1. ICY18xx Timer Thermostats User Manual and installation guide I C Y B V Postbus 193 8630 AD Lemmer The Netherlands T 0031 514 563424 Fax 0031 514 564252 iseewhy icy nl www icy nl 2008 ICY B V rev 00241108 Installation 1 Check whether the power supply for the installation is correct 24VAC or DC and turn the power off 2 Remove the plug from the back of the Timer Thermostat Connect the 2 thermostat wires to the plug and replace the plug back onto the connector 3 If applicable check whether the thermostat wires are connected to the heater clamps used for the On Off control option 1 in the schematics below 4 Mount the Timer Thermostat using 2 screws of approx 30 cm via the but ton openings and turn on the power 5 The thermostat will start up and will emit an acoustic signal 6 The flashing symbol indicates whether any pre programmed clock set tings have been lost E g as a result of a power failure The symbol will disappear by programming the thermostat clock see later on in this guide or if you do not want to use the clock by resetting the thermostat You can do this by shorting the two contact points to the right behind the right button e g using a small flathead screwdriver HEATER HETER DoE Lol option 1 option 2 ATTENTION When the device does not work correctly it may be necessary to attach the resistor included to the heater s clamp strip Please
2. 10s the display reads P2 3 Release the button The display will now read 0 4 The Timer Thermostat is now in WarmWelcome mode and will request the last 2 digits of your PIN code 5 Use the plus button and minus button to enter the correct number and wait approx 10s after you re finished 6 If the PIN code is correct WarmWelcome will be activated If the PIN code is incorrect WarmWelcome will not be activated The Timer Thermostat will now leave the WarmWelcome mode Attention Activating WarmWelcome has to be the last change to the Timer Thermostat If you touch the Timer Thermostat again WarmWelcome will be deactivated The functions of the ICY Timer Thermostat are best explained by using a realistic situation e g a recreational bungalow How the ICY Timer Thermostats work How it used to be With a conventional thermostat we often see that users keep the heating on 20 or 22 C day and night even when they are away for a day to go cycling or swim ming It is always better to come home to a warm bungalow or to wake up to a cosy room This is something they would not do at home and which costs the owner or manager of the accommodation a lot of money How it will be By using an ICY Timer Thermostat with presence detection it is no longer pos sible to keep the thermostat set to such a high temperature This results in a huge reduction in energy use The Comfort period With an ICY Timer Ther
3. 12 The display will now read t7 and after 2s the MINUTES of START COMFORT will appear e g 58 minutes You can change the value by repeating step 3 13 The display will now read t8 and after 2s the HOURS of REAL TIME will appear e g 7 o clock You can change the value by repeating step 3 14 The display will now read t9 and after 2s the MINUTES of REAL TIME will appear e g 45 minutes You can change the value by repeating step 3 15 The display will now read P1 and after 2s the first 2 digits of the pre programmed PIN code will appear e g 11 You can change the value by repeating step 3 16 The display will now read P2 and after 2s the second 2 digits of the pre programmed PIN code will appear e g 12 You can change the value by repeating step 3 The Timer Thermostat will then automatically store any changes in the memory and will beep and leave the programming mode ICY1830 35 40 45 50 Warm Welkom If a room is unused for a longer period of time the Timer Thermostat s energy saving function will cool the room down to the Anti Frost temperature e g 5 C If the room is being used again it may take several hours before it is back to a comfortable temperature If you e g would like your guests to arrive in a warm and cosy bungalow ensure the heating is switched on well in advance However the energy saving function of the ICY Timer Thermostat wil
4. consult the manual of your heater and connect the Timer Thermostat according to the sche matics above option 2 ICY1830 35 40 45 50 Programming guide Please read this guide thoroughly and write down all the values you need to fill in before starting programming ATTENTION The ICY1810 has already been pre programmed This programme cannot be altered If the buttons are not touched for approx 10s the Timer Thermostat will auto matically select the next function Terminology used in this guide COMFORT TEMPERATURE temperature maintained during the day and when user is present at night DORMANT TEMPERATURE temperature maintained at night and when user is absent ANTI FROST TEMPERATURE temperature maintained when the Timer Thermostat has not been used for a longer period of time e g 12 hours 1 Keep the left minus button pressed for 10s until the display reads P1 Release the button The display will now read 0 2 The Timer Thermostat is now in programming mode and will request the first 2 digits of your PIN code 3 Use the right plus button and left minus button to enter the correct number and wait approx 10s after you re finished 4 The display will now read P and after 2s it will read 0 The Timer Ther mostat will now request the second 2 digits of your PIN code Now repeat step 3 5 If the PIN code is correct continue with step 6 If the PIN code is incorrect the T
5. e free no wear and tear to contact points and other mov ing parts No separate power supply or battery necessary because of the advanced electronics used ICY1810 ICY1830 ICY 1835 ICY1840 ICY1845 ICY1850 Warm Welcome A A A A A Light sensor A A A A A Clock functions A A Wirelessly controllable o o o o A and programmable Presence detection by using Touch control A A A A A Motion detector A Key responder A A standard O optional The IN option The IN option makes it possible to control and program the ICY Timer Thermo stats remotely via radiotelegraphic communication The IN option is available for a surcharge and offers you the opportunity to activate and alter all the functions and settings from reception if using the ICY Net
