C installation helpline 0844 412 1777 Architecture for loop powered beams ZLP2000 230Vac Z60D or Z7 1B short circuit isolator High level transmitter Low level controller connected via dedicated 3 core to high level receiver Notes Controllers mounted low level Even distribution throughout the loop 6 beams maximum with 1km loop length No loop powered sounders Minimum of 8m between beam sets All mounted 300mm 600mm from the ceiling See BS siting section See isolator section Book commissioning 01509 232651 7 19 Intrinsically safe equipment l S Earth Note DX070 ZP ZB _MTL5025 The GBX70 galvanic isolator does not require a dedicated sn PRAIA l S earth The MTL5025 galvanic isolator also does not need Repas T ian 104mm a dedicated I S earth Any Screens Earths not wired in the mo LL elt diagram opposite should be terminated separately inside the H Bai enclosure to a suitable building earth 35mm 12 5mm Di 157mm 175mm 770D in rai Notes 75mm S DE All barrier equipment must be installed outside the Hun hazardo
5. Clymac Fire Systems Installation Manual Welcome to Clymac Fire Systems The Clymac ZP2 amp ZP3 analogue addressable fire alarm systems are both flexible and easy to install This pocket sized installation manual is designed to provide quick reference information at each stage of your installation The manual offers practical system installation guidance using an easy to follow format It deals with the various system architectures using colour coding to identify the type of connection followed by individual installation information for each product More detailed guidance is given separately for our specialist products interfacing arrangements and cable types to ensure they are fully explained Please make use of our Installation Helpline if you require any further support Your call to the helpline goes directly through to our team of technical support engineers who are trained to provide an instant response LPS 1014 Certificated LPS 1204 Assessed to ISO 9001 2000 Fire Detection and Alarm Certificated Fixed Certificate No 687 System Firm Certificate System Installer No CFA 154 Certificate No CFSI 018 Fire Industry Association Certificate No NAC G 3213 ee Wiring guide eg Equipment information Networks and Redcare 8 1st fix compatibility guide 50 Loop devices a Addressable equipment 54 24Vdc alarm devices and external PSU 12 24Vdc conventional alarm equipment 68 Isolators Li PSU s and
6. equipment with this specified n voltage type ZN 18 Transformer rectifier 1 5A E ee meme Surface mounting with cable top ai side or bottom not back entry Ae All transformer rectifiers require un switched fused spurs connected to radials from the main electrical distribution board Output is 24Vac and only suitable for powering door holders or other equipment with this specified ee voltage type ZN 16 Transformer rectifier 3A O nm wm ren Surface mounting with cable top 0 side or bottom not back entry ATI All transformer rectifiers require un switched fused spurs connected to radials from the main electrical distribution board Output is 24Vac and only suitable for powering door holders or other 0 equipment with this specified voltage type L Installation helpline 0844 412 1777 Book commissioning 01509 232651 co Ye d ZREDCARE BOX Redcare enclosure Width Surface mounted enclosure for 24Vdc Redcare communicator ei kd kd 24Vdc supply from panel PSU and 1 number 2 core cable for fire kd Any cable entry kd Schematic shown on page 8 Z67 IP heat sensor Diameter Depth Zone Positive Zone Negative Terminate screens to 5amp connector block or similar not to building earth 8 No base required kd Flying leads from the back of the detector 70mm fixing centres do not allow
7. 4 2 A N Ba A A C installation helpline 0844 412 1777 Book commissioning 01509 232651 aS K A 4 Rl vclertele 2710 lonisation sensor Diameter Depth Loop Positive Loop Negative 106mm N A N A N A Depth dimension excludes base Suitable bases Z7SB 1 Z7RB 1 Z755BV 27558 MI Did Z7 B A Z720 Heat sensor Diameter Depth Loop Positive Loop Negative 106mm N A N A N A Depth dimension excludes base Suitable bases Z7SB 1 Z7RB 1 Z755BV Z755B A d i gt Z7 IB A Y Z730 Optical sensor Diameter Depth Loop Positive Loop Negative Screen 106mm N A N A N A Depth dimension excludes base Suitable bases Z7SB 1 Z7RB 1 Z755BV rss Mle L j gt i P T A P CQO Installation helpline 0844 412 1777 a Z732 Optical heat sensor Diameter Depth Loop Positive Loop Negative 106mm N A N A N A Depth dimension excludes base a Suitable bases Z7SB 1 Z7RB 1 Z755BV 7 Na Z832 Multi sensor Diameter Depth Loop Positive Loop Negative 106mm N A N A N A Depth dimension excludes base kd Suitable bases Z7SB 1 Z7RB 1 e Gg Wy Z7 IB alll 7 ZLP2000 Addressable beam detector ron Depth Height wit n som om x rom om See diagram on page 24 d LI x FIRERAY 2000 l Le LI E Book commissioning 01509 232651 CO A Z DPU Duct
8. Fixing centres 50 60mm apart Back entry only Switch setting 00010 provides 1st tone sweeping with 2nd tone continuous st tone sweeping with 2nd tone continuous CLY200D IP65 sounder CLY280 High output sounder Diameter Depth Alarm Positive Alarm Negative Width Depth Alarm Positive Alarm Negative Screen Terminate screens to 5amp connector block or similar not to building earth Terminate screens to 5amp connector block or similar not to building earth Fixing centres 50 60mm apart Use designated gland entries top and bottom when used externally or IP rating is required Switch setting 00010 provides 1st tone sweeping with 2nd tone continuous CLY230 Bell CLY407 Xenon beacon and sounder Diameter Depth Alarm Positive Alarm Negative Screen Diameter Depth Alarm Positive Alarm Negative Screen Terminate screens to 5amp connector block or similar not to building earth Fixing centres 50 60mm apart Use internally entries top and back only Switch setting 00011000 2nd tone 988Hz continuous Terminate screens to 5amp connector block or similar not to building earth Fixing centres 50 60mm apart Fixing centres 50 60mm apart Use internally entries top and back only Use designated gland entries top and bottom when used externally or IP rating is required st tone sweeping with 2nd tone continuous
