Tripp Lite SmartOnline SU1000XL User's Manual
Contents
1. Model SU1000XL SU2200XL SU3000XL Series AGSU1000DT AGSU2200DT AGSU3000DT Input Voltage Range 80 138 VAC 80 138 VAC 80 138 VAC Output Voltage Nominal 120 VAC 120 VAC 120 VAC Output Capacity VA Watts 1000 800 2200 1600 3000 2400 Battery Runtime Half Full Load Minutes 18 6 18 6 17 6 System Battery Voltage 36 VDC 72 VDC 72 VDC Recommended Dedicated 15 amp 20 amp or 15 amp 30 amp Electrical Circuit Rating Approvals UL cUL NOM UL cUL NOM UL cUL NOM FCC Class B Class A Class A ALL UNITS Input Frequency 50 60 Hz Auto Selecting Output Waveform in Line and Battery Modes Pure Sine Wave Transfer Time 0 ns Maximum Harmonic Distortion with Linear Load 3 Maximum Harmonic Distortion with Linear Load 6 Battery Recharge Time to 80 Capacity 2 4 hours Battery runtime can be extended with addition of optional Tripp Lite External Battery Packs sold separately SU1000XL model uses BP36V13 battery packs SU2200XL and SU3000XL models use BP72V12 2U battery packs External batteries will increase both the battery runtime and the battery recharge time Since this model includes two plug options the amperage of the recommended circuit would change to match the amperage of the plug The output capac ity would also change based on the plug type used SU2200XL includes a 20 amp NEMA 5 20P plug attached to its line cord but also includes a 15 amp NEMA 5 15P plug loose in the box that ca
2. Parpadeando L NEA DERIVACI N Encendidas FALLA 50 Condici n No hay salida debido a un sobrevoltaje en bus y entrada anormal Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico Parpadeando L NEA DERIVACI N Encendidas FALLA 25 Condici n No hay salida debido a un bajo voltaje en bus y entrada anormal Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico Parpadeando L NEA DERIVACI N Encendidas FALLA 100 75 Condici n No hay salida debido a una alta temperatura interna y entrada anormal Revise el UPS para asegurarse de que hay suficiente espacio para permitir la circulaci n de aire cerca de las ranuras de ventilaci n y que el ventilador est funcionando correctamente Reinicie el UPS Si el problema persiste p ngase en contacto conTripp Lite para solicitar servicio t cnico Almacenamiento y servicio Almacenamiento Almacenamiento y servicio continuaci n Servicio Primero apague el sistema UPS presione el interruptor OFF para desconectar la ali mentaci n en las tomas del UPS luego desconecte el cable de alimentaci n de la toma de corri ente Despu s desconecte todos sus equipos para evitar el desgaste innecesario de la bater a Si desea almacenar este sistema UPS por un per odo prolongado recargue completamente las bate
3. Mod le SU2200XL illustr BATT CON DC 72V 39A C Exploitation de base Commutateurs du panneau avant o Commutateur ON TEST MARCHE TEST Le commutateur commande quatre fonctions distinctes du syst me UPS Mise en fonction du syst me UPS Pour allumer le syst me UPS appuyez sur le commutateur et maintenez le enfonc pendant plusieurs secondes jusqu ce que vous entendiez un signal sonore puis rel chez le Le voyant ON LINE ALIMENTATION s allume Autotest du syst me UPS En cours d exploitation en ligne normale appuyez sur le commutateur et maintenez le enfonc jusqu ce que vous entendiez un signal sonore Cette proc dure lance un autotest de la batterie d une dur e de 10 secondes Le syst me UPS passera en mode d exploitation de la batterie les voyants lumineux ON BATT BATTERIE EN FONCTION ET BATT ACTIVE METER INDICATEUR DE CHARGE DE BATTERIE ACTIVE s allument pendant 10 secondes Interruption de l alarme Pour interrompre l alarme du syst me UPS signalant l exploitation en mode de batterie appuyez sur le commutateur et maintenez le enfonc jusqu ce que vous entendiez un signal sonore D marrage froid du syst me UPS Pour utiliser votre systeme UPS comme source d alimentation autonome lorsque l alimentation en c a n est pas disponible c est dire durant une panne de courant appuyez sur le commutateur et maint
4. Entreposage et entretien Sp cifications Entreposage Veuillez d abord teindre votre syst me UPS appuyez sur le commutateur OFF ARR T pour couper l alimentation lectrique au niveau des prises du syst me UPS puis d branchez le cordon d alimentation de la prise murale D branchez ensuite tout le mat riel pour viter d puiser la batterie Si vous envisagez d entreposer votre syst me UPS pour une p riode prolong e rechargez compl tement les batteries tous les trois mois en branchant le syst me une prise de secteur pendant 4 ou 6 heures Si vous laissez les batteries de votre syst me UPS d charg es pendant une p riode de temps extr mement longue elles souffriront d une perte permanente de capacit Entretien Avant d envoyer votre UPS pour r parations suivre ces tapes 1 Relire les directives d installation et de fonctionnement dans ce manuel pour vous assurer que le probl me n a pas pour origine une mauvaise lecture des directives V rifier galement que les disjoncteurs du circuit du syst me UPS n ont pas saut C est la cause la plus courante des demandes de service on peut y rem dier facilement en suivant les directives de remise en marche dans ce manuel 2 Si le probl me persiste ne pas communiquer ou renvoyer l UPS au vendeur la place appeler Tripp Lite au 773 869 1233 Un technicien des r parations vous demandera le num ro de mod le de l UPS son
5. TRIPP LITE POWER PROTECTION 1111 W 35th Street Chicago IL 60609 USA Customer Support 773 869 1234 www tripplite com Ge Printed on Recycled Paper 200408112 93 2280 Owner s Manual SmartOnline Intelligent True On Line Tower UPS Systems e True On Line Operation Pure Sine Wave Output Models SU1000XL SU2200XL amp SU3000XL Important Safety Instructions Quick Installation Optional Installation Basic Operation Troubleshooting Storage and Service Specifications Espa ol 13 Fran ais 24 TRIPP LITE POWER PROTECTION 1111 W 35th Street Chicago IL 60609 USA Customer Support 773 869 1234 www tripplite com Copyright 2004 Tripp Lite All rights reserved SmartOnline is a trademark of Tripp Lite Important Safety Instructions SAVE THESE INSTRUCTIONS This manual contains instructions and warnings that should be followed during the installation operation and storage of all Tripp Lite UPS Systems Failure to heed these warnings will void your warranty UPS Location Warnings nstall your UPS indoors away from excess moisture or heat conductive contaminants dust or direct sunlight For best performance keep the indoor temperature between between 32 F and 104 F 0 C and 40 C Leave adequate space around all sides of the UPS for proper ventilation UPS Connection Warnings Connect your UPS directly to a properly grounded AC power outlet Do not plug
6. VOYANT DEL FAULT D FAILLANCE Ce voyant rouge clignote lorsque le syst me UPS d tecte une d faillance interne surchauffe surtensions etc ou un probl me de c blage dans les prises murales phases invers es absence de mise la terre etc Le syst me UPS ne d tecte les probl mes de c blage que lorsqu il est branch dans une prise de courant mais qu il n est pas allum Si le voyant ne s teint pas apr s avoir red marr le syst me UPS communiquez avec un lectricien pour qu il v rifie la ligne c a Votre syst me UPS est en mesure de d tecter la pr sence de la plupart des probl mes de c blage mais pas tous VOYANT DEL LOAD ACTIVE METER INDICATEUR DE CHARGE ACTIVE Ce voyant vert s allume lorsque le syst me UPS recoit de l alimentation lectrique en courant alternatif pour indiquer que le jeu des quatre voyants double fonction affichent le niveau de charge de votre syst me UPS VOYANT DEL BATT ACTIVE METER CHARGE DE BATTERIE ACTIVE Ce voyant vert s allume lorsque le syst me UPS recoit de l alimentation lectrique de la batterie pour indiquer que le jeu des quatre voyants DEL double fonction affichent le niveau de charge de la batterie de votre syst me UPS Remarque le voyant DEL ON BATT BATTERIE EN FONCTION s allume aussi VOYANT DEL OVERLOAD SURCHARGE Ce voyant rouge s allume constamment pour indiquer que la capacit de votre syst me UPS a t d
7. Si le probl me persiste consultez le service la client le de Tripp Lite Clignotent LINE BYPASS ALIMENTATION VITEMENT Allum s D FAILLANCE FAULT 75 Probl me Aucune sortie en raison d une tension de sortie faible et d une entr e anormale Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite Clignotent LINE BYPASS ALIMENTATION EVITEMENT Allum s FAULT D FAILLANCE 50 Probl me Aucune sortie en raison d une tension de source lev e et d une entr e anormale Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite Clignotent LINE BYPASS ALIMENTATION EVITEMENT Allum s FAULT D FAILLANCE 25 Probl me Aucune sortie en raison d une tension de source basse et d une entr e anormale Red marrez le syst me ups Si le probl me persiste consultez le service la client le de Tripp Lite Clignotent LINE BYPASS ALIMENTATION VITEMENT Allum s FAULT D FAILLANCE 100 75 96 Probl me Aucune sortie en raison d une temp rature interne lev e et d une entr e anormale Assurez vous qu il y a suffisamment d espace autour du syst me UPS pour que l air circule pr s des vents et que le ventilateur fonctionne correctement Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite
