Operating Instructions - Process pressure transmitter IPT
Contents
1. Display VE T Basic adjustment 2 Display Diagnostics Service Info Displayed value 2 1 Pressure V Displayed value V 2 1 Display unit 2 2 Scaling 2 3 0 0 0 Scaled Volume V lv 100 100 0 Lighting 2 4 C 28 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 6 Set up with the indicating and adjustment module wikal Diagnostics Display gt Diagnostics Service Info Basic adjustment 3 Pointer 3 1 p min 5 8 mbar p max 167 5 mbar T min 12 5 C T max 85 5 C Sensor status OK 3 2 Trend curve 3 3 1 Start trend curve Service Display Diagnostics gt Service Info Basic adjustment 4 Current output 4 1 Output mode 4 20 mA V Fail mode lt 3 6 mA Y Min current 3 8 mA Y max current 20 5 mA Y Simulation Start simulation V 4 2 Reset 4 3 Language 4 4 Select reset V Deutsch V Copy sensor data Copy sensor data 47 PIN Enable 48 Application 49 Level V Info Display Diagnostics Service gt Info me nt Basic adjustment 5 Instrument type 5 1 Serial number 12345678 Date of manufacture 1st October 2009 Software version 3 80 5 2 Last change using PC 5 3 Sensor characteristics 5 4 Display now 1st October 2009
2. Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 29 6 Set up with the indicating and adjustment module wi KAI 6 6 Saving the parameter adjustment data It is recommended noting the adjusted data e g in this operating instructions manual and archive them afterwards They are hence available for multiple use or service purposes If IPT 11 is equipped with an indicating and adjustment module the most important data can be read out of the sensor into indicating and adjustment module The procedure is described in the operating instructions manual Indicating and adjustment module in the menu item Copy sensor data The data remain there permanently even if the sensor power supply fails If it is necessary to exchange the sensor the indicating and adjustment module is inserted into the replacement instrument and the data are written into the sensor under the menu item Copy sensor data 30 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wi KAI 7 Setup with PACTware and other adjustment programs 7 Setup with PACTware and other adjustment programs 7 1 Connecting the PC Connecting the PC to the signal cable 0 ovo c HART Modem Fig 10 Connecting the PC to the signal cable 1 RS232 connection 2 HART resistor 250 Q 3 IPT 113 Necessa
3. You can find the specifications in chapter Technical data or on the type label Select an installation position you can easily reach for mounting and connecting as well as later retrofitting of an indicating and adjustment module The housing can be rotated by 330 without the use of any tools You can also install the indicating and adjustment module in four different positions each displaced by 90 Use the recommended cables see chapter Connecting to power supply and tighten the cable gland You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cable entry Rain and condensation water can thus drain off This applies mainly to outdoor mounting as well as installation in areas where high humidity is expected e g through cleaning processes or on cooled or heated vessels Q ONO g Fig 2 Measures against moisture penetration The ventilation for the electronics housing is realised via a filter element in the vicinity of the cable glands 10 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 4 Mounting be Temperature limits Welding the socket Sealing Screwing in hy gienic fittings Fig 3 Position of the filter element with single and double chamber housing 1 Filter element for ventilation of the
4. 8 Incl non linearity hysteresis and non repeatability 40 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 10 Supplement Turndown1 1upto5 1 lt 0 25 x TD Turndown gt 5 1 lt 0 05 x TD Influence of the product or ambient temperature Thermal change zero signal and output span Applies to the digital signal output HART Profibus PA Foundation Fieldbus as well as to the analogue current output 4 20 mA and refers to the set span Turn down TD is the ratio nominal measuring range set span Thermal change zero signal and output span reference temperature 20 C 68 F In the compensated temperature range lt 0 05 0 1 x TD 0 100 C 32 212 F Outside the compensated temperature lt 0 05 0 15 x TD range Thermal change zero signal and output span with absolute pressure measuring range 0 1 bar reference temperature 20 C 68 F In the compensated temperature range lt 0 1 0 1 x TD 0 100 C 32 212 F Outside the compensated temperature lt 0 15 0 15 x TD range Thermal change current output Applies also to the analogue 4 20 mA current output and refers to the set span Thermal change current output lt 0 15 at 40 80 C 40 176 F Long term stability similar to DIN 16086 DINV 19259 1 and IEC 60770 1 Applies to
5. 15 psig 15 150 psig 1300 psig 15 psig 15 350 psig 1900 psig 15 psig 15 900 psig 2900 psig 15 psig 0 7 0 7 psig 200 psig 3 psig 1 5 1 5 psig 290 psig 6 psig 3 3 psig 430 psig 12 psig 7 7 psig 500 psig 15 psig Absolute pressure 0 1 5 psi 200 psi 0 psi 0 15 psi 500 psi 0 psi 0 35 psi 700 psi 0 psi 0 70 psi 900 psi 0 psi 0 150 psi 1300 psi 0 psi 0 350 psi 1900 psi 0 psi 0 900 psi 2900 psi 0 psi Reference conditions and actuating variables similar to DIN EN 60770 1 Reference conditions according to DIN EN 61298 1 Temperature 15 25 C 59 77 F Relative humidity 45 75 Air pressure 860 1060 mbar 86 106 kPa 12 5 15 4 psig Determination of characteristics Limit point adjustment according to IEC 61298 2 Characteristics linear Reference installation position upright diaphragm points downward Influence of the installation position lt 0 2 mbar 20 Pa 0 003 psig Deviation determined according to the limit point method according to IEC 607708 Applies to digital interfaces HART Profibus PA Foundation Fieldbus as well as to analogue current output 4 20 mA Specifications refer to the set span Turn down TD is the ratio nominal measuring range set span Deviation Turn down1 1upto5 1 Turn down gt 5 1 lt 0 075 lt 0 015 x TD Deviation with absolute pressure measuring range 0 1 bar
6. 6 2 Insert indicating and adjustment module 16 6 3 Adjustment system 00008 18 6 4 Setup procedure 0 000000 0008 19 6 5 Menu schematic 0 000000 0008 28 6 6 Saving the parameter adjustment data 30 7 Setup with PACTware and other adjustment programs 7 1 Connecting the PC 0 000040 31 7 2 Parameter adjustment with PACTware 31 7 3 Parameter adjustment with AMS and PDM 32 8 Maintenance and fault rectification 8 1 Maintenance cleaning 000055 33 8 2 Rectify malfunctions 0 04 33 8 3 Instrument repair 00000408 34 2 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wi KAI Contents 9 Dismounting 9 1 Dismounting steps 000000008 36 92 Removal ess e hart taka a e a a e ari 36 10 Supplement 10 1 Technical data nnana aaaea ven 37 10 2 Dimensions 0 0 00 cece eee 45 Supplementary documentation Information Supplementary documents appropriate to the ordered version come with the delivery You can find them listed in chapter Product description po Instructions manuals for accessories and replacement parts Tip To ensure reliable setup and operation of your IPT 11 we offer accessories and replacement parts The corresponding documenta tions are po e O
