Operating instructions Mechatronic flow sensor SBY2xx SBG2xx

image

Contents

1. 9 4 3 Configure colour change 15 9 4 4 Set the damping for the switching output 9 4 5 Set damping for the analogue 9 4 6 Set output status in fault condition l a a a 9 5 Service NN TO 9 5 1 Read the min max values for the temperature 9 5 2 Resetting all parameters to factory setting ESO UU T UU MM 23 10 1 Reading the process 23 10 2 Reading the set parameter value 24 10 3 Error indications self diagnostics sess 24 u u E TR 25 25 1 Preliminary note 1 1 Symbols used p Instructions gt Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 2 Safety instructions Please read this document prior to set up of the unit Ensure that the product is suitable for your application without any restrictions If the operating instructions or the technical data are not adhered to p
2. 80008233 00 05 2015 ifm electronic Operating instructions Mechatronic flow sensor efeckorao0o0 SBY2xx SBG2xx SBN2xx Contents Preliminaiy oT 4 1 1 Symbols U ed ous oou emer 4 2 Salely 4 5 S Eee a S 5 Switching JUNCO m 9 4 2 Analogue function D 6 4 3 Frequency output n nnn nnn nn 8 4 4 OTANI ce ets cee crested 8 4 4 1 General information I ease doeet 8 4 4 2 Device specific information sss 9 4 4 3 Parameter setting tools sess 9 SB cic WT N 9 6 DEN EET uu T 10 7 Operating and display elements seen 11 MO T 12 8 1 Process value display RUN and main 12 8 1 1 Explanation main 13 8 2 Extended functions Basic settings 14 8 2 1 Explanation basic settings CFG sss 15 8 3 Extended functions Min max memory Display 16 8 3 1 Explanation min max memory 16 8 3 2 Explanation display settings 015 16 3 P
3. LEDs 2 flow or temperature in the indicated unit of measurement 3 Alphanumeric display 4 digits Display of current process values volumetric flow quantity temperature Display of the parameters and parameter values 4 Button e Enter Change from the RUN mode to the main menu Change to the setting mode Acknowledge the set parameter value 5 Buttons up A and down Select parameters Change parameter values hold button pressed Change of the display unit in the normal operating mode Run mode Locking Unlocking press buttons simultaneously gt 10 seconds 8 Menu 8 1 Process value display RUN and main menu CFG MEM DIS For SBN2xx units gph F 1 Output functions for ou1 gt 8 2 1 _ The parameters are only displayed when selected at ou 12 8 1 1 Explanation main menu Switching output with hysteresis function Set point 1 upper limit value at which OUT1 switches Reset point 1 lower limit value at which OUT1 is reset Switching output with window function FH1 Set point 1 upper limit value at which OUT1 switches FL1 Reset point 1 lower limit value at which OUT1 switches Frequency output FSP1 Process value start point on OUT1 only if SEL1 TEMP FEP1 Process value end point on OUT1 Frequency at process value end point on OUT1 Extended functions Opening of the lower menu level 13 8 2 Extended functions
4. Display red in case of switched output OUT Display green in case of switched output OUT1 diS Update rate and orientation of the display SELd Standard measuring unit of the display volumetric flow value or medium temperature 16 9 Parameter setting Parameters can be set before installation and set up of the unit or during opera tion If you change parameters during operation this will influence the function of the plant gt Ensure that there will be no malfunctions in your plant During parameter setting the unit remains in the operating mode It continues to monitor with the existing parameter until the parameter setting has been completed The parameters can also be set via the IO Link interface 4 4 9 1 Parameter setting in general 1 Change from the RUN mode to the main menu 2 Select the requested parameter A or V 3 Change to the setting mode i Aljor gt 1s 4 Modification of the parameter value 5 Acknowledge the set parameter value 6 Return to the RUN mode EB If C Loc is displayed when attempting to change a parameter value a change is made via a parameter setting software at the same time tempo rary locking EB If S Loc is displayed the sensor is permanently locked via software This locking can only be removed with a parameter setting software 9 1 1 Select submenu Click A or V to select submenu EF CFG MEM DIS gt Briefly press e to change to the submenu
