Installation and operating instructions: Radio-control

image

Contents

1. approx 2 minto 1h Brightness approx 3 2000 Ix Temperature range 0 C to 45 C Type of protection IP 20 Dimensions Diameter 103 mm Height 42 mm Digital Addressable Lighting Interface The international digital interface standard for the lighting industry Date 13 09 02 Combined Sensor ADVANCED Version 1 0 Subject to change without notice Errors and omission excepted Page 12 Installation instructions Combined Sensor DALI LS PD ADVANCED
2. DVANCED central unit Programmed devices can be deleted via the MPU gt see the operating instructions for the manual programming unit Page 6 Installation instructions Combined Sensor DALI LS PD ADVANCED OSRAM amp 4 Installation Electrical equipment may only be installed by qualified electricians The combined sensor is mounted on the ceiling and monitors an area directly beneath it Fig B The brightness value measured on the combined sensor comprises the reflected artificial lightD and daylight and depends on the reflective properties of the surface Fig C Fig B Fig C eee 1 7m 2 5m ba 4 Make sure the sensor is positioned so that sunlight does not shine directly on it If required the detection area can be restricted by means of the shield supplied see 4 Detection area and shield Do not install the combined sensor in the immediate vicinity of any heat sources such as luminaires or radiators fans or ventilation shafts Lamps that are cooling down and air movements caused for example by open windows may be detected and lead to unwanted activation of the lighting system Installation Abb D 1 Attach the base plate to the ceiling with the screws provided Fig D 2 Turn the combined sensor anticlockwise through approx 45 on the base plate until it clicks into place Important Do not attach the combined sensor to the base plate u
3. OSRAM Installation and operating instructions Radio control combined sensor Type DALI LS PD ADVANCED Chat OSRAM GmbH Hellabrunner Str 1 D 81536 Munich Tel 49 0 89 6213 0 Fax 49 0 89 6213 2020 Customer Service Center KSC Germany Albert Schweitzer Str 64 D 81735 Munich Tel 49 0 1803 677 200 Fax 49 0 1803 677 202 www osram com OSRAM Page 2 Installation instructions Combined Sensor DALI LS PD ADVANCED Contents 1 Function OVErVICW ccccccccsesecceeeeecceeesesseaeeessaneeeenes Page 4 2 Activating the sensor inserting the batteries Page 5 3 Programming in the DALI ADVANCED central unit Page 6 4 nstallallon ansssesnee a Page 7 5 Detection area and Shield 400ne nn Page 8 6 Adjustment of the sensor 00nn44 nenn nnnnnneee nn Page 9 7 Lighting control setpoint adjustment Page 9 8 Notes on radio operation ccccceeeeeeeeeeeeeeeeeeeeeeeeees Page 11 9 Technical data neuen Page 12 Installation instructions Combined Sensor DALI LS PD ADVANCED Page 3 OSRAM 1 Function overview The radio control combined sensor maximises energy savings by combining presence controlled lighting with daylight dependent control It comprises a passive infrared sensor PIR which reacts to the movement of heat and therefore to the presence of people and also a light sensit
4. The range of the transmitter up to 100 m in the open depends on the height at which it is installed and on the nature of the building Dry material Penetration Wood plaster plasterboard approx 90 Brick MDF approx 70 Reinforced concrete approx 30 Metal metal grating aluminium approx 10 cladding Fig L OSRAM cE 07000 Notes on radio operation This radio system may only be connected to other communication networks if this does not infringe the relevant national laws This radio system may not be used for communicating beyond property boundaries If operated in Germany the regulations contained in Official Bulletin Vfg 73 2000 must be met If used as specified this device complies with the requirements of the R amp TTE directive 1999 5 EU A complete conformity declaration can be found on the internet at www osram com The combined sensor may be operated in all EU and EFTA states Installation instructions Combined Sensor DALI LS PD ADVANCED Page 11 OSRAM 9 Technical data Rated voltage 6VDC Batteries 4x 1 5 V AAA LRO3 alkaline Do not use zinc carbon batteries R 03 or rechargeable batteries Transmission frequency 433 42 MHz Modulation ASK Range max 100m in the open Radio codes gt 1 billion Detection angle 360 Nominal range at desk level approx 5m at floor level approx 8m Installation height for nominal range 2 5m Delay time
5. damaging the electronics through electrostatic discharge you must comply with the safety precautions for electrostatically sensitive devices when changing the battery Inserting replacing the batteries 1 Detach the combined sensor from the base plate by turning the unit approx 45 clockwise Fig C 2 Remove any old batteries Wait about 2 minutes before inserting the new batteries Make sure they are the right way round Fig D 3 Attach the combined sensor to the base plate again by turning the unit about 45 anticlockwise until it clicks in place 4 For the first 30 seconds after batteries are inserted the combined sensor sends special programming telegrams Fig C Fig D 45 A Flat battery indicator The LED integrated behind the sensor window Fig A1 can only be seen in darkness It flashes three times whenever a transmission is made If the LED flashes about ten times this indicates that the batteries are almost flat LowBatt and have to be replaced Important Keep batteries away from children If a battery is swallowed seek medical attention immediately Replace the batteries with ones of the same type Old batteries should be removed immediately and disposed of properly Installation instructions Combined Sensor DALI LS PD ADVANCED Page 5 OSRAM 3 Programming in the DALI ADVANCED central unit The combined sensor must b
