USER MANUAL MATCH 500-1500 UPS - aku-bat

image

Contents

1. MAX 48V 100mA 4 2 Relay Interface Card option The card is equipped with potential free change over contacts for the following alarms e mains failure e battery low For more information please refer to the user manual that comes with the interface card 4 3 SNMP Interface Card option This card allows the data interface to be connected directly to an Ethernet network For more information please refer to the user manual that comes with the interface card 5 Maintenance 5 1 General The GE Digital Energy Match UPS is virtually maintenance free take care of proper environmental conditions and keep air inlets outlets free of dust Please read 2 1 5 2 Fuses If the AC input fuse 1 fig 1 is defect be sure it is replaced by a compatible fuse from the same make and type FERRAZ TISP 5x20 or LITTLEFUSE 215 5x20 or WICKMANN 19181 5x20 Fuse ratings see chapter 7 5 3 Batteries The service life of the battery is up to 6 years As a healthy battery is critical to the UPS keypad I allows a Quick Battery Test see 3 2 3 When the condition of the battery is critical a replace battery alarm will be generated Have your dealer replace the batteries as soon as possible 5 4 UPS Configuration Tool With the UPS configuration software that came with the unit on CD ROM you are able to change the setting of the auto off function 3 2 3 Insert the CD ROM in your computer and 1 Select RUN from the start menu
2. amp gt The UPS contains potentially hazardous voltages Do not open the UPS there are no user 7 serviceable parts inside A All maintenance and service work including replacement of the batteries should be performed A by qualified service personnel 1 3 Transport Storage e No liability can be accepted for any transport damage when the equipment is shipped in non original packaging e Store the UPS in a dry location with the batteries in a fully charged state Storage temperature must be within 20 45 C If the unit is stored for a period exceeding 3 months optimal battery lifetime is obtained if the storage temperature does not exceed 25 C e If the unit is stored for an extended period of time the batteries must be recharged periodically Connect the unit to a wall outlet and recharge the batteries for 24 hours if the storage temperature is within 20 and 30 C every 3 months if the storage temperature is within 20 and 45 C every month 2 Installation The shipping box contains a Match UPS one for Match 500 or two power cords a CD ROM and this manual After unpacking inspect the UPS for damage If you find any damage please immediately notify the carrier and place of purchase IMPORTANT Before making any connection and switching on the UPS please check the following conditions e your mains supply is 220 240 Volts and 50 or 60 Hz and e the total power demand of the connected equipment does not ex
3. Alarm Indications 3 3 1 Charger on 3 3 2 Normal operation 3 3 3 AVR active 3 3 4 On battery 3 3 5 Battery low 3 3 6 Replace battery 3 3 7 Overload 3 3 8 High temperature 3 3 9 Programmed shutdown 4 COMMUNICATION cecceccecceeeeecceceeseceeceeeeeeeaecaeceeeeaesaesaeceeeeaesaesaeseeesansaesanseneeateats 7 4 1 RS232 Port 4 2 Relay Interface Card option 4 3 SNMP Interface Card option 5 MAINTENANCE aaanneeeesoennneeessooseennnnesoornrnnnnesoonnnnnnesoorrnnnnnnesorrnnnnnnneoernnnnnnnnoonn ennn 7 5 1 General 5 2 Fuses 5 3 Batteries 5 4 UPS Configuration Tool 6 TROUBLESHOOTING vices ccseccsssetacssteetavestaetuvestinsusvsnvsiavesneesavssnvetavesteesasenteviusnteetsvnns 8 7 SPECIFICATIONS niisiis iiiaio nave lvilediehtlvdidaiitits 9 General Electric Digital Energy All rights reserved reproduction without permission prohibited This manual may be subject to change no liability can be accepted for any error or omission LX OPM_MAE_XXX_0K5_1K5_XGB_V041 1 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 1 Introduction 1 1 Introduction The GE General Electric Digital Energy Match UPS an uninterruptible power supply protects your equipment from all forms of power interference including complete power failures 1 2 Safety Rules 4 CAUTION RISK OF ELECTRICAL SHOCK The UPS contains batteries The appliance outlets may be electrically live even when the UPS is disconnected from the mains
