        Operating Instructions
         Contents
1.                          19  9  FURTHER INFORMATION   nnsaannnnnnnnnnnnnnnnnnnnnnnnennennnnnnnennnnnnnnnnnnnennnnnnnnnnnnnnn euneun ennnnnnn          20  10  SMC CONTACT                                                             21                                                                                    i 22    Page  2 of 22                                     UMIO                           7  21 SMC Operating Instructions       Safety recommendations      Please read the operating manual carefully before starting up the SI unit  retain the  operating manual at hand for later reference  Please observe all safety precautions  given in the manual  as well as the following safety recommendations     A Attention     In order to avoid damage to the SI unit   which could possibly result  in system faults   the 51 unit must not be installed in the following  areas      areas where the SI unit can come into contact with water     areas where the temperature of the SI unit would exceed 50  C     EX areas    A Attention      Switch off both the compressed air and the supply voltage before  installation of and maintenance on the SI valve manifold       Only qualified control and automation technicians are permitted to install and maintain  the equipment       Pay attention to the technical data when installing the SI unit and the valves     The mains supply circuit for the valves must conform to the PELV  Protection  Extra Low Voltage  requirements in IEC 364  4  41  Allowabl
2.     2       4        1 3 mm    The mechanical dummy jack    Address range  0   31 decimal  Do not use the address 0 for normal slave addressing  The  address 0 is reserved for automatic addressing via the master     Page  15 of 22                        IIIUULLGOVV UMIL                 LO J    7    SIMIC Operating Instructions       7 1  Address setting via the handheld programming device    A special dummy jack is required for the ADDR1 2 sockets on the front cover plate when  addressing via the hand programming device  HP      When programming using the HP  the  true  AS Interface master is dicsonnected from the slave  being addressed  and the HP device assumes the role of master  During this procedure  all other  slaves in the circuit remain connected to the  true  master    After successful completion of addressing via the HP  the ERR LED will go off     a  Models having        AS interface         EX12  SAS4 and EX1 2  SAS5  Step 1  Remove the dust cover  ADDR      Step 2  Plug the cable jack of the HP into the ADDR socket    Step 3  Set and transmit the slave address into the AS Interface circuit using the HP   Step 4  Remove the cable jack from the ADDR socket    Step 5  Replace the ADDR dust cover     b  Models having two AS Interface chips  only EX12  SAS2  Step 1  Remove the dust covers of ADDR 1 and 2     Step 2  Plug the cable jack of the HP carefully into the ADDR1 socket    Step 3  Perform the slave address setting of slave chip no  1 using the HP  range 1 to  3
3.  8 single solenoid valves    18 pin connector          common ground        2 For EX12  SAS4 and   5455        For EX12  SAS2    b  For 2 or 4 double solenoid valves       18 pin connector         Valve 0    Solenoid a    0V  common ground        El      For EX12  SAS4 and  SASS       For EX12 SAS2    Page  12 of 22    PAULUGLUL VULIDUL IIIUULLGOVV UMIL    37 eae    7    SIMIC Operating Instructions       6  Technical specification of the EX12  SAS     Serial interface protocol According to AS International Association  Specification    Complete Specification  Version 2 0       Slave protocol chip ISA3  compatible AS Interface slave chip     52701   AS Interface power supply voltage 26 5 V DC to 30 5 V DC at the AS Interface  slave via yellow AS Interface standard cable   2x1 5mm    Valve solenoid power supply voltage  24 V DC   10   21 6 V DC to 26 4 V DC      except for EX12  SAS3  via optional black AS Interface cable   2 x 1 5          Note     Use only power supply units conforming to  PELV standard          64 4 41      Load current per valve solenoid   max  100 mA  2 1 W rated power   except      EX12  SAS3  no black cable   max  70 mA  1 5 W for EX12  SAS3    Valve solenoid driver circuit p channel MOS FET transistor driver   common ground  earth      Reverse  incorrect  Provided by a series wired diode on the positive  connection protection side of the AS Interface power supply   Surge  over voltage  protection Provided via a Zener suppressor diode between    the AS 
