Home

Operating Instructions - VEGADIS 176

image

Contents

1. Fig 11 Display and adjustment elements of VEGADIS 176 Symbol adjustment menu locked Symbol error Symbol upper lower range Adjustment keys 14 segment display for unit TAG Bargraph with marks for lower and upper range 5 digit 7 segment display for measured value N OA DA The adjustment is carried out via three buttons on the housing front Key Function Adjustment key Invoke the adjustment menu Confirm selection Adjustment of parameters in the adjustment menu Plus minus buttons Selection and adjustment change of values in the adjustment menu Pushing and simultaneously will cause a reset to the nixt higher menu level without saving the adjusted value ESC The device setup can be locked with a 4 digit user code When the setup is locked a lock symbol is displayed when invoking an adjust ment parameter The adjustment functions of the process indicator are structured in the following menus The individual parameters and settings are described in chapter Setup The display in the 7 segment indication can only display figures and not alphanumerical signal Hence the procedure with number and text parameters is different Number parameters If an adjustment position contains only numbers as a paramter then the adjustment position is shown in the 14 segment display and the VEGADIS 176 Digital indicating instrument without exter
2. 6 2 Parameter adjustment Menu Setup In this menu item you specify the number of decimal points for the indication Value range 0 DEC 1 DEC 2 DEC 3 DEC 4 DEC In this menu item you specify the 5 digit number value number of decimal points as set unter DECIM for the scaling of the measured value at 4 mA Example SC__4 0 0 means display 0 0 with measurement current 4 mA The unit selected under UNIT is used in the display Value range 19 999 99 999 14 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060Yv L N3 916Zt 47916 EN 140903 VEGA 6 Setup Setup SC 20 Setup UNIT Setup TEXT Diagnosis AERR Diagnosis LERR Diagnosis FWVER SYSTM UCODE SYSTM FRSET In this menu item you specify the 5 digit number value number of decimal points as set unter DECIM for the scaling of the measured value at 20 mA Example SC__20 100 0 means display 100 0 with measurement current 20 mA The unit selected under UNIT is used in the display Value range 19 999 99 999 In this menu item you select the unit for the display By the adjust ment USER a user selectable unit can be entered in the parameter TEXT Value range C F K USER By setting USER in UNIT a user selectable unit can be entered Value range Free text 5 digit 6 3 Parameter adjustment Menu Diagnosis In this menu item acutally
3. ssssssessssessese eene 7 4 Mounting 44 QGeneralinstr ctions eee eic eee tee debate aee i e b t ei edd 9 42 Mounting preparations iiti ot cereo ecd co D rb eise Exe RR eR Ee eni deg ds 9 43 Mounting Steps erm pen eere ndr er e Eee vas E rapran erari 9 5 Connect to the signal circuit 5 Preparing the COhniectlOm oorr nce cn Fi ta tienen aii re o e nip einen 10 5 2 Connection technology and Steps ruere trn dep iet ira e Ee Fe ad 10 5 3 Wiring plan A 5 4 Swilch on phaser rrr er ee PEDE SER rr PUENTE A TENERE RTE 12 6 Setup 6 1 lIndication and adj stimient ntn rne ess 13 6 2 Parameter adjusiment Menu Setup enc t tinc endo c er rie ta 14 6 3 Parameter adjustment Menu Diagnosis ccsssssecseccessvsessseccesseesnsesseecessansseseses 15 6 4 Parameter adjustment Menu Expert sssssssssseseeeeeeen ener nnne en 15 7 Maintenance and fault rectification Tkt Maintenanee niouate etai fac cac Hee R CURE RR DEI Erra VAE HE R SAA EXP czuacves vsseatdaiee IRURE REPE EUR DD 17 7 2 Rectify faults ET 7 8 How to proceed if a repair is needed eese eese ener nennen nnne 18 8 Dismount 8 1 Dismounting steps ssssssesesssseeeseeeeene nennen enennen enhn ennt enne ne nnne ns ener nennen nen 19 82 DISPOSAL me e cs ccc sce castes aa e canes yee cteaues xevscescatacate estates ea a a sass 19 9 Supplement 9 42 Techhicaldala
4. Relating to the measuring range 2 Relating to the measuring range VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 21 9 Supplement VELA 9 3 Industrial property rights VEGA product lines are global protected by industrial property rights Further information see WWW Vega com Only in U S A Further information see patent label at the sensor housing VEGA Produktfamilien sind weltweit gesch tzt durch gewerbliche Schutzrechte N here Informationen unter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de productos est n protegidas por los derechos en el campo de la propiedad indus trial Para mayor informaci n revise la pagina web www vega com Jluuna npogykynn cbupmb BETA 3auujarorcs no BceMy Mupy npaBaMM Ha MHTeTITIEKTyaTIBHylO co6crBeHHOCTb JanbHeliwyto uHcbopmaunuto cvorpure Ha calire www vega com VEGAJXK JI MELREA ARERR 3t 3 fe amp iB 2 A Y lt www vega com 9 4 Trademark All the brands as well as trade and company names used are property of their lawful proprietor originator 22 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060 L N3 916Zt 47916 EN 140903 Notes VEGADIS 176 Digital indicating instrument without external energy for fro
