Home

K-BUS R Shutter Actuator, 4fold User manual

image

Contents

1. 45 2 ce ed www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator 1 General The Blind Shutter that is used to decorate building is indispensable in the modern building construction The Blind Shutter can make indoor air more fresh and make environment more comfortable meanwhile can also bring many benefits to our lives such as Aesthetics and energy efficient simple and neat effectively maintain the indoor temperature to warm in winter and cool in summer and save energy For free adjustment the louvre angle and incoming the light to prevent glare Make room clean and easy clean Block ultraviolet radiation into indoor protect furniture and avoid carpets from fading Protecting personal privacy Providing protection against intruders Except the Blind Shutter there are also other curtains for example Awnings Roller Blinds Vertical Blinds and so on The Shutter actuator that is described in the manual is used to achieve automatic control for the Shutter the Sun Blind and other curtains The control of Shutter Blind via motors not only saves the user task of raising and lowering the Blinds by hand but also enables the implementation of fully automatic control in accordance with the day s weather conditions and other factors The user can also adjust this posi
2. 44 a a a Rae a TST www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator uasi intermediate position Telegram value 255 louvres closed to maximum Table 6 4 communication object table status response 6 5 Communication object protect function When the protect functions have occurred general operations are disabled and their objects are not avail except modifying the preset and storing the scene N Name Object Function Description Group Addr Length C R W T Ul DataType Priority Ejo wind protect Wind protect 1 bit c Low Eji rain protect Rain protect 1 bit c Low m2 frost protect Frost protect 1 bit c i Low ET Force operation CHA CHA Blind 2 bit C Y Low G8 Operation Block CHA CHA Blind libit C Low Fig 6 5 communication object protect function No Function Object name Data type Flags 0 Wind protect Wind protect Ibit C W The communication object is enabled when the activated option is selected in the parameter wind protect which is used to receive the cyclical telegrams from the anemometers If the object receives a telegram 0 the wind protect is deactivated and the monitoring period is restarted If the object receives a telegram 0 again for the first time after wind protect the Shutter Blind is moved to the position on reset of
3. wind rain The Shutter actuator can receive bit wind protect rain protect and frost protect commands to protect the Shutter Blind in the event of storms rain and frost If a protection occurs the Shutter Blind is moved to the set position for protect and can no longer be moved until the protection is deactivated again The positions for wind protect rain protect and frost protect can be set separately for each output The anemometer the rain sensor and the frost sensor are monitored cyclically by the Shutter actuator i e the anemometer and the sensors send the protect status cyclically and the Shutter actuator expects this signal If there is no signal the Shutter actuator assumes that the anemometer and the sensors are faulty or that the bus line has been interrupted and moves all the Shutters Blinds which are influenced to the set protect position and operation is blocked The monitoring period of the Shutter actuator should be twice as long as the cyclical sending time of the anemometer and the sensor so that the Shutters Blinds do not move immediately to the wind the rain or frost protect position when a signal is omitted e g due to a high bus load When the wind the rain or frost protect is reset the Shutter Blind is moved to the set Position on reset of weather protect block and forced operation and operation is enabled Parameter wind rain frost protect These parameter is used to set whether wind protect rain prote
4. 1N E2 Guangzhou Video star Electronics Industrial Co Ltd Elg KNX K BUS Shutter Actuator 4fold User manual Ver 1 AWBS 04 00 1 KNX EIB Intelligent Installation Systems DWoecese secer www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Conents 1 General 3 1 1 Product and functional overview 3 2 Technical data 4 3 Circuit and Dimension diagram 6 3 1 Circuit diagram 6 3 2 Dimension drawing 7 4 Project design and programming 8 5 Parameter setting description in the ETS 14 5 1 Parameter window protect 14 5 2 Paramete
5. 1 DOWN 18 CH X Blind Louvre adj stop UD CHX Ibit C W CH X Shutter Stop CHX If the Shutter Blind is in motion the movement is stopped on this communication object receiving a telegram value 0 or 1 Venetian Blind operating mode if the Blind is idle it is raised for the louvre adjustment on the communication object receiving a telegram value 0 it is lowered for the louvre adjustment on the communication object receiving a telegram value 1 Shutter operating mode if the Shutter is idle no action is carried out on the communication object receiving any telegram value Telegram value 0 stop louvre adj UP Telegram value 1 stop louvre adj DOWN Table 6 2 communication object table general 6 3 Communication object Auto The priority of general operation and automatic operation is the same but they cannot occur at the same time Their priority are lower than protect functions if any protect function occurs their operation will be disabled N Name Object Function Description Group Add Length C R W T U Data Type Priority mjes Blind position for Auto 0 1008 CHA CHA Blind 1 Byte C o Low Eje4 Louvre position for Auto O 100 CHA CHA Blind 1 Byte C Low mes Sun CHA CHA Blind 1 bit c Y Low jez En Dis Auto control CHA CHA Blind 1 bit C Low Fig 6 3 communication object Auto
6. 5 1 Parameter window protect Parameter window protect can be shown in fig 5 1 which applies to every output for the Shutter actuator Here can set priority of protect functions and monitoring period and priority for weather protect function When weather protect function occur the behaviour can be set separately for per output via parameters The detailed description for every parameter as follows 14 SSS Sa ea a a a a Sa www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting Protect Setting Manual Channel a Channel B Priority of protect functions Weather protect Block Forced operation Channel C Hi i Channel D Priority of weather protect functions Wind Rain Frost Wind protect activated Monitoring period for wind 0 0 1000 1 s 0 monitoring deact Frost protect activated Monitoring period for frost lo 0 1000 1 s 0 monitoring deact Rain protect activated Monitoring period for rain lp 0 1000 1 s O monitoring deact Wait for Sensor stabilize 0 1000 1s 0 n Fig 5 1 parameter window Protect Setting Parameter priority of protect functions The parameter defines the priority between forced operation the weather protect and block Options Weather protect
7. Louvres 0 100 lo 0 opened 100 closed Response Louvre Positon deactivated Response Blind Positon deactivated Fig 5 6 parameter window CHA Position Parameter preset for move to position 1bit The parameter is used to set whether the preset position is activated to provide two preset positions Options Activated Deactivated If the option activated is selected the communication object move to preset position 1 2 appears If the object receives a telegram value 0 the Blind is moved to the preset position 1 if the object receives a telegram value 1 the Blind is moved to the preset position 2 The values of the preset position 1 2 can be set in following parameters Position 1 2 Blind Louvre 0 100 Parameter preset for set position 1bit This parameter is used to set whether the preset position 1 2 can be modified via the bus Options Activated Deactivated If selecting activated the communication object Set preset position 1 2 appears The 32 M N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator preset position1 2 can be modified via the object If the object receives a telegram value 1 the current position is stored as the new preset value for position 2 if the object receives a telegram value 0 the current p
8. block force operation Weather protect force operation block Block weather protect force operation Block force operation weather protect Force operation block weather protect Force operation weather protect block The protect functions of wind protect rain protect frost protect block and forced operation have priority over all the other functions of the Shutter actuator If one of these functions has been activated of an output the operation of the output is disabled for other movements An order of priority can also be defined among the protect functions to control the Shutter Blind specifically if more than one protect function is active at the same time For example it is possible to define via a parameter that the forced operation function has priority over other protect functions when the window is being cleaned so that the cleaners cannot 15 EEE EEE SSE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator be surprised by an command triggered by weather protect when they are cleaning the louvres Parameter priority of weather protect functions The parameter defines the priority between the weather protect functions of wind protect frost protect and rain protect Option Wind rain frost Wind frost rain Rain wind frost Rain frost wind Frost rain wind Frost