4.  BS5 6XX   Tel  01179 522155  Fax  01179 522186    Cumbernauld RC    SMC Pneumatics UK  Ltd  1  Carradale Crescent  Broadwood Bus  Park  Cumbernauld   Glasgow G68 9LE   Tel  01236 781133   Fax  01236 780611    Ipswich RC    SMC Pneumatics UK  Ltd  Unit 6 amp 7 Alpha Bus  Park  Whitehouse Road  Ipswich  Suffolk   IP1 5LT   Tel  01473 240040   Fax  01473 747707    Poole Regional Centre    SMC Pneumatics UK  Ltd  Unit 4  Acorn Bus Centre  Ling Road   Poole   Dorset   BH12 412   Tel  01202 732233   Fax  01202 737743    SMC Eire    SMC Pneumatics  11  Ltd  2002 Citywest Business  Campus  Naas Road  Saggart   Dublin   Tel   353 1 4501822  Fax   353 1 4502710    Coleshill RC    SMC Pneumatics  UK  Ltd  24  The Courtyard   Gorsey Lane   Coleshill   Warwicks   B46 1JA   Tel  01675 467177   Fax  01675 465073    Droitwich RC    SMC Pneumatics  UK  Ltd  Unit 3  Wassage Way  Hampton Lovett Ind  Estate  Droitwich   Worcs  WR9 ONX   Tel  01905 774544   Fax  01905 797343    Manchester RC    SMC Pneumatics UK  Ltd  3  Modwen Road   Waters Edge Business Park  Ordsall Lane Salford  Manchester   M5 3EZ   Tel  0161 8767371   Fax  0161 8767372    Sheffield RC    SMC Pneumatics UK  Ltd  Unit 4    North Anston Bus  Centre  Houghton Road   North Anston   Sheffield    31 7JJ   Tel  01909 565504   Fax  01909 569717    Page  21 of 22    FAVLUAGLY L  VELLOVI             ULLILD                       SMC    Operating Instructions    NOTES    Page  22 of 22    
5.  by the system controller  SPS  PC or controller   and not by  the master   The master  however  notices after at most 5 ms  max  cycle time  if a slave trips out     The AS Interface telegram conveys the message between the master and the slaves in both  directions  First the master output data is sent to the slaves  write   then the slave input data  per  slave and within one telegram  is returned to the master  read             AS Interface telegram consists of the master call  the master idle time  master pause   the  slave response and the slave pause  see below      AS interface telegram   From master to slave and from slave to master  for a single slave access      master call master pause slave response slave pause  ST CB A4 A3 A2 A1 A0 1413 12 11 IO PB EB 3 10 BT           12 11 IO PB EB 1BT  ST start bit is always 0 BT 1 bit time   ca    1  5  EB end bit is always 1 PB parity bit  even parity   14 10 5 bit from master to slave 13 14 bit from slave to master    A4 A0 5 bit for slave address   00000 1 1 1 1 1 binary corresponds to 0 31 decimal   CB control bit     0 for data parameter address access    1 for command access    For a description of the master  refer to the master manufacturer s handbook  where details of  the particular AS Interface master used can be found  The master answers this telgram  cyclically for all connected and activated slave addresses     The main component of the AS Interface is a special slave chip  which can control   a  4 inputs only  
6.  plastic thread could be damaged     srews             AS interface connector cover     d            AS interface  cable                Fig  1    Applicable to the yellow cable  the green PWR LED and the EXT LED light up when the power  supply to the AS Interface is switched on    Applicable to the black cable  if provided   only the EXT LED lights up when the valve power  supply is switched on  The ERR LED does not light up  as this would imply a communication  error between the AS Interface master and the AS Interface slave s        only  if EX12  housing is mounted on DIN rail    Page  11 of 22    FAVLUAGLY LT  VELLOVI             ULLILD  Lv Twila     SMC   lt 7 Operating Instructions    7  Identify both AS Interface connectors  yellow and black  on the white labels found on the top  covers of the AS Interface connectors     Set only free addresses for new slaves  the default address is 0  and transmit the information  via the ID  and I O code to the master  ID code   0  I O code   8  i e  only solenoid outputs      5  Valve connector pin assignment    The SI valve manifold has been internally pre wired  The 18 pin connector joins the AS Interface  unit EX12  SAS  to the valve block  The pins have been pre assigned for the 4  or 8  in the case  of the EX12  SAS2 model  output drives  Pins 17 and 18 are for the common ground  earthing    and pins 9 16 are not connected  The wiring of the SI valve manifold can take various forms   depending on the application     a  For 4 or