6. e programmed for lighting control in the central unit so that the central unit can identify the sensor as part of its system The actual function of the sensor is assigned to the central unit by the manual programming unit MPU A combined sensor can only be assigned to one group of the lighting control system A maximum of eight combined sensors or light sensors can be integrated in the system Procedure 1 Remove the batteries from the combined sensor 2 On the manual programming unit MPU start the radio startup programming mode 3 Put the batteries back in if programming wait for 2 minutes before doing so The sensor will now transmit special programming telegrams for approx 30 seconds to which the manual programming unit will react presence sensor found On the MPU enter the number of the luminaire group to be controlled by this sensor 4 Terminate the radio startup procedure on the MPU This completes the programming process Notes When you enter the group on the MPU the message programming will appear This message does not disappear until the light sensor stops sending programming telegrams up to 30 seconds after the battery has been inserted During this time no other functions can be performed by the system We recommend that you label the combined sensor with the device number indicated on the MPU and enter this number in the documentation for the lighting system Deleting the device in the DALI A
7. ive resistor that measures the luminance in a defined detection area The sensor forwards this dual information brightness and presence to the DALI ADVANCED central unit The data is evaluated in the central unit and the lighting system controlled accordingly When movement is detected the combined sensor switches the luminaires of the relevant group on and automatically starts controlling the lighting level Lighting control remains active as long as the sensor detects movement When movement is no longer detected the lighting system is switched off after a user definable delay The lighting system is also switched off if a brightness threshold is exceeded Abb A The combined sensor consists of the following z Sensor window with LED below it 5 Decorative ring lt lt Base plate Light sensor Under the decorative ring there are three controls Sensitivity of the motion detector Delay for switching off the system ane time if no movement is detected ADIB NM in in Not used here moo i The setpoint value is assigned via the manual programming unit Page 4 Installation instructions Combined Sensor DALI LS PD ADVANCED OSRAM amp 2 Activating the sensor inserting the batteries Battery type The combined sensor is operated on four AAA LR 03 alkaline batteries not included Do not use zinc carbon batteries R 03 or rechargeable batteries To avoid
8. ntil you have inserted the batteries and programmed the sensor in the central unit Installation instructions Combined Sensor DALI LS PD ADVANCED Page 7 OSRAM 5 Detection area and shield The motion sensor has a detection angle of 360 The PIR sensor operates with six detection levels and 80 lenses If installed at a height of 2 5 m the sensor will have a detection area approx 5 m in diameter at desk level approx 80 cm Fig E The diameter at floor level is approx 8 m The detection area is increased if the sensor is mounted higher but this reduces the detection density Fig F and the sensitivity of the sensor Fig F 0 8m Shield You can use the shield supplied to mask off areas that you do not wish the sensor to cover The shield is simply placed over the sensor window Trim the shield only along the lines marked Fig G The following information relates to an installation height of approx 2 50 m giving a detection field diameter of approx 8 m at floor level Trimming changes the diameter of the detection field at floor level as follows Complete shield area approx 2 20 m Abb G Area Il trimmed approx 4 00 m Areas Il and III trimmed approx 6 00 m No shield approx 8 00 m Page 8 Installation instructions Combined Sensor DALI LS PD ADVANCED OSRAM amp 6 Adjustment of the sensor To change the delay or the sensitivity you must first remove the decorati
