Home
        Trane IntelliPak Modular Series User's Manual
         Contents
1.                 Or       Liquid Line 2  Service Valves High  ig  Pressure  Cutout  High           Compressor  Cutout  Schrader  Valve    Compressor Valve    Figure O M Z Typical water cooled  SXWG  compressor section components     SCXG SVX01B EN 105    e TRANE    Owner       Inlet Guide Vanes On occasion  the inlet guide vane actuator  Perform the following procedure every or inlet guide vanes may need to be  six months for proper inlet guide vane removed  For proper adjustment of inlet  operation  guide vanes and or actuator  see Figure  1  Spray all parts of guide vane assembly O M 8   with WD40  Pg aT a SUIT EE  2  Spray all steel parts of guide vane Note  Perform this procedure monthly if  assembly with ZRC the unit is in a coastal area or corrosive    3  Spray hubs and moving parts with dry environment     silicone lubricant  Mobil Mobilux 2  Shell  alvonia 2  or equivalent      Linkage          Figure O M 8  Proper adjustment of inlet guide vanes     106 SCXG SVX01B EN    Coil Fin and External Cleaning    Keep coils clean to maintain maximum  performance  For operation at its highest  efficiency  clean the refrigerant coil often  during periods of high cooling demand or  when dirty conditions prevail  Clean the  coil a minimum of once per year to  prevent dirt buildup in the coil fins  where  it may not be visible     Remove large debris from the coils and  straighten fins before cleaning  Remove  filters before cleaning     Clean refrigerant coils with cold water  and
2.             File Number PL UN SCXF SVX01B EN 700  The Trane Company Supersedes SCXG SVX01A EN  A Division of American Standard Inc  a    WWW          com Stocking Location LaCrosse   Inland  For more information contact  your local district office or  e mail us at comfort trane com SinceTheTrane Company has a policy of continuous product improvement  it reserves the right to change design    An American Standard Company and specifications without notice     
3.       IntelliPak     Commercial Self Contained  Modular Series  20 35 Ton                   Models     BO  and later Design Sequence    SCWG  020   025   030   035  SIWG  020   025   030   035  SCRG  020   025   032   SIRG  020   025   032       July 2000 SCXG SVX01B EN    e TRANE      American Standard Inc  2000    About This Manual  Literature Change History    Use this manual for commercial self   contained models SCWG  SIWG  SCRG   and SIRG  This is the original issue of this  manual  It provides specific installation   owner maintenance  and diagnostic  troubleshooting instructions for    BO    and  later design sequences  The    BO    design  sequence includes the VFD option  change from Square D Altivar 66 to  Altivar 58  For information on previous  design sequences  contact your local  Trane representative     Warnings and Cautions    Warnings in this manual indicate potential  hazardous situations that can result in  death or serious injury     Cautions in this manual indicate potential  hazardous situations that may result in  minor or moderate injury and or  equipment damage     Examples     Disconnect electrical power  source before servicing unit to  prevent injury or death from  electrical shock     Use only copper conductors for  electrical unit connections to  prevent equipment damage           Common HVAC Acronyms   For convenience  a number of acronyms  and abbreviations are used throughout  this manual  These acronyms are  alphabetically listed and defined
4.      1 15   Occupied Zone Temperature   Cooling  93   Occupied Zone Temperature   Heating  94    Occupied Unoccupied Contacts 79  Occupied Unoccupied Inputs 78  Occupied Unoccupied Switching 91  Operating Procedures 111   Option Menu and Keypad Operation 69  Optional Controls 5    P    Periodic Maintenance Checklists 110   Piping Components 109   Plenum 41   Points List 77   Pre Installation Checklist 16   Pre Startup Checklist 63   Pre Startup Procedures 39   Pressure Cutouts 96   PRESSURIZE sequence          80   Program Button 66   Program Menu 66   Programmable Night Setback Zone  Sensors 55   Programmable Night Setback Zone  Sensor Installatio 56   Programming the Time Clock Option  73   PURGE sequence  D  81   PURGE with duct pressure control  E   81    R    Receiving 63   Receiving and Handling 9   Receiving Checklist 9   Refrigerant Charge 104   Refrigerant Coils 107   Refrigerant Emissions 102  103   Refrigerant Leak Testing 103   Refrigerant Piping 36   Refrigerant System 102   Remote Human Interface Module  Option 80   Remote Human Interface Panel 58   Remote Mounted Thermostat Option  50   Remote Mounted Thermostat Wiring  50   Remote Panel Indicator Signals From  UCM to ZSM 70   Remote Zone Sensor Options 51   Reset based on outdoor air tempera   ture 94   Reset based on zone temperature 94       121    e TRANE    Return Air Humidity Sensor Failure  115   Return Air Temp Sensor Failure 115   Return Air Temperature Sensor 90   RHI 58  80   Rigging and Handling 13 
5.      2  Fan isolator locations     SCXG SVX01B EN 39    e TRANE    Note  The compressors and fan assembly    are internally isolated  Therefore  external  isolation devices  spring mounting  isolators  are at the discretion of a vibration  specialist consulted by the building or  HVAC system designer  In general  the  Trane Company does not recommend  double isolation     40    Installation    Unit Vibration Isolator Option    Vibration isolation is not necessary for the  unit since the factory internally isolates  the fan and compressors  thus creating  double isolation  The Trane Company  strongly recommends that you consult a  vibration specialist when considering  double isolation  If job requirements  dictate unit isolators  use a housed spring  isolator with a locating pin  Factory   provided unit isolators are type CP and  indicate the spring number on the outer  housing  See Figure I PR 3  Set the  spring type vibration isolators in position  before completing electrical  piping  or  duct connections  Units require four  isolators per unit  Reference the isolator  placement sheet that ships with the  isolators to indicate proper placement     Unit Isolator Installation Procedure  Follow the procedure below to install  isolators    1  Position the isolators under the unit  base referring to the isolator placement  sheet that ships with the unit isolators   Lift one end of the unit at a time to  position the isolators  Fasten the  isolators to the floor using anchor bol
6.      Wall Mounting the RHI Panel   1  Prior to mounting the panel  the  microprocessor module must be  removed from the enclosure  Complete  step 2 in the previous discussion    Mounting on a 4 in  x 4 in  Electrical  Box   before proceeding     2  With the microprocessor removed   refer to Figure I PR 31 for the location of  the mounting holes to be used for wall  mounting     3  Place the enclosure against the  mounting surface and mark the  mounting holes     Note  The top of the enclosure is marked  with                 4  With the enclosure in the correct  position  remove the enclosure and  drill the necessary holes in the surface  for the appropriate fasteners   plastic  anchors  molly bolts  screws  etc      5  Remove the necessary knockouts for  the wire or conduit entry before  mounting the panel     6  Place the enclosure back onto the  surface and secure it with the  appropriate screws     7  Follow step 5 in the previous section    Mounting on a 4  by 4  Electrical  Box     to replace the microprocessor  within the enclosure     59    TRANE    Installation                                                                                                                                                                                                                                                                           4 78    0 20 X 0 40 SLOT      6 PLACES 20 25   HOLE  EIU i  i 1 id  6 08       10 70 12 01 3 40      10 98      e    2       4 31         0 65      
7.     12  Insulate discharge and suction lines  with the insulation provided     13  Remove panel FLR and open the  bottom control panel door  FLL  Pull the  fan motor leads  coiled in the fan  section  through the knockout in the  bottom of the fan section to the control  panel  Ensure that the bushing is  installed in the hole to prevent the  wires from chafing  Refer to the unit  wiring diagrams to connect the fan  motor leads properly and ensure  correct phase sequencing     IntelliPak Units  UCM  Only   14  Remove panels FML  FMM  and FMR    15  Pull the circular plug connector  CPC   from the compressor section through  the knockouts into the fan section   Install the bushings  provided on the  wiring harnesses  in the knockouts    16  Using the CPC wiring diagram   connect the male CPC to the female  CPC in the top control panel    17 If the unit has the mixed air  temperature option  route the capillary  tube on back of the filter rack     Units with Thermostat Only   18  Remove panel FMR  See Note 1 on  Figure         10    19  Pull frost protection wires from the  bottom control panel throughknockouts  in bottom of fan section  Route wires to  the appropriate frost protection  switches on the evaporator coil   Reference the unit wiring diagrams to  connect frost protection wiring  connectors     Air Cooled Units Only    20  Route the refrigerant circuit wires for  circuits 1 and 2 from the bottom control  panel through the knockouts to the  solenoid valves The solenoi
8.     23 _ Maximum Heating Setpoint 43 to 96 F 96 F  I  I     OPTION     Option Value Option Number     and    Use       Figure       8  Typical option menu screen     SCXG SVX01B EN 69    e TRANE    Note  On both programmable zone sensor    options  changing either option 9 or 10 will  erase the current program  To avoid  reprogramming  set options 9 and 10  before programming     Intelligent Copy    Note  Once you have used Intelligent    Copy  you cannot use it again until you  ERASE all weekday and weekend time    periods by pressing ERASE for 5 seconds     If your heating and cooling requirements  are the same for each day of the week   and for each day of the weekend  your  ZSM is designed to employ Intelligent  Copy    To program the five weekdays  Monday  through Friday  program only one  weekday  Likewise  to program the  weekend  Saturday and Sunday  pro   gram only one day  After programming  one weekday and or one weekend day   Intelligent Copy automatically copies your  program to the other days     Using Intelligent Copy    1  Be sure to select the seven day  programming format in the Options  Menu  See Tables I P 1 and       2    2  Be sure the entire program is blank    3  Go to the program menu    4  Enter your setpoint parameters   Intelligent Copy will automatically copy  these parameters to the other  weekdays    5  Depress the DAY pushbutton until a  weekend day icon appears    6  Enter setpoint parameters  Intelligent  Copy will automatically copy these  p
9.     SXWG 29   SXWG 30 27  12 2  25  11 3    SXWG 35 27  12 2  27  12 2           Table O M 2  Air Cooled Unit  SXRG  Refrigerant Charge                Unit Size Circuit 1 Circuit 2 Circuit 1 Circuit 2  Charge Ibs         Charge Ibs   kg    SXRG 20 B 10T A 10T 36 36   SXRG 25  32 B 10T    15   36 58   104    To charge the system  complete the   following procedure    1  Charge liquid refrigerant into the liquid  line service valve of each compressor  circuit  The vacuum will draw some of  the required refrigerant into the  system  See Figure O M 7 on page 105    2  Complete the charging process by  charging gaseous refrigerant into the  suction line shrader valve with the unit  running  However  make sure that  some refrigerant is present in each  circuit before starting the compressors   The refrigerant container should be  upright so that gaseous refrigerant is  drawn off the top     Note  Charge each circuit with R22  See  Tables O M 1 and O M 2     Ax CAUTION    Do not allow liquid refrigerant to  enter the suction line  Excessive  liquid will damage the  compressor        SCXG SVX01B EN    e TRANE    Owner       Compressor  Junction           Oil Charging Pressure i  iauid Li Valve Relief Suction  Liquid Line 12  Line  Service Valves        Front View  Discharge  uda     N Compressor    f     lt  J Junction  Suction   Box  ai t   Discharge     Line     wil   Oil Level  Oil Level roe     Sight Glass  Sighi Glass H gh E    2 Oil Charging  uro au TTS Dim     Valve  Top View 
10.     s  without Cover e     Figure I PR 23  Typical zone sensor installation     SCXG SVX01B EN    Programmable Night Setback  Zone Sensors    Programmable night setback  NSB  zone  sensors provide programming and zone  temperature sensing for the self   contained unit  It allows the user to  monitor room temperatures and  program settings in the space  without  having to access the unit control panel     Reference programming instructions for  these zone sensors on page 64     SCXG SVX01B EN    Installation    e TRANE       Constant Volume Zone Sensor    BAYSENS019 Description   This seven day programmable sensor  with night setback has four periods for  occupied unoccupied programming per  day  If power is interrupted  the program  retains in permanent memory  If power is  off longer than 2 hours  only the clock and  day may have to be reset     The six programming keys on the front of  the zone sensor allow selection of system  modes  heat  cool  auto  and off   two fan  modes  on and auto   The zone sensor  has dual temperature selection with  programmable start time capability    The occupied cooling setpoint ranges  between 40 and 80          warmup  setpoint ranges are between 50 and 90 F  with a 2 degree deadband  The  unoccupied cooling setpoint ranges  between 45 and 98 F The heating  setpoint ranges between 43 and 96 F    Two liquid crystal displays  LCD  display  zone temperature  setpoints  week day   time  and operational mode symbols     The DIP switches on the 
11.    Digit 15  16   Motor HP    05   07   10   15   20   25     5 HP Motor   75 HP Motor  10 HP Motor  15 HP Motor  20 HP Motor  25 HP Motor    Digit 17  18  19   Fan RPM    085  090  095  100  105  110    850 rpm  900 rpm  950 rpm  1000 rpm  1050 rpm  1100 rpm    115  120  125  130  135  140  145  150  155  160  165  170  175    1150 rpm  1200 rpm  1250 rpm  1300 rpm  1350 rpm  1400 rpm  1450 rpm  1500 rpm  1550 rpm  1600 rpm  1650 rpm  1700 rpm  1750 rpm  180 1800 rpm  185 1850 rpm    Digit 20   Heating Type     Steam Coil  LH     Hot Water Coil  LH     Electric Heat  1 Stage     Hydronic Heat Ctrl Interface     Elec  Heat Ctrl Interface  1 stage  Steam Coil Ship Separate  LH  Hot Water Coil Ship Separate  LH    Steam Coil  RH     Hot Water Coil  RH     Steam Coil Ship Separate  RH     Hot Water Coil Ship Separate  RH    None                   gt     igit 21   Unit Isolators    lsopads    Spring Isolators    None  igit 22   Unit Finish    Paint   Executive Beige    Protective Coating    Protective Coating w  Finish Coat  Digit 23  0   None  Digit 24   Unit Connection  1   Disconnect Switch  2   Terminal Block  3   Dual Point Power    Digit 25   Industrial Options        Protective Coated Evaporator Coil       Silver Solder  C  D  E    Ng          ozmumvuz    w      Stainless Steel Screws    AandB    AandC    SCXG SVX01B EN      Drain Pan Type  Galvanized Sloped  Stainless Steel                oe ere             8        X  57  E   g                          3   N             
12.    The SCRG SIRG air cooled condenser  should be wired to the control panel of  the SCRG SIRG unit to ensure proper  system operation  Reference unit wiring  diagrams for correct terminal locations   Table I PR 3 provides recommended  wires sizes for length of run     Table I PR 6  Control Wire Size and Maxi   mum Length       Wire Gauge Max  Wire Length  22 30 ft   20 50 ft   18 75 ft   16 125 ft   14 200 ft        SCXG SVX01B EN    Standard with All Units        Figure         15  BAYSENS017  Zone Temperature Sensor Only    CV Unit Zone Sensor Option    Figure I PR 16  BAYSENS008   Dual setpoint  manual automatic  changeover sensor  Accessory Model  Number Digit 6   E    VAV Unit Zone Sensor Option       Figure I PR 17 BAYSENS021   Single setpoint sensor with system  function lights  Accessory Model Number  Digit 6   H    SCXG SVX01B EN    e TRANE    Pre Startup  equirements       installation       Remote Zone Sensor Options    Zone sensor options are available and can be ordered with the unit or after the unit  ships  Following is a full description of zone sensors and their functions  Installation  instructions are on page 53  Instructions for the programmable zone sensor are on  page 55  Refer to Table O GI 2 on page 79 for the zone sensor temperature vs   resistance coefficient curve     BAYSENSO17B Description   This zone sensor module ships with all units  and can be used with                5019   BAYSENS020  or       5    5021 remote sensors  When this sensor is wi
13.    e CV unoccupied mode indicator  CV units  only    e Alarm   e Fan run request   e Water pump request  water cooled  only     Analog input  e Airside economizer damper minimum  position    Analog output  e Outside air damper actuator    Heat Module   e Analog output    GBAS Module     Binary inputs  e Demand limit contacts    Binary outputs   e Dirty filter relay   e Refrigeration fail relay  e Heat fail relay   e Supply fan fail relay   e Active diagnostics    Analog inputs     Occupied zone cooling setpoint     Occupied zone heating setpoint     Unoccupied zone cooling setpoint     Unoccupied zone heating setpoint or  minimum outside air flow setpoint     Supply air cooling setpoint     Supply air heating setpoint     Supply air static pressure setpoint    ECEM Module     Analog inputs  e Return air temperature  e Return air humidity    In addition  units with a VOM have     Binary inputs   e VOM mode A  unit off     VOM mode B  pressurize     VOM mode C  exhaust     VOM mode D  purge     VOM mode E  purge w duct pressure  control    Binary output  e VO  relay    TCI Module     Binary input    Enthalpy enable airside economizer    Binary outputs     Compressor on off status     Ventilation status     Condenser water flow status    Heat status    Analog outputs     Supply air pressure   e Supply air temperature   e Suction temperature of each circuit     Entering economizer water temperature    Zone temperature     Entering condenser water temperature    Supply air tempera
14.    fused disconnect switch in the control box  terminals  Refer to specific wiring  diagrams and fuse information in the  unit s control panel     A CAUTION    Disconnect electrical power  source to prevent injury or death  from electrical shock        Use only copper conductors for  electrical unit connections to  prevent equipment damage        Correct phase sequence is  critical  If phase sequence of the  incoming line voltage is not  correct  it may result in motor  damage        Voltage Range   Voltages must be within    10  the  nameplate voltage  Ensure the unit  voltage is balanced by measuring at the  compressor terminals  Voltage imbalance  on three phase systems can cause motor  overheating and premature failure   Maximum allowable imbalance is 2 0  percent     Voltage Imbalance   Read the voltage at the compressor  terminals to determine if it is balanced   Voltage imbalance on three phase  systems can cause motor overheating  and premature failure  The maximum  allowable imbalance is 2 096  Voltage  imbalance is defined as 100 times the  sum of the deviation of the three voltages  from the average  without regard to sign   divided by the average voltage  For  example  if the three measured voltages  are 221  230  and 227  the average  voltage would be      221   230   227    226 volts  3    The percentage of voltage imbalance is  then   100    226 221    2 2   226    Control Power   In this example  2 296 imbalance is not  acceptable  Whenever a voltage  imbalanc
15.   0   None    Digit 19   Tracer Communications  Interface Kit  TCI    12 TCI Comm 3 Kit   0   None    Digit 20   Ventilation Override Module Kit   VOM    1 VOM Kit   0   None    Digit 21   Sensors and Thermostats       BAYSENS017   Zone Temp Only  CV  and VAV   B   BAYSENS013   Zone Temp with  Timed Override Button  CV and VAV        BAYSENS014   Zone Temp with  Timed Override Button  Setpoint Dial                        E   BAYSENS008   CV Zone Sensor  F  BAYSENS010   CV Zone Sensor with  Indicator Lights  G   BAYSENS019   CV Programmable  Night Setback Sensor  H         5    5021         Zone Sensor  with Indicator Lights    J   BAYSENSO20          Programmable  Night Setback Sensor   K   Remote Sensor Kit   L   Outside Air Temperature Sensor Kit   M   Outside Air Humidity Sensor Kit   0  None    Digit 22   Low Entering Air Temperature   Protection Device   1   Low Entering Air Temperature  Protection Device Kit   0   None   Digit 23   High Duct Temperature   Thermostat   1   High Duct Temp  Thermostat Kit   0   None   Digit 24   Plenum High Static Switch   1   Plenum High Static Switch Kit   0   None   Digits 25     45   Future Use   0   None    SCXG SVX01B EN    Receiving and Handling    Shipping Package   Commercial self contained units ship  assembled on skids with protective  coverings over the coil and discharge  openings  Figure I PC 1 illustrates     typical shipping package     Ship Separate Accessories  Field installed sensors ship separately  inside the unit s ma
16.   10                                                           Figure I PR 10  Vertical discharge electric  heat installation     46    Installation    4  Use the hole pattern in the electric heat  as a template for marking and drilling  346    diameter holes in the unit    5  Bolt the electric heaters to the unit  using 1 4    sheetmetal screws     Note  It is very important that electric  heaters are selected based on unit voltage  and tonnage because discharge opening  sizes vary by unit tonnage     Electric Heat Coil Wiring Procedure   1  Before wiring the electric heater   remove the unit wiring diagram from  the unit control panel and refer to the  connection points     Disconnect electrical power  source before wiring electric heat  to unit to prevent risk of injury or  death from electrical shock        2  Punch out the appropriate knockouts in  the electric heater control box and on  the unit s left side panel  Run the wires  down the side of the unit from the  heater to the lower unit control box   Place the wire in conduit in accordance  with local code     A CAUTION    Use only copper conductors for  electrical connections to prevent  equipment damage           WER                                               Dre Aat e    LEFT END VIEW       A eur    FRONT VIEW    Figure I PR 11  Electric heater dimensions     Table I PR 4  Electric Heat Dimensions   English    inches                 Unit Size B1 B2 2   20Tons 10 34 15 5 8 27 3h  25Tons 12 1   4 15   26 3 4  30  
17.   4 request is issued to the compressor  staging control function     Reset Required   PMR  A manual reset is  required after the disgnostic is set  It can  be reset by the HI  Tracer Summit    or by  cycling power to the RTM     Compressor Trip   Ckt 1  2  3  or 4  Problem  The compressor ckt  1  2  3  or 4  has tripped     Reason for Diagnostic  The ckt  1  2  3  or  4 compressor proving input is detected  open continuously for more than 3  seconds when either or both compressor  outputs on that circuit energize  as  described in the compressor protection  function      Reason for Diagnostic  The circuit  compressor proving input is detected  open continuously for more than 3  seconds when either or both compressor  outputs on that circuit energize  as  described in the compressor protection  function      UCM  Reaction  A    lockout ckt  1  2  3  or  4    request is issued to the compressor  staging control function     Reset Required   PMR  A manual reset is  required after this diagnostic occurs  The  diagnostic can be reset by the unit  mounted HI module  Tracer Summit    or  by cycling power to the RTM     Condenser Temp Sensor Failure   Circuit    1  2  3  or 4   Problem  The saturated condenser  temperature input is out of range for  circuit  1  2  3  or 4     Check  Sensor resistance should be  between 830 ohms  200 F  and  345 7Kohms   40 F   If so  check field unit  wiring between sensor and MCM SCM     Reason for Diagnostic  The unit is reading  a signal that is 
18.   A base for DIN  rail mounting is optional     Wiring the Timeclock   1  Wire 24  120  or 220 VAC to input  terminals  Make sure to apply correct  voltage  Using incorrect voltage will  void the warranty    2  Connect wire to the screw terminals  according to the unit wiring diagrams   Use 12 to 22 AWG wire     57    e TRANE    Installing the Remote Human  Interface Panel    Human Interface  HI  Panel   The HI enables the user to communicate  necessary unit operating parameters and  receive operating status information  from within the occupied space     The HI displays top level information in  the LCD window  unless the operator  initiates other displays  for the various  unit functions  It also displays menu  readouts in a clear language 2 line  40  character format  The 16 key keypad  allows the operator to scroll through the  various menus to set or modify the  operating parameters  See Figure I PR   31 to reference the HI keypad     Remote Human Interface Panel   The remote human interface  RHI  panel  is identical to the unit mounted HI with the  exception of the    unit select    key  This  key allows the operator to switch from  one unit to the next to program or view  status information regarding a particular  unit     The RHI functions the same as the unit  mounted HI with two exceptions  The first  is the    test start    function  The operator  can view the service parameters  but can  only initiate the service test function at  the unit  The RHI door has a lock
19.   Condenser Piped  SXWG 20 35 1 V  NPT 2    NPT       Waterside Economizer Option   The waterside economizer option takes  advantage of cooling tower water to  either precool the entering air to aid the  mechanical cooling process or  if the  water temperature is low enough   provide total system cooling  Waterside  economizing enables when the unit s  entering water temperature is below the    unit s entering mixed air temperature by  a minimum of 4 F plus the economizer s  approach temperature  The approach  temperature default is 4 E Waterside  economizing disables when the unit s  entering water temperature is not below  the unit s entering mixed air temperature  by at least the water economizer  approach temperature  The approach  temperature defaults to 4 F The  economizer acts as the first stage of  cooling  If the economizer is unable to  maintain the supply air setpoint  the unit  control module brings on compressors as  required to meet the setpoint     The waterside economizer includes a coil   modulating valves  controls  and piping  with cleanouts  The coil construction is 1   2   inch  13 mm  OD seamless copper tubes  expanded into aluminum fins  The  evaporator and economizer coils share a  common sloped  IAQ  drain pan  Drain  pan options are either galvanized or  stainless steel  and are insulated and  internally trapped     The waterside economizer coil is avail   able with either a two or four row coil   with no more than 12 fins per inch  The  tubes are ar
20.   Depressing the negative side  will decrease the time     Each time you depress the positive or  negative side    minus    and    plus     the  time will either advance or decrease  respectively by one minute  If you press  and hold either side of the time button   the time change will accelerate rapidly     When you reach the correct time  release  the time button and the time will be set  into permanent memory     Note  To ensure the time changes are    made  the ZSM will initiate a 30 second  user stabilization time before making  changes to the ZSM operation mode     Keypad Operation    Note  After toggling to the program  screen  the week is divided into seven  days with each day divided into four  periods  Therefore  28 program settings  are possible     Program Button  Depressing the program button will  toggle the display from normal run mode    66    Installation    to the program menu  See Figure       2   Before toggling to the program menu   use the mode button to select the type  setpoints to review or program  heat   cool or auto   For example  if you select  cool mode before toggling to the program  menu  then only the cool setpoints are  reviewed or programmed  If you select  heat mode  then only the heat setpoints  are reviewed or programmed  In auto  mode  both heat and cool setpoints are  reviewed and programmed      While in program menu  each time you  press and release the program button   the ZSM toggles through the four  periods that divide each day  
21.   NFPA  90        Make duct connections to the unit with a  flexible material such as heavy canvas  If  a fire hazard exists  Trane recommends  using Flexweave 1000  type FW30 or  equivalent canvas  Use three inches for  the return duct and three inches for the  discharge duct  Keep the material loose  to absorb fan vibration     Note  The compressors and fan assembly  are internally isolated  Therefore  external  isolation devices  spring mounting  isolators  are at the discretion of a vibration  specialist consulted by the building or  HVAC system designer     Run the ductwork straight from the  opening for a minimum of three fan  diameters  See Figure I MR 1  Extend  remaining ductwork as far as possible  without changing size or direction  Do not  make abrupt turns or transitions near the    unit due to increased noise and excessive  static losses  Use elbows with splitters or  turning vanes to minimize static losses     Poorly constructed turning vanes may  cause airflow generated noise  Align the  fan outlet properly with the ductwork to  decrease noise levels in the duct and to  increase fan performance  To complete  trunk ductwork to the VAV terminal units   refer to the VAV box manuals for specific  requirements  Check total external static  pressures against fan characteristics to  be sure the required airflow is available  throughout the ductwork     To achieve maximum acoustical perfor   mance  minimize the duct static pressure  setpoint          Discharge  Duct  
22.   Occupied Zone Temperature   Heating  Relies on input from a sensor directly in  the space  while a system is in occupied  heating mode or an unoccupied period  to  stage electric heat on and off or modulate  the hydronic heating valve as required to  maintain the zone temperature within the  heating setpoint deadband  The supply  fan will operate when there is a request  for heat     Electric Heat   On units with electric heat  the zone  temperature can be controlled to a  heating setpoint during the occupied  mode by cycling a single stage electric  heater  An interface is provided for field  supplied single stage electric heat  The  zone temperature heating setpoint and    94    Owner       deadband are user defined at the HI  panel     Hydronic Heat  Hot Water or Steam   On units with hot water or steam heating   the zone temperature can be controlled  to a heating setpoint during the occupied  mode  The zone temperature heating  setpoint and deadband are user defined  at the HI panel or zone sensor  VAV  occupied heating initiates by closing a  field supplied switch or relay contacts  connected to the changeover input on the  RTM  Supply air static pressure is  maintained     Supply Air Setpoint Reset  VAV Units  Only    Supply air reset can be used to adjust the  supply air temperature setpoint on the  basis of a zone temperature or outdoor  air temperature  Supply air reset  adjustment is available at the HI panel for  supply air heating and supply air cooling  contro
23.   Rigging and Unit Handling 12   RTM Alarm Relay 78   RTM Analog Outputs 78   RTM Aux  Temp  Sensor Failure 116   RTM Binary Outputs 78   RTM Data Storage Error 116   RTM Module Board 78   RTM Remote Economizer Minimum   Position 78   RTM Sensors 79   RTM Zone Sensor Failure 116    S    Saturated Condenser Temperature  Sensors 89   SCM 80   SCM Communication Failure 116   Selection Procedures 38   Semi Annual Maintenance 110   Service Access 11   Service Valves 97   Setting the Time 73   Ship Separate Accessories 9   Ship With Accessory Model Number  Description 7   Shipping Package 9   Skid Removal 16   Space Static Press Setpt Failure 116   Special Note on Refrigeration Emis   sions 2   Split Apart Unit Assembly 14   Standard Remote Sensor   BAYSENS017  53   Standard Two Position Damper  Interface 88   Startup Log 75   Static Pressure Transducer Installatio  49   Status Annunciator Output 78   Steam and Hot Water Coils 107   Step Control 96   suction pressure approaches 7   4 psig  89   suction pressure exceeds 22   4 psig  89   Supply Air Fan 86          122    Supply Air Pressure Sensor Failure 116  Supply Air Pressure Setpoint Failure  116  Supply Air Setpoint Reset 94  Supply Air Static Pressure Limit 86  Supply Air Temp Cool Setpoint Fail 117  Supply Air Temp Heat Setpoint Fail  117  Supply Air Temperature Control 93  Supply Air Temperature Failure 117  Supply Air Temperature Low Limit 90  Supply Air Temperature Sensor 90  Supply Air Tempering 94  Supply Airflow Provin