9. Channel D Force operation 2bit deactivated Operation block activated When block its position no reaction Position on Reset of Weather alarm blocked and foreced operation no action Fig 5 5 parameter window CHA Protect Parameter position for wind rain frost protect These parameters are used for setting the behaviors in the event of weather protect Options Activated up Activated down Activated stop Activated no reaction Deactivated Activated position 2 Activated position 1 If the option deactivated is selected the weather protect is deactivated for the output If the option no reaction is set the output contact retains in their current status in the event of weather protect If the option up is set the Blind is moved to the very top when the weather protect occur If the option down is set the Blind is moved to the very bottom If the option position 1 2 is selected the Blind is moved to the position1 2 Parameter force operation 2bit This parameter is used to set whether the forced operation is activated 28 N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator The forced operation is controlled by 2bit command When the forced operation is carried out the Blind is moved to the top or the bottom general operation is disabled On reset of
10. activated Limit 1 0 top 100 battom 0 Limit 2 0 top 100 bottom lo J Fig 5 3 parameter window Channel X 20 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Parameter working mode This parameter is used to define the output mode Different output modes have different parameters and communications Options No function Venetian Blind Shutter If selecting no function the output is disabled If selecting Venetian Blind the output is for the Blind operation mode which can operate the Blind with louvres If selecting Shutter the output is similar with the Blind operation mode except that it cannot adjust louvres The section 5 3 details the parameters and communication objects for the venetian Blind mode Parameter position on bus voltage recovery The parameter is used for setting the behavior of the output on bus voltage recovery Options No reaction Up Down Position 1 Position 2 If the option no reaction is set the output contacts remain in their current position If the option up is set the Blind is moved to the top after bus voltage recovery If the option down is set the Blind is moved to the bottom after bus voltage recovery If the option position 1 2 is selected the Blind first is moved to the top or t
11. parameters On bus voltage recovery the action can be set via parameter for the Shutter actuator The Shutter actuator for 230V AC drives The following functions can be set via the application program gt Movement UP DOWN gt Stop Louvre adjustment gt Move into preset position up to 2 preset positions gt Set preset position modification of the preset position during operation gt Move to position 0 100 gt Adjustment louvre to position 0 100 only Blind working mode gt Scenes gt Automatic sun protection gt Monitoring of wind rain and frost protect cyclical gt Block gt Forced operation gt Status display of the current position status display of the current operating mode gt LED display gt Two operation mode Venetian Blind and Shutter 2 Technical data Power supply Operating voltage 21 30V DC via the EIB bus for automatic operation or manual operation Current input 12mA Power consumption via EIB lt 360mW 4 ee ee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Outputs Number of outputs 4 independent outputs each with 1 changeover contact UP DOWN mechanically interlocked Nominal voltage 230V AC Max switching current 6A Operating and Red LED and push button For assignment of the physical address display Green LED flashing Indicate the device running normally OK UP DOWN buttons 2 push butt
12. status If selecting stop the object receives a telegram value 0 the Blind is halted immediately and the output contact reverts to the neutral position If selecting save position the object receives a telegram value 0 the Blind is moved to the saved position if the position is not changed it is no action Note If selecting save position option here more than one protect function occur at the same time the Shutter actuator only records the position that the Blind is moved to in the event of the first protect function Therefore the saved position is the position that the first protect function occurs If here only a protect function occurs and the action of the protect function is stop the Blind will be not carried out movement on reset of protect function because of its position no change If here only a protect function occurs when its object receives a telegram value 0 30 EEE EE A T EE EEE EE_EE mmm www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator the Blind is moved to the set position on reset of the protect functions If more than one protect function occur when the object of the highest priority protect function receives a telegram value 0 the Blind is moved to the set position of the higher priority protect function For example currently there are three protect functions occur the pr
13. the drive mechanism 4 Programming or bus voltage recovery On bus voltage failure the output contact reverts to the neutral position All the communication objects adopt the value 0 or 129 after programming or bus voltage recovery The shutter Blind is moved to the set position after bus voltage recovery If the option position X has been set as the position after bus voltage recovery or a defined position of the shutter Blind is required for the first time it is first of all raised to the very top or all lowered to the very bottom near the target location direction to determine the current position and then into the target position Only when the shutter Blind has been moved to the very top or bottom determine the current position If the option no reaction has been set as the position after bus voltage recovery the Shutter actuator does not detect the current position of the Shutter Blind The communication objects Response Blind Shutter position and Response louvre position have the value 129 and are not sent on the EIB 5 Reference movement The Shutter actuator continually determine the current position of the shutter Blind as well as the position of the louvre angle using the duration of individual movements Over longer periods slight inaccuracies may occur when determining the position due to temperature variations and 9 S A EE EEE arr SS ESSE EE EEE www video star com cn maketing
14. the forced operation function the Blind is moved to the set position on reset of weather protect blocked and forced operation and general operation is enabled The forced operation function is suitable for example for raising Blinds when the windows are cleaned The operation of the Blind is blocked at the same time so that the cleaners are not put in danger due to unexpected movements Options Activated Deactivated If the option activated is selected the communication object forced operation appears If the object receives a telegram value 0 or 1 the forced operation is reset If the object receives a telegram value 2 the Blind is moved to the top If the object receives a telegram value 3 the Blind is moved to the bottom Parameter operation block This parameter is used to set whether the operation block is activated In the blocked function the output of the Shutter actuator can be moved to the set position for block when the block function is recalled via a 1bit command and general operation is blocked After a reset the Blind is moved to the set position on reset of weather protect blocked and force operation and general operation is enabled For example it is possible to block the operation of an interior Blind via the function if the window has been opened Options Activated Deactivated If the option activated is selected the communication object operation block appear
15. the option no reaction is selected the object receives a telegram 0 the Blind is moved to the top the object receives a telegram 1 the Blind is moved to the bottom If the option move to position 1 2 is selected the object receives a telegram 0 the Blind is moved to the top then to position 1 2 the object receives a telegram 1 the Blind is moved to the bottom then to position 1 2 If the option move to save position is selected the object receives a telegram 0 the Blind is moved to the top then back to its original position the object receives a telegram 1 the Blind is moved to the bottom then back to its original position The Shutter actuator continually determine the current position of the Blind as well as the angle position of the louvre using the duration of individual movements Over longer periods slight inaccuracies may occur when determining the position due to temperature variations and ageing processes Therefore the Shutter actuator uses the upper and lower limit positions to clearly define the current position of the Blind Each time that the Blind is in the upper or lower limit position the position is updated in the memory of the Shutter actuator If the limit positions have not been reached during normal operation a reference movement can be triggered via a bus telegram to move the Blind right to the top or right to the bottom 22 R www video star com cn maketin
