        JCC Installation Manual 1.12.2008
         Contents
1.   JCC  IM  1 12 2008 9    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements N  7  Refrigerant Pipe Connections    a  Pipe Installation   Run the suction and liquid lines in the appropriately sized refrigeration grade copper tubing as  per the tables in section 2  c   Pipework should be run in the same size as the connections on  the J5LC Condensing unit     b  Unit Connections   The outdoor condensing unit connections are terminated in male flare connections as detailed  in table 2  c   Indoor pipe connections are provided as plain copper tails that may require a  reducing fitting to match the pipework size to the evaporator connection size     c  Insulation  Use appropriate insulation tubing with a minimum 3 8    thickness on both refrigerant lines     8  Pressure Testing    a  Pressure Testing   Before evacuating the system it must be tested for any potential leaks  A pressure leak test  should be carried out using oxygen free nitrogen  OFN   NEVER USE OXYGEN FOR  PRESSURE TESTING SYSTEMS  Before starting any pressure testing  ensure the area  surrounding the system is safe  inform relevant personnel and fit warning signs indicating high  pressure testing  Also use correct PPE as required     A simple procedure for testing is as follows   1  Pressure system slowly up to 3 bar  45 psi  for 5 minutes and check for any signs of  leakage   2  Increase pressure slowly up to 10 bar  150 psi  for 5 minutes and check for 
2. Dimensions                                           Model Width  mm  Depth  mm  Height  mm  Weight  kg   JCC25E 865 370  480 30  J5LC15C 700 250 540 30  JCC40E 865 370  480 33  J5LC20C 855 328 648 59  JCC50E 900 370  540 36  J5LC25C 855 328 750 62  JCC60E 900 370  540 38  J5LC28C 855 328 750 68                           Excluding fan    Ref  JCC  IM  1 12 2008 3    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements N    c  Pipe Sizes and Maximum Pipe Runs                                                                   Model Pipe Connection Sizes Max Pipe Run  Liquid Gas Length Rise   JCC25E 1 4  1 2  12m 5m   J5LC15C 1 4     1 2    JCC40E 1 4    5 8  15m 8m   J5LC20C 1 4    1 2    JCC50E 1 4  5 8  15m 8m   J5LC25C 1 4    5 8    JCC60E 3 8  3 4  15m 8m   J5LC28C 3 8  5 8    Notes        1  J5LC Condensing Units are Pre Charged for a 7 6m Pipe Run  2  Run Pipework in the same size as the condensing unit connection and  use copper reducers at the evaporator where necessary    d  Refrigerant Charge    e JCC25E matched with J5LC15C     Pre Charged with 0 83kg R410a  Additional Charge     20g per metre up to maximum permissible    e JCC40E matched with J5LC20C     Pre Charged with 1 38kg R410a  Additional Charge     20g per metre up to maximum permissible    e JCC50E matched with J5LC25C     Pre Charged with 1 54kg R410a  Additional Charge     20g per metre up to maximum permissible    e JCC60E matched with J5LC28C     
3. E Hall requirements N  9  Electronic Controller Setup    JCC 25E  amp  JCC 60E     Danfoss EKC 101    a  To check the setpoint  Press both buttons on the controller together  Set temperature is displayed     b  To change the setpoint   Press both buttons on the controller together  Set temperature is displayed    Then press either the top button to raise the setpoint or the bottom button to lower the  setpoint  Press both buttons again to save the new setpoint     c  Manual Defrost  Press and hold the lower button for four seconds  To stop the defrost press and hold the  lower button for a further four seconds     JCC 40E  amp  JCC 50E     Dixell XR 20C    a  To check the setpoint  Press and immediately release the SET key  The display will show the current set point value     b  To change the setpoint  Press and hold the SET key for two seconds  The current setpoint value will be displayed and  the Snow LED starts blinking    Press either thet   keys within 10 seconds to adjust the setpoint up or down   To memorise the change press the SET key again    c  Manual Defrost  To start a manual defrost press and hold the DEF key for 2 seconds    d  To lock the Controller    Press and hold both the keys for more than three seconds  POF will appear on the  controller display  It is not now possible to change the setpoint    To cancel the controller lock  press and hold the same keys for three seconds until PON is  displayed  It is now possible to change the setpoint again    For fur
4. Heronhill   for all your J amp E Hall requirements    JCC Cellar Cooler Range  Installation Manual  December    08 Onwards     Contents    1     Installation  amp  Safety  a  Installation  b  Handling  c  Application  d  Electrical Connection  e  Warranty  f  General Information    Technical Specification  a  Cooler Duties  b  Dimensions  c  Pipe Sizes  amp  Maximum Pipe Runs  d  Refrigerant Charge    Electrical Details  amp  Fuse Ratings    Wiring Diagrams  a  JCC25E  amp  JCC60E  b  JCC40E  amp  JCC50E  c  All Outdoor Units  J5LC15C     J5LC28C     Locating  amp  Mounting Indoor Unit  a  Location  b  Fixing  c  Service Connections    Locating and Mounting Outdoor Unit  a  Location  b  Fixing  c  Service Connections    Refrigerant Pipe Connections  a  Pipe Installation  b  Unit Connections  c  Insulation    Pressure Testing  a  Pressure Testing  b  Evacuation    9  Electronic Controller Setup    a  Models   JCC 25E  amp  JCC 60E     Danfoss EKC 101  b  Models     JCC 40E  amp  JCC 50E     Dixell XR 20C    10  CE Documentation    Ref  JCC  IM  1 12 2008 1    Tel  018123 665660 www heronhill co uk    Page Number    M MMM MM    ooo OND o Z EGG    ooo    10    10    10  10    11    12    CE    Fax  01823 665807    Heronhill   for all your J amp E Hall requirements N    1  _ Installation  amp  Safety    a  Installation  The units making up the J  amp  E Hall International JCC cellar cooling system must only be installed  by a qualified engineer following the mandatory and local c