5. Basic settings Main menu eA V CFG out Hno Hnc Fro Fnc FRO VA uni e Lmin mah Y dAP 9 0 1 A vA 0 Y MEdi 9 H20 OIL OIL 2 Y FOU1 9 On OFF OU VA FOU2 9 On OFF OU VA _ FLOW TEMP VA SEL2 9 FLOW TEMP Y For SBN2xx units gpm gph Restoring the factory settings Submenu basic settings Submenu min max memory Submenu display settings 14 8 2 1 Explanation basic settings CFG Flow and temperature Hno Hnc Fno Fnc FRQ uni Stendardunitofmeasurement orvoumetictorv RE SEL1 Standard unit of measurement for evaluation by OUT1 volumetric flow value or medium temperature SEL2 Standard measured variable for evaluation by OUT2 volumetric flow value or medium temperature 15 8 3 Extended functions Min max memory Display Main menu A V MEM ES Lo T 1234 vA vA CFC HiT 1234 Y v YA e d 2 8 SELd FLOW TEMP Y 8 3 1 Explanation min max memory MEM Lo T Min value of the temperature measured in the process Hi T Max value of the temperature measured in the process 6 3 2 Explanation display settings DIS Assignment of the display colours red and green within the measuring range Display always red Display always green
6. 9 1 2 Exit parameter setting or menu level gt Press A V simultaneously gt Return to the next higher menu level The changed parameter settings are not accepted 17 9 1 3 Change to the process value display RUN mode There are 3 possibilities 1 Wait for 30 seconds 9 1 5 Timeout 2 Change from the submenu to the main menu from the main menu to the pro cess value display with A or 3 Press A V simultaneously until the RUN mode is reached 9 1 4 Locking Unlocking The unit can be locked electronically to prevent unintentional settings On delivery not locked Locking gt Make sure that the unit is in the normal operating mode gt Press A and V simultaneously for 10 s until Loc is displayed E During operation LOC is briefly displayed if you try to change parameter values Unlocking gt Make sure that the unit is in the normal operating mode gt Press A and V simultaneously for 10 s until uLoc is displayed 9 1 5 Timeout If no button is pressed for 30 s during parameter setting the unit returns to the operating mode with unchanged values 9 2 Settings for consumed quantity monitoring 9 2 1 Limit value monitoring with OUT1 hysteresis function gt Select SEL1 and set FLOW Menu CFG gt Select ou1 and set the switching function SEL 1 Hno hysteresis function normally open 001 Hnc hysteresis function normally closed Main menu g
7. FEP1 1 Frequency signal in Hz 2 Volumetric flow quantity or temperature 3 The device is in the error state FOU OFF or the process value transmitted in an analogue way is below the display range or the current flow is 0 4 The unit is in the error state FOU ON 4 4 IO Link 4 4 1 General information This unit has an IO Link communication interface which requires an O Link capa ble module IO Link master for operation The IO Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during operation In addition communication is possible via a point to point connection with a USB adapter cable You will find more detailed information about IO Link at www ifm com gb io link 4 4 2 Device specific information You will find the IODDs necessary for the configuration of the IO Link unit and detailed information about process data structure diagnostic information and parameter addresses at www ifm com gbj io link 4 4 3 Parameter setting tools You will find all necessary information about the required IO Link hardware and software at www ifm com gb io link 5 Installation 3 gt Insert the unit into the pipe according to the direction of flow arrow and tighten With water containing dirt gt horizontal installation recom mended IN inlet OUT outlet Baffled pipes on the sensor s inlet or outlet side are not necess
