Home
BMM Heaters Limited Compact HM Range Installation, Service and
Contents
1. Item Part No Fan amp Limit Stat JTL 13A or Honeywell Spark Electrode 10101 Ionization Probe 10201 Flue fan 10301 Gas Valve 10401 In shot burner 10501 Control box 10601 Relay 10701 Modulating Valve 10801 Burner tube 10901 Flue Fan Relay 11001 Terminal Guard 11002 Control Panel 11003 Further parts or alternative parts can be supplied by BMM Heaters Ltd BMM Heaters Ltd reserve the right to upgrade or alter spare part at there discretion All components can be purchased from BMM Heaters WARNING Only use parts recommended by BMM Heaters or other wise stated in this manual You must first contact BMM Heaters if you want to use alternative parts 33 Section 16 Troubleshooting Note Please refer to controller supplement supplied with this manual where more specific troubleshooting will be found Fault Cause Check Burner Lockout Burner fault Refer to burner check sector supplement finding lockout occurred chart on controls box Overheat trip Dirty filters low Filters supply supply air fan belts damper operations Burner held off No enable signal Check BMS Controls back via Tl amp T2 in heater interface panel Main fan runs Electrical Summer Winter continuously switch set to summer Manual Fan thermostat set to low Fault Fan Limit
2. national codes to perform the installation To install the heater in accordance with the Clearances to Combustibles of this heater To plan for the installation of supports flues and air intakes To provide access to burners for servicing To provide the owner with a copy of this installation commissioning operation and service To never use a heater To ensure that there with the requirements manual as a support for a ladder is sufficient ventilation in the area to comply of all relevant local and national codes Section 4 Technical HMA Technical Table 1 Data MODEL output ominal heat kW ee aac ea inimum heat Gas consumption Gas connection in inlet gas pressure ax inlet gas m pressure Burner Pressure njector Size mm umber of tubes Combustion air mm o ual Current burner amps g aximum air M3 sec volume inimum air flow M3 sec HMB Technical Table 2 MODEL Ti ominal heat cee ae A ominal heat eal inimum heat pee lee kW kW kW Gas consumption Gas connection bsp mbar mbar bar ax inlet gas pressure Burner Pressure in inlet gas pressure umber of tubes Combustion air mm inlet Current burner amps only et_weight aximum air M3 sec volume inimum air flow Calculations are worked out using the calorific value 10 7 kWh m 1007 mbar 15 C Each appliance has bee
3. BMM Heaters Limited Compact HM Range Installation Service and User Manual Indirect gas fired warm air heater type B22 C4 amp C5 Please read this document prior to the installation and servicing of this equipment Failure to follow these instructions can cause damage to property injury or death to person Work should only be carried out by suitable qualified personnel and Corgi registered BMM Heaters Limited 1 Copeland Court Forest Grove Middlesbrough TS2 1RN Tel 01642 240700 Fax 01642 240708 Email sales bmmheaters co uk Web www bmmheaters co uk CONTENTS PAGE Contents Section 1 Introduction esssssesssecccseeccsseccsseccsseccssesesse 3 Section 2 Health amp Safety s sescseeccseeccsseccsseccssecesse 4 Section 3 Installers Responsibilitie 5 Section 4 Technical Datar usssissisicisosiiiiisis 6 Section 5 Heater Installation we ecessseseees 7 SECCLON 6 ALL SUPPLY on ccecsssscsssseccsseccseeccssecssenscseesees 9 Section 7 Overheat Protection sssssseccseeccseccce 10 Section 8 Flue System amp Ventilation 11 Section 9 Gas Pipe WOLK ssssccseecoseecoseecossecosescossseee 14 Section 10 Condensate Drains essssescseecosecceseseee 15 Section 11 Electrical Connections 15 Section 12 Commissioning ssessseeccsseccssecossecossscossseee 18 S ction 13 Servicing zsssseisrsossscisoscssecsresscesss
4. Once satisfied th commission engineer must seal the overheat device otroaoodaa o All gas nipples are to be replaced and checked for tightness and checked with leak detection fluid 23 A leak detection test is to be done with leak detection fluid and electronic leak detector on the gas train while the burner is running to see if there are any leaks in the burner gas train and a soundness test is to be done on all gas work Finally make a full record of combustion data on commissioning sheet provided a copy is to be presented to the customer and to BMM Heaters on completion of work The commissioning sheet should include the following a Model and serial numbers b Heater running temperature and over heat settings c Full thermal input d Governor pressure settings pilot for start gas and main for full e Gas flow rates for full fire Burner damper setting and pressure switch settings g Flame signal strength on full fire h Exhaust gas 07 CO CO and temperature 19 After setting all air pressure switches and valves etc you must mark the position or lock off if possible Please note BMM Heaters provide a full commissioning service if required Also if you require further information call BMM Heaters technical department TYPICAL FLUE GAS READINGS Q 5 ol ct O OY ol CO 9 5 to 8 8 CO up to 100 PPM Typical
5. heat exchanger to prevent damage to the heat exchanger If you require any further information or you have any special requirements please contact our technical department WARNING Electrical Shock Hazard Use extreme caution while working on this appliance Failure to follow these instructions can result in death or electric shock Only competent engineers should carry out work on this appliance Section 12 Commissioning COMMISSIONING MUST BE CARRIED OUT BY A COMPETENT REGISTERED ENGINEER CORGI ALSO TO BE USED WITH BURNER COMMISSIONING DETAIL SEE BURNER INSERT Operating amp Safety Instructions This Heater does not have a pilot It is equipped with a direct spark ignition device that automatically lights the gas burner DO NOT try to light burners by hand 2 BEFORE OPERATING leak test all gas piping up to heater gas valve Smell around the unit area for gas DO NOT attempt to place heater in operation until source of gas leak is identified and corrected 3 Do not attempt to operate unit if there is indication that any part or control has been under water Any control or component that has been under water must be replaced prior to trying to start the unit Start up 1 Turn thermostat or temperature controller to its lowest setting 2 Turn off gas supply at the manual shut off valve 3 Turn off power to the unit at the disconnect switch 4 Remove access panel or open door