9. available Call active LED per Refuge Point Fault relay output on board Active Call relay output on board Anti Tamper input on board Can be interfaced with optional toilet alarm kits add part no TC8 to include additional LED s to panel needed for this Back box size for flush mounting H 360mm W 460mm D 98mm CDC L or R RS16F 16 Way Refuge Panel Surface Refuge Points Height Width Depth Supply Battery Backup See pages 34 amp 35 for wiring details Also available in 32 48 amp 64 way variants larger on special order Loop or Radial Wiring Configuration types available Call active LED per Refuge Point Fault relay output on board Active Call relay output on board Anti Tamper input on board Can be interfaced with optional toilet alarm kits add part no TC16 to include additional LED s to panel needed for this Flush mount kit available Book commissioning 01509 232651 9 Disabled refuge amp toilet alarm RCO SS Refuge Type B Handset RCO SS Refuge Type B Handset Retuge Points Height Width Depth Supply Battery Backup E sn a NA See pages 34 amp 35 for wiring details Compatible with both Loop or REFUGE CALL Radial wiring types i Call Button to activate Main Panel Call active LED Must include part no FH BB for flush mount box or SH BB for surface mount box Back box
10. detector Width Depth Loop Positive Loop Negative Terminate screens to 5 Amp connector block or similar BH See diagram on page 30 L Z FH DPU Duct detector Width Depth Loop Positive Loop Negative See diagram on page 30 f P ON co Installation helpline 0844 412 1777 Book commissioning 01509 232651 KO Manual call points Z785 3 Manual call point MCP Z785B Surface box weight width Depth Loop Positive Loop Negative screen em With Depth Loop Positive Loop Negative Terminate screens to 5amp connector block or similar not to building earth Can be semi recessed or surface with Z785B Do not over tighten Do not foul the test key entry at the bottom of the unit Shallow switch boxes OK Supplied with 2 number 30mm M3 screws Z785K Keyswitch manual call point weight With Depth Lop Positive Loop Negative Sen oamm somm 2emm Red Blick Terminate screens to 5amp connector block or similar not to building earth Can be semi recessed or surface with Z785B When semi recessing 35mm switch boxes should be used TOK 003 keys used supplied with 2 number 35mm M3 screws kd Z787 IP67 manual call point Wiath Depth Loop Positive Loop Negative sereen Terminate screens to 5amp connector block or similar not to building earth Surface only with surface c
11. fixing to conduit box Applications where a back box is needed a Red Alert box should be used eg YCR 502 For use with Z70D see page 19 CLY485 Remote LED Width LED c w legend on a single gang switch plate Terminate s to number 2 middle and s to number 3 right FIRE DETECTOR OPERATED Co Installation helpline 0844 412 1777 CLY410 Door holder 24Vdc Width 24Vdc unit Rear entry with conduit box otherwise bottom or side entry only and terminate ve s and ve s as shown kd Rated holding force 112 newtons or 11 5Kg s Schematic shown on page 16 gem CLY420 Door holder 230Vac Width 230Vac unit Rear entry with conduit box otherwise bottom or side entry only and terminate LEN shown Rated holding force 112 newtons or 11 5Kg s Schematic shown on page 17 mge 996 Door holder 24Vac Width Dimensions relate to main body of the unit only kd kd kd kd Swing free and 24Vdc magnetic hold open for doors up to 950mm and 60Kg s Fitted on pull side of the door near the hinges and the external switched 24Vdc terminated to the red and black connections kd 9 Book commissioning 01509 232651 CLY475B 230Vac relay man zen Ki kd Surface mounted top side or bottom cable entry kd Relay has a 230Vac coil and double pole change over contacts rated 230Vac 5amp 2 5amp for inductive loads
12. special bases devices subject to agreement with all parties Basic rules for loop design 1 N OA WO A 127 address maximum 1 device 1 address combined sensor sounder 2 addresses 1km or 2km maximum loop powered sounders 1km Based on 1 5mm 2 core cable Continuous screen preferably not connected to building earth 300mm separation from high voltage cables Remote LED s can not be connected to sounder bases Maximum of 16 isolators per loop Addressable sounders A Sounder bases 60 number per loop or B Sounder beacon bases 40 number per loop or C Horn sounders 40 number per loop or D Horn sounder beacons 25 number per loop or E Beacons 60 number per loop Book commissioning 01509 232651 co 24Vdc alarm devices and external PSU K K K K K K K K Sprinkler C installation helpline 0844 412 1777 24Vdc Conventional alarm circuits ZP3 available with 4 circuits ZP2 with 2 circuits per loop Further circuits added by using Z752 interface or 8 way auxiliary boards ZP3 only All devices colour coded red in further sections can be connected to these circuits Enhanced or standard cable see page at end of this section Strictly radial connection only no spurs End of line resistor fitted in last device on each circuit Short circuit isolator G Addressable sensor Addressable manual Addressable relay call point Addressable interfac
13. transformer rectifiers 74 Interfacing be E Further equipment 80 lyi ith B Pt 1 2 Complying with BS 5839 Pt o Disabled refuge and toilet alarms 90 Beam detection 24 Intrinsically safe equipment 26 System commissioning Voice sounders 28 Duct detection 30 Approved cables 32 Contact details Disabled refuge and toilet alarms 34 Panel information ZP3 42 ZP2 44 Batteries and enclosures 46 C installation helpline 0844 412 1777 Book commissioning 01509 232651 CO installation helpline 0844 412 1777 Networks and Redcare Loop devices 24Vdc alarm devices amp external PSU Isolators Interfacing Complying with BS 5839 Pt 1 Beam detection Intrinsically safe equipment Voice sounders Duct detection Approved cables Disabled refuge amp toilet alarm Book commissioning 01509 232651 Networks and Redcare REDCARE BT92A 230Vac IC 230Vac CD PANEL PANEL 24Vac CN CN CD CT CD CN i REPEAT REPEAT CD IL 230Vac IL 230Vac CD ei PANEL PANEL installation helpline 0844 412 1777 ZP3 standard networks ZP3 NW1 Enhanced cable see page at the end of this section 600 1000m total depending on cable type Spurs star connections radials or combinations allowed Represented by solid purple line ZP3 secure networks ZP3 NW1 and ZP3 NLM Enhanced or standard cable see page at the end of this section 600 1000m between panels depen
