JB-QBC-5i FIRE ALARM CONTROLLER USER'S MANUAL
Contents
1. associate OR2 means in the condition any of two alarms can start bus device of associate AND means in the condition all of alarms can start bus device of associate press or to change the different logic option press or move cursor to needed location input the address after confirm it s correct press enter key The condition means all bus device input when the analogue value of bus device in condition is rising according to relative logic relationship to start the remote control module Press or to edit another one Other 4 Signal Iso 3 Zone mapping 1 LocalBox Setup 2 Type settings Other Other includes 4 items No 1 and No 3 item is designed for water mist controller Local box setup 10 20 JB QBC 5i Fire Alarm Controller Stop 1012 Start 1011 Module 1013 Zone 5001 LocalBox Setup Start code relative to start button in local control box stop code relative to stop button in local control box module code means remote module parts in local control box zone means water mist control zone of water mist controller 5001 means No 1 fire extinguishing zone of water mist controller when local control box start button is pressed need to keep press state several seconds relative fire extinguishing zone start after press stop button closed the relative fire extinguishing zone when fire extinguishing has ac
2. when designed YES system will send this machine all faults fire alarms linkages water mist zone states and actions through NMEA0183 format to VDR You can press or to switch YES or NO to confirm whether it need to set out signal or not press enter to confirm input setup VDR socket connect to A1 B1 Fire alarm repeater sum System 13 15 JB QBC 5iR Sum 002 According to the users actually requirement one fire alarm control panel can bring several fire alarm repeaters in this screen input details count in order to system monitors all fire alarm repeaters state Delays System 14 15 B1 B2 B3 Delay s 120 Here setup the delay time from fire alarm to alarm bell start as second as unit Earth fault grade System 15 15 Earth Fault Grade 052 When details using it can modify earth fault testing grade in the certain range Communication 1 Browse Room Info Communication 3 Upload Record 2 Exchange Room Info 16 20 JB QBC 5i Fire Alarm Controller Online communication menu is mainly used with computers it can download bus device position description information it also can send information of black casket to computer to offer system analysis Browse room info Beside Engine Room Browse Room Info 3004 The item has consulted room number check whether setup has made mistake or not Press or switch to last one or next address Press or s
3. B1 B2 bell Mointor System 08 15 The item mostly monitor alarm bell whether it has break off or not when it s normal alarm bell hasn t 24V output when fire alarm happened it hasn t confirmed in the certain time output 14 20 JB QBC 5i Fire Alarm Controller 24V start alarm bell details operation is the same with last one Fire alarm repeater break off fault JB QBC 5iR Mointor System 09 15 Yes The item mostly monitor fire alarm repeater whether it s right or not when the communication is not correct it can offer fault alarm Details operation is the same as the last one Water mist controller communicate System 10 15 XSW 5i Communication Yes The item mostly monitor water mist controller whether it has installed well or not when the communication isn t connected display fault alarm details operation is the same with the last one 7 short 1 length happen fountain 7 S 1 L Generator System 11 15 Yes 7 short 1 long can control alarm bell to output 7 short 1 length signal according to practice using user can chose 7 short 1 length happen fountain or using outside input 7 short 1 length happen fountain when set up inside control signal from GA1 input when set up outside 7 short 1 long control signal from GA2 input Send alarm to VDR System 12 15 Send Alarm to VDR Yes 15 20 JB QBC 5i Fire Alarm Controller
4. JB QBC 5i FIRE ALARM CONTROLLER USER S MANUAL JB QBC 5i Fire Alarm Controller Hello Welcome to Brightsky world The new technical design JB QBC 5i fire alarm control system will exceed your mind 4 loop look up at the same time speed fast function supper it can connect with XSW 5 water mist controller as the water mist system flush mounting fission installation mode is good for the marine more image interface will let you feel friendly from SCM world system speed has be improved Brightsky Electronic aim to high reliability and veracity which has show This manual will show you the supper function of the fire alarm controller Function Image menu operation new feeling Alarm message record function Display each detector state Support loop wiring mode 4 Loops total 1000 pcs intelligent bus device Give the bus device address description to confirm one alarm position These description can be input in computer Then transfer them to fire alarm controller For more details Please learn 5i program tool manual All associated message can be programmed in this controller This controller can reach the China CCS approval requirement for marine fire alarm system Our Description The following description Bus device are smoke detector heat detector manual call point signal input module etc fire alarm device and remote control module etc associate control device Due to the
