Home

Installation Manual BACnet I/O Modules - mbs

image

Contents

1. Property Identifier Property Datatype 1 2 Object_Identifier BACnetObjectIdentifier R W Object Name CharacterString max 16 characters RK W Object_Type BACnetObjectType RK IR System_Status BACnetDeviceStatus R IR Vendor_Name CharacterString R R Vendor_Identifier Unsigned16 R IR Model_Name CharacterString R_ R Firmware_Revision CharacterString R R Application_Software_Version CharacterString R R Location CharacterString O Description CharacterString O Protocol_Version Unsigned R IR Protocol_Revision Unsigned R IR Protocol_Services_Supported BACnetServicesSupported R_ R Protocol_Object_Types_Supported BACnetObjectTypesSupported R R Object_List BACnetARRAY N of BACnetObjectIdentifier R R Max_APDU_Length_Accepted Unsigned max 50 R IR Segmentation Gupported BACnetSegmentation R R Max_Segments_Accepted Unsigned O VT_Classes_Supported List of BACnetVTClass O Active_VT_Sessions List of BACnetVTSession O Local_Time Time O Local_Date Date O UTC_Offset INTEGER O Daylight_Savings_Status BOOLEAN O APDU_Segment_Timeout Unsigned O APDU_Timeout Unsigned 10 000 ms R R Number_Of_APDU_Retries Unsigned 5 R R List_Of_Session_Keys List of BACnetSessionKey O Time_Synchronization_Recipients List of BACnetRecipient O Max_Master Unsigned 127 O R Max_Info_Frames Unsigned 1 O R Device_Address_Binding List of BACnetAddressBinding empty R R D
2. AuBer an Feiertagen Telefon 49 2151 7294 0 Telefax 49 21 51 72 94 50 E Mail support mbs software de Homepage www mbs software de 2 5 Copyright 2014 MBS GmbH All rights reserved MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 3 Einf hrung Die Produktlinie umfasst 3 Ger te f r die digitale Ein und Ausgabe sowie f r analoge Eing nge 3 1 Module AI 24 Analog Input Module Al 24 Channel 01 16 PT1000 Channel 17 24 0 10VDC um mba software de Dieses Modul bietet 16 Kan le fur PT1000 Geber Aufl sung 0 5 C Temperaturbereich 30 bis 150 C und 8 Kan le 0 10V Aufl sung 0 1V Stromversorgung 9 25V AC DC 1 5 W 3 2 Module DI 24 Digital Input Module DI www mbs software Dieses Modul bietet 24 isolierte Eingangskan le Eine LED pro Kanal zeigt den Eingangszustand an Stromversorgung 9 25V AC DC 4 5W MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 3 3 Module DO 8 ua Digital Output Module DO 0o aa L E rere See TT Dieses Modul bietet 8 digitale Ausgange mit einer Schaltleistung von je 1250W Durch eingebaute Schalter lassen sich die Ausgange manuell schalten Eine LED pro Kanal zeigt den Ausgangszustand an Stromversorgung 9 25V AC DC 10W 3 4 Gemeinsame Eigenschaften aller Module Alle Module hab
3. MS TP MAC Adresse 1 BACnet Device Id 0 Baud Rate 9600 bit s Unsolicited COV disabled MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 3 Einstellung der MAC Adresse der Module 10 3 1 Arbeitsmodus MS TP Master und Slave Die BACnet I O Module k nnen sowohl im MS TP Master Mode wie im Slave Mode verwendet werden Die MAC Adressen von MS TP Master Nodes sind im Bereich von 0 127 die der Slave Nodes von 128 254 Slave Adressen unter 128 werden nicht unterst tzt fur I O Module Die MAC Adresse f r Master Nodes kann mittels Jumper von 0 31 und f r Slaves von 128 135 eingestellt werden Andere BACnet MAC Adressen k nnen mittels Proprietary Propertys des Device Objekts eingestellt werden Im MS TP Master Mode unterst tzen die Module BACnet Device Profile B ASC Application Specific Controller Im Slave Modus ist das Modul im passiv Modus und unterst tzt nur die BACnet Device Profile B SA Smart Actuator Die BACnet Ger teinstanznummer der Module wird bei der Konfiguration mittels der Jumper entsprechend der MAC Adresse eingestellt Im Slave Modus k nnen die Module nicht automatisch ber die Nachrichten Who Is und I Am erkannt werden Beim ndern der MS TP Adresse mittels Jumper wird die Gerateinstanznummer und der Objektname auf die Default Einstellung zur ck gesetzt 10 3 2 Einstellung des Modus MS TP Master Zur Ei
4. 1 BACnet Conformance Code 135 2004 2 BACnet Conformance Code AI 24 R Required Readable W Writable O Optional Not supported MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 14 BACnet PICS DI 24 Date 11 01 2009 Vendor Name MBS GmbH Product Name BACnet I O module DI 24 Product Model Number DI 24 Application Software Version 1 0 Firmware Revision 1 0 BACnet Protocol Version 1 BACnet Protocol Revision 4 Product Description The MBS DI 24 module is a highly reliable BACnet Digital Input module supporting 24 channels isolated digital input The module supports all standardized BACnet MS TP baud rates from 9600 up to 76800 bit s The modules may run in MS TP master and slave mode BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actuator B SA OOROODO List all BACnet Interoperability Building Blocks Supported Annex K DS RP B Data Sharing ReadProperty B DS WP B Data Sharing WriteProperty B DS COVU B Data Sharing ChangeofValue Unsolicited B DM DDB B Device Management DynamicDeviceBinding B DM DOB B Device Management DynamicObjectBinding B DM DCC B Device Management DeviceCommunicationControl B DM RD B Device Managem