8. 1000 800 2200 1600 3000 2400 Temps d exploitation des piles demi charge pleine charge minutes 18 6 18 6 17 6 Tension du syst me de piles 36 VDC 72 VDC 72 VDC Calibre de circuit lectrique sp cialis recommand 15 amp res 20 amp res ou 15 amp res 30 amp res Homologations UL cUL NOM UL cUL NOM UL cUL NOM CFC Classe B Classe A Classe A TOUTES LES UNITES Fr quence d entr e 50 60 Hz auto s lection Forme d onde de sortie en mode trait et en mode pile onde sinusoidale pure Dur e de transfert 0 ns Distorsion harmonique maximale avec charge lin aire lt 3 Distorsion harmonique maximale avec charge lin aire lt 6 Temps de recharge des piles capacit de 80 2 4 heures Le temps di SU1000XL utilise la fois le temps d ion des piles peut tre allong gr ce l ajout de bloc piles externes Tripp Lite optionnels vendus s par ment Le mod le oc piles BP36V13 Les mod les SU2200XL et SU3000XL utilisent les bloc piles BP72V12 2U Les piles externes augmenteront ation et le temps de recharge des piles Puisque ce mod le comprend deux types de fiches l amp rage du circuit recommand changerait pour s agencer celui de la fiche La capacit de sortie changerait galement en fonction du type de fiche utilis Le mod le SU2200XL comprend une fiche NEMA 5 20P de 20 amp res fix e son cor don d alimentation mais comprend aussi une fiche NEMA 5 15P de 15 amp r
9. BYPASS LINE D FAILLANCE EVITEMENT ALIMENTATION 50 Probl me En mode d vitement en raison d une tension de source lev e Red marrez le syst me UPS Si le probl me persiste consultez le Service la client le de Tripp Lite Voyants allum s clignotent et probleme Allum s FAULT BYPASS LINE D FAILLANCE EVITEMENT ALIMENTATION 25 6 Probl me En mode d vitement en raison d une tension de source basse Solution Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite Allum s FAULT BYPASS LINE D FAILLANCE EVITEMENT ALIMENTATION 100 75 96 Probl me En mode d vitement en raison d une temp rature interne lev e Assurez vous qu il y a suffisamment d espace autour du syst me UPS pour que l air circule pr s des vents et que le ventilateur fonctionne correctement Red marrez le syst me UPS Clignotent LINE ALIMENTATION Probl me Entr e anormale Cela indique que la puissance lectrique est trop lev e ou trop basse pour que le syst me UPS puisse fonctionner en mode d vitement Si un convertisseur tombe en panne le syst me UPS ne pourra pas alimenter le mat riel qui y est branch Allum s FAULT D FAILLANCE 100 Clignotent LINE BYPASS ALIMENTATION EVITEMENT Probl me Aucune sortie en raison d une tension de sortie lev e et d une entr e anormale Red marrez le syst me
10. EN jte BEF TE E E re VCCI DEE ESS lt A HE CI ei E zx KE ER BC i FH FETE zHBjeuvcu RENT A APT SPEC T amp 55 SZ Sar Note on Labeling Two symbols are used on the label V AC Voltage DC Voltage Manual del usuario SmartOnline Sistemas UPS inteligentes realmente en l nea para montaje en torre e Operaci n realmente en l nea Salida sinusoidal pura Modelos SU1000XL SU2200XL y SU3000XL LU He NOM Importantes instrucciones de seguridad Instalaci n Operaci n b sica Localizaci n de fallas Almacenamiento y servicio Especificaciones English Francais TRIPP LITE POWER PROTECTION 1111 W 35th Street Chicago IL 60609 EE UU Atenci n al cliente 773 869 1234 www tripplite com O 2004 Tripp Lite Todos los derechos reservados SmartOnline es una marca registrada de Tripp Lite 24 Instalaci n Importantes instrucciones de seguridad A GUARDE ESTAS INSTRUCCIONES Conexi n y encendido Este manual contiene advertencias e instrucciones importantes que deben seguirse durante la instalaci n operaci n y almacenamiento de todos los sistemas UPS de Tripp Lite El Conecte su UPS en un De no cumplirse estas advertencias la garant a ser anulada A tomacorriente Advertencias sobre la colocaci n del UPS Conecte el UPS directamente en una salida Instale el sistema UPS bajo techo alejado
11. en estas sali LII 15 amp 120V NEMA 5 15R 20 amp 120V NEMA L5 20R das est filtrada para proteger los equipos conectados 20 amp 120V i nmm F NEMA 5 20R contra sobretensiones perjudiciales y ruido en la l nea Cada modelo de UPS incluye cierto n mero de recep t culos dispuestos en dos bancos de carga separados claramente identificados en el panel posterior del UPS Usando el software PowerAlert y puertos de comunica ciones RS 232 puede encenderse o apagarse la ali mentaci n a cualquiera de estos bancos en forma remo Lar ta y sin afectar la energ a de los otras salidas Vea las NEMA L5 30R instrucciones del software PowerAlert para m s detalles Interruptor de protecci n del mando del interruptor de entrada Este interruptor reconfigurable evita que una corriente de entrada alta da e el UPS o los aparatos conectados a l Si este interruptor se dis para aseg rese de que el sistema UPS est conectado a una energ a de CA del voltaje adecuado antes de reconfigurar el interruptor empu j ndolo hacia adentro Ventilador El ventilador enfr a los componentes internos del UPS Se encender siempre que haya energ a de l nea presente Conector del paquete de bater as externas Util celo para conectar paquetes de bater as Tripp Lite opcionales si desea tiempo de fun cionamiento adicional P ngase en contacto con el Servicio de aten ci n al cliente de Tripp Lite al 773 869 1234 para obtener el
12. las bater as Interruptor OFF Apagado Este interruptor apaga el suministro de energ a en los recept culos del UPS Presione el interruptor man t ngalo presionado hasta que escuche un sonido y su ltelo El UPS seguir cargando y el ventilador seguir enfriando los componentes internos incluso despu s de haber apagado los recept culos del UPS Para apagar completamente el UPS incluido el cargador desconecte el cable de energ a del UPS despu s de presionar el interruptor OFF Luces indicadoras del panel frontal LED ON LINE Esta luz verde se iluminar y permanecer fija para indicar que el UPS est en operaci n en l nea normal filtrado y resin tetizado del voltaje de la l nea de CA entrante para proporcionar una salida en forma de onda sinusoidal pura Cuando esta luz est encen dida puede controlar el nivel de carga del UPS en los LED LOAD ACTIVE METER LED LINE L nea Esta luz verde se iluminar y permanecer fija para indicar que el voltaje de la l nea de CA proporcionada por el suministro en su toma de energ a es nominal La luz parpadear si el voltaje de la l nea se encuentra fuera del valor nominal ya sea demasiado bajo o demasiado alto No necesita hacer nada cuando el LED parpadea el UPS filtra de manera continua y autom tica la energ a de la l nea de CA para suministrar a su equipo energ a de CA de onda sinusoidal pura sin considerar las condicion
13. leave your UPS batteries discharged for an extended period of time they may suffer permanent loss of capacity Service On FAULT 100 Flashing LINE BYPASS Condition No Output due to High Output Voltage and Abnormal Input Restart the UPS If the problem persists contact Tripp Lite for repairs Flashing LINE BYPASS On FAULT 75 Condition No Output due to Low Output Voltage and Abnormal Input Restart the UPS If the problem persists contact Tripp Lite for repairs Flashing LINE BYPASS On FAULT 50 Condition No Output due to High Bus Voltage and Abnormal Input Restart the UPS If the problem persists contact Tripp Lite for repairs Flashing LINE BYPASS On FAULT 25 Condition No Output due to Low Bus Voltage and Abnormal Input Flashing LINE BYPASS On FAULT 100 75 Condition No Output due to High Internal Temperature and Abnormal Input Restart the UPS If the problem persists contact Tripp Lite for repairs Check the UPS to be sure that there is adequate space for air to circulate near the vents and that the fan is working properly Restart the UPS If the problem persists contact Tripp Lite for repairs Before returning your UPS for service follow these steps 1 Review the installation and operation instructions in this manual to ensure that the service problem does not originate from a misreading of the instructions Also check that the UPS Syste
14. num ro de s rie et sa date d achat et essaiera de r gler le probl me au t l phone 3 Si le probl me n cessite une r paration le technicien vous mettra un num ro d autorisation de retour de mat riel RMA qui est exig e pour une r paration Si vous avez besoin d un emballage le technicien peut vous faire envoyer un emballage appropri Emballer soigneusement l UPS pour viter des dommages pendant l exp dition Ne pas utiliser de billes de styrofoam pour emballer Tout dommage direct indirect sp cial accidentel ou fortuit arriv l UPS pendant le transport Tripp Lite ou un centre de service autoris Tripp Lite est exclu de la garantie Les frais de transport des syst mes UPS envoy s Tripp Lite ou un centre de service autoris Tripp Lite doivent tre pr pay s Inscrire le num ro de RMA sur le paquet Si l UPS est encore couvert par la garantie de deux ans joindre une copie de votre facture d achat Renvoyer l UPS pour r paration par un transporteur assur l adresse que vous a donn e le technicien de service de Tripp Lite La politique de Tripp Lite en est une d am lioration continue Ces sp cifications sont sujettes changement sans pr avis Mod le SU1000XL SU2200XL SU3000XL No s rie AGSU1000DT AGSU2200DT AGSU3000DT Plage de tension d entr e 80 138 VAC 80 138 VAC 80 138 VAC Tension de sortie nominale 120 VAC 120 VAC 120 VAC Capacit de sortie VA Watt