5. gez 92 mm gk 3 62 IS Required tools e Slotted screwdriver 4 3 Mounting steps Proceed as follows 1 Insert the instrument from the front into the cut opening 2 Attach mounting clips laterally on the housing 3 Tighten threaded rods steadily with the screwdriver VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 9 5 Connect to the signal circuit VEGA Note safety instructions Take note of safety instructions for Ex applications Connection technology Connection procedure Terminal assignment 5 Connect to the signal circuit 5 1 Preparing the connection Always keep in mind the following safety instructions e Connect only in the complete absence of line voltage In hazardous areas you must take note of the respective regulations conformity and type approval certificates of the sensors and power supply units 5 2 Connection technology and steps The voltage supply and signal output are connected via the spring loaded terminals in the housing Proceed as follows 1 Remove approx 10 cm 4 in of the cable mantle strip approx 1 cm 0 4 in of insulation from the ends of the individual wires D gi on Fig 4 Connection steps 2 and 3 2 Solid cores as well as flexible cores with cable end sleeves are inserted directly into the terminal openings 3 In case of flexible cores without end
6. 4 0 0 SC 20 100 0 UNIT TEXT EXPRT SYSTM UCODE 0000 FRSET NO INPUT DECIM 1 DEC SC 4 0 0 SC 20 100 0 UNIT 926 TEXT CURVE LINAR NAMUR YES RNGLO 03 80 RNGHI 20 00 OFFST 0 0 INPUT CURVE Selection of the linearization curve for the measurement current With this parameter the instrument can be adapted to a linear or square measurement signal Value range LINAR SQRT INPUT NAMUR Specification of the error limits according to standard NAMUR NE 43 Value range YES NO INPUT RNGLO Lower range limit If the measured current falls below this limit an error message is outputted Only visible with NAMUR NO Value range 00 00 99 99 INPUT RNGHI Upper range limit If the measured current exceeds this limit an error message is outputted Only visible with NAMUR NO Value range 00 00 99 99 INPUT OFFST Entering an offset value for indication of the measured value Value range 19999 99999 16 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 0607 L N3 916Z2t 47916 EN 140903 7 Maintenance and fault rectification Causes of malfunction Fault rectification Check the 4 20 mA signal 9 Error limits NAMUR NE 43 Sensor diagnosis 7 Maintenance and fault rectification 7 1 Maintenance If the instrument is used properly no special maintenance is required in normal operation 7 2 Rectify faults VEGADIS 176 offers maximum reliability N
7. sleeves press the terminal from above with a small screwdriver the terminal opening is then free When the screwdriver is released the terminal closes again Information You can find further information on the max wire cross section under Technical data Electromechanical data 4 Checkthe hold of the wires in the terminals by lightly pulling on them 5 Connect screen to the potential equalisation terminal 5 3 Wiring plan The terminals are on the rear of the housing 1 2 3 4 5 COICO Fig 5 Terminal assignment VEGADIS 176 10 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060Yv L N3 916Z2t 47916 EN 140903 5 Connect to the signal circuit Connection to passive sensors Connection to passive sensors with backlight Terminal Function Polarity Notes 1 Output sensor Display with back light 2 Output sensor 3 Output sensor Bridged internally with terminal 4 4 Input voltage sup Bridged internally ply with terminal 3 5 Input voltage sup ply The terminal for the potential equalisation is also on the rear of the instrument Fig 6 Potential equalisation VEGADIS 176 1 Potential equalisation terminal 1 2 3 4 5 LLO oo 290 Fig 7 Wiring plan VEGADIS 176 to passive sensors 1 Tothe sensor 2 Topower su