5. BACnet MS TP I O Module Rev 1 8 02 09 2014 NNN MBS Made by Specialists Inhaltsverzeichnis 1 DokumentenreviSion ENEE NENNEN 5 2 Willkommen bei den BACnet I O Modulen 6 21 BEREICH een 6 2 2 Merkmale 6 2 3 Andere BACnet Produkte von MBS NEEN 6 24 Produkt e 7 2 5 COPYING da 7 SON tg eu Le EE 8 3 1 Module Al 22 nee 8 3 2 Mod le DI 24 ans ee 8 3 3 Module Dos ec 9 3 4 Gemeinsame Eigenschaften aller Module 9 4 Anschl sse und Bedienelemente c ccceeceeseeeeseeeeaes 10 4 1 LEDs 10 4 2 Digital Eingangs Modul Anzeige cceeseeeeee eee nennen 11 4 3 Digital Output Modul Schalter cece eee nenn Rn nen 12 E Ce EN e EE 13 5 1 Einbau der Module ana e 13 5 2 Zur Installation ben tigte Werkzeuge ceeeeeee eens 13 5 3 Anschluss der Module 14 5 4 Besondere Vorschriften f r die Inbetriebnahme von AI 24 ele EE 14 5 5 Besondere Vorschriften f r die Inbetriebnahme von DI 24 isle 3 EE 14 5 6 Besondere Vorschriften f r die Inbetriebnahme von DO 8 Modulen ae ee 14 d ra Ee el 15 7 Al 24 Anschl ssbelegung eege ee Eed e 16 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 8 Al 24 Anschlussbelegung ce an echte eier 18 9 DO 8 Anschlussbelegung success ee 20 10 Konfiguration der I O Module ENEE 22 10 1 Benutzung der Jumper zur Konfiguration u zsr4 4 23 10 1 1 Setzen des konfgurationsmodus nn
6. ANSI ATA 878 1 2 5 Mb ARCNET Clause 8 ANSI ATA 878 1 RS 485 ARCNET Clause 8 baud rate s MS TP master Clause 9 baud rate s 9600 19200 38400 76800 MS TP slave Clause 9 baud rate s 9600 19200 38400 76800 oO oO oO oO oO M M MBS GmbH Tel 49 21 51 72 94 0 Romerstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Point To Point EIA 232 Clause 10 baud rate s Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium Other OOOO Device Address Binding Is static device binding supported This is currently necessary for two way communication with MS TP slaves and certain other devices oO Yes M No Networking Options O Router Clause 6 O Annex H BACnet Tunneling Router over IP O BACnet IP Broadcast Management Device BBMD O Does the BBMD support registrations by Foreign Devices Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously ANSI X3 4 IBM Microsoft DBCS ISO 8859 1 ISO 10646 UCS 2 ISO 10646 UCS 4 JIS C 6226 OOOOON If this product is a communication gateway describe the types of non BACnet equipment networks s that the gateway supports No gateway functionality yet Remarks If set to slave mode the supported Device Profile is reduced to B SA The BIBB DS COV U B is not supported in slave mode The BIBB DM DCC B supports
7. R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 7 AI 24 Anschlussbelegung www mbs software de Analog Input Module Channel 01 16 PT1000 Channel 17 24 0 10VDC bis 51 MBS Made by Specialists 1 bis 26 Connector no Description Connector no Description 1 Al 1 PT1000 27 Not assigned 2 Al 1 PT1000 28 Not assigned 3 Al 2 PT1000 29 Not assigned 4 Al 2 PT1000 30 Al 11 PT1000 5 Al 3 PT1000 31 Al 11 PT1000 6 Al 3 PT1000 32 Al 12 PT1000 7 Al 4 PT1000 33 Al 12 PT1000 8 Al 4 PT1000 34 Al 13 PT1000 9 AI 5 PT1000 35 Al 13 PT1000 10 AI 5 PT1000 36 Al 14 PT1000 11 Al 6 PT1000 37 Al 14 PT1000 12 AI 6 PT1000 38 Al 15 PT1000 13 AI 7 PT1000 39 Al 15 PT1000 14 AI 7 PT1000 40 Al 16 PT1000 15 Al 8 PT1000 41 Al 16 PT1000 16 Al 8 PT1000 42 Al 17 0 10VDC 17 AI 9 PT1000 43 Al 18 0 10VDC 18 AI 9 PT1000 44 Al 19 0 10VDC 19 Al 10 PT1000 45 Al 20 0 10VDC 20 Al 10 PT1000 46 0 10VDC GND 21 MS TP RS485 GND 47 0 10VDC GND 22 MS TP RS485 Signal A 48 Al 21 0 10VDC 23 120 Ohms Termination 49 Al 22 0 10VDC 24 MS TP RS485 Signal B_ 50 Al 23 0 10VDC 25 9 25V 51 Al 24 0 10VDC 26 GND MBS GmbH Tel 49 21 51 72 94 0 FAX 49 21 51 72 94 50 www mbs software de R merstrasse 15 D 47809 Krefeld
8. R IR Segmentation Gupported BACnetSegmentation R R Max_Segments_Accepted Unsigned O VT_Classes_Supported List of BACnetVTClass O Active_VT_Sessions List of BACnetVTSession O Local_Time Time O Local_Date Date O UTC_Offset INTEGER O Daylight_Savings_Status BOOLEAN O APDU_Segment_Timeout Unsigned O APDU_Timeout Unsigned 10 000 ms R R Number_Of_APDU_Retries Unsigned 5 R R List_Of_Session_Keys List of BACnetSessionKey O Time_Synchronization_Recipients List of BACnetRecipient O Max_Master Unsigned 127 O R Max_Info_Frames Unsigned 1 O R Device_Address_Binding List of BACnetAddressBinding empty R R Database_Revision Unsigned 1 R_ R Configuration_Files BACnetARRAY N of BACnetObjectldentifier O Last_Restore_Time BACnetTimeStamp O Backup_Failure_Timeout Unsigned16 O Active_COV_Subscriptions List of BACnetCOVSubscription O Slave_Proxy_Enable BACnetArray N of BOOLEAN O Manual_Slave_Address_Binding List of BACnetAddressBinding O Auto_Slave_Discovery BACnetArray N of BOOLEAN O Slave_Address_Binding List of BACnetAddressBinding O Profile Name CharacterString O Baud rate proprietary 701 UNSIGNED 9600 19200 38400 76800 oOo W MAC address proprietary 702 UNSIGNED 0 127 master 128 254 slave Oo w 1 BACnet Conformance Code 135 2004 2 BACnet Conformance Code AI 24 R Required Readable W Writable O Optional Not supported MBS GmbH R merstrasse 15 D 47
9. 05 Notification_Class Unsigned 05 Alarm_Value BACnetBinaryPV O5 Event_Enable BACnetEventtTransitionBits O5 Acked_Transitions BACnetEventTransitionBits 05 Notify_Type BACnetNotifyType 05 Event_Time_Stamps BACnetARRAY 3 of BACnetTimeStamp O5 Profile_Name CharacterString O DS COVU B proprietary 700 BOOLEAN FALSE no COV TRUE COV U O W EN Writable if OutOfService is TRUE 1 BACnet Conformance Code 135 2004 2 BACnet Conformance Code DI 24 R Required Readable W Writable O Optional Not supported MBS GmbH R merstrasse 15 D 47809 Krefeld Tel 49 21 51 94 0 FAX 49 21 51 72 94 50 www mbs software de 15 BACnet PICS DO 8 Date 11 01 2009 Vendor Name MBS GmbH Product Name BACnet I O module DO 8 Product Model Number DO 8 Application Software Version 1 0 Firmware Revision 1 0 BACnet Protocol Version 1 BACnet Protocol Revision 4 Product Description The MBS DO 8 module is a highly reliable BACnet Digital Output module supporting 8 channels digital relay output The module supports all standardized BACnet MS TP baud rates from 9600 up to 76800 bit s The modules may run in MS TP master and slave mode BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smar