15. C line during normal operation and from battery power C Q during blackouts and severe brownouts Power provided at these outlets is filtered to protect connected equipment 15 amp 120V 20 ampi 20V against damaging surges and line noise Each UPS NEMA 5 15R NEMA 5 20R model includes a select number of receptacles arranged into two separate load banks clearly indicated on the rear panel of the UPS system Using PowerAlert Software and RS 232 communications power at either of these load banks may be turned ON and OFF remotely without affecting the power output at any other recepta cles See PowerAlert Software instructions for details 20 amp 120V 30 amp 120V NEMA L5 20R NEMA L5 30R INPUT BREAKER Input Circuit Breaker Switch This resettable breaker prevents high input current from damaging the UPS or the attached load If this breaker trips make sure your UPS is connected to AC power of the proper voltage before resetting the circuit breaker by pushing the breaker switch in Fan The fan cools the UPS s internal components It is always on when line power is present External Battery Pack Connector Use to connect optional Tripp Lite Battery Packs for additional runtime Contact Tripp Lite Customer Support at 773 869 1234 for the appropriate Tripp Lite battery pack to connect Refer to instructions available with the Battery Pack for complete connection information and safety warnings Basic Operation continued Rear Pa
16. Cualquier da o directo indirecto especial accidental o resultante al UPS producido durante el despacho a Tripp Lite o a un centro autorizado de servicio Tripp Lite no est cubierto por la garant a Los sistemas UPS enviados a Tripp Lite o a alg n centro de servicio autorizado de Tripp Lite deben tener los cargos de transporte prepagados Marque el n mero RMA en la parte externa del paquete embalado Si el UPS est dentro del per odo de garant a de 2 a os adjunte una copia de su recibo de compra Devuelva el UPS para servicio a la direcci n dada por el t cnico de Tripp Lite utilizando un transportista asegurado Especificaciones Tripp Lite tiene una pol tica de mejoramiento continuo Las especificaciones est n sujetas a cambio sin previo aviso Modelo SU1000XL SU2200XL SU3000XL Series AGSU1000DT AGSU2200DT AGSU3000DT Rango de voltaje de entrada 80 138 VCA 80 138 VCA 80 138 VCA Voltaje de salida Nominal 120 VCA 120 VAC 120 VCA Capacidad de salida VA Vatios 1000 800 2200 1600 3000 2400 Tiempo de respaldo de bateria Media Plena carga Minutos 18 6 18 6 17 6 Voltaje de baterias del sistema 36 VCC 72 VCC 72 VCC Capacidad recomendada del circuito el ctrico dedicado 15A 20 Ao 15 A 30A Aprobado por UL cUL NOM UL cUL NOM UL cUL NOM FCC Clase B Clase A Clase A TODAS LAS UNIDADES Frecuencia de entrada 50 60 Hz De selecci n autom tica forma de onda de salida en l nea y mod
17. Lite propose une gamme compl te de cartouches de piles de remplacement R B C pour le syst me ASI Visitez Tripp Lite sur Internet l adresse www tripplite com support battery index cfm afin de trouver les piles de remplacement qui conviennent votre ASI Les batteries du syst me UPS sont recyclables Veuillez consulter les r glements de votre e localit pour les conditions de recyclage ou si vous habitez les Etats Unis composez le POWER PROTECTION 1 800 SAV LEAD pour obtenir plus d information ce sujet Ne jetez pas les batteries au feu Ne reliez que des blocs batteries Tripp Lite de type et de tension appropri s au connecteur de batterie externe Il ne faut jamais brancher ni d brancher des batteries externes pendant que le syst me UPS utilise l alimentation de la batterie Ne faites pas fonctionner le syst me UPS sans batteries English 1111 W 35th Street Chicago IL 60609 USA Service la client le 1 773 869 1234 www tripplite com Tripp Lite 2004 Tous droits r serv s SmartOnline est une marque de commerce de Tripp Lite Installation Installation suite Connexion et d marrage Ell Branchez votre ASI dans une prise de courant lectrique Branchez directement l ASI une prise de courant correctement mise la terre 3 fich es dont le circuit n est pas partag avec une charge lectrique lev e par exemple une unit de climatisation un r frig ra
18. are only needed to extend runtime Adding external batteries will increase recharge time as well as runtime Make sure that each end of the cable is fully inserted into its connector Several small sparks may result during battery connection this is normal SU2200XL shown SU2200XL shown BATT CON DC 72V 39A Basic Operation Front Panel Switches ON TEST Switch This switch controls four separate UPS functions UPS Power ON To turn the UPS on press this switch hold it for several seconds until you hear a beep then release it The ON LINE LED will illuminate UPS Self Test During normal on line operation press this switch and hold it until you hear a beep This initiates a 10 second self test of the battery The UPS will shift to battery power the ON BATT and BATT ACTIVE METER LEDs will illuminate for ten seconds Alarm Silence To silence the UPS on battery alarm press this switch and hold it until you hear a beep UPS Cold Start To use your UPS as a stand alone power source when AC power is unavailable i e during a blackout press this switch and hold it until you hear a beep The UPS will then provide bat tery power to its outlets The ON BATT Indicator Light will be illuminated since your UPS will be operating from battery power OFF Switch This switch turns power OFF at the UPS receptacles Press this switch hold it until y
19. ated and the UPS is in the Bypass mode During normal operation this LED will light briefly when the unit is plugged in but if an internal fault or overload occurs this light will illuminate constantly to show that connected equipment will receive filtered AC utility power but will not receive battery power during a blackout In this case contact Tripp Lite for service FAULT LED This red light will flash when your UPS detects an internal fault overheating overvoltages etc or when it detects a wiring fault in your wall outlet reversed phases missing ground etc The UPS will only detect wiring faults when it is plugged into a utility outlet but not turned ON If the light persists after restarting the UPS contact an electrician to check the AC line Your UPS will identify the presence of most but not all wiring faults LOAD ACTIVE METER LED This green light will illuminate when your UPS is receiving AC power to indicate that the set of four dual function LEDs is displaying the load level of your UPS BATT ACTIVE METER LED This green light will be lit when your UPS is operating from battery power to indicate that the set of four dual function LEDs is displaying the battery charge level of your UPS Note the ON BATT LED will also be illuminated OVERLOAD LED This red light will be lit when your UPS s capaci ty has been exceeded while it is in on line operation The UPS alarm will beep continuously Immediatel
20. bargo no se la toma de corriente se anular la garant a del sistema suministra energ a a las tomas de corriente de CA de su UPS hasta que se ste encienda Si el sistema UPS recibe energ a el ctrica por medio de un generador de CA accionado por motor ste deber proporcionar una salida de corriente limpia y filtrada del tipo uti lizado para computadoras A Enchufe su equipo al sistema UPS Advertencias sobre la conexi n de equipos A kid PY Se muestra SU2200XL No utilice los sistemas UPS de Tripp Lite en equipo para el soporte de la vida humana enis eoo cn d donde un fallo o mal funcionamiento podr a causar anomal as o alterar significativa b bicis ta electro e mente el rendimiento del dispositivo para el soporte de la vida humana SODFECALERLS SL Conecta SSGCITOCOTIGSHUOS O 2 impresoras l ser a las tomas de corriente del UPS No conecte supresores de sobretensi n o cables de extensi n a la salida del sistema UPS Esto podr a dafiar el UPS y anular a la garant a del supresor de sobretensiones y del UPS 50 wj O Lm Advertencias sobre las bater as ElEncienda su sistema UPS ON El sistema UPS no requiere ning n mantenimiento rutinario No abra el UPS por ning n Presione el interruptor ON TEST motivo excepto para el reemplazo de las bater as Esta unidad no contiene partes inter A Ence
21. completamente insertado en su conector Es normal que se produzcan peque as chispas durante la conexi n de las bater as Se muestra SU2200XL Se muestra SU2200XL BATT CON DC 72V 39A Interruptores del panel frontal o Interruptor ON TEST Encendido Prueba Este interruptor con trola cuatro funciones separadas del UPS UPS encendido Para encender el UPS presione el interruptor man t ngalo presionado por varios segundos hasta que escuche un sonido y su ltelo Se encender el LED ON LINE Autoprueba del UPS Durante una operaci n en l nea normal pre sione el interruptor y mant ngalo presionado hasta que escuche un sonido Esto inicia una autoprueba de la bater a que dura 10 segun dos El UPS cambiar a energ a de bater as se iluminar n los LED ON BATT y BATT ACTIVE METER durante diez segundos Silenciar alarma Para silenciar la alarma del UPS en bater a pre sione el interruptor y mant ngalo presionado hasta que escuche un sonido Encendido en fr o del UPS Para usar su UPS como una fuente de energ a aut noma cuando no haya energ a de CA disponible es decir durante un apag n presione este bot n y mant ngalo presionado hasta que escuche un sonido El UPS suministrar entonces energ a de las bater as a sus tomas de corriente La luz indicadora ON BATT se iluminar cuando su UPS est operando con energ a de