24.   Standing water in drain pans can  promote microbial growth  mold  which  may cause unpleasant odors and serious  health related indoor air quality problems  If  microbial growth is found  it must be  removed immediately and that portion of  the unit properly cleaned and sanitized     Inspecting and Cleaning the  Fan    Inspect the fan section every six months  or more frequently if operating  experience dictates  Clean accumulated  dirt and organic matter on the fan interior    surfaces following the procedure below     1  Disconnect all electrical power to the  unit    2  Don the appropriate personal  protective equipment  PPE     3  Use a portable vacuum with HEPA  filtration to remove the loose dirt and  organic matter  The filter should be  99 97  efficient at 0 3 micron particle  size    4  If no microbial growth  mold  exists   thoroughly clean the fan and associated  components with an industrial cleaning  solution  Carefully follow the cleaning  solution manufacturer s instructions  regarding personal protection and  ventilation when using their product    5  If microbial growth is present  remove  the contamination  Step 2  and  thoroughly clean the affected area with  an EPA approved sanitizer specifically  designed for HVAC use  Carefully follow  the sanitizer manufacturer s instructions  regarding the product usage    6  Rinse the affected surfaces thoroughly  with fresh water and a fresh sponge to  prevent potential corrosion of metal  surfaces    7  Allow the 
25.   WATER OUTLET  191 SEE DETAIL          629    SEE DETAIL    A       pup FRONT VIEW WATER INLET ON PAGE 21  64mm ENPT __ 432  WATER OUTLET WATER OUTLET  356  64mm          __ IATER       WATER INLET en ee        38mm           CONDENSER     194  FITTINGS  4X   FT SIDE VIEW ET SIDE VIEW  FACTORY PIPED UNITS DIRECT CONDENSER CONNECTIONS  19mm  4x     ISOLATOR HOLE LOCATION  889 784  ON BOTTOM OF UNIT   VERTICAL DISCHARGE OPTION  SEE DETAIL  B  FOR  DIMENSIONAL DATA   ON PAGE 21    279    TOP VIEW             RETURN AIR INLET  OPENING    FILTER ACCESS  FILTER ACCESS    38mm           ORAIN    QUICK RELEASE QUICK RELEASE       ACCESS PANEL ACCESS PANEL 108  191  38mm           4X   114 38MM INPT BACK VIEW  DRAN     WATER INLET  191     64MM           WATER OUTLET 292     WATER OUTLET  375    yi 384     WATER INLET        WATER OUTLET    RIGHT SIDE VIEW  FACTORY PIPED UNITS    RIGHT SIDE VIEW  DIRECT CONDENSER CONNECTIONS    SCXG SVX01B EN    e TRANE     Installation       SCRG SIRG Unit        English    inches  HORIZONTAL DISCHARGE OPTION  SEE DETAIL    B    FOR  DIMENSIONAL DATA   ON PAGE 21                          o  9 Q  4 57     c     Bg           u     QUICK RELEASE 1 1 2  INPT  ACCESS PANEL DRAIN  35 1 2      7    SEE DETAIL                    ON PAGE 21 LIQUID LINES      LEFT SIDE VIEW FRONT VIEW 5 8  TUBES  2X  41 2  AIR COOLED UNITS DISCHARGE LINES    5 8  TUBES  2X  9 1   4     RIGHT SIDE VIEW  AIR COOLED UNITS    FILTER ACCESS         03 4           ISOLATOR MOUNTING
26.   cooling  If outdoor conditions  tempera   ture and humidity  are suitable or the  EWT is within specified setpoints  the  RTM will attempt to use    free cooling     without using any compressors  The RTM  will use either the airside or waterside  economizer option  When outdoor air  conditions are not suitable  only mechani   cal cooling will function and outside air  dampers will remain at their minimum  position  If the unit does not have an  economizer  mechanical cooling will  operate to satisfy cooling requirements     Units With Economizer   If the entering condenser water  temperature  units with a WSE  or the  outside air enthalpy  units with an ASE  is  appropriate to use    free cooling     the  economizer will attempt to satisfy the  cooling zone temperature setpoint     Note  When using an ASE with econo   mizer enabled  O A temperature enable  can be used instead of comparative  enthalpy if the O A temperature falls below  the economizer setpoint     Then compressors will stage on as  necessary to maintain supply air tem     perature setpoint  which is user defined  at the HI  Minimum on off timing of  compressors prevents rapid cycling     When both airside and waterside  economizers are on a single unit  priority  must be set at the HI  The economizer  with the highest priority attempts cooling  first  Once it is operating at its maximum   and if additional cooling is necessary  the  other economizer enables before  mechanical cooling begins     Cooling Wate
27.   i   m 285   Lec 336           340       SIDE VIEW     9 84     FRONT VIEW   6  2 1 075  amp      875 KNOCKOUTS        ON TOP  amp  2 ON BOTTOM                                    0 94      7 19    1 00              8 12    BOTTOM VIEW    Figure         32  Remote      mounting holes and knockout locations     60    SCXG SVX01B EN    Wiring the Remote Human  Interface    The remote human interface requires 24  VAC   4 volts power source and a  shielded twisted pair communication link  between the remote panel and the  interprocessor communication bridge   ICPB  module at the self contained unit     Field wiring for both the low voltage  power and the shielded twisted pair must  meet the following requirements     Note  To prevent control malfunctions  do  not run low voltage wiring  30 volts or less   in conduit with higher voltage circuits     1  All wiring must be in accordance with  NEC and local codes     2  Reference Table I PR 8 on page 58 for  recommended wiring distance and size     3  Communication link wiring must be 18  AWG shielded twisted pair  Belden  8760  or equivalent      4  Communication link must not exceed  5 000 feet maximum for each link     5  Do not run communication link  between buildings     A WARNING    Before servicing unit  disconnect  all electric power  including  remote disconnects  Failure to do  so May Cause severe personal  injury or death        Low Voltage  AC  Field Wiring  Connections   To access the wire entry locations  open  the RHI
28.   malfunctioning of expansion  valves  damaged compressors  and so  on    will result in pressure variations  which are outside the normal range     Note  If phasing at the main incoming    power terminal is incorrect  switch two of  the three incoming power leads  If a  compressor has been replaced and the  phase is changed at the compressor  it will  run backwards and discharge pressure will  be very low  To resolve incorrect compres   sor wire phasing  change phasing at the  compressor     It is important that pressures be mea   sured under stable and constant condi   tions in order for the readings to be  useful  The unit mounted  remote  mounted  or discharge air setpoint can be  temporarily adjusted to simulate full load  conditions     Voltage Imbalance   Voltage imbalance on three phase  systems can cause motor overheating  and premature failure  Maximum  allowable imbalance is 2 0 percent  and  the readings used to determine it must be  measured at the compressor terminals     Voltage imbalance is defined as 100  times the sum of the division of the three  voltages from the average voltage  If  for  example  the three measured voltages  are 221  230  227  the average would be      22142304227    226 volts  3    The percentage of voltage imbalance is  then     100  226 221    2 2   226    In this example  2 2 percent imbalance of  more than 2 0 percent exists  be sure to  check the voltage at the unit disconnect  and terminal block switch  If an imbalance  at the unit
29.   occurs after communication has been  restored     Mode Input Failure  Problem  The RTM mode input is out of  range     Check  Sensor resistance should be  between 1 ohm and 40 Kohms  If so   check field unit wiring between sensor  and RTM     Reason for Diagnostic  The mode input  signal on the RTM is out of range   resistance    1k ohm or resistance  gt  40k  ohms      SCXG SVX01B EN    UCM s Reaction  The system mode  reverts to the default  HI set  system  mode     Reset Required   INFO  An automatic  reset occurs after the mode input returns  to its allowable range for 10 seconds     N    NSB Panel Zone Temperature Sensor  Failure   Problem  The NSB panel s zone temp  sensor input is out of range   This input is  at the NSB panel  not on the unit itself      Check  If have an external sensor  connected to the NSB panel zone sensor  input  then the internal NSB panel zone  sensor should be disabled  Verify sensor  resistance  If in valid range  check wiring  between the sensor and NSB panel     NSB Panel Comm Failure   Problem  The RTM has lost  communications with the night setback  panel  programmable zone sensor      Check  Field unit wiring between RTM  and NSB Panel     Reason for Diagnostic  The RTM has lost  communication with the NSB panel     UCM s Reaction  The unit reverts to the  next lower priority mode switching  source  typically the HI default mode   If  the NSB panel zone sensor is the  designated sensor source for any  functions  those functions are dis
30.   provided isolator placement sheet  Lift  one end of the unit at a time to position  isolators to the floor  using anchor bolts     2  Level the unit by adjusting isolator  heights  Unit weight may cause the  upper housing to rest on the lower  housing of the spring isolators  The  isolator clearance shown in the side  view of Figure I PC 9  must be 1 4        inches  To increase the clearance  lift    16    Installation       Top View    Upper  Housing    Side View  1 4  1 2               I  23 4    1 2  Dia  Positioning Pin    Leveling Bolt    Clearance Unloaded  Height  Lower  Housing        et   SS i  paaa 22 23 5 7 8   5 8          Neoprene Pad    Figure         9  Optional spring isolator dimensional data     the unit off the isolator and turn the  leveling bolt counterclockwise  Recheck  the unit level and the housing  clearances  Maximum allowable  difference between isolator heights is 1 4  inch  Shim as required under the  isolators     Note  The compressors and fan assembly  are internally isolated on most units  Due  to this  the addition of external isolation  devices  spring mounting isolators  is at  the discretion of the building or HVAC  system designer     Pre Installation Checklist    Complete the following checklist before  beginning unit installation        Verify the unit size and tagging with the  unit nameplate        Make certain the floor or foundation is  level  solid  and sufficient to support the  unit and accessory weights  See Table  I DW 1 on 
31.  127  V  87 7  26168    10 460V 9 7  8 7  12  7  127  7   8W  7  26168    15 200V 9  33  8  33 22 3   217  3 117  V  75168    15 460V 9 y  8 7      123  7  127    8  7  26168    20 200  9  3  8  32  22     21   3  1   V  75168    20 460V 9 7  8 V  16  V  157  V  87 7  31168    25 200V 14 1 12 1 26 n 24   7  121  7  126168    25 460V 95  93  8  7  22 3   21     VW  V   75168    Variable Frequency Drive Dimensions   Metric  mm    Motor HP Voltage A B c D E F G H J K Weight   7 5 200V 229 13 203 13 324 6 311 6 210 6 12 kg    7 5 460V 175 10 156 10 286 10 267 10 184 6 7 kg    10 200V 229 13 203 13 324 6 311 6 210 6 12 kg    10 460V 229 13 203 13 324 6 311 6 210 6 12 kg    15 200V 244 19 206 19 559 10 540 10 286 6 34 kg    15 460V 229 13 203 13 324 6 311 6 210 6 12 kg    20 200V 244 19 206 19 559 10 540 10 286 6 34 kg    20 460V 229 13 203 13 416 6 403 6 210 6 14 kg    25 200V 356 25 305 25 660 10 629 22 308 10 57 kg    25 460V 244 19 206 19 559 10 540 10 10 286 34 kg   SCXG SVX01B EN                                                                                     Installation  Variable Frequency           F        Drive with Bypass B _ G      H m     G I 1 E  D        D    J  ki     r1       1 00  DIA  25mm    37  DIA  9mm  MOUNTING HOLES  4X   MOUNTING HOLES  4X     FRONT VIEW LEFT SIDE VIEW    A B C KNOCKOUTS   TOP AND BOTTOM     i 2121   Qi  O MARNE O o                                                                                            VIEW BOTTOM VIEW    SCXG SVX01B
32.  44 8 19 6  25 25 20 55 6 24 2  30   24 66 8 29 0    32 26 72 4 31 6  35   28 78 34 0       Note     Electric heat amperage should not be considered when determining minimum circuit ampacity  The current of the  unit in the heating mode will not exceed the current of the unit in the cooling mode     SCXG SVX01B EN    e TRANE       Installation       Pre Startup Procedures    Before starting up units perform the  following procedures to ensure proper  unit operation     Unit Protective Covers   Remove the shipping protection  coverings from the human interface  panel  HI  at the control panel  the filter  box  or air inlet opening   the discharge  air opening  and optional variable  frequency drive  VFD      Compressor Isolators   Loosen compressor isolator mounting  bolts and remove shipping bracket from  beneath the compressor feet  Retighten  isolator mounting bolts  Torque to 18 ft   Ibs     2 ft  Lbs      Supply Fan Isolators   Remove the shipping channels and  mounting bolts from beneath the fan  See  Figure I PR 1  Open both fan  compartment access doors to access the  channels  The unit has six isolator  mounting points  See Figure I PR 2        While keeping the fan mounting frame  level  turn the fan isolator height adjusting  bolts until the fan housing P gasket  compresses 1 4    against the roof transi   tion piece  See Figure I PR 1     Remove 2 shipping bolts Remove 2 shipping bolts  and channels from flange and channels from flange    Isolators       Figure    
33.  5   4 8 mm  holes  Gently tap  the plastic wall anchors into the holes  until the anchor tops are flush with the  wall     6  Pull the zone sensor module wires  through the subbase as shown in Figure  I PR 31    7  Loosely secure subbase to the wall  with the mounting screws  Do not  tighten the subbase screws yet    8  Level the subbase by sight  then firmly  tighten the three subbase mounting  screws     Figure         29  Securing the subbase     A   CAUTION    Do not overtighten the subbase  screws  Overtightening may  cause the screws to crack the  subbase        9  Before wiring the subbase  identify the  wires from the unit s low voltage  terminal strip  Each screw terminal is  labeled    10  Remove TB from subbase and  discard the tape    11  Strip the wires        and connect the  wires from the units low voltage  terminal strip to the zone sensor  module subbase  Reference connection  details on the unit wiring diagrams   located on the unit    12  Firmly tighten each screw terminal    13  Fit the wires as close to the subbase  as possible     SCXG SVX01B EN       Figure         30  Grasslin time clock option     SCXG SVX01B EN    Installation    e TRANE       Time Clock Option    The time clock option has a  programmable timer that is factory wired  to the unoccupied input to provide on off  control  The time clock will not allow the  unit to pass through the night setback   morning warmup mode  except on units  with optional night heat morning warm  up  or progra
34.  EN 29    e TRANE    Installation    Variable Frequency Drive With Bypass Dimensions   English    inches                                   Motor HP Voltage A B C D E F G H J K L M Weight  7 5 200V 19  17   1  41 393  13   12 3   38 17  20   23  126 Ibs   10 200V 197  17  17  41 39   13   12 31  38 1   20   2   126165   10 460V 19 1   177  17  4 3997  13  12 37  38 17  20   2    126 lbs   15 200V 20 18 17  49 477  16   147  6 463     207    180 Ibs   15 460V 1975  17   17  4 393  13   12 3   38 1   20   23  126 Ibs   22 2V 2 18 17 49 477 163  14  6 4      207    1801   20 460V 197  17  17  41 39 3   13   12 31  38 1   20   2   126165   25 200V 20 18 17  49 477  16   147  6 46     207     180 Ibs   25 460V 20 18 17  49 477  16   147  6 46     207    180 Ibs        Variable Frequency Drive With Bypass Dimensions   Metric                                      Motor HP Voltage A B C D E F G H J K L M Weight  75 200V 495 445 48 1041 1010 343 305 83 965 38 521 60 57 kg   75 460V 362 311 48 889 857 343 305 83 813 38 375 60 40 kg   10 200V 495 445 48 1041 1010 343 305 83 965 38 521 60 57 kg   10 460V 495 445 48 1041 1010 343 305 83 965 38 521 60 57 kg   15 200V 508 457 48 1244 1216 416 378 152 1178   521   82 kg   15 460V 495 445 48 1041 1010 33 305 83 965 38 521 60 57        20 200V 508 457 48 1244 1216 416 378 152 1178   521   82 kg   20 460V 495 445 48 1041 1010 343 305 83 965 38 521 60 57 kg   25 200V 508 457 48 1244 1216 416 378 152 1178   521   82 kg   25 460V 508 457 48 1244 121
35.  LOCATION   ON BOTTOM OF UNIT   VERTICAL DISCHARGE OPTION  SEE DETAIL  B  FOR  DIMENSIONAL DATA    L ON PAGE 21  ut       SCXG SVX01B EN 19    e TRANE    Installation       SCRG SIRG Unit        HORIZONTAL DISCHARGE OPTION  Metric    mm  SEE DETAIL  B  FOR  DIMENSIONAL DATA  ON PAGE 21             FILTER ACCESS  FILTER ACCESS    38mm INPT  DRAIN       SEE DETAIL         ON PAGE 21 LIQUID LINES  LEFT SIDE VIEW FRONT VIEW 16mm TUBES  2X  114  AIR COOLED UNITS DISCHARGE LINES    16mm TUBES  2x  235    RIGHT SIDE VIEW  AIR COOLED UNITS    FILTER ACCESS         19mm  4X    ISOLATOR MOUNTING LOCATION   ON BOTTOM OF UNIT   VERTICAL DISCHARGE OPTION  SEE DETAIL  B  FOR  DIMENSIONAL DATA   ON PAGE 21   279       BACK VIEW    20 SCXG SVX01B EN    e TRANE          Installation  SCRG SIRG SCWG SIWG Detail SCRG SIRG SCWG SIWG Detail     A    Electrical Connections        A    Electrical Connections      English    inches  Metric    mm        12 375    9 375    38mm KO    LOW VOLTAGE  CUSTOMER CONNECTIONS    61 50  KO  LOW VOLTAGE  CUSTOMER CONNECTIONS       Unit Dimensions   English   inches                 UnitTons A B c D E F   SCWG SCRG 20 20 10   58  5  13  117   SCWG SCRG 25 9   12  575  5  137  T  SCWG 30   35 SCRG 32 18 145  56   5  13  17           FRONT VIEW   SHOWN WITH HORIZONTAL DISCHARGE OPTION     Unit Dimensions   Metric  mm              UnitTons A B C D E F  SCWG SCRG 20 508 508 1486 130 337 292  SCWG SCRG 25 489 489 1464 130 337 292  SCWG 30   35 SCRG 32 457 457 1435 130 
36.  M   Manifolded  Air Cooled     Digits 7  8   Unit Nominal Capacity  20   20 Tons  Water or Air   22   22Tons  Water Only   25   25 Tons  Water or Air   29   29 Tons  Water or Air   30   30 Tons  Air Only    32   32 Tons  Water Only   35   35 Tons  Water or Air   38   38 Tons  Water Only   40   40 Tons  Air Only    42   42 Tons  Water Only   46   46 Tons  Water Only   50   50 Tons  Air Only    52   52 Tons  Water Only   58   58 Tons  Water Only   60   60 Tons  Air Only    65   65 Tons  Water Only   72   72 Tons  Water Only   80   80 Tons  Water Only     Digit 9   Unit Voltage  6   200 Volt 60 Hz 3 ph  4   460 Volt 60 Hz 3 ph  5   575 Volt 60 Hz 3 ph  0   Not Defined    Digits 10  11   Design Sequence    0  A Design    Digit 12   Unit Power Connection  1   Single Point Power   2   Dual Point Power   0   Not Defined    Digit 13  14   Motor HP  05   5 HP Motor  07   7 5 HP Motor    10   10 HP Motor   15   15 HP Motor   20   20 HP Motor   25   25 HP Motor   30   30 HP Motor   40   40 HP Motor   50   50 HP Motor  460V  amp  575V Only   0   Not Defined    Digit 15   Exhaust Comparative Enthalpy  Module  Field Installed    1           Kit   2  None    Digit 16   Generic BAS Module  1   GBAS 0 5 VDC Kit  0 None    Digit 17   Heat Module   1   Electric Heat Module Kit   2   Hydronic Heat Module Kit  0 None    Digit 18   Remote Human Interface and   IPCB   1   Remote Human Interface Panel Kit   RHI Only    2   Interprocessor Communications  Module Kit  IPCB Only    3  RHI and IPCB Kit 
37.  Measure fan belt tension with a  Browning  Gates  or equivalent belt  tension gauge  Determine deflection by  dividing the belt span distance  in inches   by 64  See Figure O M 2     Recommended belt tension range values  are on the unit fan scroll  The belt tension  label is on the top right hand corner of the  fan scroll  See Figure       4     Follow the procedure below to measure  belt tension     1  Measure belt span between centers of  sheaves and set the large    O    ring of  the tension gauge at 1  inch for each  inch of belt span    2  Set the load    O    ring at zero    3  Place the large end of the gauge at the  center of the belt span  Press down until  the large    O    ring is even with the top  of the belt line or the next belt as in  Figure O M 2  Place a straight edge  across the sheaves as a reference  point  See Figure O M 1 on page 99    4  Remove the gauge  Note that the load     O    ring now indicates a number on the  plunger scale  This number represents  pounds of force required to deflect the  belt    5  Check the reading from step 4 against  the values given on the unit fan scroll  If  necessary  readjust belt tension     100    Owner       Adjusting Belt Tension   To adjust belt tension refer to Figure O M    2 and perform the following procedure    1  Loosen bolts A  B  and E on both sides  of the sliding motor base  See Figure O   M 4    2  Loosen nuts C and D  as required for  motor horsepower  to slide the motor  on its mounting plate in the
38.  Remote Human Interface  Module Option    The optional remote mount human  interface  RHI  panel has all the functions  of the unit mounted version except for  service mode  To use a RHI  the unit must  be equipped with an optional  interprocessor communications bridge   IPCB   Model number digit 32   2   indicates if the ICPB was ordered with the  unit  If not  contact your local Trane  representative to order an ICPB kit for  field installation  The RHI can be located  up to 1 000 feet  304 8 m  from the unit  A  single RHI can monitor and control up to  four self contained units if each one  contains an IPCB  The IPCB switches must  be set as SW1  off  SW2   off  and SW3    on     Interprocessor Communications Board     Option used with RHI   The interprocessor communication board  expands communications from the CSC  unit s UCM network to a remote human  interface panel  DIP switch settings on the  IPCB module for this application are   switches 1 and 2  off switch       on       80    Owner       Waterside Module   Standard  on AllWater Cooled Units    The waterside module  WSM  controls all  water valves based on unit configuration   In addition  the WSM monitors waterflow  proving and the following temperatures       entering water    entering air low    mixed air    entering condenser water    refrigerant circuit 3      saturated condenser     evaporator frost     motor winding    refrigerant circuit 4      condenser     evaporator     motor winding    Cooling Tower I
39.  a constant speed  However  the fan  may have the IGV or VFD option that  modulates airflow based on supply air  temperature control  Pressing the stop  key on the HI will turn the supply fan off   The fan is on continuously when a CV unit  is in occupied mode and except when a  unit is in the night heat morning warmup  mode  During the night heat and setback  mode the fan cycles on and off in  response to a call for heat  See Table O   GI 9 for available fan horsepower     Low Entering Air Temperature Sensor  This is standard on all units with a  hydronic coil or waterside economizer  It  can also be ordered as an option     A thermostat limit switch is factory  mounted on the unit s entering air side  with a capillary tube serpentine across  the coil face  If the temperature falls  below 35 F  2 C   the fan shuts down and  the waterside economizer and or  hydronic heat valve options open to allow  full water flow  The heat output also  energizes  A manual reset is required   The low entering air temperature  setpoint is adjustable     High Duct Temperature Thermostat   A factory supplied temperature limit  switch with reset element detects the  supply air duct temperature  This sensor  should be field installed downstream  from the unit s discharge in the supply air  duct  If the supply air duct temperature  exceeds 240 F  115 6 C   the unit shuts  down and displays a diagnostic  A  manual reset is required at the unit  The  high duct temperature can be adjusted at  the the
40.  and may  cause personal injury     Note  Plenum insulation must be applied  properly to prevent air bypass around the  plenum  See Figure  PR 4        Plenum Bottom View                   Dashed line indicates correct insulation placement     Figure I PR 4  Correct plenum insulation placement     SCXG SVX01B EN 41    e TRANE    42    Installation    Waterside Economizer  Installation Procedure    1     Install screws       the top  6x  and  bottom  6x      Economizer    Loosen and pull all end devices that  go through the bushing or the filter  rack  upper right corner of rack        Remove the filter rack from the back    of the unit by removing the 1   4    hex  head screws from the top and bottom  of the filter rack assembly  The filter  rack assembly will hang on the unit  when the screws are removed   Remove the filter rack by lifting it up  off the unit       Remove the economizer from the    crate and position it behind the unit  with the headers on the left side   when facing the back of the unit   Remove the plastic envelope that is  taped to the economizer box  assembly  This envelope contains the  gasket that must be installed onto the  vertical side flanges of the box       Install the pressure sensitive gasket to    the unit side of the vertical flange on  the economizer box       Hang the economizer on the unit as    shown in Figure I PR 5  Lift the  economizer by using the holes  provided in the top panel of the  economizer            6  Align economizer holes
41.  assumed to be an open circuit  The system will use  the default minimum position value     RTM Analog Outputs   The RTM has two 0 10 vdc outputs  one  for the inlet guide vane option and one for  the economizer option  These outputs  provide a signal for one or two damper  actuators  There are no terminal strip  locations associated with these wires   They go directly from pins on the RTM  circuit board to the actuator motor     RTM Binary Outputs   The RTM has an output with pressure  switch proving inputs for the supply fan   There is a 40 second delay from when  the RTM starts the supply fan until the fan  proving input must close  A fan failure  diagnostic will occur after 40 seconds   This is a manual reset diagnostic  and all  heating  cooling  and economizer  functions will shut down  If this proving  input is jumped  other nuisance  diagnostics will occur  If the proving input  fails to close in 40 seconds  the  economizer cycles to the minimum  position  This is a manual reset  diagnostic  External control of the fan is  not recommended     VAV Drive Max Output   This is a single pole  double throw relay  rated at a maximum voltage of 24 vac  2  amps  The relay contacts of this relay  switch when the unit goes from the  occupied mode to the unoccupied mode  by means of the occupied binary input   The contacts will stay switched during the  unoccupied and morning warmup mode   They will return to the position shown on    the unit wiring diagram when the unit  returns
42.  be used to  shut down unit operation  This switch is a  binary input wired to the RTM  When  opened  the unit shuts down immediately  and can be cancelled by closing the  switch  Refer to the unit wiring diagrams   attached to the unit control panel  for  proper connection terminals  The switch  must be rated for 12 ma   24 VDC  minimum  This input will override all VOM  inputs  if the VOM option is on the unit     SCXG SVX01B EN    Owner       Occupied Unoccupied Contacts Table         2         Sensor Resistance vs  Temperature  To provide night setback control if a                                        remote panel with night setback was not Temperature  F  Resistance  ohms  Temperature  F      Resistance  ohms                     40 346  71 11 60  ordered  install    field supplied contact      nete 5    Sages a 230 241 7 72 11 31  This binary input provides the building s 20 170 1 13 1103  occupied unoccupied status to the RTM  It    1214 74 1076  can be initiated by a time clock  ora 5 103 0 75 10 50  building automation system control 0 87 56 76 10 25  output  The relay s contacts must be rated 5 74 65 71 10 00  for 12 ma   24 VDC minimum  Refer to 10 63 8 78 9 76  the appropriate wiring diagrams 15 54 66 79 6 53     attached to the unit control panel for the                                                 25 40 40 85 8 25  proper connection terminals in the unit 30 2485 90 155  control panel  35 30 18 100 582  Emergency Stop Input 40 26 22 105 5 21  A binary input i
43.  below     BAS   Building automation systems  CFM   Cubic feet per minute   CKT    Circuit   CV   Constant volume   CW   Clockwise   CCW   Counterclockwise   E A   Exhaust air    ECEM   Exhaust comparative enthalpy  module   F A   Fresh air   GBAS   Generic building automation  system   HGBP   Hot gas bypass   HI   Human Interface   HVAC   Heating  ventilation and air  conditioning   IGV   Inlet guide vanes          Inputs outputs   IOD  Installation owner diagnostic  manual   IPC   Interprocessor communications  IPCB   Interprocessor communications  bridge   LH   Left hand   MCM   Multiple compressor module  MWU   Morning warmup   NSB   Night setback   O A   Outside air   psig   Pounds per square inch  gauge  pressure   R A   Return air   RH   Right hand   RPM   Revolutions per minute   S A   Supply air   SCM   Single circuit module   SZ   Single zone  unit airflow    TCI  Tracer   communications module  UCM   Unit control modules   VAV  Variable air volume   VCM  Ventilation control module  VOM   Ventilation override module  w c   Water column   WSM   Waterside module   ZSM   Zone sensor module    Special Note on Refrigeration  Emissions    World environmental scientists have  concluded that ozone in our upper  atmosphere is being reduced due to the  release of CFC fully halogenated  compounds     The Trane Company urges all HVAC  service personnel to make every effort to  prevent any refrigerant emissions while  installing  operating  or servicing equip   ment  Always cons
44.  control  drum and line pressures when  pressure testing the system   Excessive pressures may cause  line ruptures  equipment damage   or an explosion which may result  in injury or death        10          e TRANE       A WARNING       Do not exceed 200 psig when  leak testing the system  Damage  to the unit could result  or an  explosion may occur causing  injury or death        In the event of required system repair   leak test the liquid line  evaporator coil   and suction line at pressures dictated by  local codes  using the following  guidelines    1  Charge enough refrigerant and dry  weight  Use an accurate scale or  charging cylinder to determine the  exact weight of the refrigerant entering  the system  Failure to use either a scale  or acharging cylinder can lead to  undercharging or overcharging  resulting in unreliable operation        Do not apply flame to the  refrigerant container to increase  refrigerant pressure  Uncontrolled  heat may cause excessive drum  pressures and explosions   resulting in injury or death and  equipment damage     A CAUTION    Do not allow liquid refrigerant to  come into contact with the skin   If it does  treat the injury as if the  skin had been frostbitten or  frozen  Slowly warm the affected  area with lukewarm water and  seek medical attention  immediately           Table O M 1  Water Cooled Unit  SXWG  Refrigerant Charge              Unit Size Circuit A Circuit B  Charge 165   kg  Charge 165           SXWG 20 25  11 3  25  11 3