6. Filters must be fireproof if fitted and a motor shield is required over the main supply fan motor if directly in front of the heater When installing the heater minimum clearance is required around the heater If the heater is to be fitted at a height then the structure of the gantry must be capable of the heaters weight which can be found in section 4 table 1 2 also a safe working platform and access must be allowed for to enable easy and safe working access Note The front of the heater is the side on which the burner is fastened When designing a system allowance must be made so equipment can be serviced after installation and for the fitting of any spares which may be required The BMG is designed to be installed within an Air Handling Unit or ductwork The appliance is designed to work in a maximum ambient temperature of 40 c The Air Heaters are mounted direct on the floor and do not need any fixing The base on which the heater is positioned should not be less than 150mm 6 inches thick and must be constructed of non combustible material Any combustible material adjacent to the heater and the flue system must be placed or shielded as to ensure that its temperature does not exceed 65 C WARNING No air heater shall be installed where there is a foreseeable risk of flammable particles gases vapours or corrosion inducing gases or vapours being drawn into either the heated air stream or th
7. can be found in Section 4 table 1 2 The maximum flue length of C appliances is 12 metres in total amp the maximum flue length for a B appliance is 12 metres Note 1 x 90 Elbow 1metre length and 1 x 45 bend 500mm length All flue pipes must be sealed Using seamless aluminum or stainless flue pipe as supplied by BMM Heaters Ltd or equivalent Pleas nsure that the manufacturer s instructions are followed B Type Appliance If the air heater is a B Type appliance then the air for combustion will be taken from either the room or outside via combustion air grills fitted on the burner compartment The installer must make sure there is adequate ventilation and that it complies with BS6230 amp BS5440 plus any other relevant regulation amp fire regulation All joints must be sealed to prevent products of combustion from entering the building If the flue is to pass through a combustible part of a building then the flue pipe will require a non combustible sleeve with an air gap of at least 20mm The flue must be installed at least 150mm away from any combustible material The temperature of any combustible material must not exceed 65 C when the heater is in operation When maximum flue runs are unavoidable or when the flue is subjected to cold air and condensation is unavoidable then provisions must be made to remove condensation at a point to which it can be directed into a drain o
8. stat Main fan Fails toJ Electrical Fan Motor faulty run Fan Limit stat faulty Contactor faulty Motor on overload 34 Section 17 Users Instructions Servicing installation and commissioning must only be carried out by a competent person This appliance requires servicing at least an annual service The outside of this cabinet can be clean using polish or a damp cloth products which are high corrosive when in contact with metal should be used WARNING If you smell gas 1 Open all windows and door 2 DO NOT try to light any appliance 3 DO NOT use electrical switches 4 DO NOT use any telephone in your building 5 Leave the building 6 Immediately call your local gas supplier after leaving the building follow the gas supplier s instructions 7 If you cannot reach your gas supplier call the fire department USERS INSTRUCTIONS Once the controls have been fully installed and proved with the Heater all interlocks proved etc the supply air has been balanced and only when the Heater has been fully commissioned by a qualified registered engineer Corgi you are now able to use your Heater safely Easy Lighting and Shutting Off Instructions Burner Start up Ls Ensure Burner and Heater On Off Switch is on 2 Fan switch is in auto position If the heater is controlled via a BMS then the supply fan should be running before the burner can sta
9. approx 1 PPM Flue Stack Temperature Up to 250 c Nett 24 Burner Flames Prior to completing the start up check the appearance of the main burner flame See Figures below for flame Characteristics of properly adjusted Natural gas systems Burner Flame Start up 3 Mbar Manifold Burner Flame High Fire 8 75 Mbar Manifold Pressure Draft Inducer High Speed Pressure Draft Inducer High Speed Figure 6A Figure 6B 1 The burner flame should be predominately blue in color and well defined and centered at the tube entry as shown in Figures above Distorted flame or yellow tipping of natural gas flame may be caused by lint and dirt accumulation inside burner or at burner ports at air inlet between burner and manifold pipe or debris in the main burner orifice Soft brush or vacuum clean affected areas Poorly defined substantially yellow flames or flames that appear lazy indicate poor air supply to burners or excessive burner input Verify gas supply type and manifold pressure with rating plate Poor air supply can be caused by obstructions or blockage in heat exchanger tubes or vent discharge pipe Inspect and clean as necessary by to eliminate blockage Vacuum any dirt or loose debris Clean heat exchanger tubes with stiff brush Poor flame characteristics can also be caused by undersized combustion air openings or flue gas recirculation into combustion air supply Increase air opening size or re direct flue pr