7. 1 decimal    Select slave addresses not already used in the AS Interface circuit    Step 4  Remove the cable jack from the ADDR1 socket    Step 5  Plug the cable jack of the HP carefully into the ADDR2 socket    Step 6  Perform the slave address setting of slave chip no  2 using the HP  Use a  different address to that used in step 3  range 1 to 31 decimal     Step 7  Remove the cable jack from the ADDR2 socket    Step 8  Replace the ADDR1 and ADDR2 dust covers on the cover plate     Page  16 of 22                                               Lv eae    9        Operating Instructions       7 2  Addressing via the AS Interface master    The following procedure is recommendet for addressing via the AS Interface master     a  Models having one AS Interface chip  EX12  SAS4 and EX12  SAS5    No dummy jack is required when setting addresses via the master  as only AS Interface chip     one AS Interface slave  is visible to the master  Programming is done in the normal manner     Note    Refer to the AS I Master operating manual     b  Models having two AS Interface chips  only     12  5  52    The EX12  SAS2 unit is pre set with the address 0  i e   both internal slaves have the address 0   As the address 0 may only be present once in the circuit as seen by the master  the dummy jack  provided must be used to isolate the chip which is not being programmed     step 1  Connect the yellow AS Interface cable  and the black cable  if provided     step 2  Remove the dust covers from AD
8. C  Electromagnetic Compatibility   emission  The standard AS Interface cable enables simple and quick installation by using an  insulation piercing connection     For the data decoupling of the yellow cable  a special AS Interface power supply device must be  used  This AS Interface power supply is directly connected to the yellow cable  ASI ve and ASI   ve line  and is positioned as near as possible to the master in order to minimize the voltage drop     In addition to the yellow cable mentioned above  some AS Interface units are provided with  similar  optional  black cables for additional actuator power supply    Only power supply devices conforming to the PELV  Protection Extra Low Voltage  standard  should be connected to the black cable s   Ordinary  24V DC transformers must under no  circumstances be used     The SMC interface units which are provided with an additional  24V DC power supply for  electrical components  black cable connection  can be used for emergency OFF applications   The yellow and black cables are completely independent of one another  i e   when the  24V DC  supply  black cable  is switched off  the AS Interface circuit  yellow cable  remains in operation     Because of their special geometrical asymmetry and size  both the yellow standard cable and  the optional black AS Interface cable are mechanically protected against incorrect polarity     The AS Interface is a single master multiple slave system  i e   there is only one master  controlling se
9. DR1 and ADDR2    step 3  Insert the dummy jack into the ADDR2 socket and set the address of the AS   Interface chip no  1   slave      1     step 4  Remove the dummy jack from the ADDR2 socket  insert the jack into the  ADDR 1 socket and set the address of the AS Interface chip no 2   slave no 2     step 5  Remove the dummy jack from the ADDR1 socket    Step 6  Replace the ADDR1 and ADDR2 dust covers on the plate     Page  17 of 22    FAVLUAGLY LT  VELLOVI                  ULLILD                       SMC Operating Instructions    8  Diagnostic and safety functions    Y    8 1 ERROR LED  red lamp  ERR     The red ERR LED  error LED  indicates a communication error between the master and     slave  A communication error arises when the master  despite repeated calls  fails to receive a  correct answer from the slave  When a communication error arises  the master reports a  configuration error and removes the failed slave from the circuit in order to ensure that the  remaining slaves in the circuit can continue functioning  The master is not able to determine  whether the error arises from the slave itself or from a line disturbance  Because of their internal  watchdogs  SMC slaves EX12 SAS  can recognize that no telegrams are being sent  and  announce a communication error via the ERR LED  In this case  it is up to the user to decide  whether the valve actuator should be reset to a preset state or should be left in the last operating  position  see Section 8 2     On error cor