7. Fig 14 IPT 11 SA Tri Clamp 2 RT Tri Clamp 1 3T DRD 3R Varivent Form F 46 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 10 Supplement Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 47 Printing date WiKAl WIKA Alexander Wiegand SE amp Co KG Alexander Wiegand StraBe 30 63911 Klingenberg Germany Phone 49 9372 132295 Fax 49 9372 132706 e mail support tronicewika de www wika de CE amp All statements concerning scope of delivery application practical use and operating conditions of the sensors and processing systems correspond to the information avail able at the time of printing Subject to change without prior notice 37301 EN 100302
8. 7 8 Press down the opening levers of the terminals you will hear the terminal spring closing Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 13 5 Connecting to power supply wi KAI Electronics and connec tion compartment 9 Check the hold of the wires in the terminals by lightly pulling on them 10 Connect the screen to the internal ground terminal connect the outer ground terminal with potential equalisation 11 Tighten the compression nut of the cable entry The seal ring must completely encircle the cable 12 Screw the housing cover on The electrical connection is finished 5 3 Single chamber housing Display Fig 6 Electronics and connection compartment with single chamber housing 1 Spring loaded terminals for voltage supply 2 Ground terminal for connection of the cable screen 14 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wi KAI 5 Connecting to power supply Wiring plan Pa GE ha Zz o N N Display l Fig 7 Wiring plan single chamber housing 1 Voltage supply Signal output 5 4 Switch on phase Switch on phase After connecting IPT 11 to power supply or after a voltage recurrence the instrument carries out a self check for approx 30 seconds e Internal check
9. OK and select Temperature unit with gt gt Activate the selection with OK and select the requested unit with gt e g F gt Confirm with OK The temperature unit is hence switched over from C to F Proceed as follows 1 Activate in the menu item Position correction the selection with OK Position correction Offset 0000 mbar 53 mbar AY DoF D 2 Select with gt e g to accept actual measured value Position correction Accept current measured value gt Accept Edit 3 Confirm with OK and move to min zero adjustment with gt Selection options C F 24 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0E001 NA LOEZE 37301 EN 100302 wikal 6 Set up with the indicating and adjustment module Carrying out zero ad justment po po Carrying out span ad justment po po Proceed as follows 1 Edit the mbar value in the menu item zero with OK Zero 000 0 0000 0 mbar 0000 0 mbar 2 Set the requested mbar value with and gt 3 Confirm with and move to span adjustment with gt The zero adjustment is finished Information The zero adjustment shifts the value of the span adjustment The span i e the difference between these values however remains unchan ged Information For an adjustment with pressure simply enter the actual measured value
10. OK and select Units of measure ment with gt Activate the selection with OK and select the requested unit with gt in the example mbar Confirm with OK and move to position correction with gt The adjustment unit is thus switched over from bar to mbar po Information When switching over to adjustment in a height unit in the example from bar to m the density also has to be entered Proceed as follows 1 Push the OK button in the measured value display the menu overview is displayed Confirm the menu Basic adjustment with OK the menu item Units of measurement will be displayed Activate the selection with OK and select the requested unit with gt in the example m Confirm with OK the submenu Density unit appears Unit of measurement Density unit gt kgldm 6 pef Select the requested unit e g kg dm with gt and confirm with OK the submenu Density appears Unit of measurement Density 0001000 kg dm Enter the requested density value with gt and confirm with OK and move to position correction with gt 20 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0E001 NA LOEZE 37301 EN 100302 wikal Carry out position cor rection Carrying out min ad justment 6 Set up with the indicating and adjustment module bie The adjustment unit is thus switched over from bar t
11. WikAl 5 Part of your business Operating Instructions Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA Document ID 37301 Contents WIKA Contents 1 About this document 1 1 Function cee pee saks cee ea ee bee eas 4 1 2 Target group seos si a aaa i ee ee 4 1 3 Symbolism used 0 0 0000008 4 2 For your safety 2 1 Authorised personnel 00008 5 2 2 Appropriate use ren 5 2 3 Warning about misuse 04 5 2 4 General safety instructions 5 2 5 Safety label on the instrument 6 2 6 CE conformity 0000 6 2 7 Fulfillment of NAMUR recommendations 6 2 8 Safety instructions for Ex areas 6 3 Product description 3 1 Configuration avvvvvvv rv 7 3 2 Principle of operation 004 8 3 3 Operation 0 0 0000000 eee ee 8 3 4 Packaging transport and storage 8 4 Mounting 4 1 General instructions 04 10 4 2 Mounting steps 00008 11 5 Connecting to power supply 5 1 Preparing the connection 000048 12 5 2 Connection procedure 0000000 13 5 3 Single chamber housing 0004 14 5 4 Switch on phase ccc eee ees 15 6 Set up with the indicating and adjustment module 6 1 Short description 00040 16
12. contains the most important data for identification and use of the instrument e Instrument type e Article and serial number device e Technical data Measuring range process pressure process temperature signal output voltage supply protection protection class Order number Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 3 Product description wikal Application area Functional principle Voltage supply Packaging e Article number documentation e SIL identification with SIL rating ex works 3 2 Principle of operation IPT 11 is a pressure transmitter for use in the paper food processing and pharmaceutical industries as well as in water sewage water plants Depending on the version it is used for level gauge absolute pressure or vacuum measurement Measured products are gases vapours and liquids also those containing abrasive substances A measuring cell with front flush abrasion resistant diaphragm is the sensor element The hydrostatic pressure of the product or the process pressure effects a capacitance change in the measuring cell via the diaphragm This change is converted into a respective output signal and outputted as measured value The ceramic measuring cell is also equipped with a temperature sensor The temperature value can be displayed via the indicating and adjustment module or processed via the signal output Two wire electronics 4 20 mA for powe