45.  detergent  or with one of the com   mercially available chemical coil clean   ers  Rinse coils thoroughly after cleaning     Economizer and evaporator coils are  installed so the evaporator is directly  behind the economizer  To clean between  the coils  remove the sheet metal block  off  Access the block off by removing the  corner panels on the unit s left or right  rear side     A CAUTION    Caution  Do not clean the  refrigerant coil with hot water or  steam  The use of hot water or  steam as a refrigerant coil cleaner  agent will cause high pressure  inside the coil tubing and  subsequent damage to the coil     A CAUTION    Caution  To prevent damage to  the unit  do not use acidic  chemical coil cleaners  Also  do  not use alkaline chemical coil  cleaners with a pH value greater  then 8 5  after mixing  without  using an aluminum corrosion  inhibitor in the cleaning solution           SCXG SVX01B EN    Owner    e TRANE       A WARNING    Some chemical coil cleaning  compounds are caustic or toxic   Use these substances only in  accordance with the  manufacturer s instructions   Failure to do so may result in  injury  death  or equipment  damage        If the refrigerant coil is installed back to  back with the waterside economizer coil   use a cleaner that is acceptable for  cleaning both types of coils     Inspecting and Cleaning Coils   Coils become externally fouled as a result  of normal operation  Dirt on the coil  surface reduces it s ability to transfer heat  th
46.  disconnect switch does not  exceed 2 0 percent  the imbalance is  caused by faulty wiring within the unit  Be  sure to conduct a thorough inspection of  the unit electrical wiring connections to  locate the fault  and make any repairs  necessary     Table D T 1  Common Unit Problems and Solutions             Plugged drain line    Problem Possible Cause Remedy   Drain pan is overflowing Plugged drain line Clean drain line  Unit not level Level unit   Standing water in drain pan Unit not level Level unit    Clean drain line       Wet interior insulation    n       Excess Dirt in unit Missing filters  Filter    Coil face velocity too high  Improper trap design   Drain pan leaks overflowing   Co       Reduce fan speed  Design trap per unit installation instructions  Repair Leaks    Replace filters  il       Microbial growth  mold     Standing water in drain pan    See  Standing water in drain pan  above    111    e TRANE    Diagnostics   Refer to the  ntelliPak  Self Contained  Programming Guide  PKG SVPO1B EN   for specific unit programming and  troubleshooting information  In particular   reference the  Service Mode Menu  and     Diagnostic Menu    sections in the  programming guide  Refer to the  following text for general diagnostic and  troubleshooting procedures  Common  diagnostics and troubleshooting  procedures follow below     A    Auto Reset S A Static Pressure Limit  Problem  The supply air static pressure  went too high     Reason for Diagnostic  The S A static  pre
47.  entire section carefully  to become familiar with the procedures     Disconnect electrical power to  prevent injury or death from  electrical shock        Receiving   Olnspect unit and components for  shipping damage  File damage claims  immediately with the delivering carrier    LICheck unit for missing material  Look  for ship with drives  isolators  filters   and sensors that are packaged  separately and placed inside the main  control panel  fan section  or  compressor section  See page 9 for  more information on ship with items    LICheck nameplate unit data to verify  against the sales order requirements     Unit Location   LIRemove crating from the unit  Do not  remove the shipping skid until the unit is  set in its final position    LIEnsure the unit location is adequate for  unit dimensions  ductwork  piping  and  electrical connections    OEnsure access and maintenance  clearances around the unit are  adequate  Allow space at the end of the  unit for shaft removal and servicing   See the  Service Access  section on  page 11     Unit Mounting   LIPlace unit in its final location    ORemove shipping skid bolts and skid    Olf using isolators  properly mount using  the isolator placement sheet    ORemove shipping brackets on the  compressors and supply fan    ORemove the unit protective shipping  covers     Component Overview                  the fan and motor shafts are  parallel    LlVerify the fan and motor sheaves         aligned     LICheck the belt tension for p
48.  exhaust  damper  inlet guide vane positioning or  variable frequency drive output  and  airside economizer operation based on  that information     Reference the RTM points list on page 77     Note  Emergency stop and external auto     stop  stop the unit immediately  emer  gency stop generates a manual reset  diagnostic that must be reset at the unit  human interface  External auto stop will  return the unit to the current operating  mode when the input is closed  so this  input is auto reset     RTM Remote Economizer Minimum  Position   The remote minimum position  potentiometer  BAYSTAT023A  provides  a variable resistance  0 270 ohms  to  adjust the economizer minimum position  from 0 to 100  when connected to the  economizer remote minimum position  input of the RTM  RTM must be selected    78    Owner       as the source for economizer minimum  position  If the RTM is the selected source  for economizer minimum position  and if  a valid resistance per Table O GI 1 is  provided to the RTM remote minimum  position input  the OA cfm compensation  function will not operate  even if enabled      Default    is the only possible source for  economizer minimum position when  using the OA cfm compensation function     Table      1  Economizer Remote Minimum  Position Input Resistance           Input Economizer  Resistance Min  Position  0 30 ohms 0    30   240 ohms 0 100    Linear   240   350 ohms 100       gt  350 ohms N A           Note  A resistance greater than 350 ohms is 
49.  fan capacity and limit  horsepower at lower system air require   ments  When in any position other than  full open  the vanes pre spin the air in the  same direction as the supply fan rotation   As the vanes approach the full closed    position  the amount of    spin    induced by  the vanes increases at the same time  that intake airflow and fan horsepower  diminish  The IGV s will close when the  supply fan is off     Supply Air Static Pressure Limit   The opening of the IGV s and VAV boxes  coordinate during unit startup and  transition to from occupied unoccupied  modes to prevent supply air duct  overpressurization  However  if for any  reason the supply air pressure exceeds  the user defined supply air static  pressure limit set at the HI panel  the  supply fan VFD shuts down and the IGV s  close  The unit will attempt to restart  up  to three times  If the overpressurization  condition still occurs on the third restart   the unit shuts down and a manual reset  diagnostic sets and displays at the HI     Variable Frequency Drive Option   The variable frequency drive  VFD  is  driven by a modulating 0 10 vdc signal  from the RTM module  A pressure  transducer measures duct static  pressure  and the VFD adjusts the fan  speed to maintain the supply air static  pressure within an adjustable user   defined range  The range is determined  by the supply air pressure setpoint and  supply air pressure deadband  which are  set at the HI panel     VFD s provide supply fan motor s
50.  function  if  applicable  and the compressor staging   chilled water cooling function will be  cancelled    b  If any of the GBAS setpoint control  parameters are the Hl selected setpoint  sources  then those setpoints will revert  to the default HI setpoints    c  Any active GBAS output control  parameters will be ignored    d  A failsafe function in the GBAS module  will cause all GBAS outputs to be  zeroed and deenergized     Reset Required   PAR  An automatic reset  occurs after communication has been  restored     H    Heat Failure   Problem  The heat has failed     Electric heat unit  Typically  this is  because the electric heat section became  too hot     Reason for Diagnostic  The heat fail input   on the heat module was closed    a  for more than 80 seconds    b  for ten consecutive occurrances  each  lasting five seconds or more  within a  210 second period            Reaction  An information only  diagnostic is set     Reset Required   INFO  An automatic  reset occurs after the heat fail input  remains open for 210 seconds  continuously     Heat Module Auxilliary Temperature  Sensor Fail   Problem  The heat mod aux temp sensor  input is out of range     Check  Sensor resistance should be  between 830 ohms  200 F  and  345 7Kohms   40 F   If so  check field unit  wiring between sensor and heat module     Reason for Diagnostic  At least one  enabled unit function has the heat  module auxillary temperature input  designated as its sensor  and the unit is  reading a 
51.  has the same function in   temporary manual override menu as in   all other menus  with a few exceptions      Depressing the holdtemp or program  buttons while in temporary manual  override menu will enter settings and  begin temporary manual override run  mode  See Figure I P 5     0 02    DAYS HOURS    SUPPLY AIR    OVERRIDE  TIME       Figure       6  Temporary manual override  menu screen       Depressing the day button will toggle  the ZSM between the day and hour  icon      Depressing the mode button will toggle  the ZSM between the heat and cool  icons and setpoints      Depressing the erase button will cancel  the override and return the ZSM to  normal run mode       f no button is pressed for 20 seconds   the ZSM exits temporary manual  override menu and enters the normal  run mode  ignoring the temporary  manual override menu settings     Temporary Manual Override Run Mode  The temporary manual override run  mode sends setpoint data to the UCM  from the setpoint data entered in the  temporary manual override menu  See  Figure       7     In temporary manual override run mode   most of the keypad functions lock out with  these exceptions      The mode button still functions as in  normal run mode      Depressing the holdtemp button toggles  the ZSM between temporary manual  override menu and temporary manual  override run mode  If no button is  pressed for 20 seconds  while in the  temporary manual override menu  the  ZSM exits to the normal run mode   ignoring the 
52.  in the control panel for field installation in  the supply air duct work  The installer is  responsible for providing pneumatic  tubing     Transducer Location   Place the head assembly in an area of the  ductwork that will provide an average  and evenly distributed airflow pattern   Use the following guidelines to determine  an appropriate installation location     1  Locate the static head assembly about  two thirds to three  fourths of the way  down the longest duct run  in an area  approximately 10 duct diameters  downstream and 2 duct diameters  upstream of any major interferences   turns  or changes in duct diameter    2  When installing pneumatic tubing  between the head assembly and  transducer in the control panel  do not  exceed 250 feet for 1 4    OD tubing or  500 feet for      OD tubing     Static Pressure  Head Assembly                  Sheet Metal Screws   provided by installer     Installing the Transducer   Complete the following procedure to   properly install the inlet guide vane static   pressure transducer    1  Mount the pressure sensing head  assembly in the duct so that the sensing  tip is in the middle of the duct  and  perpendicular to the airflow  This will  provide proper pressure measurement   See Figure I PR 14    2  Connect the pneumatic tubing from the  sensing head to the push on tubing  connection in the control panel  Use a  plastic static pickup tubing  Do not  exceed 250 feet for      OD tubing or  500 feet for 3      OD tubing     The tr
53.  non   condensing   Ambient Storage Conditions     Temperatures   50 to 200 F     Relative humidity  5 to 9596  non   condensing    Table I PR 9  Wiring Recommendations for  the Remote HI Panel             Distance from Unit Recommended   to Remote HI Wire Size   0 460 feet 18 gauge   461 732 feet 16 gauge   733 1000 feet 14 gauge  SCXG SVX01B EN    Mounting the Remote Human  Interface  RHI  Panel    The installer must provide all mounting  hardware such as  hand tools  electrical  boxes  conduit  screws  etc  Refer to  Figure I PR 32 on page 60 for the  mounting hole and knockout locations     Procedure   Follow the procedure below for  mounting the remote HI panel on a 4    by  4    electrical junction box  Place the  microprocessor in a clean dry location  during the enclosure mounting  procedures to prevent damage     1  Mount an electrical junction box in the  wall so that the front edge of the box  will be flush with the finished wall  surface     2  Prior to mounting the panel  the  microprocessor module must be  carefully removed from the enclosure   To remove the module     a  Lay the remote panel face up on a flat  surface and remove the locking screw  from the right hand bottom end of the  panel     b  Remove the recessed hinge screw  from the left hand bottom end of the  panel     c  Unlatch the door of the enclosure as if  to open it  and slide the left hand side of  the door upward away from the hinge   Lay it aside     d  With the key pad visible  remove the  t
54.  panel door and remove the two  screws on the right hand side of the key  pad  Swing the keypad open  exposing  both the wire entries and the back of the  HI module  Refer to Figure I PR 32 on  page 60 and connect one end of the three  conductor 24 volt wires to the remote  panel terminal strip           and  ground      SCXG SVX01B EN    Installation    e TRANE       Communication Link  Shielded Twisted  Pair  Wiring   Trim the outer covering of the shielded  cable back approximately 1 inch  See  Figure I PR 35  Do not cut the bare  shield wire off  Strip approximately 7    inch of insulation from each insulated  wire to connect them to the terminal strip  at the remote panel     Connect the white lead to the positive      terminal  the black lead to the negative      terminal  and the bare shield wire to the  terminal at the remote human interface  panel     Close the key pad plate  Install and  tighten the two screws removed earlier   Close the outer door and install the  recessed locking screw at the bottom  right hand side of the enclosure to  prevent accidental starting of the unit by  unauthorized personnel while completing  the wiring at the self contained unit     At the Self Contained Unit   Connect the opposite end of the three  conductor 24 volt wire to the appropriate  terminal strip as follows     Note  Although the 24 volt power is not  polarity sensitive  do not connect either  the    plus  or    minus  terminals from the  remote panel to ground at the self   
55.  pressure control valve that allows  compressor operation down to entering  water temperatures of 35 F  2 C      For more information on constant and  variable water flow  see the Owner s  section of this manual     Note  Units with a waterside economizer  can be set from the human interface panel  for variable or constant water flow           Flexible  Cleanout Connection  Tee Union   From    SWUD  Unit       To SWUD  Unit    UNION Flexible  Plugged Connection  Cleanout  Tee    Figure I MR 3  Condenser water piping components for cooling tower system     Pressure Thermometer           T Gauge        Flexible  Union Connection From    To SWUD      Unit  Shutoff Pressure    Valve Plugged Gauge Thermometer ri  Flexible  Connection  Tee  Pressure Reducing     Balancing Valve    Figure I MR 4  Typical water piping for city or well water system     35    e TRANE    36    Installation    Refrigerant Piping  Air Cooled  Units Only     The maximum line pressure design of  each refrigerant circuit is 3 psig  Include  the following items when designing  refrigerant piping  oil traps  dual risers  oil  return  etc  Refer to the Trane  Reciprocating Refrigeration Manual for  proper line sizing and layout     See the    Start Up    section on page 74 of  this manual for instructions on refrigerant  evacuation  charging  and superheat  measurement  Leak test the entire  refrigeration system after all piping is  complete     Leak Test  Remote Air cooled Units  Only    Units ship with a hold
56.  proper  direction to tension or relieve tension on  the belt    3  Adjust nuts A D and bolt E  Do not  stretch the belts over the sheaves    4  Retighten all nuts and bolts    5  Verify tension is adjusted properly     A CAUTION    Do not over tension the belts   Excessive tension will reduce fan  and motor bearing life  accelerate  belt wear  and possibly cause  shaft failure           Deflection   Belt Span 64    Figure O M 2  Fan Belt Adjustment     Recommended belt tension range values         on the unit fan scroll  To access the  fan scroll  face the right hand side of the  unit and remove the top left panel  The  belt tension label is on the top right hand  corner of the fan scroll  See Figures O M   4     The correct operation tension for a V belt  drive is the lowest tension at which the  belt will not slip under the peak load  conditions  It may be necessary to  increase the tension of some drives to  reduce flopping or excessive start up  squealing     Force Scale    Small    O Ring              7  221    550505041  SY    xe  XxX    50   5555560    1   250        x     555250605050    9   SEC    ZIX       5050        re         5   L    2   5   25   RS  3       jane Span Scale  O Ring             TI    Figure O M 3  Belt Tension Gauge        Figure O M 4  Location of fan belt label on  fan scroll     SCXG SVX01B EN    Owner       Figure O M 5  Fan assembly     25 HP  Fan Motor                 Figure O M 6   Fan motor adjustment points     SCXG SVX01B EN 101    e T
57.  switches   Water cooled units also include a liquid  line service valve for each circuit     For more detailed information  see the  Owner s section of this manual        Figure         1  IntelliPak  commercial self contained Modular Series unit     SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE       Control Options   Units can have either a thermostat  control or IntelliPak   UCM control  network     IntelliPak   Unit Controls   Standard controls supplied with the  IntelliPak   unit include the human  interface  HI  panel with unit control  module  UCM   hi lo inlet air temperature  sensor  and frost protection  All setup  parameters are preset from the factory     Human Interface Panel   The HI is unit mounted and accessible  without opening the unit s front panel  It  allows easy setpoint adjustment using  the HI keypad  In addition  the HI displays  all unit operating parameters and  conditions in a clear language display   which can be configured for either  English  French  or Spanish     The optional remote human interface   RHI  will control up to four self contained  units  each containing an interprocessor  communications bridge  IPCB   It has all  the same features as the unit mounted HI  except for the service mode     For more information on setpoint defaults  and ranges and unit programming  see  the IntelliPak   Self Contained Program   ming Guide  PKG SVP01B EN  A copy  ships with each unit     Unit Control Module   The UCM provides    smart   
58.  system  has stabilized     Normal start up can occur provided that  Tracer Summit   is not controlling the  module outputs or the generic BAS is not  keeping the unit off     To ensure that Tracer Summit  has no  affect on unit operation  remove Tracer      wiring and make required changes to  setpoint and sensor sources  See the  IntelliPak    Self Contained Programming  Guide  PKG SVPO1B EN  for more  information     Unit Startup    Reference the  ntelliPak    Self Contained  Programming Guide  PKG SVP01B EN   for unit operating instructions  A copy  ships with each unit     For units with the VFD option  reference  Instruction Bulletin  Altivar 58 Adjustable  Drive Controllers and or Installation  Guide  Type H Controllers Keypad  Display  A copy ships with each VFD     SCXG SVX01B EN    e TRANE    installation                                     Startup Log  Complete this log at unit start up   Unit  Unit Location   Unit Voltage   A B      Evaporator   Evaporator fan motor horsepower  Evaporator fan motor amps   Evaporator fan RPM  actual   B        Evaporator System Static  from test and balance report or actual readings     Supply Duct Static    Return Duct Static   Evaporator Air Conditions with both compressors operating    Enter  Leaving    Dry Bulb   F  Dry Bulb   F    Wet Bulb   F  Wet Bulb   F   Evaporator System CFM  test and balance sheet or actual tested    Compressor Amp Draw   Circuit A  Circuit B    A B C A B C  Circuit C  Circuit D   A B          C   Sucti
59.  temperature for supply air  temperature control  supply air  temperature reset  supply air  temperature low limiting  and supply air  tempering  It is mounted in the supply air  discharge section of the unit and  connected to the RTM     Supply Airflow Proving Switches   This is binary input device used on units  to signal the RTM when the supply fan is  operating  It is mounted in the supply fan  section and is connected to the RTM   During a request for fan operation and if  the differential switch opens for 40  consecutive seconds  compressor  operation turns off  heat operation turns  off  the request for supply fan operation is  turns off and locks out  IGV option closes   economizer damper option closes  and a  manual reset diagnostic initiates     Low Entering Air Protection Device   The low entering air protection device   LEATPD  is a binary input on units with  hydronic heat or a waterside economizer   It is optional on all water cooled units     If the LEATPD is on a unit with factory    installed heat  it is mounted in the heat   section and connected to the heat   module  If the entering air temperature to   the heating coil falls to 40 F the normally   open contacts on the LEATPD close and   cause the following events    a  the hydronic heat actuator fully opens    b  the supply fan turns off   c  the outside air damper closes   d  the SERVICE light at the remote zone  sensor option turns on    e  a LEATPD diagnostic displays at the  human interface panel     I
60.  the subbase enable  or disable applicable functions  i e   morning warmup  economizer minimum  position override during unoccupied  status  heat installed  remote zone  temperature sensor  12 24 hour time  display  and daytime warmup  During an  occupied period  an auxiliary relay rated  for 1 25 amps   30 volts AC with one set  of single pole double throw contacts  activates                          Figure         25  BAYSENS020  Programmable  night setback sensor   Accessory Model Number Digit 6   J    55    e TRANE    Programmable Night Setback  Zone Sensor Installation    Mounting Location   Mount the sensor on the wall in an area  with good air circulation at an average  temperature  Choose a location that is  easily accessible  and on a wall where the  subbase can be mounted about 5 feet    1 5 meters  above the floor     Avoid mounting space temperature   sensor is areas subject to the following   conditions    e Drafts or    dead    spots behind doors or  in corners   e Hot or cold air from ducts   e Radiant heat from the sun or appliances   e Concealed pipes and chimneys   e Unheated or non cooled surfaces  behind the sensor  such as outside walls   e Airflows from adjacent zones or other  units       PROGRAM       TIME                DAY ERASE            33 4    95 mm   HOLD TEMP  SS  MODE FAN  e   e  J 1               51 2    140 mm     Figure I PR 26  BAYSENSO019 dimensions        33 4    95mm              HOLDTEMP       MODE             L         140mm   Figure 
61.  the system s condenser  piping in reverse returns  This helps  balance the system by equalizing the  length of supply and return pipes   Multistory buildings may use a direct  return system with balancing valves at  each floor     Install the supply riser and its return in  close proximity  Furnish both with  permanent thermometers to check the  waterside balance during start up and  routine maintenance checks     Also  include strainers at each pump inlet  and unit  Install drain valves at the riser s  base to allow drainage points for system  flushing during start up and routine  maintenance  For condenser draining  and header removal  include a shutoff   balancing valve on the entering and  leaving waterside pipes  drain tees  and  unions of each unit  Also  install a shutoff  valve on the unit entering water pipe for  condenser draining     SCXG SVX01B EN    Installation    e TRANE        Note  Unit does not have floor drains     Water Temperature Requirements   Do not allow the entering water  temperature to go below 54 F  12 2 C  on  units with constant water flow  basic  piping   This will cause the compressors  to shut down and the mechanical cooling  function will lockout  However  the  economizer  if enabled  will continue to  function  The compressors will reset  when the entering water temperature  reaches 58 F  15C      Pressure  Gauge          Valve Pressure  Gauge    Water    Units with variable water flow  intermedi   ate piping  have a modulating condensing 
62.  to establish  the minimum damper position     When outdoor air conditions are above  the setpoint or comparative enthalpy    93    e TRANE    control setting  only mechanical cooling  will function and outside air dampers will  remain at their minimum position     Mechanical Cooling   If the zone temperature cannot be  maintained within the setpoint deadband  using the economizer option or if there is  no economizer  the RTM sends a cooling  request to the MCM  The compressor  module checks the compressor  protection circuit before closing stage  one  After the first functional stage starts   the compressor module monitors the  saturated refrigerant temperature and  closes the condenser fan output contact  when the saturated refrigerant  temperature rises above the lower limit  setpoint     Air Cooled Units Only   The compressor module closes the  condenser fan output contact when the  saturated refrigerant temperature rises  above the lower limit setpoint     Water Cooled Units Only   The WSM modulates the condenser coil  water valves to maintain condenser  temperature  if applicable  Otherwise  it  will check the entering condenser water  temperature to ensure it is greater than  54 F or if not  it will lock out cooling     Auto Changeover  Units with Heat    When the system mode is in auto  the  mode will change to cooling or heating as  necessary to satisfy the zone cooling and  heating setpoints  The zone cooling and  heating setpoints can be as close as 2 F   1 1 C    
63.  to the occupied mode  This binary  output signals the VAV boxes or other  terminal devices to go full open     RTM Alarm Relay   This is a single pole  double throw relay  rated at a maximum voltage of 24 vac  2  amps max  Relay contacts can be  programmed from the unit human  interface  This relay can be programmed  to pick up on any one or group of  diagnostics from the HI     Status Annunciator Output   The status annunciator output is an   internal function within the RTM module   on CV and VAV units  It provides    a  diagnostic and mode status signals to  the remote panel  LEDs  and to the HI    b  control of the binary alarm output on  the RTM    c  control of the binary outputs on the  GBAS module to inform the customer  of the operational status and or  diagnostic conditions     Occupied Unoccupied Inputs   There are four ways to switch to   occupied unoccupied    1  Field supplied contact closure  hardwired binary input to the RTM   2  Programmable night setback zone  sensor   3  Tracer Summit     4  Factory mounted time clock    VAV Changeover Contacts   These contacts are connected to the RTM  when daytime heating             units with  internal or external hydronic heat is  required  Daytime  occupied  heating  switches the system to operate as a CV  unit  Refer to the unit wiring diagram for  the field connection terminals in the unit  control panel  The switch must be rated at  12 ma   24 VDC minimum     External Auto Stop Switch   A field supplied switch may
64.  to the unit  does not exceed 400 psig     Note  To prevent water pump damage   design system piping to provide relief  when using energy saving waterside  economizer valves     Condensate Drain Connections   The condensate drain is internally  trapped  Condensate drain connections  are on the units left side  Connect  condensate drain piping to the 1 1 4    NPT  female fitting  using at least       OD  copper or 3   4    OD iron pipe  Pitch the  condensate line downward a minimum of  1   for each 10  of horizontal run  away  from the unit  Be sure to install the  condensate drain  P  trap drain plug   Before starting the unit  fill the trap with  water to prevent negative pressure in the  fan section from impeding condensate  flow To facilitate drain pipe cleaning   install plugged tees in place of 90    elbows     Table I MR 1  Water Connection Sizes     Unit Size  SXWG 20 35       Direct Condenser  17 2 NPT    Factory Piped  21 NPT             Figure I MR 2  Direct condenser connections     SCXG SVX01B EN    General Waterside Recommendations   Cooling Towers   Cooling tower control affects the unit  cycle rates  Condenser water  temperature swings from 10 15 degrees  F may cause excessive compressor   water valve  and unit cycling  Be sure to  set the tower controls to minimize  compressor unit cycling     Waterside Piping Arrangements   Install a condenser water pump between  the cooling tower  either open or closed   and the self contained unit  Lay out the  remainder of
65.  unit control  with safety features and control relays  for pumps  dampers  etc  The Modular  Series IntelliPak   self contained unit is  controlled by a microelectronic control  system that consists of a network of  modules  These modules are referred to    as unit control modules  UCM   In this  manual  the acronym UCM refers to the  entire control system network     These modules perform specific unit  functions using proportional integral  control algorithms  They are mounted in  the unit control panel and are factory  wired to their respective internal compo   nents  Each module receives and  interprets information from other unit  modules  sensors  remote panels  and  customer binary contacts to satisfy the  applicable request  i e   economizing   mechanical cooling  heating  ventilation   See the Owner s section of this manual  for a detailed description of each  modules function     Optional Controls   Optional controls include a disconnect  switch  dirty filter switch  water flow  switch  water cooled only   supply air  temperature reset  or external setpoint  inputs  Night heat morning warmup is  available with electric  steam  or hot  water heat control options     The static pressure probe  zone night  heat morning warm up  supply air  temperature reset sensor options ship  separate inside the unit control panel for  field installation  For more detailed  information on the unit control options   see the Owner s section of this manual     Unit Nameplate    The uni
66.  valve will sacrifice  free cooling and modulate to maintain  condensing saturated temperature  If not  economizing  the condenser valve will  modulate to maintain condensing  saturated temperature     Water cooled units without head pres   sure control will lock out mechanical  cooling at entering condenser water  temperatures below 54 F Mechanical  cooling will resume when the entering    89    e TRANE    condenser water temperature exceeds  58 F    Low Ambient Control  Air Cooled Units  Only    The low ambient modulating output on  the compressor module is functional on  all units with or without the low ambient  option  When the compressor module  stages up to it s highest stage  stage 2 or  3 depending on unit size   the modulating  output is 100   10 VDC   When the  control is at stage 1  the modulating  output  0 to 10 VDC  controls the  saturated condensing temperature to  within the programmable condensing  temperature low ambient control point     Low Ambient Compressor Lockout  Air   Cooled Units Only    The low ambient compressor lockout  utilizes an analog input device  When the  system is configured for low ambient  compressor lockout  the compressors will  not operate if the temperature of the  outside air falls below the lockout  setpoint  When the temperature rises 5 F  above the lockout setpoint  the  compressors will operate  The setpoint  for units without the low ambient option is  50 F For units with the low ambient  option  the setpoint is 0 F The setpo
