Operating Instructions - ACS-Control
Contents
1. accessible e Enter correct code ERRT lights up in the 7 segment e Please contact the manufacturer if errors of display this kind occur The device does not react as e If you are not sure if the device has been expected parameterised before then follow the steps as written in chapter 6 and set it back to its delivery status 7 The temperature value is unstable e Please check the possibility to set aside the galvanic insulation for a discharging of failures as described under chapter 3 Electrical connection Before make sure that the possible metal sensor is separated from the sensor element ACS CONTROL SYSTEM GmbH ILauterbachstr 57 D 84307 Eggenfelden www acs controlsystem delinfo acs controlsystem de 15 OHO BORS Wy fill level water level pressure temperature flow visualization signal converter sensoric Wir erwarten Ihren Anruf ACS CONTROL SYSTEM GmbH Lauterbachstr 57 D 84307 Eggenfelden Tel 49 0 8721 9668 0 ACS CONTROL SYSTEM X OE info acs controlsystem de knowhow with system contsys ere a Stand 07 2014 Your partner for measuring technology and automation
2. equaliser normally signal ground e The device is not suitable for installation in areas where there is a risk of explosion e Any electrical connection deviating from the connection diagram can endanger human life and or can destroy the equipment e The terminal area of the devices is part of the service Here electrostatic discharge needs to be avoided Attention High voltages can cause dangerous body currents e Galvanic isolated potentials within one complex need to be placed on an appropriate point normally earth or machines ground So a lower disturbance sensibility against impacted energy can be reached and dangerous potentials that can occur on long lines or due to faulty wiring can be avoided 1 4 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden Iwww acs controlsystem delinfo acs controlsystem de The unit permanently indicates e The input has a very high measurement overflow check the measuring circuit e The input is open 2 The unit permanently shows e The input has a very low measurement check underflow the measuring circuit e The input is open 3 The word HELP lights up in the e The unit has found an error in the 7 segment display configuration memory Perform a reset on the default values and reconfigure the unit according to your application Program numbers for parameterising e Programming lock is activated of the input are not
3. levels Menu Level Here it is possible to navigate between the individual menu items Parameterization level The parameters stored in the menu item can be parameterized here Functions that can be adjusted or changed are always indicated with a flashing of the display Adjustments made at the parameterization level should be always confirmed by pressing the P key to save them However the display automatically saves all adjustments and then switches to operation mode if no further keys are pressed within 10 seconds E to parameterization level with the relevant parameters Menu level For navigation at the menu level B To confirm the changes made at the parameterization Parameterization level eve To change the value or setting Example _ gt _ Parameterization level 4 1 Programming via configuration software PM TOOL MUSB4 You receive the software on CD incl an USB cable with a device adapter The connection is done via a 4 pole micromatch connector plug on the back and the PC is connected via an USB connector plug system requirements PC with USB interface Software Windows XP Windows Vista With this tool the device configuration can be created skipped and safed on the PC Via the easy to handle program surface the parameter can be changed whereat the mode of operation and the possible selection options can be preset via the program CAUTION During parameter
4. KA fill level water level pressure temperature flow visualization signal converter sensoric DET NON 7 Ao swantier NNA Q PTI 2 s wire Jllf X i CL U O Lm I VV III Boe VY 7 n Na d J i Technical features e red display of 1999 9999 digits optional green orange or blue display e minimal installation depth 25 mm without plug in terminal e adjustment via factory default or directly on the sensor signal e min max memory e displayed in C F e display flashing at threshold exceedance undershooting e impedance matching e programming interlock via access code e protection class IP65 at the front e plug in terminal e pc based configuration software PM TOOL with CD and USB adapter for devices without keypad for a simple adjustment of standard devices IACS knowhow with s Bia i L i ACS CONTROL SYSTEM ur partner for measurin g technology and aui Order code power supply 0 230V AC 2 24V DC galvanic seperated 6 4 20 mA 2 wire current loop display function input 2 Pt100 input 2 3 wire up to 850 C function output O display 230V AC 24 V DC version O standard configuration S standard protection IP65 DAL 101 Gib ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden l www acs controlsystem delinfo acs controlsystem de Content 1 2 3 4 10 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden l www acs control
5. ain Setting the decimal place sign of physical unit END Default 000 0 Al A m lA m lA P a Ooa Olly OCC e The decimal place and the physical unit are set with V A If e g the temperature measurement is chosen in C 0 C or 0 0 C can be selected on the parameterization level Confirm with P the display then switches back to the menu level again Impedance matching OFFS Default 0 0 g ar eh The value for the sensor alignment is adjusted from the smallest to the highest place with V A and confirmed digit per digit with P After the last place the display switches back to the menu level The value alignment for a temperature measurement in C can be set between 20 0 and 20 0 and for a measurement in F between 36 0 and 36 0 If the measurement is redirected later the value is rounded Setting the display time SEC Default 0 0 v j then P The display time is set with A V The display moves up in increments of 0 1 sec up to 1 second and in increments of 1 0 to 10 0 seconds Confirm the selection by pressing the P button The display then switches back to the menu level again ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden Iwww acs controlsystem delinfo acs controlsyst