5. habit or description requirement use detector to replace smoke detector heat detector manual call point signal input module etc fire alarm device 1 20 JB QBC 5i Fire Alarm Controller Technical data Main power supply MSBD AC 220V 10 15 50HZ Emergency power supply ESBD AC 220V 10 15 50HZ Ship s DC power supply DC 24V 10 10 Inner battery supply DC 24V 7AH Power consumption Monitor state 2 4W Alarm state 10W Basic monitor capacity 4 loops it can connect 5i series bus device 1000pcs The current of one flame detector is the same as 8 normal bus device s rolling period 10S Signal transmission distance 1500m Wiring mode 1 Loop wiring 2 5i series detector two lines non polarity 3 5i series module two lines polarity T anode T cathode Using cable Signal line is 1 5mm2 marine communication cable Power supply line is 2 5mm2 power cable Output control terminal Fire alarm output FIRE EXT1 EXT3 fire alarm delay output B1 B3 delay time can be changed Others like default output etc Working environment temperature 0 55 Relative humidity 95 Outline dimension 290 180 51 H W T mm3 Installation mode Flush mounting fission installation Weight About 12Kg Alarm record The number of recording about the alarm message is
6. modules have some problems the controller will report detector or remote control module fault MSBD FAULT main AC220V power supply fault MSBD fault means the voltage of AC220V power is lower than 187V including power off the controller give MSBD fault fault indicator flash meanwhile the controller will switch to the emergency power supply automatically ESBD FAULT emergency AC220V power supply fault When it hasn t ESBD report ESBD fault Ship s DC24V power supply fault When it hasn t ship s DC24V input report DC24V fault Battery fault Battery fault in the controller means the battery s voltage is lower than 19 2V battery break off or battery cannot be charged the controller report battery fault Earth fault When earth insulated resistance of the controller hasn t reach insulated requirement it will report earth fault Loop break off fault 7 20 JB QBC 5i Fire Alarm Controller When the loop has break off the controller can report the disconnected loop number and T T line disconnected Door hold fault Magnetic Door hold disconnection fault In normal magnetic door hold has EOL When it is disconnected report door hold fault B1 B2 fault Alarm bell line disconnection In normal alarm bell has EOL when control alarm bell break off report alarm bell break off fault XSW 5i fault Water mist controller disconnected or fault When water mist controller combined with fire alarm cont
7. to register details register diagram is the following Register 0049 074 0049 means current register detector numbers 4 loops in total 074 means current checking detector address Max address 250 device register need 2 times to confirm all register bus devices be counted System management There are 15 items in system management it mainly aim to configure the system states Associated status System 01 15 Associated Status Auto 12 20 JB QBC 5i Fire Alarm Controller When the linkage state set up automatic detector report fire alarm it can be according to programmed logic relationship to start the relative devices when set up manual devices only can manual start the detector only can fire alarm Main power supply fault monitor System 02 15 MSBD 220VAC Mointor Yes when set up YES system monitor main power whether it has fault or not When it has fault offers fault alarm It can press or to switch YES or NO to confirm whether it needs to report fault press enter to confirm all input informations Emergency power supply fault monitor System 03 15 ESBD 220VAC Mointor Yes when set up YES system monitor emergency power whether it has fault or not when it has fault offer fault alarm It can press or to switch YES or NO to confirm whether report fault or not press enter to input the setup when it hasn t emer