67.  with the holes  in the unit channel  Install screws in the  top  6x  and bottom  6x  of the  economizer    7  Remove the units rear middle panel  and unbraze the two copper pipes in  the 2         water pipe  Do not remove  the pipe outlet blockoff panel    8  Remove the economizer tubing  assemblies from the shipping box   Check ship separate parts against  those shown in Figures I PR 6  I PR 7 l   PR 8  and I PR 9  Face the front of the  unit to see which side the water pipe  exits to determine if the unit has either  right or left hand piping    9  Assemble tubing as shown in Figure l   PR 6 or I PR 9  Tack all tubes in place  before brazing to ensure proper fit up   For right hand piped units  install the  ball valve actuator assembly and  actuator  Refer to the unit wiring  diagram for wiring connection points    10  Install the pipe insulation on all pipe  line to prevent sweating  Install the  rear middle panels  Re install the filter  rack on the back of the economizer coil  box and affix with screws provided     Waterside economizer must  be lifted and hooked over  flange in the opening of the  unit channel   Unit Top    Figure I PR 5  Installing the waterside economizer     SCXG SVX01B EN    e TRANE       Installation       Waterside Economizer with  Left Hand Factory Piping                                  Components  30 9 16     ASSEMBLY  1  38 7 8   ASSEMBLY  2  ws 9 1    ASSEMBLY  3 TET Rh d Lge  16 3 8     Figure I PR Z Waterside economizer with left hand fact
68.  zero  The  outside air damper minimum position  function will revert to using the O A flow    compensation function if O A flow  compensation is enabled or set to the  default minimum position function if O A  flow compensation is disabled or not  available    Reset Required   PAR  An automatic reset  occurs after communication is restored   communications with the VOM     Velocity Pressure Sensor Failure  Problem  The velocity pressure input  signal is out of range     Check  Check field unit wiring between  sensor and VCM     Reason for Diagnostic  The unit is reading  a signal that is out of range for the  velocity pressure transducer input   during calibration  V  lt  40 mV or V  gt  420  mV  during operation  V  lt  40 mV orV  gt   0 75 V      UCM s Reaction  The minimum airflow  control function is disabled  The outside  air damper minimum position function  reverts to using the O A flow  compensation function if O A flow  compensation is enabled or to the default  minimum position function if O A flow  compensation is disabled or not available     Reset Required   PAR  An automatic reset  occurs after the designated space  pressure transducer sends a signal within  range for 10 continuous seconds     VOM Communications Failure  Problem  The RTM has lost  communication with the VCM     Check  Field unit wiring between RTM  and            Reason for Diagnostic  The RTM has lost  communications with the VOM     UCM s Reaction  Ventilation override  actions will not be al
69. 0 7575 1  Actuator Assembly  X21080406030 14 ft   Rubatex Insulation  X21040098390 10 ft     Gasket        These items require field assembly        Item        Description  Assembly  1  Assembly  2  Assembly  3  Assembly  4   Tube  25    x 11 3 4     Tube  2          x 20 1 4     Actuator Assembly                         Q     m O  O       gt           Figure I PR 8  Waterside economizer with right hand factory piping tubing assembly       9 1       33 3 8        Assembly 1 Assembly 3  5 5 8   16 3 8   Assembly 4       Assembly 2    Figure I PR 9  Detail view of ship separate tubing assemblies for waterside economizer right hand factory piping     44 SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE       Hydronic Coil Installation    These instructions are for steam and hot  water coil installation  The hydronic coil  assembly has a full coil  piping  a modu   lating temperature control valve  and a  disc temperature limit device located in  the unit near the fan on the motor frame   Hydronic coils are available with either  right or left hand pipe connections  Piping  connections are identical to the unit  piping  For example  if you have right   hand unit piping  the hydronic coil will  have right hand connections  The  hydronic coil assembly has temperature  controls to keep the unit s internal cabinet  temperature below 105 F to prevent  motor and bearing damage     Installation Procedure   1  Remove filter rack from the back of the  unit  Remove the    inch h
70. 2   Stage Off 5   Stage On  on the suction line near the TXV bulb of 3   Stage On 6   Stage Off  each circuit to protect the evaporator   from freezing     Control Response    Figure O SO 3  Typical pulldown curve for unit operating improperly outside control band   If the evaporator temperature ap     proaches the specified setpoint  adjust   able between 25 and 35 F at the HI  the  compressor s  will cycle off  The supply  fan remains on to help de ice the coil  The  compressors will restart when the  evaporator temperature has risen 10 F  above the specified cutout temperature  and when the compressor s  have been  off a minimum of three minutes  This  prevents rapid cycling of the compres   sors     Service Valves   Service valves are factory installed on  each circuit before and after the  compressor to allow compressor  isolation for servicing     SCXG SVX01B EN 97    e TRANE    Maintenance Procedures    Air Filters   Filter access doors are on the same side  of the unit as the water piping  connections  To replace throwaway  filters  remove the dirty elements and  install new filters with the filter s  directional arrows pointing toward the  fan  Verify that no air bypasses the filters     All unit sizes require four 16 x 25 x 2 inch   508 x 635 x 51 mm  and four 20 x 25 x 2  inch  508 x 635 x 51 mm  filters     Inspecting and Cleaning the  Drain Pan    Check the condensate drain pan and  drain line to ensure that the condensate  drains properly at least every six mont
71. 3 Fan   Diameters    Return  Air    Figure           1  Duct connection recommen   dations     33    e TRANE    Water Piping    Note  To prevent water damage  install all    piping drain and vent plugs     Condenser Connections   Condenser water piping knockouts are in  the lower left end panel  If necessary   remove insulation to gain access  All field  installed piping must conform to  applicable local  state  and federal codes   To complete condenser water  connections follow the procedure below     Note  Four condenser waterline drain    plugs ship         bag in the units left end   The installer must field install these four  plugs using pipe thread sealer  An addi   tional plug are provided for units with a  waterside economizer     1  Install the vent plugs in the economizer  coil headers and condenser manifolds   These plugs ship in a bag with the  condenser drain plugs     34    Installation       2  Attach the water supply line to the inlet  connection  and the return line to the  outlet connection  Entering and leaving  water connections for all condensers  are factory manifolded and require only  single connections for entering and  leaving water  If the unit has a  waterside economizer and or control  valves  the factory pipes between these  components    3  If using a cooling tower  refer to Figure  I MR 3 on page 35 for a typical piping  circuit from the unit  For typical city or  well water piping  see Figure I MR 4 on  page 35    4  Ensure the water pressure
72. 32  35 Tons 14 3 4 15 5 8 23 3   4       Table I PR 5  Electric Heat Dimensions   Metric                         Unit Size   1   2 Z   20Tons 273 397 705  25Tons 311 397 679  30  32  35 Tons 375 397 603       SCXG SVX01B EN    Installation    e TRANE          Variable Frequency Drive  Option  VFD     The variable frequency drive  VFD   option can only be used with IntelliPak  units  The VFD and VFD w bypass is  available from 7 5 to 25 hp and is a  Square D model Altivar 58  All VFDs are  pre configured and run tested at the  factory prior to shipping  The VFD is wall  mounted  For more information on the  VFD  see the manuals that ship with each  VFD  Altivar 58 Adjustable Speed Drive  Controllers Keypad Display and   Altivar 58 Adjustable Speed Drive  Controllers Installation Guide Type H  Controllers     Control and line voltage wiring  from the VFD to the unit must be  in accordance with all local and  National Electric Codes  Do not  touch circuit components until  main power has been turned off  and  charge  lamp is  extinguished  The capacitors are  still charged and can be quite  dangerous        Disconnect electrical power  source to prevent injury or death  from electric shock  Do not  connect or disconnect wires and  connectors while power is  applied to the circuit           A CAUTION    Use only copper conductors for  electrical unit connections to  prevent equipment damage        VFD Mounting Requirements   Proper location of the VFD is important to   achieve pr
73. 337 292          p pee    LJ LJ    TOP VIEW   SHOWN WITH VERTICAL DISCHARGE OPTION     SCXG SVX01B EN 21    e TRANE    Hot Water Coil       AIR INLET    22                         Installation                                  HOT WATER OUTLET CONNECTION  HOT WATER OUTLET CONNECTION             Hot Water Coil Dimensions   English    inches     UnitTon A B C D E F G H J  20 35 277  539  16   73   4   167  431  5   7               Hot Water Coil Dimensions   Metric  mm     UnitTon A B C D E F G H J  20 35 946 1365 422 1867 378 413 1099 14 187             SCXG SVX01B EN    e TRANE       Installation       Steam Coil                               VACUUM TRAP CONNECTION                      CONDENSATE RETURN       Z                         AIR INLET P VACUUM TRAP CONNECTION       Q CONDENSATE RETURN      STEAM INLET CONNECTION  R           Steam Coil Dimensions   English    inches   Unit Ton A B C D E K L M N P Q R  20 35 371  53   16  737  10  22  3  157  1 41 93  43   Steam Coil Dimensions   Metric  mm   UnitTon A B C D E K L M N P Q R  20 35 946 1365 422 1867 276 572 86 403 25 1041 238 111       SCXG SVX01B EN 23    e TRANE    Installation          eA                7                Installation       Waterside Economizer    10    254mm     53 3 4    1365mm                     AIR INLET                                                 SCXG SVX01B EN 25    TRANE    Installation    SEE DETAIL A ON PAGE 27                                     LIFT ON BOTTOM EDGE  OF ECONOMIZER   TYP 
74. 4 5 vde 50 to 90 F  CV and VAV   Occupied Zone Heating Setpoint 0 5 to 4 5 vdc 50 to 90 F  CV units onl   Unoccupied Zone Heating Setpoint 0 5 to 4 5 vde 50 to 90 F    CV and           Supply Air Cooling Setpoint 0 5 to 4 5 vde 40 to 90 F    VAV units only    NI Air Hydronic Heating Setpoint 0 5 to 4 5 vdc 40 to 180 F    VAV units only    Space Static Pressure Setpoint 0 5 to 4 5 vdc 0 03 to 0 30 IWC   Supply Air Pressure Setpoint 0 5 to 4 5 vdc 0 0 to 5 0 IWC    VAV units only        Note  1  Input voltages less than 0 5 vdc are considered as 0 5 vdc input signal is lost  the setpoint will     clamp    to the low end of the setpoint scale  No diagnostic will result from this condition   2  Input voltages greater than 4 5 vdc are considered to be 4 5 vdc   3  The actual measured voltage is displayed at the HI     Table O GI Z GBAS Input Voltage Corresponding Setpoints  Volts Temp  Volts Temp  Volts Temp Volts Temp                            0 6 51 17 61 27 71 28 81  07 52 18 62 28 72 29 82  08 53 19 63 29 73 3 0 83  0 9 54 2 0 64 3 0 74 3 1 84  1 0 55 2 1 65 3 1 75 3 2 85  1 1 56 2 2 66 3 2 76 3 3 86  1 2 57 2 3 67 3 3 77 34 87  1 3 58 2 4 68 34 78 3 5 88  1 5 59 2 5 69 3 5 79 3 6 89       83    e TRANE    Waterside Components    Waterside components consist of water  piping  water valves  water flow switch  option  water cooled condensers  SXWF  only   and the economizer option     Water Purge   This user definable feature allows the  user to select a purge schedule to  auto
75. 52 100  SCRG 25 47 100  SCRG 32 52 100       SCXG SVX01B EN    e TRANE    Owner       band according to the desired unit    performance  Increasing the control band 7 1   reduces the equipment cycle rate and 1   1st stage on   increases the maximum potential supply 2 2   2nd stage on  air temperature deviation from setpoint  3   3rd stage on  Conversely  decreasing the control band 3    reduces the maximum potential tem   perature deviation  but increases the  compressor cycle rate     Follow these recommendations concern   ing the supply air temperature control  band settings based on expected unit  sizing        2 Cooling stage unit  9 F    3 Cooling stage unit  7 F Typical Pulldown Response    4 Cooling stage unit  6 F Figure O SO 2  Typical pulldown curve for unit operating properly within control band     Low Ambient Compressor Lockout   This function will lock out the compressor  if the outdoor air temperature sensor  reads an outdoor temperature below the  low ambient compressor lockout  temperature setpoint  This setpoint is  adjustable at the human interface panel   Compressors will lock Out when outdoor I          c  air temperature falls below that selected  temperature and will start again when Set  the temperature rises 5 F above the Point  setpoint         Control  Band    Evaporator Coil Frost Protection  FROSTAT       The FROSTAT    system eliminates the  need for hot gas bypass  It utilizes an 1   Stage On 4   Stage Off  evaporator temperature sensor mounted 
76. 6 416 378 152 1178   521   82             30 SCXG SVX01B EN    Installation    e TRANE          Flexible Horizontal Discharge    Plenum    SCXG SVX01B EN    Flexible Horizontal Discharge Plenum Dimensions   English    inches              20 35 Tons A B C  Low Height 35 177  86 5  Standard Height 35 25 1  86        Flexible Horizontal Discharge Plenum Dimensions   Metric  mm              20 35 Tons A B C  LowHeight 889 438 2197  Standard Height 889 641 2197       e TRANE    Installation                                                          Table I DW 1  Unit Weights  English   SCWG SCRG SIWG SIRG  2 Row 4 Row  Unit Base Airside Waterside Waterside Heating  Size Weight Economizer Economizer Economizer Coil Box  Ibs  Ibs  Ibs  Ibs  Ibs   SCWG SIWG 20 2620 273 488 584 460  25 2730 273 488 584 460  30 2864 273 488 584 460  35 3000 273 488 584 460  SCRG SIRG 20 2344 273 488 584 460  25 2479 273 488 584 460  32 2614 273 488 584 460  Notes   1  All unit weights include refrigerant  water  inlet guide vanes and controllers  electric heat and valves   2  Add 150 Ibs  to total weight to obtain approximate shipping weight   3  Flexible horizontal discharge plenum option weights   Standard height plenum   352 Ibs   Low height plenum   262 165   4  VFD weights are on pages 28 and 30   Table I DW 2  Unit Weights  Metric   SCWG  SIWG SCRG SIRG  2 Row 4 Row  Unit Base Airside Waterside Waterside Heating  Size Weight Economizer Economizer Economizer Coil Box  Kg Kg Kg Kg Kg  SCWG SIWG 20 13
77. 65 195 65 155 210  25 1400 195 65 155 210  30 1500 225 85 175 210  35 1640 225 130 230 210  SCRG SIRG 20 1325 195 65 155 210  25 1425 225 85 175 210  32 1530 225 130 230 210  Notes     1  All unit weights include refrigerant  water  inlet guide vanes and controllers  electric heat and valves   2  Add 68 kg  to total weight to obtain approximate shipping weight   3  Flexible horizontal discharge plenum option weights   Standard height plenum   160 kg  Low height plenum   119 kg  4  VFD weights are on pages 28 and 30     32    SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE       Duct Connections    Disconnect electrical power  source before servicing the unit   Failure to do so may result in  injury or death from electrical  shock or entanglement in moving  parts        Return air enters the rear of the unit and  conditioned supply air discharges  through the top  Attach supply air  ductwork directly to the unit s top panel   around the fan discharge opening  A duct  collar is not provided     Note Units equipped with the flexible  horizontal discharge plenum option may  include a duct collar when holes are factory  cut  If discharge openings are field cut   refer to the    Plenum Installation    section     Install all air ducts according to the  National Fire Protection Association  standards for the    Installation of Air  Conditioning and Ventilation Systems  other than Residence Type  NFPA 90A   and Residence Type Warm Air Heating  and Air Conditioning Systems
78. 8   Installing the Transducer 49   ntelligent Copy 70   IntelliPak Unit Controls 5   ntermediate Water Piping 84   Interprocessor Communication Bridge  Module Wiring 61   nterprocessor Communications Board  80   PCB 80    K    Keypad Lockout 67  Keypad Operation for Temporary  Manual Override Men 67  68          L  Leak Test 36  LEATPD 90    Literature Change History 2  Low Air Temp Limit Trip 114  Low Ambient Compressor Lockout    SCXG SVX01B EN    e TRANE       90  97  Low Ambient Control 89  90  Low Ambient Sensor 86  Low Entering Air Protection Device 90  Low Entering Air Temperature Sensor  86  Low Pressure Control 89  Low Pressure Control Open 114  Low Pressure Control Open 114  Low Voltage  AC  Field Wiring  Connections 61    M    Maintenance Procedures 98   Manual Override 73   Manual Reset SA Static Press Limit  114   MCM 80   MCM Communications Failure 114  Measuring Belt Tension 100  Mechanical Cleaning of Condenser and  Economizer Coils 108  Mechanical Cooling 94   Minimum Outside Air Setpoint w VCM  Module        Traq 81   Mode Button 67   Mode Input Failure 114   Model Number Description 6  Monthly Checklist 110   Morning Warmup 91   Mounting Location 53   Mounting the Remote Human Interface  59   Mounting the Subbase 53   MWU 91    N    NSB Panel Comm Failure 115  NSB Panel Zone Temperature Sensor  Failure 115          O A Humidity Sensor Failure 115  O A Temp  Sensor Failure 115  Occupied Sequence Of Operation 93  Occupied Zone Heat Setpoint Failure           
79. AS  VOM   and RHI   N   GBAS  TCI  and RHI   P   VOM  TCI  and          R   GBAS  VOM  TCI  and RHI   0   None    Digit 34   Agency  T  UL Agency Listing  0  None    Digit 35   Filter Type  1   2 inch Construction Throwaway  2   2 inch Med Eff  Throwaway    Digit 36   Miscellaneous Control Option        Low Entering Air Temp  Protect  Device  LEATPD      High Duct Temp T Stat     Plenum High Static Switch     Kit for Heat Mode Output  w t stat      AandB   AandC   Band C   A  B  and C   None                                BAYSTATOS7A   2 Heat 2 Cool  Programmable Thermostat  0  None    Digit 7   Mixed Air Temperature Protec   tion Kit  field installed    1   Mixed Air Temperature Protection Kit  0   None   Digit 8   Carbon Dioxide Sensor  field  installed    1   Carbon Dioxide Sensor Kit   0   None   Digit 9   Future Option   0   None   Digit 10  11   Design Sequence   AO   A Design    e TRANE    installation       AfterShipment    Accessory Model Number              20 4 2      A B2    065 B A 1    010 AACF A 1    10   20       123 4 5 67 8 9 1011 12 13 14 1516 171819 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36       Digit 1   Parts Accessories  P   Parts Accessories    Digit 2   Unit Model  S  Self Contained    Digit 3   Shipment  A  After Unit    Digit 4   Development Sequence  F   Signature Series  G   Modular Series    Digit 5   Condenser Medium  W   Water Cooled  R   Remote Air Cooled    Digit 6   Refrigerant Circuit Configuration  N   Independent  Water Cooled  
80. Assembly    section  on page 14 before completing this  step  Test lift the unit to determine  exact unit balance and stability before  hoisting it to the installation location   See Figure         7 and         8 on page  13 for typical rigging procedures   including cautions and proper uses of  such equipment as fork lifts  spreader  bars  and hooks     4  Remove the skids from under the unit   See the    Rigging and Handling     section on page 12  Refer to the    Skid  Removal    section on page 16  If you  find internal damage  file a claim  immediately to the delivering carrier     5  Remove the protective shipping covers  from the unit  Refer to the    Unit  Protective Covers    section on page 39     Note  Unit height and connection locations    will change if external vibration isolators  are used  The unit may be raised an  additional 5 7 5 inches with spring type  isolators     Note  Unit height and connection locations    will change if the unit is constructed to be  split a part in the field  See unit submittal  drawings for connection locations     6  Electrical supply power must meet  specific balance and voltage  requirements  as described in the   Electrical Requirements  section on  page 37     7  Water cooled units only  model  SXWG   The installer must furnish and  install a condenser main and standby  water pump  cooling tower  pressure  gauges and all components for the  waterside piping  See the  Water  Piping  section on page 34 for general  waterside 
81. BOTH ENDS        Airside Economizer Dimensions   English    inches     Unit Size A B C D E F   F2 G   G   Hm  HQ J K L M  SCWG SIWG 20 25 36 655  37 741  67  56   49   231  20   5   7 207  17  17 49    SCRG SIRG 20   SCWG SIWG 30 35 36 65   37 747  6  61  623  28   207  3   7 207  17  5   62   SCRG SIRG 25  32                Airside Economizer Dimensions   Metric  mm     Unit Size A B C D E    1  F 2 GA  G 2    1  H 2 J K L M  SCWG SIWG 20 25 914 1667 940 1886 156 1435 1264 591 521 143 178 521 435 305 1264  SCRG SIRG 20  SCWG SIWG 30 35 914 1667 940 1886 156 1559 1594 714 521 83 178 521 435 140 1594  SCRG SIRG 25  32             26 SCXG SVX01B EN       Detail    A          DETAIL A SHOWS THE AIRSIDE ECONOMIZER WITH ALL     1  DAMPER CONFIGURATIONS CURRENTLY AVAILABLE AND  2   ALL OPENING DIMENSIONS  NECESSARY FOR DUCT WORK      Detail             STATIC PRESSURE TUBE FROM UNIT     5 gt         STATIC PRESSURE TUBE FROM UNIT  AND CONNECTOR ON ECONOMIZER    ECONOMIZER    GASKET  Factory  provided  for field  installation     SCXG SVX01B EN 27    e TRANE    Variable Frequency Drive    28    Variable Frequency Drive Dimensions   English    inches     B    Installation        K  MOUNTING  HOLES  4X     FRONT VIEW       RIGHT SIDE VIEW                                                                         Motor HP Voltage A B C D E F G H J K Weight   75 200V 9 7 8 7  29  WV  127  V  87 7  26168    75 460V 6        6  Choo 11  S 00 7h 3o o 77  OW   15lbs    10 200V 9 U 8 7  12   7 
82. Chemical Clean Full Cap   4 row     Chemical Clean Low Cap   2 row     Mechanical Clean Full Capacity   4 row  Ship Separate    Mechanical Clean Low Capacity   2 row  Ship Separate  G   Chemical Clean Full Capacity   4 row  Ship Separate  H   Chemical Clean Low Capacity   2 row  Ship Separate  0   None    Digit 28   Ventilation Control        Airside Econ w Traq  Damper   Top O A Inlet    C   Airside Econ w  Standard  Dampers  Top O A Inlet    E  Airside Econ w Traq    Damper and  Comparative Enthalpy   Top O A Inlet    F  Airside Econ w  Std Dampers and  Comparative Enthalpy  Top O A  Inlet    G   Trag Damper Ventilation Interface     n    Installation    e TRANE       Ve 2 For 2 Pos  Cntrl Interface  Non    igit 29   Water Piping    Right Hand Condenser Connection    Left Hand Condenser Connection    Right Hand Basic Piping  Left Hand Basic Piping  Right Hand Intermediate Piping    Left Hand Intermediate Piping    Right Hand Basic w  Flow Switch    Left Hand Basic w  Flow Switch    Right Hand Intermediate   w  Flow Switch  M  Left Hand Intermediate   w  Flow Switch   0   None             a ae    Digit 30   Condenser Tube Type   A   Standard Condenser Tubes  B 90 10 CuNi Condenser Tubes  0   None    Digit 31   Compressor Service Valves  1   With Service Valves  0   None    Digit 32   Miscellaneous System Control    Timeclock   Interface for Remote        Dirty Filter Switch   1       2   1            2             1 2              None         2  3  4  5  6  7  0    Self Con
83. HCFC22   R22  rather than CFC12  R12  or any  other fully halogenated refrigerants  Be  aware of any new leak test methods  which eliminate refrigerant as a trace  gas      When cleaning system components or  parts  do not use CFC11  R11  or CFC  113  R113   Refrigeration system clean   up methods using filters and dryers are  recommended  Do not use solvents  which have ozone depletion factors   Properly dispose of used materials    eTake extra care to properly maintain all  service equipment directly supporting    refrigerant service work such as  gauges  hoses  vacuum pumps  and  recycling equipment    e Stay aware of unit enhancements   conversion refrigerants  compatible  parts  and manufacturer s  recommendations that will reduce  refrigerant emissions and increase  equipment operating efficiencies   Follow specific manufacturer s  guidelines for conversion of existing  systems     To assist in reducing power generation  emissions  always attempt to improve  equipment performance with improved  maintenance and operations that will  help conserve energy resources     Refrigerant Leak Testing    Do not work in a closed area  where refrigerant or nitrogen  gases may be leaking  A  sufficient quantity of vapors may  be present and cause injury or  death        Do not use oxygen  acetylene  or  air in place of refrigerant and dry  nitrogen for leak testing  A  violent explosion may result  causing injury or death        Always use a pressure regulator   valves  and gauges to
84. I PR 27 BAYSENS020 dimensions     Installation Procedure   1  Remove the zone sensor module from  the subbase  Carefully hold the zone  sensor module with one hand and  firmly grasp the subbase with the other     56    Installation    See Figure I PR 27 To remove the zone  sensor module from the subbase   gently pull away and upward         CAUTION    The zone sensor module is an  electronic sensitive device  Do  not touch printed circuit board   electronic components  or  connector pins  Handle plastic  housing only to prevent damage  to electronic components         Figure I PR 28  Removing the zone sensor  module from the subbase     2  After disassembly  protect the internal  surfaces from contact with objects or  substances that could cause damage    3  Remove the terminal block from  subbase and set aside for wiring   Discard the tape    4  Mount the zone sensor module using  the mounting hardware included in the  shipping package  The mounting  hardware is contained in single plastic  bag and includes    Plastic wall anchors  3 x   e Mounting screws  3 x   The zone sensor module can mount  directly to a wall or to a junction box  mounted to    wall  To mount to     junction box  you must have the  mounting plate and adapter kit   BAYMTPLOO3  Installation instructions  are enclosed with the mounting plate   5 To mount the zone sensor module  directly to a wall    a  Hold the subbase in position and mark  the three mounting hole locations on  the wall    b  Drill three 3
85. NE       Su Mo Tu We Th Fr Sa    NOWE TAFTS MODE  CL  bL   OFF   Desired         L HEAT       HEAT COOL  AM PM                                OVERRIDE AUTO   T I  AMAN                  II I  OCCUPIED Ton ER ERN  AUTO      ROOM TEMP             Figure I P 5  Override run mode screen     Temporary Override Run Mode   The temporary override run mode sends  setpoint data to the Unit Control Module   UCM  from the setpoint data entered in  the temporary manual override menu     In temporary override run mode  most of  the keypad functions lock out with these  exceptions    e The mode button still functions as in  normal run mode    e The fan button still functions as in  normal run mode    e Depressing the holdtemp button toggles  the ZSM between the temporary  manual override menu and override  run mode   if no button is pressed for 20  seconds while in temporary manual  override menu  the ZSM exits to normal  run mode  ignoring the temporary  override settings       Depressing either the T or   arrow while  in the override run mode will cause the  ZSM to toggle to the temporary manual  override menu      The erase button will turn off the check  filter icon if displayed    e Simultaneously depressing and holding  the positive and negative sides of the   minus  and  plus  for four seconds  will lock out the keypad    eTime is not adjustable in this mode      The program button is disabled     68    Installation    Keypad Operation for Temporary Manual   Override Menu   The keypad
86. Only    During occupied mode  if the zone  temperature falls to a preset  user   defined zone low limit temperature  setpoint  the unit is put into daytime  warmup  The system changes over to CV  heating  the VAV boxes drive full open   However  unit airflow modulation control  operates to maintain duct static setpoint   and full heating capacity is provided until  the daytime warmup setpoint is reached   The unit is then returned to normal  occupied mode     Supply Air Tempering   Supply air tempering is available on units  without volume control and with hot  water  steam  or electric heat or units with  supply air temperature control with  steam or hot water heat  When the unit is  in heat mode but not actively heating  if  the supply air temperature drops to 10 F   5 5 C  below the occupied zone heating  temperature setpoint  electric heat will  stage on or the hydronic valve will  modulate to maintain a minimum supply  air temperature  The unit transitions out  of heat mode if the supply air  temperature rises to 10 F  5 5 C  above  the occupied zone heating temperature  setpoint     Changeover   This mode only functions on units with  supply air temperature control and  hydronic heat  When the changeover  binary input is closed the unit will control  to a discharge air heating setpoint  This  setpoint is entered at he              can be a  higher temperature than the supply air  cooling setpoint  This function maintains  duct static pressure     SCXG SVX01B EN    Compr
87. RANE    102    Owner       Refrigerant System    Special Note on Refrigerant Emissions  Follow the Trane recommended  procedures on operation  maintenance   and service to ensure refrigerant  conservation and emission reduction   Also  pay specific attention to the  following    e Whenever removing refrigerant from  air conditioning or refrigerating  equipment  recover for reuse  recycle   reprocess  reclaim   or properly  destroy it    e Always determine possible refrigerant  recycling or reclaiming requirements  before beginning recovery  Questions  about recovered refrigerants and  acceptable refrigerant quality  standards are addressed in ARI  Standard 700    e Use approved containment vessels  and safety standards  Comply with all  applicable transportation standards  when shipping refrigerant containers    eTo minimize emissions while  recovering refrigerant  use recycling  equipment  Always attempt to use  methods which will pull the lowest  possible system vacuum while  recovering and condensing refrigerant  into containment      When leak checking with trace  refrigerant and nitrogen  use HCFC22   R22  rather than CFC12  R12  or any  other fully halogenated refrigerants   Be aware of any new leak test  methods which eliminate refrigerant  as a trace gas    e When cleaning system components or  parts  do not use CFC11  R11  or  CFC113  R113   Refrigeration system  clean up methods using filters and  dryers are recommended  Do not use  solvents which have ozone depleti
88. Reaction  Off or close requests are   issued as appropriate to the following   functions    a  Compressor staging chilled water  cooling control   b  Heat operation   c  Supply fan control and proof of  operation   d  Exhaust fan control and proof of  operation    e  Exhaust actuator control   f  Outside air damper control   g  On        units  IGV VFD control    Reset Required   PMR  A manual reset is  required after the emergency stop input  recloses  The diagnostic can be reset by  the HI  Tracer Summit    or by cycling  power to the RTM     Entering Cond Water Temp Sensor Fail  Problem    Activation Conditions  temperature  lt   50  F or temperature  gt  209 F and unit  configured for water cooled   condenser   c  Time to React  10 sec  lt T  lt  20 sec   d  Diagnostic Text  Human Interface  Display   ENT COND WATER TEMP  SENSOR FAIL      e  Actions to be Initiated  A    Lockout All  Ckts     request is issued to the     Compressor Staging Function      f  Reset  An automatic reset occurs after  the entering condenser water  temperature input returns to within range  continuously for 15 seconds     Entering Water Temp Sensor Fail  a  Data used  module packet byte  bit      SCXG SVX01B EN    Diagnostic  Troubleshooting    e TRANE       WSM  01 18 05   b  Activation Conditions  temperature  lt     50 F or temperature  gt  209 F and unit  configured with water cooled   condenser and or economizer   c  Time to React  10 sec  lt T  lt  20 sec   d  Diagnostic Text  Human Interf