16. weather protect blocked and forced operation If the object receives a telegram 1 during the monitoring period the Shutter Blind is moved to the set position for wind protect If no telegram is received during the monitoring period the Shutter actuator will think the anemometers fault and move the Shutter Blind to the set position for wind protect Telegram value 0 no wind protect operation enabled Telegram value 1 wind protect operation disabled 1 Rain protect Rain protect Ibit C W The communication object is enabled when the activated option is selected in the parameter rain protect which is used to receive the cyclical telegrams from the rain sensors If the object receives a telegram 0 the rain protect is deactivated and the monitoring period is restarted If the object receives a telegram 0 again for the first time after rain protect the Shutter Blind is moved to the position on reset of weather protect blocked and forced operation If the object receives a telegram 1 during the monitoring period the shutter Blind is moved to the set 45 aR www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator position for rain protect If no telegram is received during the monitoring period the Shutter actuator will think the rain sensor fault and move the Shutter Blin
17. 338465 GVS K BUS KNX EIB Shutter Actuator 6 2 Communication object general The communication objects have the same operation for per output and are used individually Their priority are lower than protect functions if any protect function occurs their operation will be disabled N Tane Object Function Description Group Addr Length C R W T U DataType Priority mis Blind position 1Byte 0 100 CHA CHA Blind 1 Byte C p Low Biz Blinds Up Down limited En Dis CHA CHA Blind 1 bit Es S gt 5S Low G18 Louvre adj stop UD CHA CHA Blind ibt C Low 416 Louvre position 1Byte 0 100 CHA CHA Blind 1Byte C W Low EiT Move blinds Up Down CHA CHA Blind Ibit C Low 11 Move to preset position 1 2 CHA CHA Blind libit C W Low Ge Reference Movement CHA CHA Blind 1 bit C E Low Gs Scene Save CHA CHA Blind 1 Byte E og Low 13 Set preset position 1 2 CHA CHA Blind ibt C W Low Fig 6 2 communication object general No Function Object name Data type Flags 6 CH X Shutter Blind Reference movement CHX 1bit C W The communication object is enabled when the deactivated option is not selected in the parameter position after reference movement If the object receives a telegram value the Shutter Blind is carried out a reference movement that makes sure its location exactly Telegram value 0 first the Shutter Blind is fully raised then
18. 42 SSS x _ SSE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator No Function Object name Data type Flags 62 CH X Shutter Blind En Dis Auto control CHX lbit C W The communication object is used to disable and enable the Auto Operation If the object receives a telegram 0 the Auto Operation is deactivated if the object receives a telegram 1 the Auto Operation is activated Telegram value 0 deactivate the Auto Operation Telegram value 1 activate the Auto Operation 63 CH X Shutter Blind Sun CHX Ibit C W If the communication object receives a telegram 0 or 1 the shutter blind is moved into a predefined position see the parameter chapter description 65 CH X Shutter Blind Blind Shutter position for Auto 0 100 CHX 1byte C W In Auto Operation status if this communication object receives a telegram value the Shutter Blind moves to the corresponding position for the received value In the Venetian Blind operation mode after the Shutter reaching the target position the louvres are positioned as before Only the object Louvre position 1 byte receives a telegram value the louvres will be positioned accordingly Telegram value 0 top deeds intermediate positio
19. Actuator 2 Connect the EIB bus voltage 3 The input connected to 230V AC drive voltage for the Shutter actuator If connecting the load to the Down terminal instead of the Up terminal then switchover mode may be inverted After finished installing and wiring up the Shutter actuator and the Shutter Blind the manual operation is carried out according to the operation mode So the Shutter actuator must be programmed first Only then the manual operation works accordingly 4 Project design and programming Overview of the function we fat Max number of Max Number of Max number of Application program we h communication objects group address associations Shutter actuator 4flod 6A 78 150 150 230M Main functions for the Shutter actuator are described as follows 1 Total move time for UP DOWN The total move time is the period that the Shutter Blind requires to move from the upper limit position to the lower limit position If the Shutter actuator receives an UP or DOWN movement command the corresponding output is switched and the Shutter is moved in the required direction until the Shutter actuator receives a STOP command or until the set the total move time has elapsed plus a period of the parameterized overflow time or until the upper or lower limit position has been reached and the motor is switched off via the limit switch 2 Duration of louvre adjustment and Maximum number of lo
20. Blind Teleg Status of operation CHX lbyte C R T The communication object is used to send the information about the current operating status of the output for the Shutter actuator Only one of the following operating states can be activated at the same time The status of operation is sent after a change the telegram 0 direct operation general operation the telegram 1 manual operation button operation the telegram 2 Forced operation the telegram 3 the blocking operation the telegram 4 Wind protection the telegram 5 frost protection the telegram 6 rain protection The telegram 7 auto operation Other are not used 14 CH X Shutter Blind Response Blind position CHX lbyte C R T The communication object is visible in the parameter Response Blind position with activated option The object is used to send the current position of the Shutter Blind after the completion of a movement Telegram value 0 top Sed intermediate position Telegram value 255 bottom 19 CH X Blind Response Louvre position CHX lbyte C R T In the Venetian Blind mode the communication object is visible in the parameter Response louvre position with activated option The object is used to send the current position of the louvre after the completion of a movement Telegram value 0 louvres opened to maximum
21. HB Auto Channel C CHC Drive CHC Protect CHC Position CHC Scene CHC Auto Channel D CHD Drive CHD Protect CHD Pasition CHD Scene CHD Auto ox j Cancel I Default Fig 5 8 parameter window CHA Auto Parameter Auto Control operation The parameter is used to set whether the Auto Control operation is activated i e the Automatic sun protection function Options Activated Deactivated 35 a S www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator If the option activated is selected the following three parameters will be visible The communication objects En Dis Auto control Sun Louvre position for Auto 0 100 and Blind position for Auto 0 100 also will be visible When the object En Dis Auto Control receives a telegram 1 the Auto Operation is activated When the object En Dis Auto Control receives a telegram 0 or the user sends a direct movement command e g UP DOWN move into position etc the Auto Operation is deactivated If the command is not belong to the direct movement command e g store the current set the preset position etc the Auto Operation is still activated The priority of general operation and automatic operation is the same but they cannot occur at the same time Note After the automatic op
22. an also be determined with the help of the total move time It is therefore important to measure and set the total move time as accurately as possible particularly if the functions Move to position and Status response are used Only then is it possible to calculate the current position of the Blind precisely Parameter duration of louvre adjustments 10 250 5ms The parameter is used for setting the duration of louvre adjustment in milliseconds After an upward movement of the Blind the louvres normally are open horizontal louvre position If the Blind is now lowered the louvres are closed first of all vertical louvre position and the Blind moves downwards If the Blind is now raised again the louvres are opened again first horizontal louvre position and then raised See following Diagram 25 ET ES N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator raised Blind 4 Blind lowered N TTT TT Parameter Max number of louvre adjustments 1 60 as reference for 0 100 WI The parameter is used for setting the maximum number of louvre adjustments It determines the current position of the louvres during operation So the maximum number of louvre adjustments must be counted by the commissioning engineer and entered a more precise value in the parameter The parameter is used together wi
23. ct or frost protect is active Options Activated Deactivated If the option activated is selected the communication object wind protect frost protect 16 T A T T www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator or rain protect appears If these objects receive telegram 1 or no telegram when the monitoring periods have elapsed The Shutter Blind is moved to the set position for wind protect for rain protect or frost protect If these objects receive telegram 0 the protect functions are reset Then lower priority operations can be carried out to control the Shutter Blind The monitoring period is restarted after the object each receipt of a telegram 0 Parameter monitoring period for wind frost rain protect 0 1000 1s 0 monitoring deactive These parameters are used for setting the monitoring period for the wind protect for frost protect or rain protect The monitoring period in the Shutter actuator should be at least twice as long as the cyclical sending time of the sensor so that the Shutter Blind is not immediately moved to the protect position due to the negligible omission of a signal e g due to a high bus load If the value of this parameter is set to 0 the monitoring of the wind protect frost protect or rain protect is deactivated and their communications are also invalid Parameter wa
