Home
        Trane Performance Air Handlers Installation and Maintenance Manual
         Contents
1.              Air handler    basic structure     eee                Air handler    Structural base structure Se    steel curb    _         Dunnage                                     Zi 4 5    CAH SVX01B EN 19    S TRANE     Installation   Mechanical    TCP Flat Concrete Pad    The TCP base for concrete is designed to sit flat on the concrete with full perimeter contact     Concrete pads should be perfectly level  flat  and sized to the minimum exterior base channel  measurements  See Figure 7     Figure 7  Flat concrete pad mount                                                 Air handler  base structure           P    e    Concrete   i a  pad A I g       CAH SVXOIB EN    e TRANE     Installation   Mechanical    TCP Roof Curbs for Large Units with Shipping Splits    CAH SVX01B EN    Larger units with shipping splits may require full width intermediate support  With any raised type  roof support such as curbs or dunnage  provisions must be made to carry the weight of the base  cross members at the sectional splits  Since these unit bases are designed with lifting lugs between  the sections  temporary support must be provided so additional sections can be set down with a  12 inch gap to allow for working room between sections and lug removal The use of field provided  outriggers has proven to be a successful way to accomplish this  as shown in Figure 8     Figure 8  Large units with shipping splits may require intermediate support  Field supplied  outriggers may be a useful too
2.            1TB1 4   24 Vac   GND    Trag dampers are low leak dampers that modulate and measure airflow  Each Traq damper section  is supplied with a factory mounted ventilation control module  VCM  on the interior of the mixing  box  The VCM has an input terminal for power and an output terminal for air velocity  see  Figure 76   A direct digital controller controls the factory mounted and wired actuators     VCM  Transducer  Calibration  The VCM has an auto zero function that recalibrates the  transducer once every minute  When troubleshooting  allow for the recalibration time before  making any measurements     Input Power  The only input the VCM needs is the 24 Vac power connected to terminals 1TB1 5  and 1TB1 6     Output Velocity Signal  The 2 to 10 Vdc linear output signal from the VCM represents air  velocity  This voltage can be converted to represent airflow  cfm or L s  using the formula below   Table 5 and Table 6     In Table 6 the cfm at 10Vdc is a calculated value based on area and peak velocity  In certain  situations  it can be advantageous to raise the velocity of airthrough the remaining Trag dampers  by closing off one or more dampers in the unit  The cfm at 10Vdc can be recalculated based on the  proportion of remaining Trag dampers or by multiplying the remaining area of dampers by peak  velocity                 Table5  Altitude adjustment factors Airflow   k  cfm   10v   5 2  Sea level   1 0 or  volts  2   Elevation  feet  k Airflow   k  L  s   10V   Te
3.            base structure             Concrete  pad    4    Dunnage                      CAH SVXOIB EN    S TRANE    Installation   Mechanical    TCC J oining Sections   Edge to Edge    CAH SVX01B EN    NOTICE   Microbial Growth    The roof curb or foundation must be level and the condensate drain at the proper height for  proper coil drainage and condensate flow  Standing water and wet surfaces inside the    equipment can become an amplification site for microbial growth  mold   which may cause  odors and damage to the equipment and building materials     NOTICE  Level Foundation     A level foundation is critical to proper unit and door alignment  operation  and sealing  Failure to  level and align sections properly can lead to structural damage     Important  Units must be installed level for proper drainage of condensate from the drain pan  and for squareness of the sections during installation  In addition  each section ina  multi section unit must be properly supported    Note  Leveling each section  beginning with the first section  is critical  Failure to level and align  the sections immediately creates greater misalignment or even structural damage  afterward    L The end section must be installed first making sure it s properly aligned with the remainder of   the curb  Anchorthis section securely so the base lugs can be used to pull the next section for  base connections     2  Forunits with curb base  remove shipping blocks  see Figure 21      Figure 21  Shipping 
4.          Check relief Liquid line  Condensing unit valve  2 e  Expansion e  valves e      o  8 B Moisture  Se  5 indicating YANG Access i    t     Bi sight glass port Filter drier  S p access  E rt  SE  ES  Im Distriburtor Manual  ball valve  Access  port Manual ball valve     i  Frostat    control Suction line    Kit with sensor   X13790452010 SEN 01212  Kit with switch   X13100429010 THT 02442    Line Sizing  Properly sizing the liquid line is critical to a successful split system application  The  selected tube diameter must provide at least 5  F  2 7  C  of subcooling at the expansion valve  throughout the operating envelope  Increasing the size of the liquid line will not increase the  available subcooling     Routing  Install the liquid line with a slight slope in the direction of flow so that it can be routed with  the suction line  Minimize tube bends and reducers because these items tend to increase pressure  drop and to reduce subcooling at the expansion valve  Liquid line receivers  other than those that  are factory installed  are not recommended     CAH SVX01B EN    S TRANE     Coil Piping and Connections    Insulation  The liquid line is generally warmer than the surrounding air  so it does not require  insulation  In fact  heat loss from the liquid line improves system capacity because it provides  additional subcooling     Components  Liquid line refrigerant components necessary for a successful job include a filter  drier  access port  solenoid valve  moistur
5.    1000 0 982  2000 0 964 For example  if the VCM on a size 30 air handler at sea level  k 1   3000 0 949 has a 10 volt signal  it would represent 17 335 cfm  4000 0 930  8181 L  s  through the Traq damper  If the voltage were 6 volts   5000 0 914 airflow through the Traq damper would be 8 668 cfm  4091 L  s    6000 0 897  7000 0 876  8000 0 860  9000 0 846  10 000 0 825       CAH SVXOIB EN    81    Table 6  Back or Top Inlet Traq Dampers   Air Mixing and Economizer Section   VCM voltage versus airflow at sea level       Traq Damper Peak Velocity CFM   10VDC  Part Number Size  inches  Quantity Total Area  ft    fpm  Peak Velocity L S   10VDC  DMP01123 13 1 0 9213 2500 2303 1087  DMP01124 16 1 1 3956 2650 3698 1745  DMP01663 20 1 2 1806 2650 5779 2727  DMP01125 24 1 3 1400 2700 8478 4001  DMP01126 28 1 4 2739 2700 11540 5446       Fan Inlet Airflow Measuring System    Figure 77  Piezometer ring airflow A fan inlet airflow measuring system with a piezometer ring is available   measurement on many centrifugal and plenum fans  Each system comes with a  differential pressure transmitter  The piezometer ring is connected to the  LO port of the transmitter and the reference pressure point is connected  to  or actually is  the HI port of the transmitter  See Figure 77        In the absence of a factory provided control system  consult the transmitter manufacturer or the  factory for wiring     Note  Ensure that the transmitter has a separate power source     Transmitter Sizing    The
6.    Fans    The fan and motor assembly are internally isolated  The fan and motor bases are bolted to a  minimum of four spring isolators  The isolators are secured to the fan section support base   Shipping tie down blocks are bolted to the isolators between the fan base and the isolator support  frame     To activate the isolation  remove the shipping tie down blocks  Retain these blocks for use in  adjusting isolators if necessary     Isolator Adjustment    Note  Isolators are pre adjusted and setatthe factory  Follow this procedure only if necessary and  as it applies to the isolators used in this unit  This procedure can and should be performed  by one person to ensure that the proper sequence is followed     Figure 43  Isolator   Isolators are selected for distribution of equipment weight   but may not all compress the same  This procedure  assumes the base surface is level  Isolators are not  intended to be leveling devices     1 Verify that the shipping bolts that hold the fan base in  a fixed position have been removed  See Figure 43     Fan  base            PE P ees Jam  Sh   Si    Se c     a  MAR Put 2  Removethejamnuton top of theisolator adjusting stud    at the first isolator to be adjusted  Check that the  Adjusting shipping block is in place   Shipping   nut Se  tie down 3  Turn the adjusting nut two or three turns only   counterclockwise on each isolator in a sequenced    block  shim       manner  The equipment weight will compress the   spring inside the hous
7.    Pipe Cabinet                Ribbed Butyl tape    Ribbed Butyl tape    Note 1 S   see Note 1  Pipe cabinet wall    Inside corner cap  AHU outdoor roof    DETAIL A  Ribbed Butyl tape    Screw 10 16 x  750 self driller    Pipe cabinet outer roof       Picture frame    mounting chanels  factory assembled to unit    Slots provided to allow  final adjustment of outer roof    Inside corner cap Not  ote     1  Seam to be sealed with three ribbed Butyl tape  prior to attaching inside corner cap with screws   10 16 x  750 self driller      Ribbed Butyl tape   see Note 1     DETAIL B    CAH SVXOIB EN 45    e TRANE     Installation   Mechanical    Duct Connections    All duct connections to the units should be installed in accordance with the standards of the  National Fire Protection Association  NFPA  for selecting and installing of air conditioning and  ventilating systems other than residence type  NFPA 90A   and residence type warm air heating and  air conditioning systems  NFPA 90B      To ensure the highest fan efficiency  duct turns and transitions must be made carefully  minimizing  air friction losses and turbulence  Proper duct work installation by such organizations as SMACNA   Sheet Metal and Air Conditioning Contractors National Association  Inc   should be adhered to     Bottom Opening Duct Installation    L Install gasket to duct flange to ensure air tight seal     2  Install duct into place underneath framed opening in unit base per Figure 40  Refer to factory  curb l
8.   Note  The adjustable block off should always be installed last  next to the access door     6  Close and secure the access door  If the door can be closed without compressing the filter   adjust the block off by loosening its screws and position it to provide an airtight seal     Z  WARNING  Hazardous Chemicals     Cleaning agents can be either acidic or highly alkaline  Handle chemical carefully  Proper  handling should include goggles or face shield  chemical resistant gloves  boots  apron or suit as  required  For personal safety refer to the cleaning agent manufacturer   s Materials Safety Data  Sheet and follow all recommended safe handling practices  Failure to follow all safety  instructions could result in death or serious injury     Z  WARNING   No Step Surface    Do not walk on the sheet metal drain pan  Walking on the drain pan could cause the supporting  metal to collapse  Failure of the drain pan could result in death or serious injury     The condensate drain pan and drain line must be checked to ensure the condensate drains as  designed  This inspection should occur a minimum of every six months or more often as dictated  by operating experience     If evidence of standing water or condensate overflow exists  identify and remedy the cause  immediately  Refer to    Troubleshooting    on page 98 for possible causes and solutions     87    e TRANE    Routine Maintenance    Fans    To clean drain pans    L Disconnect all electrical power to the unit    2  Wearing
9.   When the sheaves are aligned  the straightedge will touch  both sheaves at points A through D  see Figure 75  to confirm the shaft  is parallel  For uneven width sheaves  place a string in the center groove  of both sheaves and pull tight  Adjustthe sheaves and tighten the sheave  set screws to the proper torque given in Table 4     Check Multiple Belts    Tighten the belts slightly and rotate the drive several times     Onmultiple beltdrives  ensuretheforce of deflection is approximately the  same on each belt by pushing each belt in an equal distance at a point  halfway from each sheave  see Figure 75   Ifthis force is notthe same for  each belt  the motor and fan shaft are not parallel  Realign as required   After realignment  tighten the belts again to the standard belt tensioning  specifications  If the force is still not the same for all belts  the belts or  sheaves are worn and must be replaced     unga    Sheave    Table 4  Fan and drive compound torque settings  inches              Screw Size Hex Key Square Head Hex Head Torque  in  Ib   Torque  ft  Ib     1 4 1 8 3 8 7 16 66 90 5 5 7 5  5 16 5 32 1 2 1 2 126 164 10 5 13 7  3 8 3 16 9 16 9 16 228 300 19 0 25 0  7 15 7 32 5 8 5 8 348 450 29 0 37 5  1 2 1 4 3 4 3 4 504 650 42 0 54 2  5 8 5 16 15 16 15 16 1290 1390 107 0 116 0   10 3 32     28 40 2 3 3 3       80    CAH SVXOIB EN    Traq    Dampers    Figure 76  Traq damper terminal connections    Ventilation Control Module        Velocity  2 10 Vdc   GND             
10.   solenoid  valve    liquid line   circuit 1     filter drier    10     Pitch the liquid line slightly   1 inch 10 feet   1 cm 3 m    so the refrigerant drains  toward the evaporator  See Figure 64     Provide one expansion valve per  distributor     Slightly pitch the outlet line from the  suction header toward the suction  riser   that is  1 inch 10 feet  1 cm 3 m  in  the direction of flow  Usethe tube diameter  that matches the suction header  connection     Arrange the suction line so the refrigerant  gas leaving the coil flows downward  past  the lowest suction header outlet  before  turning upward  Use a double elbow  configuration to isolate the thermal  expansion valve bulb from other suction  headers     For horizontal tubing  usethetube diameter  recommended by the condensing unit  manufacturer     For the vertical riser  use the tube diameter  recommended by the condensing unit  manufacturer  Ensure the top of the riser is  higher than the evaporator coil     Pitch the suction line slightly   1 inch   10 feet  1 cm 3 m    so the refrigerant  drains toward the evaporator     Insulate the suction line     ThetopoftheCircuit 1suction riser mustbe  higher than the bottom evaporator coil  Use  the tube diameter recommended by the   condensing unit manufacturer for the riser     The top of the Circuit 2 suction riser must be  higher than the top evaporator coil  Use the  tube diameter recommended by the   condensing unit manufacturer for the riser     67    e TRANE    C
11.  CAH SVX01B EN 39    S TRANE     Installation   Mechanical    TCC Stacking Procedure    L After bottom section of stacked arrangement is in place  ensure top is clean and free of debris     2  Apply two layers of 0 188 inch x 2 inch gasketing around perimeter of top section layout  See  Figure 34     3  Apply two layers of 1 inch x 2 inch tape around perimeter of openings in lower unit roof  See  Figure 34 and Figure 35     Lift upper section into place carefully aligning into proper position  see Figure 35    5  Install 0 250 14 x 0 750 self drilling screws in each hole around upper unit base perimeter   Install flashing at base of top section  see Figure 35 Detail A      Figure 34  Upper base connection to lower unit gasket              Apply two layers of 1 inch x 2 inch  gasketing around all openings in    the lower unit roof   Upper unit    Factory installed  engagement plate Apply  188 inch x 2 inch  gasketing around lower    Lower unit unit perimeter        250   14 x  75 leached self driller  screws in every hole  around upper  unit base perimeter     40 CAH SVXOIB EN    e TRANE    Installation   Mechanical    Figure 35  Stacked assembly    Base    N Flashing    Detail A   Screw 10 16 x  750    Apply two layers of 1 in  x 2 in  gasket  around all openings in the lower  unit roof     PCAP                          Upper unit     250 14 x  750 leached self driller  screws in every hole  around  upper unit base perimeter     Apply 2 layers of  188 x 2 in  gasket  around l
12.  For all other applications   install a single solenoid valve  the   pumpdown  solenoid valve  between the  liquid line filter drier and the sight glass     CAH SVX01B EN    S TRANE     Coil Piping and Connections    Single Circuit Condensing Unit  Evaporator Coil with Four Distributors    Figure 62  Single circuit evaporator coil with four distributors    suction line thermal expansion    valves  TXV   7  8 aaa    v                   ef IR  3   i    pumpdown       solenoid valve  3  4 distributor  suction line  78 thermal expansion  valves  TXV     Wem  trim   solenoid valve  6 5    pumpdown     solenoid valve  3  GN    3 uj  4 distributor    CAH SVX01B EN    Evaporator Coil  with Horizontal Split   Standard  Circuiting             filter drier        Evaporator Coil with  Intertwined Circuiting       filter drier       Pitch the liquid line slightly   1 inch 10 feet   1 cm 3 m    so the refrigerant drains  toward the evaporator  See Figure 62     Provide one expansion valve per distributor     Slightly pitch the outletline from the suction  header toward the suction riser   that is    1 inch 10 feet  1 cm 3 m  in the direction of  flow  Use the tube diameter that matches  the suction header connection       Arrange the suction line so the refrigerant    gas leaving the coil flows downward  past  the lowest suction header outlet  before  turning upward  Use a double elbow  configuration to isolate the thermal  expansion valve bulb from other suction  headers     For horizont
13.  K acca esee e Rr AREE Ir RE ER wd E 83  External Insulating Requirements      84  Routine Maintenance            enn 85  AN cp  PE 86  Throwaway Filters         ccc ren 86  Permanent Filters          res 86   Front Load Filters 2 0 0 0    cette 86   Side Load Filters  2 62 ee eem eee ele eee eS 87   Drain PANS  eene tee ae haw a deed ath d aln pe dor IR Rn emia ake d abd 87  FANS fT  88  Inspecting and Cleaning Fans             000  c cece eee 88   Fan Bearing Lubrication      89  Bearing Set Screw Alignment    89  Motor Bearing Lubrication      90   Fan Motor Inspection           res 90   CONS  C 91  Steam and Water Coils           eee 91  Cleanable Cooling Coils          ccc eee 92  Refrigerant Coils         0 0 0 tte 92   Coil Winterization           ee 93  Chilled Water Coils          nh 93  Cleanable Coils  i i naaa oda dem e nbn e ce Bede Sr IRR dn d 93  Moisture Purge Cycle           tees 93  Internal Insulation    isses rnm eR Ra tex x TEARS 94  Elle te uiu sedere eos ber a e doe Buon Ec Sere arbe had Oe RU e Rie d 96  Multiple Fatis    coiere RE Rr Rhe E eee E s 96  Ultraviolet  UV  Light Maintenance    96  Cleaning the Bulbs            e 96  Replacing the Bulbs           eres 97  Disposal of Bulbs   raam ranana z aaa aaao a ren 97    CAH SVX01B EN    CAH SVX01B EN    Troubleshooting      TRANE    General Information    Use this manual to install  startup  operate  and maintain the Custom Climate Changer    air  handler  Carefully review the procedures discussed in 
14.  Routine Maintenance    Coil Winterization    NOTICE  Coil Freeze up     Properly drain and vent coils when not in use  Trane recommends glycol protection in all  possible freezing applications  Use a glycol approved for use with commercial cooling and  heating systems and copper tube coils  Failure to do so may result in equipment damage     In general  most coil manufacturers recommend the same method to protect coils from  subfreezing temperatures  Primarily  this consists of draining water from the coil before the heating  season and thoroughly blowing the coil out with compressed air  Trane also recommends flushing  the coil with glycol if coils will be exposed to temperatures below 35 degrees  If coils are purchased  from a manufacturer other than Trane  contact that coil manufacturer for recommendations  specific to their product     Install field fitted drains and vents to permit winterization of coils not in use and to assist in  evacuating air from the water system during startup  If draining is questionable because of dirt or  scale deposits inside the coil  fill the coil with glycol before the heating season begins     Note  On many units  there are multiple coils in the coil section  Be sure to winterize all coils in a  given coil section     Chilled Water Coils    Cleanable Coils    Note  Use care in removing header plugs from coils  Over torquing may result in twisted tubes   1 Removethe vent and drain plugs   2  Blow the coil out as completely as possible with
15.  Trane specification requires that the flow meter option have a total accuracy of 5 percent  The  total accuracy is a combination of       how accurately the piezometer ring itself is in sensing airflow    how accurately the transmitter senses the differential pressure      how accurately the controller translates the signal from the transmitter to a differential  pressure     Selecting the proper transmitter is critical in orderto get accurate airflow measurements using the  piezometer ring  How accurately the transmitter senses the differential pressure is dependent on       the pressure range selected    accuracy of the selected transmitter    82 CAH SVXOIB EN    Trane air handlers use a 0 20 inch range transmitter as standard  To sufficiently cover VAV turndown  on the smallest fans with the above range  a transmitter with an accuracy of 0 25 percent  full scale   is used as standard  If a field provided transmitter with a lower accuracy is selected  the range   should be chosen closer to the actual  maximum pressure differential expected for the application     The transmitter outputs a signal that represents the differential pressure which is used to calculate  airflow  To adequately calculate and display the airflow for the smaller fans  ensure that the analog  inputis programmed with enough decimal places to sufficiently represent the pressure differential  being measured  For instance  Rover should be used to increase the number of decimal places  being used  to a ma