89. Temporary Manual Override   While in normal run mode  depressing  the hold temp button toggles the ZSM to  the temporary manual override menu     The mode will override any number of  programmed setpoints through any of  the 28 programmed periods  After  entering setpoints and length of override  time  these new settings are used in place  ofthe setpoints programmed for normal  run mode     Time Button     While in the program menu  each time  you press and release the positive or  negative side of the time button  the  time will advance or decrease by ten  minute increments  If you press and  hold the positive or negative side      minus    and  plus  keys   the ZSM  will increment rapidly      When the display is in the normal run  mode  each time you press and release  the positive or negative side of the time  button   minus  and  plus  keys   the  time will advance or decrease by one  minute  If you press and hold the  positive or negative side   minus  and   plus  keys   the ZSM will increment  rapidly     Note  Blank temperature settings may be    entered at any of the four daily periods   When a setpoint is left blank and in an  occupied condition  the ZSM will default to  the last occupied setpoint     Keypad Lockout   If you simultaneously depress and hold  both the positive and negative sides of  the  minus  and  plus  keys for four  seconds  the lock icon will appear and all  keypad functions will lock out  If you  repeat this operation  the lock icon will  disapp
90. Those four  periods are  Morn ing   Day  Eve ning    and Night     To exit the program menu  depress the  program button for two seconds        Morn Day Eve Nite  Su Mo Tu We Th Fr Sa    mF  oe Desired   oan   at 1              HEAT COOL  AM PM    OCCUPIED             Figure I P 3  Display Program Menu Screen     Program Menu  BAYSENSO20 Only    Note  After toggling to the program    screen  the week is divided into seven  days with each day divided into four  periods     Setpoint programming depends on the  setting status  occupied or unoccupied   and whether or not the heat installed   modulated heat  morning warmup  or  daytime warmup options are enabled     In the occupied period  the cool supply air  temperature is always set  If heat  installed and modulated heat options are  on  the supply air heat is also set during  occupied periods  The warmup tempera   ture is also set in occupied periods  if heat  installed and warmup options are  enabled     During unoccupied periods  only the  desired room temperature setpoints are  entered  Each unoccupied period has a  heat and cool setpoint  and both setpoints  are offered during programming     Blank temperature settings may also be  entered  When a setpoint is blank  the  program will default to the last setpoint of  its type  If there is no setpoint of its type   the default setpoint is used  If all setpoints  in the time period are blank  is erased  after exiting from the program menu     The ZSM has independent  seven da
91. abled     Reset Required   PAR  An automatic reset    occurs after communication has been  restored      0     O A Humidity Sensor Failure  Problem  The outside air humidity sensor  data is out of range     Check  Check field unit wiring between  the sensor and RTM     Reason for Diagnostic  The unit is reading    SCXG SVX01B EN    Diagnostic  Troubleshooting    e TRANE       a signal that is out of range for the outside  air humidity sensor  humidity  lt  5  or  humidity  gt  100             5 Reaction  The economizer enable  r e enthalpy function reverts to dry bulb  temperature changeover     Level 1      control     Reset Required   PAR  An automatic reset  occurs after the OA humidity input  returns to its allowable range for 10  seconds     O A Temp  Sensor Failure  Problem  The outside air temperature  sensor input is out of range     Check  Sensor resistance should be  between 830 ohms  200 F and 345 7  Kohms   40      If so  check field unit wiring  between sensor and RTM     Reason for Diagnostic  The unit is reading  a signal that is out of range for the outside  air temperature input on the RTM  temp    lt   55 F or temp  gt  209 F             Reaction  These unit functions   occur      low ambient compressor lockout  disables   e O A damper drives to minimum position   e on        units with S A temp  reset type  selected as O A temp  reset  the reset  type reverts to    none    for the duration  of the failure    Reset Required   PAR  an automatic reset  occurs 
92. ace  Display     ENTERING WATERTEMP  SENSOR FAIL      e  Actions to be Initiated  A    Disable  Water Side Economizer    request is  issued to    Water Side Economizer  Temperature Enable Function      f  Reset  An automatic reset occurs after  the Entering Water Temp  input returns to  within range continuously for 10 seconds     Evap Temp Sensor Failure   Circuit 1  2  3   or 4   Problem  The evaporator temperature  sensor  ckt  1  2  3  or 4  is out of range     Check  Sensor resistance should be  between 830 ohms  200 F  and  345 7Kohms   40 F   If so  check field unit  wiring between sensor and MCM SCM     Reason for Diagnostic  The unit is reading  a signal that is out of range for the circuit    1 evaporator temperature sensor input    temp  lt   55 F or temp  gt  209                   Reaction  The coil frost protection  function for the refrigeration circuit   1   2 3  or 4  only is disabled     Reset Required   PAR  An automatic reset  occurs after the  1  2  3  or 4 evap temp  input returns to its allowable range for 10  seconds     G    GBAS 0 5 VDC Module Comm Failure  Problem  The RTM has lost  communication with the GBAS module     Check  Field unit wiring between RTM  and GBAS     Reason for Diagnostic  The RTM has lost  communication with the GBAS module     UCM s Reaction  The UCM will initiate the   following actions        If the demand limit input was closed  prior to the communications loss  then    the demand limit commands issued to  the heat operation
93. after the O A temperature input  returns to its allowable range  To prevent  rapid cycling of the diagnostic  there is a  10 second delay before the automatic  reset     Occupied Zone Heat Setpoint Failure  Problem  The occupied zone heat setpoint  input is out of range     Reason for Diagnostic  The input  designated as occupied zone heating  setpoint source is out of range for the  outside air temperature input on the RTM   temp   lt  45 F or temp  gt  94 F      UCM s Reaction  The active occupied    zone heating setpoint reverts to the  default value     Reset Required   PAR  an automatic reset  occurs after the occupied zone heating  setpoint input returns to its allowable  range for 10 continuous seconds  or after  a different occupied zone heating setpoint  selection source is user defined     R    Return Air Humidity Sensor Failure  Problem  On units with both airside  economizer and comparative enthalpy  installed  the return air humidity sensor  input is out of range     Check  Check field unit wiring between  the sensor and ECEM     Reason for Diagnostic  The unit is reading  a signal that is out of range for the return  air humidity sensor  humidity  lt  5  or  humidity  gt  100       UCM s Reaction  The economizer enable  r e  enthalpy function reverts to reference  enthalpy changeover     Level 2     control     Reset Required   PMR  An automatic  reset occurs after the RA humidity input  returns to its allowable range  continuously for 10 seconds     Retum Air T
94. age immediately by phone and  mail  Request an immediate joint  inspection of the damage by the carrier    and consignee     O Notify your Trane representative of  the damage and arrange for repair   Have the carrier inspect the damage  before making any repairs to the unit     Shipping Covers    Detail A     C  Channel    Figure         1  Typical unit mounted on shipping skid     Filter Channels  Note 1    Filter Channels  Note 1    Supply and Control  Wiring Knockouts    Metal Channel  Shipping Skid    Optional spring isolators or  isopads  strapped inside of unit        e TRANE    Installation    Installation Preparation    Before installing the unit  perform  the following procedures to  ensure proper unit operation     1  Verify the floor or foundation is level   Shim or repair as necessary  To ensure  proper unit operation  install the unit  level  zero tolerance  in both horizontal  axis  Failure to level the unit properly  can result in condensate management  problems  such as standing water  inside the unit  Standing water and wet  surfaces inside units can result in  microbial growth  mold  in the drain  pan that may cause unpleasant odors  and serious health related indoor air  quality problem     2  Allow minimum recommended  clearances for maintenance and  routine service  See    Service Access     section on page 11     3  Position the unit and skid assembly in  its final location  If unit shipped split   apart  follow the procedure in the     Split Apart Unit 
95. agnostic  there is a 10 second  delay before the automatic reset     RTM Data Storage Error  Problem  There was a data transmission  error     Check  This can be caused by an  intermittant power loss  Turn the unit off  for 1 2 minutes  then back on again  If  diagnostic persists  then the RTM may  need to be replaced     Reason for Diagnostic  An error occurred  while the RTM was writing data to its  internal non volitile memory  EEPROM             Reaction  An information only  diagnostic will be displayed at the Human  Interface     Reset Required   INFO  A manual reset  may be made at the Human Interface  at    Tracer Summit   or by cycling power to  the RTM     RTM Zone Sensor Failure    116    Diagnostic  Troubleshooting       Problem  The RTM zone temperature  sensor input is out of range     Check  Sensor resistance should be  between 830 ohms  200 F and 345 7  Kohms   40 F   If so  check field unit wiring  between sensor and RTM     Reason for Diagnostic  At least one  enabled unit function has the RTM zone  temperature input designated as its  sensor  and the unit is reading a signal  that is out of range for this input  temp        55 F or temp    150 F      UCM   Reaction The functions with the  RTM zone temperataure input deignated  as their sensor are disabled     Reset Required   PAR  an automatic reset  occurs after the designated zone  temperature signal returns to its  allowable range  To prevent rapid cycling  of the diagnostic  there is a 10 second  delay 
96. ak w o Vol  CTRL  w  Supply Air  Temp Ctrl   8   Thermostat Interface   9   Thermostat Interface w Anti Short   A            AB                                  Thermostat Interface w   Compressor Start Delay  B   Thermostat Interface w Anti Short  CycleTimer and Comp  Start Delay    Digit 10  11   Design Sequence  BO      B    Design    Digit 12   Unit Construction       Vertical Discharge       Vertical Discharge with Double Wall    6    C  D      mm    G    H    Horizontal Discharge   Horizontal Discharge w  Double  Wall   Vertical Discharge  Ship Separate  Vertical Discharge w  Double Wall   Ship Separate   Horizontal Discharge  Ship Separate  Horizontal Discharge w  Double  Wall  Ship Separate    igit 13   Plenum Type    D  B  C    E  F  H    J    p    M           R    U    V       0      Std Plenum w  Factory Cut Holes  Low Plenum w  Factory Cut Holes  Std Plenum w  Field Cut Holes  Low Plenum w  Field Cut Holes  Std Plenum Double Wall  Perf    w  Field Cut Holes   Low Plenum Double Wall  Perf   w  Field Cut Holes   Std  Plenum w Factory Cut Holes   Ship Separate   Low Plenum with Factory Cut  Holes  Ship Separate   Std Plenum w  Field Cut Holes  Ship  Separate   Low Plenum w  Field Cut Holes   Ship Separate   Std Plenum Double Wall  Perf  w   Field Cut Holes  Ship Separate  Low Plenum Double Wall  Perf  w   Field Cut Holes  Ship Separate  Without Plenum    Digit 14   Motor Type    1    2    3      Std  Efficiency ODP  Premium Eff  ODP  Std  Efficiency Totally Enclosed 
97. amper position to  compensate for VAV supply air modula   tion is inherent in the unit controls  and    can be enabled by the operator     The mixing box fabrication is 16 gauge  galvanized steel  Opposed low leak  damper blades are fabricated from 16   gauge galvanized steel and rotate on  rustproof nylon bushings  A factory  installed 24V modulating spring return  actuator controls both damper positions     Airside Economizers with Traq    Damper  Outside air enters the unit through the  Traq    damper assembly and is  measured by velocity pressure flow  rings  The velocity pressure flow rings  are connected to a pressure transducer   solenoid assembly  which compensates  for temperature swings that could affect  the transducer  The ventilation control  module  VCM  utilizes the velocity  pressure input  the RTM outdoor air  temperature input  and the minimum  outside air CFM setpoint to modify the  volume  CFM  of fresh air entering the  unit as the measured airflow deviates  from setpoint     When the optional preheat temperature  sensor is installed at the auxiliary  temperature on the VCM and the preheat  function is enabled  the sensor will  monitor the combined  averaged  fresh  air and return air temperatures  As this  mixed air temperature falls below the  preheat actuate temperature setpoint   the VCM activates the preheat binary  output to control a field installed heater   The output deactivates when the tem   perature rises 5 F above the preheat  actuate tempera
98. and cooling functions  VAV units     Reset Required   PAR  an automatic reset  occurs after the designated S A  temperature input returns to its allowable  range  To prevent rapid cycling of the  diagnostic  there is a 10 second delay  before the automatic reset     Supply Fan Failure   Problem  There is no supply airflow  indication after the supply fan has been  requested on     Check  Check belts  linkages  etc  on the  Supply Fan assembly  If these are ok   check field unit wiring between RTM and  supply fan  If the supply fan will run in  service mode  then verify airflow proving  switch and wiring     Reason for Diagnostic  The supply airflow  input is detected OPEN for 40 continuous  seconds during any period of time in  which the supply fan binary output is ON   between 830 ohms  200 F  and  345 7Kohms   40 F   If so  check field unit  wiring between the sensor and MCM     This input is ignored for up to 5 minutes  after the supply fan is first started  until  airflow is first detected     UCM s Reaction   OFF or  Close    requests are issued as appropriate to the   following functions    a  Compressor staging chilled water  control   b  Heat operation   c  Supply fan control and proof of  operation    d  Exhaust fan control and proof of  operation   e  Exhaust actuator control   f  Economizer actuator control    g  IGV   VFD control    Reset Required   PMR  A manual reset is  required anytime after the diagnostic is  set  The diagnostic can be reset at the HI   Trace
99. ansducer inside the control panel  picks up low side or reference pressure     Note  If plastic tubing pulls away from a  connection  trim it back before replacing it  on the fitting  Stretched tubing may leak  and cause faulty control                      Duct    Pressure Sensor       Note  Place sensor inlet  perpendicular to airflow    Figure I PR 14  Static pressure sensor installation     49    e TRANE    50    Installation    Remote Mounted Thermostat  Option   Mount the thermostat in the largest  space occupied by the most people for  the best average temperature sensing   The thermostat should be mounted about  5 feet from the floor in contact with freely  circulating air  but not with major drafts     Avoid the following areas    e Behind doors or in corners where ther is  no free circulation    e Locations where the sun s rays or  infrared radiation from appliances or  fireplaces may affect thermostat  operation    e Surfaces subject to vibration      On walls that contact outside air      Adjacent to or in line with conditioned air  discharge grilles or doorways     Remote Mounted Thermostat Wiring  After the thermostat is mounted  wire the  thermostat back to the unit control panel  according to the correct diagram shown  on inside of panel door     The total resistance of the thermostat and  the control wiring to each terminal must    not exceed 1 ohm  Table I PR 6 provides  recommended wire sizes for length of  run     Wiring the Remote Air cooled CCRC and  SCRG
100. arameters to the other weekend day     Remote Panel Indicator Signals From  UCM to ZSM   The unit control module  UCM  can send  four signals to the ZSM       Heat     Cool            e Service    Each of these four signals have three  different conditions  See Table I P 3   e Off             e Flashing    70    Installation    Table       2  Zone Sensor BAYSENS020 Option Menu Settings                                                                             Option   Description Value Factory Setting  1 Morning Warmup 0   Disabled 0  1 z Enabled  2 Economizer minimum 0   Disabled 1  Position override 1 Enabled  3 Temperature Scale 0   Fahrenheit 0  1 Enabled  4 Heat Installed 0      0  1   Yes  5 Time Clock 0 12 hours 0  1 24 hours  6 Hydronic Heat 0 No 0  1 Yes  7 Daytime Warmup 0   Disabled 0  1 Enabled  8 Programmable Days Week 0   7 days  M T W T ES S  0  1 23 days  M F S  S   2   2 days  M F 5 5   9 Programmable Periods Day 2 3 4 4  10 Remote Sensor Installed 0      0  1 Yes  11 Check Filter Interval 0   Disabled 350  3000 to 50 in 50 hour  increments  12 Display Zone Temperature 0 No 1  1 Yes  13 Keypad Lockout Enabled 0   Disabled 1  1  Enabled  14 Initial Time Setting inTemporary 1 2 3 4 5 3  Override Mode  hrs   15 Buzzer Options 0   Key Press only 1  1   Key Press  amp  Check filter  2   Key Press  Check Filter   and System Failures  16 Zone Temperature Calibration Displays current temp  0 offset  with any offsets  17 Default Cooling Setpoint 45 to 98 F  unoccupie
101. ariable Water Flow 85   VAV Box Option 79   VAV Changeover Contacts 78   VAV Drive Max Output 78  92   VCM 81  87   VCM Communication Failure 118   Velocity Pressure Sensor Failure 118   Ventilation Control Module 81  87   Ventilation Override Module 80   VFD 47  86   VFD Electrical Installation Procedure  47   VFD Mounting Requirements 47   VFD with Bypass 86   Voltage Imbalance 37  111   Voltage Range 37   VOM 80   VOM Communications Failure 118    W    Wall Mounting the RHI Panel 59  Warnings and Cautions 2   Water Condenser Connection Sizes 84  Water Flow Fail 119   Water Flow Switch Option 84   Water Piping 34   Water Piping Options 84   Water Purge 84  89          SCXG SVX01B EN    SCXG SVX01B EN    e TRANE          Water Temperature Requirements 35   Water Valves 109   Water Cooled Condensers 84   Water Cooled Unit Piping 63   Waterside Components 84   Waterside Economizer Flow Control  84   Waterside Economizer Installation  Procedure 42   Waterside Economizer Option 84   Waterside Module 80   Waterside Piping Arrangements 35   Wiring 53   Wiring the Remote Air cooled CCRC  and SCRG 50       Wiring the Remote Human Interface  61   Wiring the Timeclock 57   WSM 80   WSM Communications Fail 119   WSM Mixed Air Temp Sensor Fail 119    Z    Zone Cool Setpoint Failure 119   Zone Sensor Installation 53   Zone Sensor Maximum Lengths and  Wire Size 53   Zone Temperature   Heating 94   Zone Temperature Control 93    123          TRANE Literature Order Number SCXG SVX01B EN    
102. at can result in comfort problems   increased airflow resistance and thus  increased operating energy costs  If the  coil surface dirt becomes wet  which  commonly occurs with cooling coils   microbial growth  mold  may result   causing unpleasant odors and serious  health related indoor air quality  problems     Inspect coils at least every six months or  more frequently as dictated by operating  experience  Cleaning frequently is  dependent upon system operating hours   filter maintenance  and efficiency and dirt  load  The suggested cleaning method is  below     Steam and Hot Water Coils   1  Disconnect all electrical power to the  unit    2  Don the appropriate personal  protective equipment  PPE     3  Gain access to both sides of the coil  section    4  Use a soft brush to remove loose  debris from both sides of the coil    5  Use a steam cleaning machine  starting  from the top of the coil and working  downward  Clean the leaving air side of  the coil first  then the entering air side   Use a block off to prevent steam from  blowing through the coil and into a dry  section of the unit    6  Repeat step 5 as necessary  Confirm  that the drain line is open following  completion of the cleaning process     7  Allow the unit to dry thoroughly before  putting the system back into service    8  Straighten any coil fins that may be  damaged with a fin rake    9  Replace all panels and parts and  restore electrical power to the unit    10  Ensure that contaminated material  do
103. ate  the unit will either  maintain a constant level of cooling  capacity with the supply air temperature  within the control band  or the highest  active cooling level will cycle to provide  an average supply air temperature equal  to the setpoint     If the supply air temperature swings  outside the limits of the control band  the  mechanical cooling capacity will increase  or decrease by one level accordingly  The  change occurs by integrating the tem   perature offset from the control band  limit    A minimum time delay of five minutes  follows each change in cooling level  This  time delay promotes stability by allowing  the system to respond to the change  before any further control action occurs   As the supply air temperature ap   proaches setpoint  the time duration  between changing levels of cooling  capacity increases     See Figure O SO 2 for the typical unit  operating curve  Figure O SO 3 shows  typical unit performance when supply air  temperature swings exceed the control  band limits     Adjust the supply air temperature control    Table O SO 3  IntelliPak Unit Cooling Capacity Percent        Cooling Stage   Utilized       Unit Tons Cool 1  SCWG 20 53  SCWG 25 53  SCWG 30 47    Cool 2 Cool 3  100       100        65 100    SCWG35 0B 10             Table O SO 4  Thermostat Controlled Unit Cooling Capacity             Stages   Unit Cooling Stages  Size Cool 1 Cool 2    ity Utilized   Capacity  SCWG 20 53 100  SCWG 24 53 100  SCWG 30 65 100  SCWG35 0B  SCRG 20 
104. ates  If the  water is cool enough for economizing  but  mechanical cooling is also required  the  economizer valve fully opens to establish  full water flow through the condensers   Whenever the water is too warm for  economizing and there is a call for  cooling  the economizer valve fully closes  and the bypass valve fully opens   establishing full water flow through the  condensers  Full water flow is always  maintained through the condensers  when mechanical cooling is required   Both valves close whenever cooling is  not required  and in the event of a power  failure  See Figures O GI 4 and O GI 5     SCXG SVX01B EN    e TRANE    Owner              Condenser 1              Condenser 1                                                           Condenser 2        Condenser 2  v2  Figure O GI 3  Basic water piping configu  Figure         4  Intermediate water piping  ration  constant water flow  configuration  variable water flow            Condenser 1                Economizer                vi    Condenser 2                      v2        Iu      c          Figure O GI 5  Intermediate piping configuration with waterside  economizer  variable or constant water flow     85    e TRANE    Unit Airside Components    The unit s air delivery system consists of  condensers  dampers  enthalpy switch  option  airside economizer option  filters   low ambient sensors  and factory  mounted single or double wall plenums     Supply Air Fan   The unit has a single supply fan that runs  at
105. ating Mode  RTM sensors include  zone sensors with   T inti Resistance  or without setpoint inputs and modes  applied to RTM Mode CV Units VAV Units  supply air sensor  duct static pressure  input terminals  Ohms  Fan Mode System Mode System Mode  outside air temperature  outside air 2320 Auto Off Off  humidity  airflow proving  and dirty filter  4870 Auto Cool    7680 Atl Att Ati  10 7700   Oo Of             13 320 On Cool  16 130 On Auto  19 480 Auto Heat  27 930      Heat       Note  Mode boundaries are 1000 to 40 000 ohms  Other boundaries are equal to the midpoint between the  nominal mode resistance     SCXG SVX01B EN 79    e TRANE    Compressor Module  SCM and           Standard on All Units    The compressor module   single circuit  and multiple circuit  energizes the  appropriate compressors and condenser  fans upon receiving a request for  mechanical cooling  It monitors the  compressor operation through feedback  information it receives from various  protection devices     Human Interface Module    Standard on all units    The human interface  HI  module enables  the operator to adjust the operating  parameters for the unit using it s 16 key  keypad on the human interface panel   The HI panel provides a 2 line  40  character  clear language  English   Spanish  or French  LCD screen with unit  status information and menus to set or  modify operating parameters  It is  mounted in the unit s main control panel  and accessible through the unit s control  panel door    
106. before the automatic reset     S    SCM Communication Failure  Problem  The RTM has lost  communication with the SCM     Check  Check field unit wiring between  the RTM and SCM     Reason for Diagnostic  The RTM has lost  communication with the SCM     UCM s Reaction  A    Lockout    request is  sent to the compressor staging control  function  A failsafe function in the SCM  will cause all SCM outputs to be zeroed  and deenergized     Reset Required   PAR  An automatic reset  occurs after communication has been  restored     Space Static Press Setpt Failure  Problem  The active space static pressure  setpoint is out of range     Check  Check setpoint value  Also  if  space pressure setpoint source is GBAS   but this setpoint has not been assigned to  any of the 4 analog inputs on GBAS  this  message will occur     Reason for Diagnostic  The unit is reading  a signal that is out of range for the space  static pressure setpoint  input    0 03 IWC  or input    0 20 IWC     UCM  Reaction  The default space  pressure setpoint will become the active  space pressure setpoint     Reset Required   PAR  An automatic reset  occurs after the designated space  pressure setpoint source sends a signal  within range for 10 continuous seconds   or after a different space pressure  setpoint source is user defined     Supply Air Pressure Sensor Failure  Problem  The supply air pressure sensor  voltage input is out of range     Check  Check field unit wiring between  the sensor and RTM     Reas
107. contained unit     Remote Display End    Connected the two insulated  leads to the Remote Panel       Connect the wire connected to the  positive     terminal at the remote panel   Connect the wire connected to the  negative     terminal at the remote panel   Connect the ground wire from the  remote panel to the unit control panel  casing     Interprocessor Communication Bridge  Module Wiring   Refer to Figure I PR 33 and trim the outer  covering of the shielded cable back  approximately one inch  Cut the bare  shield wire off even with the outer  covering  Strip approximately 1   inch of  insulation from each insulated wire in  order to connect them to the terminal  strip at the unit  Wrap tape around any  exposed foil shield and or base shield  wire     Note  The communication link is polarity  sensitive     Refer to the unit wiring diagram and  connect the white lead to the positive      terminal and the black lead to the  negative     terminal   These terminals  are numbered  Reference to color is for  clarification to maintain polarity      Note  To maintain polarity  do not connect  the base shield wire to ground at the self   contained unit     Unit End    Cut ground Shield Wire    Outer Off at Unit End              d Ingulation             Foil Bhield    to the ground screw provided  in the Remote Digplay panel    Cover any exposed Foil dniela      and Shield Wire with electrical  Connect the Shield Ground Wire tape    oo HA       Connect the two ingulated  leads to t
108. crements    e Depressing and holding either the T or    arrow will cause the temperature  setting to increment rapidly     Simultaneously depressing the 7 or    arrow for two seconds while in the  program menu or temporary override  menu will toggle the ZSM between an  occupied and unoccupied condition     Holdtemp Button  While in normal run mode  depressing  the hold temp button toggles the ZSM to    a temporary manual override menu  See  Figure       3    This mode overrides any number of  programmed setpoints through any of  the 28 programmed periods  After  entering setpoints and length of override  time  these settings are now used        CO  aa Desired           HEAT COOL  DAYS HOURS  OVERRIDE I                lt  gt     OCCUPIED an       am             Figure       4  Temporary Manual Override  Menu Screen     Keypad Operation for Temporary Manual   Override Menu   The keypad has the same function in   temporary manual override menu as in   all other menus  with a few exceptions       Depressing the day button will toggle  your ZSM between the day and hour  icon  See Figure       3 on page 65    e Depressing the mode button will toggle  your ZSM between the heat and cool  icons and setpoints    e Depressing the erase button will cancel  the override and return the ZSM to  normal run mode    e Depressing the holdtemp or program  buttons while in the temporary manual  override menu will toggle your ZSM to  the temporary override mode  See  Figure       4     67    e TRA
109. ction               Reaction  A    Lockout Ckt   1  2  3   or 4    request is issued to the compressor  staging control function     Reset Required   PMR  A manual reset is  required anytime after the diagnostic is  set  The diagnostic can be reset by the  human interface  Tracer Summit    or by  cycling power to the RTM     M    Manual Reset SA Static Press Limit  Problem  The supply air static pressure    went too high for the third consecutive  time    Reason for Diagnostic  The auto reset  supply air static pressure limit diagnostic  has occurred for the third time while the  unit is operating in occupied mode            Reaction  A  supply air pressure  shutdown  signal is sent to the following  functions    a  Compressor staging control    b  Economizer actuator control    c  Heat operation    d  Supply fan control    e  IGV VFD control    f  Exhaust fan control   g  Exhaust actuator control    Reset Required   PMR  A manual reset is  required and can be accomplished at the  HI  Tracer Summit    or by cycling power  to the RTM     MCM Communications Failure  Problem  The RTM has lost  communication with the MCM     Check  Check field unit wiring between  RTM and MCM     Reason for Diagnostic  The RTM has lost  communications with the MCM            Reaction  A    Lockout    request is  sent to the compressor staging control  function  And a failsafe function in the  MCM will cause all MCM outputs to be  zeroed and deenergized     Reset Required   PAR  An automatic reset
110. ction nameplate matches that on  the compressor nameplate    2  Remove the connector brackets holding  the the sheet metal shipping cover on  compressor section  Retain brackets  and screws    3  Remove shipping cover from the  compressor section and verify the ship   with packge contains    e suction and discharge line couplings  e insulation  e sheet metal screws   4  Lift fan section onto the compressor  section using the rigging method in  Figure l PC 8 on page 13    5  Remove skid from the fan section   placing the fan section onto the  compressor section  Reference Figure l   PC 9 on page 15    6  Install the connection brackets with the  sheet metal screws  referenced in step  2  on all sides of the unit  Reference  Detail    A    in Figure l PC 9    7  Remove the unit panels labeled RU and  RL in Figure         10 on page 15  To  remove panels  first remove the four  shipping screws located in the corner of  each panel  Next  turn the remaining 1 4  turn fasteners to the unlatch position   The panel is supported by a    lip     channel  So  lift the panel up and off the  unit to remove it  See Detail  A in Figure  I PC 9 on page 15    8  Connect the drain hose to the drainpan  outlet fitting and secure it with the drain  hose clamp provided    9  Circulate nitrogen thoughout  refrigerant circuits    10  Unbraze and remove the caps on the  discharge and suction lines in both the  compressor and fan sections    11  Install and braze discharge and suction  line couplings