4. connect this cord to the male input socket 2 at the rear of the UPS 3 Using the output cord s provided connect the computer to the appliance outlets 4 of the unit 4 Connect the mains cord of the UPS to a working grounded AC wall socket outlet The green LED on 7 fig 5 will blink now mains power is available and the batteries are charging If the LED does not blink press l briefly Probably LED replace battery lights up the LED goes out as soon as the batteries have been fig 3 charged 5 For best results allow the UPS to recharge the batteries during a period of approx 2 hours It is acceptable to use the UPS without first charging the battery but the runtime may be reduced 6 For advanced communication possibilities the RS232 interface port 3 can be connected to a computer system and or optional interface cards 5 can be added See chapter 4 LX OPM_MAE_XXX_0K5_1K5_XGB_V041 3 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 3 Operation Please refer to figure 5 3 1 Start up 3 1 1 Start up mains available 1 Press keypad l 13 briefly LED on already blinking will illuminate continuously now 2 The equipment connected to the UPS can now be switched on 3 1 2 Start up mains not available If the mains input is absent power cord not connected or mains failure 1 Press keypad I briefly and then 2 Press keypa
5. 2 Type a conftool type for a the appropriate drive letter 3 Press ENTER See also README TXT LX OPM_MAE_XXX_0K5_1K5_XGB_V041 7 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 6 Troubleshooting Whenever a malfunction occurs first check external factors e g connections temperature humidity or load to determine whether the problem is caused by the unit itself or by its environment Subsequently check the input fuse it may be blown If so replace the fuse see 5 2 and be sure that the UPS is not overloaded The following chart is a simple troubleshooting checklist only If the suggested solution does not succeed or if the information is insufficient to solve the problem please contact your dealer or consult www gedigitalenergy com PROBLEM POSSIBLE CAUSE SOLUTION Connected equipment not Overload causes reduced Reduce load operating properly buzzer output voltage sounds continuously Blown input fuse Output overload Reduce load read 5 2 replace fuse System failure Contact your dealer or consult www gedigitalenergy com UPS will not switch on to normal Line cord not connected Read 2 2 Installation operation LED on remains off Connect line cord charger off Dead socket outlet or mains Contact qualified electrician voltage lt approx 187Vac or Battery start is possible see mains frequency out of 3 1 2 tolerance UPS overtemperature Read 2 1 Allow UPS to cool down Blown input
6. 3 28 16 42 84 190 120 190 190 10 26 70 41 70 70 4 13 41 23 41 41 8 30 15 30 30 8 20 20 10 7 2 10 0 20 8 16 5 20 8 20 8 144 x 155 x 350 225 x 180 x 360 steel plastic IP20 EN 50091 1 1 EN 50091 2 10 to 40 C lt 35 dB A 95 non condensing GE DE Match 500 1500 user manual 4 1 GB
7. CE GE Digital Energy Match Uninterruptible Power Supply GE Digital Energy Match on YI alarm E avr E progr shutdown T replace battery fl on battery GB ko ay yy Certified Quality System Manufactured by Ses ISO 9001 EN 29001 a Reg No 10448 GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 lor yy ISO 9001 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 K KEMA CERTNR 19167 Switzerland Website www gedigitalenergy com 01 02 1992 DESIGN PRODUCTION OF UPS Match UPS Technology for the Digital World GE Digital Energy USER MANUAL Match Uninterruptible Power Supply 500 1500 VA Please read these instructions carefully before installation and start up of the Match UPS Keep this manual in a safe place for future reference CONTENTS 1 INTRODUCTION 0 cceccccecscecscesseesseeceeeseeeceeesseeseeeseeeceeesseeceeeseeeseeseeseeeseaesseessaeeeaes 2 1 1 Introduction 1 2 Safety Rules 1 3 Transport Storage 2 INSTALLATION ciranac A A A E AA NERE 2 2 1 Installation Rules 2 2 Installation Procedure 3 OPERATION ongcnoniunina ena d a a E E 4 3 1 Start up 3 1 1 Start up mains available 3 1 2 Start up mains not available 3 2 Use Normal Operation 3 2 1 Normal operating conditions 3 2 2 Load indication 3 2 3 Auto off no load shutdown 3 2 4 Battery test 3 2 5 Switching off 3 3 Use Status and