8. teet ee e trt eee ete tite dissect estne 20 9 2 Dimensions rmn enim mn ri enr i i niri Era eir rn 21 2 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 0607 L N3 9162t 47916 EN 140903 VEGA Contents Safety instructions for Ex areas Please note the Ex specific safety information for installation and op x eration in Ex areas These safety instructions are part of the operating instructions manual and come with the Ex approved instruments Editing status 2014 08 05 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 3 1 About this document VEGA FO D peme 1 About this document 1 1 Function This operating instructions manual provides all the information you need for mounting connection and setup as well as important instruc tions for maintenance and fault rectification Please read this informa tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device 1 2 Target group This operating instructions manual is directed to trained specialist personnel The contents of this manual should be made available to these personnel and put into practice by them 1 3 Symbols used Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result Warning If this warning is ignor
9. 13 140 F 40 85 C 13 185 F Class B 2 according to EN 60654 1 1 5 mm AWG 16 0 5 mm AWG 21 LC display 5 digit 17 mm 0 67 in 19999 up to 99999 3 keys E 30V DC Voltage drop with current value 4 20 mA Without lighting max With lighting max Current range Overcurrent resistance HART signal 1 0V 2 9V 3 6 22 MA 200 mA fuse protection supply side Not influenced HART transparent 20 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 0607 L N3 916Z2t 47916 EN 140903 VEGA 9 Supplement Deviation Deviation Signal resolution Influence of the ambient temperature Reference temperature Start up time Electrical protective measures Protection rating Front side Rear side Protection class Overvoltage category Approvals lt 0 1 gt 13 bit lt 0 1 10 K 25 C 5 C 77 C 9 C 10 min IP 65 IP 20 IH Il degree of pollution 2 Instruments with approvals can have different technical specifications depending on the version For that reason the associated approval documents of these instruments have to be carefully noted They are part of the delivery or can be downloaded under www vega com via VEGA Tools and Instrument search as well as via Downloads and Approvals 9 2 Dimensions VEGADIS 176 43 mm Fig 15 VEGADIS 176
10. Operating Instructions VEGADIS 176 Digital indicating instrument without external energy for front panel mounting BH Document ID 47916 Contents VEGA Contents 1 About this document Tet FUNCUOM ETATE DETROIT DII 4 1 2 Targat group sssr nnns anaa eaa e cea e fe sare ta diane eed ted vic en Da 4 T 3 Symbols used niei bee re ee Pe red ee a ade do ede anes 4 2 For your safety 25 Authorised persotllniel 2 2 arret aei ores censentur en tua ee ec esent Des EOE eap Enies CEEE 2 2 Appropriate lise cns tt tae e essen eren sc tee Fee eare issue te festes ben eet usb rues epe E 2 3 Warning about incorrect use 24 General Safety inslructions iecore terrena Ee bY eas eee ELE RE NER Usu 6 eean KEE aaia iti ENES 2 5 Safety label on the instrument visics ssccsceesiscscscsssessaessessecssssessseconcecstesseisessessansssseesetessaesseiees 5 2 6 CE conformity 27 NAMUR recommendations sco coerente rientra teret aa ior Pe Dona d EXE sube ER EE ORE Ero ua E ERE 6 2 8 Environmental inStructions cus eoo ee oocrc titer epe oe baa eoe eee E EXE pube SERRE RE av aN Ean E ERR 6 3 Product description 3 4 COMPIQUIATION 2 eee eee e cee ccee cece cee eeesaeeeeeceaeeeaeeeaeeecaeecaeeseeecesaessaeseeecaeeeeesessesaeeeneeeesees 7 3 2 Principle Of operation sessssssssssssssseeeeeee ener nnne enhn nt nennen etn nne n ennt nnn n nennen 7 3 3 Operation 3 4 Packaging transport and storage
11. action after fault recti Depending on the reason for the fault and the measures taken the fication Steps described in chapter Set up may have to be carried out again 7 3 How to proceed if a repair is needed You can find a repair form as well as detailed information on how to proceed at www vega com downloads and Forms and certificates By doing this you help us carry out the repair quickly and without hav ing to call back for needed information If a repair is necessary please proceed as follows e Printand fill out one form per instrument e Cleanthe instrument and pack it damage proof e Attach the completed form and if need be also a safety data sheet outside on the packaging e Please contact the agency serving you to get the address for the return shipment You can find the agency on our home page WWW Vega com 18 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 0607 L N3 916Zt 47916 EN 140903 8 Dismount 8 Dismount 8 1 Dismounting steps Take note of chapters Mounting and Connecting to power supply and carry out the listed steps in reverse order 8 2 Disposal The display and adjustment module consists of materials which can recycled by specialised recycling companies We have purposely designed the components to be easily separable WEEE directive 2002 96 EG This display and adjustment module is not subject to the WEEE directive 2002 96 EG an