14. 0Vac door holders E 230V L Door N Holders P P P P Screen Screen Loop in Input monitoring eg sprinklers Sprinklers P P P P Screen Screen Loop in Book commissioning 01509 232651 Interface connections Input monitoring eg fire fault from remote system Output contact eg gas valve 230Vac E m 7320 Door Holders Contacts Screen Loop Loop Loop Loop in out in out Output contact eg lift Conventional zone Conventional Zone Lift Important Contact only rated 30Vdc 1A P P P P Screen Screen 24v PSU Screen optional Loop Loop in out Optional PSU is needed where a large number of Z70D s are connected to one loop seek advice from Clymac l d 4 x D x D D di d 4 f CO Installation helpline 0844 412 1777 Book commissioning 01509 232651 CO gt a g Complying with BS 5839 Pt 1 MCP s at least 15mm proud of wall and 1200mm above floor 600mm 150mm ry 600mm 150mm Heat detector distance from ceiling 25mm to 150mm Smoke beam detector distance from ceiling 25mm to 600mm Detectors in unventilated voids to be mounted in the top 10 or 125mm whichever is greatest SR 500mm gt 500mm Detectors should not be mounted within 500mm of obstructions such as walls beams or ductwork greater than 250mm in depth installation helpline 0844 412 1777 a 200mm gt
15. 0msq 50msq This is the General Coverage of Heat and Smoke Detector types based on a flat ceiling You can add 1 to this for each degree a ceiling is angled Maximum of 25 allowed Heat Spacing also applies to Multi sensors amp Combined Smoke Heat Detectors Applies to corridors less than 2m in width For wider corridors normal detector spacing applies i e 10m and 7m Only Smoke detectors or a mixture of Smoke amp CO detectors should be used in corridors amp escape routes Book commissioning 01509 232651 Beam detection Addressable and conventional versions of the beam detector are available The following notes describe the connections for both Receiver end Transmitter end Blue label Red label 110mm 10 100m Vertical Horizontal alignment 70mm alignment Terminate to local conduit box Screen Screen not to building earth Red Brown Blue Black Yellow Grey Terminate to local conduit box Screen Screen not to building earth Red Brown Blue Blue 5 100m In Out Terminate to local conduit box Screen earth lug located in conduit box Local 24Vdc Brown Rx Black OV Rx Grey Signal Rx supply Z2000 or addressable loop ZLP2000 Controller Fire Fault Loop in and out required for both ___ 22000 Z2000 and ZLP2000 only When the Z2000 is used an additional 24Vdc supply is required 210mm
16. 1777 4 ZC 5 18 amp ZC 5 EN Power supply unit wm we om Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D All PSU s require un switched fused spurs connected to radials from the main electrical distribution board ZC 10 12 Power supply unit wm wan ren Ensure the cables do not enter near 5 the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D All PSU s require un switched fused spurs connected to radials from the main electrical distribution board Book commissioning 01509 232651 co ZH 15 3 Power supply unit with zen Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D All PSU s require un switched fused spurs connected to radials from the main electrical distribution board kd kd ZH 3 7 Power supply unit wm Dein Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D kd All PSU s require un switched fused spurs connected to radials from the ui main electrical distribution board ZH 5
17. 24 Power supply unit wm Dein a H Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D All PSU s require un switched fused spurs connected to radials from the main electrical distribution board Cola kd A b 4 Installation helpline 0844 412 1777 T ZH 10 40 Power supply unit 500mm 450mm Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as e Z45D Z570 Z51D All PSU s require un switched fused spurs connected to radials from the main electrical distribution board Orma kd kd ZH 20 Power supply unit 500mm 450mm 200mm wm pm Batteries in separate box ZH 68 E 1 number 2 core 2 5mm cable required ZH 68 E Battery enclosure was Dein Used with ZC 5 EN for 72 hours ee standby See page 13 h N b h 2 Book commissioning 01509 232651 lt KZ Transformer rectifiers ZN 17 Transformer rectifier 0 375A wm wm ren Surface mounting with cable top e e side or bottom not back entry All transformer rectifiers require AH un switched fused spurs connected to radials from the main electrical distribution board Output is 24Vac and only suitable sane for powering door holders or other e
18. 4 412 1777 Book commissioning 01509 232651 Bases 1st fix plates Z7SB 1 Surface sensor base Z7 IB Combined sensor base amp isolator Diameter Depth Loop Positive Loop Negative Screen Diameter Depth Loop Positive Loop Negative Screen Unit designed to be fixed to conduit Used instead of detector base e box or similar with fixing centres Z7SB 1 50 90mm apart kd kd Devices should have two fixings in the conduit box to avoid the base spinning around when the heads are installed kd Remote LED connection on 2 on 3 Z7RB 1 Recessed sensor base Diameter Depth Loop Positive Loop Negative Screen Unit designed to be fixed to conduit box or similar with fixing centres 50 90mm apart i kd Devices should have two fixings in the conduit box to avoid the base spinning around when the heads are installed Remote LED connection on 2 on 3 120mm clearance hole ceiling lt 25mm Z755SPB Sounder st fix plate Diameter Depth Loop Positive Loop Negative Screen e Unit designed to be fixed to conduit box or similar with fixing centres 50 90mm apart kd Devices should have two fixings in the conduit box to avoid the base spinning around when the heads are installed Common mounting plate for all addressable sounders Dimensions shown include base but not horn No remote LED connection W White R Red kd LT a gt