13. electronics housing 2 Blind stopper Information Make sure that the filter element is always free of buildup during operation A high pressure cleaner must not be used for cleaning Higher process temperatures mean often also higher ambient temperatures Fig 4 Temperature ranges 1 Process temperature 2 Ambient temperature Make sure that the upper temperature limits for the environment of electronics housing and connection cable specified in chapter Technical data are not exceeded 4 2 Mounting steps To mount IPT 11 a welded socket is necessary Use components from the line of WIKA mounting accessories gt Note the applicable welding standards segment welding proce dure when welding the socket Use the seal corresponding to the process fitting Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 11 5 Connecting to power supply wi KAI Note safety instructions Take note of safety instruc Ex tions for Ex ap plications Select power supply Selecting connection cable Cable screening and grounding 5 Connecting to power supply 5 1 Preparing the connection Always keep in mind the following safety instructions e Connect only in the complete absence of line voltage e f overvoltage surges are expected overvoltage arresters should be installed In hazardous areas you should take note of the appropriate regulations conformity and type appr
14. indicated at the bottom of the display If the adjustment ranges are exceeded the message Outside parameter limits appears The editing procedure can be aborted with ESC or the displayed limit value can be accepted with OK Proceed as follows 1 Edit the mbar value in the menu item span with OK Span 100 0 1000 0 mbar 0000 0 mbar Information The displayed pressure for 100 corresponds to the nominal measuring range of the sensor in the above example 1 bar 1000 mbar 2 Set the requested mbar value with gt and OK 3 Confirm with OK and move to the menu overview with ESC The span adjustment is finished Information For an adjustment with pressure simply enter the actual measured value indicated at the bottom of the display Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 25 6 Set up with the indicating and adjustment module wi KAI If the adjustment ranges are exceeded the message Outside parameter limits appears The editing procedure can be aborted with ESC or the displayed limit value can be accepted with OK Copy sensor data This function enables reading out parameter adjustment data as well as writing parameter adjustment data into the sensor via the indicating and adjustment module A description of the function is available in the operating instructions manual Indicating and adjustment module The following data are read out or written
15. justment Proc ess pressure measurement po T If the adjustment ranges are exceeded the message Outside parameter limits appears The editing procedure can be aborted with ESC or the displayed limit value can be accepted with OK Proceed as follows 1 Edit the value in the menu item Max adjustment with OK Max adjustment 100 0 is 1000 0 mbar 0000 0 mbar Information The displayed pressure for 100 corresponds to the nominal measuring range of the sensor in the above example 1 bar 1000 mbar Set the requested percentage value with gt and OK Edit the requested mbar value with OK Set the requested mbar value with and gt Confirm with OK and move to the menu overview with ESC The max adjustment is finished ar wo DY Information For an adjustment with filling simply enter the actual measured value indicated at the bottom of the display If the adjustment ranges are exceeded the message Outside parameter limits appears The editing procedure can be aborted with ESC or the displayed limit value can be accepted with OK Process pressure measurement Set up IPT 11 in the following sequence Select application Process pressure measurement Select the unit of measurement Carry out position correction Carrying out zero adjustment 5 Carrying out span adjustment In the menu item Adjustment unit you select the physical unit in which the adjustment sh
16. of the electronics e Indication of the instrument type the firmware as well as the sensor TAGs sensor designation e Output signal jumps briefly approx 10 seconds to the set fault current Then the corresponding current is outputted to the cable the value corresponds to the actual level as well as the settings already carried out e g factory setting Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 15 6 Set up with the indicating and adjustment module wi KAI Function Configuration T Mount Dismount indicat ing and adjustment module 6 Set up with the indicating and adjustment module 6 1 Short description The indicating and adjustment module is used for measured value display adjustment and diagnosis It can be mounted in the following housing versions and instruments e All sensors of the IPT 1 instrument family in the single as well as double chamber housing optionally in the electronics or connec tion compartment e External indicating and adjustment unit Note You can find detailed information on adjustment in the operating instructions manual ndicating and adjustment module 6 2 Insert indicating and adjustment module The indicating and adjustment module can be inserted and removed at any time It is not necessary to interrupt the voltage supply For installation proceed as follows Unscrew the housing cover 2 Place the indicating and adjustment modul
17. the parameter e ESC key interrupt input jump to the next higher menu The sensor is adjusted via the four keys of the indicating and adjustment module The LC display indicates the individual menu items The functions of the individual keys are shown in the above illustration Approx 10 minutes after the last pressing of a key an automatic reset to measured value indication is triggered Any values not confirmed with OK will not be saved 18 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 6 Set up with the indicating and adjustment module wikal Level or process pres sure measurement Parameter ad justment Level measurement Select unit po 6 4 Setup procedure IPT 11 can be used for level as well as for process pressure measurement Default setting is level measurement The mode can be changed in the adjustment menu Depending on the application only the respective subchapter Level or process pressure measurement is of importance There you find the individual adjustment steps Level measurement Set up IPT 11 in the following sequence 1 Selecting adjustment unit density unit 2 Carry out position correction 3 Carrying out min adjustment 4 Carrying out max adjustment In the menu item Adjustment unit you select the physical unit in which the adjustment should be carried out e g mbar bar psi The position corre