22. del calor o la humedad excesivos de los cont tripolar de CA con el tercer polo correcta aminantes conductivos del polvo o de la luz solar directa mente puesto a tierra y que no comparta el Para lograr el mejor rendimiento mantenga la temperatura interior entre 0 C y 40 C circuito con una carga el ctrica pesada como 32 F y 104 F un equipo de aire acondicionado un refriger Mantenga suficiente espacio alrededor del sistema UPS para permitir una ventilaci n ador etc La salida debe tener una capacidad adecuada igual o mayor que la del interruptor autom ti catmuechataliencncta x co del UPS consulte las Especificaciones Il SU1000XL NEMA 5 15 Advertencias sobre la conexi n del UPS P Conecte su sistema UPS directamente a una toma de corriente de CA con una conexi n a Una vez que su UPS est enchufado se encen tierra adecuada No conecte el sistema UPS a s mismo ya que esto lo dafiar der la luz del ventilador y todas las luces indi No modifique los conectores del UPS y no utilice un adaptador que pueda eliminar la cadoras Los LED LINE L nea y LOAD conexi n a tierra del sistema ACTIVE METER Medidor activo de carga se No utilice cables de extensi n para conectar el UPS en la toma de corriente de CA Si se encender n y el UPS emitir un sonido que indi utiliza otro tipo de supresor de sobretensi n que no sea Tripp Lite para conectar el UPS a ca funcionamiento normal Sin em
23. e le syst me UPS envoie un signal en branchant les broches 8 et 5 en parall le Pour teindre le syst me UPS distance il envoie un signal de 5 12 volts sur la broche 3 en utilisant la broche 5 comme masse n gative pendant au moins 3 8 secondes Vous pouvez brancher le syst me UPS la fois un commutateur d arr t d urgence et un ordinateur en utilisant un c ble d arr t d urgence de Tripp Lite non inclus commandez l accessoire no 73 0901 aupr s de Tripp Lite Suivez les directives de branchement fournies avec le c ble d arr t d urgence D pannage D pannage suite Les voyants du panneau de configuration du syst me UPS s allument selon la s quence ci dessous pour indiquer que le syst me UPS ne fonctionne pas normalement Voyants allum s clignotent et probleme Allum s REPLACE BATT REMPLACER LA BATTERIE Probl me Remplacez la batterie Solution Laisser l UPS recharger pendant au moins 12 heures et effectuer un auto test en utilisant le commutateur ON Test comme d crit en page 28 Si le voyant est toujours allum communiquez avec le service la client le de Tripp Lite Allum s BATT LOW ON BATT BATTERIE FAIBLE BATTERIE EN FONCTION Probl me Batterie faible Attendez vous ce que le syst me UPS cesse de fonctionner sous peu Allum s BYPASS LINE LOAD OVERLOAD EVITEMENT ALIMENTATION CHARGE SURCHARGE Probl me En mode d vitement en raison d
24. e constamment et l alarme du syst me UPS met trois signaux sonores si le microprocesseur du syst me UPS d tecte une d faillance de batterie ou si l autotest du syst me UPS choue apr s que vous allumez votre syst me UPS et que la batterie du syst me UPS n est pas compl tement charg e Laisser l UPS recharger pendant au moins 12 heures et effectuer un auto test en utilisant le commutateur ON Test comme d crit en page 28 Si le voyant est toujours allum communiquez avec le service la client le de Tripp Lite Apr s le signal sonore initial le syst me UPS continue de se faire entendre toutes les heures jusqu ce que la d faillance soit corrig e Prises d alimentation c a Ces prises alimentent l quipement branch avec une puissance de sortie sinu soidale partir de la ligne c a pendant le fonctionnement normal et avec les piles pendant les pannes d lectricit et lorsque l clairage est r duit L nergie fournie ces pris 15 amp 120V NEMA 5 15R 20 amp 120V NEMA L5 20R PR 20 amp 120V NEMA 5 20R 30 amp 120V NEMA L5 30R es est filtr e pour prot ger l quipement branch des surtensions et du bruit de ligne pouvant l endommager Chaque mod le d ASI comprend un nombre d termin de prises r parties sur deux bancs d essai distincts claire ment marqu s sur le panneau arri re du syst me ASI l aide du logiciel PowerAlert et des ports de communica t
25. enez le enfonc jusqu ce que vous entendiez un signal sonore Le syst me UPS alimentera ses prises par l interm diaire de sa batterie Le voyant ON BATT BATTERIE EN FONCTION s allume puisque votre syst me UPS est aliment par la batterie Commutateur OFF ARR T Ce commutateur coupe la mise sous tension des prises de courant du syst me UPS Appuyez sur le commutateur jusqu ce que vous entendiez un signal sonore puis rel chez le Le syst me UPS continuera de charger la batterie et le ventilateur continuera de refroidir les composants internes apr s que vous aurez coup la mise sous tension des prises du syst me UPS Pour couper compl tement l alimentation du syst me UPS y compris l alimentation du chargeur d branchez le cordon d alimentation apr s avoir appuy sur le commutateur OFF ARRET Voyants du panneau avant VOYANT DEL ON LINE ALIMENTATION Ce voyant vert s allume constamment pour signaler que le syst me UPS fonctionne normalement en mode d exploitation en ligne en filtrant et en resynth tisant la tension de ligne c a pour fournir une onde sinusoidale de sortie pure Lorsque ce voyant est allum vous pouvez surveiller le niveau de charge de la batterie de votre syst me UPS l aide des voyants DEL LOAD ACTIVE METER INDICATEUR DE CHARGE ACTIVE VOYANT DEL LINE ALIMENTATION Ce voyant vert s allume constamment pour indiquer que la tensi
26. es dans la bo te qui peut tre fix e au cordon d alimentation par un lec tricien qualifi Note sur l tiquetage Deux symboles sont utilis s sur l tiquette V Voltage c a Voltage c c
27. es de baja o alza de voltaje Si esta luz est apagada quiere decir que no hay voltaje de l nea de CA apag n o que hay un voltaje muy alto y que el UPS pro porcionar energ a a los equipos conectados desde la bater a Operaci n basica continuaci n Luces indicadoras del panel frontal continuaci n DVERLOAD REPLACE O ACTIVE METER 5 100 O BATT LOW ON BATT ONLIN LED BYPASS Derivaci n Esta luz amarilla se ilumina para indicar que el inversor de CC CA del UPS se encuentra desactivado y el UPS est en el modo Derivaci n Durante el funcionamiento normal este LED se iluminar brevemente al momento de enchufar la unidad pero en caso de ocurrir una falla o sobrecarga interna la luz per manecer fija para indicar que el equipo conectado recibir energ a el ctrica de CA filtrada pero no la energ a de las bater as durante un apag n En este caso cont ctese con Tripp Lite para obtener servicio t cnico LED FAULT Falla Esta luz roja parpadear cuando su sistema UPS detecte una falla interna sobrecalentamiento sobrevoltajes etc o cuando detecte una falla de cableado en las tomas de corriente fases invertidas ausencia de tierra etc El UPS detectar fallas de cablea do s lo cuando se encuentre conectado a una toma de energ a el ctri ca que no est encendida Si la luz sigue encendida despu s de reini ciar el UPS comun quese con un electrici
28. ic replacement battery for your UPS The UPS batteries are recyclable Refer to local codes for disposal requirements or in the USA only call 1 800 SAV LEAD or 1 800 8 BATTERY 1 800 8 228 8379 or visit www rbrc com for recycling information Do not dispose of the batteries in a fire Do not operate your UPS without batteries Quick Installation Connection and Start Up El Plug your UPS into an electrical outlet Plug the UPS directly into a properly ground ed 3 wire AC outlet that does not share a cir cuit with a heavy electrical load such as an air conditioner refrigerator etc The outlet must have an amp rating equal to or greater than your UPS s input breaker rating see Specifications Note Once your UPS is plugged in the fan and all Indicator Lights will turn ON The LINE and LOAD ACTIVE METER LEDs will illuminate and the UPS will beep to indicate normal operation However power is not supplied to your UPS s AC outlets until the UPS is turned on El Plug your equipment into your UPS Your UPS is designed to support computer equipment only You will overload your UPS if you connect devices with high power demands such as household appliances or laser printers to your UPS s outlets El Turn your UPS ON Press the ON TEST Switch Hold it for several seconds until you hear a beep Release it The ON LINE LED will now light and your UPS will begin providing power to i
29. ion RS 232 l alimentation de l un ou l autre de ces bancs d essai peut tre activ e ou d sactiv e distance sans affecter la tension de sortie de quelque autre prise Consultez les instructions du logiciel PowerAlert pour obtenir plus de d tails Commutateur de disjoncteur du circuit d entr e Ce disjoncteur r enclenchement emp che que du courant d entr e lev endom mage le syst me UPS ainsi que le mat riel qui y est branch Si ce dis joncteur se d clenche assurez vous que votre syst me UPS est branch une prise d alimentation en c a d une tension appropri e avant de r armer le disjoncteur en appuyant sur son commutateur Ventilateur Le ventilateur refroidit les composants internes du sys t me UPS Il est toujours en fonction lorsque l alimentation secteur est pr sente Connecteur pour bloc batterie externe Utilisez le pour relier des blocs batteries Tripp Lite suppl mentaires de mani re augmenter la dur e d ex cution Communiquez avec le service la client le de Tripp Lite au 773 869 1234 pour connaitre le bloc batterie Tripp Lite appropri brancher Consultez le guide de l utilisateur fourni avec le bloc batterie externe pour les instructions compl tes relatives son installation et les pr cautions prendre Panneau arri re suite ACCESSORY Communications x Fente a accessoires Enlevez le petit volet de cette fente pour installer des accessoires op