8. GB_V041 4 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 3 3 Use Status and Alarm Indications o status indications low priority alarms I high priority alarms Situation the operating mode abnormal operating situations situations in which the actual output voltage of the UPS is no longer guaranteed immediate action should be taken fig 5 GE Digital Energy Match 2 Sx T on S SHI alam 2 9 a Gk avr i val progr shutdown V replace battery on battery 10411412413 14 progr repl on on alarm avr shutd batt batt buzzer o Charger on 3 3 1 o Normal operation 3 3 2 o Automatic voltage regulation 3 3 3 On battery 3 3 4 1x 8s I Battery low 3 3 5 ee we Replace battery 3 3 6 ee a I Overload 3 3 7 oe eae High temperature 3 3 8 o tC o e AA o Progr shutdown pending 3 3 9 o Progr shutdown in progress 3 3 9 Operating modes and corresponding indications see 3 3 1 3 3 9 intermitting continuous resettable press push button T gt 2 secs LX OPM_MAE_XXX_0K5_1K5_XGB_V041 5 GE DE Match 500 1500 user manual 4 1 GB 3 3 1 3 3 2 3 3 3 3 3 4 3 3 5 3 3 6 3 3 7 3 3 8 3 3 9 GE Digital Energy Charger on The batteries are charging see 2 2 4 Norm
9. al operation See 3 2 1 AVR Automatic Voltage Regulation active The quality of the incoming mains is poor and the AVR boosts a low incoming voltage or reduces a high one see chapter 7 On battery The UPS uses the energy stored in the batteries see chapter 7 Batteries autonomy The UPS will shutdown e after the batteries have been discharged automatic restart or e if keypad O is pressed manual restart required or e if a UPS shutdown command is given by the computer manual restart required Autonomy indication fig 6 Q During battery operation press keypad l briefly The 4 yellow LEDs indicate during 3 seconds the remaining autonomy time for WZ a the actual load E gt 20min N D gt 10min Battery low end of autonomy E gt 5min The batteries are nearly discharged Controlled shutdown of your T gt 2min computer equipment should be completed within 1 minute fig 6 Replace battery The batteries are bad The alarm only goes out after the next battery test if the batteries have either been sufficiently charged discharged batteries or replaced by a new set worn out batteries Overload The demanded power of the equipment exceeds the UPS s rated output power If overload persists during battery operation the UPS may shut down High temperature Overtemperature shut down during battery operation can occur from e extreme environmental temperature e lack of proper ventilation e overload situation When the pre al
10. arm sounds check these conditions to avoid shutdown or damage If the temperature rises further the UPS will e if it runs on mains switch off the battery charger e if it runs on battery switch off completely Output voltage is no longer available Programmed shutdown Probably your UPS monitoring software allows you to program a sleep period of the UPS by sending two commands to the UPS e shut down after minutes blinking LED and subsequently e shut down during hours continuous LED The programmed shutdown in progress can be cancelled press keypad l for at least 5 seconds to cancel shutdown and switch UPS on press keypad 0 for at least 5 seconds to cancel shutdown and switch UPS off LX OPM_MAE_XXX_0K5_1K5_XGB_V041 6 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 4 Communication 4 4 RS232 Port fig 7 The RS 232 Port is a plug in interface port 9 pin Sub D male which enables advanced communication between the UPS and the computer interface kit required We strongly recommend to use only original GE Digital Energy software products in combination with the interface port Pin Function fig 7 1 RS232 input UPS shutdown i 2 RS232 output K R O 3 No function lt A T TO 4 Plug and Play L lt meP n 5 Common K 7 6 No function DC ae O 7 Battery low K RS232 4 LO 8 UPS connected 7 pce 9 Mains failure RS232
11. ceed the rated output power of the UPS indicated on the rating label 6 fig 1 2 1 Installation Rules e The UPS is intended to be used in normal domestic and office situations e Protect the UPS according to the wiring rules with a 16A D type fuse e The UPS must be powered from a single phase grounded wall outlet Do not use extension cords e Avoid locations that are excessively humid near water near heat sources or in direct sunlight e The ambient temperature should not exceed 40 C Optimal battery lifetime is obtained if the ambient temperature does not exceed 30 C e tis important that ventilation air can move freely around and through the unit Do not block the air vents e Do not plug appliances such as electric heaters toasters and vacuum cleaners into the UPS e Be careful when connecting laser printers be sure that the demanded power does not exceed the capacity of the UPS e The sum of the leakage currents of the UPS and the connected loads should not exceed 3 5mA LX OPM_MAE_XXX_0K5_1K5_XGB_V041 2 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 2 2 Installation Procedure fig 1 6 TOT TTT EUDVTYUT EET ATT TTETTTT TT Match 500 700 Match 700L 1500 1 Switch off your computer and unplug it from the socket outlet 2 Disconnect the power cord from the computer rating 250Vac 10A and