10. FAULUGLUL VULIDUL              UMIO  AWTU AUU J    7  21 SIMIC Operating Instructions       Operating Instructions       Actuator Sensor Interface Units  AS Interface        EX12  SAS2  EX12  SAS4  EX12  SAS5        0  1  2                 Page  1 of 22                        IIIUULLGOVV                                             2 5     Operating Instructions  CONTENTS  Page  1  GENERAL INFORMATION ABOUT THE   5                                                              4  2  OVERVIEW OF EX12  SAS  DEVICES                                  creer rcc crc err                        8  4  INSTALLATION OF THE EX12  SAS          6             222222 222 2   11  5  VALVE CONNECTOR PIN   5                                    422222   2     2       44    71 07 1  12  6  TECHNICAL SPECIFICATION OF THE EX124 SAS1I                          ceres 13  7  SLAVE ADDRESS SETTING PROCEDURRE                               224  22   22224 10  15  7 1  ADDRESSING VIA THE HANDHELD PROGRAMMING DEVICE                                              16  7 2  ADDRESSING VIA THE AS INTERFACE                           4040      0                   nnne nnn 17  8  DIAGNOSTIC AND SAFETY                 6    0        2   22   2  222    2   2 2    18  8 1 ERROR LED                           556        temen QR                                        18  8 2 CLEAR HOLD Rl                                                                        18  8 3 LEDS FOR POWER SUPPLY  GREEN LEDS  PWR  AND  EXT             
11. Interface positive and negative voltage  supply terminals     ID Code 0 hex   0          8 hex  i e   only outputs  no sensor inputs   Default addresses 0 dec  for EX12  SAS4 and EX12  SAS5    2 x 0 dec  for EX12  SAS2  2 slaves     Parameter bits of AS Interface Not connected  not used  slave protocol chip    Safety fall back function a  Switch position CLEAR  Default      all valves are switched OFF in the event of  a communication error     b  Switch position HOLD   all valves retain their last valid ON OFF position  as per last valid communication telegram     LED indicators a  PWR  green  for AS Interface voltage    Page  13 of 22    9       Watchdog timer    Opto coupler    Connectors    Insulation piercing connection  of yellow and black AS  interface cables     EMC test standards    Protection class  Operating temperature    AS international Association  test certificate    Applicable SMC series valves    Single solenoid valves                                           LAL                   J    Operating Instructions       supply  typically 30 V DC   b  EXT  green  for valve solenoid voltage  supply  24 V DC nominal    c  ERR  red  for communication error     One provided per interface chip  having a   delay time of ca  50 ms    In the event of a communication error    the red ERR LED lights up  After error correction   the ERR LED automatically goes out     Provided between AS Interface and valve  solenoid driver     a  Yellow and black AS Interface cable  b  Socket
12. LEAR HOLD switch and both addresses before installation of the AS   Interface cable     e  Ensure that the total length of the yellow AS Interface cable does not exceed 100m per AS   Interface power supply unit     f  Ensure that  24 V DC   10  is available at the slave for valve solenoid power supply   This  could possibly require a higher voltage at the power supply unit  as the voltage drop is directly  proportional to the length of the yellow AS Interface cable       0  After switching on the AS Interface power supply  the green PWR LED should light up  The  red ERR LED might light up for a few seconds  depending on the actual master used  Once  the master has recognized all the slaves  the red ERR LED will go out     h  If  when switching on the power supply  the mode switch is in the HOLD position  all valves  will initially go to the OFF position  no current flow      i  Both AS Interface cables  yellow and black  are protected against both incorrect polarity and  incorrect insertion   If the cables are incorrectly connected  no damage to the SMC AS Interface unit will occur  as  the impedance and phase values will be out of range   In the worst case  e g   max  cable length of 100 m and 31 AS Interface slaves    communication between the other participants will  only  be disturbed by reversing the black  and yellow cables     j  Itis recommended that new slaves be installed and address programmed one after the  other  and that the ID code and       code of each new sl
13. V DC for      solenoid power supply  Use the correct  connector for additional solenoid power supply  black   Do not use 30 V supply for the black  AS Interface cable      Note that the valve solenoid voltage in the circuit must be a bit higher than the target voltage   24 V DC  directly at the valve  The voltage drop depends only on the current consumption in  the black cable     Page  19 of 22                                               Lv eae    7   lt A SMC Operating Instructions       9  Further information        ID code   Ohex  I O code   8hex is valid for all three EX12 SAS  types   Note that for model EX12 SAS2 the master has to be given the ID  and I O codes twice  as  there are two slaves     b  Yellow and black AS Interface cable  