10. be used with most Building Management Systems However BMM Heaters can supply a control panel which includes a thermostat timeclock and frost protection The Instruction and product information will be supplied with the control unit if you require a control panel please contact BMM Heaters and quote the part number On Off Burner The heater interface panel connections 1 240v amp N supply 2 T1 amp T2 is the enable Tl amp T2 must break when up to the temperature required All interlocks to be wired in series with Tl amp T2 The burner must be interlocked with the supply fan 3s T3 Lockout 240v Please note The supply fans require a 10min overrun after burner shutdown to cool the heat exchanger to prevent damage to the heat exchanger If you require any further information or you have any special requirements please contact our technical department Modulating Burner The heater interface panel connections 1 240v amp N supply 2 T1 amp T2 is the enable Tl amp T2 must break when up to the temperature required All interlocks to be wired in series with Tl amp T2 The burner must be interlocked with the supply fan 3 T3 Lockout 240v 4 Modulating valve terminal 1 Ov 5 Modulating valve terminal 2 24vac 6 Modulating valve terminal 5 10vdc Please note 17 The supply fans require a 10min overrun after burner shutdown to cool the
11. d 0 10v DC is required as standard on Modulating heaters All wiring and control cables must be ran in conduit and correct size glands used etc All appliances must be earthed Each heater manufacture is individually made to suit the customer so a dedicated circuit will be attached to this manual BMM Heaters will also attach a circuit within the interface panel 15 Table 3 Electrical Data Model Motor Motor Motor Motor Burner size size rated rated Voltage Three Single supply supply phase phase fuse fuse Three Single phase Phase 35 N a 500 w N a 5 Amps 240v 1ph 50Hz 45 500w 500 w 10 Amps 5 Amps 240v 1ph 50Hz 60 750w 1 1kW 10 Amps 10 Amps 240v 1ph 50Hz 70 750w 1 1 kW 10 Amps 10 Amps 240v 1ph 50Hz 85 750w 1 1 kW 10 Amps 10 Amps 240v 1ph 50Hz 95 1 1 kW N a 10 Amps 10 Amps 240v 1ph 50Hz Controls BMM Heaters can supply controls for these heaters upon request Please confirm with us the type of controls prior to connecting to check compatibility Note All heaters have been electrically tested at BMM Heaters factory This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety 16 Section 13 Heater Controls The heater can
12. d Connection The following considerations are to be taken into account a A union and gas ball valve must be fitted to the inlet connection on the heater so that the heater can be isolated or removed without having to isolated the whole gas supply to the building b Pipe work smaller than the inlet gas connection should not be used c The gas supply pipe is adequately sized to carry correct volume of gas from the gas meter to the heater s d The heat input and gas flow rates for each heater can be found in section 4 table 1 2 3 and 4 to aid in the design of gas supply pipe work e All gas pipe work and electrical connections must b adequately supported and must not support any of the heaters weight or rely on the strength of the burner gas pipe work f Unless the heater is suspended or movement is apparent the BMM Heater must be connected with medium heavy or copper pipe otherwise the use of an approved flexible connection between the isolating valve and the heater can be used We recommend that the flexi hose is one size bigger than the heater connection to reduce any pressure loss The minimum inlet gas pressure for natural gas should be 20 mbar Please note We require a minimum of 17 5mbar at the inlet when running and a maximum of 75mbar if this is exceeded then an external to the appliance governor must be fitted Important The complete installation must be purged and tested for gas sou
13. e air for combustion In such cases installation may only proceed if the air to be heated and the air for combustion are ducted to the heater from an uncontaminated source preferably outside the building If this heater is to be suspended then the weight in table 1 2 in section 4 must be taken into account Section 6 Air Supply Ductwork All delivery and return air ducts including air filters jointing and any insulation or lining must be constructed entirely of materials which will not contribute to a fire are of adequate strength and dimensionally stable for the maximum internal and external temperatures to which they are to be exposed during commissioning and normal operation In the selection of materials account must be taken of the working environment and the air temperatures which will result when the overheat limit thermostat is being commissioned Where inter joint spaces are used as duct routes they should be suitably lined with fire resisting material A full and unobstructed return air path to the air heater must be provided If the air heater is to be installed in a plant room the return air and warm air discharge arrangements must be such as to avoid interference with the operation of the flue by the air circulation fan The return air intake and the warm air outlet s should therefore be fully ducted in the plant room to and from the heater respective
14. ean and check for corrosion e Brush any deposits from all of the flue ways using a brush Also brush down the heat exchanger tubes e Remove any soot from the heat exchanger with a vacuum cleaner e Inspect soundness of combustion chamber heat exchanger 26 e Replace all items in reverse order e Once servicing is complete the heater must be re commissioned Note Regarding External Heaters If the heater is housed within an Air Handling Unit there will be sufficient room to allow servicing Servicing as per our standard internal procedures Please note in extreme weather conditions always ensure any electrical connections etc are protected and do not allow water onto them If stand alone external heater there will be a door which is hinged up over to allow protection to the engineer from weather conditions Wet Conditions If it is found that the area in which the heater is installed has become wet flooded the heater must be electrically isolated immediately and an investigation to find out if any water has penetrated into the heater controls If so ensure they are dried out properly before re installing the electric supply 27 Burner Maintenance The in shot gas burners require inspecting and cleaning on an annual basis we also recommend that the injectors are checked at the same tim Only suitable cleaning agents can be used to clean this prod