8. The process value to be displayed as standard temperature or volumetric can be preset 9 4 2 Configuration of the standard display A standard unit of meas urement can be defined for the volumetric flow quantity l min or m h for SBN2xx gpm or gph 9 4 1 In RUN mode further process values can be read in addition to the preset stand ard display gt Press the buttons A or V gt The LED of the selected process value display is lit and the current process value is displayed gt After 30 seconds the display changes to the standard display LED Process value display Current flow volume per hour Current medium temperature 1 m Currentflow volume per minute E 23 10 2 Reading the set parameter value 1 Change from the RUN mode to the main menu 2 Select the requested parameter A or V 3 Change to the setting mode gt The currently set value is displayed for 30 s By pressing e several times the display switch es between parameter and parameter value 4 Return to the RUN mode without parameter change 10 3 Error indications self diagnostics Sa Warning message SC1 Short circuit in OUT LED1 for OUT1 flashing 7 Operating and display elements SC2 Short circuit in OUT2 LED2 for OUT2 flashing 7 Operating and display elements SC Short circuit in both outputs LED1 and LED2 flashing 7 Operating and display elements OL Detection zone of volum
9. of the measured values every 50 ms d2 update of the measured values every 200 ms d3 update of the measured values every 600 ms rd1 rd2 rd3 display as for d1 d2 d3 rotated by 180 OFF The measured value display is deactivated in the Run mode The LEDs remain active even if the display is deactivated Error mes sages are displayed even if the display is deactivated 20 9 4 3 Configure colour change display gt Select coLr and define the colour of the process value display Menu DIS rEd GrEn r1ou G1ou 1 Fixed colour setting MAW MEW Ed w GrEn 2 Switching output OUT1 with hysteresis function rou SP1 Glou mw SP1 3 Switching output OUT1 with window function rou EE FL1 www FL1 MAW initial value of the measuring range MEW final value of the measuring range 9 4 4 Set the damping for the switching output gt Select and set the damping constant in seconds Menu CFG T value 63 96 setting range 0 5 s dAP 9 4 5 Set damping for the analogue output gt Select dAA and set a damping constant in seconds Menu CFG setting range 0 5 s dAA 21 9 4 6 Set output status in fault condition gt Select FOU1 and set the value Menu CFG 1 Switching output FOU1 On output 1 switches ON in case of an error FOU2 OFF output 1 switches OFF in case of an error OU output 1
10. aramotor SC 17 9 1 Parameter setting in general U u 17 9 1 1 Select submenu tta l bio reet annt 7 9 1 2 Exit parameter setting or menu 17 9 1 3 Change to the process value display RUN mode 18 9 14 Locking u u u uU u uu u u uuu 18 SK ESSET II OU ENCORE OP rcc 18 9 2 Settings for consumed quantity monitoring 18 9 2 1 Limit value monitoring with OUT1 hysteresis function 18 9 2 2 Limit value monitoring with OUT1 window function 9 2 3 Configure the analogue output for volumetric flow 9 2 4 Configure the frequency signal for volumetric flow 9 3 Settings for temperature monitoring eee 9 3 1 Limit value monitoring with OUT1 hysteresis function 9 3 2 Limit value monitoring with OUT1 window function 9 3 3 Configure the analogue output for temperature 9 3 4 Configure the frequency signal for temperature 9 4 User settings optional RN 9 4 1 Set the standard unit of measurement for volumetric flow 9 4 2 Configuration of the standard
11. ary The sensor has the function of a non return valve The sensor head can be rotated by 360 gt Do not install the unit on ferromagnetic materials Ferromagnetic materials are all metals exerting an attractive force on test magnets gt Do not operate the unit in the vicinity of magnetic constant and alternating fields e g welding systems gt If the sensors are installed side by side observe a minimum distance of 50 mm between the sensor axes 6 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply according to EN 50178 SELV PELV gt Disconnect power gt Connect the unit as follows BK black BN brown BU blue WH white Colours to DIN EN 60947 5 2 Sample circuits 1 x positive switching 1 x analogue 1 x negative switching 1 x analogue 1 BN 1 BN L 2 WH 4 BK 4 BK 2 WH 3 BU 3 BU L wo L e Switching signal limit values for volumetric flow quantity e Switching signal limit values for temperature Frequency signal for volumetric flow quantity Frequency signal for temperature e O Link Pin 4 OUT1 Pin 2 Analogue signal for volumetric flow quantity OUT2 Analogue signal for temperature 10 7 Operating and display elements 1 2 Indicator LEDs LED 1 switching status OUT1 lights if output 1 is switched