16.  Verify with an appropriate voltmeter that all capacitors have discharged  Failure to  disconnect power and discharge capacitors before servicing could result in death or serious  injury     Note  For additional information regarding the safe discharge of capacitors  see  PROD SVBO6A EN or PROD SVBO6A FR    NOTICE  Use Copper Conductors Only     Unit terminals are not designed to accept other types of conductors  Use of aluminum or other  type of wiring may result in galvanic corrosion or overheating  Failure to use copper conductors  may result in equipment damage     If the unit does not include a factory mounted starter  wiring to the unit fan motor must be provided  by the installer and must comply with all national and local electrical codes  The installer must also  furnish a service disconnect switch in compliance with national and local electrical codes     Fan motors require motor overload protective devices that are rated or selected in compliance with  the National Electric Code  NEC  or Canadian Electric Code  Specific unit and motor connection  diagrams are provided on the starter VFD if Trane provided  or refer to the motor nameplate     If wiring directly to the motor  a flexible connection at the motor to permit fan belt adjustment  should be provided  Fractional horsepower motors may be factory connected to a terminal box on  the unit  If this construction is provided  the installer should complete field wiring to this connection  box  For a typical high volt
17.  Washer  563 ID x 1 375 OD    Bolt  500 13 x 3 500 Hex    Figure 28  J oin intemal shipping split frame  Graphic 1 Figure 29  J oin intemal shipping split frame  Graphic 2    AN Da  VN    TIPP  UI n p       IYAN   i      36 CAH SVX01B EN    e TRANE    Installation   Mechanical    TCC Wall Section Assembly  Typical   L Verify external unit squareness   2  To complete the exterior joint  install a bead of caulk full height of side panel joint     3  Over caulk  install 3 16 inch x 1 25 inch ribbed grey butyl the full height of the side panel up to  underside of roof overhang  Leave the paper backing on this tape  sealing the joint does not  require this to be removed  The paper will be facing out towards seam cap     4  Install side seam cap over butyl tape and secure with  10 16 x 0 750 self drilling screw  The  bottom two screws on this seam cap will be larger  74x 20 self drillers with neoprene gasket  see  Figure 30      TCC Indoor Roof Section Assembly  Typical   L Verify external unit squareness     2  Apply the 125 inch x 0 33 inch ribbed butyl tape to the exterior of the roofs covering the seam  of the two adjoining sections  see method sheet      3  Install seam cap over the butyl  uniformly straddling the splits  Secure with the provided  number 10 sheet metal screws  See Figure 30     Figure 30  Install seam cap over the butyl tape    Screw 10 16 x  750 self driller    Screw 10 16 x  750  self driller       Seam cap    Butyl tape    Joint cap    DETAIL A    Screw 10 
18.  brush to remove loose  debris from both sides of the coil     3  Install a block off to prevent spray from going through the coil and into a dry section of the unit  and or system ductwork     4  Mixa high quality coil cleaning detergent with water according to the manufacturer s  instructions     Note  If the detergent is strongly alkaline after mixing  PH 8 5 or higher   it must contain an  inhibitor  Follow the cleaning solution manufacturer s instructions regarding the use of the  product     5  Place the mixed solution in a garden pump up sprayer or high pressure sprayer  If a high  pressure sprayer is to be used       Maintain minimum nozzle spray angle of 15 degrees      Spray perpendicular to the coil face      Keep the nozzle at least 6 inches from the coil      Do not exceed 600 psi    Spray the leaving air side of the coil first  then the entering air side    Thoroughly rinse both sides of the coil and the drain pan with cool  clean water   Repeat steps 6 and 7 as necessary     Q0 0 x 9    Straighten any coil fins damaged during the cleaning process    10  Confirm the drain line is open following the cleaning process    1L Allow the unitto dry thoroughly before putting it back into service   12  Replace all panels and parts and restore electrical power to the unit     13  Be careful any contaminated material does not contact other areas of the unit or building   Properly dispose of all contaminated materials and cleaning solution     92 CAH SVXOIB EN    e TRANE   
19.  compressed air     3  Fill and drain the coil several times with full strength glycol so that it mixes thoroughly with the  water retained in the coil     Drain the coil out as completely as possible     5  To ensure no water remains in the coil  do not replace the vent and drain plugs until the coils  are put back into service     Remove all vent and drain plugs    Allow the water to drain from the coil    Remove the header covers    If tubes are fouled  clean the tubes with a nylon or wire brush     To ensure no water remains in the coil  do not replace the header covers until the coils are put  back into service     UU P DH FH    Note  When the coils are put back into service  use new gaskets  Trane recommends washers be  used under the bolt heads and bolts be evenly tightened to 50 ft Ibs torque     Moisture Purge Cycle    CAH SVX01B EN    By it s very nature  any HVAC unit with a cooling coil serves as a dehumidifier  reducing the  surrounding air s ability to hold water vapor as its temperature falls  This normally doesn t present  a problem when the unit is running  However  when the fan stops  water vapor condenses on the  cold metal surfaces inside the air handler and remains there until the air warms sufficiently to re   evaporate it  This damp  dark environment   though temporary    can encourage the growth of  mold  mildew  and other microbial contaminants     93    e TRANE    Routine Maintenance    Providing a moisture purge cycle 15 to 30 minutes after shutdown
20.  disperses the cold  humid air  inside the air handling system more evenly throughout the building  This four step cycle       Closes the outdoor air dampers      Turns off the cooling coil      Opens any variable air volume terminals connected to the air handler     Operates the supply fan for 10 to 15 minutes     Airmovementdiscourages water condensation and hastens re evaporation of any condensate that  does happen to form  This simple preventative measure effectively combats microbial growth and  curbs moisture related deterioration of air handling components     Intemal Insulation    94    NOTICE  Microbial Growth   Wet interior unit insulation can become an amplification site for microbial growth  mold   which    may cause odors and damage to the equipment and building materials  If there is evidence of  microbial growth on the interior insulation  the insulation should be removed and replaced prior    to operating the system     The process of cooling and dehumidification produces condensate that must be continuously  removed from the air handling unit  The section of the unit from the entering air side of the cooling  coil to the leaving edge of the drain pan is considered to be the    wet    section of the unit  Other  potentially    wet    sections are immediately downstream of a humidifier and or an outside air intake  section     Internal insulation in areas of the unit that are normally considered to be  dry  must also be  periodically inspected to ensure the ins
21.  expansion valve  The expansion valve is the throttling device that meters the  refrigerant into the evaporator coil  Metering too much refrigerant floods the compressor   metering too little elevates the compressor temperature  Choosing the correct size and type of  expansion valve is critical to ensure it will correctly meter refrigerant into the evaporator coil  throughout the entire operating envelope of thesystem  Correct refrigerant distribution into the  coil requires an expansion valve for each distributor     Figure 59  Type F refrigerant coil with packed elbow           CAH SVX01B EN    The thermal expansion valve must be selected   for proper size and capacity  The size of the  Cut here expansion valve should cover the full range of  for piping loadings  Check that the valve will successfully  operate at the lightest load condition  For  improved modulation  choose expansion  valves with balanced port construction and  external equalization     Perforated plate     packed elbow     Cutthe process tube and cap assembly from the  liquid connection as shown in Figure 59 and  install the expansion valve directly to the liquid  connections     Venturi type  distributor       61    e TRANE    Coil Piping and Connections    Suction Lines    62    NOTICE  Valve Damage     Disassemble the thermal expansion valve before completing the brazing connections  If  necessary  wrap the valve in a cool  wet cloth while brazing  Failure to protect the valve from  high temperatures ma
22.  in and on the equipment  which could result in corrosion  damage or wet storage stains     The unit controller and all other electrical electronic components should be stored in conditions of   20  F to 120  F and 5 to 95 percent relative humidity  non condensing  Electrical components are  not moisture tolerant  Factory protective coverings should be removed prior to storage     Long Term Storage    CAH SVX01B EN    For longer periods of storage  allow proper clearance around the unit to perform periodic  inspection and maintenance of the equipment    While the unit is in storage    e Every two weeks  rotate the fan and motor shaft 30 revolutions by hand  Check for free rotation       Every six months  check fan shaft bearings and grease lines  Add grease using a manual grease  gun following the lubrications recommendations in    Fan Bearing Lubrication    on page 89     e Check the motor lubrication  remove and clean grease plugs and check for the presence of  moisture in the grease  If moisture is present  remove the motor and send it to an authorized  repair shop for bearing inspection replacement  If no moisture if present  refer to the motor  manufacturer   s lubrication recommendation for proper lubrication    e TRANE    Pre Installation Requirements    Outdoor Storage Considerations    Outdoor storage is not recommended  however  when outdoor storage is necessary  several things  must be done to prevent damage     Note  Keep the equipment in the original shipping con
23.  leaves the factory  If damage has occurred to the unit during shipment   follow these instructions     Note  Trane is not responsible for shipping damage     L Makespecific notation  describing the damage  on the freight bill  Take photos of the damaged  material if possible     2  Report all claims of shipping damage to the delivering carrier immediately and coordinate  carrier inspection if necessary     Note  Do not attempt to repair the unit without consulting the delivering carrier    3  Notify your Trane sales representative of the damage and arrange for repair    Note  Do not attempt to repair the unit without consulting the Trane sales representative   4  Keep the damaged material in the same location as it was received     Note  Itis the receiver s responsibility to provide reasonable evidence that concealed damage was  not incurred after delivery     Storage Recommendations    General Storage    Air handlers and or field installed accessories that must be stored for a period of time before  installation must be protected from the elements  A controlled indoor environment is  recommended for proper storage     Note  The warranty does not cover damage to the unit or controls due to negligence during  storage     NOTICE  Use Canvas Only     All factory shipping protection should be removed  This wrapping is for transit protection only  and should not be used for jobsite storage  Use only canvas tarps to cover air handlers  Plastic  tarps can cause condensation to form
24.  making any welded flange  or welded elbow type connections     If extended drains and vents are required on water coils  they must be field installed or ordered  from the factory     Pipe coils counterflow to airflow     NOTICE  Connection Leaks     Use a backup wrench when attaching piping to coils with copper headers to prevent damage to  the coil header  Do not use brass connectors because they distort easily and could cause  connection leaks     When attaching the piping to the coil header  make the connection only tight enough to prevent  leaks  Maximum recommended torque is 200 foot pounds     NOTICE  Over Tightening     Do not use teflon based products for any field connections because their high lubricity may  allow connections to be over tightened  resulting in damage to the coil header     Use pipe sealer on all thread connections     NOTICE  Leakage   Properly seal all penetrations in unit casing  Failure to seal penetrations from inner panel to    outer panel may result in unconditioned air entering the unit  and water infiltrating the  insulation  resulting in equipment damage     After completing the piping connections  seal around pipe from inner panel to outer panel     53    e TRANE    Coil Piping and Connections    Drain Pan Trapping    54     N WARNING  No Step Surface     Do not walk on the sheet metal drain pan  Walking on the drain pan could cause the supporting  metal to collapse  Failure of the drain pan could result in death or serious injury     Thr
25.  or realign drive for clearance        Bearing noise    Poor alignment    Failed bearing  Inadequate lubrication    Loosen bearing set screws and realign  see    Bearing Set  Screw Alignment    on page 89    Replace bearing    Replace bearing        Low water coil  capacity    Incorrect airflow    Incorrect water flow  Incorrect water temperature    Coil is piped incorrectly    Dirty fin surface  Incorrect glycol mixture    Check fan operating condition    Inspect the water pumps and valves for proper operation and  check the lines for obstructions    Adjust the chiller or boiler to provide the proper water  temperature    Verify coil piping  see    Coil Piping and Connections    section  on page 53     Clean the fin surface  see    Coils    section on page 91    Verify glycol mixture and adjust if necessary        Low refrigerant coil  capacity    Incorrect airflow    Expansion valve is not operating properly or is sized  incorrectly    Incorrect refrigerant charge  Condensing unit failure    Coil is piped incorrectly    Clogged refrigerant line filter  Failure of suction liquid line components    Dirty fin surface    Fin frosting    Check fan operating condition    Check sensing bulb temperature    Verify valve operation    Verify proper valve size    Verify refrigerant charge and adjust if necessary   Verify condensing unit operation    Verify coil piping  see    Coil Piping and Connections    section  on page 53     Change filter core    Verify component operation   Clean
26.  such as the duct static control signal  to modulate the fan speed     Ultraviolet  UV  Light Maintenance    Z  WARNING  Hazardous Voltage and Exposure to Ultraviolet Radiation     If UV lights are present in this unit  it contains components that emit high intensity ultraviolet   UV C  radiation which can be harmful to unprotected eyes and skin  Disconnect all electrical  power  including remote disconnects before servicing  Follow proper lockout tagout procedures  to ensure the equipment cannot be inadvertently energized  Failure to disconnect power before  servicing could result in death or serious injury     The intensity of the ultraviolet energy emitted from the ultraviolet bulbs is dependent on the  cleanliness and age of the bulb  The surface of the bulb should be kept as clean as possible for  optimum intensity  Depending on the filtration level of the HVAC system and the general hygiene  of the building  periodic cleaning may be necessary  Before attempting any maintenance  procedures  always follow all warnings and cautions as detailed in this maintenance section     Cleaning the Bulbs    96    Note  If bulbs are found to be broken  see the proper warning and cautions below regarding  broken bulbs and hazardous vapors     L Disconnect all electrical power to the unit and the ultraviolet bulbs     2  Wearing soft cloth gloves and safety glasses  usetwo hands and firmly grasp the bulb at each  end     3  Rotate the bulb 90 degrees in either direction and move bulb aw
27.  the appropriate personal protective equipment  remove any standing water   3  Scrape solid matter off of the drain pan   4    Vacuum the drain pan with a vacuum device that uses high efficiency particulate arrestance   HEPA  filters with a minimum efficiency of 99 97 percent at 0 3 micron particle size     5  Thoroughly clean any contaminated area s  with a mild bleach and water solution or an EPA   approved sanitizer specifically designed for HVAC use     6  Immediately rinse the affected surfaces thoroughly with fresh water and a fresh sponge to  prevent potential corrosion of metal surfaces     Allow the unitto dry completely before putting it back into service     Be careful any contaminated material does not contact other areas of the unit or building   Properly dispose of all contaminated materials and cleaning solution      N WARNING  Rotating Components     Disconnect all electric power  including remote disconnects before servicing  Follow proper  lockout  tagout procedures to ensure the equipment can not be inadvertently energized  Secure  drive sheaves to ensure rotor cannot freewheel  Failure to secure drive sheaves or disconnect  power before servicing could result in death or serious injury      N WARNING    Hazardous Voltage     Disconnect all electric power  including remote disconnects before servicing  Follow proper  lockout  tagout procedures to ensure the equipment can not be inadvertently energized  Failure  to disconnect power before servicing could res
28.  the fin surface  see    Coils    section on page 91    Do not use steam to clean refrigerant coils    Verify defrost cycle operation    Verify Frostat operation    Verify refrigerant charge        Low steam coil  capacity    Incorrect airflow   Coil is piped incorrectly  Incorrect steam pressure  Excessive steam superheat    Failure of steam line condensate return components  Boiler failure  Dirty fin surface    Check fan operating condition    Verify coil piping  see    Coil Piping and Connections    section  on page 53     Verify steam pressure and adjust if necessary    Check steam superheat    Steam superheat should not exceed 50  F    Verify component operation   Verify boiler operation   Clean the fin surface  see    Coils    section on page 91         Drain pan is  overflowing    Plugged Drain Line  Unit not level  Improper trap design    Clean drain line  Level unit  Design trap per unit installation instructions       Standing water in  drain pan    Improper trap design  Unit not level  Plugged drain line    Design trap per unit installation instructions  Level unit  Clean drain line       Wet interior insulation    Coil face velocity too high  Improper trap design   Drain pan leaks overflows  Condensation on surfaces    Reduce fan speed   Design trap per unit installation instructions  Repair leaks   Insulate surfaces       Excess dirt in unit    Missing filters  Filter bypass    Replace filters  Reduce filter bypass by ensuring all blockoffs are in place        Mi
29.  tube diameter that matches the suction   header connection     4  The top of the Circuit 1 suction riser must be higher than the bottom evaporator coil  Use the  tube diameter recommended by the condensing unit manufacturer for the riser     5  Arrange the suction line so the refrigerant gas leaving the coil flows downward  past the lowest  suction header outlet  before turning upward     6  Thetop of the Circuit 2 suction riser must be higher than the top evaporator coil  Use the tube  diameter recommended by the condensing unit manufacturer for the riser     7 Pitch the suction lines slightly   1 inch 10 feet  1 cm 3 m    so the refrigerant drains toward the  evaporator     8  Insulate the suction lines     66 CAH SVX01B EN    e TRANE     Coil Piping and Connections    Dual Circuit Condensing Unit  Evaporator Coil with Four Distributors    Figure 64  Dual circuit evaporator coil with four distributors                            suction line   circuit 2     thermal expansion  78 valves  TXV   suction line 5 3 doc  EN   circuit 1  ce   78 3 EL   4    DI  5 3 JS   3  4 distributor  suction lines  thermal expansion  78 aq a valves  TXV   3 Es    E  e i  s KE    pang     3   5 a  5 3  6 6    3    Esch   CR  4 distributor    CAH SVX01B EN    solenoid  valve    Evaporator Coil  with Horizontal Split   Standard  Circuiting         liquid line   circuit 2     liquid line   circuit 1     filter drier    Evaporator Coil with  Intertwined Circuiting          liquid line   circuit 2   
30. 0 0  851 1 500 25 6 38 0 n a n a  1 000 2 500 n a n a 3 3 4 9  2 2 2 4  2 501 4 000 n a n a 2 9 4 3  1 000  2 500 3 6 5 1 4 2 6 2  3V  3VX 2 65 3 65  2 501 4 000 3 0 4 4 3 8 5 6  1 000 2 500 4 9 7 3 5 3 7 9  4 12 6 90  2 501 4 000 4 4 6 6 4 9 7 3  500 1 749 n a n a 10 2 15 2  4 4 6 7 1 750 3 000 n a n a 8 8 13 2  3 001 4 000 n a n a 5 6 8 5  5V  5VX dins 500  1 749 HE 18 9 14 8 22 1    1 750 3 000 11 2 16 7 13 7 20 1  500 1 749 15 5 23 4 17 1 25 5  11 8 16 0  1 750 3 000 14 6 21 8 16 8 25 0  200 850  0 49   12 5 17 0 33 3 n a n a  av 851 1 500 26 8 39 9 n a n a  200 850 39 6 59 2 n a n a  18 0 22 4  851 1 500 35 3 52 7 n a n a  Determine Fan Speed    CAH SVXOIB EN    Fan speed can be determined using a strobe type tachometer  or revolution counter     Check unit vibration if the fan speed is changed more than five percent from the original designed  speed  or if parts such as shafts  fan wheels  bearings  or other drive components are replaced  Do  not exceed the maximum fan speed     Pay particular attention to any vibration  noise  or overheating of the motor and fan bearings   however  note that bearings may run warm during break in     79    Figure 75  Proper drive alignment    Fixed  Sheave          Center line  must coincide       Lines must   gt       be parallel    Straight  Edge       Align Fan and Motor Sheaves    Align the fan and motor sheaves using a straightedge  The straightedge  must be long enough to span the distance between the outside edges of  the sheaves
