White Rodgers 1131-102 Well Immersion Single Control Installation Instructions
Contents
1. NO 37 2071B Replaces 37 2071 amp 37 9195 9548 CONVERTIBLE CONTROLS CONT To convert from Vertical to Horizontal model remove Knockout Plug and Plate Remove Hex Nut inside con trol and swing capillary upward into back knockout Place Knockout Plate beneath Hex Nut on back of control and tighten Hex Nut inside control If bottom knockout is not used for wiring insert Knockout Plug EXTENDING CAPILLARY Some controls have excess stored capillary which may be extended for use with an extended shank well Use reason able care when straightening and forming the capillary INSTALLATION If the boiler manufacturer recommends a control location then follow such recommendations If none are offered the following are suggested locations For high limit service the control should be located in the hottest part of the boiler This is usually near the top of the boiler A high limit control should not be in the same section of the boiler that contains the heat exchanger that supplies domestic hot water For low limit or operating service the control should be so located that it responds to the temperature of that section of the boiler that heats domestic hot water When used as a circulator control it may be located near the boiler outlet or riser WIRING Convertible Control converted to Vertical Model With the capillary fully extended the bulb should slide all the way to the end of the well When used on a co
2. correctement dans la gaine Tout le c blage doit tre conforme aux codes et r glements locaux et nationaux qui r gissent les installations lectriques CABLAGE ROUGE BLEUE OUVERTURE NEUTRE SUR HAUSSE DE TEMP RATURE 6 BLANCHE FERMETURE SUR HAUSSE DE TEMPERATURE Le r gulateur est dot d un commutateur unipolaire bidirectionnel d clic La borne situ e en haut gauche rouge est la borne neutre Celle qui se trouve en haut droite bleue ouvre le circuit sur une hausse La borne centrale inf rieure blanche ferme le circuit sur une hausse Se r f rer aux sch mas de c blage fournis parle fabricant de la chaudi re ou du br leur ou aux circuits de r f rence fournis avec la commande principale Les renseignements ci dessous pr cisent les bornes utiliser selon l application Limiteur Pour utiliser la commande comme limiteur maximum ou minimum se servir des bornes ouverture sur hausse rouge et bleue Circulateur Pour utiliser la commande comme circulateur se servir des bornes fermeture sur hausse rouge et blanche Commande combin e circulateur avec limiteur minimum Pour une application de ce type faire appel aux trois bornes Le sch ma de c blage ci dessous repr sente un circuit typique pour un syst me de chauffage dot d une chaudi re a serpentin domestique sans r servoir CABLAGE suite Sch ma pour un syst me gaz ou mazout avec serpenti
3. AU CHAUDE Unipolaire bidirectionnel SPDT avec gaine INSTRUCTIONS D INSTALLATION Utilisateur conservez ces instructions pour vous y r f rer au besoin SI VOUS NE LISEZ PAS ATTENTIVEMENT CES INSTRUCTIONS AVANT D INSTALLER ET D UTILISER LA COMMANDE VOUS RISQUEZ DE CAUSER DES BLESSURES ET DES DOMMAGES MATERIELS La commande type 1131 a t con ue pour servir avecun syst me de chauffage eau chaude Elle est dot e d un commutateur unipolaire bidirectionnel et de bornes assurant louverture et la fermeture sur hausse La commande peut servir de limiteur minimum ou maximum de circulateur ou en combinaison de limiteur avec circulateur ll existe des mod les diff rentiel fixe ou r glable et qui conviennent aux gaines verticales ethorizontales Certains des mod les sont aussi dot s dans le bo tier d un surplus de capillaire qui permet de les utiliser avec une gaine normale ou longue Un autre mod le id al comme remplacement est dot d un bo tier rainure et d un surplus de capillaire Il peut ainsi servir avec une gaine normale ou longue mont e verticalement ou horizontalement LA PR SENTE COMMANDE DOIT TRE INSTALL E PAR UN TECHNICIEN QUALIFI Ne d passez pas les charges nominales Toutle c blage doit tre conforme aux codes etr glements locaux et nationaux qui r gissent les installations lectriques Cette commande est un instrument de pr cision qui doit tre ma