24. ction to the bus and the respective manual operation buttons do not have a function In the manual operation mode the connected drives can only be controlled via the push buttons located on the device Incoming telegrams on the EIB are not carried out with the exception of telegrams to the protect communication objects If an protect e g a wind protect is triggered at a protect communication object the respective outputs are moved to the corresponding protect position and can no longer be operated via the manual operation buttons on the device Note In manual operation or protect operation status it is possible that the current position is stored as a new default value for this scene and stored as a value of the preset position via bus 14 UP DOWN buttons In the manual operation mode each output can be controlled individually via 2 buttons UP and DOWN The buttons have different functions depending on the operation mode In Venetian Blind operation mode Long push button action gt 1 5 second move UP DOWN The Blind is raised after a long operation of the upper push button A long push button at the lower push button lowers the Blind Short push button action lt 1 5 second STOP louvre adjustment If the Blind is in motion the movement is stopped by pressing one of 12 R A E ES ES Sama www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shu
25. d downward ON OFF Shutter Blind is in upper limit position OFF ON Shutter Blind is in lower limit position Shutter Blind is between lower limit OFF OFF position and upper limit position OFF Operation mode automatic operation ON Operation mode manual operation flashing Toggling between automatic operation 13 aLL TT www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator and manual operation Note In the Shutter working mode there is no louvre adjustment function except the Venetian Blind working mode 16 Working mode Here two operating mode can be freely selected for each individual output of the Shutter actuator Venetian Blind Shutter The Venetian Blind operating mode is particularly suitable for controlling Blinds with the functions UP DOWN and STOP louvre adjustment The Shutter operating mode is particularly suitable for controlling shutters awnings roller Blinds and other hangings with the functions UP DOWN and STOP as well as for controlling doors and windows The functions in the Shutter operating mode only differ slightly from the functions in the Venetian Blind operating mode The only difference is that there is no louvre adjustment function in the Shutter operating mode 5 Parameter setting description in the ETS
26. d to the set position for rain protect Telegram value 0 no rain protect operation enabled Telegram value 1 rain protect operation disabled 2 Frost protect Frost protect Ibit C W The communication object is enabled when the activated option is selected in the parameter frost protect which is used to receive the cyclical telegrams from the frost sensors If the object receives a telegram 0 the frost protect is deactivated and the monitoring period is restarted If the object receives a telegram 0 again for the first time after frost protect the Shutter Blind is moved to the position on reset of weather protect blocked and forced operation If the object receives a telegram 1 during the monitoring period the shutter Blind is moved to the set position for frost protect If no telegram is received during the monitoring period the Shutter actuator will think the frost sensor fault and move the Shutter Blind to the set position for frost protect Telegram value 0 no frost protect operation enabled Telegram value 1 frost protect operation disabled 7 CH X Shutter Blind Force operation CHX 2bit C W The communication object is enabled in the parameter force operation 2bit with activated option If the object receives a telegram value 2 or 3 the output moves to the set position for force operation and the
27. ding position for the received value In the Venetian Blind operation mode after the Shutter reaching the target position the louvres are positioned as before Only the object Louvre position 1 byte receives a telegram value the louvres will be positioned accordingly Telegram value 0 top Beets intermediate position Telegram value 255 bottom 16 CH X Blind Louvre position 1 byte 0 100 CHX 1byte C W Only in the Venetian Blind operation mode the communication is visible If the object receives a telegram value the louvres are positioned according to the received value 41 EEEE EE iwoE gt EPpEPpx LE _ _i_i_ S gt yS Ei_ _ hE SsSsSsSsSsS zyWD _ a T www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator louvres opened to maximum Telegram value 0 ode intermediate position Telegram value 255 louvres closed to maximum 17 CH X Shutter Blind Move Blind Up Down CHX 1bit C W If this communication object receives a telegram with the value 0 the Shutter Blind is raised If the object receives a telegram with the value 1 the Shutter Blind is lowered The output contact reverts to the neutral position once the total move time for UP DOWN movement has elapsed Telegram value 0 UP Telegram value
28. e means that the object has a normal link to the bus W means the object value can be modified via the bus R means the value of the object can be read via the bus T means that a telegram is transmitted when the object value has been modified U means that value response telegrams are interpreted as a write command the value of the object is updated 38 Eaa aR www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator 6 1 Communication object manual Here communication objects apply to the whole device aren t influenced by the protect functions although their priority is higher N Name Object Function Description Group Addr Length C R W T U Data Type Priority GAS Teleg Status of Voltage Teleg Status of Voltage libit C T Low G4 Teleg Status of Manual Teleg Status of Manual libit C T Low E3 En Dis Manual En Dis Manual 1 bit C g ls Low Fig 6 1 communication object manual No Function Object name Data type Flags 3 En Dis Manual En Dis Manual 1bit C W The communication object is enabled when the enable disable by object option is selected in the parameter manual operation which is used to disable and enable the Man Auto Button If the object receives a telegram 0 the Man Auto Button is disabled if the object receives a telegram 1 the Man Auto Button
29. ensor as to whether there is direct sunlight on the window Once the delay period has elapsed the Shutter actuator positions the shutter blind according to the set Position for sun 1 sun or Position for sun 0 no sun 37 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator 5 4 Working mode Shutter The Shutter operation mode is similar with the Venetian Blind operation mode in the parameters and the objects and their function is also almost the same The only difference is that there is no louvre adjustment function in the Shutter operating mode Venetian Blind sunBlind and Shutter difference as shown L L 0 FINAL UPPER POSITION 0 mm S 23 wg o w 2 4 S 8 N D S A Os aA 5 2 N i 8 N 100 FINAL LOWER POSITION max mm sunblind shutter The functions described in chapters 5 3 for the Venetian Blind operating mode also apply to the Shutter operating mode with the exception of the louvre adjustment function 6 Description of communication objects The communication object is a media that the device communicates with the other devices on the bus which means only communication objects can have the right to communicate on the bus The following details the role of each communication object Note C in Flag column in the below tabl
30. er window manual Parameter Manual operation The parameter defines whether the switchover between the operating states manual operation and automatic operation is enabled or disabled via the Man Auto Button on the Shutter actuator Options Enable Disable by object Enable If the Enable Disable by object is selected the En Dis Manual communication object appears The object receiving telegram value 0 disable the Man Auto Button and then the manual automatic mode cannot be switched If the object receiving telegram value 1 enable the Man Auto Button and then the manual automatic mode can be switched via the button If the enable is selected the Man Auto Button has been enabled Parameter Manual to automatic method This parameter defines how long the Shutter actuator remains in the manual operation state after the Man Auto Button has been pressed Options By push button Automatically and by push button 18 a ea www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator If the by push button option is selected the Shutter actuator will remain in the manual operation until the Man Auto Button is pressed again If the automatically and by push button option is selected the Shutter actuator will remain in the manual operation until the Man Auto Butto
31. eration is deactivated only when the object En Dis Auto Control receives a telegram 1 the operation is activated again Parameter Position for sun 1 sun This parameter is used to set the position that the shutter is moved into when there is blazing sun i e when the object sun receives a telegram 1 the shutter is moved into the position Options No reaction Up Down Stop Position Position2 Receive 1 byte If the option no reaction is set the output contacts remain in their current position when the object sun receives a telegram 1 If the option receive 1 byte is set when the object sun receives a telegram 1 the position depending on the values that the objects Louvre position for Auto 0 100 and Blind position for Auto 0 100 received After programming or bus voltage recovery the two objects values are uncertain and then their values are 129 by default Only when the two objects receive the values the position is confirmed In any operating status the values that the 36 T A E gt X www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator two objects receive can be stored including the protection operation of the higher priority Parameter Position for sun 0 no sun This parameter is similar with last parameter The diff