19. CERTIFICATION CERTI cor SE LPS 1014 Certificated LPS 1204 Assessed to ISO 9001 2000 Fire Detection and Alarm Certificated Fixed Certificate No 687 System Firm Certificate System Installer No CFA 154 Certificate No CFSI 018 B all e I d PF 7 Fire Industry Association B SIB id ected wn Certificate No NAC G 3213 e Clymac Cloudway Court Belton Road Loughborough LE11 1LW Tel 01509 232651 Fax 01509 232665 Email sales clymac co uk www clymac co uk PART No Z IM1
20. EO S P Bp o E gt 52 S B Ss N yd v ESEN Sco 5 O gt 9 a Y bo 47 I once aa F a S lt 7 S So e Z QZ ou 2540 CO BS se ES LL gt E lt x UO Lu Z v LE d i 08 aoe O 0 ko O is a 9 5 SES SES E Ba V 06 SES BUS T gt VAS JZ oi DO ILE 8 LEE FP Z cq vv DO S UV N50 Pee v o 2 02 L ego O gt Ka O to n o in an alarm condition Volt free relay contacts switch 1mm T amp E Three cores of four core stranded burglar alarm cable 3A Fused Spur Book commissioning 01509 232651 O Disabled refuge amp toilet alarm 10 30 zone panel 10 30 zone panel wiring connections Ceiling Pull 4 Call Point Common positive Common negative Installation helpline 0844 412 1777 Book commissioning 01509 232651 lt N 2 Panel information CH E E Been e w ZP3 panel ZP2 panel Batteries and enclosures installation helpline 0844 412 1777 Book commissioning 01509 232651 Q ZP3 Panel ZP3 FC Flushing collar Depth of panel once recessed N Wall cut out size Height 570mm k Width 440mm Depth 120mm kd ZP3 1 240 Single loop panel Loops Width Supply Loop 24V alarm Terminations Terminations 230Vac See diagram A See diagram B 0 75A ZP3 2 240 2 loop panel ZP3 RDU B Repeat panel Loops Width Supply Loop 24V alarm Loops Height Width Depth Supply 540mm 230Vac Se
21. Loop Positive Loop Negative Screen Terminate screens to 5amp connector block or similar not to building earth See pages 28 amp 29 for wiring details Fixing diameter of 60mm P44 rating Z FC3 D Voice Sounder Beacon Deep Base weight with Depth Loop Poste Loop Negative sereen Terminate screens to 5amp connector block or similar not to building earth See pages 28 amp 29 for wiring details Fixing diameter of 50mm IP66 rating use bottom gland holes and IP glands only Book commissioning 01509 232651 Vi Sounders visual FC3 B Voice Sounder Midi een width Depth Loop Positive Loop Negative Screen Terminate screens to 5amp connector block or similar not to building earth See pages 28 amp 29 for wiring details For use in indoor large open areas warehouses etc kd 4 x fixing points 85 8mm apart IP44 rating FC3 D Voice Sounder Maxi en width Depth Loop Positive Loop Negative screen Terminate screens to 5amp connector block or similar not to building earth See pages 28 amp 29 for wiring details For use in outdoor or in indoor large open areas warehouses etc 3 x fixing points 30mm apart on arm IP67 rating use gland holes and IP glands only FC3 C I Mini Fire Cryer Base Sounder Diameter Depth Alarm Positive Alarm Negative Screen Terminate screens to 5
22. able installation Bottom 20mm glands used to retain IP67 Installation helpline 0844 412 1777 Book commissioning 01509 232651 9 Sounders visual Z755HA 2 Sounder Diameter Depth Loop Positive Loop Negative Units available in white or red and are designed to fit to same colour base Z755SPB Horns can be locked with removable clip Z755HAV 2 Sounder beacon Diameter Depth Loop Positive Loop Negative Units available in white or red and are designed to fit to same colour base Z755SPB Horns can be locked with removable clip Z755B Sounder base Diameter Depth Loop Positive Loop Negative Designed to fit Z755 SPB C installation helpline 0844 412 1777 Z755BV Sounder beacon base Diameter Depth Loop Positive Loop Negative Screen 127mm N A N A N A Designed to fit Z755 SPB Z755V Beacon Diameter Depth Loop Positive Loop Negative Screen Unit designed to fit into detector surface base Z7SB 1 2 Z755WV 2R IP65 sounder beacon Z755WP IP65 sounder Width Depth Loop Positive Loop Negative Use 20mm glands bottom for IP rating Use the holes provided for fixing Book commissioning 01509 232651 K Isolators Interface equipment Z7 IB Surface base and isolator Diameter Depth Loop Positive Loop Negative Used instead of detector base Z7SB 1 f weight width Depth Loo
23. amp connector block or similar not to building earth See pages 28 amp 29 for wiring details Fixing Diameter of 57 5mm Fits underneath standard detector bases or with optional front plate can be used as standalone fitment kd Only use in small rooms offices hotel bedrooms etc installation helpline 0844 412 1777 Book commissioning 01509 232651 ZC 1 3 Power supply unit Width Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D d All PSU s require un switched fused spurs connected to radials from the main electrical distribution board kd kd ZC 1 7 Power supply unit O nom wen pa Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D 4 All PSU s require un switched fused spurs connected to radials from the main electrical distribution board kd ZC 3 12 Power supply unit O mm w o Ensure the cables do not enter near the position for the batteries bottom half There is generally enough space for small interface equipment such as Z45D Z570 Z51D All PSU s require un switched fused spurs connected to radials from the main electrical distribution board d C installation helpline 0844 412