15. ights easily and reliable at minimum pressure e Mount cap and O ring and reconnect pressure feedback connection if applicable Checkout After any adjustment set appliance in operation and observe through a complete cycl to ensure that burner system components function correctly Once set this unit requires sealing 21 The flame signal strength must be checked as below 1 A quality Volt Ohm Amp Meter with a scale capable of reading microamperes is required Typically meters with only milliamp scales cannot provide necessary reading sensitivity Digital VOAM with DC Set meter to read lowest DC microamp scale Microampere scale 2 Disconnect flame sensor lead from flame sensor on burner tray Test leads need to be connected in series 3 Connect Red test lead between A amp on meter and flame sensor lead terminal Connect the Black test lead to COM connection on meter and to flame sensor tab 22 Digital VOAM with DC Microampere scale Set meter to read lowest DC micro amp scale 4 Initiate operating cycle When burners ignite flame signal in micro amps will register on meter readout Flame signal should be greater than 1 0 micro amp Flame rod should straight and located 22mm in front of the burner face as received from the factory No adjustment of flame rod position should be made unless it has been bent during handling 5 A reading between 5 and 1 0 micro amp is
16. ir the use of any other object ie drill bit etc could widen the injector causing the unit to over fire and could cause damage to the heater or to person The limit control provides protection for the heater should the temperature rise above a safe level If an overheat condition occurs the limit control will shut down the burner and hold it off until the manual reset button is pressed NOTE If the limit requires re setting more than once after first re set then a competent engineer must be called to investigate further Fan setting 35 c ON If required 25 c OFF High Limit 20 c above normal running temperature no greater than 100 c Important When integrated with building management system the fan will be operated via their controls and all interlocks must be fitted to ensure the burner cannot start until the supply fan is running On burner shutdown the supply fan overrun will continue running for 10 15 minutes to dissipate residual heat WARNING If cracks have been found on the heat exchanger tube the heat exchanger must be replaced before putting the unit back on line Supply Fan Assembly Inspect the fan blades to see they are not damaged and that there is no excessive building up of deposits that could give an imbalance via access panel on the side of the heater If necessary clean the fan blades The main fan bearings ar permanently sealed and do not
17. lly resetting If this happens on a regular basis it must be investigated by a competent registered ngineer as this could cause serious damage to the heater The over heat is set 20 c above the running temperature after 30 minutes If the heater is supplied without a fan in module form then the fan stat on the L4064 will have to be wired by others Otherwise BMM Heaters will wire the fan control please s dedicated wiring diagram supplied with this heater WARNING If the heater has a Honeywell combined thermostat installed then the jumper link must be removed from the replacement thermostat Heat exchanger damage may be the result Failure to follow these instructions can result in death injury property damage or product damage Once the overheat is set to the correct operating temperature the commission engineer must seal the overheat stat Ensure that the fan and limit settings are as follows Fan On 39 C Fan Off 25 C Limit 20 c above normal running temperature no greater than 100 c 10 Section 8 Flue System amp Ventilation Always ensure that adequate combustion air is provided to suit the total installation of all combustion equipment in accordance with BS6230 or BS5440 The ventilation rates for B Type appliances can be found on page 13 im this manual Flue pipe runs may be horizontal or vertical and terminate either through the wall or roof The flue dia
18. ly The openings in the structure of the plant room through which the ducting passes must be fire stopped In addition where there is a risk of combustible material being placed close to the warm air outlets suitable barrier rails should be provided to prevent any combustible material being within 900mm 3 ft of the outlets Airflow It is essential that the correct amount of air is provided through the heater and should be evenly distributed when entering the heater All pressure calculations resistances for air are ambient with the heater in the off position Adjustable by pass plates HM Compact models fitted into larger cabinets for internal or external use should be fitted with adjustable air balancing plates or a simple restriction damper If the work is not going to be carried out by BMM Heaters Ltd then we recommend that the installer ensures that it can be altered to give guaranteed minimum equal air over the heat exchanger See Minimum and Maximum air flow volumes in section 4 table 1 2 Section 7 Overheat Protection Device Overheat protection is fitted in case the air flow falls below the minimum necessary for safe operation of the heater which may be caused by failure of the supply fan motor or belt failure dirty filters or inlet damper failure If the air flow falls too low the high limit will trip out and will require manua