12. d the respective national laws in Germany e g ElektroG Pass the display and adjustment module directly on to a specialised recycling company and do not use the municipal collecting points These may only be used for privately used products according to the WEEE directive Correct disposal avoids negative effects on humans and the environ ment and ensures recycling of useful raw materials Materials see chapter Technical data If you have no way to dispose of the old instrument properly please contact us concerning return and disposal VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 19 9 Supplement 9 Supplement 9 1 Technical data General data Materials Housing front Housing Rear of the housing Inspection window of the indication Installation position Weight approx Ambient conditions Ambient temperature Function range Read area Storage and transport temperature Climatic class Electromechanical data Terminals for wire cross section up to solid flexible Strand with end sleeve and plastic sleeve Display and adjustment elements Indication Height of figures Indication range Adjustment elements Signal and supply circuit Operating voltage via 4 20 mA circuit max Aluminium Sheet steel galvanized Polycarbonate PC Horizontally 0 3 kg 0 661 Ibs 40 60 C 40 140 F 25 60 C
13. ed injury to persons and or serious damage to the instrument can result Danger If this warning is ignored serious injury to persons and or destruction of the instrument can result Ex applications This symbol indicates special instructions for Ex applications SIL applications This symbol indicates instructions for functional safety which must be taken into account particularly for safety relevant applications List The dot set in front indicates a list with no implied sequence Action This arrow indicates a single action Sequence of actions Numbers set in front indicate successive steps in a procedure Battery disposal This symbol indicates special information about the disposal of bat teries and accumulators 4 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060 L N3 916Zt 47916 EN 140903 2 For your safety 2 For your safety 2 1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator During work on and with the device the required personal protective equipment must always be worn 2 2 Appropriate use VEGADIS 176 is a digital indicating instrument for 4 20 mA circuits 2 3 Warning about incorrect use Inappropriate or incorrect use of the instrument can give rise to application specific hazards e g vessel overfill or damage
14. ent VEGADIS 176 e Mounting material e Documentation this operating instructions manual Ex specific safety instructions with Ex versions if necessary further certificates 3 2 Principle of operation VEGADIS 176 is a digital indicating instrument for measured value indication in 4 20 mA circuits The measured value is displayed via the LC display the digital indication can be scaled The instrument is suitabe for front panel mounting L3 Fig 1 Connection of VEGADIS 176 to the sensor 1 Voltage supply Signal output sensor 2 VEGADIS 176 3 4 20 mA signal cable 4 Sensor VEGADIS 176 is looped directly into the 4 20 mA circuits and requires no separate external energy Connection is carried out via a detachable plug with spring loaded terminals in the housing 3 3 Operation Adjustment is carried out via keys in the front plate of the instrument 3 4 Packaging transport and storage Your instrument was protected by packaging during transport Its capacity to handle normal loads during transport is assured by a test based on ISO 4180 The packaging of standard instruments consists of environment friendly recyclable cardboard For special versions PE foam or PE VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 7 3 Product description VEGA Transport Transport inspection Storage Storage and transport temperature fo
15. evertheless faults can oc cur during operation These may be caused by the following e g e Sensor e Process e Voltage supply e Signal processing The first measure is to check the sensor output signal according to the operating instructions manual of the respective sensor In many cases the reasons can be determined this way and faults rectified System errors of VEGADIS 176 are displayed via the system error message of the following chart Connect a multimeter in the suitable measuring range according to the wiring plan Error code Cause Rectification 4 20mA Wrong connection to Check and correct if necessary ac signal miss voltage supply cording to chapter Wiring plan ing No power supply Check cables for breaks repair if necessary Operating voltage Check adapt if necessary too low or load resist ance too high In Ex applications the regulations for the wiring of intrinsically safe circuits must be observed The instrument can be adjusted to error limits according to NAMUR NE 43 If one of these values is violated then the instrument displays a diagnosis code Error limit with current value Error Diagnosis code 1 lt 3 6mA Lower range F100 3 6 mA lt lt 3 8 mA Unpermitted measured S901 value 20 5 mA lt lt 21 0 mA Unpermitted measured S902 value 221mA Upper range F100 The instrument has diagnosis functions for the senso