31. 16 x  750 self driller    Screws  250 14 x 1 00 Hes WSH HD self driller    CAH SVXOIB EN 37    38    e TRANE     Installation   Mechanical    TCC Outdoor Roof Section Assembly  Typical     L J oin two outdoor roof panels together at the seams at the direction of airflow and secure them  in place with 5 16 inch x 3 4 inch bolts and 5 16 lock nuts  Cut the proper length of roof joint strip  to cover the seam between two outdoor roof panels at the direction of airflow   exclude single  outdoor roof panel   See Figure 31      Figure 31  J oin outdoor roof panels at the seams    SCREW  10 24 X  56 SELF DRILLER       2  Join outdoor roof panels together at the seams in the direction perpendicular to airflow and  secure them in place with 5 16 inch x 3 4 inch bolts and 5 16 lock nuts  Install the roof joint strip  to cover the seam between two outdoor roof panels in the perpendicular to airflow direction  of  Use 3 8 inch butyl tape to cover the seam between two outdoor roof panels overhang at the  side the unit  Bend joint strip over roof panel and use two number 10 sheet metal screws  one  in each roof panel  to secure joint strip  Trim the roof joint strip to insure that it does not protrude  more than 1 16 inch beyond outdoor roof overhang  see Figure 32 and Figure 33      CAH SVXOIB EN    e TRANE     Installation   Mechanical    Figure 32  Trim roof joint strip    Si        BUTYL TAPE    NUT   313 18  BOLT   313 18 X 0 750 HEX  DETAIL A    Figure 33  Trim roof joint strip      
32. 18 ga  galv          CAH SVX01B EN    e TRANE     Installation   Mechanical    TCP Base to Interior Wall Section Assembly    Note  Failure to completely compress the gasketing may result in air leakage     L Jointhetwo units and secure with field provided 5 8 inch flat washers and 5 8 inch X 2 1 2 inch  grade 9 bolts though each of the six holes     2  Apply caulk the length of the base between the 2 inch X 2 inch angle on the one base section    and the wall on the adjoining section  See Figure 17 below  Note  Use a polyurethane or  equivalent caulk     3  Secure the 2 inch X 2 inch angle to the adjoining wall with  14 sheet metal crews on 12 inch  centers along the length of the angle and wall     Figure 17  TCP base to interior wall sections         4 in  x 1 4 in  gasket    Secure 2 in  x 2 in  angle to wall  with  14 SM screws at 12 in  centers    Caulk    kaaa  __ i         Interior  wall           Split    Interior  wall    Split Split    Base to Wall Assembly Complete    30 CAH SVX01B EN    e TRANE    Installation   Mechanical    TCP Stacked Unit Assembly  L Install and assemble all lower sections as described in typical assembly   2  Liftfirst piece of upper section into place assuring proper alignment with lower unit     3  Install 10 gauge 12 inch angle clips as shown in Figure 18 and secure with grade 5 self tapping  screws placed 4 inches on center     4  Lift next upper piece into place and secure shipping split with appropriate hardware then  anchor to lower se
33. 2  7 16 20 UNF 45  1 2 13 UNC 69  1 2 20 UNF 83  9 16 12 UNC 99  9 16 18 UNF 118  5 8 11 UNC 150  5 8 18 UNF 176  3 4 10 UNC 254  3 4 16 UNF 301  7 8 9 UNC 358  7 8 14 UNF 422  1 8 UNC 500  1 14 UNF 602  Note  Soft metric conversions are not acceptable for screw and hex sizes   Motor Bearing Lubrication  AN WARNING  Hazardous Voltage     Disconnect all electric power  including remote disconnects before servicing  Follow proper  lockout  tagout procedure to ensure the power cannot be inadvertently energized  Failure to  disconnect power before servicing could result in death or serious injury     Obtain an IOM from the motor manufacturer for the specific motor installed  The motor  manufacturer s recommendations take precedence for all matters related to the start up and    routine maintenance of the motor     Motor grease fittings have been removed from factory installed motors in compliance with UL  regulations  Motor bearings require periodic maintenance throughout their life  Many different  styles of motors come as standard selections  so please obtain the motor IOM and use the    manufacturer recommended grease     Fan Motor Inspection    90    Inspect fan motors periodically for excessive vibration or temperature     CAH SVXOIB EN    e TRANE    Routine Maintenance    Coils    Z  WARNING  Hazardous Chemicals     Coil cleaning agents can be either acidic or highly alkaline  Handle chemical carefully  Proper  handling should include goggles or face shield  chemical resist
34. N y  Y  NUS S     AN 18 ga  trim cap AN                                                                                                                        10 SMS ee d EP  P d  Zip  screw    18 ga  strip            18 ga  trim cap       18 ga  strip     No greater than 6 inch spacing  on all fasteners    18 ga  trim cap                                                                                        28 CAH SVX01B EN    S TRANE    Installation   Mechanical    TCP Indoor Roof Assembly   Multiple Span   Ensure shipping split sections are aligned and pulled together properly   Apply a bead of caulk to full height of wall joint    Apply 3 inch x 1 8 inch adhesive backed foam gasket to inner joining strip   Install inner joining strip using  14 x 15 inch gasketed tec screws     Fit the pre cut hub cap over the joining strip the vertical height of the wall flush with the roof  and secure it to the wall with  8 sheet metal screws     6  Fill the top and bottom openings with caulk as a moisture seal  Screw holes can be pre drilled  with a  29 bit   Apply a bead of caulk over top corner of cap seam   Using  10 sheet metal screws  attach corner seam trip cap as shown in Figure 16        UP WN H    Figure 16  TCP indoor roof assembly   multiple span    6 inch trim cap xul HE  10 sheet metal screw    Cap and Caulk  gasket                         Standing seam       10 ga  galv     14 sheet metal screw  on 10 inch centers                                              Zip screws    
35. S TRANE    Installation   Operation   Maintenance   Custom Climate Changer     Air Handlers       X code   X39640745010       J uly 2010 CAH SVX01B EN      TRANE    Wamings  Cautions and Notices    Wamings  Cautions and Notices  Note that warnings  cautions and notices appear at  appropriate intervals throughoutthis manual  Warnings are provide to alert installing contractors  to potential hazards that could result in personal injury or death  Cautions are designed to alert  personnel to hazardous situations that could result in personal injury  while notices indicate a  situation that may result in equipment or property damage only accidents     Your personal safety and the proper operation of this machine depend upon the strict observance  of these precautions     ATTENTION  Warnings  Cautions and Notices appear at appropriate sections throughout  this literature  Read these carefully     WARNING  Indicates a potentially hazardous situation which  if not avoided  could  result in death or serious injury     CAUTION  Indicates a potentially hazardous situation which  if not avoided  could  resultin minor or moderate injury  It could also be used to alert against unsafe practices     NOTICE  Indicates a situation that may result in equipment or property damage only  accidents           Important  Environmental Concems     Scientific research has shown that certain man made chemicals can affect the earth s naturally  occurring stratospheric ozone layer when released to the atm
36. This gasket must be applied to the full perimeter of the section split on both  sections to be joined     Move the next mating section into alignment with the positioned section  Alignment of sections  must be completed before gasket surfaces meet  The two sections should be within 12 inches  to reduce the amount of dragging required     Remove lifting lugs on mating section as required     Figure 9  Insert supplied bolts through each hole of 9  Pulling sections together on a flat surface can be done by  mating connecting plate  using chain come alongs hooked onto the welded square    E     Connecting  plate    22       tubes located on each side of the shipping split  These square  tubes are designed to fully support the stress of pulling  sections together  Sections should be pulled together until  mating gaskets make contact and factory supplied bolts can  be installed in connecting plate     10  When sections are close enough to allow full threading of the  factory supplied nut onto the bolt  chain come alongs can be  removed  The use of an electric impact gun to tighten bolts in  a sequential manner will allow the additional section to be  pulled into the final position     1L Check overall unit length to assure proper joint compression     Note  Failure to compress the gasketing may result in air  leakage     12  Once the sections are pulled together  install the assembly  hardware as applicable for the walls  roof  and the base as  demonstrated in the following assembl
37. ace and bypass control is used     NOTICE  Coil Condensate     Condensate must flow freely from the coil at all times to prevent coil damage from water  hammer  unequal thermal stresses  freeze up and or corrosion  In all steam coil installations  the  condensate retum connections must be at the low point of the coil  Failure to follow these  instructions may result in equipment damage     Proper steam trap installation is necessary for satisfactory coil performance and service life  For  steam trap installation   L Install the steam trap discharge 12 inches below the condensate return connection  Twelve    inches provides sufficient hydrostatic head pressure to overcome trap losses and ensures  complete condensate removal     a  Usefloatand thermostatic traps with atmospheric pressure gravity condensate return  with  automatic controls  or where the possibility of low pressure supply steam exists   Float and  thermostatic traps are recommended because of gravity drain and continuous discharge  operation      b  Use bucket traps only when the supply steam is not modulated and is 25 psig or higher     57    e TRANE    Coil Piping and Connections    Note  Trane steam coils require a minimum of 2 psi of pressure to ensure even heat distribution   2  Trap each coil separately to prevent holding up condensate in one or more of the coils   3  Install strainers as close as possible to the inlet side of the trap     4  If installing coils in series airflow  control each coil bank ind
38. aced prior    to operating the system     The following areas should be specifically addressed  as applicable     Supply and return water piping connections   Supply and return refrigerant piping connections  Condensate drain lines and connections  Outdoor air intake duct connections   Discharge duct connections   Special requirements for low temperature air systems    CAH SVX01B EN    S TRANE    Routine Maintenance    The following checklist is provided as an abbreviated guide to periodic maintenance  Detailed  procedural information is given after this checklist      N WARNING  Hazardous Service Procedures     The maintenance and troubleshooting procedures recommended in this section of the manual  could result in exposure to electrical  mechanical or other potential safety hazards  Always refer  to the safety wamings provided throughout this manual conceming these procedures  When  possible  disconnect all electrical power including remote disconnect and discharge all energy  storing devices such as capacitors before servicing  Follow proper lockout  tagout procedures to  ensure the power can not be inadvertently energized  When necessary to work with live  electrical components  have a qualified licensed electrician or other individual who has been  trained in handling live electrical components perform these tasks  Failure to follow all of the  recommended safety wamings provided  could result in death or serious injury        WARNING  Rotating Components     Disconnect 
39. aft failure  Under tensioning belts is the primary  cause of premature belt failure  Belts should not squeal at startup  Recheck belt tension after  8 hours  24 hours  and 100 hours of operation and monthly thereafter     Figure 72  Tension drive belt label    gut V BELT DRIVE KIT 1627373  MODULE 0400    PURCHASE ORD  NUMBER B24597 061 H5D073B A  CUSTOMER S KIT    H5D073B A 012 0400   MTR HP   10 0   FAN RPM   1458 CD   9 4 AT 3 00 TRN OPN    TENSION INFO   3 86 LB   0 14 IN   DRIVE S BELTS   B40  MOTOR SHEAVE   2VP75X 1 3 8  MOTOR BUSHING   NONE REQUIRED  FAN SHEAVE   2B5V80  FAN BUSHING   B 1 7 16    Figure 73  Belt tensioner       Proper belt tension is required to ensure maximum bearing and  drive component life and is based on motor horsepower  requirement  A label located on the bearing support on the drive  side of the unit lists all drive parts  the proper belt tension  and  deflection for that tension for the specific drive  Figure 72      If the drive is changed from the original  proper belt tension can be  estimated using Table 3     The correct operation tension for a V belt drive is the lowest tension  at which the belts will not slip under the peak load conditions  It may  be necessary  however  to increase the tension of some drives to  reduce excessive belt flopping or to reduce excessive startup  squealing     Check the fan belt tension at least three times during the first days of    Span Scale  Large O Ring       78    Deflection      operation because the
40. age wiring schematic  see Figure 66     69    e TRANE     rica    Installation   Elect    igh voltage wiring schematic    Ih    Figure 66  Typical                                  CAH SVX01B EN       BE    gees          APP  SAP    MOWC   Emer aupen ANO MEDLL FELD sn TIMOG      E 200 070 SHOWN  SEE WSET  A  FOR OTHER VOLTAGES     mem     CONTACTS   SRVER CADMIUM ONDE   1 0HP  SAMP     12000    TD SEE ze SCHDIATC maa FOR ACTUAL QUANTITY OF TRANSFORMERS      E 122 MG ASSOCHIED PLUG SETS USED WITH UPCH OPTION ONLY           TES crit ue uiu eu ns Saa lal       i   itj PT fii    3  al    ah ji  ii EY    LI  fli d d  SH bh    A WARNING    HAZARDOUS Y VOLTAGE     70    S TRANE     Installation   Electrical    NOTICE  Penetration Leaks   Properly seal all penetrations in unit casing  Failure to seal penetrations from inner panel to    outer panel may result in unconditioned air entering the unit  and water infiltrating the  insulation  resulting in equipment damage     Figure 67  Transfo plate Figure 68  EE eg Control Figure 69  ue ce drive       All units with starters or variable frequency drives  VFDs  that have direct digital controllers  DDCs   are provided with line voltage to 120 Vac power transformers  see Figure 67  with power 120 Vac  to 24 Vac control transformers  see Figure 68   Figure 69 shows a typical VFD power box     To provide field wiring to units with DDC or low limit controls     e IfVFDorstarteris notfactory mounted  provide 120 Vac power to a transformer in th
41. ains  or slings  may not be of the same length  Adjust as necessary for even unit lift  Other lifting  arrangements may cause equipment or property only damage  Failure to properly lift unit could  result in death or serious injury  See details below      N WARNING  Heavy Objects     Always place  assemble  and suspend sections  subassemblies one at a time  Do not lift units in  windy conditions  Do not raise units overhead with personnel below unit  Failure to follow these  instructions could result in death  serious injury  or equipment damage     WARNING    Z  WARNING   Improper Unit Lift    Test lift unit approximately 24 inches to verify proper center of gravity lift point  To avoid  dropping of unit  reposition lifting point if unit is not level  Failure to properly lift unit could  result in death or serious injury or possible equipment or property only damage     NOTICE  Equipment Damage     Do not use a fork lift on air handlers or subassemblies  Improper use of fork lifts on units may  result in equipment damage  Trane is not responsible for equipment damage resulting from  improper forklifting practices     Preparation of the roof curb or pier mount and roof openings should be completed before lifting  unit to the roof  Per job requirements  air handlers will ship as a complete assembly or in sections   Tranerecommends thatthe contractor use spreader bars and slings to rig units and sub assemblies   sections      CAH SVX01B EN 15    e TRANE   Installation   Mechani
42. al tubing  usethetube diameter  recommended by the condensing unit  manufacturer     For the vertical riser  use the tube diameter  recommended by the condensing unit  manufacturer  Ensure the top of the riser is  higher than the evaporator coil     Pitch thesuction line slightly   1 inch 10 feet   1 cm 3 m    so the refrigerant drains  toward the evaporator     Insulate the suction line     Only use a  trim  solenoid valve for  constant volume  humidity sensitive  applications  For all other applications   install a single solenoid valve  the   pumpdown  solenoid valve  between the  liquid line filter drier and the sight glass     65    e TRANE    Coil Piping and Connections    Dual Circuit Condensing Unit  Evaporator Coil with Two Distributors     Figure 63  Dual circuit evaporator coil with two distributors                    suction line Evaporator Coil   circuit 2  with Horizontal Split  78 RERUM   liquid line    Standard  Circuiting         circuit 2   j C   H distrib solenoid  suction line      tsiributor valve  circuit 1   circuit 1  3  78 5 SO   liquid line         circuit 1   4 j    thermal filter drier  E expansion  3 valve  TXV        L Pitch the liquid lines slightly   1 inch 10 feet  1 cm 3 m    so the refrigerant drains toward the  evaporator  See Figure 63     2  Provide one expansion valve per distributor     Slightly pitch the outlet line from the suction header toward the suction riser   that is  1 inch   10 feet  1 cm 3 m  in the direction of flow  Use the
43. all electric power  including remote disconnects before servicing  Follow proper  lockout  tagout procedures to ensure the power can not be inadvertently energized  Secure  drive sheaves to ensure rotor cannot freewheel  Failure to secure drive sheaves or disconnect  power before servicing could result in death or serious injury     Table 7  Routine maintenance checklist       Frequency    Maintenance       After 48 hours  of operation    Belts have acquired their permanent set  Readjust but do not overtighten  See  Tension the Fan Belt  on page 78 for more  information           Every week Observe unit weekly for any change in running condition and unusual noise     Clean or replace air filters if clogged or dirty  coat permanent filters with oil after cleaning  and  change bag filters when  pressure drop is 1 in  wg  See  Air Filters  on page 86 for more information     Relubricate fan bearings if necessary  See  Fan Bearing Lubrication  on page 89 for more information   Every month   Check and adjust fan belt tension        Every three to  six months    Check fan bearing grease line connections  Lines should be tight to the bearings    Check bearing and motor bracket bolt torque and bearing setscrew torque    Align fan and motor sheaves  Tighten sheave set screws to the proper torque  See  Align Fan and Motor Sheaves  on  page 80 for more information    Inspect and clean drain pans  See the  Drain Pans  section on page 87 for more information    Tighten electrical connecti
44. am             10 ga  galv           14 sheet metal screw  on 10 inch centers                                           Zip screws    18 ga  galv    e e       Apply a bead of caulk to the seam the full length that roof cap will cover    Apply 3 inch x 1 8 inch adhesive backed neoprene gasket to underside of roof cap   Install roof cap using  10 sheet metal screws in pre punched holes    Apply a bead of caulk over the butt joint where roof caps meet    10  Install roof cap trim piece at joint of each roof cap using  10 sheet metal screws     om x 9    CAH SVXOIB EN    e TRANE     Installation   Mechanical    TCP Indoor Roof Section Assembly  Typical     Ensure shipping split sections are aligned and pulled together properly   Apply a bead of caulk to full height of wall joint    Apply 3 inch x 1 8 inch adhesive backed foam gasket to inner joining strip   Install inner joining strip using  14 x 15 inch gasketed tec screws     Fit the pre cut hub cap over the joining strip the vertical height of the wall flush with the roof  and secure it to the wall with  8 sheet metal screws     6  Fill the top and bottom openings with caulk as a moisture seal  Screw holes can be pre drilled  with a  29 bit     7 Apply a bead of caulk over top corner of cap seam     UU BA WN H    8  Using  10 sheet metal screws  attach corner seam trip cap as shown in Figure 15     Figure 15  TCP indoor wall and roof assembly   trim cap                      18 ga  strip      Interior  Gasket     of unit     TI
45. amely eyes and skin  To reduce the potential  for inadvertent exposure to the lights by operating and maintenance personnel  electrical  interlocks that automatically disconnect power to the lights are provided at all unit entry points to  equipment where lights are located     Z  WARNING  Equipment Damage From Ultraviolet  UV  Lights     Trane does not recommend field installation of ultraviolet lights in its air handling equipment for  the intended purpose of improving indoor air quality  High intensity   C band ultraviolet light is known to severely damage polymer  plastic  materials and poses a  personal safety risk to anyone exposed to the light without proper personal protective  equipment  could cause damage to eyes and skin   Polymer materials commonly found in HVAC  equipment that may be susceptible include insulation on electrical wiring  fan belts  thermal  insulation  various fasteners and bushings  Degradation of these materials can result in serious  damage to the equipment     Trane accepts no responsibility for the performance or operation of our air handling equipment  in which ultraviolet devices were installed outside of the Trane factory     e TRANE     Table of Contents    General Information      8  Operating Environment    8  Unit Description      8  Factory Mounted Controls         0 0 0  ccc ccc eee n 9  lg ME PPP 9   Pre Installation Requirements      10  Receiving Checker  10   Assembly Hardware      10  Resolving Shipping Damage    11  Storage Reco