24. arm have to be synchronised together Contact Clymac for detailed support on Maximum circuit loads lengths installation helpline 0844 412 1777 EOL Fire Panel Sounder Circuit End of Line BOL 2 core Fire Rated Cable 1 5mm Min Sounder Circuits Sounder Circuit needed for each Voice Alarm circuit _ wired 2 core Fire Rated Cable 1 5mm Min Each circuit PSU Fault Monitoring Note all voice sounders connected to Z FS4 board are syn chronised even if the fire panel sounder circuit inputs are not Alert Message is activated by a pulsing fire panel sounder circuit input NOTE ZP3 on board sounder circuits cannot be pulsed need to fit MA8 board Evac message is activated from a steady fire panel sounder circuit input Other messages can be activated by shorting inputs C D E F to Ov Contact Clymac for detailed support on Maximum circuit loads lengths and more information Book commissioning 01509 232651 Duct detection Z DPU Duct Detector Clymac use two types of duct detector as shown Both use the same principles of positive and negative pressure to force a sample through the detector as such some common rules apply 1 Three times the width of the duct away from any CRE bend branch or reducer 2 Designed to work with linear air flow 1m s 8m s 3 The body of the detector must be completely sealed Z DPU Duct Detector 1 Designed to b
25. ding on cable type Ring connections only Represented by solid and dotted purple line Repeat panels ZP3 RDU ZM2 RDU 24Vdc via main panel or PSU represented by green lines Data cable from main panel represented by orange lines Star radial or spur connections allowed Enhanced or standard cable see page at the end of this section 4 core cable should not be used Redcare ZREDCARE 24Vdc via main panel or PSU represented by green line Two core cable for each signal represented by orange line BT Redcare BT92A block installed by BT local to Redcare box Analogue lines not exceeding 3 REN can be used Lines cannot be through PABX systems Lines that use data cannot be used Allow 3 weeks once all information is provided to Clymac Book commissioning 01509 232651 lt Loop devices Short circuit isolator Addressable sensor Addressable manual OA Addressable sensor call point and sounder Addressable sounder Addressable relay Addressable sensor Addressable interface and sounder beacon Addressable sounder and beacon C installation helpline 0844 412 1777 Addressable detection loops Available with 1 2 or 4 loops All devices colour coded blue in further sections can be connected to these circuits Cable should be Standard or Enhanced see page at the end of this section Spurs off the loop are possible without
26. e 24Vdc sounder Addressable sounder interface Sounder closest to control panel to be installed on dedicated circuit Configuration when using external batteries and chargers 2 Core FP 230Vac 230Vac ZH 68 E ZC 5 EN 68Ah PSU Battery Enclosure 2 Core FP Book commissioning 01509 232651 7 Isolator schematic Short circuit isolators Z60D or Z7 IB Fitted to the loops blue circuits Maximum 16 per loop Roof Space arrangement assumes no structural separation Do not take an address Not to be fitted to spurs loop only Ideally not concealed from view Distributed as shown A Sounder nearest the panel B Each change of floor within 5 devices C Every 32 trigger devices D Every 2000msq Note C or D Key 1st Floor Isolator base C W blanking cover Addressable sensor Addressable manual call point Combined sensor and isolator DIN mounted isolator output contact DIN mounted Addressable sensor Addressable sounder and sounder Ground Floor co Installation helpline 0844 412 1777 Book commissioning 01509 232651 Interface connections 24Vdc door holders Important Contact only rated 30Vdc 1A sAvde Doors PZ Ut loe 010 di T TG Important Contact only rated 30Vdc 1A 24Vdc Doors DC Output P P P P Screen Screen Loop C1 C2 250p oua ZN 16 or 18 23
27. e diagram A See diagram B 0 75A ZP3 4 240 4 loop panel Loops Width Supply Loop 24V alarm Terminations Terminations 540mm 230Vac See diagram A See diagram B 0 75A ff Diagram A Loop Terminations Top entry QQODOO inti Out Loop 1 In 220009 200000 screen screen Loops Alarms Diagram B 24V Alarm Terminations Sounder 2 Sounder 1 screen screen C installation helpline 0844 412 1777 Book commissioning 01509 232651 KO ZP2 Panel Add Part No ZP2 LB for a 2 Loop Expansion Board Two Inputs on board e Fire Fault Contacts on board 24v Sounder Circuits on board 2 on 1 loop 4 on 2 loop panels Loop Terminations 24v Sounder Circuit Relay Terminations Terminations ZP2 F1 S 03 1 Loop Panel Small Cabinet 1 298mm 410mm 162mm 240Vac 2x 12V 3 0A 7Ah ZP2 F2 S 03 2 Loop Panel Small Cabinet twee it mp nth Sepp nt aci COS N 2 298mm 410mm 162mm 240Vac 2x12v 3 0A 7Ah A EARTH BA C NC NO C NC NO Loop 1 Out 1 Out2 Fire Out Fault Out Rel Rel 000000 0000000000 000000 10000 H T 0 TT TI TTT Battery Battery ZP2 F1 03 1 Loop Panel Standard Cabinet 1 550mm 450mm 171mm 240Vac 2 XR IN 3 0A 18Ah ZP2 F2 S 03 2 Loop Panel Standard Cabinet 2 550mm 450mm 171mm 240Vac 2 RIV 3 0A 18Ah C installation helpline 0844 412 1777 Book commissioning 01509 232651 O 298mm N A 410
28. e fixed directly to the flat surface of the duct 2 To help achieve a good seal the unit comes complete with rear gasket rubber strip between connection detection chambers 3 Use knockouts provided for cable entry 4 When modifying the pipes to fit the duct each must be proportionally reduced The inlet pipe will require a 32mm UPVC end cap glued on The outlet must be Duct cut at a 40 degree angle Air flow Z DPU FH Duct Detector 1 Designed to be fixed away from the duct Z DPU FH Duct Detector 2 To help achieve a good seal the enclosure is designed to be fixed to the surface using the same fixing centres 180mm 100mm as the lid O O FT 3 All cable entries must be sealed with suitable glands SIL dani O 130mm d Each entry into the duct requires a 32mm hole This Sy a S is sealed with the 32mm ribbed grommets supplied 5 Inlet amp outlet should be inline and approx 450mm apart lt Air flow lt mS e M7 Duct installation helpline 0844 412 1777 Book commissioning 01509 232651 lt Q Approved cables Standard cables Enhanced cables Manufacturer Name Manufacturer Name AEI Cables Ltd Durham Firetec Multicore LSZH AEI Cables Ltd Durham Firetec Enhanced Multicore LSZH Cavicel SpA Firecel SR 114 H l Cavicel SpA Firecel SR 114 E Doncaster Cables Firesure i Draka UK Ltd Firetuf Plus Draka UK Ltd Firetuf EMC l Irish Driver Harris Kilfla