19. marginal for the operating control If flame sensor is immersed in burner flame and a marginal signal is obtained a poor ground connection is indicated Identify cause of poor ground and correct 6 If the flame rod is not in contact with the burner flame check that burners are secured properly to bracket Then check gas pressure at start up gas manifold pressure should be 3mbar If manifold pressure is correct check for partial blockage in gas orifice or flame holder of sensor burner Clean and replace as necessary 7 If start up is satisfactory and low flame signals are obtained during operating cycle check as follows a If draft inducer is operating at high speed 2800 rpm or higher gas manifold pressure must be 3mbar to 8 75mbar Typical flame current readings are greater than 1 0 micro amp for HM burners Note The flame sensor is not a thermal device and therefore its temperature does not directly affect the flame signal reading The flame sensor does not have to glow to produce a suitable flame signal After running the unit for a period of on hour you will be able to get a runnin temperature from the fan limit side of th stat When you have this you must set the over heat to 20 c above th running temperature The supply fans should be shut down once when th burner is running to try the overheat protection device and the fans mus be switched on as soon as it locks out on over heat
20. mbustion air aoa Combustion air C type 4 amp 5 suitable for indoor and outdoor if fitted outside this unit must be installed within an AHU B Type appliance has high and low level gills installed on the front panel this appliance is suitable for outdoor installation Section 2 Heater Safety The Installation of this appliance must be done by a registered installer contractor suitably qualified in the installation and service of gas fired heating equipment WARNING Improper installation adjustment alteration service or maintenance can result in death injury or property damage Read the installation operation and service manual thoroughly before installing or servicing this appliance Note To Installer Please take the time to read and understand theses instructions prior to any work servicing or installing this appliance Installers must leave a copy of this manual with the end user owner To Owner This manual must be kept in a safe place in order to provide necessary information for service engineers at a later date Section 3 Installers Responsibilities To install the heater as well as the gas and electrical supplies in accordance with applicable specifications and codes BMM Heaters recommends the installer contact a local Building Inspector Fire Officer or Insurance Company for guidance To use the information given in the manual together with the local and
21. mer ventilation switch on off switch to off and set fan switch from auto to manual Cleaning Of Heater The heater can b cleaned xternally using a damp cloth with a light detergent Please note this is on the outer panel only away from all of the electrics No substance can be used that will cause harm to the surface of the metal or remove paint etc Please Note You must not use water on unpainted galvanized finished surfaces Section 14 Removal and Replacement Parts Honeywell gas valve Ts Isolate electric and gas Qa Remove Din Plugs by using a terminal screwdriver to undo locking screw 30 3s 4 Undo valve flanges with Phillips screw driver Lift out valve assembly Replace and re assemble in reverse order taking care that the O rings are in position 5 Check for gas soundness and re commission heater Fan and limit stat hes Isolate electric supply 2 Remove outer casing and disconnect wires The wires are held in by spring terminals which will release by pushing a small screwdriver into the slot next to the wiring termination 3 Remove fixing screws which secure stat to front of panel carefully withdraw stat from heater and remove casing 4 Re assemble in reverse order and check settings adjust if required to fan on 35 fan off 25 high limit 90 Supply Fan he Isolate electric supply 2 Remove front lower access panel ou To
22. n range rated burner pressures can be found on the burner pressure once commissioned must be entered in the actual 2 87 6 the data plate and Section 5 Heater Installation This appliance must be installed in accordance with the rules in force Before installation check that the local distribution conditions nature of gas and pressure and to make sure the appliance is compatible When the heater is installed within Great Britain the whole installation must comply with the requirements and recommendations of BS 6230 2005 Installation of gas fired forced convection air heaters for commercial and industrial space heating The air heater must be installed in accordance with the rules in force and the relevant requirements of any fire regulations or insurance company s requirements appertaining to the area in which the heater is located particularly where special risks are involved such as areas where petrol vehicles are housed where cellulose spraying is carried out in wood working departments etc Clearances and Positioning The following clearances for installation and servicing must be observed To the Front Equal to the depth of the heater To the Rear 1 Metre To at least one side 1 Metre Above the heater 1 Metre Clearances A minimum of 500mm upstream and downstream must be allowed for due to the radiant heat