18. 5 FFKM FDA 3A Plastic PBT Alu die casting powder coated 316L NBR stainless steel housing silicone Aluminium housing Polycarbonate UL 746 C listed 316Ti 316L 0 8 8 kg 1 764 17 64 Ibs depending on process fitting Output variable Output signal Signal resolution Failure signal output current Max output current Load Fulfilled NAMUR recommendations 4 20 mA 1 6 pA mA value unchanged 20 5 mA 22 mA lt 3 6 mA adjustable 22 mA see load diagram under Power supply NE 43 Run up time approx Dynamic behaviour output 10s Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 37 10 Supplement wikal 100 47 90 10 4 Fig 11 Sudden change of the process variable tr dead time ta rise time ts jump response time 1 Process variable 2 Output signal Dead time lt 150 ms Rise time lt 100 ms 10 90 Step response time lt 250 ms ti 0 s 10 90 Damping 63 of the input variable 0 999 s adjustable Input variable Adjustment Adjustment range of the min max adjustment relating to the nominal measuring range Percentage value 10 110 Pressure value 20 120 Adjustment range of the zero span adjustment relating to the nominal measuring range zero 20 95 span 120 120 7 Difference between zero and span max 120 of the nomin
19. Dispose of the packaging material via specialised recycling companies Transport must be carried out under consideration of the notes on the transport packaging Nonobservance of these instructions can cause damage to the device The delivery must be checked for completeness and possible transit damage immediately at receipt Ascertained transit damage or concealed defects must be appropriately dealt with Up to the time of installation the packages must be left closed and stored according to the orientation and storage markings on the outside Unless otherwise indicated the packages must be stored only under the following conditions Not in the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see chapter Supplement Technical data Ambient conditions e Relative humidity 20 85 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 9 4 Mounting wikal Suitability for the proc ess conditions Mounting position Moisture Ventilation 4 Mounting 4 1 General instructions Make sure that all parts of the instrument exposed to the process in particular the sensor element process seal and process fitting are suitable for the existing process conditions These include above all the process pressure process temperature as well as the chemical properties of the medium
20. Vers 4 0 ceramic sensor 4 20 mA 35 9 Dismounting wikal po 9 Dismounting 9 1 Dismounting steps Warning Before dismounting be aware of dangerous process conditions such as e g pressure in the vessel high temperatures corrosive or toxic products etc Take note of chapters Mounting and Connecting to power supply and carry out the listed steps in reverse order 9 2 Removal Note When disposing of old instruments take note of the valid legal and municipal regulations The appropriate parts must be recycled 36 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 10 Supplement 10 Supplement 10 1 Technical data General data Parameter pressure Gauge pressure absolute pressure vacuum Measuring principle Service interface Ceramic capacitive dry measuring cell IC bus Materials and weights Material 316L corresponds to 1 4404 or 1 4435 Materials wetted parts Process fitting Diaphragm Joining material diaphragm Basic ele ment measuring cell Measuring cell seal Materials non wetted parts Housing Seal between housing and housing cover Inspection window in housing cover for indicating and adjustment module Ground terminal Weight 316L Ceramic 99 9 oxide ceramic Glass solder FKM VP2 A FFKM Kalrez 6375 EPDM A P 75 5 KW75F FFKM Chemraz 53
21. al range Recommended max turn down 10 1 no limitation Nominal measuring ranges and overload capability in bar kPa Nominal range Overload capacity max Overload capacity min pressure pressure Gauge pressure 0 0 1 bar 0 10 kPa 15 bar 1500 kPa 0 2 bar 20 kPa 0 0 2 bar 0 20 kPa 20 bar 2000 kPa 0 4 bar 40 kPa 0 0 4 bar 0 40 kPa 30 bar 3000 kPa 0 8 bar 80 kPa 0 1 bar 0 100 kPa 35 bar 3500 kPa 1 bar 100 kPa 7 Values less than 1 bar cannot be set 38 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 MA c0 001 NA LOEZE 37301 EN 100302 wikal 10 Supplement Nominal range 2 5 bar 0 250 kPa 5 bar 0 500 kPa 10 bar 0 1000 kPa 25 bar 0 2500 kPa 60 bar 0 6000 kPa 1 0 bar 100 0 kPa 1 1 5 bar 100 150 kPa 1 5 bar 100 500 kPa 1 10 bar 100 1000 kPa 1 25 bar 100 2500 kPa 1 60 bar 100 6000 kPa 0 05 0 05 bar 5 5 kPa 0 1 0 1 bar 10 10 kPa 0 2 0 2 bar 20 20 kPa 0 5 0 5 bar 50 50 kPa Absolute pressure oj o o o e Overload capacity max pressure 50 bar 5000 kPa 65 bar 6500 kPa 90 bar 9000 kPa 130 bar 13000 kPa 200 bar 20000 kPa 35 bar 3500 kPa 50 bar 5000 kPa 65 bar 6500 kPa 90 bar 9000 kPa 130 bar 13000 kPa 200 bar 20000 kPa 15 bar 1500 kPa 20 bar 2000 kPa 30 bar 3000 kPa 35 bar 3500 kPa O
22. ation FKM VP2 A 20 150 C 4 302 F EPDM A P 75 5 KW75F 40 150 C 40 302 F FFKM Kalrez 6375 10 150 C 14 302 F FFKM Chemraz 535 30 150 C 22 302 F Vibration resistance mechanical vibrations with 4 g and 5 100 Hz Shock resistance Acceleration 100 gi Electromechanical data version IP 66 IP 67 Cable entry plug 2 Single chamber housing e 1xcable gland M20 x 1 5 cable 5 9 mm 1 x blind stopper M20 x 1 5 or 1 x closing cap NPT 1 x blind plug NPT or amp 1 x plug depending on the version 1 x blind stopper M20 x 1 5 Double chamber housing amp 1xcable entry M20 x 1 5 cable 5 9 mm 1 x blind stopper M20 x 1 5 plug M12 x 1 for the external indicating and adjustment unit optional or 9 With process fitting PVDF max 100 C 212 F 10 Tested according to the regulations of German Lloyd GL directive 2 11 Tested according to EN 60068 2 27 12 Depending on the version M12 x 1 according to DIN 43650 Harting 7 8 FF 42 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0E001 NA LOEZE 37301 EN 100302 wikal 10 Supplement Spring loaded terminals for wire cross sec tion up to Indicating and adjustment module Voltage supply and data transmission Indication Adjustment elements Protection rating unassembled mounte