111. d    SCXG SVX01B EN     VO relay     energized  e Exhaust fan  field installed    on  e Exhaust damper  field installed    open    PURGE sequence    D     This sequence could be used for purging  the air out of a building before coming out  of unoccupied mode of operation on VAV  units  Also  it can be used to purge smoke  or stale air   e Supply fan   on  e Supply fan VFD     on  60 Hz    if equipped   e Inlet guide vanes VAV boxes     Open   if equipped   e Outside air damper     Open  e Heat     all stages     Off  Modulating heat  output at 0 vdc  e Occupied unoccupied output     Energized  e VO relay     Energized    Exhaust fan  field installed    On    Exhaust damper  field installed    Open    PURGE with duct pressure control  E   This sequence can be used when supply  air control is required for smoke control   e Supply fan     on   e Supply fan VFD     on  if equipped    e Inlet guide vanes   controlled by supply  air pressure control function with  supply air pressure high limit disabled   e Outside air dampers     open     Heat   all stages     off  hydronic heat  output at 0 vdc   e Occupied unoccupied output     energized   e VO relay     energized   e Exhaust fan  field installed    on     Exhaust damper  field installed    open    Note  Each system  cooling  exhaust   supply air  etc   within the unit can be  redefined in the field for each of the five  sequences  if required  Also the definitions  of any or all of the five sequences may be  locked into the so
112. d  74    18 Default Heating Setpoint 43 to 96 F  unoccupied  68 F  19 Default Supply Air Cool 40 to 80 F  occupied  55F  20 Default Supply Air Heat 60 to 160 F 100 F  21 Default Warmup 50 to 90 F  occupied  68  22 Minimum Cooling Setpoint 45to 98 F 4      23 Maximum Heating Setpoint 43 to 96 F 96 F  24 Minimum Supply Air Cool 40 to 80 F  occupied  40 F       25s Maximum Supply AirHeat GO to 1GOF GO      26s Maximum Warmup    50 to 90 F    90 F       Table       3  UCM Signal Conditions                       Signal Condition   Heat On FlashingHEAT is ON and indicated by a solid HEAT icon in the  Display  Failure in the cooling system indicated by a flashing COOL  FAIL icon    Cool On FlashingCOOLING is ON and indicated by a solid COOL icon in the  Display  Failure in the cooling system indicated by a flashing  COOL FAIL icon    On Off FlashingSystem is OFF and indicated by a solid colon on the time of   On day display  System is ON and indicated by a flashing colon on   the time of day display  System is in TEST mode and indicated by a  flashing TEST icon    Service Flashing ON System requires service and is indicated by a solid SERVICE    icon  There is a FAN failure indicated by a flashing SERVICE icon        Note  There is no indication for a signal in the OFF condition  If Option 16 is set to    2     any flashing signals will  also give audible buzzer indication    SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE             2  s MornDay EveNite      Su Mo Tu W
113. d valves  are located in the liquid refrigerant  lines on the right hand side of the unit   Refer to the unit wiring diagrams to  make splice connections     SCXG SVX01B EN    ATTACH ANGLE    AS    EACH SIDE    Installation    e TRANE       FROST PROTECTION SWITCH   BASIC CONTROL UNIT                 SHOWN ON    PANEL LIP  DETAIL A    Figure         9 How to assemble the split apart modular unit          NOTES         lt  PANEL FMM IS ONLY USED ON UNITS WITH    INTELLIPAK CONTROL  UNITS W BASIC CONTROLS  HAVE ONE PANEL THAT REPLACES FMM  amp  FMR                                                                                               FUL   FUM   FUR  FML FMM  FMR     EN    o   FL   FLR  FRONT VIEW    SCXG SVX01B EN                                                                   RU                                  SOLENOID VALVE                SOLENOID VALVE                                                                                                                           RL                                  ei          RIGHT SIDE    Figure I PC 10 Modular unit panel description and internal connections     COUPLING   4 PLACES     __ DRAIN  HOSE    A    HA    FAN MOTOR  POWER WIRES     REFRIGERANT CIRCUIT 2      REFRIGERANT CIRCUIT 1        SSEMBLED  UNIT       CONTROL PANEL    RNESSES      AIR COOLED  UNITS ONLY    e TRANE    Skid Removal    The unit ships on skids to provide forklift  locations from the front or rear  The skid  allows easy maneuverability of the 
114. e  compressor and an motor terminals  with the unit running  Voltage must be  within the range listed on the motor  nameplate  Phase imbalance must be  less than 2 0 percent    2  Check all wiring and connections to be  sure that they are intact  secure and  properly routed  The as wired system  diagrams are provided in the unit  control panel    3  Check that all fuses are installed and  properly sized    4  Inspect air filters and coils to bel sure  that airflow to the unit is not restricted    5  Check the zone thermostat settings    6  Ensure that the fan is rotating in the  proper direction  If phasing is wrong at  the main power terminal block  the fan  and compressors will not run    7  Inspect ductwork and duct connections  for tightness    8  Inspect air temperature  Extremely  warm return air will decrease the  cooling capacity of the air conditioner     Some common unit problems and  solutions are in Table D T 1  A complete  list of operating diagnostics begin on  page 112  Reference the  ntelliPak    Programming Guide  PKG SVP01B EN     SCXG SVX01B EN    Diagnostic  Troubleshooting    e TRANE       for additional operational info on the UCM  system     Operating Procedures   Install pressure gauges on the discharge  and suction line access valves  When the  unit has stabilized  after operating  approximately 15 minutes at full load    record suction and discharge pressures   System malfunctions such as low airflow   line restrictions  incorrect refrigerant  charge
115. e Th Fr Sa    4      T  el  6                     cr  CIC            DAYSAMPM HOURS    OVERRIDE         MODE       OFF       HEAT       COOL  AUTO  EMER       TIME  re estu  8          o  rest        Check Filter  Desired S  18                                    en             10    11 12    ROOM TEMP 16  OPTION  15  13 14    Figure       9  BAYSENS019 complete icon display     Icon Descriptions    BAYSENS019 Icon Descriptions   Refer to Figure I P 9 for a pictorial view of   the written descriptions below    1  The four periods of the day used only  during programming mode    2  The seven days of the week used  during programming and in normal  mode to display the day  not current in  Program Menu     3  Four digits used to display the time of  day in normal run mode  Also used in  Programming Menu and Temporary  manual Override Menu  and options  menu    4 Time of day colon used on the time of  day clock  The colon blinks to indicate  the UCM system is functional    5  AM and PM are used to indicate the  time of day when using a 12 hour clock   AM and PM are not used when a 24  hour clock is selected    6  DAYS and HOURS are used to set the  override timer period    7  Displayed in temporary manual  OVERRIDE mode  and when setting the  override timer    8  Only used when setting the override  timer     9  Displays the desired state of either  OCCUPIED or UNOCCUPIED    10  The padlock symbol indicates that the  keyboard lockout is in effect    11  This extends the mode selec
116. e air  temperature and relative humidity  sensor are provided for field installation  to monitor reference enthalpy   Economizer operation enables when the  outside air enthalpy is less than 25 BTU s   Ib   adjustable 19 28 BTU s Ib    During  occupied mode  the outside air damper  opens to 15   adjustable 0 100956  for  ventilation purposes  Also  the ability to  alter the outside air damper position to  compensate for VAV supply air  modulation is inherent in the unit controls   and can be enabled by the operator  An  analog 2 10 VDC output  adjustable  0 10  VDC  is provided to modulate the field   provided 30 second damper actuators   adjustable 1 255 seconds      Airside Economizer Interface with  Comparative Enthalpy   Units with airside economizer interface  and comparative enthalpy are equipped  with the necessary control sequences to  allow using outside air for the first stage  of cooling  in occupied or unoccupied  mode and when ambient conditions are  favorable for economizing  Inherent in the  unit controller is the ability to suppress  the setpoint below the normal unit  setpoint  This allows the building to  improve comfort levels when possible   and at the same time  optimize building  mechanical cooling operation for peak  operating efficiency  A factory installed    88    Owner       Air Cooled Condensers   SXRG units are designed for use with the  remote air cooled condenser  model  CXRC  For more information  see the air   cooled condenser Installation  Ow
117. e and pipe cover on  the coil box  Connect the wires that are  coiled in the coil box  referring to the  wiring diagram installed on the unit  control panel door  Route wires into the  unit through knockouts in the top of the  box    7  Reinstall the filter rack on the back of  the heating coil rack  If the unit has the  waterside economizer option  the filter  rack will require additional support legs     45    e TRANE    Electric Heat Installation    The electric heat option consists of a  single stage heater and is used in  IntelliPak units or units with a field   installed thermostat  The electric heater  ships separate for field installation and  wiring  Available heater kW per unit size  is listed      Table I PR 3  Electric heat can  be installed on units with either a vertical  or horizontal discharge  However  it  cannot be installed on units with plenums   See Figure I PR 10  Tables I PR 4  and  I PR 5 for electric heat dimensional data     Table I PR 3  Available Electric Heat kW                   Unit Size Heater kW  20Tons 16  25Tons 20  30Tons 24  32Tons 26  35Tons 28       Installation Procedure   1  Remove the fan discharge shipping  covers  if they have not already been  removed    2  Install the open cell gasket around the  discharge opening on the heater    3  Position the electric heater so that the  unit fan discharge openings line up with  the electric heater openings  For a  vertical discharge unit  position the  electric heater as shown in Figure I PR 
118. e assembly and  perform maintenance procedures in  the IGV maintenance section on page  106     Note  Perform this procedure monthly if  the unit is in a coastal or corrosive environ   ment     Annual Maintenance   Check and tighten all set screws  bolts    locking collars and sheaves    1  Inspect  clean  and tighten all electrical  connections    2  Visually inspect the entire unit casing  for chips or corrosion  Remove rust or  corrosion and repaint surfaces    3  Visually check for leaks in refrigerant  piping    4  Inspect fan  motor  and control contacts   Replace badly worn or eroded contacts    5  Inspect the thermal expansion valve  sensing bulbs for cleanliness  good  contact with the suction line  and  adequate insulation from ambient air    6  Verify the superheat setting is between  12 and 17 F at the compressor     When checking operating pressures and   conditions  establish the following   nominal conditions for consistent mea    surements    1  Leaving air temperature greater than  60 F   2  Entering air temperature between 80  and 90 F   3  Entering water temperature greater  than 65 F   4  Inlet vanes at least halfway open   5  Compressors running at full load   6  Drain the condensing water system  and inspect it thoroughly for fouling   Clean the condensers if necessary     SCXG SVX01B EN    System Checks    Before proceeding with technical trouble  charts or controls checkout  complete the  follow system analysis    1  Measure actual supply voltage at th
119. e is equal to the inner  tube diameter     4  Wrap each refrigerant line component  with a wet cloth to keep it cool during  brazing  Excessive heat can damage  the internal components     5  If using flux  apply it sparingly to the  joint  Excess flux will contaminate the  refrigerant system     6  Apply heat evenly over the length and  circumference of the joint     7  Begin brazing when the joint is hot  enough to melt the brazing rod  The hot  copper tubing  not the flame  should  melt the rod     8  Continue to apply heat evenly around  the joint circumference until the brazing  material is drawn into the joint by  capillary action  making a mechanically  sound and gas tight connection     9  Visually inspect the connection after  brazing to locate any pinholes or  crevices in the joint  Use a mirror if joint  locations are difficult to see     SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE          Unit Wiring Diagrams  Specific unit wiring diagrams are  provided on the inside of the control    panel door  Use these diagrams for  connections or trouble analysis     Supply Power Wiring    It is the installer   s responsibility to provide  power supply wiring to the unit terminal  block or the non fused disconnect switch  option  Wiring should conform to NEC and  all applicable code requirements     Bring supply wiring through the knockout  in the lower left side of the unit control  panel  Connect the three phase wires to  the power terminal block or the non
120. e of more than 2 096 exists   check the voltage at the unit disconnect  switch  If the imbalance at the unit  disconnect switch does not exceed 2 096   faulty unit wiring is causing the  imbalance  Conduct a thorough  inspection of the unit electrical wiring  connections to locate the fault  and make  any repairs necessary     Access the connection terminal block  through the control panel on the unit s  upper left side  All wiring should conform  to NEC and applicable local code  requirements     Be sure all wiring connections are secure   Reference the unit specific diagrams  inside the control panel     A  CAUTION    Unit transformers are sized to  provide power to the unit only   Do not use these transformers to  supply power to field equipment   Field connections to these  transformers may create  immediate or premature  component failures        37    e TRANE    Selection Procedures    RLA   Rated Load Amps  Compressor LRA   Locked Rotor Amps  Fan Motor LRA   Locked Rotor Amps   N E C  Table 430   150  FLA   Full Load Amps  N E C    Table 430   150    Voltage utilization range is  10 percent    Determination of minimum circuit  ampacity  MCA     MCA   1 25 x largest motor amps VFD  amps  FLA or RLA    the sum of the  remaining motor amps     Determination of maximum fuse size   MFS  and maximum circuit breaker size   MCB     MFS and MCB   2 25 x largest motor  amps  FLA or RLA    the sum of the  remaining motor amps     If the rating value determined does not  equal a s
121. ear and all keypad functions will be  available again     SCXG SVX01B EN    Installation    e TRANE       e Keypad lockout applies only to normal  run mode and temporary manual  override mode     Day Button            normal run mode  depressing the day  button will move the current day ahead      While in the program menu  depressing  the day button will move you through  the seven days of the week and allow  you to program temperature settings  for each of the four daily periods     Erase Button     Pressing the erase button while in  normal run mode will turn off the check  filter icon      Pressing the erase button while in the  program menu  will erase all time and  temperature setpoints of a given  period      The erase button will acknowledge the  failure buzzer  Option 16  until 12 00 am     Mode Button     BAYSENS019 only  Pressing the mode  button toggles through all modes  off   heat  cool  auto  and emer  HP unit     e BAYSENS020 only  Pressing the mode  button while in normal run mode  or  temporary manual override run mode   will toggle through both modes  off and  auto     Fan Button    The fan button allows you to toggle  between on and auto     Up and Down Button Arrows   e Depressing T or 4 arrow while in normal  run mode will cause your ZSM to toggle  to the temporary manual override  menu        Depressing either T or   arrow while in  the program menu or temporary  override menu will cause the  temperature setpoint to advance or  decrease in one degree in
122. ecommended tension  Refer to   Adjusting BeltTension  section on  page 100    7  Retighten bearing set screws to the  proper torques after aligning the  sheaves    8  Check the fan bearing locking collars  for tightness on the shaft  To tighten the  locking collar  loosen the set screw and  slide the collar into its proper position  over the extended end of the inner  case Tighten the set screw to the  appropriate torque value    9  During air balancing  verify the sheave  alignment  belt tension  and that the  shaft is parallel     SCXG SVX01B EN    For uneaven width sheaves   use a taut string down the  4 F j center of both sides        Straightedge should  touch sheave at top    and bottom    Fixed Sheave Fixed Sheave    Straightedge Straightedge    Straightedge should  touch sheave at top    and bottom       Fixed Sheave    Figure O M 1  Fan shaft and motor sheave alignment     99    e TRANE    Fan Bearings   The opposite drive end bearing is a  special bearing with close tolerance fit of  balls and races  Replace this bearing with  the same part number as the original  bearing     Fan Belt Tension    Note  Check fan belt tension at least twice  during the first days of new belt operation  since there is a rapid decrease in tension  until belts are run in     Proper belt tension is necessary to  endure maximum bearing and drive  component life and is based on fan brake  horsepower requirements  If frayed or  worn  replace belts in matched sets     Measuring Belt Tension  
123. ecuring it to the skid from the  side flanges  Retain these screws for  later use     Unit Preparation   3 The support legs are secured to the  skid  and the hanging bracket is secured  with wire ties to an inside flange near  the cabinet s base  Remove the  C channel collar and install it on the unit   if not already installed     4  Remove the roll of      thick gasket  from the damper cabinets W supports   and apply it to the C channel collar  mounted on the rear of the unit  This  gasket will provide a seal between the  damper cabinet and the unit     5  Attach the legs  with screws provided   to the leg brackets located on the  damper s base     6  Attach a field provided clevis of  suitable strength   gt  1 2       to each of the  corner lifting brackets through the  7     diameter holes     7  Attach to the clevises a means of lifting  the damper cabinet from its skid     Unit Installation  8  Slowly raise the damper cabinet from  its skid     9  Attach the hanging bracket across the  front of the damper cabinet  Position it  with its short flange pointing to four  o clock  and secure it with screws  provided  See Figure I PR 13     10  Lift the damper cabinet and position it  such that the hanging bracket is  positioned over the unit s C channel  collar     Installation          SPREADER    Figure         12  Proper lifting of the airside economizer     10  Lower the damper cabinet until the  holes in its side flanges are aligned with  the holes in the C channel colla
124. ed upstream of the  hydronic coil     Units with Electric Heat   LIVerify the supply air temperature  sensor is installed downstream of the  electric heat coil     63    e TRANE    Programmable Zone Sensor  Option    BAYSENS019    INDICATES TIME  OF DAY BY HOUR  AND MINUTE    INDICATES    Installation            SuMoTuWeThFrSa    88 98    AM            MORNING OR  AFTERNOON    INDICATES  OCCUPIED AND  UNOCCUPIED  PERIOD    INDICATES  KEYPAD  LOCKOUT STATUS    INDICATES   OPERATING  MODE   IN EFFECT        OFF   HEAT   COOL     AUTO     EMER          5    5019 Keypad and Display  Explanation    1  Up and Down Buttons   e Increases or decreased programmed  temperature settings in program menu    Shifts to temporary manual override in  normal run mode      Increases or decreases temperature  while in temporary override menu     2  Time Adjust Button   Used to set the correct time of day  Used  to set programmed time for temperature  variations     3  Program Button  Toggles between the display control  screen and the display program screen     64                    OCCUPIED       INDICATES INDICATES   FAN STATUS  ROOM  TEMPERATURE              AUTO       HOLD TE    MP      quum    MODE FAN  aue          Figure       1  BAYSENS019 Keypad and display configuration     4  Erase Button     Erases time and temperature settings  throughout each of the programmed  periods      Exits temporary manual override     5  Day Button  Toggles through the seven days of the  week     6  Hold Tem
125. elt  operation  Belt tension will rapidly de   crease until the belts are run in     110    Owner       5  Check the liquid line sight glasses  during operation  Bubbles in the sight  glasses indicate a possible shortage of  refrigerant or an obstruction in the  liquid lines  such as dirty liquid line filter  driers    6  Inspect filter driers for leaks  flow  obstructions  or temperature drop  across the filter drier  A noticeable  temperature differential  such as 5 F in  the liquid line may indicate an  obstruction  Replace the filter drier if it  appears clogged    7  Inspect the optional waterside  economizer coil  Clean the coil to  prevent airflow restrictions through the  fins    8  Check and record operating pressures     Semi Annual Maintenance   1  Verify the fan motor is properly  lubricated  Follow lubrication  recommendations on the motor tag or  nameplate  Contact the motor  manufacturer for more information    2  Lubricate fan bearings  For best results   lubricate bearings during unit operation   Refer to the    Fan Bearings    section on  page 100    3  With power disconnected  manually  rotate the fan wheel to check for  obstructions in the housing or  interference with fan blades or inlet  guide vane option  Remove  obstructions and debris  Center the fan  wheel if necessary    4  Check the fan assembly sheave  alignment  Tighten set screws to their  proper torques    5  Check water valves for leakage at  valve stem packing nut     6  Inspect the inlet van
126. emp Sensor Failure  Problem  On units with the comparative  enthalpy option  the return air  temperature sensor input is out of range     Check  Sensor resistance should be  between 830 ohms  200 F  and  345 7Kohms   40 F   If so  check field unit  wiring between the sensor and ECEM     Reason for Diagnostic  The unit is reading  a signal that is out of range for the return  air humidity sensor  temp     55 F or  temp  gt  209 F      UCM s Reaction  The economizer enable  r e  enthalpy function reverts to reference  enthalpy changeover     Level 2     control     Reset Required   PAR  An automatic reset  occurs after the RA temp input returns to    115    e TRANE    its allowable range continuously for 10  seconds     RTM Aux  Temp  Sensor Failure  Problem  The RTM auxillary temperature  sensor data is out of range     Check  Sensor resistance should be  between 830 ohms  200 F and 345 7  Kohms   40 F   If so  check field unit wiring  between sensor and RTM     Reason for Diagnostic  At least one  enabled unit function has the RTM  auxillary temperature input designated  as its sensor  and the unit is reading a  signal that is out of range for this input   temp   lt   55 F or temp  gt  209 F            5 Reaction  The functions with the  RTM auxillliary temperataure input  deignated as their sensor are disabled     Reset Required   PAR  an automatic reset  occurs after the designated zone  temperature signal returns to its  allowable range  To prevent rapid cycling  of the di
127. en and the display program screen     4  Erase Button   e Erases time and temperature settings  throughout each of the programmed  periods    e Exits temporary manual override     5  Day Button  Toggles through the seven days of the  week     6  Hold Temp Button   Shifts controller to temporary manual  override  and begins temperature  override     7  Mode Button   eToggles the controller between the two  modes  off and auto    e Advances to next setpoint in program  menu    8  During Programming Indicates    e Heat supply air   e Cool supply air   e Warmup temperature    65    e TRANE    Initial Power Up   Before applying power to your ZSM  and  before performing setup and operation  procedures  verify that all wiring is  correct  See Figures I P 9 on page 71 and        10 on page 72 for a complete zone  sensor icon display description     For BAYSENS020 only  at initial power  up  the ZSM controls to default tempera   tures of 68 F  19 C  for warmup  and 55 F   13 C  supply air  until the ZSM is pro   grammed or the arrow keys are pressed   If the arrow keys and mode are moved   the ZSM starts controlling to these new  settings     Time and Day Settings   On power up your ZSM will be in normal  run mode and will begin operating using  setpoints  The display will show the  wrong day and time and will need to be  set     To set the time  there is a single rubber  button on the keypad    minus    and     olus    mark time     Depressing the positive side will advance  the time
128. equired   PAR  An automatic reset  occurs after the SA temp cooling setpoint  input returns to within range for 10  continuous seconds  or after a different  SA temp cooling setopint selection  source is user defined     Supply Air Temp Heat Setpoint Fail  Problem  The active supply air  temperature cooling setpoint is out of  range     Reason for Diagnostic  The input  designated as the SA temp heating  setpoint is out is out of range  Temp  lt  35  F or Temp  gt  185                Reaction  The default             SA  temp heating setpoint becomes the  active SA temp heating setpoint     Reset Required   PAR  An automatic reset  occurs after the SA temp heating setpoint  input returns to within range for 10  continuous seconds  or after a different  SA temp heating setopint selection  source is user defined     Supply Air Temperature Failure  Problem  The supply air temperature  sensor input is out of range     Check  Sensor resistance should be  between 830 ohms  200 F  and 345 7  Kohms   40 F   If so  check field unit wiring  between sensor and RTM     SCXG SVX01B EN    Diagnostic  Troubleshooting    e TRANE       Reason for Diagnostic  The unit is reading  a signal that is out of range for the supply  air temperature input on the RTM  temp     lt   55 F or temp  gt  209 F      UCM s Reaction  These unit functions are   disabled    e supply air tempering   e economizing     supply air temperature low limit function   CV units      supply air temperature control heating  
129. er flow with or without a  waterside economizer  A two way  modulating control valve is wired and  installed in the unit to maintains a specific  range of water temperature rise through  the condenser when entering fluid    84    Owner       temperature is less than 58 F  15 C   This  option allows the compressor to operate  with entering fluid temperature down to  35 F  2 C   The minimum valve position to  maintain minimum condenser flow rates  is user defined at the Hl  This valve drives  closed if the unit shuts down or if a power  failure occurs       Water Flow Switch Option   A water flow switch is factory installed in  the condenser water pipe within the unit   Whenever the flow switch detects a  water flow loss prior to or during  mechanical cooling  compressor  operation locks out and a diagnostic code  displays  If water flow is restored  the  compressor operation automatically  restores     To prevent injury or death due to  instantaneous release of high  pressure water  provide relief  valves on system water piping   This will also help prevent water  pump damage or stoppage due to  excessive system pressure        Water Cooled Condensers   Units that are set up for variable water  flow will modulate a water valve to  maintain a user defined condensing  temperature setpoint  Condensing  temperature will be referenced utilizing  factory installed sensors located at each  condenser     Table O GI 8  Water Condenser Connection  Sizes          Unit Size Direct Factory
130. erve refrigerants for  continued use     SCXG SVX01B EN    SCXG SVX01B EN    e TRANE          Cross reference to related publications information     IntelliPak  Self Contained Programming Guide  PKG SVPO1B EN  Remote Air Cool Condenser Installation  Owner  and Diagnostic Manual  CXRC     SVX01A EN    Installation    General Information  Pre installation Considerations  Dimensions Weights  Mechanical Requirements  Electrical Requirements  Pre Startup Requirements  Programming   Startup    Owner    General Information  Sequence of Operation  Maintenance   Diagnostic Troubleshooting    Troubleshooting  Diagnostics    17    33  ou  39  64  74    d             3  98  111    111  112    e TRANE    Modular Series Self Contained  Unit Components    Commercial self contained units are  complete HVAC systems used in floor by   floor applications  Units are easy to install  because they feature a single point  power connection  factory installed and  tested controls  single water point  connection  factory installed options  and  an internally trapped drain connection   Modular self contained units can ship as  split apart units for installation ease  Split   apart units ship with a dry nitrogen  charge and require field refrigerant  charging     Units consist of multiple compressors   water cooled condensers  water cooled  units only   an evaporator coil  dual  forward curved fans  and control panel   Air cooled units require a remote air   cooled condenser  model CXRC  The  hermetica
131. es not contact other areas of the unit  or building  Properly dispose of all  contaminated materials and cleaning  solutions     Refrigerant Coils   1  Disconnect all electrical power to the  unit    2  Don the appropriate personal  protective equipment  PPE     3  Gain access to the coil section of the  unit  both sides     4  Use a soft brush to remove loose  debris from both sides of the coil    5  Mix a high quality coil cleaning  detergent with water according to the  manufacturer   s instructions  If the  detergent is strongly alkaline after  mixing  pH 8 5 or higher   it must  contain an inhibitor  Carefully follow the  cleaning solution manufacturer   s  instructions regarding product use    6  Place the mixed solution in a garden  pump up sprayer or high pressure  sprayer  If using a high pressure  sprayer note the following    e Maintain a minimum nozzle spray  angle of 15 degrees   e Spray perpendicular to the coil face   e Protect other areas of the unit and  internal controls from contact with  moisture or the cleaning solution      Keep the nozzle at least 6 inches from  the coil     Do not exceed 600 psig    Draining the Coil  4   CAUTION    Failure to properly drain and vent  coils when not in use during  freezing temperatures may result  in coil freeze up damage        Drain plugs are in the piping below each  coil s supply and return header  Use these  plugs to drain the coil and piping  When  draining the coil  open the vents at the top  of the supply and r
132. esignated as the unoccupied zone  cooling setpoint source is out of range   Temp  lt  45 F orTemp  gt  94 F             Reaction  The active unoccupied  zone cooling setpoint reverts to the  default value     Reset Required   PAR  An automatic reset  occurs after the designated unoccupied  zone cool setpoint input returns to its  allowable range for 10 continuous  seconds  or after the user defines a  different  valid unoccupied zone cool  setpoint selection source     Unoccupied Zone Heat Setpoint Failure  Problem  The unoccupied zone heating  setpoint input is out of range     Reason for Diagnostic  The input  designated as unoccupied zone heating  setpoint source is out of range  temp  lt  45  F or temp  gt  94 F            5 Reaction  The active unoccupied  zone heating setpoint reverts to the  default value     Reset Required   PAR  An automatic reset  occurs after the designated unoccupied  zone heat setpoint input returns to its  allowable range for 10 continuous  seconds  or after the user defines a  different  valid unoccupied zone heating  setpoint selection source     V    VCM Communication Failure  Problem  The RTM has lost  communication with the VCM     Verify  Check field unit wiring between  RTM and VCM     Reason for Diagnostic  The RTM has lost  communication with the VCM     UCM s Reaction  All active commands  and setpoints provided by the VCM are  canceled and or ignored  A fail safe  function in the VCM will cause all outputs  to deenergize and or set to