AS Interface  and valve solenoid voltage supply    The AS Interface unit can be disconnected from the yellow and black AS Interface cables  when the power supply  yellow and black  is switched ON  This also applies to the      12 5  55  without black cable   The remaining AS Interface circuit is not adversely  affected by this     C  For models supplied with black AS Interface cable  for additional valve solenoid power  supply   Disconnection of the valve manifold board should only be done once the solenoid  power supply is switched OFF     Caution     Use only voltage supply units which conform to PELV standard        364 4 41  for   24V DC solenoid power supply  this does not apply to model EX12 SAS5      d  Set the position of the C
14. ave be checked against the master  configuration     k  Asthe AS Interface is an open system  accessories available on the open market can be  installed  Refer to the certified devices in the CD ROM product catalog of your national AS   Interface manufacturers association    Most available AS Interface accessories simplify usage  and are easy to install     Page  20 of 22    Y    FAVLUGLY LT  VELLOVI                           ULLILD                       77 SIC Operating Instructions       Note that some passive housings of common AS Interface I O modules are designed for  yellow and black AS Interface cables  while others are designed for 2 x yellow cables  for    branching      10  SMC contact addresses    SMC  UK   Belfast RC    SMC Pneumatics  UK  Ltd  Unit 3  Shaftesbury House  Edgewater Road   Belfast          9JQ   Tel  01232 778414   Fax   01232 778422    Crawley RC    SMC Pneumatics  UK  Ltd  9  Pelham Court   Pelham Place   Broadfield   Crawley  W Sussex RH11 9AZ  Tel  01293 614094   Fax  01293 614135    Gateshead RC    SMC Pneumatics UK  Ltd  Unit B6  Marquis Court  Marquis Way   Team Valley Trading Est   Gateshead   Tyne  amp  Wear       11 ORU   Tel  0191 4872040   Fax  0191 4872041    Milton Keynes RC    MK Regional Centre  SMC Pneumatics UK  Ltd  Vincent Avenue   Crownhill   Milton Keynes   Bucks   MK8          Tel  01908 265247   Fax  01908 262705    Bristol RC    SMC Pneumatics  UK  Ltd    Unit 5 East Gate Office Centre    Eastgate Road  Eastville   Bristol  
15. b  4 outputs only  c  4 inputs   4 outputs simultaneously  i e   within one telegram     In case c   a system having 31 slaves will have a maximum of 248 binary inputs and outputs   This chip is provided with 4 parameter bits for non cyclic setting of special slaves  If these  parameter bits are used  the master sends asynchronous parameter telegrams between normal  data cycles    Note      EX12  SAS  units do not use the parameter bits of the internal AS Interface chips     Page  5 of 22    Y    FAVLUAGLY LT  VELLOVI                  ULLILD                       77 SIC Operating Instructions  The SMC AS Interface slaves are provided with an internal watchdog timer  WDT   This WDT    provides a safety fall back function  i e   in the event of a communication error the outputs will be  reset to a definite state  normally all OFF  and the red ERR LED will light up     The slave address  which is non volatilely stored  can be changed automatically via the master  or manually via a handheld programming device  HP   The handheld programming device  replaces the actual AS Interface master during address programming  It is not absolutely  necessary to use the handheld programming device to set the addresses  as each slave can be  directly programmed by the master     Many slave addresses cannot be set simultaneously  one telegram can only be addressed to a  single slave  5 bits are required for one slave address    4   0 implies 2     32 slaves     The address 0 is usually reserved 
16. e valve voltage    range is  21 6v to   26 4v DC       Use only certified AS Interface mains supply circuits for the voltage supply to the AS   Interface       Donot open and try to repair the equipment yourself  nor attempt to modify it   SMC are not liable for any damage resulting from such activities     Page  3 of 22    FAVLUAGLY LT  VELLOVI                      ULLILD                        5       lt 7 Operating Instructions    1  General information about the AS Interface    The AS Interface system replaces the expensive parallel wiring of single distributed sensors   inputs  and actuators  outputs    Distributed  here means decentralized  local inputs and  outputs  I Os  using only a few bits  1 4 bits      Most inputs and outputs  I Os  are binary or discrete and are located beneath the well known  fieldbus level  according to the OSI ISO reference model  Here  binary    discrete  or digital  means simple ON OFF operations  such as  for example  the 24 V DC ON OFF control of the    SMC solenoid valves without transmission of analog values via the ASI network     Compared with other fieldbuses  the AS Interface is both relatively easy to use and cost    effectivel  The system does not require termination resistors or baud rate setting     The data and energy transmission is done via a simple 2 wire cable  Yellow AS Interface  standard cable  via a connector and an APM  Alternating Pulse Modulation  modulation using  sin    pulses  which have fewer harmonics and low EM