8. e same time you can use or to switch the alarm type and use or to see the last or the next message in the same type 6 20 JB QBC 5i Fire Alarm Controller FirstFile 2001 09 31 Fire 02SuSi 00Asso 00 02 02 2001 09 31 SIGN Engine room in this picture 02 02 the first 02 means No 2 fire alarm the second 02 means fire alarm sum is 2 2001 is No 1 detector of No 2 loop give this alarm 09 31 is the fire alarm happening time SIGN is bus device type Engine room is this detector s description Fault alarm In order to let fire alarm control system in good condition for a long time controller should monitor the status of lines bus device detectors remote control modules etc and power supply If the status is abnormal give fault alarm During the fault stage the controller set out fault warning sound the fault indicator in the panel flash fault type displayed on the screen If it is the fault of the detector or remote control module alarm address quantity time etc information will be displayed in screen Operator should debar fault in time after fault disappear the controller reset automatically and turn to normal monitoring state 02 05 2001 09 31 SIGN 06 12 17 09 31 Fault Sum 05 Engine room Detector or remote control module fault In normal state each of detector or remote control module has relatively steady value If the value is abnormal it means detectors or remote control
9. ey and enter the password Menu Password If the password is correct you will enter main menu otherwise return to monitoring state Main menu had nine menu options browse record time program other register system communication exit Press or to select each function press enter key to enter the functions All the menu need to be operated according to the protocol press enter key to enter and press cancel key to exit Browse Browse 02Loop 010 001 002 003 005 006 007 011 012 013 045 02 loop 010 means 10 bus devices registered in Loop 2 press or to switch to Loop 1 or loop3 Press or to switch to the next page or last page the loop is the same Record FAULT 2002 Record 010 500 2006 05 15 09 45 In record there are all informations of fire alarm controller includ all fire alarm fault associate super signal and water mist fire extinguishing zone action Max record 500 pieces Press or to change to the next or last page Time 9 20 JB QBC 5i Fire Alarm Controller Time 2006 05 15 09 45 Press or to move cursor input current machine time confirm it s correct then press enter key Program Associate 1007 1007 Logic AND Condition 1002 1003 Program 001 In the item of logic you can choice OR1 OR2 or AND OR1 means in the condition any of alarm can start the bus device of
10. gency AC220V power supply it can set up this item no need DC24V fault monitor Ships DC24V Monitor Yes System 04 15 when set up YES system monitor whether DC24V power supply has fault or not when it has fault it can offer fault alarm It can press or to switch YES or NO to confirm whether it needs to report fault or not press enter to confirm input setup When the ship hasn t reserved DC24V power it can set up this item NO Battery fault monitor 13 20 JB QBC 5i Fire Alarm Controller System 05 15 Battery Mointor Yes when set up YES system monitor inside battery whether it has fault or not when it has fault it will offer fault alarm It can press or to switch YES or NO to confirm whether it will report fault or not Press enter to confirm input setup Earth fault monitor System 06 15 Earth Fault Mointor Yes The item mostly monitor system whether earth all right or not when earth can t be satisfied with requirements it can offer fault alarm details operation is the same as last one Door hold break off fault monitor System 07 15 Door Hold Monitor Yes The item mostly monitor magnetism door whether it has break off or not when it s normal magnetism door output 24V when it has fire alarm not output 24V details operation is the same as last one Alarm bell break off fault monitor Yes
11. he person is tested by our company then he can operate the controller due to basic maintain the trained person can deal with it If You unfamiliar the abnormity condition you can call our service engineer or we will service on current place You can also visit our website to know our company dynamic state Specially Wuxi Brightsky Electronic Co Ltd will obey abidance development strategy so our company will keep the modification right which we don t inform you before All right by Wuxi Brightsky Electronic Co Ltd 20 20