16. il is also used Dispose of the packaging material via specialised recycling companies Transport must be carried out in due consideration of the notes on the transport packaging Nonobservance of these instructions can cause damage to the device The delivery must be checked for completeness and possible transit damage immediately at receipt Ascertained transit damage or con cealed defects must be appropriately dealt with Up to the time of installation the packages must be left closed and stored according to the orientation and storage markings on the outside Unless otherwise indicated the packages must be stored only under the following conditions e Notin the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see chapter Supplement Technical data Ambient conditions e Relative humidity 20 85 8 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060 L N3 916Zt 47916 EN 140903 VEGA 4 Mounting 4 Mounting 4 1 General instructions Mounting location instal The instrument is designed for use in a front panel The installation lation position position is horizontal 4 2 Mounting preparations Prepare panel cut out 92 x 45 mm 3 62 x 1 77 in according to illus tration and DIN 43700 Max panel thickness 13 mm 0 51 inch Yj
17. nal energy for front panel mounting 13 6 Setup VEGA Adjustment menu Setup DECIM Setup SC_4 adjusted parameter in the 7 segment display Push the E key for editing and then enter the user code Text parameters If the adjustment position contains text parameters then first only the adjustment position is displayed in the 14 segment display After pushing the E key again the adjusted parameter is shown in the 14 segment display For editing push the key and finally enter the user code Return The return is carried out e Atthe end of the individual menus and menu points with Back and pushing the E key to the next higher menu level e After pushing and simultaneously see table on top to the next higher menu level up to the measured value indication e Automatically 10 min after the last key pressing to the measured value indication In all cases the EXPRT menu is again locked Note If the adjustment menu is locked by a user code the individual menus and parameters can be displayed but not modified To modify a pa rameter the user coded has to be entered The following table shows the menu structure Menu Function Description SETUP Setup Fundamental device set tings DIAG Diagnostics Device information indi cation of error messages EXPRT Expert Expert settings for the device setup Editing in the menu Expert is protected through an access code Default 0000
18. nt panel mounting 23 Printing date VEGA All statements concerning scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior notice C 47916 EN 140903 VEGA Grieshaber KG Schiltach Germany 2014 VEGA Grieshaber KG Phone 49 7836 50 0 Am Hohenstein 113 Fax 49 7836 50 201 77761 Schiltach E mail info de vega com Germany www vega com
19. occurring diagnosis messages Actual Error are displayed If the several message appear together the mes sage with the highest priority will be displayed In this menu item the last diagnosis message Last Error with the highest priority is displayed In this menu item the firmware version is displayed 6 4 Parameter adjustment Menu Expert The menu Export contains in addition to all menu items from the menu Setup also the submenus and menu items described here When invoking the expert menu the user code will be enquired UCODE Default 0000 With the user code the device setup can be protected against unau thorized modifications When the setup is locked the lock symbol will be displayed when invoking an adjustment parameter With default setting 0000 the user code is not active i e parameters in the setup can be modified without entering the code For the expert menu the code must always be entered also with default setting Value range 0000 9999 Resetting the device setup to default values By selecting YES and confirming with the E key the instrument will be reset Value range YES NO The following table shows the default values after a reset VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 15 VEGA 6 Setup Menu Submenu Menu item Default values SETUP DECIM 1 DEC SC