12. constant E When set to the window function the set and reset points have a fixed hys teresis of 0 25 of the final value of the measuring range This keeps the switching status of the output stable if the volumetric flow varies slightly 4 2 Analogue function The unit provides an analogue current signal that is proportional to the volumetric flow quantity and the medium temperature Within the measuring range the output signal is between 4 and 20 mA Outside the measured and displayed value range or in case of a fault the signals 4 mA or 20 mA are provided Figures Caption Output current in mA Volumetric flow quantity final value of the measuring range MEW 100 Medium temperature Measuring range Display range The unit is in the error state FOU OFF The process value transmitted in an analogue way is therefore above the display range The unit is in the error state FOU ON cO gt A Volumetric flow monitoring 0 100 2 MEW B Temperature monitoring 4 3 Frequency output The unit provides a frequency signal that is proportional to the volumetric flow quantity and the medium temperature Up to the limit value set under FEP1 for OUT1 TEMP between the limit values set under FSP1 and FEP1 the frequency signal is between 0 Hz and the fre quency value set under FrP1 130 120 96 FrP1 100 FSP1 100 120 130
13. edium temperature 4 Function The unit detects the volumetric flow quantity based on the principle of differen UK tial pressure The unit features an IO Link interface and is designed for full bidirectional communication The unit displays the current volumetric flow quantity or temperature It gener ates 2 output signals according to the parameter setting OUT1 IO Link 4 selection options Parameter setting Switching signal limit values for volumetric flow 9 2 1 9 22 quantity or switching signal limit values for temperature 9 3 1 2 9 3 2 or frequency signal for volumetric flow quantity 9 2 4 or frequency signal for temperature 9 3 4 OUT2 2 selection options Parameter setting Analogue signal for volumetric flow quantity 9 2 3 or analogue signal for temperature 9 3 3 4 1 Switching function OUT1 changes its switching status if it is above or below the set switching limits flow or temperature Hysteresis or window function can be selected Example of volumetric flow monitoring Hysteresis function Window function SP set point FH upper limit value IP reset point FL lower limit value HY hysteresis FE window Hno Fno NO normally open Hnc Fnc NC normally closed E When the hysteresis function is set the set point SPx is defined first and then the reset point rPx which must be of a lower value If only the set point is changed the reset point remains
14. ersonal injury and or damage to property can occur Improper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connec tion set up operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator In order to guarantee the correct condition of the device for the operating time it is necessary to use the device only for media to which the wetted materials are sufficiently resistant Technical data The responsibility whether the measurement devices are suitable for the respective application lies with the operator The manufacturer assumes no liability for consequences of misuse by the operator Improper installation and use of the units result in a loss of the warranty claims During installation or in case of a fault housing damage media under high pressure or hot media can leak from the system gt Install the unit according to the applicable rules and regulations gt Ensure that the system is free of pressure during installation gt Ensure that no media can leak at the mounting location during installation gt Equip the unit with suitable protection e g cover to avoid hazard to person nel from leaking media 3 Functions and features The unit monitors liquid media water glycol solutions industrial oils coolants It detects the two process categories volumetric flow or m
15. etric flow or temperature exceeded Measured value between 120 and 130 of the final value of the measuring range UL Below the detection zone of temperature Measured value between 120 and 130 of the final value of the measur ing range Err Unit faulty malfunction Measured value greater than 130 of the final value of the measuring range C Loc Setting pushbuttons locked parameter change rejected Active IO Link communication S Loc Setting pushbuttons locked parameter change rejected Unlock using parameter setting software IOE n Malfunctioning The unit is faulty and must be replaced 24 11 Technical data Technical data and scale drawing at www ifm com 12 Factory setting Parameter Factory setting Usersetting SP1 FH1 LOW 20 pF LOW 9 9 0 0 0 SP1 FH1 TEMP 12 54 F Wem FrP FLOWTEM 105 FSP1 EMP JU CA 1 FEP1 LOW Ho J o RON RON ROW NE INN x T _ x pM O FLOW L min gal min ui FOU 0 FOU g FLOW FLOW The percentage values refer to the final value of the measuring range The values in brackets apply to the SBN2xx designs More information at www ifm com C1