10. 23 10 1 2 Setzen der Konfiguration unse ee 23 10 1 3 Programmierschritte esse een 23 10 2 Setzen der Baud Rate ENEE ENEE EE 24 10 2 1 Selektieren des Modus Baud Rate einstellen 24 10 2 2 Selektieren der Baud Rate EEN 24 10 2 3 berpr fen der Baud Rate 25 10 2 4 Zur cksetzen des Moduls auf die Defaulteinstellung26 10 2 5 Setzen des Reset MOdUS sgannggegensgesggsgisegagega gen 26 10 2 6 berpr fung des Reset Modus nenn nn 26 10 3 Einstellung der MAC Adresse der Module 27 10 3 1 Arbeitsmodus MS TP Master und Slave accses 27 10 3 2 Einstellung des Modus MS TP Master 27 10 3 3 Einstellen der gew nschten MAC Adresse 28 10 3 4 berpr fung der Master MAC Adresse sacc 29 10 3 5 Einstellung des Modus MS TP Glave 30 10 3 6 Einstellung der gew nschten Slave MAC Adresse 30 10 3 7 berpr fung der Slave MAC Adresse ssec 31 11 Einstellung der BACnet Eigenschaften 32 11 1 Einstellung der Baud Rate ui 32 11 2 Einstellung der MAC Adresee nun nn 32 11 3 Einschalten der COV Unsolicited z2ren20sen0nnnn0n 32 11 4 Andere ver nderbare Properties unussunennnnennn nenn nn 33 12 Technical Specifications au 35 13 BACnet PICS Al 24 nn in 36 14 BACN et PICS DI 24 usa eanna aKa Eaa 40 15 BACnet PICS DO B uk 44 The MBS logo is a registered trademark of MBS GmbH BACnet is a registered trademark of ASHRAE Inc MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 9
11. 250VAC DO1 2 DO1 1 DO1 4 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Anschluss 1 pro Ausgang Gemeinsamer Anschluss Anschluss 2 pro Ausgang Offner Kontakt Anschluss 4 pro Ausgang Schlie er Kontakt Zur Terminierung der RS485 Schnittstelle die Klemmen 23 und 24 verbinden MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 Konfiguration der I O Module Mittels der Jumper werden die Module programmiert Jumper JP1 JP5 HI OO0O00000000000000000000000 Auf allen weiteren Bildern sind die Jumper von hinten links zu sehen Anschlussschrauben Teil 2 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 1 Benutzung der Jumper zur Konfiguration 10 1 1 Setzen des Konfigurationsmodus Einstellen des Konfigurationsmodus durch setzen des Jumpers laut Abbildung on JJ J 234 eee o om ero Dieses Beispiel setzt den Modus Baud Rate einstellen 10 1 2 Setzen der Konfiguration Einstellen des Konfiguration durch setzen des Jumpers laut Abbildung JJJJJ 12345 Dieses Beispiel setzt die Baud Rate auf 76800 bit s 10 1 3 Programmierschritte Die Programmierung erfolgt durch folgende Schritte Step 1 Entfernen der Spannungsversorgung Step 2
12. Setzen der Jumper f r die gew nschte Einstellung Step 3 Verbinden mit der Spannungsversorgung Step 4 Kontrolle der Einstellung durch berpr fung der TxD LED Step 5 Entfernen der Spannungsversorgung Step 6 Entfernen aller Jumper Step 7 Verbinden der Spannungsversorgung Wichtig Im Betriebsmodus d rfen niemals Jumper gesteckt sein MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 2 Setzen der Baud Rate Diese Kapitel zeigt die Einstellung der Baud Rate Die Standard Baud Rate ist 9600 bit s 10 2 1 Selektieren des Modus Baud Rate einstellen 10 2 2 Selektieren der Baud Rate MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 2 3 berpr fen der Baud Rate Nach dem erneuten verbinden der Spannungsversorgung l sst sich am Blinkrhythmus der roten TxD LED die Baud Rate ablesen 9600 bit s TxD LED blinkt 1 mal 19200 bit s TxD LED blinkt 2 mal 38400 bit s TxD LED blinkt 3 mal 76800 bit s TxD LED blinkt 4 mal MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 2 4 Zur cksetzen des Moduls auf die Defaulteinstellung 10 2 5 Setzen des Reset Modus JI EI 13 12345 CEET ommo o 10 2 6 berpr fung des Reset Modus Nach dem Reset blinkt die TxD LED 5 mal Die default Werte sind
13. angeschlossen werden Wird eine Spannungsquelle an die Eing nge angeschlossen so k nnen die Eing nge zerst rt werden Die Garantie erlischt wenn andere Spannungsquellen verwendet werden 5 6 Besondere Vorschriften f r die Inbetriebnahme von DO 8 Modulen Die Ausg nge d rfen mit maximal 5A und 250VAC belastet werden F r das Schalten von h heren Lasten sind entsprechend Leistungsschalter vorzusehen MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 6 MS TP Anschluss a E O o D 0 Bs o EE Hd oo LH E De GK c 5E ab He a Rx Ya Q Node without bias resistors un S bg EN G i o E b 2 E x Widerst nde le kOhm Knoten mit lokalen Bias Widerst nden Node with local bias resistors 47 konm Max no of devices per segment 32 Rx Tx RTS 5V Max length of segment 1 200m 4 000 ft Q O i 510 Ohm 5V t o 4 u D E H e E E v r MS TP Verkabelung MS TP Wiring o E a 8 un D D 3 un un E E a a Knoten mit Netzwerk Bias Widerst nden Node with network bias resistors 120 Ohm 510 onm Der BACnet MS TP Netzwerkanschluss ist in dem Diagramm abgebildet Die Busstruktur erlaubt keine T Abzweigungen Der MS TP Bus muss terminiert werden 120 Ohm Widerst nde zwischen den Anschl ssen MBS GmbH Tel 49 21 51 72 94 0
14. mbs software de Sues Made by Specialists