17. first start up of  the slaves it is possible that the red ERR LEDs go on for a few seconds  they will go off again  after successful activation     Page  18 of 22                                                37 eae    7    SIMIC Operating Instructions       8 3 LEDs for power supply  green LEDs  PWR  and  EXT     PWR  power  monitors the AS Interface voltage power supply  26 5 V     31 6 V at the slave   yellow cable  and EXT  external  the additional valve solenoid power supply   24V   10  black  cable      EXT is completely independent of PWR  If the black cable provided is not connected  the           solenoids will have no power supply  EX12 SAS4 and  SAS2     In the case of model EX12 SAS5  without black cable   the valve solenoids are supplied with  power from an internal  24V voltage regulator via the yellow cable     If the voltage falls below a certain value  the two green LEDs will not switch off completely  but  will glow weakly  If this occurs  ensure that the following voltages are present  especially at the  slaves and the black cable    a  yellow AS Interface standard cable    AS Interface voltage at ASI unit   29 5   31 6 V   AS Interface voltage at slave  26 5   31 6 V  max  voltage drop of 3 V 100 m    b  optional black AS Interface cable   not with EX12 SAS5      valve solenoid voltage at the device  23 6   28 5 V DC  26 V DC nominal   valve solenoid voltage at the slave  21 6   26 4 V DC    24 V DC   10      Notes       Avoid voltages greater than  26 4 
18. for a new AS Interface slave which has not previously been  connected to the AS Interface net  The slave address 0 can only be used once within the net     The address 0 is used for automatically setting the address via a master telegram  In this case   the master allocates the new slave the lowest  unused address between 1 and 31     Note     The AS Interface master only permits one address 0  Each EX 12   SAS2 device contains  two ASI slaves  as well as two addresses  both of which are preset to 0  For this reason  use    of the blind connector supplied by SMC is essential when first starting up the system via the  master  see 7 2      Page  6 of 22    FAVLUGLY LT  VELLOVI               ULLILD                        5       lt 7 Operating Instructions    Overview of common AS Interface features     Medium for data   energy   Unshielded 2 wire AS Interface cable      yellow AS Interface standard cable     Insultion piercing connections according to IEC 60352 6    Number of participants Up to 4 sensors and 4 actuators per slave          max  124  bidirectional  max  248 binary participants  Adresses Each slave is allocated a definite address   Address setting by means of the master or a programming   g   a handheld programming device and cable jack  immediate response from slave  bidirectional  4 bits  pure data  per slave and message    Device interface 4 configurable data interfaces  as inputs or outputs or  bidirectional  plus 4 parameter outputs and 2 control outputs  Str
19. obe  to the host or to the slaves    Master functions Initialization of the network  identification of participants   acyclic setting of the slave parameter valves  diagnosis of thg  net and AS Interface slaves  error messages to the host   setting of addresses in replaced slaves       Notes      4n addition to its slave address  every certified slave has a fixed and non volatile ID  and  0  code  Identification   and Input Output Code  according to the AS Interface Association  for  slave identification by the master      The ID   1 0 code and the address are non volatilely stored in an internal EEPROM after  power OFF  Only the slave address can be changed by the user  via the master or a  handheld device        EX12  SAS  devices are not provided with sensor inputs     Page  7 of 22                                      UMIL LAL tea    7    SMC Operating Instructions       2  Overview of EX12  SAS  devices    The SMC actuator sensor interface  AS Interface  models EX12  SAS4  EX12  SAS2 and  EX12  SAS5 described here are designed for use with SMC non IP65 VQ  and SY           manifolds     The table below shows a type overview of SMC non IP65 AS Interfaces             fe          0 1 2 for housing    Solenoid outputs  24  8  4      Schematic diagrams Fig  1a     attachment plate     valves      yellow   black yellow   black only yellow  no black  end plate    single solenoid valves   single solenoid valves   single solenoid valves  1 2 3 4   1 2 3 4 5 6 7 8 1 2 3 4  double 