46. an be pre drilled with a  29 bit     Interior Wall and Roof J oint Assembly  Typical    1 See Figure 12  Ensure shipping split sections are aligned and pulled together properly   2  Pre drill interior joining strip screw holes using  29 drill bit    3  Apply a bead of caulkthe full height of interior wall joint    4  Install joining strips using  10 sheet metal screws     Figure 12  Wall section assembly     8 x 1 in  Phillips zip screw  2 3 4 in  wide joining strip    LIZ    Add caulking before 4 in  x 1 4 in  gasket    installing J strip 6  wa                                                                                                                                                             Wall panel section split    3 in  x 1 8 in  neoprene gasket is sms    applied to metal joining strip   Apply gasket to metal strip 4    72 2 3 4 in  wide joining strip    before installation      8 x 1 in  Phillips zip screw               Trim cap    i E   10 x 1 in  self tapping screw    Add caulking after    quM J strip    iL La                                                                                                                               CAH SVXOIB EN 25    e TRANE     Installation   Mechanical    TCP Outdoor Roof Assembly   Single Span  L Ensure shipping split sections are aligned and pulled together properly  See Figure 13     2  Adda bead of caulk along the length of the roof seams  Install the pre cut   cap over the seam  and secure with  14 sheet metal screws 
47. ant gloves  boots  apron or suit as  required  For personal safety refer to the cleaning agent manufacturer   s Materials Safety Data  Sheet and follow all recommended safe handling practices  Failure to follow all safety  instructions could result in death or serious injury     All coils should be kept clean to maintain maximum performance     Steam and Water Coils    To clean steam and water coils   L Disconnect all electrical power to the unit     2  Wearing the appropriate personal protective equipment  use a soft brush to remove loose  debris from both sides of the coil     3  Install a block off to prevent spray from going through the coil and into a dry section of the unit  and or system ductwork     4  Mixa high quality coil cleaning detergent with water according to the manufacturer s  instructions     Note  If the detergent is strongly alkaline after mixing  PH 8 5 or higher   it must contain an  inhibitor  Follow the cleaning solution manufacturer s instructions regarding the use of the  product     5  Placethe mixed solution in a garden pump up sprayer or high pressure sprayer  If a high  pressure sprayer is to be used     a  Maintain minimum nozzle spray angle of 15 degrees    b  Spray perpendicular to the coil face    c  Keep the nozzle at least 6 inches from the coil    d  Do not exceed 600 psi    Spray the leaving air side of the coil first  then the entering air side    Thoroughly rinse both sides of the coil and the drain pan with cool  clean water   Repeat 
48. aring failure     The grease used in electric motor bearings is usually not compatible with the grease used in fan  bearings  Never mix the two grease types  See Table 8 for compatible greases and Table 9 for  maximum grease capacity     Note  Lubricate the bearing according to the motor manufacturer s recommendations and use the  manufacturer recommended grease       Fan bearings without lubrication lines are sealed bearings  Re lubrication is not required       Fanbearings equipped with lubrication lines should be lubricated with a lithium based grease  that conforms to NLGI No  2 for consistency                 Table8  Compatible Greases Table 9  Fan bearing maximum grease capacity  Type Shaft size  inches  Capacity  fluid ounce   Texaco Multi Fak 2 1 2   3 4 1 7   Shell Alvania 2 7 8   13 16 3 8   Mobil 532 11 4 11 2 5 8   Chevron Dura Lith 2 111 16  1 15 16 7 8   Exxon Beacon 2 27 16 11 4   Keystone 84H 2 1 2   2 15 16 2          Refer to Table 10 for minimum torque of motor mounting and bearings bolts     Figure 78  Bearing set screw alignment  Bearing Set Screw Alignment  Align bearing set screws as illustrated in Figure 78     Table 10 provides bearing set screw torque  measurements        89    e TRANE    Routine Maintenance    Table 10  Minimum hex head bolt torque in Ib  ft   Grade 5 bolts                          Size  inches  Thread Designation Minimum Torque  1 4 20 UNC 6  1 4 28 UNF 7  65 16 18 UNC 14  5 16 24 UNF 16  3 8 16 UNC 24  3 8 24 UNF 28  7 16 14 UNC 4
49. aves or disconnect  power before servicing could result in death or serious injury     Throwaway Filters    To replace throwaway filters  install new filters with the directional arrows pointing in the direction  of airflow     Note  Bag and cartridge filters must have an airtight seal to prevent air bypass  If using other than  Trane supplied filters  apply foam gasketing to the vertical edges of the filter     Permanent Filters    To clean permanent filters    L Disconnect all electrical power to the unit    Wash the filter under a stream of water to remove dirt and lint   Remove oil from the filter with a wash of mild alkali solution   Rinse the filter in clean  hot water and allow to dry     Coat both sides of the filter by immersing or spraying it with Air Maze Filter Kote W or an  equivalent     6  Allow to drain and dry for about 12 hours   7 Reinstall the filter     Note  It may be preferable to keep extra  clean filters to replace the dirty filters to minimize unit  downtime for filter maintenance     uk WN    Front Load Filters    86    Most filters in custom units are installed in unitary sheet metal frames  Filters are secured with a  metal clip  There are several different styles     To install filters    Disconnect power to the unit    Open or remove the filter clip    Remove the filter from the rack    Install new filters with the directional arrows pointing in the direction of airflow   Secure the filter using the appropriate clip for each filter     The filte
50. ay from the fixture and out of  unit     4  Wipe down each bulb with a clean cloth and alcohol  Avoid touching the bulb with bare hands  as skin oils can accelerate future glass soiling and degrade the bulb performance     5  Carefully return the bulb to the fixture and rotate it 90 degrees in either direction until itis firmly  secured     6  Close and latch all unit panels and reenergize power to the lights     CAH SVXOIB EN    e TRANE    Routine Maintenance    Replacing the Bulbs    Z  WARNING  Hazardous Vapors     If large numbers of UV bulbs are broken  an appropriate respirator should be considered to  prevent inhalation of mercury vapors  Failure to use a respirator could result in death or serious    injury    N CAUTION  Broken Glass     Bulbs are fragile and can be easily broken  Always use gloves and eye protection when handling  these bulbs  Failure to handle bulbs properly may result in minor to moderate injury  Refer to the  MSDS sheet from the bulb manufacturer for additional safety information     Ultraviolet bulbs should be replaced annually if operated continuously or after 9 000 hours of use  if operated intermittently  Replacement bulbs must be the specific size and wattage as originally  supplied from the factory     Note  Although the lights may continue to generate a characteristic blue glow beyond 9 000  operating hours  the ultraviolet radiation emitted by the bulbs degrades over time and will  no longer provide the intended benefit     Disconnect powe
51. ayout provided with unit submittals for duct size and location     Figure 40  Field supplied duct connection to AHU bottom supply  retum air opening    Bottom  supply return    Trane NYA    base  typical     E Trane AHU __  Field supplied base  typical     rigid duct       Field supplied  rigid duct    46 CAH SVX01B EN    S TRANE    Installation   Mechanical    3  Bottom of unit base elevation is AG inch lower than edge of duct opening in bottom of unit   During unit installation on roof curb  either raisefield provided duct per Option A  see Figure 41   or add additional gasket material to compensate for the AG inch offset per Option B  see  Figure 42      Figure 41  Field supplied duct connection option details   Figure 42  Field supplied duct connection option details    Option A Option B           Supply opening  in floor            Supply opening  in floor Edge of    supply  opening    Edge of  supply  opening       Gasket x    Additional       1 2 in  gasket Bottom  of unit  base  elevation      Bottom of  unit base  elevation    Building roofing  and structure  may vary per job         Building         Option A Option B    roofing  Additional 1 2 inch of and structure Additional 1 2 inch  duct length option may vary per job of gasket material  Not to scale  option  Not to scale     Note  Bottom of unit base elevation is 1 2 inch lower than edge of duct Note  Bottom of unit base elevation is 1 2 inch lower than edge of duct  opening in bottom of unit  During unit instal
52. block removal        Remove shipping blocks    33    S TRANE     Installation   Mechanical    3  Install 3 16 inch x 125 inch ribbed grey butyl tape to bottom rail  each side wall  and top rail   Remove paper backing from butyl tape  This will ensure the module to module joint is water  tight along the bottom  See Figure 22 and Figure 23     Figure 22  Apply butyl tape to shipping splits       Butyl tape                      Butyl tape                                  34 CAH SVXOLB EN    e TRANE     Installation   Mechanical    Figure 24  Remove lifting lug bolts 4  Lift next section into place sitting it as close to the  previous section as possible     5  Remove lifting lug bolts  See Figure 24     Using a come along on each side in unison  pull second  section securely to first section  Insert all 5 8 inch  threaded rod through base lugs and tighten nuts to pull  sections firmly together for final fit  See Figure 25 and  Figure 26 for assembly details     Remove bottom hardware    Figure 25  Insert field provided threaded rods       Rod threaded  62 11x13 38  THD    Nut 62 11    CAH SVX01B EN 35    e TRANE     Installation   Mechanical    TCC Intemal Shipping Split Frame Assembly  Typical     L After exterior shipping split has been sealed  interior 2 5 inch x 2 5 inch angles can be bolted  together using supplied hardware  see Figure 27  Figure 28  and Figure 29      Figure 27  J oin intemal shipping split frame         Washer  563 ID x 1 375 OD    Nut  500 13 Hex Mach   
53. cal  Lifting Considerations    Figure 2  Recommended  attachment to lifting lugs              16    Before lifting the unit  estimate the approximate center of gravity for lifting  safety  Because of the placement of internal components  the unit weight may  be unevenly distributed  with more weight in the coil and fan areas  Refer to  the unit submittals for section weights  Test the unit for proper balance and  rigging before lifting     Always assemble unit at the installation site  Never bolt sections together  before rigging     Always rig subassemblies or sections as they ship from the factory  See the  unit submittal drawings for correct placement of sections     Lift all sections individually using all lifting lugs provided  See Figure 2  See  specific instructions for handling the pipe cabinet  see    TCC Wall Section  Assembly  Typical     on page 37  and inlet and exhaust hoods  see    Outdoor  Unit Weather Hood s     on page 52      Make the loop of the sling parallel to  the direction of airflow whenever  possible       Each of the cables used to lift the unit  must be capable of supporting the  entire weight of the unit     e When hoisting the unit into position   use the proper rigging method  such  as straps  slings  spreader bars  or  lifting lugs for protection and safety   See Figure 3     e The air handler is not designed to be  lifted  rigged or ceiling suspended  from the top of the unit       Never lift units in windy conditions   Personnel should be po
54. commended in this section of the manual  could result in exposure to electrical  mechanical or other potential safety hazards  Always refer  to the safety wamings provided throughout this manual conceming these procedures  When  possible  disconnect all electrical power including remote disconnect and discharge all energy  storing devices such as capacitors before servicing  Follow proper lockout  tagout procedures to  ensure the power can not be inadvertently energized  When necessary to work with live  electrical components  have a qualified licensed electrician or other individual who has been  trained in handling live electrical components perform these tasks  Failure to follow all of the  recommended safety wamings provided  could result in death or serious injury  including  remote disconnects before servicing  Follow proper lockout  tagout procedures to ensure the  power can not be inadvertently energized  When necessary to work with live electrical  components  have a qualified licensed electrician or other individual who has been trained in  handling live electrical components perform these tasks  Failure to follow all of the  recommended safety wamings provided  could result in death or serious injury     Table 1L Air handler troubleshooting recommendations       Symptom Probable Cause    Recommended Action       First start after relubrication  Grease distribution     As e Over lubrication  Bearing is excessively Over tensioned belts    hot No lubricant    Misalign
55. crobial growth   mold  inside air  handler    Standing water in drain pan    Moisture problems    See    Standing water in drain pan    above    See    Wet interior insulation    above       CAH SVX01B EN    99    e TRANE    www trane com    For more information  contact your local Trane  office or e mail us at comfort trane com          Literature Order Number CAH SVXOIB EN  Date July 1  2010  Supersedes CAH SVXOIA EN  J uly 2005        Trane has a policy of continuous product and product data improvement and reserves the right to  change design and specifications without notice  Only qualified technicians should perform the  installation and servicing of equipment referred to in this literature     
56. ction as described above     5  Continue until all sections are installed and anchored properly   Install the 18 gauge cover trim cap using  10 self drilling screws  See Figure 18     Figure 18  Stacked unit trim assembly                                                          Cap Upper unit  18 ga  steel   050 if aluminum                                                                                                                                                          10 1 2 S 777 WY Yj YG yy  7 1 2 12 in  clip every 8 ft  NI  and at all corners use  41 2 grade 5 self tapping  screws 4 in  ctc          _______  e  11 2 10 ga  steel y    me   125 if aluminum  0  Roof trim cap 0T  14 ga  minimum     125 if aluminum  Lower unit    F                  CAH SVX01B EN 31    e TRANE    Installation   Mechanical    TCC Model Assembly Instructions    NOTICE  Roof Curb Structurally Sound    Check with curb manufacturer and job engineer to ensure the roof curb is structurally sufficient  to support the weight of the unit  The curb should be checked to ensure it is level and square   Curb bowing  buckling  or sagging can lead to unit assembly and operation problems up to  complete failure     If your nameplate model number begins with TCC  use the assembly instructions below     TCC Overhang Base on Common Roof Curb    L A base designed for use with a roof curb allows for 1 2  inch clearance around the full perimeter    of the curb       Theend section must be installed first making 
57. e at worst case  loaded filters   minus external pressure          Figure 51  Drain pan trapping for section under positive pressure    L   H   K   pipe diameter   where    K   1 2 inch  minimum    H   1 2 inch plus the total unit  static pressure at worst case   loaded filters     CAH SVX01B EN 55    e TRANE    Coil Piping and Connections    Steam Coil Piping    Air handlers fitted with steam coils have labeled holes for piping penetrations  Figure 52 and  Figure 53 illustrate typical steam coil piping configurations  See Table 2 for the codes of system  components in these figures     The coil condensate return line must be piped full size of the condensate trap connection  except  for a short nipple screwed directly into the coil header   s condensate return tapping  Do not bush  or reduce the coil return tapping size     Table 2  Code of system components for piping figures             Code System component  FT Float and thermostatic steam trap  GV Gate valve  OV Automatic two position  ON OFF  control valve  VB Vacuum breaker  ST Strainer  AV Automatic or manual air vent  MV Modulating control valve  Figure 52  Typical piping for Type N steam coils and Figure 53  Typical piping for Type NS steam coils and  horizontal tubes for horizontal airflow horizontal tubes for horizontal airflow          FULL SIZE OF  COIL CONNECTION    56 CAH SVX01B EN    CAH SVX01B EN    e TRANE    Coil Piping and Connections    NOTICE  Breaker Cracking Pressure     The 1 2 inch NPT  15 degree sw
58. e indicating sight glass  expansion valve s   and ball  shutoff valves  Figure 58 illustrates the proper sequence for positioning them in the liquid line   Position the components as close to the evaporator as possible     Filter drier  There is no substitute for cleanliness during system installation  The filter drier  prevents residual contaminants  introduced during installation  from entering the expansion  valve and solenoid valve     Access port  The access port allows the unit to be charged with liquid refrigerant and is used  to determine subcooling  This port is usually a Schraeder valve with a core     Solenoid valve  In split systems  solenoid valves isolate the refrigerant from the evaporator  during off cycles  under certain conditions  they may also trim the amount of active evaporator  as compressors unload  Generally  the    trim    solenoid valve is unnecessary for variable air   volume comfort cooling applications  and is only required for constant volume applications  when dehumidification is a concern     Moisture indicating sight glass  Be sure to install one moisture indicating sight glass in the  main liquid line  The only value of the sight glass is its moisture indication ability  Use actual  measurements of temperature and pressure   not the sight glass   to determine subcooling  and whether the system is properly charged  The moisture indicator sight glass must be sized  to match the size of the liquid line at the thermal expansion valve     Thermal
59. e the tube  diameter recommended by the  condensing unit manufacturer     Forthe vertical riser  usethetube diameter  recommended by the condensing unit  manufacturer  Ensure the top of the riser is  higher than the evaporator coil     Pitch the suction line slightly   1 inch   10 feet  1 cm 3 m    so the refrigerant  drains toward the evaporator     Insulate the suction line     The top of the Circuit 1 suction riser must  be higher than the bottom evaporator coil   Use the tube diameter recommended by   the condensing unit manufacturer for the  riser     10  The top of the Circuit 2 suction riser must    be higher than the top evaporator coil  Use  the tube diameter recommended by the  condensing unit manufacturer for the  riser     Only use a    trim    solenoid valve for  constant volume  humidity sensitive  applications  For all other applications   install a single solenoid valve  the   pumpdown  solenoid valve  between the  liquid line filter drier and the sight glass     CAH SVX01B EN      TRANE    Installation   Electrical    CAH SVX01B EN    Z  WARNING  Hazardous Voltage w  Capacitors     Disconnect all electric power  including remote disconnects before servicing  Follow proper  lockout tagout procedures to ensure the equipment cannot be inadvertently energized  For  variable frequency drives or other energy storing components provided by Trane or others  refer  to the appropriate manufacturer s literature for allowable waiting periods for discharge of  capacitors 
60. e valve jack  when a separate circuit is recommended  see Figure 68        Install outside air sensor and space sensor  if ordered     For valve jack mounting and wiring detail  see Figure 70     Note  The valve jackis typically located atthe air leaving side of the coil connection inside panel   For coils with headers on both sides of the unit  the valve jack is located at the return  connection for water coils and the supply connection for steam coils     CAH SVXOIB EN 71    S TRANE    Installation   Electrical    Figure 70  Valve jack wiring details    Conduit    assembly Valve    quick  connect       Quick Connects    The actuators  factory mounted or field supplied  are separately wired and controlled by a direct   digital controller or other building logic  Figure 71 illustrates the typical quick connect scheme     Figure 7L Typical quick connects with wiring identification       72 CAH SVX01B EN      TRANE    Controls Interface    The portable operator display is used for temporary connection to and operation of Tracer M P580   581 and AH540 541 controllers  With the portable operator display  you can monitor data  change  setpoints  monitor alarms  and override points  The portable operator display includes a 10 ft  3 m   cable with connector that is stored in the storage compartment of the carrying bag  The cable  cannot be disconnected from the operator display  Keep this document with the portable operator  display for access to calibration and cleaning instruction