15. mittels Schreiben auf das Proprietary Property 702 des Device Object gesetzt Der Datentype ist UNSIGNED und der Wertebereich 0 254 Master Nodes Adressen liegen im Bereich von 0 127 Slave Node Adressen im Bereich von 128 254 Die Einstellungen werden nach einem Reset wirksam Dazu kann entweder die Spannungsversorgung Aus und Eingeschaltet oder der BACnet Befehl ReinitializeDevice gesendet werden 11 3 Einschalten der COV Unsolicited Unsolicited COV Broadcast Change of Value notification wird Ein oder Ausgeschaltet durch Schreiben des gew nschten COV U Modus auf die Proprietary Property 700 des BACnet Object f r den gew nschten Bereich Der Datentyp ist BOOLEAN und die Werte sind FALSE kein COV U oder TRUE COV U aktiv Die Einstellungen werden nach einem Reset wirksam Dazu kann entweder die Spannungsversorgung Aus und Eingeschaltet oder der BACnet Befehl ReinitializeDevice gesendet werden MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 11 4 Andere ver nderbare Properties Das BACnet PICS Dokument Protocol Implementation Conformance Statement der I O Module enth lt eine Liste der ver nderbaren Properties und deren Wertebereich MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Anhang Technical Specifications BACnet PICS MBS GmbH Tel 49 21 51 7
16. 2 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 12 Technical Specifications All modules Power supply 9 25V AC DC CPU ATMEL AT89S8253 1 x serial port EIA 485 BACnet MS TP B A AGND Screw connectors 3mm screw size max 2 5mm2 wire Power LED green RxD LED yellow TxD LED red Weight lt 500g Dimensions height 91mm width 155mm depth 60mm including DIN rail mounting Environmental temperature range 0 45 C 32 113 F e Environmental humidity range 20 80 percent relative humidity non condensing AI 24 16 channels PT1000 resolution 0 5 C range 30 C 150 C power consumption 1 5 W DI 24 24 channels isolated digital input 12VDC provided as common supply source green input state LED per channel power consumption 4 5 W DO 8 8 channels digital relay output max load 1250W 5A 250VAC per channel manual override switch states AUTO OFF ON green output state LED per channel power consumption 5 W Manufacturer MBS GmbH Roemerstrasse 15 D 47809 Krefeld www mbs software de info mbs software de This product is available as an OEM product please call MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 13 BACnet PICS AI 24 Date 11 01 2009 Vendor Name MBS GmbH Product Name BACnet I O module AI 24 Product Model Number AI 24 Application Software Ve
17. 4 50 D 47809 Krefeld www mbs software de 1 Dokumentenrevision Anzeige der Dokumentenversion 10 01 2009 Frank Schubert Revision 1 0 Initial Version 26 11 2010 ANE Revision 1 1 nderung Anschlussbelegung getauscht GND und 9 25V 20 12 2010 ANE Revision 1 2 Deutsche Version 12 01 2011 ANE Revision 1 3 MAC Adresse min 1 19 05 2011 ANE Revision 1 4 getauscht AGND und GND 11 06 2012 ANE Revision 1 5 Terminierung Klemmen ge ndert 05 11 2012 ANE Revision 1 6 Korrektur Leistungsaufnahme 06 05 2013 ANE Revision 1 7 Schaltbild Anschlussbelegung 02 09 2014 ANE Revision 1 8 Textkorrektur MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 2 Willkommen bei den BACnet I O Modulen 2 1 bersicht Danke f r die Wahl der BACnet I O Module Diese Ger te sind entwickelt als zuverl ssige und einfach zu installierende digitale Ein und Ausgabeger te sowie als analoges Eingabeger t im BACnet Netzwerk 2 2 Merkmale Unterst tzung des BACnet Data Link Layers MS TP Master and Slave Mode Ger te Profile B ASC im Master Mode B SA im Slave Mode AI 24 16 Kan le PT1000 8 Kan le 0 10V DI 24 24 Kan le isolierter Eingang DO 8 8 Kan le digitale Ausg nge 1250W je Kanal 2 3Andere BACnet Produkte von MBS Universal BACnet Router UBR 01 Hochleistungsrouter zwischen den BACnet La
18. 809 Krefeld Tel 49 21 51 72 94 0 FAX 49 21 51 72 94 50 www mbs software de Analog Input Object Type Property Identifier Property Datatype zk Ji Object_Identifier BACnetObjectldentifier 1 24 R IR Object_Name CharacterString max 16 characters R W Object_Type BACnetObjectType R R Present_Value REAL Rt R Description CharacterString max 16 characters O W Device_Type CharacterString max 16 characters O W Status_Flags BACnetStatusFlags R IR Event_State BACnetEventState R IR Reliability BACnetReliability O Out_Of_Service BOOLEAN R Iw Update_Interval Unsigned O Units BACnetEngineeringUnits R wt Min_Pres_Value REAL O Max_Pres_Value REAL O l Resolution REAL O COV_Increment REAL 02 Ww Time_Delay Unsigned 03 Notification_Class Unsigned 03 High_Limit REAL 03 Low_Limit REAL 03 Deadband REAL 03 Limit_Enable BACnetLimitEnable 03 Event_Enable BACnetEventTransitionBits 03 Acked_Transitions BACnetEventTransitionBits 03 Notify_Type BACnetNotifyType 03 Event_Time_Stamps BACnetARRAY 3 of BACnetTimeStamp 03 Profile Name CharacterString O DS COVU B proprietary 700 BOOLEAN FALSE no COV TRUE COV U O W Rt Writable if OutOfService is TRUE wt Unit is writable for Analog Input channels no 17 24 0 10V inputs possible values are 5 volts and 124 millivolts
19. RS485 Signal B 550 Digital Input24 25 9 25V 51 COM 26 GND MBS GmbH R merstrasse 15 D 47809 Krefeld Tel 49 21 51 72 94 0 FAX 49 21 51 72 94 50 www mbs software de COM bezeichnet die gemeinsame Masse f r alle Eing nge Wird eine andere Spannungsquelle an die Eing nge angeschlossen so k nnen die Eing nge zerst rt werden Zur Terminierung der RS485 Schnittstelle die Klemmen 23 und 24 verbinden Eingangsbeschaltung COM 24 Digital Input 24 COM Digital Input 2 cOM1 Digital Input 1 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 9 DO 8 Anschlussbelegung 35 30 bis DEREN 10 20 H 10 50 s 70 80 Auto 3 i I 3 3 4 i R Made by Spec Digital Output Module www mbs softw FTSE 1 bis 26 Connector no Description Connector no Description 1 DO1 4 19 Not assigned 2 DO1 1 20 Not assigned 3 DO1 2 21 MS TP RS485 GND 4 DO2 4 22 MS TP RS485 Signal A 5 DO2 1 23 120 Ohms Termination 6 DO2 2 24 MS TP RS485 Signal B 7 DO3 4 25 9 25V 8 DO3 1 26 GND 9 DO3 2 27 Not assigned 10 DO4 4 28 Not assigned 11 DO4 1 29 Not assigned 12 DO4 2 30 DO7 2 13 DO5 4 31 DO7 1 14 DO5 1 32 DO7 4 15 DO5 2 33 DO8 2 16 DO6 4 34 DO8 1 17 DO6 1 35 DO8 4 18 DO6 2 Maximale Schaltleistung je Ausgang 1250VA 5A