6. e maintained until the thermostat is used again This means it is impossible that an empty bungalow is being unnecessarily heated This results in the third important saving Saving energy Results of tests and experiences from customers indicate that the reduction de pending on the application is between 20 and 55 Living comfort and the environment The experiences of several bungalow parks have shown that with the right pro gramming your guests will not experience any negative impact on their living comfort The effect is mostly the opposite Because people are becoming more and more environmentally conscious they experience this function as a positive contribution to a reduction in energy wastage and as a contribution towards a better environ ment The patent Because of their unique function the ICY Timer Thermostats cannot be compared to other electrical thermostats That is why our Timer Thermostat is patented What are the applications Bungalow parks holiday homes hotels congress centres apartment complexes student housing nursing homes schools office buildings community centres sports facilities Why use a Timer Thermostat e High energy saving approx 30 because unnecessary heating is pre vented e Very user friendly Highly reliable as a result of the touch controls and absence of moving parts and a relay Robust and stylish solid impact proof cover and modern design e Totally maintenanc
7. imer Thermostat will beep and leave the programming mode 6 The display will now read t1 and after 2s the pre programmed ANTI FROST TEMPERATURE will appear e g 14 C You can change the value by repeating step 3 7 The display will now read t and after 2s the pre programmed MAXIMUM COMFORT TEMPERATURE will appear e g 24 C You can change the value by repeating step 3 8 The display will now read t3 and after 2s the pre programmed COMFORT PERIOD will appear e g 12 x 10 minutes 2 hours You can change the value by repeating step 3 9 The display will now read t4 and after 2s the pre programmed DORMANT TEMPERATURE will appear e g 17 C You can change the value by repeating step 3 10 The display will now read t5 and after 2s the pre programmed DORMANT PERIOD will appear e g 12 hours You can change the value by repeat ing step 3 Continue with step 15 for the ICY1830 35 50 Timer Thermostat Continue with step 11 for the ICY1840 45 11 The display will now read t6 and after 2s the HOURS of START COM FORT will appear e g 10 o clock When the clock is not being used the display will now read You can change the value by repeating step 3 By using the minus button to go to the minimum the clock will be disabled When the clock is disabled continue with step 15 When the clock is enabled continue with step 12
8. l reactive the Dormant temperature after the Comfort period has elapsed which means the bungalow will only be heated until e g 15 C To ensure that in these situations the bungalow is heated until e g 20 C the Comfort period should be temporarily extended To make this possible ICY has developed WarmWelcome WarmWelcome will maintain the last set temperature until the Timer Ther mostat is operated again This makes it possible without changing any settings to maintain a certain temperature for a maximum of 2 days When your guests arrive someone will for whatever reason touch the Timer Thermostat WarmWelcome will automatically be deactivated and the Timer Ther mostat will resume its normal cycle WarmWelcome will be activated by entering the last 2 digits of your PIN code After entering the code the Timer Thermostat will not give any indication whether the PIN code was correct or incorrect This means it is not noticeable if WarmWel come is activated or not The only way to see this is when the Comfort period is maintained This means it is almost impossible for your guests to activate Warm Welcome as after every attempt they have to wait for an entire Comfort period to see whether it elapses which indicates whether the PIN code entered was correct or incorrect Activating WarmWelcome 1 Set the temperature to the setting you want WarmWelcome to maintain 2 Keep pressing the right hand button until after approx
9. mostat the user can set the desired temperature by sim ply pressing the buttons on the thermostat The maximum temperature can how ever be set by you e g 24 C This results in the first important saving After a certain period the Comfort period the Timer Thermostat will beep indi cating that the temperature will be lowered You can decide how long the Comfort period will last e g 2 hours This does not apply to the ICY1810 When the user is present the Timer Thermostat can be reactivated to start a new Comfort period In the case of the ICY1845 and the ICY1850 the user does not need to reactive the Timer Thermostat These two types detect the presence of users by means of a motion detector and a key responder respectively The Dormant period When no one is present the temperature will be reduced to the Dormant tempera ture set e g 15 C as soon as the Comfort period elapses The user will have to press the Timer Thermostat again to start a new Comfort period This results in the second important saving The Dormant temperature is maintained until the Dormant period has expired You can decide how long this Dormant period will last e g 12 hours The Anti Frost period When the Dormant period has elapsed and no one has reactivated the Timer Thermostat this usually means the bungalow is no longer in use The Timer Thermostat will now switch to the Anti Frost temperature e g 7 C The Anti Frost period will b

Download Pdf Manuals

image

Related Search

Related Contents

FabrikaFarkopov.RU +7 (495) 669-44-86    Drive Sit to Stand Setup - Integra Healthcare Equipment  「ミニマスター」取扱説明書  1290 Infinity II Evaporative Light Scattering Detector User Manual  AYUDA DE TIS - Workshop support guide  E-ConsentPro 2.1 Benutzerhandbuch WebClient  tüv rheinland immissionsschutz und energiesysteme  TELEVISOR A CORES MANUAL DE SERVIÇO  instruction book manual de instrucciones livret d`instructions  