30. is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference using one or more of the following measures reorient or relocate the receiving antenna increase the sepa ration between the equipment and the receiver connect the equipment into an outlet on a circuit different from that which the receiver is connected con sult the dealer or an experienced radio television technician for help The user must use shielded cables and connectors with this product Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment This device complies with part 15 of the FCC rules Operation is subject to the following 2 conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation The SU1000XL is a Class B product based on the standard of the Voluntary Control Council for Interference VCCI from Information Technology Equipment If this is used near a radio or television receiver in a domestic environment it may cause radio interference Install and use the equipment according to the instruction manual COR
31. m s circuit breaker s are not tripped This is the most common cause of service inquiries which can be easily remedied by following the resetting instructions in this manual 2 If the problem continues do not contact or return the UPS to the dealer Instead call Tripp Lite at 773 869 1233 A service technician will ask for the UPS s model number serial num ber and purchase date and will attempt to correct the problem over the phone 3 If the problem requires service the technician will issue you a Returned Material Authorization RMA number which is required for service If you require packaging the technician can arrange to send you proper packaging Securely pack the UPS to avoid damage during shipping Do not use Styrofoam beads for packaging Any damages direct indirect special incidental or consequential to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty UPS Systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid Mark the RMA number on the outside of the package If the UPS System is within the 2 year warranty period enclose a copy of your sales receipt Return the UPS for service using an insured carrier to the address given to you by the Tripp Lite service technician Specifications The policy of Tripp Lite is one of continuous improvement Specifications are subject to change without notice
32. mputer at once using a Tripp Lite EPO cable not included order accessory 73 0901 from Tripp Lite Follow the connection procedures included with the EPO Cable Troubleshooting The UPS s control panel lights will turn on in the sequences below to signal that the UPS is having operational difficulties Lights On Flashing and Condition On REPLACE BATT Condition Replace Battery Solution Let the UPS system charge for at least 12 hours and perform a self test using the ON Test Switch as described on page 5 If the light continues to stay on contact Tripp Lite for service On BATT LOW ON BATT Condition Battery Low Prepare for imminent UPS shutdown On BYPASS LINE LOAD OVERLOAD Condition On Bypass due to Overload Reduce the load the UPS supports On FAULT Condition Short Circuit Remove the cause of the short circuit from the UPS output Flashing FAULT Condition Wiring Fault Check the utility line for wiring problems such as reversed line and neutral or a missing ground On FAULT REPLACE BATT Condition Battery Voltage too High Restart the UPS If the problem persists contact Tripp Lite for repairs On FAULT REPLACE BATT OVERLOAD Condition EEPROM Error On FAULT BYPASS LINE 100 Condition On Bypass due to High Output Voltage On FAULT BYPASS LINE 75 Condition On Bypass due to Low Output Voltage On FAULT BYPASS LINE 50 Condition On Bypa
33. n i ne Ne pas tenir compte de ces mises en garde annule la garantie Mises en garde relatives l emplacement du systeme UPS nstallez votre syst me UPS l int rieur loin de l humidit de la chaleur excessive des impuret s conductrices de la poussi re et de la lumi re directe du soleil Mod les SU1000XL SU2200XL amp SU3000XL Pour un meilleur rendement maintenez la temp rature ambiante entre 0 C et 40 C i 32 F et 104 F Laissez suffisamment d espace autour du syst me UPS pour maintenir une bonne ventilation US FC NO Mises en garde relatives au raccord du systeme UPS Branchez directement votre syst me UPS une prise de courant alternatif munie d un contact de mise la terre Ne branchez pas votre syst me UPS sur lui m me car ceci Importantes consignes de s curit l endommagera Ne modifiez pas la prise du syst me UPS et n utilisez pas un adaptateur qui rendrait la connexion de mise la terre du syst me inop rante Installation N utilisez pas de rallonges lectriques lors du branchement du syst me UPS une prise c a Votre garantie sera annul e si le branchement s effectue l aide de suppresseurs de surtension autres que ceux fabriqu s par Tripp Lite 1 1 Si votre syst me UPS est aliment par une g n ratrice de courant alternatif celle ci devra Exploitation de base fournir un courant filtr et sans parasites convenant au mat riel informatique Syst mes de tours ASI c
34. n be attached to the line cord by a qualified electrician FCC RADIO TV INTERFERENCE NOTICE FOR CLASS A MODELS Note This equipment has been tested and found to comply with the limits for a Class device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when oper ated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications Operation of this equipment is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The user must use shielded cables and connectors with this product Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment FCC RADIO TV INTERFERENCE NOTICE FOR CLASS B MODELS Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruc tion manual may cause interference to radio communications However there
35. nas No conecte ni desconecte las bater as externas cuando el sistema UPS est operando con bater as No haga funcionar su UPS sin bater as E ED Instalaci n continuaci n Operaci n b sica Este sistema UPS funcionar correctamente sin estas conexiones El Conexi n de puerto serial Utilice el cable serial incluido conecte un puer to serial de su computadora al puerto serial de su UPS Instale en su PC el software PowerAlert incluido en el CD ROM para control de UPS apropiado para su sistema operativo Vea la secci n Comunicaciones en operaci n b sica de esta manual para determi nar c mo monitorear y administrar el sistema UPS a trav s de este puerto El Conexi n del paquete de bater as externas Verifique que las bater as externas que desea conectar tengan el mismo voltaje de la lista que aparece en el conector para bater as del UPS Conecte cualquier extremo del cable de conexi n de bater a proporcionado con el paquete de bater as en el conector para bater as externas del UPS y el otro extremo en el conector de salida de la bater a que se encuentra en el panel posterior del paquete de bater as externas Debido a que su UPS ya posee bater as inter nas las bater as externas son necesarias s lo para prolongar el tiempo de funcionamiento Si agrega bater as externas incrementar el tiem po de recarga as como el tiempo de respaldo Aseg rese de que cada extremo del cable est
36. ndidas DERIVACI N L NEA CARGA SOBRECARGA Condici n En Derivaci n por sobrecarga Reduzca la carga que soporta el UPS Encendidas FALLA Condici n Cortocircuito Retire la causa del cortocircuito de la salida del UPS Parpadeando FALLA Condici n Falla de cableado Revise la l nea de suministro para detectar problemas de cableado como por ejemplo l nea invertida y neutra o ausencia de conexi n a tierra Encendidas FALLA REEMPLAZAR BATER A Condici n Voltaje de la bater a demasiado alto Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico Encendidas FALLA REEMPLAZAR BATER A SOBRECARGA Condici n Error de EEPROM Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico Encendidas FALLA DERIVACI N L NEA 100 Condici n En derivaci n debido a sobrevoltaje de salida Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico Encendidas FALLA DERIVACI N L NEA 75 Condici n En derivaci n debido a bajo voltaje de salida Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar Servicio t cnico Encendidas FALLA DERIVACI N L NEA 50 Condici n En derivaci n debido a sobrevoltaje en bus Reinicie el UPS Si el problema persiste p ngase en con