20. Zur Terminierung der RS485 Schnittstelle die Klemmen 23 und 24 verbinden Eingangsbeschaltung 0 10VDC ang T PT 1000 I ANG i I I L AR PT 1000 1 An i alt PT 1000 an MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 8 DI 24 Anschlussbelegung 30 bis 51 Sees seg Oe Oy YOY yy PVORUR IV PVP UVVUUVVVVVUY nm SsIn o0I mjoI jo el Sje Sjaj EJES MBS Digital Input Module www mbs software de ZE ooo asd Aao NANa NTN ANNONS TNO US 1 bis 26 Connector no Description Connector no Description 1 Digital Input1 27 Not assigned 2 COM 28 Not assigned 3 Digital Input2 29 Not assigned 4 COM 30 Digital Input11 5 Digital Input3 31 COM 6 COM 32 Digital Input12 7 Digital Input4 33 Digital Input13 8 COM 34 COM 9 Digital Input5 35 Digital Input14 10 COM 36 Digital Input15 11 Digital Input6 37 COM 12 COM 38 Digital Input16 13 Digital Input7 39 Digital Input17 14 COM 40 COM 15 Digital Input8 41 Digital Input18 16 COM 42 Digital Input19 17 Digital Input9 43 COM 18 COM 44 Digital Input20 19 Digital Input10 45 Digital Input21 20 COM 46 COM 21 MS TP RS485 GND 47 Digital Input22 22 MS TP RS485 Signal A 48 Digital Input23 23 120 Ohms Termination 49 COM 24 MS TP
21. anal aktiv Kanalreihenfolge von links nach rechts ist 1 24 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 4 3 Digital Output Modul Schalter Das DO 8 Modul besitzt 8 Schalter um die Ausg nge manuell zu schalten Die LED zeigen den Zustand der Ausg nge an Schalter Ausgangs LED oO O0000090000000000 I ON OFF I AUTO OO000000000000000000000000 Jeder Ausgang kann in 3 Zust nde geschaltet werden AUTO Der Ausgang wird ber das BACnet geschaltet OFF Der Ausgang ist Aus ON Der Eingang ist Ein Die Reihenfolge der Ausg nge von links nach rechts 1 8 Die Ausgangs LED ist AN wenn der Ausgang eingeschaltet ist Die Logik des schalten kann ber entsprechende BACnet Einstellungen invertiert werden Achtung Durch das manuelle Schalten in den Zustand AUS oder EIN wird die BACnet priority auf Manuel gesetzt und der Ausgang kann nicht mehr ber BACnet kontrolliert werden bis der Ausgang wieder auf AUTO gesetzt wird MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 5 Installation 5 1 Einbau der Module Die Module sind mit einer DIN Montage TS 35mm ausgestattet Setzen Sie dazu das Modul von oben auf die Schiene und verriegeln mit dem unteren Schieber in der Schiene H OO000000000000000000000000 Ziehen max 3mm Zum Entfe
22. atabase_Revision Unsigned 1 R_ R Configuration_Files BACnetARRAY N of BACnetObjectldentifier O Last_Restore_Time BACnetTimeStamp O Backup_Failure_Timeout Unsigned16 O Active_COV_Subscriptions List of BACnetCOVSubscription O Slave_Proxy_Enable BACnetArray N of BOOLEAN O Manual_Slave_Address_Binding List of BACnetAddressBinding O Auto_Slave_Discovery BACnetArray N of BOOLEAN O Slave_Address_Binding List of BACnetAddressBinding O Profile Name CharacterString O Baud rate proprietary 701 UNSIGNED 9600 19200 38400 76800 oOo W MAC address proprietary 702 UNSIGNED 0 127 master 128 254 slave Oo w 1 BACnet Conformance Code 135 2004 2 BACnet Conformance Code DO 8 R Required Readable W Writable O Optional Not supported MBS GmbH R merstrasse 15 D 47809 Krefeld Tel 49 21 51 72 94 0 FAX 49 21 51 72 94 50 www mbs software de Binary Output Object Type Property Identifier Property Datatype zk Ji Object_Identifier BACnetObjectldentifier 1 8 R R Object Name CharacterString R W Object_Type BACnetObjectType R R Present_Value BACnetBinaryPV W iw Description CharacterString max 16 characters O W Device_Type CharacterString max 16 characters O W Status_Flags BACnetStatusFlags R IR Event_State BACnetEventState R IR Reliability BACnetReliabi
23. en folgende Eigenschaften e BACnet MS TP Master und Slave Mode einstellbar e Baud Rate 9600 19200 38400 76800 einstellbar e Ger te Profile B ASC Funktionalit t im Master Mode B SA Funktionalit t im Slave Mode e RxD TxD Anzeige LEDs e Power LED e DIN Aufnahme TS35 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 4 Anschl sse und Bedienelemente Dieses Bild zeigt die Frontansicht der I O Module Konfigurations Jumper Anschl sse Teil 2 Power LED TxD LED RxD LED O0O0000000000000000000 OO0O00000000000000000000000 Anschl sse Teil 1 DIN Aufnahme 4 1 LED Das I O Modul besitzt LEDs zur Anzeige des Systemstatus 1 MS TP TxD Diese rote LED blinkt wenn das Modul Daten ber den MS TP Bus bertr gt 2 MS TP RxD Diese gelbe LED blinkt wenn das Modul Daten ber den MS TP Bus empf ngt 3 Power Die gr ne LED zeigt den Zustand der Stromversorgung an MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 4 2 Digital Eingangs Modul Anzeige Das DI 24 Modul besitzt 24 LED zur Anzeige des Eingangszustand je Kanal Eingangskanalanzeige H __ oO _O000000000000000000000 0000000000000 0000000000 ee O0O000000000000000000000000 Die Eingangsanzeige zeigt den Zustand der Eing nge mittels LED an LED aus Kanal inaktiv LED an K