6. e saved during operation and can be called up via the arrow keys A W The values are lost if the device is restarted If the threshold value correction Li is selected the limit values can be changed during operation without hindering the operating procedure With TARA the display is tared to zero and is saved permanently as offset The device confirms the correct taring by showing 8000 in the display If NO is parameterized the navigation keys V A have no function in operating mode Flashing of display FLAS Default NO a Al A nN Li g he g Ob fe iy ae g PI Here flashing of the display can be added as an extra alarm function either to the first limit value select Li 7 the second limit value select Li 2 or to both limit values select LI 12 With NO works setting no flashing is assigned at all 8 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden Iwww acs controlsystem delinfo acs controlsystem de Menu level Parameterization level Limit values limits L Default 0200 0 p 2 oI gge For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other Hysteresis for limit values H9 Default 0000 0D pege gge For both limit values a hysteresis functio
7. em de 7 Parameterization level 5 3 Programming interlock RUN Activation deactivation of the programming lock and completion of the standard parameterization RUN Default ULOC Cor S Cee Choose between the deactivated key lock ULOC works setting and the activated key lock LOC with the navigation keys A V Make the selection with P After this the display confirms the settings with and automatically switches to operating mode If LOC was selected the keyboard is locked To get back into the menu level press P for 3 seconds in operating mode Now enter the CODE works setting 72 3 4 that appears using the A Y keys plus P to unlock the keyboard FAIL appears if the input is wrong 5 4 Extended parameterization By pressing the A amp Y keys during standard parameterization for one second the display switches to the extended parameterization mode Operation is the same as in standard parameterization Menu level Parameterization level Min max value inquiry assignment of key functions TAST Default NO ci A n a C fy ee iv no fw PI Here you can enter for the operating mode either a min max value inquiry or a threshold value correction on the arrow keys If the min max memory is activated with EHER the measured min max values will b
8. er 2 before installation and keep it for future reference Proper use The DAL 101 device is designed for the evaluation and display of Pt100 signals Danger Careless use or improper operation can result in personal injury and or damage to the equipment Control of the device The panel meters are checked before dispatch and sent out in perfect condition Should there be any visible damage we recommend close examination of the packaging Please inform the supplier immediately of any damage Installation The DAL 101 device must be installed by a suitably qualified specialist e g with a qualification in industrial electronics e There must be no magnetic or electric fields in the vicinity of the device e g due to transformers mobile phones or electrostatic discharge e The fuse rating of the supply voltage should not exceed a value of 6A N B fuse e Do not install inductive consumers relays solenoid valves etc near the device and suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes e Keep input output and supply lines separate from each other and do not lay them parallel with each other Position go and return lines next to one another Where possible use twisted pair So the best measuring results can be received e Screen off and twist sensor lines Do not lay current carrying lines in the vicinity Connect the screening on one side on a suitable potential
9. isation with connected measuring signal make sure that the measuring signal has no mass supply to the programming plug The programming adapter is galvanic not isolated and directly connected with the PC Via polarity of the input signal a current can discharge via the adapter and destroy the device as well as other connected components 6 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden l www acs controlsystem delinfo acs controlsystem de 5 Setting up the device 5 1 Switching on Once the installation is complete you can start the device by applying the current loop Check beforehand once again that all the electrical connections are correct Starting sequence For 1 second during the switching on process the segment test 8 8 8 8 8 is displayed followed by an indication of the software type and after that also for 1 second the software version After the start up sequence the device switches to operation display mode 5 2 Standard parameterization To be able to parameterize the display press the P key in operating mode for 1 second The display then changes to the menu level with the first menu item TYPE Menu level Parameterization level Type of the temperature measurement TYPE Default C m p A ce S E For representing of temperature choose between C and F and confirm with P The display then switches back to the menu level ag