29. e only please contact the help line 5 The Draka Firetuf EMC should be used in applications where a risk of electrical or radio interference is anticipated such as Airports installation helpline 0844 412 1777 Book commissioning 01509 232651 lt Disabled refuge amp toilet alarm Loop wired 16 line disabled refuge call system Radial wired disabled refuge call system Ricer 1 Ricer 2 t Staircore 1 West Staircore 2 East RCO SS SH BB802 Up to the Up to the 8th Floor 8th Floor 2nd Floor lt gt Loop Highway 4 CORE Screen Fire rated cable RCO SS SH BB 4th Floor 4th Floor Cable 8 16 24 Core Size Slaves Slaves Slaves NEE 2100 1600 1200 Mtrs Mtrs Mtrs 25mm 2400 2100 1900 i Mtrs Mtrs Mtrs 2400 2400 2400 Extra PSU o mE Bera rsu Mtrs 1st Floor 3rd Floor 3rd Floor 2 Core Enhanced Fire Rated 2nd Floor 2nd Floor CCTV Volt free output Induction loop Audio output Toilet call loop interface Bring back toilet call 2 Core indicators on same network 1st Floor 1st Floor Toilet call fe O loop interface Toilet call Bring back toilet loop interface call indicators on Bring back toilet call Te gt same network e indicators on same network Note Toilet call signals CDC R RS4 must be wired to the main Master panel on a radial system Anti Tamper Anti Tamper Input from Fire Input from Fire CDC L R RS16 Alarm Panel Alar
30. e unit is supplied with o ring and gasket for IP rating For interfacing monitoring requirements call the installation helpline 0844 412 1777 UV IR Flame detection Width All information can be provided by the installation helpline 0844 412 1777 of Z805 Radio modem Width All information can be provided by the installation helpline 0844 412 1777 lo Installation helpline 0844 412 1777 ZNLINK Interface kd kd kd kd Width Surface mounting unit that gives a two way signal over a 2 core cable between panels One Znlink per panel maximum 10 panels Six core required between Znlink and local panel Panel specification Aux 24Vdc Clymac supply none latching zone class change spare sounder cct Book commissioning 01509 232651 Apollo I S equipment Z DP672 1 5 Optical Smoke Detector Diameter Depth Loop Positive Loop Negative See diagram on page 26 for more information Depth dimension including base 100mm x 50mm Suitable base Z DB670 Z DT673 674 678 I S Heat Detectors See diagram on page 26 for more information Z DT673 A2S class 50c Fixed Temp Z DT674 A2R class 50c RoR Z DT678 CS class 80c Fixed Temp Depth dimension including base 100mm x 50mm kd Suitable base Z DB670 Z DP672T I S Multi Sensor Detector Diameter Depth Lo
31. ing runs as smoothly as possible we would request that the following points have been observed prior to booking the commissioning visit 1 2 E 10 11 12 Book commissioning 01509 232651 7 working days notice for commissioning visit As fitted drawings marked up with address numbers Text label sheets complete at the time of booking the commissioning Any specific system configuration identified Loop complete and tested for continuity on both cores and screen No cable faults exist short cct between cores cores to screen or cores to building earth Cables terminated to the panel have each core correctly flagged Access equipment and operator available for our use Zone charts require 3 weeks notice and a disk copy of the AutoCad drawings All equipment is fitted that is directly connected to the cable installation i e sounder 1st fix plates sensor base MCP s interfaces All plug in devices that require addressing will be fitted by Clymac Free use of welfare facilities light power etc Clymac endeavour to work with personnel on site to overcome most problems Assistance may be required to fix cable faults fitting sensors etc drive access equipment and connect mains JIM MU Contact details installation helpline 0844 412 1777 0844 412 1777 01509 232651 01509 232665 commissioning clymac co uk AI www clymac co uk PRODUCT MN ff Of AIA 1 PRODUCT
32. ivates the Lamp Sounder unit and a rest unit to restore the system 12v Call Active Output for connecting to the disabled refuge system above or a 12v relay for a dry contact output Extra Pull Cords can be fitted to each toilet alarm system Book commissioning 01509 232651 Disabled refuge amp toilet alarm NC910 10 Zone Toilet Alarm Panel Alarm Circuits Height Width Depth Supply Battery Backup See page 39 for wiring details Surface or Flush Mounting suffix part no with S or F Flush backbox dimensions H 162mm x W 1176mm x D 55mm For battery backup order separate PSU part no BF360 12 LED per Toilet Alarm Circuit Zone Integrated Alarm Buzzer Labelling space for each zone NC920 20 Zone Toilet Alarm Panel Alarm Circuits Height Width Depth Supply Battery Backup See page 39 for wiring details Surface or Flush Mounting suffix part no with S or F Flush backbox dimensions H 162mm x W 1176mm x D 55mm For battery backup order separate PSU part no BF360 12 LED per Toilet Alarm Circuit Zone Integrated Alarm Buzzer Labelling space for each zone NC942B Single Zone Controller c w PSU Alarm Circuits Height Width Depth Supply Battery Backup NC809DB Button Reset Point Alarm Circuits Height Width Depth _ Supply Battery Backup from panel See pages 37 39 for wiring details f a Co