23. ction compensates the influence of the mounting position or static pressure on the measurement It does not influence the adjustment values Information The steps 1 3 and 4 are not necessary for instruments which are already preset according to customer specifications You can find the data on the type label on the instrument or in the menu items of the min max adjustment The indicating and adjustment module enables the adjustmetn without filling or pressure Thanks to this you can carry out your settings already in the factory without the instrument having to be installed The actual measured value is also displayed in the menu items for min max adjustment In this menu item you select the adjustment unit as well as the unit for the temperature indication in the display To select the adjustment unit in the example switching over from bar to mbar proceed as follows 1 Push the OK button in the measured value display the menu overview is displayed 1 Selection options mbar bar psi Pa kPa MPa inHg mmHg inH2O mmHzO Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 19 6 Set up with the indicating and adjustment module wi KAI gt Basic adjustment Display 5 Diagnostics Service Info Confirm the menu Basic adjustment with OK the menu item Unit will be displayed Unit Unit of measurement bar Temperature unit CV Activate the selection with
24. d into the sensor without cover Materials Housing Inspection window amp 1 x closing cap NPT 1 x blind stopper Ye NPT plug M12 x 1 for the external indicating and adjustment unit optional or amp 1 x plug depending on the version 1 x blind stopper M20 x 1 5 plug M12 x 1 for the external indicating and adjustment unit optio nal 2 5 mm AWG 14 through the sensor LC display in dot matrix 4 keys IP 20 IP 40 ABS Polyester foil Voltage supply Operating voltage Non Ex instrument EEx ia instrument Exd instrument Operating voltage with lighted indicating and adjustment module Non Ex instrument EEx ia instrument EEx d ia instrument Permissible residual ripple lt 100 Hz 100 Hz 10 kHz Load 12 36 V DC 12 30 V DC 18 36 V DC 20 36 V DC 20 30 V DC 20 36 V DC Uss lt 1V Uss lt 10 mV see diagram Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 43 10 Supplement wikal 1000 750 250 12 14 16 18 20 22 24 26 28 30 32 34 36 V Fig 12 Voltage diagram 1 Voltage limit EEx ia instrument 2 Voltage limit non Ex Exd instrument 3 Operating voltage Electrical protective measures Protection rating Housing standard IP 66 IP 6713 Overvoltage category II Protection class ll Approvals Depending on the version instruments with approvals can ha
25. digital interfaces HART Profibus PA Foundation Fieldbus as well as to analogue current output 4 20 mA Specifications refer to the set span Turn down TD nominal measuring range set span Long term drift of the zero signal lt 0 1 x TD year Ambient conditions Ambient storage and transport temperature 40 80 C 40 176 F Process conditions The specifications to the pressure stage and the product temperature are used as an overview The specifications of the type label are applicable Pressure stage process fitting Thread 316L PN 60 Thread Aluminium PN 25 Thread PVDF PN 10 Hygienic fittings 316L PN 6 PN 10 PN 25 PN 40 Flange 316L PN 16 PN 40 or 150 Ibs 300 Ibs 600 Ibs Flange with extension 316L Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 41 10 Supplement wikal without PN specification PN 16 PN 40 or 150 Ibs 300 Ibs 600 Ibs Flange PVDF PN 16 Product temperature standard version depending on the meas cell seal FKM VP2 A 20 120 C 4 248 F EPDM A P 75 5 KW75F 40 120 C 40 248 F 1 h 140 C 284 F cleaning temperature FFKM Kalrez 6375 10 120 C 14 248 F FFKM Chemraz 535 30 120 C 22 248 F Product temperature version with extended temperature range depending on the meas cell seal as well as order specific
26. e in the desired position on the electronics you can choose any one of four different positions each displaced by 90 3 Press the indicating and adjustment module onto the electronics and turn it to the right until it snaps in 4 Screw housing cover with inspection window tightly back on Removal is carried out in reverse order The indicating and adjustment module is powered by the sensor an additional connection is not necessary 16 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wi KAI 6 Set up with the indicating and adjustment module Fig 8 Insert indicating and adjustment module Note If you intend to retrofit the instrument with an indicating and adjustment module for continuous measured value indication a higher cover with an inspection glass is required po Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 17 6 Set up with the indicating and adjustment module wi KAI Key functions Adjustment system 6 3 Adjustment system Fig 9 Indicating and adjustment elements 1 LC display 2 indication of the menu item number 3 Adjustment keys e OK key Move to the menu overview Confirm selected menu Edit parameter Save value e gt key to select Menu change Select list entry Select editing position e key Change value of
27. gnals as well as to evaluate the error messages via the indicating and adjustment module The procedure is described below Further comprehensive diagnostics can be carried out on a PC with the software PACTware and the suitable DTM In many cases the causes can be determined this way and faults rectified Checking the 4 20 mA Connect a handheld multimeter in the suitable measuring range signal according to the wiring plan 4 20 mA signal not stable e Level fluctuations gt Set the integration time via the indicating and adjustment module or PACTware no atmospheric pressure compensation Check the pressure compensation in the housing and clean the filter element if necessary Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 33 8 Maintenance and fault rectification wi KAI E9 Fault messages via the indicating adjustment module Reaction after fault rec tification 4 20 mA signal missing amp Connection to voltage supply wrong gt Check connection according to chapter Connection steps and if necessary correct according to chapter Wiring plan No power supply Check cables for breaks repair if necessary Operating voltage too low or load resistance too high gt Check adapt if necessary eve Current signal greater than 22 mA or less than 3 6 mA e electronics module or measuring cell defective gt Exchange the instrument or send it for repair In Ex a
28. hazards e g vessel overfill or damage to system components through incorrect mounting or adjustment 2 4 General safety instructions This is a high tech instrument requiring the strict observance of standard regulations and guidelines The user must take note of the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules The instrument must only be operated in a technically flawless and reliable condition The operator is responsible for trouble free operation of the instrument During the entire duration of use the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 5 2 For your safety wikal 2 5 Safety label on the instrument The safety approval markings and safety tips on the device must be observed 2 6 CE conformity This device fulfills the legal requirements of the applicable EC guidelines By attaching the CE mark we provide confirmation of successful testing 2 7 Fulfillment of NAMUR recommendations The device fulfills the requirements of the applicable NAMUR recommendations 2 8 Safety instructions for Ex areas Please note the Ex specific safety information for installation and ope