32. erence is that here defined the position that the shutter is moved into when the object sun receives a telegram 0 Parameter Delay for sun 0 6000 s This parameter defines the delay time i e the time that the Shutter actuator delays executing action when the object sun received a telegram 0 or 1 Mainly to prevent component damage or affect the motor life due to light frequent fluctuations lead to the Shutter actuator frequent action Option 0 6000 s The follow is a simple automatic sun protection system The brightness sensor is used to sense the light intensity The push button can be connected with the universal interface or substitute for other switch sensor on the bus With the help of the second switch sensor the user can specify whether to enable the automatic sun protection or to control the shutters blinds manually If the automatic sun protection is activated via a switch sensor the shutter blind moves automatically until either the automatic sun protection is deactivated via the same switch sensor or the user sends a direct movement command and the automatic function is thus also deactivated Brightness sensor control gt 4 sun sun 1 y activated j p Position for 0 no sun sun 0 i Automatic Direct positioning via UP DOWN or control deactivated movement into position The Shutter actuator receives the information via the brightness s
33. et the preset position of Blinds for a scene 0 100 0 top 100 bottom Parameter Louvres 0 100 0 opened 100 closed This parameter is used to set the preset position of louvres for a scene 0 100 0 34 ETT N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator opened 100 closed 5 3 6 Parameter window CHA Auto The parameter window CHA Auto is shown in fig 5 8 Here can set the automatic sun protection operation Depending on the strength of induction light for the brightness sensor the Shutter actuator moves the shutter blind into a set position For example the shutter blind can be raised if the sun is very weak or is not shining on the window at all As much light as possible is thereby let into the room If there is blazing sun on the window the shutter blind can be lowered and the louvres can be adjusted to the extent that direct sunlight cannot penetrate the room Meanwhile the residual opening in the blinds lets in a sufficient level of diffuse light into the room W 1 1 1 Shutter actuator 4 fold 6A 230E Protect Setting CHA Auto Manual Channel A s CHA Drive Auto control operation activated CHA Protect CHA Position Position for sun 1 sun down CHA Scene Position for sun 0 no sun Channel B CHB Drive Delay for sun 0 6000 s CHB Protect CHB Position CHB Scene C
34. g video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Depending on the parameter settings the Blind either remains in the reference position after the reference movement or moves back into the saved position Parameter limit move position The parameter is used to set whether the limit move position is activated If selected activated the Blind is moved in the set position range Options Deactivated Activated If the option activated is selected the communication object Blinds UD limited appears together with the parameters limit 1 and limit 2 When the object receives a telegram value 1 the moving range is limited when the object receives a telegram value 0 cancelling limit The moving range is set via the following parameters limit1 2 Note If the Shutter actuator has not gotten a reference position after programming or bus voltage recovery the Blind is moved completely up or down when receiving a limited command for the output It is not stopped at the upper or lower limit in this case After determine the current position the moving position will be limited in moving range When a reference movement or protect functions have been carried out the limit is cancelled If the Blind is positioned in a higher position than the upper limit it is only moved down after receiving a limited command If the Blind is positioned in a lower pos
35. he bottom toward near the target location moving after bus voltage recovery before it is moved to the set position then moved to the target location All the communication objects adopt the value 0 after programming or bus voltage recovery Note If the option no reaction has been set the position after programming or bus voltage recovery the Shutter actuator does not detect the current position of the Blind The communication objects response Blind position and response louvre position have 21 M N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator the value 129 and are not sent on the bus If after programming or bus voltage recovery a defined position of the Blind is required for the first time it is first of all raised to the top or dropped to the bottom toward near the target location moving to determine the current position and then into the target position Only the Blind finish a full running can confirm position Parameter position after reference movement This parameter specifies how the Shutter actuator behaves after a reference movement Options Deactivated No reaction Move to position 1 Move to position 2 Move to save position If the option deactivated is selected the reference movement is deactivated other option is selected and the communication object reference movement appears If
36. iority is wind protect gt operation block gt forced operation when the object wind protect receives a telegram value 0 the Blind will be moved to the set position of the block protect when the object operation block receives a telegram value 0 the Blind will be moved to the set position of forced operation when the object forced operation receives a telegram value 0 the Blind will be moved to the set position on reset of weather protect blocked and forced operation 5 3 4 Parameter window CHA Position The parameter window CHA Position is shown in fig 5 6 Here can set the preset positions for the Blind and louvre adjustment as well as response about the current position status of the Blind and louvre The current positions of the Blind and louvre are responded after the completion of a movement 31 a a 5 SO SF www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting CHA Position Manual Channel Ay E r n CHA Drive Preset for move to position 1bit deactivated CHA Protect Preset for set position 1bit deactivated CHA Scene Position 1 Blinds 0 100 o Channel B 0 top 100 bottom Channel C Position 1 Louvres 0 100 0 Channel D 0 opened 100 closed Position 2 Blinds 0 100 lo 0 top 100 botttom L Position 2
37. is enabled disable the Man Auto Button Telegram value 0 Telegram value 1 enable the Man Auto Button 4 Teleg Status of Manual Teleg Status of Manual Ibit C T The communication object is enabled when the yes option is selected in the parameter report on Man Auto Status change The object sends the status telegram after manual automatic operation status is switched When the manual operation is switched to the automatic operation the object sends a telegram 0 when the automatic operation is switched to the manual operation the object sends a telegram 1 Telegram value 0 the current status for automatic operation Telegram value 1 the current status for manual operation 5 Tele Status of Voltage Tele status of Voltage Ibit C T The communication object is enabled when the yes option is selected in the parameter report on auxiliary voltage value change The object sends the status telegram on auxiliary voltage change If the voltage drops below 9V the object sends telegram value 0 if the voltage is 9V above the object sends telegram value 1 Telegram value 0 the voltage is too low the voltage normal Telegram value 1 Table 6 1 communication object table manual 39 a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39
38. it for sensor stabilize 0 1000 1s The parameter defines the delay time of starting monitoring for the weather protect after bus voltage recovery in order to wait for sensor stabilize Normally the sensor steady required a period after bus voltage recovery in order to prevent the Shutter Blind protect occur false positives due to the sensors don t monitor telegrams send in stable period 5 2 Parameter window manual Parameter window manual can be shown in fig 5 2 It is possible to switch between manual operation and automatic operation by pressing the Man Auto Button about 2s When the manual automatic operations are switched successfully the Man Auto LED will flash for three times In the manual mode the Man Auto LED is on In the automatic mode the Man Auto LED is off The devices are in the automatic mode after connection to the bus and the manual operation buttons have no function 17 a a a a ri a a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting Channel s r Channel B Manual operation enabled Channel C Channel D Manual to automatic method automatically and by push button Man to automatic after 10 6000 1s 10 Report on Man Auto status change Report on auxiliary voltage value change Fig 5 2 paramet