4. WHITE RODGERS TYPE 1131 HOT WATER CONTROL S P D T Well Immersion INSTALLATION INSTRUCTIONS Operator Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND OR PROPERTY DAMAGE Type 1131 controls are designed for use on hot water heating installations They have single pole double throw switch action offering open on rise terminals as well as close on rise terminals These controls may be used as a high limit low limit circulator or combination low limit circulator control Models are available with either horizontal or vertical well and with either fixed or adjustable differential Some of these models also have excess capillary stored within the enclosure permitting them to be used with wells having either a standard or extended shank Another model ideal for replacement purposes has both a slotted case and excess capillary stored within the enclosure This control can be used with either a standard or extended shank well on either horizontal or vertical well installations THIS CONTROL MUST BE INSTALLED BY A QUALIFIED INSTALLER Do not exceed the specification ratings All wiring must conform to local and national electrical codes and ordinances This control is a precision instrument and should be handled carefully Rough handling or distorting compo nents could cause the control to malfunc
5. cs lectriques et d incendie COMMANDES CONVERTIBLES D gager la tige de montage de la gaine et retirer la plaque de conversion Glisser le capillaire dans la rainure jusqu la plaque inf rieure Fixer la plaque de conversion l arri re de la commande l aide du bouchon de conversion qui se trouve dans l enveloppe Introduire la tige de montage de la gaine dans la plaque inf rieure et serrer solidement l crouhexagonal l int rieur de la commande PI CE No 37 2071B Remplace 37 2071 amp 37 9195 Imprim aux E U A 9548 COMMANDES CONVERTIBLES suite Pour convertir la commande de la verticale l horizontale retirer d abord le bouchon et la plaque de conversion Retirer l crou hexagonal l int rieur de la commande et glisser le capillaire dans la rainure jusqu la plaque arri re Placer la plaque de conversion sous crou hexagonal l arri re de la commande et serrer l crou hexagonal l int rieur de la commande Si l ouverture de la plaque inf rieure ne sert pas au c blage y poser le bouchon de conversion EXTENSION DU CAPILLAIRE Certaines commandes ont un surplus de capillaire qui peut tre allong afin de servir avec une gaine allong e Proc der soigneusement pour redresser et former le capillaire INSTALLATION Si un emplacement de la commande estrecommand par le fabricant de la chaudi re alors veuillez vous y conformer Si aucun e
6. e temperature at which the low limit stops the burner and permits the circulator to run B FIXED INDICATOR A ADJUSTING SLOT C DIFFERENTIAL ADJUSTING SCREW D MOVABLE INDICATOR MOTOR CIRCULATOR MOTOR HIGH LIMIT CIRCULATOR LOW LIMIT If excessive boiler temperature causes the high limit to open the circulator continues to run but the burner shuts down until the high limit recloses If low boiler temperature causes the R W contacts of the low limit circulator control to open the burner stays on but the circulator stops until the R W contacts reclose When the thermostatis satisfied the circulator stops The burner also shuts down if the R B contacts of the low limit circulator control are open SETTING THE CONTROL Controls with a Fixed Differential Insert a screwdriver in centre slot A and turn the dial until the fixed indicator B points to the highest desired tem perature of the cycle The fixed indicator points to the temperature at which the contacts open on high limit and low limit applications On circulator applications the fixed indicator points to the temperature at which the circulator will start On combination low limit and circulator applications the fixed indicator points to the temperature at which the low limit stops the burner and permits the circulator to run B FIXED WHITE RODGERS 1131 REGULATEUR D E
7. maximum ou de limiteur minimum Lorsque la commande sert de circulateur l indicateur du c t gauche indique la temp rature de mise en marche du circulateur Lorsque la commande sert de circulateur avec limiteur a minimum l indicateur du c t gauche indique la temp rature laquelle le limiteur minimum arr tera le br leur tout en permettant au circulateur de fonctionner B INDICATEUR FIXE L A FENTE DE R GLAGE