61. eaded condensate drain connections are provided on only one side of the coil section  Pitch the  connection lines horizontal or downward toward an open drain  Trane recommends installing a  plug to facilitate cleaning of the trap    Figure 50 illustrates the proper trapping  piping  and operation of the trap for negative pressure  sections  Use the formula under the figure to determine the correct minimum depth for the  condensate trap    Figure 51 illustrates the proper trapping  piping  and operation of the trap for positive pressure  sections     Note  Positive pressure traps require a different design than negative pressure traps     If a section has a drain pan for cleaning purposes only  it does not need a trap  however  a cap or  shutoff valve should be installed on the drain connection  Only sections handling condensate  such  as a cooling coil section or moisture eliminator section  require a trap     NOTICE  Water Damage     When more than one section has a drain pain  trap each section individually  Connecting all  drains to a common line with only one trap can result in condensate retention and possible  water damage to the air handler or adjoining space     CAH SVX01B EN    e TRANE     Coil Piping and Connections    Figure 50  Drain pan trapping for section under negative pressure          Normal operation   L   H  J   pipe diameter   where    H   1 inch for each inch of negative   pressure  plus 1 inch   J  1 2 H    Negative pressure   total unit static  pressur
62. eating and or cooling coils  filters  and dampers  See the unit  submittal drawings for detailed descriptions     The fans are internally isolated  To insure fan stability  the unit ships with a minimum of four lock   down devices that prevent the fan from shifting during shipment and installation  These spacers  must be removed prior to fan operation to ensure proper vibration isolation  Retain these spacers  for use in adjusting fan isolators if required     Theunits are available with factory mounted controls for climate and humidity control  These can  be use as stand alone devices or operate with a complete controls system  End devices include  factory mounted starters and variable speed drives     Custom Climate Changer  air handlers ship as complete assemblies or in sections  Some jobsite  assembly is required when the units ship in sections     8 CAH SVXOIB EN    e TRANE    General Infomation    Factory Mounted Controls    CAH SVX01B EN    Trane air handlers are available with a wide selection of factory mounted controls  including  controllers  motor starters  and variable frequency drives  VFD      Most control components are mounted inside the unit  Depending on the system configuration   this may include damper actuators  dirty filter switches  averaging temperature sensors  and low  limit switches  VFDs  starters  controllers  control transformers  static pressure transducers  DC  power supplies  and customer interface relays will be in enclosures mounted on the 
63. ed bearing    Allo    w machine to cool down and restart     Clean surface of grease and purge   Adjust belt tension     App    ly lubricant  Check bearings for damage     Correct alignment  Check shaft level        Blown fuse or open circuit breaker  Overload trip  Improper wiring or connections    Motor fails to start  Improper current supply    Rep  Che  Che    lace fuse or reset circuit breaker   ck and reset overload   ck wiring with diagram supplied on unit     Compare actual supply power with motor nameplate  recommendations  Contact power company for adjustments        p z Check that motor and drive rotate freely  Check bearing  Mechanical failure    lubricant   Open phase Check line for an open phase   Motor stalls Overloaded motor Reduce load or replace with larger motor     Low line voltage    Che    Ck across AC line  Correct voltage if possible        Poor alignment    Excessive vibration Shipping spacers not removed    Over tensioned belts  Misaligned drive    Alig    n bearing set screws  see    Bearing Set Screw Alignment       on page 89   Loosen and retighten bearing set screws   Remove shipping spacers and or bolts  see    Fans    section on    pag    e 48      Adjust belt tension     Alig    n drive        Motor runs and then Partial loss of line voltage    dies down Starter shorts when motor warms up    Che    ck for loose connections  Determine adequacy of main    power supply     Rep    ace starter        Motor does not come Low voltage at motor termina
64. ependently with an automatic  steam control valve  Size the traps for each coil using the capacity of the first coil in direction  of airflow     5  Usea modulating valve that has linear flow characteristics to obtain gradual modulation of the  coil steam supply     Note  Do not modulate systems with overhead or pressurized returns unless the condensate is  drained by gravity into a receiver  vented to atmosphere  and returned to the condensate  pump    6  Pitch all supply and return steam piping down 1 inch for every 10 feet in the direction of the   steam or condensate flow     Note  Do not drain the steam mains or take offs through the coils  Drain the mains ahead of the  coils through a steam trap to the return line     7 Ensure overhead returns have 1 psig of pressure at the steam trap discharge for every 2 feet  of elevation for continuous condensate removal     Water Coil Piping Figure 54  Typical piping for type 5W one row water coil    Figure 54  Figure 55  and Figure 56  illustrate typical water coil piping  configurations     Type WA  5A  5W  D  K  W  UW  TT  P2   P4  and P8 water coils are self venting  only if the water velocity exceeds   15 feet per second  fps  in the coil  tubes  Type UU  WD  and 5D water coils  are self venting only if the water  velocity exceeds 2 5 fps in the coil  tubes  See the unit submittals for coil  water velocity  If the water velocity is    VE Water su pply    main         b Water    below these minimums  ventthe coil by Drain  one 
65. h One Distributor   63  Single Circuit Condensing Unit  Evaporator Coil with Two Distributors 64  Single Circuit Condensing Unit  Evaporator Coil with Four Distributors 65  Dual Circuit Condensing Unit  Evaporator Coil with Two Distributors    66  Dual Circuit Condensing Unit  Evaporator Coil with Four Distributors   67  Dual Circuit Condensing Unit  Evaporator Coil with Eight Distributors   68    Installation   Electrical      Aa kaa a odes deer En adden mas m Roh dob kc Pd 69  Quick Connects    72   Controls Interface 113 2s sca Ak Ie o CR Ren eR RCR RR GR ICE CADRE RC TIR TRAC mA av a 73  Connecting the Operator Display    73  Setting Up the Operator Display                  esses eee 73  Calibrating the Operator Display      73  Adjusting Brightness and Contrat  74  External Communications Port           saaara aranna 74  erudi AY 75  Pre Startup Checker  75  General Checks    75   Fan Related Check  75    CAH SVX01B EN 5    Coil Related Check  76    Motor Related Check  76   Unit Operation    77  Calculate Motor Voltage Imbalance               000 cece eee 77  Tension the Fan Belt            eres 78  Determine Fan Speed      79   Align Fan and Motor Sheaves                 esses eres 80  Check Multiple Belt  80  Traq    Dampers ed E eee RR RR RR ERI ERES 81  Fan Inlet Airflow Measuring System             0 00 cece eee eens 82  Villa EE 82  Transmitter Sizing  rs angna aao maaa aa Aaa A E a RO aa AA AA A 82  Transmitter Calibration        0 0 0    cece 83  Constant Factor
66. hanged due to shipping and handling vibration     e Check that air filters are in place and positioned properly     Remove any debris from the unit interior     Close and secure all unit access doors     Note  UL listed units require a removable latch on access doors  The door clip shipped with the  unit meets this requirement       Inspect electrical connections to the unit and unit controllers     Connections should be clean and secure     Compare the actual wiring with the unit diagrams       Reference the appropriate controller manual for more details about starting units with  factory mounted controls     e Leave this manual with the unit     Fan Related Checks    CAH SVXOIB EN    e Ifthe unit is internally isolated  ensure that the fan isolator tie down bolts have been removed   e Rotate all fan wheels manually to confirm they turn freely in the proper direction   e Check fan shaft bearings  fan wheel  and drive sheave set screws for proper torque settings     Fan sheaves should be tight and aligned     Bearing set screws should be torqued       Inspect the inlet vane assembly for freedom of movement  If resistance is above the  recommended torques  checkthe assembly for any binding or misalignment  Do notforce the  vanes     e Check fan drive belt tension      nspectfan motor and bearings for proper lubrication  if necessary     75    Start Up  Coil Related Checks  NOTICE  Proper Water Treatment   The use of untreated or improperly treated water in coils may result in 
67. ing approximately   1 4 inch     4  Check that the bushing on the isolator stud is centered  in the isolator  Adjust to center by moving the stud in    ib    e E   the fan base hole     5  This procedure will raise the equipment load until the isolators are all off the shims  shipping  tie down blocks  approximately 1 32 inch  the thickness of a credit card   and the internal gap  is approximately equal to the external gap     Note  Do not adjust isolators once the fan base is off of the shipping tie down blocks     6  Continue adjusting other isolators in sequence and repeat the same adjustment  Continue until  all isolators are adjusted     7 Replace the jam nut on each isolator adjusting bolt  tighten the nut  and remove the shipping  tie down block     48 CAH SVX01B EN    e TRANE    Installation   Mechanical    Control Dampers    If the damper actuators are not factory mounted install damper actuators and connecting linkage   Check damper operation and linkage alignment     Damper blades should be non binding  Adjust damper frame as necessary to ensure free blade  movement     Magnahelic Air Filter Gage    Air Filters    CAH SVX01B EN    Check zero adjustment of the gage  Turn both vent valves to the    Vent    position and adjustthe gage  pointer to zero by means of the external adjustment screw in the face of the gage  After zeroing   turn the vent valves to the    Line    position     Z  WARNING  Hazardous Voltage with Capacitors     Disconnect all electric power  incl
68. ing check valve vacuum breaker is recommended because other  vacuum breakers  such as spring loaded ball check breakers  have cracking pressures as high as  1 25 inches Hg  17 inches of water   Vacuum breakers with fitting sizes smaller than 1  2 inch NPT  are too small to relieve vacuum quick enough to ensure complete condensate drainage  Other  types of swing check valve vacuum breakers are acceptable if the fittings size is not smaller than  1 2 inch NPT and the cracking pressure is not larger than 0 25 inches Hg  3 4 inches of water    Failure to follow these instructions may result in equipment damage     To prevent coil damage  complete the following recommendations     e Install a 1 2 inch NPT  15 degree swing check valve vacuum breaker with cracking pressure of  0 25 inches Hg  3 4 inches water  or lower at the top of the coil  This vacuum breaker should be  installed as close to the coil as possible     e ForcoiltypesA  AA  N  NS  and NN  install the vacuum breaker in the unused condensate return  tapping at the top of the coil       Types T and ST coils require that the vacuum breaker be located as near as possible to the  supply connection     e  Ventthe vacuum breaker line to atmosphere or connect it into the return main at the discharge  side of the steam trap    Note  Vacuum breaker relief is mandatory when the coil is controlled by a modulating steam  supply or automatic two position  ON OFF  steam supply valve  Vacuum breaker relief is  also recommended when f
69. inside of the  unit     Small items that cannot be factory mounted  such as space temperature sensors  outside air  temperature sensors  and humidity sensors  will ship inside the control enclosures  or packaged  and shipped inside the fan or mixing box section  Larger items are shipped inside the fan section     Note  All control valves ship directly to the    ship to address    from the vendor unless another  address is given on the Trane sales order     All factory mounted control systems  controls that are factory wired to a unit controller or terminal  strip  ordered without starters or variable frequency drives  VFDs  are provided with 120 to 24 Vac  control transformers mounted and wired in the auxiliary control panel  The customer must provide  120 Vac 50 60 Hz control power  A dedicated 15 amp circuit is recommended     Factory mounted control systems ordered with factory mounted starters or VFDs are supplied with  line to 24 Vac control transformers  No additional power wiring is required     For a more in depth understanding of controls  refer to the following manuals    e Tracer MP580 581 Programmable Controllers catalog  CNT PRC002 EN     Tracer MP581 Programmable Controllers Hardware Installation  CNT SVNO1C EN    Variable Frequency Drives TR200 Series  BAS SLBO26 EN    Custom air handlers and or field installed accessories that must be stored for a period of time prior  to being installed must be protected from the elements  All controllers and electrical elect
70. installed  PE    Add caulking after  Tf   trimming gasket  A R    LT l  Eas                                                          CAH SVX01B EN 23    e TRANE     Installation   Mechanical    TCP Base Section Assembly with Tumed Up Floor    L SeeFigure 11  Apply 4 inch x Y inch neoprene gasket to the full perimeter face of each shipping  split section     2  Join the two sections and secure with field provided 5 8 inch flat washers and 5 8 inch x 2 Y gt   inch grade 9 bolts through each of the six holes     3  Apply a heavy bead of caulk to the inside of the U channel     Press U channel down over upturned flanges with moderate pressure to ensure itis fully seated  onto upturned flanges  The caulk will cure and act as an adhesive to hold U channel in place   no fasteners are required     Figure IL Uptumed floor assembly       24 CAH SVXOIB EN    S TRANE    Installation   Mechanical    TCP Wall Section Assembly    Exterior Wall Assembly  Typical    L See Figure 12  Ensure shipping split sections are aligned and pulled together properly   Apply a bead of caulk to full height of wall joint    Apply 3 inch x 1 8 inch adhesive backed foam gasket to inner joining strip    Install inner joining strip using  14 x L5 inch gasketed tec screws     uk WN    Fit the pre cut hub cap over the joining strip the vertical height of the wall flush with the roof  and secure it to the wall with  8 sheet metal screws  Fill the top and bottom openings with caulk  as a moisture seal  Screw holes c
71. ions when exposed to live electrical components  could result in death or serious injury     Before complete startup  bump start the unit and confirm the fan wheel rotates properly  as  indicated by the rotation arrow located on the fan housing  After initial startup       Calculate the motor voltage imbalance  notifying the power company to correct unacceptable  imbalances       Periodically check the fan belt tension     Calculate Motor Voltage Imbalance    After startup  measure the motor voltage and amperage on all phases to ensure proper operation   Thereadings should fall within the range given on the motor nameplate  The maximum allowable  voltage imbalance is 2 percent    Voltage imbalance is defined as 100 times the sum of the absolute deviation of the three voltages  from the average  divided by twice the average voltage  For example  if the three measured  voltages are 221  230 and 227  the average voltage would be 226 volts  The percent of voltage  imbalance is then calculated     100A    Voltage imbalance                                2xAvgVoltage    where   A    226 221     230 226     227 226     Voltage imbalance   2 2   not acceptable     Inthe example  2 2 percent imbalance is not acceptable and the power company should be notified  to correct it     CAH SVX01B EN 77    Start Up  Tension the Fan Belt  NOTICE  Belt Tension     Do not over tension belts  Excessive belt tension will reduce fan and motor bearing life   accelerate belt wear and possibly cause sh
72. l in making this field joint        21    e TRANE     Installation   Mechanical    TCP J oining Sections Edge to Edge    Units must be installed level for proper drainage of condensate from the drain pan  In addition   each section in a multi section unit must be properly supported     Note  Leveling each section  beginning with the first  is critical  Failure to level and align the    L    2     sections immediately creates greater misalignment or even structural damage afterward   Remove all crating and wrapping from the surfaces to be joined     Place one section of the air handler into the desired position  Verify section is installed level  front to back and side to side  Verify section is square to support structure  this is critical to  insure proper alignment for next adjoining sections     Check squareness measuring the critical dimensions given  U se preselected method to anchor  first piece in place  This is necessary so movement will not affect pulling next sections into  alignment     When the unit is positioned and squareness is ensured within 1 8 inch  remove all lifting lugs  located along the split plane     After assuring positioning is correct  anchor in place either by welding unit base to the curb or  by mechanical fasteners  The first section will be used to pull remaining sections up tight so it   s  critical that first section be secured     Install 4 inch x 1 4 inch neoprene gasket to all mating surfaces of the section  including any  internal walls  
73. lass insulation     L Disconnect all electrical power to the unit     2  Wearing the appropriate personal protective equipment  use a vacuum device with a HEPA filter   99 97 percent efficient at 0 3 micron particles  to remove the accumulated dirt and organic  matter     Note  Be careful notto tear the insulation surface or edges    3  Confirm the drain line is open following the cleaning process    4  Allow the unit to dry thoroughly before putting it back into service   5  Replace all panels and parts and restore electrical power to the unit   6    Be careful any contaminated material does not contact other areas of the unit or building   Properly dispose of all contaminated materials and cleaning solution     CAH SVXOIB EN 95    e TRANE    Routine Maintenance    Controls    Multiple Fans    On units that have been selected with the external communications port  both the operator display  and Rover service tool can be connected without shutting off the unit through the external  communications port  Remove the cover plate on the port and plug into the RJ  11 port for the  operator display or the RS 485 port for the Rover service tool  This enables continuous operation  of the Air Handling unit without disruption to the operating conditions of the unit  When servicing  of the unitis complete  replace the cover plate on the external port to eliminate the air leakage path     When controlled in a bank of fans  these fan units must be controlled using a common control  signal 
74. lation on roof curb  either   opening in bottom of unit  During unit installation on roof curb  either raise  raise field provided duct or add additional gasket material to field provided duct or add additional gasket material to compensate for  compensate for the 1 2 inch offset  the 1 2 inch offset     Component Installation Requirements    Z  WARNING  Hazardous Voltage with Capacitors     Disconnect all electric power  including remote disconnects and discharge all motor start  run  capacitors before servicing  Follow proper lockout tagout procedures to ensure the power  cannot be inadvertently energized  For variable frequency drives or other energy storing  components provided by Trane or others  refer to the appropriate manufacturer s literature for  allowable waiting periods for discharge of capacitors  Verify with an appropriate voltmeter that  all capacitors have discharged  Failure to disconnect power and discharge capacitors before  servicing could result in death or serious injury     Each componentin the Custom air handler may have installation requirements that could affect the  unit s performance     Note  For components included in the unit but not included in this manual  reference the  component manufacturers specific Installation  Maintenance  and Operation manual   Copies of these manuals are either included in the package with this unitlOM or are attached  to the components mounted in the unit     CAH SVXOIB EN 47    e TRANE     Installation   Mechanical 
75. lled Evaporator Piping  Single Circuit Condensing Unit  Evaporator Coil with One Distributor    CAH SVX01B EN    Figure 60  Single circuit evaporator coil with one distributor    Evaporator Coil with  Standard Circuiting             suction line  6 7  4    thermal solenoid filter drier  wgl expansion valve  valve  TXV   3  5  distributor    Pitch the liquid line slightly   1 inch 10 feet  1 cm 3 m    so that the refrigerant drains toward  the evaporator  See Figure 60     Provide one expansion valve per distributor     3  Slightly pitch the outlet line from the suction header toward the suction riser   that is  1 inch     10 feet  1 cm 3 m  in the direction of flow  Use the tube diameter that matches the suction   header connection     For the vertical riser  use the tube diameter recommended by the condensing unit  manufacturer  Ensure the top of the riser is higher than the evaporator coil       Arrange the suction line so the refrigerant gas leaving the coil flows downward  past the lowest    suction header outlet  before turning upward     Pitch the suction line slightly   1 inch 10 feet  1 cm 3 m    so the refrigerant drains toward the  evaporator     Insulate the suction line     63    e TRANE    Coil Piping and Connections    Single Circuit Condensing Unit  Evaporator Coil with Two Distributors    Figure 6L Single circuit evaporator coil with two distributors    Evaporator coil  Suction line with horizontal split   standard  circuiting             Trim     solenoid val