37. ndido Prueba nas que puedan ser reparadas por el usuario Debido a los riesgos que presentan las bater as en relaci n con los choques el ctricos y Mant ngalo presionado por varios segundos las quemaduras causadas por corriente elevada de corto circuito el personal t cnico hasta que escuche un sonido Se moara capacitado debe observar todas las precauciones pertinentes Apague y desenchufe el Suelte el interruptor Sali sistema UPS antes de reemplazar las bater as Utilice herramientas con asas aisladas y A F lace las bater as con el mismo n mero y tipo de bater as nuevas de plomo cido E E ee reemp y up Pp de corriente Se iluminar el LED ON LINE En l nea selladas No abra las bater as No permita que ning n objeto entre en contacto con los terminales de las bater as Tripp Lite ofrece una l nea completa de cartuchos de reempla zo de bater a para UPS R B C Visite Tripp Lite en la web en www tripplite com support battery index cfm para localizar la bater a de reemplazo espec fica para su UPS Las bater as del sistema UPS son reciclables Consulte el reglamento local para conocer los requerimientos de desecho aplicables o en los EE UU solamente llame al 1 800 SAV LEAD 1 800 728 5323 para recibir informaci n sobre el reciclaje No utilice fuego para desechar las bater as Conecte nicamente paquetes de bater as Tripp Lite del tipo apropiado y del voltaje cor recto en el conector de bater as exter
38. nel continued ACCESSORY Communications Accessory Slot Remove the small cover panel from this slot to use optional accessories to remotely monitor and control your UPS Contact Tripp Lite Customer Support at 773 869 1234 for more information including a list of available SNMP network management and connectivity products TVSS Cover Plate Remove this plate to install optional modem network surge protection modules available for purchase by special arrangement with Tripp Lite SMART DB9 Port Your UPS s DB9 port can be used to monitor and control your UPS using either RS 232 or dry contact protocols It can also be used to connect an emergency power off switch RS 232 communications are very complex but are easy to implement The easiest way to monitor and control the UPS using RS 232 is to connect the UPS to a computer with a DB9 cable and install Tripp Lite s PowerAlert software on the connected computer Dry contact communications are simple but some knowledge of electronics is necessary to configure them The DB9 port s pin assignments are shown in the diagram at the left If the UPS battery is low the UPS sends a signal by bridging pin 1 and pin 5 If utility power fails the UPS sends a signal by bridging pin 8 and pin 5 To shut the UPS down remotely send a 5V to 12V signal on pin 3 using pin 5 as the negative ground for at least 3 8 seconds You may connect your UPS to an EPO switch and a co
39. ntacto en seco son simples pero se necesi ta cierto conocimiento de electr nica para configurarlas Las asigna ciones de las patillas del puerto DB9 se muestran en el diagrama de la izquierda Si la bater a del UPS est baja el UPS env a una se al haciendo puente entre la patilla 1 y la 5 Si el suministro de energ a falla el UPS manda una se al haciendo puente entre la patilla 8 y la 5 Para apagar el UPS en forma remota env e una sefial de 5V a 12V en la patilla 3 usando la patilla 5 como tierra negativo durante al menos 3 8 segundos Puede conectar el UPS a un interruptor EPO y a una computadora a la vez usando un cable EPO Tripp Lite no incluido solicite accesorio N 73 0901 de Tripp Lite Siga los procedimientos de conexi n incluidos con el cable EPO Las luces del panel de control del UPS se encender n en las secuencias descritas a contin uaci n para indicar que el UPS tiene dificultades de funcionamiento Luces Encendidas Parpadeando y condici n Encendidas REEMPLAZAR BATER A Condici n Reemplazar bater a Soluci n Deje que el sistema del UPS se cargue por lo menos 12 horas y realice una autoprueba usando el interruptor de ON Test seg n lo descrito en la p gina 22 Si la luz permanece encendida p ngase en contacto con Tripp Lite para Solicitar servicio t cnico Encendidas BATER A BAJA EN BATER A Condici n Bater a baja Prep rese para un apagado inminente del UPS Ence
40. on de la ligne c a de la prise murale est nominale Il clignote si la tension de ligne se situe l ext rieur de la plage nominale si elle est trop basse ou trop lev e Aucune action ne doit tre prise de votre part si les voyants DEL clignotent le syst me UPS filtre automatiquement et continuellement la ligne c a pour fournir une onde sinusoidale pure en tension c a peu importe les baisses de tension ou les surtensions Si le voyant est teint la tension de la ligne c a n alimente pas le syst me panne de courant ou pr sente une tension extr mement lev e Le syst me UPS alimente alors l quipement partir de la batterie Exploitation de base suite Voyants du panneau avant suite DVERLOAD REPLACE amus BYPASS C AAA ACTIVE METER ACTIVE METER 5 100 O E BATT LOW ON BATT ONLIN VOYANT BYPASS EVITEMENT Ce voyant jaune s allume pour signaler que le convertisseur c c c a est d sactiv et que le syst me UPS est en mode d vitement En cours de fonctionnement normal ce voyant DEL s allume bri vement lorsque l appareil est branch Toutefois si une d faillance interne ou une surcharge se produit il s allume en continu pour indiquer que l quipement branch re oit du courant c a filtr du secteur mais pas l alimentation lectrique de la batterie en cas de panne En pareil cas communiquez avec le service la client le de Tripp Lite
41. onnect es intelligentes e Fonctionnement r el en ligne Puissance de sortie sinuso dale Mises en garde relatives au raccord de l quipement D pannage 32 Ne raccordez pas les syst mes UPS Tripp Lite des appareils de soutien vital si leur dysfonctionnement ou leur d faillance peut causer une panne ou nuire de mani re significative l efficacit de ces dispositifs Entreposage et entretien Ne connectez pas de suppresseurs de surtension ou de rallonges lectriques la prise de votre syst me UPS De tels branchements peuvent l endommager et entrainer une annulation de sa garantie tout comme celle couvrant le suppresseur de surtension Sp cifications Mises en garde relatives la batterie Votre syst me UPS n exige pas d entretien p riodique Ne l ouvrez pas quelle que soit la raison sauf pour remplacer la batterie Aucun composant interne ne peut tre r par par 1 l utilisateur Parce que les batteries posent un risque d lectrocution et de br lure en raison d une intensit en court circuit lev e veuillez observer les pr cautions appropri es D branchez et mettez le syst me UPS hors fonction avant de remplacer les batteries Espa ol 13 Remplacez les par un nombre identique de batteries du m me type batteries au plomb bac herm tique en utilisant des outils munis de poign es isolantes N ouvrez pas les batteries Veillez ce qu aucun objet ne court circuite les bornes des batteries Tripp
42. os de bater a Onda Sinusoidal pura tiempo de transferencia 0 ns distorsi n m xima de arm nicos con carga lineal 396 distorsi n m xima de arm nicos con carga lineal lt 6 tiempo de recarga de bater a al 80 de capacidad 2 4 horas El tiempo de respaldo de la bater a puede extenderse agregando bancos de bater as externas opcionales de Tripp Lite vendidos por separado El modelo SU1000XL usa bancos de bater as BP36V13 Los modelos SU2200XL y SU3000XL usan bancos de bater as BP72V12 2U Las bater as exter nas aumentar n el tiempo de respaldo y de recarga de la bater a Ya que este modelo incluye dos opciones de enchufe la corriente del circuito recomendado puede cambiar para corresponder a la corriente del enchufe La capacidad de salida tambi n cambiar a en funci n del tipo de enchufe usado El modelo SU2200XL tiene un enchufe NEMA 5 20P de 20 amperios conectado a su cord n pero tambi n incluye otro NEMA 5 15P de 15 amperios dentro de la caja el que puede conectarse al cord n por un electricista calificado Nota sobre el rotulado Se usan dos s mbolos en la etiqueta V Voltaje CA Voltaje CC Importantes consignes de s curit CONSERVEZ CES INSTRUCTIONS EN UN LIEU SUR Le pr sent guide contient des instructions et des mises en garde qui doivent tre suivies uide de l utilisateur lors de l installation de l exploitation et de l entreposage de tous les syst mes UPS Tripp Lite S ma rtO
43. ou hear a beep then release it The UPS will continue charging and the fan will continue to cool internal components even after you turn the UPS receptacles off To turn the UPS OFF completely including the charger disconnect the UPS s power cord after pressing the OFF switch Front Panel Indicator Lights ON LINE LED This green light will be lit when the UPS is in normal on line operation filtering and resynthesizing incoming AC line voltage to provide pure sine wave output When this light is illuminated you can monitor the load level of your UPS on the LOAD ACTIVE METER LEDs LINE LED This green light will be lit when the utility supplied AC line voltage at your wall outlet is nominal It will flash if the line voltage or frequency is outside the nominal range either too low or too high No action is required on your part when the LED flashes the UPS continuously and automatically filters AC line power to pro vide your equipment with pure sine wave AC power regardless of brownout or overvoltage conditions If this light is off then AC line voltage is not present blackout or is at an extremely high voltage Basic Operation continued Basic Operation continued Front Panel Indicator Lights continued DVERLOAD REPLACE O BU AN ACTIVE METER 100 O BATT LOW ON BATT BYPASS LED This yellow light will be lit when the UPS s DC AC inverter is deactiv