24. ent ReinitializeDevice B The fixed password for DeviceCommunicationControl and ReinitializeDevice services is BACnet MBS GmbH encoded in the ANSI X3 4 character set Segmentation Capability O Segmented requests supported O Segmented responses supported Window Size Window Size Data Link Layer Options BACnet IP Annex J BACnet IP Annex J Foreign Device ISO 8802 3 Ethernet Clause 7 ANSI ATA 878 1 2 5 Mb ARCNET Clause 8 ANSI ATA 878 1 RS 485 ARCNET Clause 8 baud rate s MS TP master Clause 9 baud rate s 9600 19200 38400 76800 MS TP slave Clause 9 baud rate s 9600 19200 38400 76800 NANOOOOO MBS GmbH R merstrasse 15 D 47809 Krefeld Tel 49 21 51 72 94 0 FAX 49 21 51 72 94 50 www mbs software de Point To Point EIA 232 Clause 10 baud rate s Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium Other OOOO Device Address Binding Is static device binding supported This is currently necessary for two way communication with MS TP slaves and certain other devices oO Yes M No Networking Options O Router Clause 6 O Annex H BACnet Tunneling Router over IP O BACnet IP Broadcast Management Device BBMD O Does the BBMD support registrations by Foreign Devices Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously ANSI X3 4 IBM Mic
25. ess_Binding List of BACnetAddressBinding O Profile Name CharacterString O Baud rate proprietary 701 UNSIGNED 9600 19200 38400 76800 oOo W MAC address proprietary 702 UNSIGNED 0 127 master 128 254 slave Oo w 1 BACnet Conformance Code 135 2004 2 BACnet Conformance Code DI 24 R Required Readable W Writable O Optional Not supported MBS GmbH R merstrasse 15 D 47809 Krefeld Tel 49 21 51 72 94 0 FAX 49 21 51 72 94 50 www mbs software de Binary Input Object Type Property Identifier Property Datatype zk Ji Object_Identifier BACnetObjectldentifier 1 24 R IR Object_Name CharacterString max 16 characters R W Object_Type BACnetObjectType R R Present_Value BACnetBinaryPV Rt R Description CharacterString max 16 characters O W Device_Type CharacterString max 16 characters O W Status_Flags BACnetStatusFlags R IR Event_State BACnetEventState R IR Reliability BACnetReliability O Out_Of_Service BOOLEAN R Iw Polarity BACnetPolarity R W Inactive_Text CharacterString max 8 characters 02 W Active_Text CharacterString max 8 characters 02 W Change_Of_State_Time BACnetDateTime 03 Change_Of_State_Count Unsigned 03 Time_Of_State_Count_Reset BACnetDateTime 03 Elapsed_Active_Time Unsigned32 04 Time_Of_Active_Time_Reset BACnetDateTime 04 Time_Delay Unsigned
26. h MS TP slaves and certain other devices oO Yes M No Networking Options O Router Clause 6 O Annex H BACnet Tunneling Router over IP O BACnet IP Broadcast Management Device BBMD O Does the BBMD support registrations by Foreign Devices Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously ANSI X3 4 IBM Microsoft DBCS ISO 8859 1 ISO 10646 UCS 2 ISO 10646 UCS 4 JIS C 6226 OOOOON If this product is a communication gateway describe the types of non BACnet equipment networks s that the gateway supports No gateway functionality yet Remarks If set to slave mode the supported Device Profile is reduced to B SA The BIBB DS COV U B is not supported in slave mode The BIBB DM DCC B supports infinite lifetime only The BIBB DM RD B supports both cold start and warm start The BIBBS DM DCC B and DM RD B are supported with the optional password only The fixed password is BACnet MBS GmbH MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Standard Object Types Supported The supported object types are DEVICE BACnetObjectType ENUMERATED 8 and Binary Output BACnetObjectType ENUMERATED 4 Creation and Deletion of objects is not supported Device Object Type
27. infinite lifetime only The BIBB DM RD B supports both cold start and warm start The BIBBS DM DCC B and DM RD B are supported with the optional password only The fixed password is BACnet MBS GmbH MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Standard Object Types Supported The supported object types are DEVICE BACnetObjectType ENUMERATED 8 and Analog Input BACnetObjectType ENUMERATED 0 Creation and Deletion of objects is not supported Device Object Type Property Identifier Property Datatype 1 2 Object_Identifier BACnetObjectIdentifier R W Object Name CharacterString max 16 characters RK W Object_Type BACnetObjectType R_ R System_Status BACnetDeviceStatus R IR Vendor Name CharacterString R R Vendor_Identifier Unsigned16 R IR Model_Name CharacterString R_ R Firmware_Revision CharacterString R R Application_Software_Version CharacterString R R Location CharacterString O Description CharacterString O Protocol_Version Unsigned R IR Protocol_Revision Unsigned R IR Protocol_Services_Supported BACnetServicesSupported R_ R Protocol_Object_Types_Supported BACnetObjectTypesSupported R R Object_List BACnetARRAY N of BACnetObjectIdentifier R R Max_APDU_Length_Accepted Unsigned max 50
28. lity O Out_Of_Service BOOLEAN R Iw Polarity BACnetPolarity R W Inactive_Text CharacterString max 8 characters Oi W Active_Text CharacterString max 8 characters Oi W Change_Of_State_Time BACnetDateTime 02 Change_Of_State_Count Unsigned 02 Time_Of_State_Count_Reset BACnetDateTime 02 Elapsed_Active_Time Unsigned32 03 Time_Of_Active_Time_Reset BACnetDateTime 03 Minimum_Off_Time Unsigned32 O Minimum_On_Time Unsigned32 O Priority_Array BACnetPriorityArray R R Relinquish_Default BACnetBinaryPV R W Time_Delay Unsigned 04 Notification_Class Unsigned 04 Feedback_Value BACnetBinaryPV 04 Event_Enable BACnetEventtTransitionBits 04 Acked_Transitions BACnetEventTransitionBits 04 Notify_Type BACnetNotifyType 04 Event_Time_Stamps BACnetARRAY 3 ofBACnetTimeStamp 04 Profile_Name CharacterString O DS COVU B proprietary 700 BOOLEAN FALSE no COV TRUE COV U O W 1 BACnet Conformance Code 135 2004 2 BACnet Conformance Code DO 8 R Required Readable W Writable O Optional Not supported The manual switches override the PresentValue at priority level 1 manual life safety of the respective channel Priority level 1 and 6 are not writable using the BACnet WriteProperty service MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de MBS GmbH R merstrasse 15 D 47809 Krefeld www mbs software de info