39. ition than the lower limit it is only moved up after receiving a limited command Parameter limit 1 2 0 100 0 top 100 bottom The parameter is visible if the parameter limit move position is activated It is used for setting the upper or lower limit of the moving range 5 3 2 Parameter window CHA Drive The parameter window CHA Drive is shown in fig 5 4 Here set the relevant parameters with the Blind drive The current position of the Blinds can be usually calculated based on the total move time The duration of louvre adjustment and maximum number of louvre adjustments can calculate the current position of louvre The technical data and running time are different for different Blinds It is therefore important to know its technical data and running time before using 23 a a E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator the Blind It is the only way that the relevant parameters can be set precisely for the Shutter actuator W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting CHA Drive Manual Channel A Total move time 20 50000 0 1s 20 CHA Protect CHA Position Duration of louvre adjustment 10 250 1 Oms 10 CHA Scene Max number of louvre adjustments1 60 as reference 1 Channel B for 0 100 Channel C Channel D Pause on change in direction 0 255 20ms 0 Outpu
40. l travel time 10 overflow the time that the Blinds is moved from the top to the bottom is for the total move time plus the overflow time the overflow time 10 xthe total move time When the time has elapsed the output is disconnected immediately Regardless of whether the Blinds reach the top or the bottom the time will affect the entire movement Parameter Stop when reach Louvre Max or Min position The parameter is used to set whether the louvre adjustment is stopped when louvres reach Louvre Max or Min position Options Yes No If selecting yes the louvre adjustment is stopped when louvres reach Louvre Max or Min position If selecting no the louvre adjustment is still continually carried out when louvres reach Louvre Max or Min position then the position of the Blind will be changed 5 3 3 Parameter window CHA Protect The parameter window CHA Protect is shown in fig 5 5 Here set the actions in the event of the protect functions 27 eS Se ea ae a ay oe en N E i www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting CHA Protect Manual Channel y _ CHA Drive Position for wind protect activated up CHA Position Position for rain protect activated up CHA Scene Channel B Position for frost protect activated up Channel C
41. lock operation enabled Telegram value 1 block operation disabled Table 6 5 communication object table protect function 47 T E ee E E E i www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465
42. mmands Operation status The current status of each output of the Shutter actuator is transmitted in an 8 bit value such as manual operation forced operation wind protect and so on Only one of the operating states can be active at the same time The specific definition of the 8 bit value is detailed description in the communication object chapters 10 Scene An 8 bits data control 5 scenes are provided for per output at the same time In Venetian Blind operating mode position of the Blind and louvre position can be set in the parameters for per scene In Shutter operating mode position of the Shutter can be set After download programming these setting scenes can be recalled When the Shutter actuator receives a setting 10 D www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator scene telegram the Shutter Blind is moved to the recalled scene position or store the current position as a new default value for this scene number The highest bit of the 8 bits value is 0 recall this scene the highest bit of the 8 bits value is 1 store a new value for this scene 11 Automatic sun protection The Shutter actuator can be combined a very convenient automatic sun protection system with other device on the bus The automatic sun protection controls the shutter blind according to the level of sunlight Depending on the strength and direction of the sun
43. move to the target position Telegram value 1 first the Shutter Blind is fully lowered then move to the target position The detail process is described in relevant parameter chapter 8 CH X Shutter Blind Scene Save CHX lbyte C W It is able to recall or store the scene when sending an 8 bit command by this object The definition of the 8 bit command will be described below Assuming an 8 bit command binary coding as FKNNNNNN F recall scene with 0 store scene with 1 X 0 NNNNNN scene number 0 63 1 64 in the parameter setting corresponds to the scene number 0 63 received by the communication object Scene save For example scene 1 in the parameter setting has the same output result as scene 0 in the communication object Scene save 11 CH X Shutter Blind Move to preset position 1 2 CHX Ibit C W The communication object is visible in the parameter preset for move to position 1bit with activated 40 Ma a N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator option If the object receives a telegram value the Shutter Blind is moved to the preset position In the Venetian Blind operating mode the louvre adjustment is carried out according to the preset position once the position has been reached In the Shutter operating mode not the lo
44. n Telegram value 255 bottom 64 CH X Blind Louvre position for Auto 0 100 CHX 1byte CW In Auto Operation status the communication is visible only in the Venetian Blind operation mode If the object receives a telegram value the louvres are positioned according to the received value Telegram value 0 louvres opened to maximum deeds intermediate position Telegram value 255 louvres closed to maximum Table 6 3 communication object table Auto 6 4 Communication object status response When the position of the Shutter Blind and the position of louvre have been completed change the communication objects are updated immediately and send the current position to the bus When the operation is changed the corresponding communication object is also updated 43 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator immediately and sends the current operating status to the bus N Name Object Function Description Group Addr Length C R W T U Data Type Priority Ejo Tele Status of operation CHA CHA Blind 1 Byte C a OF Low mm pE Response louvre position CHA CHA Blind 1 Byte C R T Low G14 Response Blind Position CHA CHA Blind 1 Byte C R T Low Fig 6 4 communication object status response No Function Object name Data type Flags 10 CH X Shutter
45. n is pressed again or the set time for the manual to automatic has elapsed Parameter Manual to automatic after 10 60000 1s The parameter appears when automatically and by push button is selected in the parameter manual to automatic method It is used for setting the time for an automatic reset from the manual operation to automatic operation state after the last push button operation Options 10 60000s Note The operation buttons that are located at the front of the device is invalid in the protect functions Parameter Report on Man Auto status change The parameter defines whether the current operation status will be sent to the bus on manual automatic operation status change Options Yes No If the yes option is selected the Teleg Status of Manual communication object appears The object sends telegram value 1 the current status for manual operation the object sends telegram value 0 the current status for automatic operation When operation status changed the object sends the current status telegram on the bus immediately Parameter Report on auxiliary voltage change The parameter defines whether the auxiliary voltage status will be sent to the bus on auxiliary voltage change The auxiliary voltage is for the relays operation voltage if the voltage is too low the relays may not start Yes No If the yes option is selected the Teleg Sta
46. ons per output for UP and DOWN by long operating or STOP Louvre adjustment by short operating Display of movement 2 LEDs per output for UP and DOWN direction and position Movement Adjustment or the very top bottom Man Auto push button For switchover between manual operation and automatic operation Man Auto LED For displaying the operating mode manual operation or automatic operation Connections Load circuits 4 screw terminals for phase connection 2 screw terminals per output for UP and DOWN 230V AC drive voltage 2 screw terminals for L 2 screw terminals for N EIB KNX Bus connecting terminal black red Wire range Finely stranded 0 2 2 5mm Single core 0 2 4 0mm Type of IP 20 EN 60 529 protection Temperature Operation IC ae 45 C range Storage DTO oe Transport SPS IG rrcaa 70 C Design Modular installation device proM Housing Plastic White Colour Mounting On 35mm mounting rail DIN EN 60 715 5 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Dimensions 90 72 64 2mm H B T Weight 0 25KG Certification EIB KNX certified CE norm In accordance with the EMC guideline and the low voltage guideline 3 Circuit and Dimension diagram 3 1 Circuit diagram aT la E VBAL L LtLvwCaAvVWDA O00000 OOO00O 1 Bus connection terminal 5 Operation button Up Down Stop Step 2 Programming LED and Pu
47. operation of the output via the general communication objects is disabled If the object receives the telegram value 0 or 1 for the first time after a 2 or 3 the Shutter Blind is moved into the position on reset of weather alarm blocked and forced operation and the operation via the general communication objects is enabled again Telegram value 0 00 no control operation enabled Telegram value 1 01 no control operation enabled Telegram value 2 10 force move to the top operation disabled Telegram value 3 11 force move to the bottom operation disabled 9 CH X Shutter Blind Operation Block CHX 1bit C W The communication object is enabled in the parameter operation block with activated option If the object receives a telegram value 1 the output moves to the set position for blocking and the operation of the output via the general communication objects is disabled If the object receives the telegram value 0 for the first time after a 1 the Shutter Blind is moved into the position on reset of weather alarm blocked and forced operation and the 46 ES EERE ES A G SSS maa www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator operation via the general communication objects is enabled again Telegram value 0 no b