23. nd Definitions Indirect Fired The term Indirect Fired indicates that the products of combustion are kept isolated from the main supply air stream The burner fires into a combustion chamber the resultant products of combustion are directed into a heat exchanger and from there to an external flue which discharges into the atmosphere Factory Test All heaters produced by BMM Heaters Ltd will be subjected to various tests before they are dispatched Each heater is individual so the data will differ between each unit The relevant data can be found on the data plate attached to the heater External Heaters The construction of the unit will consist of double skin panels and be fully water proof the burner compartment will be adequately ventilated via two combustion air grills Burner Types BMM Heaters Ltd will use a series of in shot gas fired burner in multiple forms depending on output required This burner will be either on off high low or modulating control Fuel Type HM Compact Range are designed to work on G20 I2H Natural gas however if this gas is unavailable please contact us Flue Type The HM Compact Range heater is approved for the following flue type e Type C4 amp C5 Horizontal and Vertical flue Two piped e Type B22 Vertical or horizontal flue for combustion air vents Single piped C amp B type appliance Internal amp External installed AS sa Co
24. ndness in accordance with local national codes and a registered engineer The gas connection sizes can be found in section 4 Table 1 2 14 Section 10 Condensate Drains When maximum flue runs are unavoidable or when the flue is subjected to cold air and condensation is unavoidable then provisions must be made to remove condensation at a point to which it can be directed into a drain or gully Note The condensate drain must be connected in Non corrodible material not less than 20mm diameter WARNING Do not use plastic connections as the temperature may be high at the outlet to the drain Copper pipe must not be used Important Condensing heaters may be subject to local regulations with respect to the discharge of condensate Section 11 Electrical Connections All external wiring must be in accordance with current IEE Regulations and local regulation which apply The method of connection to the mains electricity supply should allow complete electrical isolation of the heater and the supply should serve th heater only The mains isolator should be provided adjacent to the heater in an easily accessible position The isolator must have contact separation of at least 3 mm on all poles The electric and controls terminations are located on the front of the Heater housed in an interface panel All heaters are compatible for inter facing with building management systems an
25. ng to have permanent air vents communicating directly with the outside air at a high level and at a low level Where communication with the outside air is possible only by means of high level air vents ducting down to floor level for the lower vent s should be used Air vents should have negligible resistance and must not be sited in any position where they are likely to be easily blocked or flooded or in any position adjacent to an extraction system which is carrying flammable vapour Grilles or louvers should be designed so that high velocity air streams do not occur within the plant room The ventilation should be installed to in accordance with local and national codes Ventilation Requirements The space in which the heater is situated must be adequately ventilated see below for the minimum ventilation area at low and high levels Low Level 540cm plus 4 5cm per kW after 60kw High Level 270cm plus 2 25cm per kW after 60kw 13 Ventilation for C Type Flue Appliances No additional combustion air is required however previsions for ventilation to cool the plant room may be required Section 9 Gas Piping All Gas Pipe work to the appliance should be installed in accordance with current regulations local and national codes and must be connected with an acceptable gas isolation valve and union so that the burner maybe removed to aid servicing and inspection of the burner Size an
26. ning for ten minutes e For 2 stage and modulating control systems manifold pressure should be 3 mbar low fire Adjust Lo Regulator on 2 stage gas valve if necessary After that the burner high fire manifold pressure should increase to 8 75 mbar e For On Off units the manifold pressure should be 8 75 mbar The burner pressure is adjusted by turning the multi block governor in either a clockwise rotation to increas th pressur or in an anti clockwise rotation to decrease the pressure Once the pressure has been set it must be sealed with the use of paint or temper sealant 19 Gas pressure ajustment governor iy eet gt He iN VY a ON_LG eoe E 2 0 cad DOP Setting the Modureg Cap Adjustment Screw 7mm for minimum Pressure setting Adjustment Screw 9mm for maximum Pressure setting 6 3 mm AMP Terminals M5 pressure feedback connection if used O Ring x 2 l Be T r lt q 4 4 H Goa Adjustment checkout and maintenance Important Adjustments should be made by qualified persons only Allow time for pressure to stabilize before making adjustments It is recommended that the Modureg is operated a few times to ensure correct setting Take care that after any adjustment cap and o ring are mounted The maximum pressure setting must first be adjusted because any adjustment of maximum pressure setting infl
27. oducts to prevent re circulation Reduced air delivery can also be the result of fan blade slippage dirt accumulation the fan blade or low voltage to draft inducer motor Inspect draft fan assembly and be sure fan blade is secure to motor shaft Check line voltage to heater 25 Section 13 Servicing INSTRUCTION FOR THE SERVICING OF THE HM RANGE PLEASE NOTE SERVICING MUST ONLY BE CARRIED OUT BY A COMPETENT REGISTERED ENGINEER CORGI BEFORE CARRYING OUT ANY WORK ON THE UNIT SEE THAT THE ISOLATING SWITCH IS IN THE OFF POSITION AND THE GAS SUPPLY IS SHUT OFF BMM HEATERS ONLY RECOMMEND THE USE OF PARTS SUPPLIED OR RECOMMENDED BY OURSELVES INFORMATION IS FOR GUIDANCE OF QUALIFIED SERVICE ENGINEERS ONLY Note We recommend that the Heater is fully serviced every year and re commissioned If the flue gas passages in the heat exchanger the combustion chamber or flue fan are blocked the Heater can overheat causing the unit to shut down on the overheat thermostat To clean the Heat exchanger a The burner assembly Burner Removal With gas and electrical supply isolated e Disconnect the electrical supply to the burner e Disconnect gas valve plugs e Unscrew gas union assembly at inlet to gas train and remove gas train assembly e Remove fixing screws holding burner to heater front and lift away burners e Fully service burner and replace electrodes if required e The flue fan must be cl