16. nd set the switching function SEL 1 Fno window function normally open 001 Fnc window function normally closed Main menu Select FH1 and set the value at which the output switches Select FL1 and set the value at which the output is reset FL1 9 3 3 Configure the analogue output for temperature gt Select SEL2 and set TEMP Menu CFG SEL2 9 3 4 Configure the frequency signal for temperature gt Select SEL1 and set TEMP Menu CFG gt Select ou1 and set FRQ SEL 1 gt Select FSP1 and set the lower temperature value at which 0 Hz is 001 provided Main menu gt Select FEP1 and set the temperature value at which the frequency set resp4 in FrP1 is provided FEP1 gt Select FrP1 and set the frequency 0 01 kHz 10 kHz FrP 1 9 4 User settings optional 9 4 1 Set the standard unit of measurement for volumetric flow Select uni and set the unit of measurement l min m h SBN2xx gpm Menu CFG gph uni The selectable units of measurement depend on the respective unit 9 4 2 Configuration of the standard display gt Select SELd and determine the standard measuring unit Menu DIS FLOW the current volumetric flow value in the standard unit of SELd measurement is displayed diS TEMP the current medium temperature in C is displayed SBN2xx F gt Select diS and set the update rate and orientation of the display d1 update
17. switches irrespective of the fault as defined with the parameters 2 Frequency output On 130 of FrP1 OFF 0 Hz ou1 frequency signal is provided without any changes Select FOU2 and set the value On output 2 switches ON in case of an error the analogue signal goes to the upper error value OFF output 2 switches OFF in case of an error the analogue signal goes to the lower error value ou output 2 switches irrespective of the fault as defined with the parameters The analogue signal corresponds to the measured value 9 5 Service functions 9 5 1 Read the min max values for the temperature gt Select Hi T or Lo T and read the value Menu MEM HI T max value LO T min value Hi T Delete memory Lo T gt Select Lo T gt Briefly press e gt Keep A or V pressed gt is displayed gt Briefly press e Ed It makes sense to delete the memories as soon as the unit operates under normal operating conditions for the first time 9 5 2 Resetting all parameters to factory setting gt Select rES gt Press e gt Press A or V and keep pressed until is displayed gt Briefly press e El It is recommended to take down your own settings in the table before carrying out the function 12 Factory setting 10 Operation 10 1 Reading the process value The LEDs 1 3 signal which process value is currently displayed
18. t Select SP1 and set the value at which the output is set 5 1 gt Select rP1 and set the value at which the output is reset rP4 18 9 2 2 Limit value monitoring with OUT1 window function Select SEL 1 and set FLOW Menu CFG Select ou1 and set the switching function SEL 1 Fno window function normally open 001 Fnc window function normally closed Main menu Select FH1 and set the value at which the output switches FH1 Select FL1 and set the value at which the output is reset FL 1 9 2 3 Configure the analogue output for volumetric flow gt Select SEL2 and set FLOW Menu CFG 3 SEL2 9 2 4 Configure the frequency signal for volumetric flow gt Select SEL1 and set FLOW Menu CFG gt Select ou1 and set FRQ SEL 1 gt Select FEP1 and set the flow value at which the frequency set in FrP1 001 gt Select FrP1 and set the frequency 0 01 kHz 10 kHz FEP1 FrP1 9 3 Settings for temperature monitoring 9 3 1 Limit value monitoring with OUT1 hysteresis function Select SEL 1 and set TEMP Menu CFG Select ou1 and set the switching function SEL 1 Hno hysteresis function normally open 001 Main menu Hnc hysteresis function normally closed Select SP1 and set the value at which the output is set 5 1 Select 1 and set the value at which the output is reset rP1 Select SEL 1 and set TEMP Menu CFG Select ou1 a