20. rection  the red ERR LED automatically goes off and the slave is brought back into  operation  It is not necessary to switch off the circuit and restart it again     8 2 CLEAR HOLD Switch    The CLEAR HOLD switch is a two position switch on the cover plate  its purpose is to provide a  safety fall back function     If the communication between the master and the slave is interrupted  the slave internal  watchdog timer indicates an error  red ERR LED lights up   In the event of such an error  the  open shut status of the valves is pre determined by the CLEAR HOLD switch setting on the  cover plate     1  CLEAR  In the event of a communication error  all valves are switched off   valves OFF and ERR LED   ON    2  HOLD  There        2 modes when ERR LED   ON     a   real  communication error    all valves retain their  previous  valid ON OFF status  b  when using the HP device   not a communication error    Note          CLEAR HOLD switch is only active when the red ERR LED lights up     If the HOLD position is selected  the valves initially go to the OFF position when the AS Interface  power supply is first switched on  The WDTs are reset after power ON and set if no master call  is made to the slave within a period of ca  50 ms  On resetting the AS Interface master  access  to the slave is again opened     After eliminating the cause of the communication error  red ERR LED goes off   the master  regains control of the solenoid outputs  Depending on the master used  during the 
21. s for handheld programming device   used to set addresses   Two jacks for EX12 SAS2  ADDR1 2    One jack for EX12  SAS4 and  5  55  ADDR    Note   A special dummy jack  1 3       is necessary  for programming the EX12  SAS2 via the AS  interface master     According to IEC 60352 6    Emission according to EN50081 1   Interference according to EN50082 2     IP20  0   50  C    Provided by the AS Interface test laboratory  in Leipzig  Germany     VQ1000 2000  Negative common polarity   SY 3000 5000  Negative common polarity     max  4 for EX12  SAS4and  5  55  max  8 for EX12  SAS2    For future information on SMC valves and valve connection terminal boards  refer to SMC valve    catalogues     Page  14 of 22                                     UMIO                           7  21 SMC Operating Instructions       7  Slave address setting procedure    There are two methods of setting the slave addresses    1  Using the AS Interface master    2  Using the handheld programming device    When using automatic programming via the master  address 0   the mechanical dummy jack   must be used to disconnect one of the two AS Interface chips of the EX12 SAS2 from the yellow   AS Interface cable    No dummy jack is required for the     12 5  54 and  5  55 versions    For    0  1 2   Model number  Address programmed via AS  Address programmed via  Interface master  bus  hand programming device   and dummy jack    EX12    SASA es        ye  2      f  using dummy jack      12    5455 _______  
22. series     Page  9 of 22    FAVLUGLY LT  VELLOVI                                                         5        Operating Instructions    3 Components on the cover plate   simplified overview   not to scale     Green PWR LED All types Green LED for AS Interface power supply  yellow  cable    Red ERR LED All types Red LED for communication error  watch dog    green EXT LED EX12  SAS4 and  SAS2 Green LED for valve solenoid power supply    24VDC PELV     ____ ee O  ADDR1   ADDR2  one socket   EX12  SAS4  Jack sockets for handheld programming device for  jack sockets  SAS5 address setting  2 slave addresses  as there are 2  two sockets  EX12  SAS2 ASI chips   ADDR 1  for chip no  1 or solenoid outputs  0 1 2        3  ADDR2  for             2      solenoid outputs  4 5 6 and 7     Solenoid output no  0 is assigned to the first  Socket after the device     CLEAR HOLD switch All types Mode switch CLEAR HOLD  CLEAR  in the event of a communication error  all  valves are switched to the OFF position  HOLD  in the event of a communication error  all    valves remain in their current ON OFF positions      e  AS Interface connector All types  for the yellow cable  left   Connector for the black   EX12  SAS4 and  SAS2  cable  right  actuators        Page  10 of 22                                                                         7   lt 7 SMC Operating Instructions       4  Installation of the EX12  SAS  slaves    We recommend the following installation procedure        1  Ensure 