44. paque te de bater as Tripp Lite adecuado Consulte las instrucciones que vienen con el paquete de bater as para obtener informaci n completa sobre conexi n y advertencias de seguridad Operaci n b sica continuaci n Localizaci n de fallas Panel posterior continuaci n ACCESSORY Comunicaciones Ranura para accesorios Retire el pequefio panel que cubre esta ranura para instalar accesorios opcionales utilizados en el monitoreo y control remoto del sistema UPS P ngase en contacto con el Servicio de atenci n al cliente de Tripp Lite llamando al 773 869 1234 para obtener m s informaci n incluyendo una lista de los productos disponibles de SNMP de administraci n de redes y de conectividad Placa de TVSS Retire esta placa para instalar m dulos de protecci n de sobrevoltaje para m dem red disponibles para compra mediante acuerdo especial con Tripp Lite Puerto DB9 inteligente Puede usarse el puerto DB9 del UPS para monitorear y controlar el UPS usando protocolos RS 232 o de con tacto en seco Puede usarse tambi n para conectar un interruptor de apagado de energ a de emergencia EPO Las comunicaciones de RS 232 son muy complejas pero f ciles de implementar La manera m s f cil de monitorear y controlar el UPS usando RS 232 es conectando ste a una computadora con un cable DB e instalar el software PowerAlert de Tripp Lite en la computa dora conectada Las comunicaciones de co
45. pass e lorsqu il fournit une exploitation en ligne L alarme sonore du syst me UPS retentit continuellement Eliminez imm diatement la surcharge jusqu ce que le voyant et l alarme s teignent Si vous ne supprimez pas imm diatement la surcharge le syst me UPS passera de l exploitation en ligne l exploitation en mode d vitement VOYANT BATT LOW CHARGE FAIBLE Ce voyant jaune s allume lorsque la charge de la batterie du syst me UPS est faible L alarme sonore du syst me UPS retentit jusqu ce que la charge de la batterie soit puis e ou que les batteries soient ad quatement recharg es VOYANT DEL ON BATT BATTERIE EN FONCTION Ce t moin vert s allume constamment pour indiquer que la tension de ligne c a n est pas pr sente et que le syst me UPS alimente votre mat riel l aide de la charge de la batterie Le syst me UPS se fera galement entendre toutes les deux secondes moins qu il soit interrompu l aide du commutateur ON TEST MARCHE TEST Lorsque ce voyant est allum vous pouvez surveiller le niveau de charge de la batterie de votre syst me UPS l aide des voyants DEL BATT ACTIVE METER INDICATEUR DE BATTERIE ACTIVE Exploitation de base suite Exploitation de base suite Voyants du panneau avant suite O AD REPLACE BA BATT Panneau arri re VOYANT DEL REPLACE BATT REMPLACER LA BATTERIE Ce voyant rouge s allum
46. r as del sistema UPS una vez cada tres meses conect ndolo a una l nea de CA que tenga corriente y permiti ndole que cargue sus bater as por un per odo de 4 a 6 horas Si deja las bater as del sistema UPS descargadas por un periodo de tiempo prolongado pueden perder su capacidad en forma permanente Antes de enviar su UPS para que le presten servicio siga los siguientes pasos 1 Verifique las instrucciones de instalaci n y operaci n en este manual para asegurarse que el problema de servicio no sea causado por una mala interpretaci n de las instrucciones Adem s verifique que los interruptores autom ticos del UPS no hayan sido disparados Esta es la causa m s com n de pedidos de servicio que pueden ser solucionados f cilmente siguiendo las instrucciones de restablecimiento en este manual 2 Si el problema contin a no contacte con el distribuidor ni devuelva el UPS En su lugar llame a Tripp Lite al 773 869 1233 Un t cnico de servicio le pedir el modelo n mero de serie y fecha de compra del UPS y tratar de resolver el problema a trav s del tel fono 3 Si el problema requiere servicio el t cnico le emitir un n mero de Autorizaci n de devolu ci n de mercader a RMA necesario para que le presten servicio Si requiere embalaje el t c nico puede hacer arreglos para que le env en el embalaje adecuado Empaque el UPS firme mente para evitar da os durante el despacho No use camas de Styrofoam para embalaje
47. re syst me UPS fonctionnera correctement sans ces connexions El Connexion de port s rie En utilisant le c ble s rie fourni connectez le port s rie de votre ordinateur celui de votre syst me UPS Installez sur votre ordinateur le logiciel de surveillance ASI PowerAlert inclus sur le CD ROM qui convient au syst me d exploitation que vous utilisez Reportez vous la rubrique Communications de la section Exploitation de base du pr sent manuel pour d terminer comment surveiller et g rer le syst me UPS l aide de ce port El Branchement d un bloc batterie externe Assurez vous que les batteries externes que vous reliez correspondent la tension inscrite sur le connecteur de batterie du syst me UPS Branchez l une des deux extr mit s du c ble de connexion fourni avec le bloc batterie dans le connecteur de batterie externe du syst me UPS et l autre extr mit dans le connecteur de sortie de la batterie situ sur le panneau arri re du bloc batterie externe Puisque votre syst me UPS dispose de batteries internes les batteries externes ne sont utiles que pour augmenter la dur e d ex cution L ajout de batteries externes allongera le temps de recharge ainsi que la dur e d ex cution Assurez vous que chaque extr mit du c ble est compl tement ins r e dans son connecteur Il est normal que la connexion du bloc batterie produise de petites tincelles Mod le SU2200XL illustr
48. ss due to High Bus Voltage On FAULT BYPASS LINE 25 Condition On Bypass due to Low Bus Voltage Restart the UPS If the problem persists contact Tripp Lite for repairs Restart the UPS If the problem persists contact Tripp Lite for repairs Restart the UPS If the problem persists contact Tripp Lite for repairs Restart the UPS If the problem persists contact Tripp Lite for repairs Restart the UPS If the problem persists contact Tripp Lite for repairs Troubleshooting continuea Lights On Flashing and Condition On FAULT BYPASS LINE 100 75 Condition On Bypass due to High Internal Temperature Solution Check the UPS to be sure that there is adequate space for air to circulate near the vents and that the fan is working properly Restart the UPS Storage and Service Storage Flashing LINE Condition Input Abnormal This indicates that utility power is too high or low for the UPS to operate in BYPASS mode so if an inverter failure occurs the UPS will deliver no output First turn your UPS OFF press the OFF switch to turn power off at the UPS outlets then disconnect the power cord from the wall outlet Next disconnect all equipment to avoid battery drain If you plan on storing your UPS for an extended period of time fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 6 hours If you
49. sta para revisar la l nea de CA Su UPS identificar la mayor a pero no todas las fallas de cableado LED LOAD ACTIVE METER Medidor activo de carga Esta luz verde se encender cuando su UPS reciba energ a de CA para indicar que el grupo de cuatro luces LED de doble funcionalidad est indicando el nivel de carga de su UPS LED BATT ACTIVE METER Medidor activo de bater a Esta luz verde se encender cuando su UPS funcione en base a la energ a de la bater a para indicar que el grupo de cuatro luces LED de doble funcionalidad est mostrando el nivel de carga de la bater a de su UPS Nota tambi n se encender el LED ON BATT LED OVERLOAD Sobrecarga Esta luz roja se iluminar y per manecer fija para indicar que se excedi la capacidad de su UPS mientras est funcionando en l nea La alarma del UPS emitir un sonido contin uo Retire inmediatamente la sobrecarga hasta que se apague la luz y la alarma En caso de no retirar la sobrecarga inmediatamente el UPS cambiar de operaci n en l nea a operaci n de derivaci n LED BATT LOW Bater a baja Esta luz amarilla se encender cuando el nivel de carga de la bater a de su UPS est bajo La alarma del UPS emitir un sonido hasta que la carga de la bater a se agote completamente o se recarguen las bater as de manera adecuada LED ON BATT En bater a Esta luz verde se iluminar y per manecer fija para indicar que no ha
50. tacto con Tripp Lite para solicitar servicio t cnico Encendidas FALLA DERIVACI N L NEA 25 Condici n En derivaci n debido a bajo voltaje en bus Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico Localizaci n de fallas continuaci n Luces Encendidas Parpadeando y condici Encendidas FALLA DERIVACI N L NEA 100 75 Condici n En derivaci n debido a alta temperatura interna n Soluci n Revise el UPS para asegurarse de que hay suficiente espacio para permitir la circulaci n de aire cerca de las ranuras de ventilaci n y que el ventilador est funcionando correctamente Reinicie el UPS Parpadeando L NEA Condici n Entrada anormal Esto indica que el suministro de energ a es demasiado alto o bajo para que el UPS funcione en mod o DERIVACION de modo que si ocurre una falla del inversor el UPS no entregar energ a de salida Encendidas FALLA 100 g Parpadeando LINEA DERIVACION Condici n No hay salida debido a un sobrevoltaje de salida y entrada anormal Reinicie el UPS Si el problema persiste en contacto con Tripp Lite para solicitar servicio t cnico Parpadeando L NEA DERIVACI N Encendidas FALLA 75 Condici n No hay salida debido a un bajo voltaje de salida y entrada anormal Reinicie el UPS Si el problema persiste p ngase en contacto con Tripp Lite para solicitar servicio t cnico