5. Pre Charged with 1 80kg R410a  Additional Charge     50g per metre up to maximum permissible    Ref  JCC  IM  1 12 2008 4    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements N    3  Electrical Details  amp  Fuse Ratings                                                                                  FLA LRA  Power   power Fuse  Model Supply   To   Interconnecting  Amps   Amps  Rating  v ph hz Cable Amps  JCC25E   240 1 50    Indoor   2 Core TE 6 04 Ne 16  J5LC15C 24  N A  JCCAVE H T indoor 2 Core  E 7 61 L 20  J5LC20C 27  N A  JCC30E   940 1 50   Indoor   2 Core  E 9 03 i 25  J5LC25C 32  N A  JCC60E 5407 50   Indoor   2 Core  E 12 82 f 32  J5LC28C 65  Ref  JCC  IM  1 12 2008 5    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements    J amp E Hall  International   4 Wiring Diagrams   JCC25E  amp  JCC60E  Indoor         a   gt   m Da  a2   z 4  G L   f S D  u    0 O    rit I  nw o gt  ro 70   C1 p ked   Ma      lt  El  Bg    g  Z l G  ga   7  fa    na  a  4  Ro  Da   E  GG  aR  T  4  O G  G         T     20 G  m G  tI a  E   G    a           Ref  JCC  IM  1 12 2008 6    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements    JCC40E  amp  JCCSOE  Indoor         g  Pp  27  m a     Z    4  o   s  El       m  u  m EJ  Io     III    N P ru 7  Op Ked  mo     lt   A C  S o  SD iam  ne  gt   om oO  EE 7  cr  g
6. any signs  of leakage   3  Increase pressure slowly up to 33 bar  500 psi  and check for any signs of leakage   Leave system under pressure for 24 hours     Listen for any possible leaks and check all joints with bubble spray  If any leaks are  discovered  release pressure slowly from system until empty  repair leak and then restart  pressure testing procedure  Never attempt to repair a leak on a pressurized system    A strength test should also be incorporated according to local regulations    Once testing has been completed satisfactorily release the pressure from the system  gradually and safely to external atmosphere     b  Evacuation   After the pressure testing has been completed  the system should be thoroughly evacuated to  reduce the risk of moisture being present  It is recommended that a triple evacuation  procedure is carried out as follows using a suitable vacuum pump  a torr gauge and oxygen  free nitrogen  OFN      Evacuate system down to 10 torr    Break the vacuum with OFN to a pressure of 1 bar    Evacuate the system to 5 torr    Break the vacuum with OFN to a pressure of 1 bar    Evacuate system a third time to 2 torr or lower if possible    Isolate vacuum pump and leave system for 30 minutes and ensure vacuum is held     E L de a    Once above has been completed satisfactorily then refrigerant charge can be introduced to  the system     Ref  JCC  IM  1 12 2008 10    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp 
7. nit  A 3 4    BSP drain connector is supplied with the  manuals  or cable tied to the fan guard  to be site fitted to the condensate tray    Please note the correct way to fit the drain fitting locknut as below         6  Locating  amp  Mounting Outdoor Unit    a  Location   Install the JSLC condensing unit in such a way that hot air distributed by the unit cannot be  drawn back in again causing a short circuit of hot discharge air  Allow sufficient space around  the unit for maintenance  Ensure that there are no obstructions to the air flow in to or out of  the unit  The location must be well ventilated so that the unit can draw in and distribute plenty  of air to keep condensing temperatures down and thus maintain cooling capacity  There  should be a minimum clearance of 150mm from obstructions to the air inlet at the side and  rear of the condenser and at least 1000mm in front of the unit for air discharge  It is  recommended that at least 500mm clearance is maintained to the service port side of the  condenser to provide good access for maintenance     b  Fixing   J  amp  E Hall International Condensing units can be floor mounted or wall mounted using  appropriate load bearing wall brackets  not supplied   In areas where noise is a particular  concern  the unit can be mounted securely on anti vibration strips  not supplied      c  Service Connections  Access to the flared refrigerant service ports and electrical cable entry is from the right hand  side of the unit     Ref