76. ls  up to speed Line wiring to motor too small    Che  Rep    ck across AC line and correct voltage loss if possible   ace with larger sized wiring        Motor overheats Overloaded motor    Motor fan is clogged with dirt preventing proper ventilation    Red    uce load or replace with a larger motor     Remove fan cover  clean fan and replace cover        Motor mounting bolts loose  Rigid coupling connections  Worn motor bearings   Fan rubbing on fan cover    Excessive motor noise    Tighten motor mounting bolts     Rep  Rep    ace with flexible connections   ace bearings and seals     Remove interference in motor fan housing        Rapid motor bearing    Excessive overhung load due to overtensioned drive  Excessive overhung load due to a small diameter motor    Che    ck belt tension and overhung load              wear Replace sheave with larger one   sheave  Motor is poorly positioned Adjust belt tension   Loose fan belt Worn or damaged belt Replace belt or belt set  Check sheave alignment   Worn sheaves Replace sheaves   98 CAH SVXOLB EN    Table 1L Air handler troubleshooting recommendations    e TRANE    Troubleshooting       Symptom    Probable Cause    Recommended Action       Short belt life    Worn sheaves  Misaligned belt  Grease or oil on belts  Belt slipping   Belts rubbing    Replace sheaves    Realign drive with MVP sheave set at mean pitch diameter   Check for leaky bearings  Clean belts and sheaves   Improper belt tension  Adjust tension    Remove obstruction
77. m tape  See Figure 37     Figure 37  Pipe cabinet installation       CAH SVXOIB EN    43    S TRANE    Installation   Mechanical    5  Lift cabinet into place aligning base tab with lifting lug brackets on air handler base   6  Slide pipe cabinet tight up against mounting channels on side wall of air handler     7 Install bolts through lifting lug gussets to anchor pipe cabinet base to the air handler  See  Figure 38  and Table 1     Figure 38  Pipe cabinet detail          Unit       Table L Pipe cabinet hardware             Qty X Code Code Description Description   4 X25017800000 BOLT  0 625 11 X 1 750 5 8 1 75 in  Bolt   4 X28021500000 NUT  0 62 11 5 8 11 Nut   4 X22020800000 LOCKWASHER  0 625 ID 5 8 in  Lock Washer  8 X22050313010 WASHER  0 656 ID X 1 312 OD Flat Washer   8  Check pipe cabinet side walls to ensure they are plumb     O    Apply a bead of caulk along the corner between the pipe cabinet and air handler wall prior to  installing connecting angle     44 CAH SVX01B EN    e TRANE    Installation   Mechanical    10  Install inside corner cap  See Figure 39 Detail A and B   1L Install 3 16 inch x 1  25 inch grey ribbed butyl tape to unit wall where pipe cabinet roof connects   12  Lift pipe cabinet roof into place and attach to unit wall with screws  See Figure 39     Figure 39  Pipe cabinet       See Detail B          IH          TOP VIEW    Roof and base parts  removed for clarity    AHU       Picture frame    mounting chanels  factory assembled to unit          
78. manufacturer s lubrication recommendations for  proper lubrication       The motor manufacturer may recommend lubricating the motor as part of their routine  startup instructions     Checkmotor winding  An acceptable winding resistance reading is from 6 meg ohms to infinity   If reading is less than 5 mega ohms  the winding should be dried out in an oven or by a blower     Inspect the entire motor for rust and corrosion     Bump start the unit and confirm the fan wheel rotates properly  as indicated by the rotation  arrow located on the fan housing     Note  Note  For motor warranty needs  contact you local Trane sales office     76    CAH SVXOIB EN    Unit Operation    Z  WARNING  Rotating Components     During installation  testing  servicing and troubleshooting of this product it may be necessary to  measure the speed of rotating components  Have a qualified or licensed service individual who  has been properly trained in handling exposed rotating components  perform these tasks   Failure to follow all safety precautions when exposed to rotating components could result in  death or serious injury      N WARNING  Live Electrical Components     During installation  testing  servicing and troubleshooting of this product  it may be necessary  to work with live electrical components  Have a qualified licensed electrician or other individual  who has been properly trained in handling live electrical components perform these tasks   Failure to follow all electrical safety precaut
79. mmendations                0 cee een eee 11   General Storage            ete ee 11   Long Term  Storage   i e one epee Ek ex eee eds eee Rm RE Rs 11   Outdoor Storage Considerations      12  Preparing the Unit Site 2 0    nannan aaaea 12  Roof Curb Installation Checker  13   Suggested Tools  14   Installation   Mechanical 1  iae a Ah e do DER RR a ew wade eben de dee Ra 15  Lifting and Rigging             cece cette n 15  Lifting Considerations      16  Unit Assembly        2  nent teen nee 17  TCP Model Assembly Instructions            0 0 0 cece cece eee eae 18   TCP Standard Roof Cube  18   TCP Structural Roof Curb and I Beam Dunnage    ssassn sranna 19   TCP Flat Concrete bad    20   TCP Roof Curbs for Large Units with Shipping Splits                 21   TCP J oining Sections Edge to Edge    22   TCP Base Section Assembly with Flat Floor  23   TCP Base Section Assembly with Turned Up Floor                   24   TCP Wall Section Assembly      25   TCP Outdoor Roof Assembly   Single Span                 lusus  26   TCP Outdoor Roof Assembly   Multiple Gpnan   nannan 27   TCP Indoor Roof Section Assembly  Typical                         28   TCP Indoor Roof Assembly   Multiple Span              aaa  29   TCP Base to Interior Wall Section Assembly                    s  30   TCP Stacked Unit Assembly            0 0 cece eee 31  TCC Model Assembly Instructions               00  ccc eee eee eee 32   TCC Overhang Base on Common Roof Cube 32   TCC Flat Base to Steel Dunnage or C
80. o the operating conditions of the unit  When servicing  of the unitis complete  replace the cover plate on the external port to eliminate the air leakage path     74    CAH SVXOIB EN    Start Up      TRANE    Once the air handler has been assembled and installed  attention must be directed to individual  components for proper operation  Before operating the unit  complete the pre startup checklist     Z  WARNING  Hazardous Voltage with Capacitors     Disconnect all electric power  including remote disconnects and discharge all motor start  run  capacitors before servicing  Follow proper lockout tagout procedures to ensure the power  cannot be inadvertently energized  For variable frequency drives or other energy storing  components provided by Trane or others  refer to the appropriate manufacturer s literature for  allowable waiting periods for discharge of capacitors  Verify with an appropriate voltmeter that  all capacitors have discharged  Failure to disconnect power and discharge capacitors before  servicing could result in death or serious injury     Note  For additional information regarding the safe discharge of capacitors  see  PROD SVBOGA EN     Pre Startup Checklist    General Checks      Ensure the unit has been installed level     Ensure supply air and return air ducts have been connected     Ensure damper operator motors and connecting linkage have been installed     e Verify damper operation and linkage alignment  Damper blade and linkage positioning may  have c
81. of the following methods  Figure 55  Typical piping for SA  5W two row  K  W 3 to 12 row  WD  D   L Install an air vent in the top pipe and DD water coils    plug tapping of the return header     2  When the return line rises above the  top of the coil  vent from the top of  the return header horizontally to the  return piping     Note  T  ST  and TT coils are designed  with larger than normal end  tube sheet holes to allow for  maximum expansion  Air  leakage around tubes should be  expected and handled by  capping over coil ends or by  sealing around tubes with a  pliable sealant such as silicon     dq    58 CAH SVXOIB EN    e TRANE     Coil Piping and Connections    Figure 56  Typical piping for type W or WA 1 row water coil       CAH SVX01B EN 59    e TRANE    Coil Piping and Connections    Refrigerant Coil Piping    Liquid Lines    60    Note  Refer to  Important Environmental Concerns     on page 2 for information on handling  refrigerants     Use Figure 58 to determine the proper  relative sequence ofthe components in the refrigerant lines  that connect the condensing unit to an evaporator coil  Refer to    Examples of Field Installed  Evaporator Piping    on page 63 for more detailed schematics of evaporator piping     Figure 58  Example of placement for split system components                 Access  T port    n  Discharge em SELA     line Access  E port    SS ii d Filter  9 o Manual    co angle valves  oo  o 9 Manual 7   ou Compressors ball valve DI                 
82. oil Piping and Connections    Dual Circuit Condensing Unit  Evaporator Coil with Eight Distributors    Figure 65  Dual circuit evaporator coil with eight distributors    suction line  7 8     circuit 2        o    suction line  78     circuit 1     4    suction lines    28   g   3  e  8  5  6 6  4    68    a    3   3     L 3n2419     Evaporator Coil    thermal expansion with Horizontal Split    eet valves  TXV                          Es  distributor                    distributor     Standard  Circuiting          liquid line      circuit 2     liquid line   circuit 1        pump down     solenoid valve    Evaporator Coil with  Intertwined Circuiting    thermal expansion  TN  valves  TXV      trim   solenoid valve    G 11    liquid line      circuit 2     liquid line   circuit 1        filter drier     pump down   solenoid valve    Pitch the liquid line slightly   1 inch 10 feet   1 cm 3 m    so the refrigerant drains  toward the evaporator  See Figure 65     Provide one expansion valve per  distributor     Slightly pitch the outlet line from the  suction header toward the suction  riser   that is  1 inch 10 feet  1 cm 3 m  in  the direction of flow  Use the tube  diameter that matches the suction header  connection     Arrangethe suction line so the refrigerant  gas leaving the coil flows downward  past  the lowest suction header outlet  before  turning upward  Use a double elbow  configuration to isolate the TXV bulb from  other suction headers     For horizontal tubing  us
83. olds 2 inch filter    b  4       Side Load Filters    Most filters in custom units are installed in unitary sheet metal frames  If unit is provided with side  access rack  do the following for installation     2 inch or 4 inch flat filters  L Disconnect the power to the unit     2  Open the filter section access door and remove the filters and block offs from their installed  position     3  Slide the filter into the rack   4  Some side load racks will be provided with block off plates     5  Close and secure the door  making certain the door closes snug against the block off  see  Figure 48      50 CAH SVX01B EN    S TRANE    Installation   Mechanical    Figure 48  Filter block off placement                Bag or Cartridge Filters  L Disconnect power to the unit     2  Keeping the bag filters folded  slide each filter into the filter rack  pushing them tightly against  the unit  Pleats should be in the vertical position     3  If using optional pre filters  slide them into the appropriate filter rack   4  If block offs are provided with the unit  slide the block offs into the filter track   5  Close and secure the access door  making certain the door closes snug against the rack     Note  The block off is intended to make a seal when the access door is closed  It may require a few  adjustments to ensure a proper seal     CAH SVX01B EN 51    e TRANE     Installation   Mechanical    Outdoor Unit Weather Hood s   L Perthe unit drawing determine mounting location of the unit wea
84. ollow all recommended safe handling practices  Failure to follow all safety  instructions could result in death or serious injury     Cleaning Non Porous Insulating Surface    If microbial growth on a non porous insulating surface  closed cell insulation or sheet metal  surface  is observed     L Disconnect all electrical power to the unit     2  Wearing the appropriate personal protective equipment  use a brush for sheet metal surfaces  or a soft sponge on a foil face or closed cell foam surface to mechanically remove the microbial  growth     Note  Be careful not to damage the non porous surface of the insulation     3  Install a block off to prevent spray from going into a dry section of the unit and or system  ductwork     4  Thoroughly clean the contaminated area s  with an EPA approved sanitizer specifically  designed for HVAC use     5  Rinsethe affected surfaces thoroughly with fresh water and a fresh spongeto prevent potential  corrosion of the drain pan and drain line    Repeat steps 4 and 5 as necessary   Confirm the drain line is open following the cleaning process   Allow the unit to dry thoroughly before putting it back into service     0 OND    Replace all panels and parts and restore electrical power to the unit    10  Be careful any contaminated material does not contact other areas of the unit or building   Properly dispose of all contaminated materials and cleaning solution    Cleaning Porous Insulating Surface   To clean a porous insulating surface  fiberg
85. on 12 inch centers     Note  Use a polyurethane or equivalent caulk  It may be necessary to clamp the joint together or  pre drill to prevent separation when drilling with screws     3  Apply caulk to end of J  cap to seal thoroughly     Figure 13  TCP outdoor roof assembly   single span      Joining cap  Add caulking before P dd  installing J cap EN                                                                                                                      4 in  x 1 4 in  gasket  10 x 1 in  self tapping screw     o 6 e e  e e J  Roof split outdoor unit    w                                                    Roof panel    a ees section split  3 in  x 1 8 in  neoprene gasket is 2 3 4 in  wide joining strip    applied to metal joining strip   Apply gasket to metal strip  before Installation   8 x 1 in  Phillips zip screw                                                                                                    26 CAH SVXOIB EN    e TRANE    Installation   Mechanical    TCP Outdoor Roof Assembly   Multiple Span    Follow instructions in Figure 13 for installation of J  Caps     4  The multiple roof split requires and additional cap that covers the center T shaped seam  running parallel to air flow     5  Install  14 self drilling screws on 10 inch centers on underside of center split as shown in  Figure 14     Figure 14  TCP outdoor roof assembly   multiple span      S    Cap and Caulk  gasket          6 inch trim cap ao  10 sheet metal screw          Standing se
86. oncrete Pad                    32   TCC J oining Sections   Edge to Edge                0c eee eee 33   TCC Internal Shipping Split Frame Assembly  Typical                 36   TCC Wall Section Assembly  Typical               00000  e eee eee 37    CAH SVX01B EN    TCC Indoor Roof Section Assembly  Typical                         37   TCC Outdoor Roof Section Assembly  Typical                       38   TCC Stacking Procedure      40   TCC Energy Wheel and CDQ Wheel Assembly                       42   Pipe Cabinet Installation           cece 43   Duct Connectons  x Xe p p NAG EG aa WERE PAN MERE ERG rui ea 46  Bottom Opening Duct Installation      46  Component Installation Requirements      47  FANS  453 fxs edie EA S Ux CE ew ee INTR ONG EROR ed 48  Isolator Adjustment         0 00 000 nanena 48  Control Dampers      2    tee 49  Magnahelic Air Filter Gage           tee 49    X duca LL 49  Outdoor Unit Weather Hood s           aaaeeeaa 52   Coil Piping and VONNECHONS  lt    aciem amc road dam md d erbe Ert ees 53  General Coil Piping Recommendations      53  Drain Pan Trapping           0  ccc n 54  Steam Coil Piping          2 0    56  Water Coil Piping            0    ccc eI I 58  Refrigerant Coil Piping            ccc es 60  Liquid LINES iioi ana amend NAA MA KIA A gd DAAN ebe E E 60  SUCTION LINES   1er eres hha ha a chia ke dear S Qa P E E 62  Examples of Field Installed Evaporator Piping                  lusus  63    Single Circuit Condensing Unit  Evaporator Coil wit
87. ons    Inspect coils for dirt build up  See  Coils  on page 91 for more information        Every year    Inspect the unit casing for corrosion  If damage is found  clean and repaint the surface with a rust resistant primer   Clean the fan wheels and fan shaft  See  Fans  on page 88 for more information    Inspect and clean drain pans    Check damper linkages  set screws  and blade adjustment  Clean  but do not lubricate  the nylon damper rod bushings   Clean damper operators    Inspect electrical components and insulation    Inspect wiring for damage    Rotate the fan wheel and check for obstructions in the fan housing  The wheel should not rub on the fan housing  Adjust  the center if necessary and tighten wheel set screws to the proper torque    Lubricate motor bearings in accordance with motor manufacturer s recommendations  see the  Motor Bearing Lubrication   section on page 90 for more information   This may only need to be done every 2 to 3 years    Check condition of gasketing and insulation around unit  door and dampers    Examine flex connections for cracks or leaks  Repair or replace damaged material        CAH SVXOIB EN    85    e TRANE    Routine Maintenance   Air Filters   N WARNING  Rotating Components     Disconnect all electric power  including remote disconnects before servicing  Follow proper  lockout  tagout procedures to ensure the power can not be inadvertently energized  Secure  drive sheaves to ensure rotor cannot freewheel  Failure to secure drive she
88. or units may be  mounted on housekeeping pads  Refer to submittals for unit dimensions and openings     Note  For proper operation  the unit must be supported around the entire unit base perimeter  If  the unit is shipped in sections  the entire section perimeter must be supported  as well as  at the base channels of the unit splits     Provide clearance around the unit to allow adequate free air and necessary service access  Also   allow room for supply and return piping  ductwork  electrical connections  and coil removal     The building roof must be able to support the entire weight of the unit  roof curb and accessories   See submittals for approximate unit weights       Prepare the roof curb or pier mount and roof openings before lifting the unit to the roof     e Check that the gasketing or sealant on the roof curb is intact and provides an airtight seal with  the unit base       Complete all ductwork  piping and electrical connections only after mounting the unit     17    e TRANE    Installation   Mechanical    TCP Model Assembly Instructions    Ifthe model number on the nameplate begins with TCP  usethe assembly instructions below  The  TCP base is constructed for specific installation requirements such as standard roof curbs   structural support curbs  steel I beam dunnage support  and pier mounting     NOTICE    Roof Curb Structurally Sound    Check with curb manufacturer and job engineer to ensure the roof curb is structurally sufficient  to support the weight of 
89. osphere  In particular  several of the  identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine  Fluorine  and Carbon  CFCs  and those containing Hydrogen  Chlorine  Fluorine and Carbon  HCFCs   Notall  refrigerants containing these compounds have the same potential impact to the environment   Trane advocates the responsible handling of all refrigerants including industry replacements for  CFCs such as HCFCs and HFCs     Responsible Refrigerant Practices     Trane believes that responsible refrigerant practices are important to the environment  our  customers  and the air conditioning industry  All technicians who handle refrigerants must be  certified  The Federal Clean Air Act  Section 608  sets forth the requirements for handling   reclaiming  recovering and recycling of certain refrigerants and the equipment that is used in these  service procedures  In addition  some states or municipalities may have additional requirements  that must also be adhered to for responsible management of refrigerants  Know the applicable  laws and follow them     Z WARNING  Refrigerant waming information     System contains oil and refrigerant under high pressure  Recover refrigerant to relieve pressure  before opening the system  See unit nameplate for refrigerant type  Do not use non approved  refrigerants  refrigerant substitutes  or refrigerant additives     Failure to follow proper procedures or the use of non approved refrigerants  refrigerant  substi
90. ower unit perimeter    Factory installed Detail A  engagement plate  Lower unit  Wall  Flashing  Screw  10 16 x  750 self driller Base  Roof  lower unit    Detail B    CAH SVX01B EN 41    e TRANE    Installation   Mechanical    TCC Energy Wheel and CDQ Wheel Assembly  Units are shipped unstacked     1    Set sections 1   5 of the unit in place in sequence order as shown in Figure 36 and secure as   needed      Prior to setting section 2 and 3 apply 2 in  x 1 in  thick gasket across full unit width along the  wheel   s upper to lower septum     Figure 36  Energy wheel and CDQ wheel assembly           2     3     Section 5       Section 4          Section 4          X SN        E                                 Ip A A Flashin  INA Ge   SPA   AG ii    Screw 1   10 16 x  750    Section 1    Detail A       Prior to upper unit placement  install 0 188 in  x 2 in  gasketing on entire length of engagement  plate and or lower unit perimeter as needed  Engagement plates are used when the upper and  lower unit dimensions are not matched  Refer to    TCC Stacking Procedure    on page 40     Apply two layers of Lin  tall x 2 in wide gasketing around perimeter of roof opening in lower  unit section prior to lifting upper unit  Refer to    TCC Stacking Procedure    on page 40     Note  If gasketing is not installed first  leakage may occur between the upper and lower units and    4     ui    o    will result in CFM loss     Upper unit with duct opening should be placed within 1 inch of lowe