33. m 3000 Haani Cables Ltd Firecool Company Ltd Irish Driver Harris Kilflam 2000 Pirelli Cables Ltd FP Plus Company Ltd Pirelli Cables Ltd FP200 Plus Flex Pirelli Cables Ltd FP200 Gold LSOH n _ rr ee Tyco Thermal Controls Pyrotenax Mic light duty Pirelli Cables Ltd FP400 Canadaltad Tratos Cavi SpA Fire safe TW950 Ventcroftt Ltd Noburn Diamond Tyco Thermal Controls Pyrotenax PYRO S Wrexham Mineral Cables Wrexham Mic Canada Ltd Ventcroft Ltd Noburn Platinum Suitable for l 1 Standard networks Suitable for 2 Should be used on all circuits where the building has no sprinkler systems and 2 All other circuits excluding standard networks where the A building has a sprinkler system or A Is less than 30m high or 1 Secure networks when cable routes are diverse Is more than 30m high or B Is going to be evacuated in 4 or more phases or l C People will remain in occupation during a fire B Is going to be evacuated in 1 2 or 3 phases or C No people will remain in occupation during a fire 3 Enhanced cable may also be required as part of a specification or on basis of a risk assessment 4 The Pirelli FP400 cable compiles with BS6387 C W and Z At the time of writing no LCPB approved standard or enhanced grade cable with an armour was available Also in the absence of a screen the armour should be used It should be noted that all efforts to avoid interference need to be made and ELV ducts must be used Limited us
34. m Panel d installation helpline 0844 412 1777 Book commissioning 01509 232651 co K d Disabled refuge amp toilet alarm Hark 1 Disabled refuge toilet alarm Ceiling Pull Cord 3 Core 4 Core PSU amp Lamp Sounder Note Intruder alarm type cable should be used for the 3 core and 4 core interlink wiring Twin and Earth or similar rigid type cables should never be used Reset Sounder to be 1200mm max above floor 1st ring 100mm from floor 2nd ring between 800mm 1000mm from floor Hark 1 Disabled refuge toilet alarm e Use as a stand alone toilet alarm system or for interfacing into our disabled refuge system 230v AC lt __ To Ext In on CS802 loop interface card within Refuge Point OR For Radial System to main Refuge panel OR Pull Cord Unit To additional pull cords 12v Relay to give Dry Contact output installation helpline 0844 412 1777 Single zone panel Ove o a ke 8 wo Z CO D I Maso D OH UL gt CY w 0 YO gt a 3 G YG Gt mo 1 on BJ GR ce c E s Se Zo Se Se ES Dp oo Q d oo o E v y e EMS e Da VE as o T Lun Y CH n k550i O cgt S o Ga T Fa Noo Os O x VO pa C AoH S POS ZS a UN S eee CAIO G AE 5 RR Mo O e vw NG S SENS Sa 02 S 23s l SUMER O bp 6 Y i D va ce e ZB lt vzor So DO nM 2222 C Be Soo Bai e EC Sa pe m O c DECO DE E S 0 E e E V c Ooo SEL A X _ D x O
35. mm 162mm 240Vac 3 0A Connects to Panel Network Network Card needed for ZP2 main panel Batteries and enclosure ZM2 18 E ZM2 24 E f D y N E N al y amp Q Installation helpline 0844 412 1777 Book commissioning 01509 232651 O 3 Equipment information ITH en Clymac installation helpline 0844 412 1777 1st fix compatibility guide ELER Addressable equipment 24Vdc conventional alarm equipment PSU s and transformer rectifiers Further equipment Disabled refuge amp toilet alarm Book commissioning 01509 232651 1st fix compatibility guide Standard bases Only Use Z7SB 1 Surface Sensor Base Z7RB 1 Recessed Sensor Base Z7 B Combined Sensor Base and Isolator Compatible Devices Z710 Z832 Z720 Z755V Z730 Z732 Z755 COV For Blanking Isolator Base Sounder bases Only Use Z755SPB W Sounder 1st Fix Plate White Compatible Devices Z 55B Z755BV Compatible Devices Z710 Z832 Z720 Z755V Z730 Z755 COV Z732 ON y L EH P 2 co Installation helpline 0844 412 1777 Book commissioning 01509 232651 KO 1st fix compatibility guide Horn sounders Beacons Only Use Z755SPB W Sounder st Fix Plate White Z755SPB R Sounder 1st Fix Plate Red Compatible Devices Z755HAV 2R Z755HA 2R Z755HAV 2W Z755HA 2W installation helpline 084
36. nnects to either the single zone Q or Multi Zone toilet alarm panel 9 So Mounts to a standard Single J fe Gang Box lca Red LED for zone active indication e A Da Stainless Steel version available suffix part no with SS Alarm Circuits Height Width Depth Supply Battery Backup from panel See pages 37 39 for wiring details E Bee Connects to either the single zone or Multi Zone toilet alarm panel Mounts to a standard Single K f b Gang Box Si Ultra Bright Red LED s for Zone e Ze Active Indication Stainless Steel version available suffix part no with SS NC807C Pull Cord Unit Alarm Circuits Diameter Depth Supply Battery Backup 1 87mm 147mm 39mm 240Vac 3 0A Built in Rechargeable Enable a single toilet alarm to A be connected kd See page 37 for wiring details Mounts to a standard Double Gang Box kd Zone active LED indication Integrated Alarm Buzzer Integrated Reset Button Stainless Steel version available suffix part no with SS i installation helpline 0844 412 1777 from panel See pages 37 39 for wiring details Connects to either the single zone or Multi Zone toilet alarm panel Surface mount only Red LED illumination for zone active indication Book commissioning 01509 232651 installation helpline 0844 412 1777 To ensure the system commission
37. op Positive Loop Negative Screen 100mm N A N A N A See diagram on page 26 for more information Depth dimension including base 100mm x 60mm Suitable base Z DB670 co Installation helpline 0844 412 1777 Z DB670 Time Saver Base Diameter Depth Loop Positive Loop Negative Screen 105mm IN OUT See diagram on page 26 for more information Used connect I S only detectors to a Intrinsically Safe Conventional circuit Remote LED connection on IN on LED Fixing diameters of 51mm 60mm or 72mm ZC6 MCP IS 1 S Surface Call Point wm Depth Loop Positive Loop Negative sereen See diagram on page 26 for more information kd Back box included kd Depth dimension is including back box GBX70 Galvanic Isolator Width Depth Loop Positive Loop Negative 107mm N A N A N A See diagram on page 26 for more information Book commissioning 01509 232651 G Apollo I S equipment MTL5025 Galvanic isolator Width Depth Loop Positive Loop Negative See diagram on page 26 for more information DBB Sounder Diameter Depth Alarm Positive Alarm Negative Screen Terminate screens to Damp connector block or similar not to building earth See diagram on page 26 for more information kd Fixing centres 50 60mm apart Back entry only Switch setting 00010 st tone sweeping and 2nd