29. nstellung der gew nschten Slave MAC Adresse Zur Einstellung der Slave Mac Adresse werden die Jumper J3 J4 und J5 verwendet MAC Adresse 128 JJJ JJ 12345 MAC Adresse 129 JJJ JJ 12345 GC I EI a UI MAC Adresse 130 JjJJ JJ 12345 IHM ene MAC Adresse 131 JJJ JJ 12345 ee amp IR MAC Adresse 132 JJJJJ 12345 MAC Adresse 133 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Die MAC Adressen 135 254 k nnen nur mittels der Propertys des Device Objekts eingestellt werden 10 3 7 berpr fung der Slave MAC Adresse Nach dem Setzen der Master MAC Adresse blinkt die TxD LED 7 mal MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 11 Einstellung der BACnet Eigenschaften Die Konfigurationseinstellungen der Module k nnen ber die BACnet WriteProperty geschrieben und ber die ReadProperty gelesen werden 11 1 Einstellung der Baud Rate Die Baud Rate wird mittels schreiben auf das Proprietary Property 701 des Device Object gesetzt Der Datentype ist UNSIGNED und die m glichen Baud Raten sind 9600 19200 38400 und 76800 Die Einstellungen werden nach einem Reset wirksam Dazu kann entweder die Spannungsversorgung Aus und Eingeschaltet oder der BACnet Befehl ReinitializeDevice gesendet werden 11 2 Einstellung der MAC Adresse Die MS TP MAC Adresse wird
30. nstellung des Master Modus und der MAC Adresse wird kein Jumper gesetzt 3332353 12345 MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 3 3 Einstellen der gew nschten MAC Adresse Die Adresseinstellung wird ber die bin r kodierten Jumper J1 J5 vorgenommen J1 Bit0 J2 Bit1 usw Bitte beachten Sie das die Adresse 0 nur mit Hilfe der Reset Funktion oder durch Beschreiben des Device Objektes eingestellt werden kann MAC Adresse 1 JjJJ JJ 12345 MAC Adresse 2 JjJJ JJ 12345 MAC Adresse 3 JJJJJ 12345 eee eee MAC Adresse 4 JjJJ JJ 12345 usw entsprechend der bin ren Kodierung der Jumper MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de MAC Adresse 29 J JJJJ 12345 MAC Adresse 30 J JJJJ 12345 MAC Adresse 31 J JJJJ 12345 Die MAC Adressen 32 127 k nnen nur mittels der Proprietary Propertys des Device Objekts eingestellt werden 10 3 4 berpr fung der Master MAC Adresse Nach dem Setzen der Master MAC Adresse blinkt die TxD LED 7 mal MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 10 3 5 Einstellung des Modus MS TP Slave Um den Slave Modus und die MAC Adresse einzustellen werden die Jumper J1 und J2 gebr ckt on JJ J 234 oo LALLI ere 10 3 6 Ei
31. racterString R R Application_Software_Version CharacterString R R Location CharacterString O Description CharacterString O Protocol_Version Unsigned R IR Protocol_Revision Unsigned R IR Protocol_Services_Supported BACnetServicesSupported R_ R Protocol_Object_Types_Supported BACnetObjectTypesSupported R R Object_List BACnetARRAY N of BACnetObjectIdentifier R R Max_APDU_Length_Accepted Unsigned max 50 R IR Segmentation Gupported BACnetSegmentation R R Max_Segments_Accepted Unsigned O VT_Classes_Supported List of BACnetVTClass O Active_VT_Sessions List of BACnetVTSession O Local_Time Time O Local_Date Date O UTC_Offset INTEGER O Daylight_Savings_Status BOOLEAN O APDU_Segment_Timeout Unsigned O APDU_Timeout Unsigned 10 000 ms R R Number_Of_APDU_Retries Unsigned 5 R R List_Of_Session_Keys List of BACnetSessionKey O Time_Synchronization_Recipients List of BACnetRecipient O Max_Master Unsigned 127 O R Max_Info_Frames Unsigned 1 O R Device_Address_Binding List of BACnetAddressBinding empty R R Database_Revision Unsigned 1 R_ R Configuration_Files BACnetARRAY N of BACnetObjectldentifier O Last_Restore_Time BACnetTimeStamp O Backup_Failure_Timeout Unsigned16 O Active_COV_Subscriptions List of BACnetCOVSubscription O Slave_Proxy_Enable BACnetArray N of BOOLEAN O Manual_Slave_Address_Binding List of BACnetAddressBinding O Auto_Slave_Discovery BACnetArray N of BOOLEAN O Slave_Addr
32. rnen des Moduls von der DIN Hutschiene ziehen Sie an der unteren Befestigung und entnehmen das Modul Achtung Ziehen Sie die die Verriegelungslasche nicht mehr als 3mm um eine Besch digung zu vermeiden 5 2 Zur Installation ben tigte Werkzeuge Zur Installation ben tigen Sie folgende Werkzeuge Schraubenzieher 3 mm Schlitz mitgeliefert Jumper 5 St ck mitgeliefert Diese Anleitung mitgeliefert 120 Ohm Abschlusswiderst nde mitgeliefert MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de 5 3 Anschluss der Module Verbinden Sie die Ein Ausg nge mit dem Modul Schlie en Sie anschlie end das MS TP Netzwerk an und verbinden die Stromversorgung mit dem Modul Bitte beachten Sie die Spezifikationen Bei Nichteinhaltung der Spezifikationen erlischt im Schadensfall die Garantie Durch ffnen des Geh uses erlischt die Garantie Es befinden sich keine benutzerrelevanten Teile innerhalb des Geh uses Bitte beachten Sie die VDE 100 und gleichwertige Schutzvorschriften bei der Installation der Module 5 4 Besondere Vorschriften f r die Inbetriebnahme von AI 24 Modulen Beim Anschluss der 0 10V Signale ist das minus Potential mit dem GND Anschluss des Moduls und das positive Potential mit dem Signalanschluss zu verbinden 5 5 Besondere Vorschriften f r die Inbetriebnahme von DI 24 Modulen Nur potentialfreie Kontakte d rfen an die Eing nge