91. ped in sub assemblies  locate the assembly hardware  which should be  packaged and shipped inside the fan or mixing box section       Inspect and test all piping for possible shipping damage  Nipples may be installed on coils at  thefactory butshould always betightened and tested before any connections are made  Rough  handling during shipping  in addition to other factors can cause pipe connections to become  loose     Note  Trane will not be responsible for any leak at the field connections  Coils have been factory  pressure tested before shipping     Assembly Hardware    10    Trane air handlers ship with all necessary assembly hardware and gasket material  This hardware  is packaged in either a clear plastic envelope or cardboard box and can be found inside the fan   mixing box  or access section  If there is not enough space inside the section  a crate or pallet will  be loaded onto the bed of the truck  Check the parts list on the field assembly drawing against the  contents of the crate  Do not proceed with unit assembly until verification that all materials are  present  Sometimes it is necessary to use more than one section to ship hardware  Please check  all sections thoroughly before contacting your local Trane sales engineer to report missing  hardware     CAH SVXOIB EN    e TRANE    Pre Installation Requirements    Resolving Shipping Damage    Trane air handlers ship free on board  FOB   meaning that the unit belongs to the customer the  moment the delivery truck
92. ping     on page 54     Note  If unit is installed in a mechanical room on a pad  inadequate height may necessitate core   drilling the floor to attain proper trap height  Insufficient height could inhibit condensate  drainage and result in flooding the unit and or equipment room       Confirm the roof curb or foundation of the mounting platform is level and large enough to  accommodate the unit  Refer to the unit submittals for specific dimensions       Provide adequate lighting for maintenance personnel to perform maintenance duties       Provide permanent power outlets in close proximity to the unit for installation and  maintenance       Depending upon job requirements  the customer may need to provide 120 Vac power to the unit  controller  Refer to submittals for more information  A dedicated 15 amp circuit is  recommended     CAH SVXOIB EN    e TRANE     Pre Installation Requirements      Wiring for units must be provided by the installer and must comply with all national and local  electrical codes     e Rooftop curb mounted units must be sealed tightly to the curb  Use proper sealants and roof  to curb sealing techniques to prevent water and air leakage     Note  Preparation ofthe roof curb or pier mountand roof openings should be completed prior to  lifting the unit to the roof     Roof Curb Installation Checklist    Itis recommended thatthe curb be installed directly on the support members and fastened to the  supports using tack welds or other equivalent methods  P
93. r duct opening in order to  sufficiently compress gasket       Once unit is set in place verify the gasket seal between openings    After installing all of the upper unit sections  Install all thread rods  field provided  fastening  both upper and lower sections to the wheel section    Fasten the upper unit to the lower unit perimeter cap with Ys inch self drilling screws through  base rail     Note  A drill extension will be required to ensure straight alignment     42    CAH SVXOIB EN    e TRANE    Installation   Mechanical    7 Units will have field installed flashing  Remove upper unitlifting lugs  in order to install flashing  between the upper and lower unit     Parts are number matched to the unit  Each piece of flashing will be identified with a unit  section number in which it applies     Top edge of flashing will be placed behind upper unit base rail flange and fastened to lower  unit perimeter cap     Use  10 screws to install flashing     For external outdoor units caulk the corners and top edge of the flashing   Pipe Cabinet Installation  L After air handler is completely installed and checked for accuracy of level and square  pipe    cabinet install can begin     Remove bolts holding the lifting lugs in place from the base of the air handler     3  Checkto ensure that the structure the pipe cabinet is to be installed on is square and level     Install 3 16 inch x 1  25 inch grey ribbed butyl tape to flanged side of pipe cabinet wall and  remove paper backing fro
94. r the lip of the curb flanges and over the felt       Apply sealantto the four corners  Caulk all joints between the curb and the roof  Attach the    gasket material to the curb s top flanges  entire perimeter  and to the supply and return air duct  opening panel flanges    Two chain come alongs  These havethe pulling powerto bring the shipping splits together  one  on each side of the unit  Cable come alongs are not strong enough and normally will fail  The  chain versions work well     Two long drift pins to keep holes aligned as the sections come together     One half inch or 3 4 inch electric impact gun  These are very effectiveto tighten the bolts at the  base once it s close enough together to getthe bolts in     Caulk guns     Standard battery impact gun or battery drill for installation of screw in joint strips  hubcaps  and  inlet or exhaust hoods     Nut setters for battery impact gun   3 8 inch and 5 16 inch   Utility knives for cutting section to section gasket   A couple of large pry bars     Proper size sockets and wrenches to remove lifting lugs when in positions  Multiple size sockets   Must have 15 16 inch and 1 1 16 inch sockets     CAH SVXOIB EN    S TRANE    Installation   Mechanical    Installation   Mechanical  Lifting and Rigging     N WARNING  Heavy Objects     Do not use cables  chains or slings  except as shown  Each of the cables  chains or slings  used  to lift the unit must be capable of supporting the entire weight of the unit  Lifting cables  ch
95. r to the HVAC unit and the ultraviolet bulbs  SEE WARNING ABOVE     2  Wearing soft cloth gloves and safety glasses  use two hands and firmly grasp the bulb at each  end     3  Rotate the bulb 90 degrees in either direction and move bulb away from the fixture and out of  unit     4  Carefully install anew replacement bulb in the fixture and rotate it 90 degrees in either direction  until itis firmly secured     5  If broken bulbs are found or if you are required to dispose of used bulbs  the proper warning  and cautions must be followed     6  Always use cloth gloves and suitable eye protection when cleaning or replacing these bulbs   Bulbs may break if dropped or handled improperly     Disposal of Bulbs    UV bulbs  like fluorescent bulbs  contain mercury  which is a regulated hazardous waste  The  disposal requirements for hazardous wastes are determined by local  state and federal guidelines   Check all regulations before disposing of bulbs to ensure you have met all requirements     Refer to the MSDS sheet from the bulb manufacturer for additional disposal  handling and safety  information     After replacing bulbs  close and latch all unit panels and reenergize power to the lights     CAH SVXOIB EN 97      TRANE    Troubleshooting    This section is intended to be used as a diagnostic aid only  For detailed repair procedures  contact  your local Trane service representative     Z  WARNING  Hazardous Service Procedures     The maintenance and troubleshooting procedures re
96. re is a rapid decrease in tension until the belt settles  in  To measure belt tension  use a belt tensiometer  See Figure 73    Determine actual deflection by depressing one belt with the belt  tensiometer and measuring the deflection relative to the other belts or to   Force Scale belt line  See Figure 74   Adjust the belt tension to the correct pounds force  and tighten all set screws to the proper torque     Figure 74  Belt tension measurement    Belt Span  64  Belt Span                           9    CAH SVX01B EN    Table 3  Typical sheave diameter and deflection force       Smallest sheave    Belt Deflection Force  Ibs   Super gripbelts and    Gripnotch belts and                            Cross diameter range Speed  rpm  unnotched gripbands notched gripbands  section  in   range Used belt New belt Used belt New belt  1 000 2 500 3 7 5 5 4 1 6 4  3 0 3 6  2 501 4 000 2 8 4 2 3 4 5 0  1 000 2 500 4 5 6 8 5 0 7 4  A  AX 3 8 4 8  2 501 4 000 3 8 5 7 4 3 6 4  1 000 2 500 5 4 8 0 5 7 9 4  5 0 7 0  2 501 4 000 4 7 7 0 5 1 7 6  860 2 500 n a n a 4 9 7 2  3 4 4 2  2 501 4 000 n a n a 4 2 6 2  860 2 500 5 3 7 9 7 1 10 5  B  BX 4 4 5 6  2 501 4 000 4 5 6 7 7 1 9 1  860  2 500 6 3 9 4 8 5 12 6  5 8 8 6  2 501 4 000 6 0 8 9 TG 10 9  Deen 500 1 740 11 5 17 0 14 7 21 8  ik mM 1 741 3 000 9 4 13 8 11 9 17 5    500 1 740 14 1 21 0 15 9 23 5  9 5 16 0  1 741 3 000 12 5 18 5 14 6 21 6  200 850 24 9 37 0 n a n a  12 0 16 0  D 851 1 500 21 2 31 3 n a n a  200 850 30 4 45 2 n a n a  18 0  2
97. ronic  components should be stored in conditions of  20 to 120  F and 5  to 95 percent relative humidity  non condensing  Electrical components are not moisture tolerant     Note  The warranty will not cover damage to theunitor controls due to negligence during storage   A controlled indoor environment is recommended for proper storage  For further storage  considerations  refer to  Storage Recommendations  on page 11     Z  WARNING  Grounding Required   All field installed wiring must be completed by qualified personnel  All field installed wiring    must comply with NEC and applicable local codes  Failure to follow these instructions could  result in death or serious injuries     On outdoor units  entrances are provided for field installation of high and low voltage wiring  through a pipe nipple connection in the base of the unit  As a standard  there are no penetrations  into the Custom air handler for any field provided wiring or device  Before installation  consider  overall unit serviceability and accessibility before mounting  running wires  power   making  cabinet penetrations  or mounting any components to the cabinet     Wiring to the unit must be provided by the installer and must comply with all national and local  electrical codes  The fan motor nameplate includes a wiring diagram  If there are any questions  concerning the wiring of the motor  be sure to write down the information from the motor  nameplate and contact your local fan motor manufacturer representa
98. roperly supported decking should be  installed inside the air handler section of the curb when this method is used  See Figure 1     NOTICE  Roof Curb Structurally Sound    Check with curb manufacturer and job engineer to ensure the roof curb is structurally sufficient  to support the weight of the unit  The curb should be checked to ensure it is level and square   Curb bowing  buckling  or sagging can lead to unit assembly and operation problems up to  complete failure     Figure L Cross section of typical curb installation on new construction         Screw secruing roof  felt to rigid insulation  or2x 10    Flashing   field supplied        Ss    Roofing felt     field supplied        4 x 4 cant   field supplied               H    EN hd    Roof deck       Support channels    CAH SVX01B EN 13    e TRANE     Pre Installation Requirements    Suggested Tools    14    N    o Q x Oo Uu E Y    Verify that the roof structure can adequately support the combined weight of the unit and curb  assembly     Ensure that the selected installation location provides sufficient service and operational  clearances     Remove any twist within the curb due to roof supports and square the curb    Level the curb    Secure the curb to the roof support members    Install 2 inch thick boards or rigid insulation around the curb    Install cant strips around the curb    Bring field supplied roofing felt up to the top of the curb nailing strips  Nail felt into place   Install field supplied flashing unde
99. rs are often installed in a pre post filter configuration  Be sure to note the order of  installation     Note  Filters must have an airtight seal to prevent air bypass        UP WN H    CAH SVX01B EN    e TRANE    Routine Maintenance    Side Load Filters    Drain Pans    CAH SVX01B EN    Most filters in custom units are installed in unitary sheet metal frames  If unit is provided with side  access rack  do the following for installation     2 inch or 4 inch flat filters  L Disconnect the power to the unit     2  Open the filter section access door and remove the filters and block offs from their installed  position     3  Slide the filter into the rack     4  Some side load racks will be provided with block off plates  Install them into the rack last before  closing the door     5  Close and secure the door  making certain the door closes snug against the block off   Cartridge or Bag Filters   To replace cartridge or bag filters    L Disconnect all electrical power to the unit    2  Remove the dirty filters and block offs from their installed position     3  Keeping the new bag filters folded  slide each filter into the filter rack  pushing them tightly  against the unit     Note  The pleats on bag filters should be in the vertical position   4  If using the optional pre filters  replace them on the appropriate filter rack     5  If fixed and adjustable block offs are provided with the unit  slide the fixed block offs into the  filter track before the adjustable block off   
100. s     Note  The portable operator display is not used for timeclock scheduling  To provide scheduling  you must use a Tracer Summit system     Connecting the Operator Display    To connect the portable operator display   L Open the controller enclosure door     2  Attach the operator display cable to the operator display connector on the controller circuit  board  The operator display receives power from the controller and turns on automatically  when it is connected to the controller     Setting Up the Operator Display    NOTICE   Equipment Damage    To clean the operator display  use a cloth dampened with commercial liquid glass cleaner   Spraying water or cleansers directly on the screen may result in equipment damage     This section shows how to calibrate the operator display touch screen and how to adjust the  brightness and contrast  To set up the operator display screens and security  see CNT SVPOIC EN  Programming Tracer MP580 581 Programmable Controller programming guide     Calibrating the Operator Display    CAH SVXOIB EN    To calibrate the operator display    1 Onthehome screen  press Setup  The Setup menu appears   2  Page down to view the next screen    3  Press Calibrate Touch Screen  A calibration screen appears     NOTICE   Equipment Damage    Do not allow the operator display to come in contact with sharp objects  This may result in   equipment damage    4  Touch thetarget using a small  pliable  blunt object  such as a pencil eraser or your finger  Hold  
101. scaling  erosion   corrosion  algae or slime  It is recommended that the services of a qualified water treatment  specialist be engaged to determine what water treatment  if any  is required  Trane assumes no  responsibility for equipment failures which result from untreated or improperly treated water  or  saline or brackish water     Ensure coil and condensate drain piping connections are complete   e Check the piping and valves for leaks     Open or close the valves to check operation     Thedrain lines should be open   e If unit has a refrigerant coil  ensure that it has been charged and leak tested according to the  instructions provided with the condenser equipment  Adjust the superheat setting   e Remove all foreign material from the drain pan and check the pan opening and condensate line  for obstructions   e For steam coils  slowly turn the steam on full for at least 10 minutes before opening the fresh  air intake on units with fresh air dampers   Motor Related Checks    Obtain an IOM from the motor manufacturer for the specific motor installed  The motor  manufacturer s recommendations take precedence for all matters related to the start up and  routine maintenance of the motor     Check the motor lubrication for moisture and rust     Remove and clean grease plugs to inspect       Ifmoistureis present  consultan authorized repair shop for bearing inspection replacement   This may require removal and transport of motor        fnomoistureis present  referto the motor 
102. sitioned  overhead and on the ground to guide  the crane or helicopter operator in  positioning the sections       Never stack the pipe cabinet and inlet  hoods on the unit as the unit is being  lifted       Do not attach the intake exhaust  hoods to the unit prior to lifting the  unit  Doing so may damage the  equipment  Attach the hoods to the  unitonly after all sections are in place       Remove all wooden blocks before  installing the unit to the roof curb     CAH SVXOIB EN    e TRANE    Installation   Mechanical    Unit Assembly    CAH SVX01B EN    All Trane air handlers are identified by a multiple character model number that identifies each  section  Itis located on the panel on the inside of the supply fan section access door  Be sure to refer  to the information on the nameplate when ordering replacement parts or requesting service     Note  If the unit is shipped as a complete assembly  go to    Coil Piping and Connections    on  page 53     Prior to unit assembly  refer to the unit submittal drawings and unit tagging for correct placement  of sections  Failure to review the submittal drawings could result in performance or assembly  problems  If there are any discrepancies  contact your local Trane sales representative before  proceeding     All shipping supports and crating on the face of the sections must be removed and discarded to  permit proper fit up and sealing of the surfaces     Outdoor units may be mounted on the roof with a roof curb or pier mount  Indo
103. steps 6 and 7 as necessary     0020    Straighten any coil fins that may have been damaged during the cleaning process   10  Confirm the drain line is open following the cleaning process    1L Allow the unitto dry thoroughly before putting it back into service    12  Replace all panels and parts and restore electrical power to the unit     13  Be careful any contaminated material does not contact other areas of the unit or building   Properly dispose of all contaminated materials     CAH SVXOIB EN 91    e TRANE    Routine Maintenance    Cleanable Cooling Coils    Cleanable cooling coils have removable headers for cleaning    1 Remove the headers    2  Useasmall nylon or fiber brush to clean the tubes    3  Flush the tubes with water    4  Install a new rubber sealing gasket and be sure it seats properly when the header is replaced    Note  Apply washers under the bolt heads  Bolts should be evenly tightened to 50 foot pounds of  torque  beginning in the center and working toward the outside     Refrigerant Coils     N WARNING  Hazardous Pressures     Coils contain refrigerant under pressure  When cleaning coils  maintain coil cleaning solution  temperature under 150 F to avoid excessive pressure in the coil  Failure to follow these safety  precautions could result in coil bursting  which could result in death or serious injury    To clean refrigerant coils    L Disconnect all electrical power to the unit     2  Wearing the appropriate personal protective equipment  use a soft
104. sure it s properly aligned with the remainder of    the curb  Anchorthis section securely so the base lugs can be used to pull the next section for  base connections     Install 3 16 inch x 125 inch grey butyl tapeto bottom rail of installed section allowing the tape  to turn up each side wall approximately 8 inches  Remove paper backing from butyl tape  This  will ensure the module to module joint is water tight along the bottom     Lift next section onto roof curb using come alongs to pull securely to first section  See    TCC  J oining Sections   Edge to Edge  on page 33 for assembly details     TCC Flat Base to Steel Dunnage or Concrete Pad    Figure 19  Steel base to concrete pad    32    Important  Units must be installed level for proper drainage of condensate from the drain pan    and for squareness of the sections during installation  In addition  each section in a  multi section unit must be properly supported     A base designed for concrete or steel dunnage has a flat channel basethat allows the sections  to be installed level and square  Pad and dunnage should have unit perimeter marked clearly  allowing a completely square installation  See Figure 19 and Figure 20     Install first section and anchor with best method to hold securely   Proceed with remaining sections per installation guidelines     Figure 20  Flat base to steel dunnage                                                             Air handler  base structure                Air handler              
105. tainer for protection and ease of handling     Selecta well drained area  preferably a concrete pad or blacktop surface       Place the unit on a dry surface or raised off the ground to ensure adequate air circulation  beneath the unit and to ensure no portion of the unit will contact standing water at any time       Loosen the belttension on the drive belts   e Cover the unit securely with a canvas tarp     Do not stack units      Do not pile other material on the unit     Preparing the Unit Site    12    NOTICE  Microbial Growth     The roof curb or foundation must be level and the condensate drain at the proper height for  proper coil drainage and condensate flow  Standing water and wet surfaces inside the  equipment can become an amplification site for microbial growth  mold   which may cause  odors and damage to the equipment and building materials     NOTICE  Level Foundation     A level foundation is critical to proper unit and door alignment  operation  and sealing  Failure to  level and align sections properly can lead to structural damage       Ensure the installation site can support the total weight of the unit  Refer to the unit submittals  for weights       Allow sufficient space for adequate free air and necessary service access  Refer to submittals  for specific minimums       Allow room for supply and return piping  ductwork  electrical connections  and coil removal     e Ensure there is adequate height for condensate drain requirements  See    Drain Pan Trap