28. ous damage to the heater Simple Fault Finding burner faults If the burner fails to ignition for any reason it will go to lockout This will be indicated by the red light on the heater if fitted or digitally shown on a display screen Remove power from heater or remot reset call a registered engineer if this does not rectify the problem Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected WARNING Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance Some objects will catch fire or explode when placed close to the heater Failure to follow these instructions can result in death injury or property damage 36 37
29. r gully Note The condensate drain must be connected in Non corrodible material not less than 20mm diameter Copper must not be used for condensate drains 11 B Type Appliances Roof Terminated B Type Appliance B Type Appliance Wall Terminated C Type Appliances Roof Terminated C Type Appliance C Type Appliance Roof Terminated C Type Appliance Wall Terminated 12 On both B amp C type flues a terminal guard must be fitted over the terminal if the wall terminal is below 1 8 metres from floor level and the fresh air intake must be at least 500mm from floor level A terminal Guard can be provided by BMM Heaters if required please contact our sales office for a price and availability When installing as a C5 Type appliances the ducts must not be fitted on opposite wall and must be fitted on either the same wall or a walls at right angles to each other C Type flues the distance between the exhaust terminal and fresh air terminals must be at least 700mm apart If a common flue system is used the minimum size required is 200mm and the size will increase prorata to the size of the heater flue Note The fresh air duct and exhaust duct must be the same size and must not exceed the maximum flue runs allowed Ventilation for B Type Flued appliances Where the heater is to be installed in a plant room the heater requires the plant room housi
30. remove fan belt slacken both adjustment bolts on motor plate by turning anti clockwise 4 Remove rear panels opposite side to burner Dis Undo x 4 bolts and remove shelf assembly 6 Undo x 4 bolts on the fan assembly and then the fan can be withdrawn 7 Re assemble as reverse Main Supply fan La 2 3 Isolate electric supply Remove front lower access panel To remove fan belt slacken both adjustment bolts on motor plate by turning anti clockwise 4 5 J Disconnect fan motor electrics Remove motor on motor plate and undo x 4 bolts Note you will require x 4 locking nuts on replacement Re assemble in reverse order Re tighten the supply fan belt until 12mm movement is obtained Check fan rotation is correct 31 Ignition Probe HM Series Spark Igniter Location amp Spark Gap Setting Care should be taken if igniter gap needs to be adjusted to avoid cracking the ceramic sleeve around the high voltage electrode Always adjust gap by bending the ground rod 3mm 0 75mm Igniter in burner housing Recommend Tools to be used a b c d e f g h Spanner 10mm 13mm and 17mm Screwdriver Terminal medium flat blade and Phillips medium Stillsons 14 and 18 Allen keys standard metric set 1 5mm 10mm Side cutters pliers Multi meter Manometer Flue brush for exchanger tubes 32 Section 15 Spare Parts Spares List
31. require lubrication Check belts for signs of wear and replace if required Gas control valves maintenance 29 No regular maintenance is required on thes devices Please refer to section 16 for removal or replacement of parts WARNING Replace faulty gas valve with genuine BMM Heater replacement part failure to do so could result in death injury and damage to property Note Check all gas pipes and joints to ensure there are no cracks or gas leaks Any cracks in the pipe work or joint must be repaired Fan control The burner should start its safety sequenc and then fire up When the heater achieves 35 c the supply fan will cut in and your heater is up and running When the space is up to temperature the burner will stop and the supply fans will run on until the fan control reaches 25 c and then the supply fan will shut down The heater will then switch on and off as required via the day thermostat and time clock If your heater fails to start check burner lockout and high limit resets as referred to in fault findings if any further investigation is required or the heater repeatedly locks out then a Corgi registered engineer must be called to investigate further Please Note You must not electrically isolat th heater when in full fire always wait until the burner stops and the supply fan over runs to dissipate the heat befor lectrically isolating For sum
32. rt Sis Make sure the time clock and thermostats are calling for heat or that the BMS is giving enable signal to terminals 1 amp 2 in our interface panel Burner Shut down T Ensure Burner and Heater On Off Switch is off Ze Fan switch is in auto position 35 3s The fans should run on for at least 10 min or till the fan limit is below 25 c to cool heat exchanger Make sure the time clock and thermostats are not calling for heat or that the BMS is not giving enable signal to terminals 1 amp 2 in our interface panel WARNING In Emergency only Use electrical isolator and the gas isolation valve to isolate the appliance Do not use electrical isolator to switch this appliance off in normal use as the fan is required to run on to cool the heat exchanger failure to do so will cause damage to this appliance Simple Fault Finding Some possible reasons for the heater not operating are Gas supply not turned ON Electrical Supply not turned ON The time and or Thermostats may not be ON The Limit stat may have operated due to an interruption of electrical supply or fault with the distribution fan i w M H WARNING If the limit thermostats persistently operate there is a fault which must be investigated by a qualified engineer registered with corgi This Heater should not be electrically isolated during normal operation doing so without a fan run on for 10 min will cause seri