33. rosoft DBCS ISO 8859 1 ISO 10646 UCS 2 ISO 10646 UCS 4 JIS C 6226 OOOOON If this product is a communication gateway describe the types of non BACnet equipment networks s that the gateway supports No gateway functionality yet Remarks If set to slave mode the supported Device Profile is reduced to B SA The BIBB DS COV U B is not supported in slave mode The BIBB DM DCC B supports infinite lifetime only The BIBB DM RD B supports both cold start and warm start The BIBBS DM DCC B and DM RD B are supported with the optional password only The fixed password is BACnet MBS GmbH MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Standard Object Types Supported The supported object types are DEVICE BACnetObjectType ENUMERATED 8 and Binary Input BACnetObjectType ENUMERATED 3 Creation and Deletion of objects is not supported Device Object Type Property Identifier Property Datatype 1 2 Object_Identifier BACnetObjectIdentifier R W Object Name CharacterString max 16 characters RK W Object_Type BACnetObjectType RK IR System_Status BACnetDeviceStatus R IR Vendor_Name CharacterString R R Vendor_Identifier Unsigned16 R IR Model_Name CharacterString R_ R Firmware_Revision Cha
34. rsion 1 0 Firmware Revision 1 0 BACnet Protocol Version 1 BACnet Protocol Revision 4 Product Descrip tion The MBS AI 24 module is a highly reliable BACnet Analog Input module supporting 16 channels PT1000 and 8 channels 0 10V analog input The module supports all standardized BACnet MS TP baud rates from 9600 up to 76800 bit s The modules may run in MS TP master and slave mode BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actuator B SA OONOOO List all BACnet Interoperability Building Blocks Supported Annex k DS RP B Data Sharing ReadProperty B DS WP B Data Sharing WriteProperty B DS COVU B Data Sharing ChangeofValue Unsolicited B DM DDB B Device Management DynamicDeviceBinding B DM DOB B Device Management DynamicObjectBinding B DM DCC B Device Management DeviceCommunicationControl B DM RD B Device Management ReinitializeDevice B The fixed password for DeviceCommunicationControl and ReinitializeDevice services is BACnet MBS GmbH encoded in the ANSI X3 4 character set Segmentation Capability O Segmented requests supported Window Size O Segmented responses supported Window Size Data Link Layer Options BACnet IP Annex J BACnet IP Annex J Foreign Device ISO 8802 3 Ethernet Clause 7
35. t Actuator B SA OOROOD List all BACnet Interoperability Building Blocks Supported Annex k DS RP B Data Sharing ReadProperty B DS WP B Data Sharing WriteProperty B DS COVU B Data Sharing ChangeofValue Unsolicited B DM DDB B Device Management DynamicDeviceBinding B DM DOB B Device Management DynamicObjectBinding B DM DCC B Device Management DeviceCommunicationControl B DM RD B Device Management ReinitializeDevice B The fixed password for DeviceCommunicationControl and ReinitializeDevice services is BACnet MBS GmbH encoded in the ANSI X3 4 character set Segmentation Capability O Segmented requests supported Window Size O Segmented responses supported Window Size Data Link Layer Options BACnet IP Annex J BACnet IP Annex J Foreign Device ISO 8802 3 Ethernet Clause 7 ANSI ATA 878 1 2 5 Mb ARCNET Clause 8 ANSI ATA 878 1 RS 485 ARCNET Clause 8 baud rate s MS TP master Clause 9 baud rate s 9600 19200 38400 76800 MS TP slave Clause 9 baud rate s 9600 19200 38400 76800 oO oO oO oO oO M M MBS GmbH Tel 49 21 51 72 94 0 Romerstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de Point To Point EIA 232 Clause 10 baud rate s Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium Other OOOO Device Address Binding Is static device binding supported This is currently necessary for two way communication wit
36. yer BACnet IP BACnet Ethernet und MS TP Unterstutzt die Konfiguration von MS TP I O Modulen mittels eines eingebauten Webservers BACnet OPC Server Die f hrende Softwarel sung um ein BACnet Netzwerk und OPC Client Ger te zu verbinden BACnet OPC Client Der BACnet OPC Client erm glicht es OPC basierte Anwendungen einfach und schnell BACnet f hig zu machen BACnet Universal Gateways Die L sung um Kommunikationsprotokolle mit BACnet oder BACnet Ger te zu verbinden BACnet Test Framework Die Software zur Pr fung von BACnet Ger ten auf Einhaltung der Konformit t zum Standard Diese Software wird unter anderem als offizielles Europ isches Testtool vom BACnet Testlabor bei WSPLab in Stuttgart eingesetzt MBS GmbH Tel 49 21 51 72 94 0 R merstrasse 15 FAX 49 21 51 72 94 50 D 47809 Krefeld www mbs software de BACnet Training und Consulting Lernen Sie die Grundlagen des BACnet spezifizieren eines BACnet Projektes oder wie man ein BACnet Projekte entwickelt und implementiert BACnet Data Logger Loggen und analysieren Sie Ihren BACnet Netzwerkverkehr in Ihrem Projekt BACnet Data Server Monitoring Aufzeichnung und Remote Zugang zu Ihrem BACnet Project BACnet Protocol Stacks Von kleinen MS TP Implementationen bis zu gro en B BC BACnet IP Ger ten unsere L sung zur Entwicklung von BACnet Produkten 2 4 Produkt Support Unser Support ist erreichbar Montag Freitag von 9 00 16 00 Uhr

Download Pdf Manuals

image

Related Search

Related Contents

Villeneuve d`Ascq - Lille Métropole Habitat  USER`S MANUAL  Conair CS56BCR hair straightener  Samsung HT-Z120 User Manual  「ハンドブック」をダウンロードする  Manual do utilizador  Buffalo LinkStation Quad 4TB  Samsung 234 Litros Frigorífico 2 portas no frost RT22FARADWW manual de utilizador  IMPRESSA E10/20/25 Bedienungsanleitung  Carrier Access EdgeFLEX Computer Hardware User Manual  