8. mbination low limit and circulator control it should be located the same as suggested for low limit service To remove the well from the control loosen set screw in the large nut then slide the well off which exposes the bulb Screw the well into the proper tapping Slide the bulb back into the well making sure that the bulb enters the well as far as it will go Tighten the set screw CAUTION Do not dent or bend the bulb as this will prevent it from fitting into the well properly All wiring should be done in accordance with local and national electrical codes and ordinances RED A Z WHITE BLUE OPEN ON RISE COMMON OF TEMPERATURE CLOSE ON RISE OF TEMPERATURE This control has a single pole double throw snap action switch The top left hand terminal red is the common terminal The top right hand terminal blue has open on rise switch action The bottom center terminal white has close on rise switch action Refer to the wiring diagram supplied by the boiler or burner manufacturer or to the suggested circuits included with the primary control The information below shows the terminals to use for the various applications Limit Control When used as either a high limit control or as a low limit control use the open on rise terminals red and blue Circulator Control When used as a circulator control use the close on rise terminals red and white Combination Low Limit and Circulator Control F
9. mplacement n est sugg r veuillez suivre les conseils suivants Pour utiliser la commande comme limiteur maximum situer la commande dans la section la plus chaude de la chaudi re qui est habituellement la partie sup rieure Ne pas installer un limiteur maximum dans la partie de la chaudi re ou se trouve l changeur de chaleur qui fournit l eau chaude domestique Pour utiliser la commande comme limiteur minimum ou comme actionneur situer la commande dans la partie de la chaudi re qui chauffe l eau chaude domestique Pour utiliser lacommande avec un circulateur l installer pres de la sortie d eau ou de la colonne montante de la chaudi re BOUCHON DE CONVERSION PLAQUE DE CONVERSION CAPTEUR _ Commande convertie en mod le vertical Une fois le capillaire compl tement allong le capteur doit glisser jusqu au fond de la gaine Pour utiliser la commande comme limiteur minimum avec circulateur l installer de la fa on recommand e pour l utilisation comme limiteur minimum Pour s parer la gaine de la commande desserrer d abord la vis de r glage du gros crou puis glisser la gaine pour exposer le capteur Visser la gaine dans l ouverture taraud e qui convient R introduire ensuite le capteur dans la gaine en prenant soin qu il soit bien au fond Serrer la vis de r glage ATTENTION Ne pas plier ou bosser le capteur car il serait alors impossible de l introduire
10. n domestique sans r servoir THERMOSTAT 3 FILS Zz COMMANDE DE BRULEUR UTILISER W B AVEC UN 2 MAZOUT TYPE 668 THERMOSTAT 2 FILS z TENSION R SEAU eD N lt ROBINET GAZ LIMITEUR 3 D DE 24 V C A Q w MAXIMUM RELAIS AT E TRANSFO D ALLUMAGE TRANSFO TYPE 809 CAVALIER MOTEUR DE BRULEUR MOTEUR DE Le circuit R B du circulateur avec limiteur a minimum assure l ann e longue que l eau chaude domestique sera maintenue la temp rature souhait e Lorsque le thermostat ex cute un appel de chaleur le br leur est mis en marche Le circulateur est aussi mis en marche si le circuit R W du circulateur avec limiteur minimum est ferm Si la temp rature de la chaudi re est lev e entra nant l ouverture du limiteur maximum alors le circulateur Commandes diff rentiel r glable 1 Introduire la pointe d un tournevis dans la fente de r glage A Tourner le cadran pour que l indicateur du c t droit B indique la temp rature la plus basse du cycle 2 Tourner la vis de r glage du diff rentiel C jusqu ce que l indicateur du c t gauche D indique la temp rature la plus lev e du cycle L indicateur du c t gauche indique la temp rature a laquelle les contacts seront ouverts lorsque lacommande sert de limiteur maximum ou de limiteur minimum Lorsque la commande sert de circulateur l indicateur du c
11. nipul avec soin Elle peut se d traquer si elle est manipul e de fa on n gligente ou si des composantes sont d form es La commande a t calibr e avec pr cision lors de la fabrication Toute tentative de calibrer l appareil annulera la garantie de White Rodgers Les commandes convertibles sont dot es l arri re d une plaque de conversion tenue par un crou hexagonal sur les mod les horizontaux et par un bouchon de conversion sur les mod les verticaux Pour convertir la commande de l horizontale la verticale 1 Retirer le couvercle de la commande Retirer ensuite la plaque inf rieure 2 Retirer l crouhexagonal l int rieur de lacommande de la tige de montage de la gaine Pour desserrer l crou le tenir tout en tournant gauche l crou hexagonal qui se trouve l arri re de la commande WHITE RODGERS DIVISION EMERSON ELECTRIC CO 9797 REAVIS RD ST LOUIS MO 63123 314 577 1300 TELECOPIEUR 314 577 1517 9999 HWY 48 MARKHAM ONT L3P 3J3 905 475 4653 TELECOPIEUR 905 475 4625 pail EE DESCRIPTION Be Q PR CAUTIONS Afin de pr venir les chocs lectriques et les dommages mat riels pendant l installation coupez l alimentation lectrique au panneau de distribution principal AVERTISSEMENT N installez pas cet appareil sur des circuits qui d passent la tension nominale Une tension trop lev e peut endommager la commande et poser des risques de cho