23. solenoid valves   1 2 double solenoid valves   double solenoid valves  1 2  1 2 3 4       The following is valid for all three EX12  SAS  types       ID code  Identification Code   0 hex                   Input Outout Code   8 hex    i e   outputs only  no sensor inputs   Default address of EX12  SAS4 and  SAS5 1 AS Interface chip   0 dec   Default address of EX12  SAS2  2 AS Interface chips   2 x 0 dec     Page  8 of 22                                               Lv eae    7    SMC Operating Instructions         If sensor inputs are required  use a generic AS Interface 1 0 module       All EX12  SAS  models are provided with ADDR sockets for connection to the handheld  programming device for the setting of addresses using a special  1 3 mm  jack     Overview of models numbers      SMC Max  no  of No  of AS Interface Additional  24 V DC  Model number single double chips or slave Solenoid power  solenoids addresses supply  black cable    EX120 SAS4 4 2 1 yes  EX121 SAS4  EX122 SAS4    EX120 SAS2 8 4  EX121 SAS2  EX122 SAS2  EX120 SAS5  EX121 SAS5  EX122 SAS5       Overview of the EX 12 frame  housing      Three different frames  housings  of tyoe EX12  are available  each suitable for one SAS type   i e   there are 3 x 3   9 different EX12  SMC AS Interface devices  listed above      EX120  0 for direct mounting  without DIN rail  VQ valve series   EX121  1 for mounting on DIN rail  with ribbon cable  SY series       122  2 for mounting on DIN rail  without ribbon cable  SY 
24. that the position of the CLEAR HOLD switch on the cover plate is correct     CLEAR  In the event of a communication error  all valves are switched OFF   HOLD  In the event of a communication error  all valves retain their current setting     2  Connect the SMC valve manifold connecting plate to the AS Interface unit via the 18 pin  connector on the side  and lock the connector using the stopper clip at the rear    2   Place the ASI unit on the DIN rails and connect it to the SMC valve manifold mounting plate  using the 18 pin connector  Finally  tighten the securing screws    Note      dfthe unit has been supplied pre asssembled to the manifold  ignore steps 2  amp  3   3  Clamp the yellow and black AS Interface cable  if provided  in the recess in the underside of  the AS Interface connector  Fig  1     Notes              AS Interface connector cover can only be mounted one way round      Because of the asymmetrical shape of the AS Interface cable  profiled   the cable can only  be inserted in one way  Make sure that the connecting cable seats properly in the  socket  Fig  1       Before doing any installation work  check that the cables are long enough     5  Press the front cover of the AS Interface connector downwards into the socket until the first  mechanical locking stop engages  Fig  2     6  Carefully tighten both screws  2 screws per AS Interface connector  until the second  mechanical locking engages  Fig  3     Note        Do not over tighten the metal screws  the
25. veral slaves in an AS Interface net  A maximum of 31 slaves can be connected to  one master within an AS Interface net  Both the master and the slaves are connected via the  yellow AS Interface standard cable     The maximum length of the yellow cable  without a repeater  is 100 m  which includes the stub  lines and all branch lines of the AS Interface net free topology    The maximum length of the black cable depends on the power consumption of the actuators   and is normally shorter than the yellow cable  The voltage directly at the actuators must be  confirmed to be within the allowable voltage range     The AS Interface master sends as many telegrams as there are connected and active AS   Interface slaves in the net  Each slave is sequentially and cyclicly accessed by these telegrams     Page  4 of 22                                                        ULLILD  Lv Twila     SMC  21 Operating Instructions    starting with the slave with the lowest active address   For the master there are as many slave addresses as there are AS Interface chips connected  and activated in the net     The time required to access all active slaves is the data cycle time  approx  5 ms fora  maximum of 31 slaves   The access time of all active slaves is fixed or determined  real time  ability  and is proportional to the number of activated slaves  If the number of activated slaves is  halved  the access time is also halved    5 ms   15 31   approx  2 4 ms     The physical system is controlled
    