12. less than 500pcs Including opening fire alarm fault and associate associate programming max 150 OR1 OR2 AND logic each of them 50 Detector s description number Less than 1000 Character of Each detector s description Less than 20 English characters or 10 Chinese characters Structure and installation The controller is used flush mounting fission installation bosom has set up 7AH full airproof no maintenance battery compact structure distribution reasonable outline nice 2 20 JB QBC 5i Fire Alarm Controller Installation Adopt flush mounting fission installation mode integrate in operation table of marine wheel house control display part embed in the control panel offer the relative connection board convenience user connection Installation sketch map is as the following here connect one set of fire alarm controller and one set of water mist controller 3 20 JB QBC 5i Fire Alarm Controller Interface board terminal description 4 20 JB QBC 5i Fire Alarm Controller 5 20 JB QBC 5i Fire Alarm Controller From Installation to Running 1 Please read this manual carefully 2 According to Installation chapter install the controller 3 Using mega ohm meter to measure alarm bus the resistance is more than 20 mega ohm according to fire control specification requirement to install detecto
13. repaired to restart the machine After open machine the LCD screen display random code wordage or program has bad or hasn t tightened instead or insert chip again then it s OK After open machine the controller light and sounder patrol check normally but there hasn t be in a poor light and display this is due to LCD screen contrast is too small so we can t watch display content adjust main board contrast electricity position is OK 19 20 JB QBC 5i Fire Alarm Controller Attention item Fire alarm controller should have well earth there has earth signal in the controller earth requirements should be fit for GBJ116 88 fire automatic alarm system design requirement chapter 4 Fire alarm controller is belong to fire extinguishing devices normally there has person keep watch management and maintain check the function whether it s normal or not at that time checking the function whether it s OK or not on time meanwhile make the memo at any moment when it happens fault You should inform professional person or factory to repair After the main power stop using inside power supply of controller if the controller set out battery fault alarm signal it means reserved battery voltage is too low at that time it should using fetch up to prevent reserved power to discharge then destroyed battery Our service The operation person of controller should be trained by our company when t
14. roller is fault it will report XSW 5i fault JB QBC 5iR fault Fire alarm repeater fault When the fire alarm repeater combined with fire alarm controller is fault it will report JB QBC 5iR fault Fire extinguishing zone disconnection fault When the extinguishing zone of water mist controller combined with fire alarm controller is disconnected it will report fault of fire extinguishing zone Water pump state monitor Monitor pump status such as pump running water low level Device Test Device Test 001 RegVal 24 00 00 00 CurVal 24 00 00 00 Loop 01 02 03 04 Type SI You can check each module or detector analogue value 001 means No 1 detector Loop No display 4 loops RegVal is the registered value CurVal is the analogue value of the module or detector currently use or detector address will plus or minus 1 each time Use or detector address will plus or minus 20 each time Press cancel key to exit Device Test state Module operation ENTER activated Module operate Module 0000 CANCEL close in monitor state Press to enter module operation it can open or closed remote control module directly press number key to input module address press enter key to open this module cancel key closes this module and return to monitor state Test Use to test the buzzer LED LCD Screen 8 20 JB QBC 5i Fire Alarm Controller Menu operation function In monitoring state press function k
15. rs meanwhile it should check the connection diagram whether it s right or not each of tighten firmware whether it s fastened or not 4 Power on Basic function Power on First time use this controller power on all power s switch after the controller initialize self test indicator and sounder after power supply indicator flash this system is in normal monitoring state following is the system normal state s picture 10 36 JB QBC 5i Fire Alarm Control Panel BrightSky Electronic Fire alarm In the normal monitoring state the controller monitors each of registered detectors check current smoke deepness or temperature value of each detector meanwhile according to this parameter to calculate identify If the value reaches the fire alarm s condition it will change into the fire alarm state at once At this time the controller set out fire alarm sound fire alarm indicator will flash the screen display alarm address quantity etc information meanwhile the output terminal B1 B2 B3 begin to delay if no man operate the controller within 2 minutes silence or reset the delay output will be activated if the system is in automatic state the controller will activate remote control module according to the associated program open or close outside devices such as fire extinguishing pump etc The fire alarm SuSi super signal and associate information is pagination displayed If there are two alarms at th