133. essors    Units use two sizes of hermetic scroll  compressors  10 and 15 hp  and can use  from two to four compressors  When  viewing the front of the unit  compressors  are identified A through B from left to  right  The second compressor from the  left  or    compressor  is always the first to  come on  unless locked out for a  malfunction or shut off on frost protection   Refer to Table O SO 1 for compressor  cycling stages andTable O SO 3 on page  96 for percent cooling capacity by stage     The control system logic permits com   pressor operation only after the supply  fan is on  If the supply fan shuts down   compressors will not operate  Units  without head pressure control  units with  intermediate piping packages  will lock  out mechanical cooling when the entering  condenser water temperature falls below  54    Mechanical cooling will resume  when the entering condenser water  temperature exceeds 58 F    Table O SO 1  Compressor Stages     Owner    e TRANE       Compressor Cycling   Compressors cycle to maintain the  operating state required by the  temperature controls  In the event of a  compressor failure  the next available  compressor turns on  Refer to Table O   SO 1 for compressor cycling by unit  model and tons     During normal conditions  compressors  will not shut off until they have been on  for at least three minutes and will not turn  on until they have been off for at least  three minutes  Normal operating condi   tions are established on an individua
134. eturn headers     107    e TRANE    108    Owner       Also  a drain plug is at the bottom of the  inlet condenser manifold and in the outlet  pipe near the unit s left side  Remove  these plugs to drain the condensers  Be  sure to open the vent plugs at the top of  the condenser inlet and outlet manifold   See Figure O M 7 on page 105     When refilling the condenser waterside  economizer coil system with water   provide adequate water treatment to  prevent the formation of scale or  corrosion     A CAUTION    Failure to provide adequate water  treatment in condenser systems  may result in coil and condenser  fouling or undue metal damage        Cleaning the Condenser    Note  Using improperly treated or un   treated water in this equipment may result  in scaling  erosion  corrosion  algae  or  slime  Engage the services of a qualified  water treatment specialist to determine  what treatment is advisable  The Trane  Company warranty specifically excludes  liability for corrosion  erosion  or deteriora   tion of Trane equipment  Trane assumes  no responsibilities for the results of the  use of untreated or improperly treated  water  saline  or brackish water     Condensing water contains minerals that  collect on the condenser tube walls   Cooling towers also collect dust and  foreign materials that deposit in the  condenser tube  The formation of scale or  sludge in the condenser is indicated by a  decreased water flow  low temperature  difference between inlet and outlet wa
135. ex head  screws from the top and bottom of the  filter rack assembly  The filter rack  assembly will hang on the unit when  the screws are removed  The filter rack  can now be removed by lifting up on  the filter rack    2  Remove the hydronic coil from the  crate and position it behind the unit with  the open side facing the unit evaporator  coil inlet  Also  remove the plastic  envelope that is taped to the coil box  assembly This envelope contains the  mounting screws needed to attach the  coil box to the unit and the gasket  required on the vertical side flanges of  the box     3  Install the pressure sensitive gasket to  the unit side of the vertical flange on the  coil box in two places    4  Using 2          standard thread  eyebolts  thread into the coil lift plates to  raise the coil up to the height necessary  to attach it to the unit  The top panel has  a    J    hook on it to allow hanging   similar to the filter rack  Align the holes  so that the coil hangs on the unit  If the  unit has the dirty filter option  connect  the static pressure tube to the unit  before bolting the coil in place  Locate  the static pressure tubing on the unit  evaporator coil and route through the  knockout in the top corner of the coil  box    5  Align the hydronic coil with the holes in  the unit channel or waterside  economizer option  Move the coil box  up against the unit and install using six  mounting screws in the top and six in  the bottom of the coil box    6  Remove the valv
136. f it is correct  switch wires on  the fan contact so the fan is properly  phased    2  Check the fan belt condition and  tension  Adjust the tension if belts are  floppy or squeal continually  Replace  worn or fraying belts in matched sets    3  Check voltage at all compressor  terminals  Actual voltage should be  within 10 percent of nameplate voltage    4  Check voltage imbalance from these  three voltage readings  at each  compressor  Maximum allowable  voltage imbalance  phase to phase  is  2     5  Check amp draw at compressor  terminals  RLA and LRA is on the unit  nameplate    6  Measure amp draw at evaporator fan  motor terminals  FLA data is on the  motor nameplate    7  After the system has stabilized  15 to  30 minutes   check and record  operating pressures and temperatures  for all circuits     When checking the operating pressures   and conditions  establish nominal   conditions for consistent measurements   as follows    e Leaving air greater than 60 F   e Entering air temperature between 70  and 90 F   e Entering water temperature greater  than 60 F   e Inlet guide vanes at least halfway open    With all compressors running at full load    1  Compute superheat from the suction  line pressure and temperature at the  compressor on each circuit  Adjust the  thermal expansion valve settings if  necessary  Superheat should be  between 12 and 17 F   2  Inspect refrigerant flow in the liquid line  sight glass  Flow should be smooth and  even  with no bubbles once the
137. f the LEATPD is on a water cooled unit  without factory installed heat  it is wired  to the WSM  It will trip if the entering    water temperature falls to 34 F open the  economizer valve  and energize the  pump output     High Duct Temp Thermostat Option On  Units with a          The high duct temperature thermostats  are binary input devices used on units  with aTrane communication interface  module  TCI   The high duct temperature  thermostat provides a high limit unit  shutdown and requires a manual reset   The thermostats are factory set to open if  the supply air temperature reaches 240 F  or the return air temperature reaches  135 F Once tripped  the thermostat  requires a manual reset  Reset by  pressing the sensor s reset button when  the air temperature decreases  approximately 25 F below the cutout  point     Filter Switch   The filter switch is a binary input device  used on units to measure the pressure  differential across the unit filters  It is  mounted in the filter section and  connected to the RTM  A diagnostic  SERVICE signal displays at the remote  panel if the pressure differential across  the filters is at least 0 5    w c  The contacts  automatically open when the pressure  differential across the filters decrease to  0 4    w c  The switch differential is field  adjustable between 0 17    to 5 0    w c     0 05         High Duct Static Switch Option   The high duct static switch is field   mounted in the ductwork or plenums with  smoke dampers  It wil
138. ftware by simple key  strokes at the human interface panel  Once  locked into the software  the sequences  cannot be changed     Trane Communications I  Interface Module  TCI    Option    used with Trane ICS       The Trane communication interface  module allows external setpoints for  most of the unit functions to be  communicated to the unit s UCM network  via aTrane ICS    systems  DIP switch  settings on the TCI module for this    SCXG SVX01B EN    Ventilation Control Module       ube From Solenoid to    igh Side of Transducer     e TRANE    General    Owner Information       application are  switch 1    off    2    on    and Ventilation Control Module    3    off               Available only with  Traq    Damper Option  Exhaust  Comparative The ventilation control module  VCM  is    located in the airside economizer section  of the unit and linked to the units UCM  network  Using a velocity pressure  transducer solenoid  pressure sensing  ring  in the fresh air section allows the  VCM to monitor and control fresh air  entering the unit to a minimum airflow  setpoint  See Figure O GI 2 for a detail  view of the velocity pressure transducer   solenoid assembly     Enthalpy Module  ECEM    On  Units with Comparative  Enthalpy Option    The exhaust comparative enthalpy  module receives information from the  return air humidity sensor  and the RTM  outside air temperature sensor and  outside air humidity sensor  the outside  air humidity sensor and temperature  sensor to util
139. g Switches 90  Supply and Exhaust Fan Circuit Break   ers 90  Supply Duct Static Pressure Control 79  Supply Fan 99  Supply Fan Circuit Breaker  Fuses  and  Overloads 90  Supply Fan Failure 117  Supply Fan Isolators 39  Supply Fan VFD Bypass Enabled 117  Supply Power Wiring 37  System Checks 111    T    TCI 81   TCI Module Comm Failure 117   Temporary Manual Override 67   Temporary Manual Override Run Mode  68   Temporary Override Run Mode 68   Time and Day Settings 66   Time Button 67   Time Clock 91   Time Clock Option 57   Timeclock Installation 57   Timeclock Installation Checklist 57   Timed Override Activation 92   Tracer Communications Failure 117   Tracer Summit System 91   Trane Communications Interface  Module 81   Transducer Location 49    U    Unit Airside Components 86   Unit Components 4   Unit Control Components 78   Unit Control Module 5   Unit HI Communications Failure 118             Unit Isolator Installation Procedure 40  Unit Location 63   Unit Mounting 63   Unit Nameplate 5   UNIT OFF sequence  A  80   Unit Protective Covers 39   Unit Shipping 14   Unit Start Up Procedures 74   Unit Startup 74   Unit Vibration Isolator Option 40   Unit Wiring Diagrams 37   Units With Economizer 93   Unoccupied 91   Unoccupied Zone Cool Setpoint Failure  118   Unoccupied Zone Heat Setpoint Failure  118   Up and Down Button Arrows 67   Using Intelligent Copy 70    V    Variable Air Volume Zone Sensor 55   Variable Frequency Drive 86   Variable Frequency Drive Option 47   V
140. he appropriate terminals  in the unit control panel    Figure I PR 33  Dressing shielded twisted wire     61    e TRANE    62    Installation    Connecting to Tracer Summit      IntelliPak   self contained units operate  with Trane building automation software   Tracer Summit  version 10 0 4 or later or  any OS2 operating system         CAUTION    Tape the non insulated end of the  shield on shielded wire at the  unit  Any connection between the  shield and ground will cause a  malfunction  If daisy chained in  the unit  splice and tape the  shields to prevent contact with  ground        Communication Wiring    Note  Communication link wiring is a  shielded  twisted pair of wire and must  comply with applicable electrical codes     An optional communication link provides     serial communication interface  SCI   between Tracer Summit   and each  commercial self contained  CSC  unit in  the system  The CSC system can have a  maximum of 12 CSC units per connection  link to Summit    Use a single 18 AWG  shielded  twisted pair wire with stranded   thinned copper conductors to establish  each communication link between  Summit   and each unit     SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE       Pre Startup Checklist    Complete this checklist after installing the  unit to verify all recommended  installation procedures are complete  before unit start up  This does not replace  the detailed instructions in the  appropriate sections of this manual   Always read the
141. hin  4to 131      2  Locate the time clock at least 5 feet  away from any large electrical contact  or machinery to avoid possible  electrical interference problems     3  Provide a separate independent circuit  for the time clock  power supply    4  Since all electronic instruments are  sensitive to voltage spikes  pay close  attention to the following    a  If possible  supply power to the  electronic time clock from a phase  different than the one supplying power  to the load   b  Provide a suitable Varistor or RC  network across the INDUCTIVE LOADS  supply terminals to reduce voltage  spikes    c  Place a diode across the DC OPERATED  INDUCTOR terminals to eliminate back  EME   d  HIGHLY INDUCTIVE LOADS  especially  fluorescent lights  may require a relay  in which case  A  and  C  apply     The Digi 20A timeclock unit can be  surface or flush mounted  Lift off the front  cover and loosen the two screws on  opposite corners  Pull off the base   s plug  with a left to right rolling motion     Surface Mounting Inside Panel  Place screws through the bases preset  holes and screw to back of panel or wall     Wire according to the instructions in the  following section  Depending upon the  specific installation  you may find it more  convenient to complete wiring before  attaching the base     Place the terminal cover over the  terminal block by aligning the two screws  with the corner holes in the base  Push  the timer firmly onto the plug in the base   Tighten the two screws
142. hould  approve or provide all materials used in  the external circulating system  along  with the quantity of cleaning material   duration of cleaning time  and safety  precautions necessary for handling the  cleaning agent     SCXG SVX01B EN    SCXG SVX01B EN    Owner    e TRANE       Piping Components    Water Valves   Water valves have a stern packing nut  If   there is evidence of water leakage at the   valve stem  proceed as follows    1  Remove actuator motor from support  plate   Remove four mount bolts    2  Remove shaft coupling    3  Torque the packing nut to 10 ft  Ibs  of  torque    4  Replace shaft coupling    5  Replace actuator motor  reinstall the  four mount bolts      Note  If it is necessary to remove the four    valve body bolts for valve cleaning or  service  torque to 45 ft lb     Flow Switch Maintenance   Flow switches have a magnet on the  vane assembly that attracts ferrous  particulate may build up on the magnet to  the point that the vane will wedge so that  it will not operate     When the flow switch does not operate   remove and replace it or disassemble  and clean it     Cleaning the Flow Switch   If ferrous particulate contaminates tower  water  the ferrous particles will cling to  the magnet on the switch paddle  assembly  A buildup of the ferrous  particles over a period os time will cause  the paddle to stick and cease to function  properly    To avoid this problem  remove the switch  and clean each time you clean the  condensers  or clean a
143. hs  or as dictated by operating experience     If evidence of standing water or  condensate overflow exists  take steps to  identify and remedy the cause  immediately  Refer to the trouble  shooting section of this manual for  possible causes and solutions  If microbial  growth is evident in the drain pan   remove and clean it immediately  Clean  drain pans using the following procedure     1  Disconnect all electrical power to the  unit    2  Don the appropriate personal  protective equipment  PPE     3  Remove all standing water    4  Use a scraper or other tools to remove  and solid matter  Remove solid matter  with a vacuum device that utilizes high    98    Owner       efficiency particulate arrestance  HEPA   filters with a minimum efficiency of  99 97  at 0 3 micron particle size    5  Thoroughly clean the contaminated  area s  with a mild bleach and water  solution or an EPA approved sanitizer  specifically designed for HVAC use   Carefully follow the sanitizer  manufacturer s instructions regarding  product use    6  Immediately rinse the drain pan  thoroughly with fresh water to prevent  potential corrosion from the cleaning  solution    7  Allow the unit to dry thoroughly before  putting the system back into service    8  Determine and correct the cause of  any microbial contamination    9  Be careful that the contaminated  material does not contact other areas of  the unit or building  Properly dispose of  all contaminated materials and cleaning  solution     Note
144. iate  terminals at the unit control panel and  atthe zone sensor subbase  In general   zone sensor connections to the unit use  the convention of connecting zone  sensor terminals to like numbered unit  terminals  1 to 1  2 to 2  etc    The  connection detail is shown on the unit  wiring diagrams  which are located in  the unit control panel     3  Replace the zone sensor cover back  on the subbase and snap securely into  place     Standard Remote Sensor   BAYSENSO 17    When using the remote sensor   BAYSENS017  mount it in the space that  is to be controlled  Wire according to the  interconnecting wiring diagrams on the  unit     Table I PR Z Zone Sensor Maximum  Lengths and Wire Size                      Distance from Recommended  Unit to Controller Wiring Size  0 150 feet 22gauge  151  240 feet 20gauge  241 385 feet 18gauge   386  610 feet 16gauge  611 970 feet 14gauge       53    TRANE    Installation          54                                                                                              1 000        2 750  NNI i ff o     N    1  i 3 300    n DI 45208 2 100               342                 500          Figure I PR 22  Zone sensor mounting hole locations     Mounting Directly to the Wall  Q    Control Wire  sss              Wall Surface  Plastic Anchors for  Wall Installation  Mounting to Junction Box    Junction    Control Wire                   Sensor Subbase  without Cover               Seal these areas before  mounting the subbase    Sensor Subbase  
145. ime Clock 91   Fan Bearings 100   Fan Belt Tension 100   Fan Button 67   Fan Drive 99   Fan shaft and motor sheave alignment  99   Field Supplied Occupied Unoccupied  Input on the RTM 91   Filter Switch 90   Flow Switch Maintenance 109   FROSTAT 97   Full Capacity Morning Warmup 91    G    GBAS 0 5 VDC Module Comm Failure  113   GBAS Analog Input Setpoints 83   GBAS Analog Inputs 82   GBAS Binary Input 82   GBAS Binary Outputs 82   GBAS Demand Limit Relay 82   GBAS Diagnostics 82   GBAS Input Voltage Corresponding  Setpoint 83   General Waterside Recommendations   Cooling Towers 35   Generic Building Automation System  Module 82       H    Head Pressure Control 89   Heat Failure 113   Heat Module 80   Heat Module Auxilliary Temperature    SCXG SVX01B EN    Sensor Fail 113  eat Module Comm Failure 114    58  80    Location Recommendations 58  igh Duct Static Switch 90  igh Duct Temp Thermostat 90  igh Duct Temperature Thermostat 86  igh duct thermostat can be reset 90  oldtemp Button 67  uman Interface 58  uman Interface Module 80  uman Interface Panel 5  ydronic Coil Installation 45  ydronic Heat 94                      y                            Icon Descriptions 71   ICPB 61   Initial Power Up 66   Inlet Guide Vane 86   Inlet Guide Vanes 106   nput Devices and System Functions   89   nspecting and Cleaning Coils 107   nspecting and Cleaning the Drain Pan   98   nspecting and Cleaning the Fan 98   Installation Preparation 10   nstalling the Remote Human Interface   Panel 5
146. in control panel  Extra  filters  sheaves  and belts ship in the unit s  fan motor section  Condenser plugs   spring isolators  and isopads ship in the  unit s bottom left side     Receiving Checklist   Complete the following checklist  immediately after receiving unit  shipment to detect possible shipping  damage        Inspect individual cartons before  accepting  Check for rattles  bent carton  corners  or other visible indications of  shipping damage        If a unit appears damaged  inspect it  immediately before accepting the  shipment  Make specific notations  concerning the damage on the freight  bill  Do not refuse delivery        Inspect the unit for concealed  damage before it is stored and as  soon as possible after delivery   Report concealed damage to the  freight line within the allotted time  after delivery  Check with the  carrier for their allotted time to  submit a claim     SCXG SVX01B EN    Installation       Do not move damaged material from  the receiving location  It is the receiver s  responsibility to provide reasonable  evidence that concealed damage did  not occur after delivery        Do not continue unpacking the  shipment if it appears damaged  Retain  all internal packing  cartons  and crate   Take photos of damaged material if  possible           Shipping  Covers    Metal Channel    Shipping Skid    NOTE     1  Remove 4 center channels   The filter rack is to be used with 4  filters     e TRANE       O Notify the carrier s terminal of the  dam
147. in normal run  mode    3  Four digits used to display the time of  day in normal run mode  Also used in  Programming Mode  override timer  setting menu  and options menu    4 Time of day colon used on the time of  day clock  The colon blinks to indicate  the UCM system is functional    5  AM and PM are used to indicate the  time of day when using a 12 hour clock   AM and PM are not used when a 24  hour clock is selected    6  DAYS and HOURS are used to set the  override timer period    7  Displayed in temporary manual  OVERRIDE mode  and when setting the  override timer    8  Only used when setting the override  timer    9  Displays the desired state of either  OCCUPIED or UNOCCUPIED in the  Programming  Run  and Menu     10  The padlock symbol indicates that the  keyboard lockout is in effect    11  Operating mode selection box    12  Displayed in normal run mode when  displaying the actual room  temperature    13  Displayed in option setting mode only    14  Digits used to display temperature    15  HEAT and COOL have two functions   they indicate UCM status in normal run  mode and indicate which type of  setpoint is DESIRED during  programming and override setting    16  Only used during programming and  override setting to indicate the  DESIRED setpoint temperature    17  Flashes when check filter timer is  elapsed    18  Flashing cooling fail status indicator    19  Only used during UCP self test mode    20  Flashing service status indicator and  fan failure    21  Flash
148. in step 1  Enter the  time of day and days of week just as in  the programming steps above  The old  program is overwritten with the new  selections  Press  Prog   to store the  new program    3  To delete an individual program  select  the program as in step 1 and press  h   and  m  keys until            appears in  the display  Press either    Prog     or    1     key until            flashes  The program  is deleted after a few seconds     Manual Override   While in the  run  mode   G  symbol is  displayed   pressing the          key will  reverse the load status  switch load off if  itis on  or switch it on if it is off   A hand  symbol appears in the display to indicate  the override is active  At the next  scheduled switching time  automatic time  control resumes  eliminating the override     Pressing the           key a second time            appears in the display indicating  the load is permanently on    Pressing the   amp   key a third time   O      appears in the display indicating the load  is permanently off     Pressing the           key a fourth time  returns to automatic   5   appears in the  display     All days shown in the respective blocks  will switch on  or off  at the selected hour  and minute     73    e TRANE    Unit Startup Procedures    1  Check all electrical connections for  tightness    2  For water cooled units  gain access to  the liquid line service valves in the unit s  left lower section     Note  Verify the liquid line service valve is  ope
149. ing charge of dry  nitrogen  Before installing the unit  refrigerant piping  momentarily depress  either the suction or discharge line access  valve to verify the holding charge has not  been lost  If no nitrogen escapes the  access valve  leak test the entire  refrigerant system to determine the leak  source  Use a halogen leak detector  a  halide torch  or soap bubbles to leak test   After finding a leak  remove the test  pressure and repair the leak  Retest the  unit to ensure all leaks are repaired     Brazing Procedures   Proper brazing techniques are essential  when installing refrigerant piping  The  following factors should be kept in mind  when forming sweat connections     1  When heating copper in the presence  of air  copper oxide forms  To prevent  copper oxide from forming inside the  tubing during brazing  sweep an inert  gas  such as dry nitrogen  through the  tubing  A nitrogen flow of 6 to 10 cubic  feet per hour is sufficient to displace the  air in the tubing and prevent oxidation    of the interior surfaces  Use a pressure  regulating valve or flow meter to  control the flow     2  Ensure that the tubing surfaces  requiring brazing are clean  and that the  tube ends are carefully reamed to  remove any burrs     3  Make sure the inner and outer tubes of  the joint are symmetrical and have a  close clearance  providing an easy    slip     fit  If the joint is too loose  the  connections tensile strength is  significantly reduced  Ensure the  overlap distanc
150. ing heating fail status indicator    22  Used in programming mode to set  HEAT SUPPLY AIR  COOL SUPPLY AIR   and MORNING WARMUP  temperatures     SCXG SVX01B EN    Programming the Time Clock  Option    Setting the Time   Important  Depress reset key before   beginning to set time and program    1  Select military  24 00 hr   or AM PM   12 00 hr   time mode by depressing  and holding the    h    key while pressing       1h  key to toggle between military  and AM PM   AM appears in the display  when in AM PM mode     2  Press and hold down          key    3  If setting the time when daylight  savings time is in effect  press      1h   key once    1h will appear in display     4  Set hour with  h  key  If AM or PM  does not appear in display  the unit is in  military time  See note above to  change display    5  Set minutes with  m  key    6  Press  Day  key repeatedly to the day  of the week   1 is Monday  7 is Sunday    7 Release          key  colon will begin  flashing     Note  If keys h   or m   are kept de   pressed for longer than 2 seconds  a rapid  advance of figures will result     The  Digi 20  electronic time switch is  freely programmable for each day of the  week in one minute increments  For easy  and quick programming  the following 4  block programs are available      Monday through Sunday     Monday through Saturday   e Monday through Friday   e Saturday and Sunday    SCXG SVX01B EN    Installation    e TRANE       Programming   Follow the instructions below fo
151. ing screw  to deter access by unauthorized person   nel  Additionally  the RHI can control up to  four different units     HI Location Recommendations   The HI microprocessor module is  mounted inside a molded plastic  enclosure for surface mounting  It is not  weatherproof  Therefore  it is only  applicable for indoor use     Locate the RHI panel in an area that will  ensure the communication link between  the panel and the unit s  does not exceed  5 000 feet maximum or pass between  buildings  See Table I PR 8     The run length of the low voltage AC  power wiring to the remote HI must not  exceed three  3  ohms conductor  Refer  to Table I PR 9     58    Installation                                           Menus    Nou d      Test N  Status     Setpoints     Diagnostics     Start J    Setup    configuration   Service J   Custom    Mode   N a N  Previous A     Enter J   Auto        Next   Cancel Stop                                                      s                   o                         Figure I PR 31  Human Interface  HI  Panel Keypad    Table         8  Maximum Communication    Link Wiring Length          Max  Wire Max  Capaci   tance   Length Between  Conductors   1 000 ft up to 60 pf ft  2 000 ft up to 50 pf ft  3 000 ft up to 40 pf ft  4 000 ft up to 30 pf ft  5 000 ft up to 25 pf ft       Note  pf ft   picofarads foot    Ambient Temperature and Humidity   Limits   Ambient Operating Conditions     Temperature  32 to 120 F     Relative humidity  10 to 9096 
152. ints  are adjustable at the human interface  panel     Return Air Temperature Sensor   The return air temperature sensor is an  analog input device used with a return  humidity sensor on units with the  comparative enthalpy option  The sensor  monitors the return air temperature and  compares it to the outdoor temperature  to establish which temperature is best  suited to maintain cooling requirements   It is mounted in the return air path and  connected to the ECEM     Supply Fan Circuit Breaker  Fuses  and  Overloads   The supply fan motor is protected by  either circuit breakers fuses or a  combination of fuses and overloads   dependent upon unit configuration  Circuit  breakers are used on units without VFDs   They will trip and interrupt the motor  power supply if the current exceeds the  breaker trip value  The RTM shuts all  system functions off when detecting an  open fan proving switch  Units with VFDs  have fuses to protect the VFD and motor     90    Owner       Units with VFD w bypass have fuses to  protect VFD circuit and overloads to  protect the motor when in bypass     Supply Air Temperature Low Limit   The supply air temperature low limit  function uses the supply air temperature  sensor input to modulate the economizer  damper to the minimum position if the  supply air temperature falls below the  occupied heating setpoint temperature     Supply Air Temperature Sensor   The supply air temperature sensor is an  analog input device  It monitors the  supply air
153. it     SEE DETAIL  B  FOR  English    inches  ON PAGEA SEE DETAIL           ON PAGE 20                     FILTER ACCESS        FILTER ACCESS            27 5 8   WATER OUTLET    4 5 8  J    7 1   2     SEE DETAIL  A    SEE DETAIL             24 3   4   ON PAGE 21 FRONT VIEW WATER INLET ON PAGE 21  2 1   2           __ 7 1 2  17   WATER OUTLET WATER OUTLET  14   2 1   2  ENPT __ 14 3   4  WATER INLET  WATER INLET  1 1 2  INPT  CONDENSER     7 5 8     FITTINGS  4X   FT SI VIEW FILTER ACCESS FT SI VIEW    FACTORY PIPED UNITS DIRECT CONDENSER CONNECTIONS  93 4  4X    ISOLATOR HOLE LOCATION    ON BOTTOM OF UNIT            VERTICAL DISCHARGE OPTION  SEE DETAIL 78    FOR  DIMENSIONAL DATA   ON PAGE 21           69    FILTER ACCESS  FILTER ACCESS          1 1 2  INPT  DRAIN  4 1 4     QUICK RELEASE  ACCESS PANEL    QUICK RELEASE  ACCESS PANEL                        I aye  7 1 2               1 1 2  INPT  4X   4 1   2   1 1 27 INPT  ae BACK VIEW 2  DRAIN 7 7 8      WATER INLET      2 1 2  ENPT     WATER OUTLET 11 1 2     WATER OUTLET  2 1 27 ENPT 15 1 8      WATER INLET    7    WATER INLET        WATER OUTLET    RIGHT SIDE VIEW RIGHT SIDE VIEW  FACTORY PIPED UNITS DIRECT CONDENSER CONNECTIONS    SCXG SVX01B EN 17    e TRANE    Installation       SCWG  SIWG Unit     HORIZONTAL DISCHARGE OPTION  Metric   mm                 DAT    SEE DETAIL       ON PAGE 21 ONPAGE21 N             uv N  n        ul     o   lt  1448 3     c  u ul  2            902         I        702   17  n  MEG 2197   
154. ith chilled water  cooling     Reason for Diagnostic  A low air temp  limit trip is detected continuously for  more than one second  This can occur if    114    Diagnostic  Troubleshooting       the hydronic heat low air temp limit input  closes for  gt  1 second  or if the chilled  water low air temp limit trip input opens  for   1 second  On units with both  hydronic heat and chilled water  both low  air temp limit inputs are active  and the  unit will respond in the same manner  regardless of which input is used     UCM s Reaction  The UCM will initiate the   following actions    a  An  open all water valves  request is  issued to the heat module function   causing any steam  hot water  or chilled  water valves on the unit to open    b  An  all heat off  request is issued to  the heat control function    c  A  fan off  request is sent to the supply  fan control function    d  A  close damper  request is sent to  the economizer actuator control  function     Reset Required   PMR  A manual reset is  required after the low air temp limit trip  condition clears  The diagnostic can be  reset at the unit mounted human  interface  by Tracer Summit   or by  cycling power to the RTM     Low Pressure Control Open   Circuit 1  2   3 or 4   Problem  The Low Pressure Control  LPC   for Ckt  1  2  3  or 4 is open     Check  State of refrigerant charge for ckt   1  2  3  or 4     Reason for Diagnostic  The Ckt   1 LPC  input is detected open as described in the  compressor protection fun