33. scessusssssosisesss 25 Section 14 Removal and Replacement Parts 29 Section 15 Spat Essenin 32 Section 16 Troubleshooting scence 33 Section 17 Users Instruction 34 Model Serial No This manual is compatible for On Off Modulating and High Low these can be differentiated by the last letter in the model reference Modulating units will end in a M and High Low units in HL for example e HMA M is a modulating unit e HMA HL is a two stage high low e HMA is the On Off model Section 1 Introduction The instructions refer to appliances designed to operate in the UK and Ireland Appliances designed for other countries can be provided on request This appliance must be installed in accordance with the local and national codes in force and used only in a sufficiently ventilated space as specified in these instructions Before installation check that the local gas distribution systems nature of gas and pressure and adjustment of the appliance are compatible When installed within the United Kingdom the total installation must comply with the recommendations and requirements of the British Standard BS 6230 2005 Specification for the installation of gas fired forced convection air heaters for commercial and industrial space heating 2 and 3 family gases This appliance is suitable for outside installation if installation within a weather proof enclosure Terms a
34. to unit vestibule housing the gas heater 5 Check the inlet pressure is a 20mbar and carry out a tightness test on the gas pipe work once test is completed carry on with commissioning 6 Open all manual gas valves 7 Turn power on 18 8 Set thermostat or controller to its highest position to initiate call for heat and maintain operation of unit 9 Draft inducer will run for a 15 to 30 second pre purge period See Sequence of Operation provided 10 At the end of the pre purge the direct spark will be energized and gas valve will open 11 Burners ignite e Failure to Ignite 1 On the initial start up or after unit has been off long periods of time the first ignition trial may be unsuccessful due to need to purge air from manifold at start up 2 If ignition does not occur on the first trial the gas and spark are shut off by the ignition control and the control enters an inter purge period of 15 to 90 seconds during which the draft inducer continues to run 3 At the end of the inter purge period another trial for ignition will be initiated 4 Control will initiate up to three ignition trials on a call for heat before lockout of control occurs 5 Control can be brought out of lockout by turning thermostat or controller to its lowest position and waiting Check amp Adjust Manifold Pressure The burner pressure should be taken after the burner has been run
35. uct flammable liquids i e thinner must not be used to clean this equipment Polish and standard cleaning agent from your local heating parts center can be used Servicing Heat Exchanger Heat Exchanger of multi tube construction once the burner has been removed the heat exchanger tubes can be cleaned and inspected Flue Fan The flue fan impeller must be cleaned and check for corrosion on a regular annual basis Recommended intervals Weekly check Check that there are no apparent leaks Clean air filters if fitted if of the washable type or replace where necessary Quarterly check As weekly check and also Check the tension of the main fan belt s Check the flue for condensation Remove the Burner Inner Assembly clean and replace Annual Inspection Clean heat exchanger surface and inspect heat exchanger Clean and inspect flue fan Inspect and align fan and motor pulleys Check the tightness of the motor bolts Adjust fan belts for tension Inspect and adjust electrical connections Check all wiring and tube connections Remove the burner inner assembly clean and replace The modureg must be checked annually if fitted Start the Heater and check CO readings stack temperature efficiency and CO level Check the combustion air supply and check the smoke reading Overheat Limit control 28 Note The injectors in this appliance can only be clean with compressed a
36. uences minimum pressure setting Adjusting maximum pressure setting see fig 1 e Disconnect pressure feedback connection if applicable 20 Adjust Connect a tap of gas point must suitable pressure gauge to pipe line or to outlet pressur control concerned to measure burner pressure measuring be as near to burner as possible Energize modulating coil operator set control in operation and wait until an outlet pressure is recorded on pressure gauge Turn the maximum rate adjustment screw clockwise for increasing or counter cl adjustment ockwise for decreasing the maximum pressure setting if is needed Check minimum pressure setting and readjust if necessary Mount cap applicable Disconnect Connect a tap of gas point must Disconnect and O ring and reconnect pressure feedback connection if ting minimum pressure setting see fig 1 pressure feedback connection if applicable suitable pressure gauge to pipe line or to outlet pressur control concerned to measure burner pressure measuring be as near to burner as possible electrical connection of Modureg Energize operator set control in operation and wait until an outlet pressure i s recorded on pressure gauge Turn the minimum rate adjustment screw clockwise for increasing or counter clockwise for decreasing the minimum pressure setting if adjustment is needed Check if main burner l
Download Pdf Manuals
Related Search
Related Contents
Philips Wireless Headphone SHC1300 E 7110 / 116.527 E 10110 / 116.530 E 5230 Epson EB-1935 Diezel User Manual for the Herbert Amplifier STANDARD CRANE SCALE OPERATION & SERVICE MANUAL n°268 de décembre - Chambre de métiers et de l`artisanat de Samsung DV80F5E5HGW 8kg Front Load Dryer DATA SHEET () La revue de presse Copyright © All rights reserved.
Failed to retrieve file