29. iagnostics gt Service Info 3 Select the menu item Application with gt and edit with OK Warning Note the warning Output can change 4 Select with gt OK and confirm with OK 5 Select Process pressure from the list and confirm with OK In this menu item you select the adjustment unit as well as the unit for the temperature indication in the display To select the adjustment unit in the example switching over from bar to mbar proceed as follows 3 1 Push the OK button in the measured value display the menu overview is displayed 3 Selection options mbar bar psi Pa kPa MPa inHg mmHg inHzO mmHzO Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 23 6 Set up with the indicating and adjustment module wi KAI Carry out position cor rection gt Basic adjustment Display Diagnostics Service Info 2 Confirm the menu Basic adjustment with OK the menu item Unit will be displayed Unit Unit of measurement bar Temperature unit CV 3 Activate the selection with OK and select Units of measure ment with gt 4 Activate the selection with OK and select the requested unit with gt in the example mbar 5 Confirm with OK and move to position correction with gt The adjustment unit is thus switched over from bar to mbar Proceed as follows to select the temperature unit 4 gt Activate the selection with
30. o m Proceed as follows to select the temperature unit 2 gt Activate the selection with OK and select Temperature unit with gt gt Activate the selection with OK and select the requested unit with gt e g F gt Confirm with OK The temperature unit is hence switched over from C to F Proceed as follows 1 Activate in the menu item Position correction the selection with OK Position correction Offset 3 4P 0000 mbar 53 mbar 2 Select with gt e g to accept actual measured value Position correction Accept current measured value gt Accept Edit 3 Confirm with OK and move to min zero adjustment with gt Proceed as follows 1 Edit the value in the menu item Min adjustment with OK Min adjustment 000 0 s 0000 0 mbar 0000 0 mbar Set the requested percentage value with and gt Edit the requested mbar value with OK Set the requested mbar value with and gt Confirm with and move to max adjustment with gt The min adjustment is finished a fw Ph Information For an adjustment with filling simply enter the actual measured value indicated at the bottom of the display 2 Selection options C F Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 21 6 Set up with the indicating and adjustment module wi KAI Carrying out max ad justment Parameter ad
31. on low impedance If potential equalisation currents are expected the connection on the processing side must be made via a ceramic capacitor e g 1 nF 1500 V The low frequency potential equalisation currents are thus suppressed but the protective effect against high frequency inter ference signals remains 12 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0E001 NA LOEZE 37301 EN 100302 wi KAI 5 Connecting to power supply Select connec amp Take note of the corresponding installation regulations for Ex tion cable for Ex applications In particular make sure that no potential equalisation applications currents flow over the cable screen In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation 5 2 Connection procedure Proceed as follows 1 Unscrew the housing cover 2 If an indicating and adjustment module is installed remove it by turning it slightly to the left 3 Loosen compression nut of the cable entry 4 Remove approx 10 cm 4 in of the cable mantle strip approx 1 cm 0 4 in of insulation from the ends of the individual wires 5 Insert the cable through the cable gland into the sensor 6 Lift the opening levers of the terminals with a screwdriver see following illustration 7 Insert the wire ends into the open terminals according to the wiring plan Fig 5 Connection steps 6 and
32. ould be carried out e g mbar bar psi RON The position correction compensates the influence of the mounting position or static pressure on the measurement It does not influence the adjustment values 22 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 6 Set up with the indicating and adjustment module wikal Select application Process pressure measurement Select unit po In the menu items Zero and span you determine the span of the sensor the span corresponds to the end value Information The steps 1 3 and 4 are not necessary for instruments which are already preset according to customer specifications You can find the data on the type label on the instrument or in the menu items of the zero span adjustment The indicating and adjustment module enables the adjustmetn without filling or pressure Thanks to this you can carry out your settings already in the factory without the instrument having to be installed The actual measured value is displayed in addition to the menu items for zero span adjustment IPT 11 is preset to application Level measurement Proceed as follows when switching over to application Process pressure measurement 1 Push the OK button in the measured value display the menu overview is displayed 2 Select the menu Service with gt and confirm with OK Basic adjustment Display D
33. oval certificates of the sensors and power supply units Power supply and current signal are transmitted via the same two wire connection cable The supply voltage range can differ depending on the instrument version The exact range is stated in the Technical data in the Supplement Provide a reliable separation between the supply circuit and the mains circuits according to DIN VDE 0106 part 101 Keep in mind the following additional influences on the operating voltage e Output voltage of the power supply unit can be lower under nominal load with a sensor current of 20 5 mA or 22 mA in case of fault message e Influence of additional instruments in the circuit see load values in chapter Technical data The instrument is connected with standard two wire cable without screen If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas screened cable should be used Use cable with round cross section A cable outer diameter of 5 9 mm 0 2 0 35 in ensures the seal effect of the cable gland If you are using cable with a different diameter or cross section exchange the seal or use a suitable cable gland If screened cable is necessary connect the cable screen on both ends to ground potential In the sensor the screen must be connected directly to the internal ground terminal The ground terminal on the outside of the housing must be connected to the potential equalisati