48. osition is stored as the new preset value for position 1 Note The new preset values for position1 or 2 are not retained on bus voltage failure The preset values are reset to the parameterized values Parameter Position 1 Blind 0 100 0 top 100 bottom Parameter Position 2 Blind 0 100 0 top 100 bottom Parameter Position 1 Louvres 0 100 0 opened 100 closed Parameter Position 2 Louvres 0 100 0 opened 100 closed These parameters are used for setting the preset values for the position of the Blind and louvre adjustment when moving into a preset position Parameter Response Louvre position This parameter is used to set whether the current position of the louvre is responded after the completion of a movement Options Activated Deactivated If the option activated is selected the communication objects response Louvre position appears Parameter Response Blind position This parameter is used to set whether the current position of the Blind is responded after the completion of a movement Options Activated Deactivated If the option activated is selected the communication objects response Blind position appears 5 3 5 Parameter window CHA Scene The parameter window CHA Scene is shown in fig 5 7 Here can set 5 scenes for per output and their Blind position and louvre position 33 a a ae ee ee www video star com cn make
49. r window manual 17 5 3 Working mode Venetian Blind 20 5 3 1 Parameter window channel X 20 5 3 2 Parameter window CHA Drive 23 5 3 3 Parameter window CHA Protect 27 5 3 4 Parameter window CHA Position 31 5 3 5 Parameter window CHA Scene 33 5 4 Working mode Shutter 38 6 Description of communication objects 38 6 1 Communication object manual 39 6 2 Communication object general 40 6 3 Communication object status response 43 6 4 Communication object protect function
50. s as well as the follow parameter when block its block Parameter when block its position The parameter is visible if the parameter operation block is activated It is used for setting the behavior during block function Options No reaction Up 29 I a ae a Te www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Down Stop Position 1 Position 2 If the option no reaction is set the output contact retains in their current status when the object operation block receives a telegram value 1 If the option up is set the Blind is moved to the very top when the object receives a telegram value 1 If the option down is set the Blind is moved to the very bottom If the option position 1 2 is selected the Blind is moved to the position1 2 If the option stop is set the Blind is halted immediately and the output contact reverts to the neutral position Parameter position on reset of weather alarm blocked and forced operation Here defines how the output behaves on reset of weather protect blocked and forced operation Options No action Stop Save position If selecting no action the object force operation operation block wind protect rain protect or frost protect receives a telegram value 0 the output contact retains in their current
51. sh button 6 LED displaying direction and limit position 3 Man Auto Button and LED 7 Load circuit connection terminals 6 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator 4 230V AC drive voltage input terminal 3 2 Dimension drawing Points for attention It is able to use the Engineering Tool Software ETS ETS3 version or more with a VD3 VD4 file to allocate the physical address and set the parameters To guarantee all the programmable functions in particular the UP DOWN directions of movement it is important to ensure that the drive has been connected properly The technical data supplied by the drive manufacturer must be taken into account If the outputs are switched several times in rapid succession the switching of the output contacts is delayed The following process should be carried out during the initial commissioning of the Shutter actuator 1 Install and wire up the Shutter actuator The Shutter actuator has 4 outputs has two connection terminals for per output i e a down terminals and an up terminals Meanwhile each output need to be connected to 230V AC operating voltage See circuit diagram 7 SSS SSS E _ SSS www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter
52. th above parameter The louvre adjustment time that the louvres is adjusted from fully closed to fully open is for the duration of louvre adjustment times the Max number of louvre adjustments Parameter pause on change in direction 0 255 20ms The parameter is used for setting the pause on change in direction in milliseconds The technical data supplied by the drive manufacturer must be taken into account to enter a suitable value in the parameter Parameter outputs are disconnected from voltage after This parameter is used to set the output off delay time Options End position no overflow End position 2 overflow End position 5 overflow End position 10 overflow End position 20 overflow Total travel time 10 overflow If selecting End position no overflow the output is disconnected from voltage without 26 Ree ee en eee R www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator delay i e when the total move time has elapsed the output is disconnected immediately If selecting End position 2 20 overflow when the Blinds reach the end position completely up or completely down the output is disconnected after a delay time the delay time 2 20 xthe total move time If the end position does not reach completely up or completely down the output will be disconnected without delay If selecting Tota
53. the shutter blind is moved into any position via an 8bit object value or into a predefined position depending on the situation 12 Protect function Protect function weather protect forced operation and operation block Their priority can be set via parameter Any protect function has been activated for an output the Shutter Blind will be moved to the protect position and the operation of the output is disabled If more than one protect function are active at the same time the actuator will control the Shutter Blind in accordance with defined priority order in the parameter Weather protect has wind protect rain protect and frost protect Their priority can be set via parameter If the actuator has not received any signal from the weather sensors during the monitoring period it will think that the sensors occur fault or bus interrupt then the protect function is carried out immediately when the period has elapsed If the actuator receives signal 1 it will go into protect operation immediately If the actuator receives signal 0 the protection is reset and the monitoring period restarts The monitoring period can be set separately for wind protect rain product and frost product The monitoring period of the Shutter actuator should be twice as long as the cyclical sending time of the sensor so that the Shutter Blind is not moved immediately to the weather protect position when a signal is omitted e g due to a high bus load When
54. the weather protect is reset the Shutter Blind is moved to the set position on reset of weather protect blocked and forced operation and operation is enabled If more than one protect function occur when the high priority protect is reset the Shutter Blind is moved to the position 11 EEE__ _ A EE EEE EEE A www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator of the lower priority protect when the lower priority protect is reset the Shutter Blind will be moved to the reset position of protect For example currently there are three protect functions occur the priority is forced operation gt wind protect gt block when the forced operation is reset the Shutter Blind will be moved to the set position of the wind protect when the wind protect is reset the Shutter Blind will be moved to the set position of block when block is reset the Shutter Blind will be moved to the set position on reset of weather protect blocked and forced operation 13 Manual Automatic operation It is possible to switch between manual operation and automatic operation by pressing the Man Auto Button about 2s When the manual automatic operations are switched successfully the Man Auto LED will flash for three times In the manual mode the Man Auto LED is on In the automatic mode the Man Auto LED is off The devices are in the automatic operation mode after conne
55. ting video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting CHA Scene Manual Channel a CHA Drive Scene function is activated CHA Protect CHA Position 1 gt Assignment Scene NO 1 64 not assignment Channel Blind 0 100 0 top 100 bottom Q Channel C Channel D Louvres 0 100 0 opened 100 closed 0 2 gt Assignment Scene NO 1 64 not assignment Blind 0 100 0 top 100 bottom lo Louvres 0 100 0 opened 100 closed 0 3 gt Assignment Scene NO 1 64 not assignment Blind 0 100 0 top 100 bottom 0 Louvres 0 100 0 opened 100 closed 0 4 gt Assignment Scene NO 1 64 not assignment Blind 0 100 0 top 100 bottom 0 ee Fig 5 7 parameter window CHA Scene Parameter Assignment Scene NO 1 64 There are 5 various scenes can be set for per output It is able to allocate 64 different scene numbers for per scene Options Not assignment Assignment to scene 1 Assignment to scene 64 Note 1 64 in the parameter setting corresponds to the telegram 0 63 received On bus voltage failure the new value that is stored for scene is not retained the scene recovers to the parameterized value Parameter Blind 0 100 0 top 100 bottom This parameter is used to s