106. the unit  The curb should be checked to ensure it is level and square   Curb bowing  buckling  or sagging can lead to unit assembly and operation problems up to    complete failure   TCP Standard Roof Curb    Figure 4  Standard roof curb                               Air handler  base structure             Roof curb                                           18    Insulation    The TCP unit exterior base channel is  constructed to overhang the roof curb  Unit  support is provide by a square tube channel  locate inside of exterior base channel  See  Figure 4  The standard curb should be designed  to properly support the unit s weight without  bow and sized to fit within the perimeter base  channel     For large units shipped in sections  see  additional requirements in    TCP Roof Curbs for  Large Units with Shipping Splits    on page 21     CAH SVXOIB EN    S TRANE     Installation   Mechanical    TCP Structural Roof Curb and I Beam Dunnage    The TCP base for structural roof curbs  see Figure 5  and l beam dunnage  see Figure 6  are  designed to sit directly onto unit support with no overhang  The structure should be designed to  properly support unit weight without bow and sized to the unit s perimeter exterior base channel     For large units shipped in sections  see additional requirements in    TCP Roof Curbs for Large Units  with Shipping Splits    on page 21     Figure 5  Structural roof curb Figure 6  I beam dunnage mount                                                
107. ther hoods   2  Using the factory provided screws mount the weather hoods to the unit     3  On larger units  weather hoods may be large enough to require angled down supports  In those  cases  the angles are shipped attached to the hood but will need to be connected to the air  handler by the installing contractor  See Figure 49     Note  Itis required that the hoods be sealed to the unit using field provided caulk or gasket     Figure 49  Hood installation    Butyl caulk tape    AHU outdoor roof 1 00 W x  125T            Screw self driller  10 16 x  750    Butyl caulk tape  1 00 W x  125T        Nut Hex  31 18       Bolt  313 18 x  750 Hex  Hood       Bracket Support        NA Nut Hex  31 18    Angle Hood Support   when required   Bolt  313 18 x  750 Hex    Detail A    52 CAH SVXOIB EN      TRANE    Coil Piping and Connections    General Coil Piping Recommendations    Proper installation  piping  and trapping is necessary to ensure satisfactory coil operation and to  prevent operational damage     CAH SVX01B EN    Support all piping independently of the coils     Provide swing joints or flexible fittings on all connections that are adjacent to heating coils to  absorb thermal expansion and contraction strains     If the coil was ordered with factory mounted controls  install the control valves  The valves ship  separately     Note  The contractor is responsible for supplying the installation hardware     For best results  use a short pipe nipple on the coil headers prior to
108. this manual to minimize installation and  startup difficulties     Each Trane air handler section is provided with a nameplate which identifies the type of section   customer tagging information  the section serial number  the section position  the service model  number  and electrical data     Note  This information is required when ordering parts or requesting service for a Trane air  handler     Operating Environment    When considering the placement of the air handler  it is important to consider the operating  environment  The acceptable ambient temperature range for unit operation is  402F to 1409F   402C  to 60  C      For heating applications  a special motor may be required to withstand the higher temperatures   Motors with Class B insulation are acceptable for ambient temperatures up to 1049 F  while motors  with Class F insulation can withstand ambient temperatures to  1402 F  609 C      For the units furnished with gas furnaces  the heating demands require a special motor to  withstand the higher temperatures  These motors are furnished with Class  H  insulation to  withstand this rigorous duty     Note  Units with UL approval have a maximum ambient temperature requirement of 1049F  The  customer should provide adequate freeze protection for the coils  See   Coil Winterization   on page 93 for more information     Unit Description  Custom Climate Changer  air handlers are designed for a variety of controlled air applications     The basic unit consists of a fan  h
109. tive for assistance       TRANE    Pre Installation Requirements  Receiving Checklist    Based on customer requirements  Trane air handlers can ship as complete units or as individual  sections to be field assembled     Upon receiptofthe air handler s   a thorough inspection should be performed to note any shipping  damage that may have occurred and that the shipment is complete  All factory shipping protection  should be removed immediately to allow complete access for the inspection     Note  The shipping protection provided by the factory is for transit protection only and should not  be used as a jobsite storage cover     Note  Delivery cannot be refused  Trane is not responsible for shipping damage    e Check all access doors to confirm that the latches and hinges are not damaged      nspectthe interior of each section for any internal damage    Note  Concealed damage must be reported within 15 days of receipt      Inspect the coils for damage to the fin surface and or coil connections      Ifthe unit was ordered with factory mounted controls  locate all sensors     Note  Items that cannot be factory mounted should ship inside the control enclosures or should  be packaged inside the fan or mixing box section     e Check all control devices attached to the unit exterior and confirm that they are not damaged     Manually rotate the fan wheel to ensure free movement of the shaft  bearings  and drive     Inspect the fan housing for any foreign objects     e Ifthe unitis ship
110. tutes  or refrigerant additives could result in death or serious injury or equipment damage        2010 Trane All rights reserved CAH SVXOLB EN    CAH SVX01B EN    e TRANE    Wamings  Cautions and Notices    ZAWARNING  Hazard of Explosion     Use only dry nitrogen with a pressure regulator for pressurizing unit  Do not use acetylene   oxygen or compressed air or mixtures containing them for pressure testing  Do not use mixtures  of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as  they may become flammable and could result in an explosion  Refrigerant  when used as a trace  gas should only be mixed with dry nitrogen for pressurizing units  Failure to follow these  recommendations could result in death or serious injury or equipment or property only damage     Ultraviolet  UV  Germicidal Irradiation Lights    The United States Environmental Protection Agency  EPA  believes that molds and bacteria inside  buildings have the potential to cause health problems in sensitive individuals  If specified  Trane  provides ultraviolet lights  UV C  as a factory engineered and installed option in select commercial  air handling products for the purpose of reducing microbiological growth  mold and bacteria   within the equipment  When factory provided  polymer materials that are susceptible to  deterioration by the UV C light will be substituted or shielded from direct exposure to the light  In  addition  UV C radiation can damage human tissue  n
111. uction lines all the way  to inner side panel to prevent heat gain and unwanted condensation     Components  Installing the suction line requires field installation of these components  a filter   access port  and a Frostat    control when the refrigerant coil is used with Trane condensing units   Position them as close to the compressor as possible     Note  Placement of the Frostat control is illustrated in Figure 58 on page 60       Filter  The suction filter prevents contaminants  introduced during installation  from entering  the compressor  For this reason  the suction filter should be the replaceable core type  and a  clean core should be installed after the system is cleaned up       Access port  The access port is used to determine suction pressure  This port is usually a  Schraeder valve with a core     e Frostat   coil frost protection  The Frostat control is the preferred method for protecting  evaporator coils from freezing when the refrigerant coil is used with Trane condensing units   It senses the suction line temperature and temporarily disables mechanical cooling if it detects  frost conditions  The control is mechanically attached to the outside of the refrigerant line  near  the evaporator  and wired to the unit control panel       Ball shutoff valve  Adding manual  ball type shutoff valves upstream and downstream of the  filter simplifies replacement of the filter core     CAH SVXOIB EN    e TRANE     Coil Piping and Connections    Examples of Field Insta
112. uding remote disconnects and discharge all motor start run  capacitors before servicing  Follow proper lockout tagout procedures to ensure the power  cannot be inadvertently energized  For variable frequency drives or other energy storing  components provided by Trane or others  refer to the appropriate manufacturer s literature for  allowable waiting periods for discharge of capacitors  Verify with an appropriate voltmeter that  all capacitors have discharged  Failure to disconnect power and discharge capacitors before  servicing could result in death or serious injury     Front Load Filters    Most filters in custom units are installed in unitary sheet metal frames  Filters are secured with a  metal clip  There are several different styles     To install filters    Disconnect power to the unit   Open or remove the filter clip   Remove the filter from the rack     PWN FH    Install new filters with the directional arrows pointing in the direction of airflow   5  Secure the filter using the appropriate clip for each filter     Review Figure 44 through Figure 47 for an explanation of the methods for securing the different  types of filters     The filters are often installed in a pre post filter configuration  Be sure to note the order of  installation     Note  Filters must have an airtight seal to prevent air bypass     49    e TRANE     Installation   Mechanical    Figure 45  C 86 fastener  shown  or C 77 fastener holds 4   inch pleated filters    Figure 44  C 70 fastener h
113. ulation is clean and dry  Wet insulation in an area that is  normally considered to be  dry  can indicate an operational problem  referto  Troubleshooting   on page 98 for further information   The equipment should be inspected a minimum of every six  months or more frequently as operating experience dictates     Accumulated dirt and other organic matter exposed to water or extended periods of high relative  humidity  60 percent or higher  can support microbial growth  which must be removed to prevent  the unit from becoming a contaminant source     If evidence of contamination exists in either the wet or dry sections      Determine and eliminate the cause      Remove the contamination      Sanitize the affected area    See  Troubleshooting  on page 98 for assistance in identifying the cause     Z  WARNING  Hazardous Voltage     Disconnect all electric power  including remote disconnects before servicing  Follow proper  lockout  tagout procedures to ensure the power can not be inadvertently energized  Failure to  disconnect power before servicing could result in death or serious injury     CAH SVXOIB EN    e TRANE    Routine Maintenance     N WARNING  Hazardous Chemicals     Coil cleaning agents can be either acidic or highly alkaline  Handle chemical carefully  Proper  handling should include goggles or face shield  chemical resistant gloves  boots  apron or suit as  required  For personal safety refer to the cleaning agent manufacturer   s Materials Safety Data  Sheet and f
114. ult in death or serious injury     Inspecting and Cleaning Fans    88    Fan sections of air handlers should be inspected every six months ata minimum or morefrequently  if operating experience dictates  If evidence of microbial growth  mold  is found  identify and  remedy the cause immediately  Refer to  Troubleshooting  on page 98 for possible causes and  solutions  To clean the fan section     L Disconnect all electrical power to the unit   2  Wearing the appropriate personal protective equipment  remove any contamination     3  Vacuum the section with a vacuum device that uses high efficiency particulate arrestance   HEPA  filters with a minimum efficiency of 99 97 percent at 0 3 micron particle size     4  Thoroughly clean any contaminated area s  with a mild bleach and water solution or an EPA   approved sanitizer specifically designed for HVAC use     5  Immediately rinse the affected surfaces thoroughly with fresh water and a fresh sponge to  prevent potential corrosion of metal surfaces     6  Allow the unit to dry completely before putting it back into service     7 Becareful any contaminated material does not contact other areas of the unit or building   Properly dispose of all contaminated materials and cleaning solution     CAH SVXOIB EN    e TRANE    Routine Maintenance    Fan Bearing Lubrication    CAH SVX01B EN    NOTICE   Bearing Failure    Do not mix greases with different bases within the bearing  Mixing grease within the bearing  may result in premature be
115. until the beeping stops  A second calibration screen appears     5  Again  touch the target with the object  Hold until the beeping stops  The Advanced Selection  screen appears     6  Press Home  The home screen appears     73    e TRANE    Controls Interface    Adjusting Brightness and Contrast    To adjust the brightness and contrast of the operator display     L  2   3   4  To increase the brightness  press the buttons along the top row  in sequence  from left to right     On the home screen  press Setup  The Setup menu appears   Page down to view the next screen   Press the Adjust Brightness and Contrast buttons  The Brightness and Contrast screen appears     To decrease the brightness  press the buttons from right to left     Note  Contrast adjustment is not available on all computer display models     5     6     To increase the contrast  press the buttons along the bottom row  in sequence  from left to right   To decrease the contrast  press the buttons from right to left     Press Home  The home screen appears     Extemal Communications Port    On units that have been selected with the external communications port  both the operator display  and Rover service tool can be connected without shutting off the unit through the external  communications port  Remove the cover plate on the port and plug into the RJ  11 port for the  operator display or the RS 485 port for the Rover service tool  This enables continuous operation  of the Air Handling unit without disruption t
116. ve       Thermal  expansion  25  lt   gt   valve  TXV  iQ    E    Filter drier                Pump down     solenoid valve       Distributor    Evaporator coil with  intertwined circuiting            eee Liquid               so  oe  23    oe Solenoid       m Ee valve Filter drier  6 OP   Thermal   OP expansion   valve  TXV     Distributor    Pitch the liquid line slightly   1 inch 10 feet   1 cm 3 m    so the refrigerant drains  toward the evaporator  See Figure 61     Provide one expansion valve per distributor     Slightly pitch the outlet line from the suction  header toward the suction riser   that is    1 inch 10 feet  1 cm 3 m  in the direction of  flow  Use the tube diameter that matches  the suction header connection       Arrange the suction line so the refrigerant    gas leaving the coil flows downward  past  the lowest suction header outlet  before  turning upward  Use a double elbow  configuration to isolate the thermal  expansion valve bulb from other suction  headers     For horizontal tubing  usethetube diameter  recommended by the condensing unit  manufacturer     For the vertical riser  use the tube diameter  recommended by the condensing unit  manufacturer  Ensure the top of the riser is  higher than the evaporator coil     Pitch the suction line slightly   1 inch 10 feet   1 cm 3 m    so the refrigerant drains  toward the evaporator     Insulate the suction line     Only use a    trim    solenoid valve for  constant volume  humidity sensitive  applications 
117. ve     ACFM   CFM   SQRT 0 075 p    Where    ACFM   Actual airflow  ft3  min  corrected for non standard air density   p   Density  Ibm  ft3  of the air at the inlet to the fan     Note  Alternative units  including SI  can be used in place of the IP units above although the  K factor must be converted appropriately     Constant Factor K    CAH SVXOIB EN    The constant factor K is unique for each fan and is primarily a function of the area and the geometry  of the fan inlet  Pre engineered factors are available from the factory for fan types where the airflow  measurement system is available     Field obtained factors can provide maximum accuracy  To obtain the factor in the field  measure  the differential pressure being output from the transmitter while measuring the airflow through the  system  Once these two values have been measured  simply solve for K using the following  equation     K   ACFM  SQRT DP    Where    K   Field provided constant factor    ACFM   Actual airflow  ft3  min  being measured at the air density being measured   DP   Differential pressure  inches w g   being measured by the transmitter     83      TRANE    Extemal Insulating Requirements    84    NOTICE  Microbial Growth     Wet interior unit insulation can become an amplification site for microbial growth  mold   which  may cause odors and damage to the equipment and building materials  If there is evidence of  microbial growth on the interior insulation  the insulation should be removed and repl
118. ximum of 4  on an MP 580 581 controller in lieu of the default zero     Note that the adjustment of the  Zero  and  Span  controls on the transmitter itself are not  required at time of installation  The transmitter is factory calibrated to the range selected and  cannot be significantly adjusted to  tighten  the range closer to the pressure being read for the  given application  The adjustments are primarily provided to account for any drift that may occur  over time     Transmitter Calibration    Thetransmitter is factory calibrated to a specific pressure range with a 0 20 inch w g  range being  used in most cases  To check calibration and to adjust if necessary  consult the transmitter  manufacturer or the factory for specific procedures     Thetransmitter outputs a linear  4 20 mA signal representing a differential pressure measurement   With this measurement  the airflow through the fan can be calculated using the following equation     CFM   K   SQRT DP    Where    CFM   Airflow  ft3  min   assuming a standard air density of 0 075 Ibm  ft3    K   A constant factor that   s unique for each fan  See next section for more information   DP   Differential pressure  inches w g   being measured by the transmitter     Significant differences in elevation and or temperature will affect the density of air  For air at  a constant  non standard density  a field obtained K factor can be used  Alternatively  the  following equation can be used to continuously correct the equation abo
119. y result in damage to intemal components     Line sizing  Proper suction line sizing is required to guarantee the oil returns to the compressor  throughout the system s operating envelope  At the same time  the line must be sized so that the  pressure drop does not excessively affect capacity or efficiency  To accomplish both objectives  it  may be necessary to use two different line diameters  one for the horizontal run and for vertical  drops  and another for the vertical lifts     Routing  To prevent residual or condensed refrigerantfrom    free flowing    toward the compressor   install the suction line so it slopes slightly   that is  by Ya inch to 1 inch per 10 feet of run   toward  the evaporator  When the application includes a suction riser  oil must be forced to travel the height  of the riser  Riser traps and double risers are unnecessary in the suction line when the refrigerant  coil is used with Trane condensing units     Avoid putting refrigerant lines underground  Refrigerant condensation or installation debris inside  the line  service access  and abrasion corrosion can quickly impair reliability      Insulation  Any heat that transfers from the surrounding air to the cooler suction lines increases  the load on the condenser  reducing the system s airconditioning capacity  and promotes  condensate formation  adversely affecting indoor air quality   After operating the system and  testing all fittings and joints to verify the system is leak free  insulate the s
120. y sections     CAH SVX01B EN    e TRANE     Installation   Mechanical    TCP Base Section Assembly with Flat Floor   Note  Failure to completely compress the gasketing may result in air leakage    L Join the two units and secure with factory provided 5 8 inch flat washers and 5 8 inch X 2 1 2   inch grade 9 bolts though each of the six holes  See Figure 10    2  Caulk the overlapping flange along the length of each split to maintain a seal    Note  Use a polyurethane or equivalent caulk    3  Beforeinstalling the pre cut 4 inch 18 gauge joining strips  pre drill holes in the floor using the  4 inch strip as a guide with a 7 32 inch drill bit at 12 inch centers    4  After holes are pre drilled  apply an ample bead of caulkto the joint then install 4 inch strip with   14 sheet metal screws uniformly straddling the split     5  In cases of tread plate floor  some job specifications may call for the seam to be welded  In those  cases make sure the sections are pulled together tightly then weld with appropriate method   The floor construction in those cases will be such that the heat from welding will not affect the    insulation     Figure 10  TCP base assembly with flat floor        14 SMS screw    Joining strip    1 f    3 in  x 1 8 in  gasket   ff  y oW    4 in  x 1 4 in  gasket                  je  Joining trim N mM      Add caulking before    Top floor    N zi installing J strip                                                             __ Trim gasket after     strips are 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Una linea completa di pannelli comando dedicati per installazione a  SERVICE MANUAL YCV80/YCV80Q  LP840-LP850-860 User`s Guide.fm  DP2 SERIE PRINCE 300/500/700/1000W  日本語  Approx APPHS03V2 headset  console UseR GUide  G53F User`s Manual 2.2 - Gemini Telescope Design  Severin BR7954 vacuum cleaner  Télécharger ce fichier    Copyright © All rights reserved. 
   Failed to retrieve file