9. smitter has been pressed short press The lighting system is switched to 100 and the brightness is then adjusted to the setpoint stored in the central unit If the measured brightness value exceeds the current brightness setpoint at the minimum dimmer setting for the luminaires by a considerable margin the relevant group is automatically switched off The group will also be switched off if no movement is detected during the time set on the time control The lighting system can be switched off manually at any time by pressing a suitably programmed channel button Note When the system is operated for the first time and after any interruption to the power supply the assigned group must be switched on by briefly pressing a suitably programmed channel button Only then will movement detection and lighting control be available Please note the following If the lighting system was switched off because the brightness level was too high If movement is detected the lighting control will automatically switch the lighting system back on if the measured brightness is below the setpoint e g if the weather becomes overcast If the delay time has expired because there has been no movement the lighting system will not be switched on again If the lighting system was switched off because of a lack of movement As soon as movement is detected again the lighting system is switched on at 100 and lighting control is activated If the lighting system was
10. switched off by means of a programmed channel button Only after the delay time has expired will the lighting system be switched on again in response to movement This ensures that when someone switches the lighting off manually intentionally it is not automatically switched on again because the person is still in the room Terminating control If the lighting level of the regulated group is changed faded up or down using a programmed channel button on a wall mounted or hand held transmitter lighting control is terminated and the lighting value set manually is retained The same applies when a lighting scene involving the regulated group is selected Control is restarted if a suitably programmed channel button is used to switch the relevant group on or to maximum brightness short press Note If lighting control is terminated by manually adjusting the lighting system the lighting system will not be switched off automatically if no movement is detected In this case use one of the suitably programmed channel buttons to switch the lighting system off manually when you leave the room Page 10 Installation instructions Combined Sensor DALI LS PD ADVANCED OSRAM 8 Notes on radio operation A non exclusive transmission path is used for radio transmission which means that interference cannot be ruled out Radio transmission is not suitable for safety applications such as emergency shutdown or calls to the emergency services
11. ual programming unit Setting the brightness setpoint Abb The luminance measured on the combined sensor 2 2 Fig comprises the reflected artificial light x Sse O and daylight and depends on the reflective properties FIN ofthe surface It is transmitted as a brightness value at regular intervals to the central unit for evaluation If the setpoint is changed this brightness value ai is stored in the central unit as the setpoint for lighting control Changing the setpoint Select Regulation in the Lighting Control menu on the manual programming unit Enter the number of the group to be controlled You can now change the setpoint Adjust the lighting to the required setting and select Change Setpoint The message waiting for brightness value will appear The next brightness value that the combined sensor sends is stored as the new setpoint in the central unit Setpoint changed This process may take up to 90 seconds Activate lighting control by switching the Regulation option to ON Note As long as there is a radio link between the central unit and the manual programming unit lighting regulation will not be carried out Installation instructions Combined Sensor DALI LS PD ADVANCED Page 9 OSRAM Lighting control Lighting control is active if the relevant group has been switched on because movement has been detected or a programmed channel button on a wall mounted or hand held tran
12. ve ring Fig H from the combined sensor This gives you access to the following controls Abb H sens sens time lux Use this control to adjust the sensitivity of the motion detector A A First set the control to maximum sensitivity a If the sensor is too sensitive turn the control back toward min Note At minimum sensitivity the presence sensor lt 5 J J is effectively switched off 0 time This control enables you to make fine adjustments l 4 4 to the switch off delay between about 2 minutes and 1 hour The mid position corresponds to about 15 minutes If no movement is detected during the delay time the relevant group will be switched off Not used the setpoint value is determined on the manual programming unit When you have finished making the adjustments replace the decorative ring It must click into place 7 Lighting control setpoint adjustment As already mentioned a group is assigned to the combined sensor when it is programmed in the central unit The luminaires of this group will then be switched and controlled by the sensor This group must also be assigned at least one channel button on a wall mounted or hand hald transmitter for operating the lighting controls Train the relevant channel button using the manual programming unit and then assign this button to the group to be controlled control of group XX see operating instructions for the man