8. odes of practice    b  Handling  Care must be taken when the units are moved or lifted to ensure that everyone and everything is  safe  When lifting equipment is used  it must be suitable and approved    c  Application  Ensure that the unit is only used for a suitable purpose   application    d  Electrical Connection  Electrical work and connections must be made by authorised electricians in accordance with  mandatory regulations and local codes of practice    e  Warranty   Failure to comply with the manufacturer   s installation instructions could affect the performance of  the unit and invalidate the warranty  Warranty is also subject to the implementation of a planned  service   maintenance agreement    f  General Information  e All works must be carried out in accordance with manufacturer   s installation and  operating procedures    e Good working practices must be followed at all times so that mechanical and electrical  hazards are kept to a minimum    e The equipment has been fitted with covers to prevent access during operation  These  must be kept in place and additional guards fitted where necessary    e The equipment must be connected to a local external electrical isolator as one is not  supplied fitted to the unit  The rocker switch fitted to the indoor unit is for control isolation  only     e Servicing and maintenance must only be carried out by a fully qualified engineer  Before  any work is started  electrically isolate the units to make sure they cannot be s
9. t   m  x    eng 7  EAF GR  a0  z  oa of  L    ng  A o  m pda   i  9 g     ad    G  0      7 oO  m o  K 0  K  oO      a    et     Ref  JCC  IM  1 12 2008 7    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements ii    All Outdoor Units   J5LC15C     J5LC28C     PURPLE     ys    i  CM  N R BLUE    i GREEN  YELLOW    BLUE BLUE    j cu RED CAPACITOR  i      BLACK          CAPACITOR    CM   COMPRESSOR MOTOR i  FM   FAN MOTOR  poe   FIELD SUPPLY WIRING    Ref  JCC  IM  1 12 2008 8    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements T    5  Locating  amp  Mounting Indoor Unit    a  Location  The JCC Evaporator unit should be mounted level on a load bearing wall or ceiling  The  minimum distance from the floor to the bottom of the unit should be 1 8 metres to ensure  good air convection  The side inlet grilles should have a minimum clearance from  obstruction of 100mm and the minimum clearance in front of the unit should be 1500mm     b  Fixing  The evaporator should be fixed to the wall using the two off rear fixing holes or to the  ceiling using the two off top fixing holes  10mm diameter rawbolt type fixings  not  supplied  with large steel washers are necessary for local load bearing of the indoor  evaporator     c  Service Connections  The refrigerant pipe connections are accessed through the left hand side panel  Cable  entry is on the right hand side of the u
10. ther details  please contact your J  amp  E Hall International Distributor    Ref  JCC  IM  1 12 2008 11    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements    10  CE Documentation    ETL SEMKO    Certificate    ATERS       S for European Product Safety    Reference No  517031    Air conditioning appliance for    cooling heating  Type designation JCC 25E  JCC 40E  JCC 50E  JCC 60E  Certificate holder J amp E Hall Refrigeration Sdn  Bhd     Lot 10  Jalan Perusahaan 8   Kawasan Perusahaan Pekan Banting  42700 Banting   Selangor Darul Ehsan    MALAYSIA    The product complies with EN 60336 1 2002 A11 A1    the standard s  EN 60335 2 89 2002 A1  EN 50366 2003  Date of expiry 25 April 2011    EU Directive information The product satisfies the provisions for CE marking according to the Low  Voltage Directive 73 23 EEC and 93 68 EEC     Terms in Intertek Semko s Agreement on certification  Additional information in Appendix     Certification Body Intertek Semko AB  Product Certification Place Kista   Stockholm    Ref  JCC  IM  1 12 2008 12    Tel  018123 665660 www heronhill co uk Fax  01823 665807    
11. witched on  accidentally and allow sufficient time for the isolated parts to come to rest before  removing panels  Electrical isolation switches MUST be labelled to show that they are off  during the servicing and maintenance operations  Care must be taken not to touch  components or pipework which may be hot or cold  for a period after the unit is electrically  isolated    e After completing any tasks ensure all guards and covers are correctly refitted before  restoring the power to the unit    e The equipment has been specifically designed to run at low noise levels  but if further  noise reduction is desired  sound and vibration attenuators may be required  For noise  level guidance refer to technical literature  or contact the distributor for advice    Ref  JCC  IM  1 12 2008 2    Tel  018123 665660 www heronhill co uk Fax  01823 665807    Heronhill   for all your J amp E Hall requirements if  2  Technical Specification    a  Cooler Duties                                                                         Cooling Refrigerant   Indoor Unit     Mogel Capacity kW   Type Airflow ms   Noise Level dB A   JCC25E 2 45 R410a 0 83 Internal 45  J5LC15C N a External 30  JCCC40E 4 05 R410a 0 83 Internal 45  J5LC20C N a External 32  JCCC50E 5 10 R410a 1 11 Internal 45  J5LC25C N a External 32  JCC60E 6 13 R410a 1 11 Internal 45  J5LC28C N a External 34  Notes              1  dB A  Levels are free field at 10m  2  Duties Quoted   12 7  C db  10  C wb internal  32  C external    b  
    