20. pply or the processing system OJOOOO 5 Fig 8 Wiring plan VEGADIS 176 to passive sensors with backlight 1 To the sensor 2 To power supply or the processing system VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 11 5 Connect to the signal circuit Connection to active sensors Connection to active sen sors with backlight Fig 9 Wiring plan VEGADIS 176 to active sensors 1 To the sensor 1 55 T Fig 10 Wiring plan VEGADIS 176 to active sensors with backlight 1 Tothe sensor 5 4 Switch on phase After connecting the instrument to voltage supply or after voltage recovery the instrument carries out a self check for approx 10 s and then displays the following e All display segments e Firmware version e g 1 02 00 e Status message e g S901 Then the actual measured value will be displayed You can find further information of the presentation in chapter Parameter adjustment Menu Setup 12 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060 L N3 916Zt 47916 EN 140903 VEGA 6 Setup Display and adjustment elements Adjustment system 6 Setup 6 1 Indication and adjustment bs 9 Ona
21. r If an error is detection the instrument wil display a diagnosis code VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 17 7 Maintenance and fault rectification VEGA Diagnosis code Short text Rectification measure F100 Sensor error Check electrical wiring Check sensor Check sensor parameter adjustment S901 Input signal toolow Check sensor output on z defect and deviation of char S902 Input signal too high actoristic Check sensor parameter adjustment Electronics diagnosis The instrument has diagnosis functions for the own electronics If an error is detected a diagnosis message will be displayed Diagnosis code Short text Rectification measure F261 Electronics module Replace electronics F283 Memory content Restart instrument Carry out device reset Replace electronics F431 Factory calibration Replace electronics Configuration diagnosis Diagnosis code Short text Rectification measure M561 Display exceeded Check scaling 24 hour service hotline Should these measures not be successful please call in urgent cases the VEGA service hotline under the phone no 49 1805 858550 The hotline is manned 7 days a week round the clock Since we offer this service worldwide the support is only available in the English language The service is free only standard call charges are incurred Re
22. to system components through incorrect mounting or adjustment 2 4 General safety instructions This is a state of the art instrument complying with all prevailing regulations and guidelines The instrument must only be operated in a technically flawless and reliable condition The operator is responsible for the trouble free operation of the instrument During the entire duration of use the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula tions The safety instructions in this operating instructions manual the na tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user For safety and warranty reasons any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer Arbi trary conversions or modifications are explicitly forbidden The safety approval markings and safety tips on the device must also be observed 2 5 Safety label on the instrument The safety approval markings and safety tips on the device must be observed 2 6 CEconformity The device fulfills the legal requirements of the applicable EC guide lines By affixing the CE marking we confirm successful testing of the product You can find the CE Certificate of Conformity in the do
23. wnload section of our homepage VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 5 2 For your safety VEGA 2 7 NAMUR recommendations NAMUR is the automation technology user association in the process industry in Germany The published NAMUR recommendations are accepted as the standard in field instrumentation The device fulfills the requirements of the following NAMUR recom mendations e NE21 Electromagnetic compatibility of equipment e NE 43 Signal level for malfunction information from measuring transducers For further information see www namur de 2 8 Environmental instructions Protection of the environment is one of our most important duties That is why we have introduced an environment management system with the goal of continuously improving company environmental pro tection The environment management system is certified according to DIN EN ISO 14001 Please help us fulfill this obligation by observing the environmental instructions in this manual e Chapter Packaging transport and storage e Chapter Disposal 6 VEGADIS 176 Digital indicating instrument without external energy for front panel mounting 060 L N3 916Zt 47916 EN 140903 VEGA 3 Product description Scope of delivery Application area Voltage supply Packaging 3 Product description 3 1 Configuration The scope of delivery encompasses e Digital indicating instrum