51. teur etc La prise de courant doit avoir un calibre d in tensit gal ou sup rieur au calibre d entr e du disjoncteur de votre ASI consultez les sp ci fications Une fois le syst me UPS branch le ventilateur et tous les voyants s allument Les voyants LINE ALIMENTATION et LOAD ACTIVE METER INDICATEUR DE CHARGE ACTIVE s allument et le syst me UPS met un signal sonore pour indiquer qu il fonctionne normalement Les prises c a de votre syst me UPS ne sont toutefois pas aliment es en courant tant que le syst me UPS n est pas allum El Branchez votre mat riel dans votre systeme UPS Votre syst me UPS n est congu que pour accepter du mat riel informatique Vous surchargerez votre syst me UPS si vous branchez des appareils lectrom nagers ou des imprimantes laser ses prises de courant El Mettez votre syst me UPS en marche Appuyez sur le commutateur ON TEST MARCHE TEST Maintenez le enfonc pendant plusieurs secondes jusqu ce que vous entendiez un signal sonore Rel chez le Votre syst me UPS commence alimenter ses prises en tension c a Le voyant ON LINE ALIMENTATION s allume Fiche SU1000XL NEMA 5 15 illustr e Mod le PA SU2200XL illustr 50 295 cama SU1000XL illustr Vot
52. the UPS into itself this will damage the UPS Do not modify the UPS s plug and do not use an adapter that would eliminate the UPS s ground connection Do not use extension cords to connect the UPS to an AC outlet Your warranty will be voided if anything other than Tripp Lite surge suppressors are used to connect your UPS to an outlet If the UPS receives power from a motor powered AC generator the generator must provide clean filtered computer grade output Equipment Connection Warnings Do not use Tripp Lite UPS Systems for life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device Battery Warnings Your UPS does not require routine maintenance There are no user serviceable parts inside Do not open your UPS for any reason Since batteries present a risk of electrical shock and burn from high short circuit current observe proper precautions Unplug and turn off the UPS before performing battery replacement Use tools with insulated handles and replace the existing batteries with the same number and type of new batteries sealed lead acid Do not open the batteries Do not short or bridge the battery terminals with any object Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges R B C Visit Tripp Lite on the Web at www tripplite com support battery index cfm to locate the specif
53. tionnels de surveillance et de gestion de votre syst me UPS Communiquez avec le service la client le de Tripp Lite au 773 869 1234 pour plus de d tails incluant une liste des produits SNMP de gestion de r seau et de connectivit offerts Couvercle du bloc TVSS Retirez ce couvercle pour installer les modules de protection contre la surtension pour les modems et les r seaux qui peuvent tre achet s en prenant des dispositions sp ciales avec Tripp Lite Port s rie DB9 intelligent Le port DB9 du syst me UPS peut tre utilis pour surveiller et g rer le syst me UPS l aide des protocoles de communication RS 232 ou de contact sec Il peut galement servir brancher un commutateur d arr t d urgence Les communications par protocoles RS 232 sont tr s complexes mais faciles mettre en oeuvre La fa on la plus simple de surveiller et de g rer le syst me UPS en utilisant le protocole RS 232 est de brancher votre syst me UPS un ordinateur l aide d un c ble DB9 et d installer le logiciel PowerAlert de Tripp Lite sur l ordinateur branch Les communications contact sec sont simples utiliser mais une certaine connaissance de l lectronique est n cessaire pour les configurer Les assignations de broches du port DB9 sont illustr es dans le diagramme de gauche Si la batterie du syst me UPS est faible celui ci envoie un signal en branchant les broches 1 et 5 en parall le Si l alimentation est coup
54. ts AC outlets Note If this is the first time you have plugged in your UPS or if your UPS has been in storage for a prolonged period it will need to charge its batteries for 2 4 hours before it can support connected equip ment in the event of a power failure SU1000XL Plug NEMA 5 15 shown PA SU2200XL shown 50 255 cama SU1000XL Optional Installation The connections are optional Your UPS will function properly without these connections El Serial Port Connection Using the serial cable provided connect the serial port on your computer to the serial port of your UPS Install on your computer the PowerAlert UPS monitoring software pro gram included on CD ROM appropriate for your operating system See Communications in the Basic Operation section of this manual to determine how to monitor and manage your UPS using this port El External Battery Pack Connection Check to ensure that the external batteries you are connecting match the voltage listed on your UPS s battery connector Plug either end of the battery connection cable supplied with the battery pack into the UPS s External Battery Connector and the other end into the Battery Output Connector on the rear panel of the external battery pack Since your UPS has internal batteries external batteries
55. une surcharge R duisez la charge du syst me UPS Allum s FAULT D FAILLANCE Probl me Court circuit Corrigez la cause du court circuit la sortie du syst me UPS Clignotent FAULT D FAILLANCE Probl me Probl mes de c blage V rifiez l alimentation lectrique pour vous assurer de l absence de probl mes de c blage comme une ligne invers e et neutre ou une absence de mise la terre Allum s FAULT REPLACE BATT D FAILLANCE REMPLACER LA BATTERIE Probleme Tension de la batterie trop lev e Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite Allum s FAULT REPLACE BATT OVERLOAD DEFAILLANCE REMPLACER LA BATTERIE SURCHARGE Probl me Erreur de la m moire EEPROM Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite Allum s FAULT BYPASS LINE D FAILLANCE EVITEMENT ALIMENTATION 100 Probl me En mode d vitement en raison d une tension de sortie lev e Red marrez le syst me UPS Si le probl me persiste consultez le Service la client le de Tripp Lite Allum s FAULT BYPASS LINE D FAILLANCE EVITEMENT ALIMENTATION 75 Probl me En mode d vitement en raison d une tension de sortie basse Red marrez le syst me UPS Si le probl me persiste consultez le service la client le de Tripp Lite Allum s FAULT
56. y remove overload until light and alarm go off If you do not immediately remove the overload the UPS will transfer from on line to bypass operation BATT LOW LED This yellow light will be lit when your UPS s battery charge level is low The UPS alarm will beep until either the battery charge is depleted or the batteries are adequately recharged ON BATT LED This green light will be lit when AC line voltage is not present and your UPS is providing your equipment with battery power The UPS will also beep every two seconds unless silenced by the ON TEST Switch When this light is illuminated you can monitor the battery charge level of your UPS on the BATT ACTIVE METER LEDs Front Panel Indicator Lights continuea DAD REPLACE BA REPLACE BATT LED This red light will be lit and the UPS alarm will sound three beeps if your UPS s microprocessor detects a battery fault or if your UPS fails the automatic self test after you turn your UPS ON and the UPS battery is less than fully charged Let the UPS charge for 12 hours then perform a second self test see p 5 for details If the light continues to stay on contact Tripp Lite for service After the initial alarm the UPS will beep once every hour until the problem is corrected Rear Panel AC Receptacles These receptacles provide your con nected equipment with pure sine wave AC output from the Ill A
57. y voltaje en la l nea de CA y que su UPS est suministrando energ a al equipo a trav s de la bater a El UPS emitir un sonido cada dos segundos a menos que lo silencie con el interruptor ON TEST Cuando se prende esta luz puede contro lar el nivel de carga de la bater a del UPS en los LED BATT ACTIVE METER Operaci n b sica continuaci n Luces indicadoras del panel frontal continuaci n DAD REPLACE BA Panel posterior LED REPLACE BATT Reemplazar bateria Esta luz roja se ilu minar y permanecer fija y la alarma del UPS emitir tres sonidos si el microprocesador del UPS detecta una falla en la bater a o si su UPS falla en la autoprueba autom tica despu s de encendido y en caso de que la bater a no est completamente cargada Deje que el sistema del UPS se cargue por lo menos 12 horas y realice una autoprueba usando el interruptor de ON Test seg n lo descrito en la p gina 17 Si la luz permanece encendida p ngase en contacto con Tripp Lite para solicitar servicio t cnico Despu s de la alarma inicial el UPS emitir un sonido cada hora hasta que se solu cione el problema Recept culos de CA Proporcionan a sus equipos IT conectados energia de CA de onda sinusoidal pura toma da de la red durante operaci n normal y tomada de bater as durante fallas del servicio el ctrico y bajas de voltaje severas La energ a proporcionada