10. limit value HIGH can be selected HIGH upper limit value LOW corresponds to the quiescent current principle and HIGH to the operating current principle Setting the code CODE Default 7234 Lode P P 3 P i Au MN With this setting it is possible to select an individual code works setting 7 2 3 4 for locking the keyboard To lock release the key proceed according to menu item RUN 6 Reset to default values To return the unit to a defined basic state a reset can be carried out to the default values The following procedure should be used e Switch off the power supply e Press button P e Switch on voltage supply and press P button until is shown in the display With reset the default values of the program table are loaded and used for subsequent operation This puts the unit back to the state in which it was supplied Caution All application related data are lost 1 Oo ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden l www acs controlsystem delinfo acs controlsystem de 7 Functional principle of the switching points Setpoint Limit value exceedance HIGH The switching point S1 S2 is off Threshold below the threshold and on on On as ss ae te O ae Se reaching the threshold i j A z E o Off Display Hysterisis Setpoint Limit value undercut LOW The switching point S1 S2 is Threshold on below the
11. n exists that reacts according to the functional principle operating current quiescent current Function if display falls below exceeds limit value FU Default HI9H faen P To indicate if the value falls below the lower limit value LOUU can be selected LOW lower limit value and if it goes above the upper limit value HIGH can be selected HIGH upper limit value LOW corresponds to the quiescent current principle and HIGH to the operating current principle Limit value limits L 2 Default 0300 gage For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other Hysteresis for limit values H9 2 Default 0000 3 g 8 geg ae For both limit values a hysteresis function exists that reacts according to the functional principle operating current quiescent current ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden Iwww acs controlsystem delinfo acs controlsystem de 9 Menu level Parameterization level Function if display falls below exceeds limit value FU 2 Default HI9H Al A mi fy ouu fy P To indicate if the value falls below the lower limit value LOUU can be selected LOW lower limit value and if it goes above the upper
12. point slowdown a direct change of the limit value in operating mode an dadditional measuring supporting points for linearisation complete the modern device concept 2 Assembly Please read the Safety advice on page 12 before installation and keep this user manual for future reference Gap for physical unit 1 After removing the fixing elements insert the device 2 Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping screws by hand Then use a screwdriver to tighten them another half a turn CAUTION The torque should not exceed 0 1 Nm 4 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden Iwww acs controlsystem delinfo acs controlsystem de 3 Electrical connection Type DAL 101x200S Type DAL 101x200S supply of 230 VAC supply of 24 VDC 230 VAC yee 94VDC 2 wire 2 wire i lt 3 VA lt 1VA Pt100 Pt100 3 wire 3 wire Advice The galvanic isolation in devices with temperature sensors that do not have a galvanic connection to an extrinsic potential can be cancelled by an bridge from terminal 3 to 4 and thus stabilise the device against external failures Devices with a supply of 230 VAC need to connect terminal 3 to signal ground ACS CONTROL SYSTEM GmbH Lauterbachstr 571D 84307 Eggenfelden www acs controlsystem delinfo acs controlsystem de 4 Function description and operation Operation The operation is divided into two different
13. system delinfo acs controlsystem de Brief description Assembly Electrical connection and conenction examples Function description and operation 4 1 Programming software PM TOOL Setting up the device 5 1 Switching on 5 2 Standard parameterisation flat operation level Value assignment for control of the signal input displayed in C F impedance matching 5 3 Programming interlock RUN Activation Deactivation of the programming interlock or change into extended parameterisation 5 4 Extended parameterisation Superior device functions like e g allocation of functions onto the navigation keys adjustment of limit values for optical alarm LI 1 2 safety parameter for locking of the programming CODE Reset to default values Reset of the parameter onto delivery condition Alarms Switching points Functional principle of the optical switching points Technical data Safety advice Error elimination aaa kh A W NN oOo NNN 10 12 13 1 Brief description The panel instrument DAL 101 is a 4 digit device for pt100 signals and a visual limit value monitoringvia the display The confi guration happens via three front keys or via the optional PC software PM TOOL An integrated programming interlock prevents unrequested changes of the parameter and can be unlocked again via an individual code The electrical connection happens on the rearside via plug interminals Selectable functions like e g the recall of the min max value a zero
14. threshold and By P A ee ee eee switched off on reaching the r threshold 1 z vE Sy 8 I Off Display Hysterisis Alarms optical switching point display An activated setpoint can be optically indicated by flashing of the 7 segment display Functional principle of the alarms ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden l www acs controlsystem delinfo acs controlsystem de 11 8 Technical data CO O oO eme neuan emna O Protection class standard IP65 front IPOO back side Weight approx 100 g Connection plug in terminal wire cross section up to 2 5 mm Display Display time 0 1 to 10 0 seconds Measuring fault Pt100 2 3 wire 0 1 of measuring range Pt100 2 3 wire 0 1 of measuring range 21 Accuracy 230 VAC 10 max 3 VA 24 VDC 10 max 1 VA i 1 2 ACS CONTROL SYSTEM GmbH Lauterbachstr 57 1D 84307 Eggenfelden Iwww acs controlsystem delinfo acs controlsystem de Ambient conditions Working temperature 0 C 60 C Storing temperature 20 C 80 C Weathering resistance relative humidity 0 80 on years average without dew EN 61326 CE sign Conformity to directive 2004 108 EG Safety standard According to low voltage directive 2006 95 EG EN 61010 EN 60664 1 ACS CONTROL SYSTEM GmbH Lauterbachstr 571D 84307 Eggenfelden www acs controlsystem delinfo acs controlsystem de 1 3 9 Safety advice Please read the following safety advice and the assembly chapt