34. perating instructions manual External indicating and adjustment unit Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 3 1 About this document wikal 1 About this document 1 1 Function This operating instructions manual provides all the information you need for mounting connection and setup as well as important instructions for maintenance and fault rectification Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device 1 2 Target group This operating instructions manual is directed to trained qualified personnel The contents of this manual should be made available to these personnel and put into practice by them 1 3 Symbolism used Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result Warning If this warning is ignored injury to persons and or serious damage to the instrument can result Danger If this warning is ignored serious injury to persons and or destruction of the instrument can result Ex applications This symbol indicates special instructions for Ex applications List The dot set in front indicates a list with no implied sequence Action This arrow indicates a single action Sequence Numbers set in front indicate successive steps in a procedure Process pressure transmi
35. pplications the regulations for the wiring of intrinsically safe circuits must be observed E013 no measured value available gt Exchange the instrument or send it for repair E017 e Adjustment span too small gt repeat with modified values E036 no operable sensor software gt Carry out a software update or send instrument for repair E041 e Hardware error gt Exchange the instrument or send it for repair Depending on the failure reason and measures taken the steps described in chapter Set up must be carried out again if necessary 8 3 Instrument repair You can download a return form 24 KB in the Internet from our homepage www wika com under the item Service If a repair is necessary please proceed as follows 6 Print and fill out one form per instrument Fault message can also appear if the pressure is higher than the nominal range 34 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0E001 NA LOEZE 37301 EN 100302 wi KA l 8 Maintenance and fault rectification If necessary state a contamination Clean the instrument and pack it damage proof e Attach the completed form and probably a safety data sheet to the instrument e Please contact the agency serving you for the address of the return shipment By doing this you help us carry out the repair quickly and without having to call back for needed information Process pressure transmitter IPT 11
36. ptions for the adjustment programs AMS and PDM are available as DD or EDD The instrument descriptions are already implemented in the current versions of AMS and PDM For older versions of AMS and PDM a free of charge download is available via Internet Go via www wika com to the item Service 32 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wi KA I 8 Maintenance and fault rectification 8 Maintenance and fault rectification 8 1 Maintenance cleaning When the instrument is used properly no special maintenance is required in normal operation In some applications product buildup on the sensor diaphragm can influence the measuring result Depending on the sensor and application take precautions to ensure that heavy buildup and especially a hardening thereof is avoided If necessary the transmitter has to be cleaned In this case make sure that the materials are resistant against the cleaning detergents 8 2 Rectify malfunctions Reaction when malfunc The operator of the system is responsible for taking suitable measures tions occur to remove interferences Causes of malfunction IPT 11 offers maximum reliability Nevertheless faults can occur during operation These may be caused by the following e g Sensor Process Voltage supply Signal processing Fault rectification The first measures to be taken are to check the output si
37. r supply and measured value transmission over the same cable The supply voltage range can differ depending on the instrument version The exact range is stated in chapter Technical data The background lighting of the indicating and adjustment module is powered by the sensor A certain level of operating voltage is required for this You can find the exact voltage specifications in chapter Technical data 3 3 Operation IPT 11 can be adjusted with different adjustment media e with indicating and adjustment module e the suitable WIKA DTM in conjunction with an adjustment software according to the FDT DTM standard e g PACTware and PC e with manufacturer specific adjustment programs AMS or PDM e With a HART handheld The entered parameters are generally saved in IPT 11 optionally also in the indicating and adjustment module or in PACTware 3 4 Packaging transport and storage Your instrument was protected by packaging during transport Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180 8 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 3 Product description Transport Transport inspection Storage Storage and transport temperature The packaging of standard instruments consists of environment friendly recyclable cardboard For special versions PE foam or PE foil is also used
38. ration in Ex areas These safety instructions are part of the operating instructions manual and come with the Ex approved instruments Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 3 Product description Scope of delivery Constituents Type label 3 Product description 3 1 Configuration The scope of delivery encompasses e IPT 11 pressure transmitter e Documentation this operating instructions manual Test certificate for pressure transmitters Safety Manual PT 1 4 20 MA HART two wire optional Operating instructions manual Indicating and adjustment module optional Supplementary instructions manual Plug connector for con tinuously measuring sensors optional Ex specific Safety instructions with Ex versions if necessary further certificates The IPT 11 consist of the following components e Process fitting with measuring cell e Housing with electronics optionally available with plug connector e Housing cover optionally available with indicating and adjustment module The components are available in different versions Fig 1 Example of a IPT 11 with process fitting G1 A and plastic housing 1 Housing cover with integrated indicating and adjustment module optional 2 Housing with electronics 3 Process fitting with measuring cell The type label