16. tion the relative module start in the local control box Type settings Type SMOK Range 1001 1001 Type settings When find register bus device type is wrong using this option to forced correct the device type of the bus device For example when connected with flame detectors registered devices type is signal need to be changed to smoke or complex type then it can operate Zone mapping Detec 1 1001 1001 Zone mapping Detec 2 1002 1002 Zone mapping detector 1 and detector 2 relative detector 1 and 2 of water mist control panel when water mist controller set up automatic mode and detector 1 and detector 2 alarm at the same time then start relative fire extinguishing zone under manual mode detector 1 and detector 2 can alarm but it can t start linkage fire extinguishing zone Signal isolation 11 20 JB QBC 5i Fire Alarm Controller Signal 2001 Iso Area 2002 2003 Signal Iso Signal isolation is set up for liable to disturb zone it can isolate effected detectors prevent fire alarm fault Signal can be signal input module remote control module etc in the example signal input module 2001 can input detector 2002 and 2003 can t report the fire alarm meanwhile the indicator of the second loop can flash it means some detectors in the loop is isolating now Register Normal register diagram is the following 7 Register Register Now press 7 key
17. to return finished address position description information setup Restart the power of controller the system operates normally 18 20 JB QBC 5i Fire Alarm Controller Upload record Upload Record Range 001 050 The users can upload the print record into the computer use the COM received software to get the fire alarm controller history record For example input the record range is from 001 to 050 Using COM to get the following data Linkage No 5303 water mist zone 3 SV ation 2006 05 22 09 15 Linkage No 1013 13 2006 05 22 09 08 inspection No 1012 12 2006 05 22 09 08 Fault No 6013 fire display panel 3 connection fault 2006 05 22 09 05 Fault No 6012 fire display panel 2 connection fault 2006 05 22 09 05 Fault No 6042 2 loop tote lines break off 2006 05 22 09 05 Affair No 5050 start the machine 2006 05 22 09 03 Fault No 1002 2 2006 05 22 09 02 Fault No 6001 main power supply fault 2006 05 22 09 02 Fault No 6006 urgency power supply fault 2006 05 22 09 02 Tone up function It can isolate each of loop very fast directly press one loop four loop one of them relative loop red indicator always bright it means loop is isolated Repairing and Maintenance When open machine the controller hasn t any feedback Check main reserved power whether it s normal or
18. witch loop signal Press or can increase fast or reduce address For example current address is 3005 after press the address 3006 After Press the address is 4006 after press the address is 4026 Exchange room info Exchange Room Info Users can use computers to edit each address relative position description after computer programmed use our company offered software to load fire alarm controller During the details exchange information the LCD screen can display current exchanged information Adopt 485communication mode connect the connection socket A1 B1 The load diagram 17 20 JB QBC 5i Fire Alarm Controller If it s first time to use the program it must press Save to save one standard input format then open the saved files by notebook software As the following diagram Behind the relative address input details address information attention input Chinese max 10 letters 1 Chinese is similar with English or number 2 letters After setup finished return to RoomSetup program Press Load input setup files Press Setup edit Baudrate 9600 as the following diagram Press OK confirmation System Ver Chose 2006 It can choose Loop number total 4 loops then set up input address range at last press Program to input programmed address description information in the controller display current exchanged information after set up finished Press Return
Download Pdf Manuals
Related Search
Related Contents
Samsung WB500 راهنمای محصول Philips DLA40113 For iPhone 3G VideoShell equipos auxiliares para lámparas de halogenuros metálicos Bionaire EnviroKlean BAPF29 User's Manual Samsung MM-DA25T User Manual 超音波流量計 検出器 一太郎 10/9/8 文書 Dimplex S1 7KS User's Manual 取扱説明書 Datasheet - Chroma Systems Solutions Copyright © All rights reserved.