12. cy in case of battery start Output frequency stability Output waveform Power factor Transfer time Buck Boost voltage regulation Batteries ratings given for 25 C Nominal voltage Vdc Number x capacity Ah of batteries Type Service life Recharge current Battery recharge time for 90 capacity hours approximation Autonomy runtime in minutes at typical load 75 VA Watts 100 60 300 180 500 300 700 420 1000 600 1500 900 General Weight kg Dimensions hxwxd mm Match 500 700 Match 700L 1500 Enclosure protection Environment Safety Electromagnetic compatibility Ambient temperature Sound at 1 meter Maximum relative humidity LX OPM_MAE_XXX_0K5_1K5_XGB_V041 9 500 700 700L 1000 1000L 1500 500 700 700 1000 1000 1500 300 420 420 600 600 900 220 240 V 165 275 V mains operation 350V above 275V battery operation 187 V at any load 50 Hz or 60 Hz nominal 2 5 Hz typically 7W 500 700 or 12W 700L 1500 2 8 4 0 4 0 6 0 6 0 8 0 5 5 5 10 10 10 230 V suitable for 220 240 V loads nominal 2 battery operation RMS value 50Hz or 60Hz autosensing last detected frequency off factory 50 Hz lt 0 1Hz battery operation sine wave 0 6 0 7 at 90 load typical 4 ms at 165 275 V input voltage output voltage 190 254V 12 24 36 36 36 36 1x7 2x7 3x12 3x7 3x12 3x12 12V sealed lead acid maintenance free up to 6 years depending on use 3A 2 2 2 2 2 2 7 12 40 1
13. d l during 5 seconds until the buzzer sounds The LEDs on and on battery 12 will illuminate The UPS operates on battery it discharges the batteries 3 2 Use Normal Operation 3 2 1 Normal operation conditions e the mains supply is present e the UPS is on e the load does not exceed the capacity of the UPS and A e the operating temperature is below alarm level l 4 i 3 2 2 Load indication fig 4 a a 1 During normal operation press keypad l briefly T gt 25 2 Yellow LEDs will blink during 3 seconds the number is load B gt 5 dependent in case of overload LED alarm 8 blinks as well fig 4 3 2 3 Auto off no load shutdown If this function is activated the UPS will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will automatically turn on again when mains power is restored The default setting of the no load shutdown function is activated You can change this setting through the RS232 port using the UPS configuration tool that came with the unit CD ROM see 5 4 3 2 4 Battery test 1 During normal operation press keypad l for one second 2 The duration of the test is 4 seconds See also 3 3 6 3 2 5 Switching off 1 Press keypad 0 14 briefly 2 If electric isolation is required unplug the power cord from the wall outlet LX OPM_MAE_XXX_0K5_1K5_X
14. fuse See above UPS will not switch on to normal Mains voltage between Contact qualified electrician operation LED on blinks 165 187Vac UPS will not switch to battery Batteries depleted Allow the UPS to recharge the operation batteries System failure Contact your dealer or consult www gedigitalenergy com UPS switched off automatically Shut down by external Wait until mains returns software command UPS overtemperature Read 2 1 Allow UPS to cool down Mains failure battery Wait until mains returns discharged The load is lt 5 of the max Wait until mains returns load and no mains power is present No load shutdown function is active see 3 2 3 LED replace battery Quick Battery Test just after Allow the UPS to recharge the illuminates buzzer is silent installation or mains failure batteries Quick Battery Test shows weak Read 5 3 have the batteries battery replaced LX OPM_MAE_XXX_0K5_1K5_XGB_V041 8 GE DE Match 500 1500 user manual 4 1 GB GE Digital Energy 7 Specifications Match model Ratings Voltage Amperes VA with computer type load Watts W with resistive load Input AC input voltage AC input voltage window Maximum AC input voltage Minimum start up AC voltage Input frequency Input frequency range No load power consumption normal operation AC input current A AC input fuse A Output AC output voltage AC output voltage tolerance Output frequency Output frequen

Download Pdf Manuals

image

Related Search

Related Contents

Présentation par Julie ESPINAS  HELIO API User Manual Version 2.1  Mobile Scanner User`s Manual  2016 Precept Manual  Manual de los descodificadores Plus  休館日 1 2 紙芝居会 3 4 休館日 5 6 7 8 9 10  SERVICE MANUAL - Hifi-Wiki  Eurofase 23075-016 Installation Guide  Purée Granulée Nature A très faible teneur en sodium MOUSLINE  Sauna control ASV 3 Instrucciones de montaje  