39. rrection no reset Language no reset HART mode no reset Application no reset Factory setting Like basic adjustment in addition special parameters are reset to default values Pointer The min and max temperature or pressure values are each reset to the actual value Optional settings Additional adjustment and diagnosis options such as e g scaling simulation or trend curve presentation are shown in the following menu schematic You will find a detailed description of these menu items in the operating instructions manual Indicating and adjustment module 5 Special parameters are parameters which are set customer specifically on the service level with the adjustment software PACTware Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 27 Switched off V 6 Set up with the indicating and adjustment module wi KAI po Basic adjustment gt Basic adjustment 1 Display Diagnostics Service Info 6 5 Menu schematic Information Depending on the version and application the highlighted menu windows may not always be available Unit 1 1 Unit of measurement bar Y Temperature unit CV N Position correction 1 Offset Min adjustment 1 3 Max adjustment 1 4 000 0 ai 100 00 i 0 2 mbar 0 0 mbar 100 00 mbar 0000 mbar 0 0 mbar 0 0 mbar Damping 1 5 1s Linearisation curve 1 6 Sensor TAG it linear V Sensor
40. ry components IPT 11 PC with PACTware and suitable WIKA DTM HART modem HART resistance approx 250 Q Power supply unit Note For power supply units with integrated HART resistance inner resistance approx 250 Q there is no additional external resistance necessary Standard Ex separators are often provided with a sufficiently high current limitation resistance In such cases the modem can be connected in parallel to the 4 20 mA cable bae 7 2 Parameter adjustment with PACTware Further setup steps are described in the operating instructions manual DTM Collection PACTware attached to each CD and which can also be downloaded from our homepage A detailed description is available in the online help of PACTware and the WIKA DTMs Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 31 7 Setup with PACTware and other adjustment programs wi KAI J 1 Note Keep in mind that for setup of IPT 11 DTM Collection in the actual version must be used All currently available WIKA DTMs are provided in the DTM Collection on CD and can be obtained from the responsible WIKA agency for a token fee This CD includes also the up to date PACTware version The basic version of this DTM Collection incl PACTware is also available as a free of charge download from the Internet Go via www wika com to the item Service 7 3 Parameter adjustment with AMS and PDM For WIKA sensors instrument descri
41. tter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 2 For your safety 2 For your safety 2 1 Authorised personnel Mount and set up the pressure transmitter only if you know the applicable national regulations and have the appropriate qualification You must be aquainted with the regulations and instructions for hazardous areas measurement and control technology as well as electrical circuits because the pressure transmitter is electrical equipment according to EN 50178 Depending on the application conditions it is necessary that you have appropriate knowledge e g concerning corrosive products or high pressure 2 2 Appropriate use IPT 11 is a pressure transmitter for measurement of gauge pressure absolute pressure and vacuum You can find detailed information on the application range in chapter Product description Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions For safety and warranty reasons any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer Arbitrary conversions or modifications are explicitly forbidden 2 3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application specific
42. ve different technical data For these instruments please note the corresponding approval documents They are included in the scope of delivery 13 Instruments with gauge pressure measuring ranges cannot detect the am bient pressure when submerged e g in water This can lead to falsification of the measured value 44 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0 001 NA LOEZE 37301 EN 100302 wikal 10 Supplement 10 2 Dimensions Housing or PT 116mm 69 mm a am 87mm 3 27 64 z 4 6 22 2 a 77 mm 0792 577 mm z 3 1 30 3 5 16 3 1 32 32 0 OUO S 0 OYO N 7 3 my 2 0 2 5 amp z t O E E p E a O amp M20x1 5 M20x1 5 M20xi 5 Ye NPT Y2 NPT v NPT D kler O Fig 13 Housing versions with integrated indicating and adjustment module the housing is 9 mm 0 35 in higher Plastic housing Stainless steel housing Aluminium double chamber housing Aluminium housing ROD Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 45 10 Supplement wikal IPT 11 front flush connection 64mm 2 33 64 51mm 2 1 64 SA RT 0 OVO 8 55mm 51mm 66mm 2 19 32 105mm 4 9 64 3T 3R 84mm 3 5 46
43. verload capacity min pressure bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa bar 100 kPa 0 2 bar 20 kPa 0 4 bar 40 kPa 0 8 bar 80 kPa 1 bar 100 kPa r fe fe fe fe afoafoajayafa ta 0 0 1 bar 0 10 kPa 15 bar 1500 kPa 0 bar abs 0 1 bar 0 100 kPa 35 bar 3500 kPa 0 bar abs 0 2 5 bar 0 250 kPa 50 bar 5000 kPa 0 bar abs 0 5 bar 0 500 kPa 65 bar 6500 kPa 0 bar abs 0 10 bar 0 1000 kPa 90 bar 9000 kPa 0 bar abs 0 25 bar 0 2500 kPa 130 bar 13000 kPa 0 bar abs 0 60 bar 0 6000 kPa 200 bar 20000 kPa 0 bar abs Nominal measuring ranges and overload capability in psig Nominal range Overload capacity max Overload capacity min pressure pressure Gauge pressure 0 1 5 psig 200 psig 3 psig 0 3 psig 290 psig 6 psig 0 6 psig 430 psig 12 psig 0 15 psig 500 psig 15 psig 0 35 psig 700 psig 15 psig 0 70 psig 950 psig 15 psig 0 150 psig 1300 psig 15 psig 0 350 psig 1900 psig 15 psig 0 900 psig 2900 psig 15 psig 15 0 psig 500 psig 15 psig Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA 39 10 Supplement wikal Nominal range Overload capacity max Overload capacity min pressure pressure 15 25 psig 700 psig 15 psig 15 70 psig 950 psig
44. with this function Measured value presentation Adjustment Damping Linearisation curve Sensor TAG Displayed value Display unit Scaling Current output Unit of measurement Language The following safety relevant data are not read out or written SIL HART mode PIN Application Copy sensor data Copy sensor data Reset Basic adjustment If the Reset sensor specific basic adjustment is carried out the sensor resets the values of the following menu items to the reset values see chart Menu section Function Reset value Basic settings Unit of measurement bar Temperature unit C Zero Min adjustment Measuring range begin Span Max adjustment Measuring range end Density 1 kg l Density unit kg l Damping 1s Linearisation linear 26 Process pressure transmitter IPT 11 Vers 4 0 ceramic sensor 4 20 mA c0E001 NA LOEZE 37301 EN 100302 wi KAI 6 Set up with the indicating and adjustment module Menu section Function Reset value Sensor TAG Sensor Display Displayed value 1 bar Displayed value 2 Display unit Volume Scaling 0 00 to 100 0 Decimal point indication 8888 8 Current output characteristics 4 20 mA Current output failure lt 3 6 mA Current output min current 3 8 mA Current output max current 20 5 mA The values of the following menu items are not reset with Reset Menu section Function Reset value Position co