12. or this application all 3 terminals are used The wiring diagram on the next page shows a typical circuit for a hot water system having a boiler with tankless domes tic coil WIRING CONT Diagram For Gas Or Oil Fired System With Tankless Domestic Coil WIRE THERMOSTAT USE W B FOR 2 WIRE THERMOSTAT 24 VAC TYPE 668 OIL BURNER CONTROL LINE VOLTAGE Lu O zZ GAS VALVE HIGH LIMIT Q f iz IGNITION TYPE TRANS SNe 809 RELAY R BURNER JUMPER The R B contacts of the low limit circulator control main tain domestic hot water at the desired temperature year round When the thermostat calls for heat the burner starts The circulator also starts if the R W contacts of the low limit circulator control are closed Controls With Adjustable Differential 1 Inserta screwdriver in the centre slot and turn the dial until the right hand indicator B points to the lowest temperature of the cycle 2 Turn the differential adjusting screw C until the left hand indicator D points to the highest temperature of the cycle The left hand indicator points to the temperature at which the contacts open on high limit and low limit applica tions On circulator applications the left hand indica tor points to the temperature at which the circulator will start On combination low limit and circulator applications the left hand indicator points to th
13. t gauche indique la temp rature de mise en marche du circulateur Lorsque la commande sert de circulateur avec limiteur minimum l indicateur du c t gauche indique la temp rature laquelle le limiteur minimum arr tera le br leur tout en permettant au circulateur de fonctionner B INDICATEUR FIXE A FENTE DE R GLAGE C VIS DE R GLAGE DU DIFF RENTIEL D INDICATEUR MOBILE CIRCULATEUR LIMITEUR CIRCULATEUR AVEC MAXIMUM LIMITEUR MINIMUM continuera de fonctionner mais le br leur s arr tera jusqu ce que le limiteur maximum soit nouveau ferm Lorsque la temp rature de la chaudi re est basse entra nant louverture du circuit R W du circulateur avec limiteur minimum alors le br leur reste en marche mais le circulateur s arr te jusqu ce que le circuit R W du circulateur avec limiteur minimum soit nouveau ferm Une fois le thermostat satisfait le circulateur est arr t Le br leur sera aussi arr t si le circuit R B du circulateur avec limiteur minimum est ouvert R GLAGE DE LA COMMANDE Commandes diff rentiel fixe introduire la pointe d un tournevis dans la fente de r glage A Tourner le cadran pour que la temp rature maximale souhait e du cycle se trouve directement sous l indicateur fixe B L indicateur fixe indique la temp rature laquelle les contacts seront ouverts lorsque la commande sert de limiteur
14. tion This control has been accurately calibrated at the factory Any attempt to calibrate this control will void the White Rodgers warranty Convertible controls have a Knockout Plate on back of case secured by Hex Nut on Horizontal models and by Knockout Plug on Vertical models To convert from Horizontal to Vertical 1 Remove control cover Then remove bottom knockout 2 Remove Hex Nut inside control from Well Mounting Stem To loosen hold Hex Nut inside while turning Hex Nut on back of control counterclockwise WHITE RODGERS DIVISION EMERSON ELECTRIC CO 9797 REAVIS RD ST LOUIS MO 63123 314 577 1300 FAX 314 577 1517 9999 HWY 48 MARKHAM ONT L3P 3J3 905 475 4653 FAX 905 475 4625 aN Printed in U S A DESCRIPTION PRECAUTIONS CAUTION To prevent electrical shock and or equipment damage disconnect electric power to system at main fuse or circuit breaker box until installation is complete AWARNING Do not use on circuits exceeding specified voltages Higher voltages will damage control and could cause shock or fire hazard CONVERTIBLE CONTROLS 3 Pull Well Mounting Stem away from case and remove Knockout Plate 4 Swing capillary down through slot into bottom knock out 5 Secure Knockout Plate to back of case by using Knockout Plug provided in envelope 6 Insert Well Mounting Stem into bottom knockout and tighten Hex Nut inside control securely PART