38. p Positive Loop negative sereen Fran smm 28mm P P seen For use with ZDIN ZDIN2 not in 3rd party equipment bes CO Installation helpline 0844 412 1777 Z752 Sounder interface Width Depth Loop Positive Loop Negative Screen Surface mounted with normally 5 number glands required to terminate to this interface kd kd Up to 3 number top entry and the rest must be rear entry via conduit m ka box or similar a A For connections see page 12 KA Width Depth Loop Positive Loop Negative See page 19 for wiring details Din mounted unit Designed to L LA fit into ZDIN1 ZDIN2 ZDIN e 7 H Interfaces Conventional Detection i circuits to the Addressable loop SCH on a Red LED for active fire condition ee e 2 Yellow LED for conventional ae i E line fault Built In Active EOL for Head Removal monitoring 3K9 Standard EOL kd kd Z45D DIN interface wm Depth Loop Positive Loop Negative sereen A A Designed to fit into ZDIN ZDIN2 Monitors clean contacts For connections see pages 17 amp 18 V dE et 85 a ei ara og ed N P 7 A Book commissioning 01509 232651 K Interface equipment Z51D Output contact 230Vac Width Depth Loop Positive Lop Negative cen Designed to fit into ZDIN ZDIN2 Mains must be segregated from kd kd unscreened loop cables
39. size for flush mounting H 230mm W 155mm D 55mm Built in connection for interfaced with optional toilet alarm kit on loop wired type systems RCO SS IP65 Refuge Type B Handset IP65 1 B sse wa wa IP65 weatherproof version surface mount only See pages 34 amp 35 for wiring details Compatible with both Loop or Radial wiring types Call Button to activate Main Panel Call active LED Built in connection for interfaced with optional toilet alarm kit on loop wired type systems kd installation helpline 0844 412 1777 Pt last H aen MA NA See pages 34 amp 35 for wiring details Compatible with both Loop or Radial wiring types Call Button to activate Main Panel Call active LED Must include part no FH BB for flush mount box or SH BB for surface mount box Back box size for flush mounting H 230mm W 155mm D 55mm Built in connection for interfaced with optional toilet alarm kit on loop wired type systems Built in Induction loop for hearing impaired HARK1 Disabled WC Kit Unit Height Width Depth Supply Battery Backup Lamp Sounder Lamp Sounder See page 36 for wiring details Each Unit fits standard single gang boxes Stainless Steel Overdoor Lamp fits a double gang box Kit comes complete with back boxes for surface mount option Note Stainless types are flush mount only Includes a Pull cord which act
40. tone continuous XB8024 S NR Beacon Diameter Depth Alarm Positive Alarm Negative Screen Terminate screens to 5amp connector block or similar not to building earth See diagram on page 26 for more information Installation helpline 0844 412 1777 DX070 Enclosure Height Width Depth Loop Positive Loop Negative See diagram on page 26 for more information Book commissioning 01509 232651 N A Disabled refuge amp toilet alarm RS1 F 1 Way Refuge Panel Flush CDC L or R RS8F 8 Way Refuge Panel Flush See page 35 for wiring details kd kd Comes complete with single Refuge Unit Part No Single Call active LED Fault relay output on board Active Call relay output on board Anti Tamper input on board Refuge Points Height Width Depth Supply See pages 34 amp 35 for wiring details kd kd Loop or Radial Wiring Configuration types available Call active LED per Refuge Point Fault relay output on board Active Call relay output on board Anti Tamper input on board Can be interfaced with optional toilet alarm kits add part no TC4 to include additional LED s to panel needed for this Back box size for flush mounting H360mm W360mm D75mm installation helpline 0844 412 1777 See pages 34 amp 35 for wiring details kd Loop or Radial Wiring Configuration types
41. us zone One Z70D conventional interface galvanic isolator can drive a maximum of 15 devices Ex MCP amp Sensors Ex Sounder One galvanic isolator can drive either one 1 S beacon or two l S sounders The output produced by the sounder is relatively low The equipment is made from non conductive materials The installer and user should ensure it is not installed in areas that would lead to a build up of electrostatic charge such as areas with high pressure steam 24y PSU Cleaning of equipment should be with a damp cloth optional S The sounder circuits in the hazardous area not monitored for fault Screens used for alarm circuits and detector circuits must not be connected to building earth via conduit boxes or switch boxes ATEX Ex lG BI Hazardous Key area I S conventional sounder G Addressable sensor LS addressable sounder ei Addressable manual call point LS addressable manual call point LK Addressable sounder LS conventional beacon Addressable 5 Conventional Interface Zenner Barrier GBX70 Galvanic isolator 24Vdc alarm sounder MTL5025 CK K L installation helpline 0844 412 1777 Book commissioning 01509 232651 KO Voice sounders Single Message Use EOL Fire Panel Sounder Circuit End of Line EOL TS m bh eg Sounder Circuits 2 Core Fire Rated 1 5mm Min Each Circuit Note all sounder circuits used for Voice Al
42. within the ZDIN Care should be taken when lives on different phases are switched creating 415Vac within the ZDIN 230Vac 5amp double change over contacts amp kd For connections see pages 17 amp 19 Z50D Output contact Width Loop Positive Loop Negative Screen Eor use with ZDIN ZDIN2 not in 3rd c party equipment E md a 1am VDC single change K si Bains ces x For connections see pages 16 amp 18 Rn LE j d s uo o M a i y ZDIN Enclosure Width Depth Loop Positive Loop Negative Screen 35mm DIN rail 244mm long y q installation helpline 0844 412 1777 Ser P ZDIN1 Enclosure Width Depth Loop Positive Loop Negative 35mm DIN rail 90mm long 4 1 number 85mm units will fit N e ki ZDIN2 Enclosure Width Depth Loop Positive Loop Negative 35mm DIN rail 145mm long i 2 number 85mm units will fit cable entry is top bottom only kd A 8 Book commissioning 01509 232651 Co Sounders visual CLY200 Sounder CLY260 Sounder base Diameter Depth Alarm Positive Alarm Negative Screen Diameter Depth Alarm Positive Alarm Negative Terminate screens to Damp connector block or similar not to building earth ER Terminate screens to Damp connector block or similar not to building earth Fixing centres 50 60mm apart 11118818 Back entry only fia