56. tion manually making more precisely This manual provides the detailed technical information about the Shutter actuator not only the installation and programming details but also the usage explanation in actual application 1 1 Product and functional overview The Shutter actuator is the modular installation devices They can be installed in the distribution boards on 35mm DIN rail according to EN 60 715 The devices adopt screw terminal to achieve electrical connection The connection to the EIB KNX bus is established via a bus connecting terminal The input need connect 230V AC operating voltage for the Shutter actuator It is possible that working mode of the Shutter actuator is switched between manual operation and automatic operation by pressing the Man Auto Button about 2s and the Max Auto LED will display the current operating 3 EE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator status Push buttons are located at the front of the device which are used to raise and lower the Shutter Blind manually to stop the Shutter Blind movement and for Louvre adjustment The current direction of movement or the current limit position is displayed via LEDs The output contacts for the directions UP and DOWN are mechanically interlocked so that voltage cannot be applied at both contacts at the same time The pause on change in direction can be set via the
57. ts are disconnected from voltage after End position no overflow Stop when reach Louvre Max or Min position no Cancel Default Fig 5 4 parameter window CHA Drive Parameter Total move time s 0 50000 0 1s The parameter is used for setting the total move time in seconds The total move time is the period that the Blind requires to travel from the upper limit position to the lower limit position see following Diagram If the Shutter actuator receives an UP or DOWN movement command the corresponding output is switched and the Blind is moved in this direction until the Shutter actuator receives a STOP command or until the upper or lower limit position has been reached and then the motor is switched off via the limit switch If the Blind is switch off via the limit switch the corresponding output contact of the Shutter actuator remains closed until the set total move time has elapsed plus the parameterized overflow time see parameter outputs are disconnected from voltage after description only then the output contact reverts to neutral position 24 Cee ee ee eee eee eee eee eee ee aa www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator Upper limit Shutter UP switch Total travel N N N time iy Lower limit ey i ee ge eee aa switch Note The current position of the Blind during operation c
58. tter Actuator the two push buttons briefly If the Blind is idle a louvre adjustment upwards is carried out with a short operation of the upper push button a louvre adjustment downwards is carried out with a short operation of the lower push button In Shutter operation mode Long push button action gt 1 5 second move UP DOWN The Shutter is raised after a long operation of the upper push button A long push button at the lower push button lowers the Shutter Short push button action lt 1 5 second STOP If the Shutter is in motion the movement is stopped by pressing one of the two push buttons briefly If the Shutter is idle no function is carried out after a short push button action 15 LED display LEDs are located at the front of the device which are used to display the status of each output Each output is display individually via 2 LEDs The display is identical to the two operation mode automatic operation and manual operation In the Venetian Blind and shutter working mode the display LEDs is also identical The possible states of the display LEDs for the operating modes Shutter and Blinds are outlined in the following table Output UP Output DOWN Man Auto LED Status LED LED Shutter Blind is being raised or louvre is flashing OFF being adjusted upward Shutter Blind is being lowered or louvre OFF flashing is being adjuste
59. tus of voltage communication object appears Normal operating voltage of the relays must be 9V or more if the voltage drops below 9V the object sends telegram value 0 then the relays may fail to start if the voltage is 9V above the 19 T A EEE EEE EEE EE a es www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator object sends telegram value 1 the relays start normally When the voltage is lower than 9V or higher than 9V the object sends immediately the current voltage status telegram to the bus The actuator sends immediately the current voltage status telegram to the bus after programming or bus reset The following detailed description of the channel working mode and the corresponding parameters and communication objects 5 3 Working mode Venetian Blind 5 3 1 Parameter window channel X The parameter window channel X is shown in fig 5 3 Channel X or X mentioned below means any output of the switch actuator which has the same setting parameter interface and communication objects W 1 1 8 Shutter actuator 4 fold 6A 230W Protect Setting Channel A Manual Channel A CHA Drive Working mode Venetian Blind CHA Protect a CHA Position Position on bus votltage recovery no reaction CHA Scene Channel B Position after reference movement deactivated Channel C Channel D Limit move position
60. uvre adjustment Telegram value 0 move to position 1 Telegram value 1 move to position 2 12 CH X Shutter Blind Blind Up Down limited En Dis CHX Ibit C W The communication object is visible in the parameter limit move position with activated option It is used to limit moving rang for the Shutter Blind If the object receives a telegram value 1 the Shutter Blind can be moved only in the set moving rang The louvre adjustment is not limited Telegram value 0 cancel limited Telegram value 1 activate limited 13 CH X Shutter Blind Set preset position 1 2 CHX Ibit C W The communication object is visible in the parameter preset for move to position 1bit with activated option It is used to modify the preset position i e the current position of the Shutter Blind is stored as a new preset value for position1 or 2 when the object receives a telegram value Telegram value 0 the current position is stored as the new preset value for position 1 Telegram value 1 the current position is stored as the new preset value for position 2 After stored called position 1 or 2 the Shutter Blind will move to the new preset position 15 CH X Shutter Blind Blind position 1byte 0 100 CHX lbyte C W If this communication object receives a telegram value the Shutter Blind moves to the correspon
61. uvre adjustments The duration of louvre adjustment is the period that louvre adjustment is carried out when the Shutter actuator receives an up or down adjustment louvre command The maximum number of louvre adjustments is the number of adjustments needed to move the louvres from fully closed to fully open The current position of the louvres during operation is determined by the parameter Max Number of louvre adjustments The maximum number of 8 ea www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator louvre adjustments must be counted by the commissioning engineer and entered as a parameter Whether the louvre adjustment is stopped when reach to louvre Max or Min position which can be set via parameter 3 Pause on change in direction for the Shutter Blind movement and louvre adjustment To prevent the Shutter drive from being damaged by a sudden change in direction the output contacts are disconnected from the supply for the duration of the pause on reverse Only then is the output contact switched for the required direction of travel The technical data supplied by the manufacturer of the respective drive mechanism must be taken into account when setting the pause on change in direction The output contacts for the directions UP and DOWN are mechanically interlocked so that voltage cannot be applied at both contacts at the same time and thus damage
62. video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Shutter Actuator ageing processes Here a reference movement can be triggered via a bus telegram to move the Shutter Blind right to the top or right to the bottom then into the target position or back into the saved position 6 Limit move position The movement range can be limited for the user for specific applications For example the control of the Shutter Blind can be limited to a range of 20 to 80 and then the Shutter Blind can be only moved up to 20 position or moved down to 80 position 7 Preset position Each output provides two preset positions in the Shutter actuator These positions can be recalled via a 1 bit command Meanwhile the current position can also be stored as a new preset position via the function set preset position After bus voltage failure the new preset position is not retained will be restored parameter settings 8 Move to position 0 100 The Shutter Blind can be moved into any position via an 8 bit value In the Venetian Blind operating mode the louvre can also be positioned into any angle via an 8 bit value In this way it can be decided for each movement command which position the Shutter Blind should move into 9 Status response Position status when the Shutter Blind reachs to the target position the Shutter actuator sends the Shutter Blind position and the louvre position on the bus via two 8bit co