155. ith supply air temperature  control entering the unoccupied mode   the following sequence will occur    e Heating cooling functions cease and the  economizer option closes fully  The  supply fan shuts down for proper cool   down time of the heat exchanger   However  the supply fan may remain  on for a short period of time    e After the supply fan shuts down  the  occupied unoccupied relay energizes  and the IGV option fully opens  Also  the  VAV box stroke time begins  The VAV  box stroke time is field adjustable to  allow time for VAV boxes to go to the  full open airflow position    e After the max VAV box stroke time  expires and the IGVs are fully open  the  supply fan  economizer  if enabled    compressors  and heat enable to satisfy  the unoccupied zone temperature  setpoints     Note  Unoccupied economizer operation  can be enabled or disabled at the HI or  using Tracer Summit       For units without volume control entering  the unoccupied mode  the following  sequence will occur           occupied unoccupied relay  energizes and the economizer option  fully closes    e The fan mode is set to auto and the unit  will control to the unoccupied zone  temperature setpoints     With MWU enabled at the HI  if the zone            MWU Ventilation  Enable    MWU  ventilation  Enable Offset          MWU    Figure O SO 1  Typical cycling morning warmup cycle     SCXG SVX01B EN    temperature is below the MWU setpoint   the unit enters the MWU mode     Morning Warmup   This featu
156. ize the lowest possible  enthalpy level when considering  economizer operation  In addition  it  receives space pressure information to  maintain the space pressure within the  setpoint control band  Refer to the Figure  O GI 1 for humidity vs  voltage values     An optional temperature sensor can be  connected to the VCM to enable control  of a field installed fresh air preheater     Also  a field provided CO  sensor can be  connected to the VCM to control CO   reset  The reset function adjusts the  minimum cfm upward as the CO                                1 0 concentrations increase  The maximum  d effective  reset  setpoint value for fresh  07  air entering the unit is limited to the  8 0 6   system s operating cfm  Table O GI 5 lists  5      the minimum outside air cfm vs  input  031 voltage   0 2  1 Table         5  Minimum Outside Air                               0 10 20 30 40 50 60 70 80 90 100 Setpoint w VCM Module and Traq                            Percent Relative Humidity Sensing    Unit Input Volts CFM  SXWG 20 0 5   4 5 vde 6 350 8 500   Figure         1           Relative Humidity vs  SXWG 25 05 45 vde __   7  250 10 625   Voltage  SXWG 30 0 5   4 5 vde 7 250 12 750  SXWG 35 0 5   4 5 vdc 7 250 14 875  SXRG 20 0 5   4 5 vde 7 250 8 500    SXRG 25 0 5   4 5 vdc 7 250 10 625  SXRG 32 0 5   45 vde 7 250 13 600            Assembly      located ingide  the Filter Compartment    Trang    Tube From Tee to  Low Side of trangducer       Tube From High Side  of Veloci
157. kers 89  Compressor Contactor Fail 112  Compressor Cycling 95  Compressor Isolators 39  Compressor Lead Lag Operation 95  Compressor Module 80  Compressor Motor Winding Thermo   stats 89  Compressor Safety Devices 96  Compressor Stages 95  Compressor        112  Compressors 95  Condensate Drain Connections 34  Condenser Connections 34  Condenser Temp Sensor Failure 112  condensing temperature rises above  the lower limit 89  Connecting to Tracer Summit 62  Constant Volume Zone Sensor 55  Constant Water Flow 84  Control Options 5  Control Power 37  Control Sequences of Operation 91  Cooling 93  Cooling Capacity Percent 96  Cooling Tower Interlock 80  Cooling Airside Economizer 93  Cooling Waterside Economizer 93  Cycling Capacity Morning Warmup 91    D    Day Button 67   Daytime Warmup 94  Diagnostics 112   Dirty Filter 112   Dirty Filter Sensor Option 86  Draining the Coil 107   Duct Connections 33  Ductwork 63    E    ECEM 81   ECEM Communications Failure 112  Electric Heat 94   Electric Heat Coil Wiring Procedure 46  Electric Heat Installation 46  Emergency Stop 113   Emergency Stop Input 79    Entering Cond Water Temp Sensor Fail  113   Entering Water Temp Sensor Fail 113   Erase Button 67   Evacuation 103   Evap Temp Sensor Failure 113   Evaporator Coil Frost Protection 97   Evaporator Temperature Sensor Frostat  89   EXHAUST sequence          80   Exhaust Comparative Enthalpy Module  81   External Auto Stop Switch 78   External Unit Isolation 16    F    Factory Mounted T
158. l     Reset based on outdoor air temperature  Outdoor air cooling reset is sometimes  used in applications where the outdoor  temperature has a large effect on  building load  When the outside air  temperature is low and the building  cooling load is low  the supply air setpoint  can be raised  thereby preventing  subcooling of critical zones  This reset can  lower usage of mechanical cooling  thus  savings in compressor kW  but an  increase in supply fan kW may occur     Outdoor air heating reset is the inverse of  cooling  with the same principles applied     For both outdoor air cooling reset and  heating reset  there are three user  defined parameters that are adjustable  through the human interface panel    e Beginning reset temperature   e Ending reset temperature     Maximum amount of temperature reset    Reset based on zone temperature   Zone reset is applied to the zone s  in a  building that tends to overcool or  overheat  The supply air temperature  setpoint is adjusted based on the  temperature of the critical zone s   This  can have the effect of improving comfort  and or lowering energy usage  The user   defined parameters are the same as for  outdoor air reset     Supply Air Tempering  Hot Water and  Steam VAV Units Only    When supply air temperature falls below  the supply air temperature deadband low  end  the heating valve modulates open to  maintain the minimum supply air  temperature setpoint     Daytime Warmup  Units with Supply Air  Temperature Control 
159. l  compressor basis  When a compressor  starts  its timer also starts  The compres   sor evaporator circuit frost protection can  override the    minimum    timer and  reduce the five minute minimum re   quired time period     When the unit is powered up  or manually  reset there will be a three to eight minute  delay before the first compressor may be  turned on as requested by the unit  temperature control algorithm     Compressor Lead Lag Operation  Compressor lead lag is a user selectable  feature at the HI panel and is available on  all units  After each request for  compressor operation  the lead  refrigeration circuit or compressor  switches  thereby causing a more  equitable or balanced run time among  compressors     When lead lag is enabled  each time the  system cycles  it will alternate between  the standard compressor staging and the  lead lag staging  Using Table O SO 1  a  SXWG 30 ton unit will first stage com   pressor B then A  then AB for first cycle  and A  then AB for the second cycle   Appropriate condenser valves  water   cooled and condenser fans  air cooled   will stage with appropriate compressors  to maintain saturated condensing  temperature  Enabling lead lag may drop     cooling stage when compared to  standard staging  See Table O SO 1 for  compressor staging                    Unit Refrigerant Compressor HP Standard Lead Lag SCM  Size Circuit Type by Stage Compressor Compressor or  Model   Digit 5       Staging Staging MC  SXWG 20  25 Independen
160. l cause a manual  reset diagnostic if the duct static exceeds  the preset static limit  The static limit is  adjustable at the HI     SCXG SVX01B EN    Control Sequences of  Operation    Occupied Unoccupied Switching   There are four ways to switch occupied    unoccupied     1  Night setback zone sensor    2  Field supplied contact closure   hardwired binary input to RTM     3  Tracer Summit      4  Factory mounted time clock    Field Supplied Occupied Unoccupied  Input on the RTM   This input accepts a field supplied switch  or contacts closure  such as a time clock   with a rating of 12 mA at 24 VDC  minimum     Tracer Summit   System   The Tracer Summit   system can control  the occupied unoccupied status of the  self contained unit     Factory Mounted Time Clock   A time clock can control the  occupied unoccupied status of the  self contained unit     Unoccupied    The unoccupied mode helps conserve  energy during times when a building is  usually unoccupied  When in unoccupied  mode  the unit will control to the  unoccupied setpoints  usually a lower  heating setpoint and higher cooling  setpoint   Setpoints can be programmed  at the HI  Tracer Summit    or the night  setback zone sensor     The unit enters the unoccupied mode  when the RTM receives a closed signal    MWU  Terminate  Temperature                     Morning  warmup  A Temperature B         es   lt     Terminate 2    Owner    e TRANE       on the unoccupied input for more than  five seconds     For units w
161. l remain  off for a minimum of three minutes     If the LP cutout trips four consecutive  times during the first three minutes of  operation  the compressors on that circuit  will lock out and a manual reset diagnos   tic initiates    Evaporator Temperature Sensor  Frostat      The evaporator temperature sensor is an  analog input device that monitors  refrigerant temperature inside the  evaporator coil to prevent coil freezing  It  is attached to the suction line near the  evaporator coil with circuits 1 and 2  connected to the SCM MCM and circuits  3 and 4 connected to the WSM  The coil  frost cutout temperature is factory set at       F It is adjustable at the HI from 25 35     The compressors stage off as necessary  to prevent icing  After the last  compressor stages off  the compressors  restart when the evaporator  temperature rises 10 F above the coil  frost cutout temperature and the  minimum three minute    off    time  elapses     Saturated Condenser Temperature  Sensors   The saturated condenser temperature  sensors are analog input devices used on  all units  They are mounted inside a  temperature well located on a condenser  tube bend on air cooled units  and in the  condenser shell on water cooled units   The sensors monitor the saturated  refrigerant temperature inside the  condenser coil and are connected to the    SCM MCM for circuits 1 and 2  air or  water cooled   and WSM for circuits 3  and 4  only water cooled      Head Pressure Control   Head pressure co
162. ling mode   When the unit is in occupied cooling  the  RTM controls the zone temperature  within the cooling setpoint deadband by  modulating the economizer option and or  staging mechanical cooling on and off as  required     Supply Air Temperature Control    Unit Model Number Digit 9 1  2  3  or 6  When the unit is in occupied cooling  the  RTM controls the supply air temperature  to the specified supply air cooling setpoint    SCXG SVX01B EN    Owner    e TRANE       by modulating the economizer option  and or staging mechanical cooling on and  off as required  The changeover relay  contacts  field supplied  must be open on  units with hydronic heat for cooling to  operate     Cooling   Upon entering occupied mode  the RTM  receives an input from either the HI  RHI   Tracer Summit    or the GBAS to start the  supply fan  The RTM supply fan contacts  close and energize the supply fan  contactor  On units with IGV  the fan  delays until the        fully close  When the  supply fan starts  the fan proving switch  closes  signaling the RTM that airflow is  established  Depending on unit options   either the IGV will begin to drive open or  the VFD will ramp the fan  and or the  airside economizer dampers will open to  the user defined minimum position     When    cooling request is sent to the  RTM from the zone sensor  the RTM  evaluates the system operating condi   tions using the supply air and outdoor  temperature input before sending the  request to the MCM for mechanical
163. lly sealed 3 D scroll  compressor motors utilize internal motor  protection and time delays to prevent  excessive cycling  Unit controls are either  an electromechanical thermostat or  microprocessor controls on the IntelliPak  unit  See Figure         1 for a typical unit     The hermetically sealed 3 D scroll  compressor motors utilize internal motor  protection and time delays to prevent  excessive cycling     The water cooled condensers are shell  and tube type with an internal subcooler   Condensers are available as mechani     Installation    cally or chemically cleanable  The  evaporator fan is double width  double  inlet and forward curved with a fixed  pitch belt drive assembly  Frequency  drives or inlet guide vanes are optional   Motor options are standard efficiency  open drip proof  ODP  or totally enclosed  fan cooled  TEFC   or premium efficiency  ODP    All water cooled units ship with a full  refrigerant and oil charge  Air cooled  units ship with oil and a dry nitrogen  holding charge and require field piping  refrigerant connections to the air cooled    condensing unit  Also  air cooled units  have two refrigerant circuits  Water   cooled units have four refrigerant circuits   which include a filter drier  pressure relief  valve  liquid line service valve  sight glass   moisture indicator  thermal expansion  valve with a sensing bulb and external  equalizing line  discharge line shrader  valve  a suction line shrader valve  and  high and low pressure cutout
164. lowed  and the VO  Output relay will be deenergized     Reset Required   PAR  An automatic reset    occurs after communication has been  restored     SCXG SVX01B EN    SCXG SVX01B EN    Diagnostic  Troubleshooting    e TRANE       W    WSMI Communications Fail   Problem  The RTM has lost  communication with the WSM   Check  Field unit wiring between RTM  and WSM     Reason for Diagnostic  The RTM has lost   communication with the WSM           Reaction  The UCM will react as if   a freezestat has occurred by issuing    e An    All Heat On    or  Mod Output Full  Open    request to    Heat Control      eA    Fan off    request to    Supply Fan  Control        A  Close Damper    request to     Economizer Actuator Control    e The water pump to turn on and position  all water valves to provide maximum  flow through all water source heat  exchangers   e Disables preheat function if WSM Mixed  AirTemp Sensor is selected as Preheat  Sensor    Reset Required  An automatic reset  occurs after one complete set of IPC  packets is received     WSM Mixed Air Temp Sensor Fail   b  Activation Conditions  temperature  lt     50 F or temperature  gt  209 F and sensor  is selected for use by    Water Side  Economizer Temperature Enable  Function    or    Preheat Function      c  Time to React  10 sec  lt T  lt  20 sec   e  Actions to be Initiated     Water Side  Economizer Temperature Enable  Function    uses Supply Air Cooling  Setpoint instead of Mixed Air  Temperature  If Mixed Air Tempera
165. matically circulate water through the  economizer and condensers periodically  during non operational times  This allows  fresh chemicals to circulate in waterside  heat exchangers  This feature is on all  units and is defined at the HI     Water Piping Options   Water piping is factory installed with left   hand connections  Units can be ordered  with either basic piping or intermediate  piping  Also  units with waterside  economizers can be set for either  variable or constant water flow at the HI   See Figures O GI 3          4  and O GI 5 for  detailed piping configuration information     With compatible piping configurations   the unit can be configured to provide    1  Constant water flow with basic or  intermediate piping or 2  Variable water  flow  head pressure control  with  intermediate piping only     Constant water flow is for condenser  pumping systems that are not capable of  unloading the water pumping system   Variable water flow maximizes energy  saving by unloading the water pumping  system       Basic Water Piping   This option is available on units without a  waterside economizer and with  condenser water applications above 54 F   12 2 C  that do not require condensing  pressure control  Left hand water  connections and piping are extended to  the unit exterior  Manifold piping is  factory installed       Intermediate Water Piping   This option provides condensing  temperature control when the unit is  configured  user defined at the HI  for  variable wat
166. mmable night setback  See  Figure I PR 30     The timeclock  a    Digi 20    by Grasslin  is  inside the control panel  but accessible  with the control panel door closed  This  same type timer is also used for pro   grammable night setback morning warm  up  Programming instructions for the     Digi 20    timer are in the    Program   ming    section on page 73     Timeclock Installation   1  Ensure operating temperature is within  4to 131 F   2  Locate the time clock at least 5 feet  away from any large electrical contact  or machinery to avoid possible  electrical interference problems    3  Provide a separate independent circuit  for the time clock power supply    4  Since all electronic instruments are  sensitive to voltage spikes  pay close  attention tot he following    a  If possible  supply power to the  electronic time clock from a phase  different than the one supplying power  to the load    b  Provide a suitable Varistor or RC  network across the INDUCTIVE  LOADS supply terminals to reduce  voltage spikes    c  Place a diode across the DC  OPERATED INDUCTOR terminals to  eliminate back EMF   d  HIGHLY INDUCTIVE LOADS  especially  fluorescent lights  may require a relay  in which case step a  and c  apply     The timeclock can be surface or flush  mounted  Lift off the front cover and  loosen the two screws on opposite  corners  Pull off the base s plug with a left  to right rolling motion     Timeclock Installation Checklist   1  Ensure operating temperature is wit
167. n at unit start up  Each compressor  suction line contains a low pressure  sensor that will shut the compressor down  in low pressure situations  See Table O SO   2 on page 97     A CAUTION    Never manually or automatically  pump down below 7 psig  This  will cause the compressor to  operate in a vacuum and cause  compressor damage        1  Be sure all system components are  properly set and installed    2  Inspect all ductwork and duct  connections    3  Remove compressor and fan  assembly tie down bolts  However  on  20 38 ton units  do not remove the fan  assembly shipping blocks and tie down  bolts if the fan speed is 750 rpm or less     To start the unit  complete the following   list in order    1  Apply power to the unit  Close the unit  disconnect switch option    2  Make sure that the liquid line service  valves are open on water cooled units    3  Adjust setpoints at the HI     See the  ntelliPak  Self Contained  Programming Guide  PKG SVPO1B EN   for available unit operating setpoints   Refer to the job specifications for proper  setpoints     Note  A sufficient cooling load must be  visible to refrigerant circuit controls for the  mechanical refrigeration to operate  If  necessary  temporarily reduce the dis   charge air setpoint to verify the refrigera   tion cycle operation     74    Installation    1  Ensure the fan rotation is in the  direction of the arrow on the fan  housing  If rotation is incorrect  first  verify the incoming power phasing is  correct  I
168. ner  and  Diagnostic Manual  CXRC SVX01A EN   See Table O GI 10 for CXRC refrigerant  connection sizes     control board  with outside and return air  temperature and relative humidity  sensors  are provided for monitoring  outside and return air  The sensors are  field installed  Economizer operation  enables when the outside air enthalpy is  3 BTU   s lb  less than the return air  enthalpy  During occupied mode  the  outside air damper opens to 1596   adjustable 0 100956  for ventilation  purposes  Also  the ability to alter the  outside air damper position to  compensate for VAV supply air  modulation is inherent in the unit  controls  and can be enabled by the  operator  An analog 2 10 VDC output   adjustable  0 10 VDC  is provided to  modulate the field provided 30 second  damper actuators  adjustable 1 255  seconds      Condenser fans will stage per a user   defined setting  If the condenser is  equipped with head pressure control  air  modulation on last stage of condenser  capacity   the condenser airflow will  modulate to maintain condensing  temperature setpoint  Condensing  temperature is determined by sensors  located at each condenser coil     Maximum  Airflow    Increasing  Reset Amount          Increasing  Concentration    Carbon Dioxide Carbon Dioxide  Reset Start Maximum Reset    Figure O GI 6  CO  Reset Function  Outside Air vs  CO     0            Setpoint       Table         10  Remote Air Cooled Condenser Refrigerant Connection Sizes   English  inches  Me
169. ng sequence can be   used    e Supply fan     Off   e Supply fan VFD     Off  0 Hz    if equipped        Inlet guide vanes   closed   if equipped    e Outside air dampers     Closed   e Heat     all stages     Off  Modulating heat  output at 0 vdc   e Occupied unoccupied output     De   energized   e VO relay     Energized   e Exhaust fan  field installed    Off   e Exhaust damper  field installed    Closed    PRESSURIZE sequence    B     This override sequence can be used if a  positively pressured space is desired  instead of a negatively pressurized space   e Supply fan   on  e Supply fan VFD   on  60 Hz    if equipped       Inlet guide vanes VAV boxes     open   if equipped   e Outside air dampers     open  e Heat     all stages     off  hydronic heat  output at 0 vdc    Occupied  unoccupied output   energized    VO relay   energized  e Exhaust fan  field installed    off    Exhaust damper  field installed    closed    EXHAUST sequence           With the building s exhaust fans running  and the unit s supply fan off  the  conditioned space becomes negatively  pressurized  This is desirable for clearing  the area of smoke when necessary  i e   from an extinguished fire  to keep smoke  out of areas that were not damaged   e Supply fan   off  e Supply fan VFD   off  0 Hz    if equipped   e Inlet guide vanes     closed   if equipped   e Outside air dampers     closed  e Heat     all stages     Off  hydronic heat  output at 0 vdc  e Occupied unoccupied output     de   energize
170. ns any operating  compressor s  on that circuit off  locks out  all compressor operation for that circuit   and initiates a manual reset diagnostic     Compressor Motor Winding Thermostats  A thermostat is embedded in the motor  windings of each compressor  Each  thermostat opens if the motor windings  exceed approximately 221 F The  thermostat resets automatically when  the winding temperature decreases to  approximately 181 F Rapid cycling  loss  of charge  abnormally high suction  temperatures  or the compressor running  backwards could cause the thermostat to  open  During a request for compressor  operation  if the compressor module  detects a problem outside of it s normal  parameters  it turns any operating  compressor s  on that circuit off  locks out    SCXG SVX01B EN    Owner    e TRANE       all compressor operation for that circuit   and initiates a manual reset diagnostic     Low Pressure Control   Low pressure  LP  control uses a binary  input device  LP cutouts are mounted on  the suction lines near the compressors     The LP control contacts close when the  suction pressure exceeds 27   4 psig  If  the LP control is open when a compres   sor starts  none of the compressors on  that circuit will operate  They are locked  out and a manual reset diagnostic  initiates    The LP cutouts open if the suction  pressure approaches 7   4 psig  If the LP  cutout opens after a compressor starts   all compressors operating on that circuit  will turn off immediately and wil
171. nterlock   To interlock condenser pump tower with  cooling operation  wire the cooling tower  to an external 115 volt control power  source  to ground  and to control terminal  block  Normally open closed contacts are  provided     Heat Module    The heat module is standard on all units  with factory installed heat  It controls the  unit heater to stage up and down to bring  the temperature in the controlled space  to within the applicable heating setpoint   Also  it includes a LEATPD  morning  warmup  and heating outputs     Ventilation Override Module   VOM  Option    The ventilation override module can be  field configured with up to five different  override sequences for ventilation  override control purpose  When any one  of the modules five binary inputs         activated  it will initiate specified functions  such as  space pressurization  exhaust   purge  purge with duct pressure control   and unit off     Once the ventilation sequences are  configured  they can be changed unless  they are locked using the HI  Once locked   the ventilation sequences cannot be  unlocked     The compressors and condenser fans  disable during the ventilation operation  If  more than one ventilation sequence    activates  the one with the highest priority   VOM           begins first  with VOM    E     having lowest priority and beginning last     A description of the VOM binary inputs  follows below     UNIT OFF sequence    A      When complete system shut down is   required  the followi
172. ntrol is accomplished  using two saturated refrigerant  temperature sensors on air cooled units  and up to four sensors on water cooled  units     e Air cooled units  During a request for  compressor operation when the con   densing temperature rises above the  lower limit of the control band  the  compressor module  SCM MCM   sequences condenser fans on  If the  operating fans cannot bring the condens   ing temperature to within the control  band  more fans turn on  As the satu   rated condensing temperature ap   proaches the lower limit of the control  band  fans sequence off  The minimum  on off time for condenser fan staging is  5 2 seconds  If the system is operating at  a given fan stage below 100  for 30  minutes he saturated condensing  temperature is above the efficiency  check point setting  a fan stage will be  added  If the saturated condensing  temperature falls below the efficiency  check point setting  fan control remains at  the present operating stage  If the fan  stage cycles four times within a 10  minute period  the lower limit tempera   ture is redefined as being equal to the  lower limit minus the temporary low limit  suppression setting  The unit will utilize  this new low limit temperature for one  hour to reduce condenser fan short  cycling     e Water cooled  Units without WSE  the  condenser valve modulates to maintain  an average saturated condenser  temperature  Units with WSE  if econo   mizing and mechanical cooling is neces   sary the economize
173. o go to a full open  airflow position     SCXG SVX01B EN    Occupied Sequence Of  Operation    All setpoints can be adjusted using the       panel  Also  cooling heating setpoints can  be adjusted in the zone  if using one of the  zone sensor options  BAYSENS020   BAYSENS021        5    5008         5    5010        5    5019  or        5    5014   For a complete list of unit  setpoint default values and ranges  see  the IntelliPak   Self Contained  Programming Guide  PKG SVPO1B EN     Occupied Zone Temperature   Cooling  The unit transitions from unoccupied to  occupied when the occupied unoccupied  input on the RTM is open for more than  five seconds after having been closed   This input can be received from Tracer  Summit    the remote NSB zone sensor   the timed override function  or a field  supplied contact  Dependent on unit  options and the HI programming  the  following sequence will occur      The unit will begin MWU and then  switch to the occupied mode after the  MWU setpoint is met    e Purge will be enabled by Tracer  Summit   Then Tracer Summit  will  enable the occupied mode      The unit will switch from unoccupied to  occupied control immediately    Upon entering occupied mode  the IGV   option will close while the supply fan   remains on  The occupied unoccupied  relay will de energize     Zone Temperature Control    Unit Model Number Digit 9   4 or 5   A zone sensor located directly in the  space sends input to the RTM while the  CV unit is in occupied coo
174. on  factors  Properly dispose of used  materials    eTake extra care to properly maintain all  service equipment directly supporting  refrigerant service work such as  gauges  hoses  vacuum pumps  and  recycling equipment       Stay aware of unit enhancements   conversion refrigerants  compatible  parts  and manufacturer s  recommendations that will reduce  refrigerant emissions and increase  equipment operating efficiencies     Follow specific manufacturer s  guidelines for conversion of existing  systems     To assist in reducing power generation  emissions  always attempt to improve  equipment performance with improved  maintenance and operations that will  help conserve energy resources        WARNING  Do not work in a  closed area where refrigerant or  nitrogen gases may be leaking  A  sufficient quantity of vapors may       acetylene  or air in place of  refrigerant and dry nitrogen for  leak testing  A violent explosion  may result causing injury or  death           WARNING  Always use a pressure  regulator  valves  and gauges to  control drum and line pressures  when pressure testing the  system  Excessive pressures may  cause line ruptures  equipment  damage  or an explosion which  may result in injury or death           WARNING  Do not exceed 200  psig when leak testing the  system  Damage to the unit could  result  or an explosion may occur  causing injury or death       In the event of required system repair   leak test the liquid line  evaporator coil   and sucti
175. on Pressure   psig  Circuit A  Circuit B  Circuit C  Circuit D   Discharge Pressure   psig  Circuit A  Circuit B  Circuit C  Circuit D   Super Heat   F  Circuit A  Circuit B  Circuit C  Circuit D   Liquid Line Pressure   psig  Circuit A  Circuit B  Circuit C  Circuit D   Sub Cooling   F  Circuit A  Circuit B  Circuit C  Circuit D        SCXG SVX01B EN 75    e TRANE    installation    Water Cooled Units     Circuit A    Entering Water Temperature   F  Leaving Water Temperature   F   Entering Water Pressure   psig  Leaving Water Pressure   psig   Circuit B    Enter Water Temperature   F  Leaving Water Temperature   F   Entering Water Pressure   psig  Leaving Water Pressure   psig   Circuit C    Entering Water Temperature   F  Leaving Water Temperature   F   Entering Water Pressure   psig  Leaving Water Pressure   psig   Circuit D    Enter Water Temperature   F  Leaving Water Temperature   F   Entering Water Pressure   psig  Leaving Water Pressure   psig        Air Cooled Units    Data taken from outside condensing unit           Voltage  Amp Draw    A B C A B C  Entering Air Temperature   F  Leaving Air Temperature   F   Refrigerant Pressures at condenser   psig    Sub cooling at condenser   F        76 SCXG SVX01B EN    SCXG SVX01B EN    Owner    e TRANE       Points List  RTM Module     Binary inputs   e Emergency stop   e External auto stop   e Unoccupied occupied   e Dirty filter   eVAV changeover with hydronic heat    Binary outputs   eVAV box drive max         units only 
176. on for Diagnostic  The unit is reading  a signal that is out of range for the supply  air pressure sensor voltage input  Input     40mV or Input  gt  4 75V            Reaction  The IGV s will drive  closed  and the following functions are  disabled    a  SA pressure control   b  SA static pressure limit    Reset Required   PAR  An automatic reset  occurs after the SA temp heating setpoint  input returns to within range for 10  continuous seconds  or after a different  SA temp heating setopint selection  source is user defined     Supply Air Pressure Setpoint Failure  Problem  The SA pressure input signal is  out of range     Reason for Diagnostic  The SA pressure  setpoint input is sending a signal that is  out of range  Input  lt  1 0 IWC or Input  gt  4 3  IWC            Reaction  The default SA pressure  setpoint will become the active SA  pressure setpoint     Reset Required   PAR  An automatic reset  occurs after the designated SA pressure  setpoint source sends a signal within    SCXG SVX01B EN    range for 10 continuous seconds  or after  a different SA pressure setpoint source is  user defined     Supply AirTemp Cool Setpoint Fail  Problem  The active supply air  temperature cooling setpoint is out of  range     Reason for Diagnostic  The input  designated as the SA temp cooling  setpoint is out is out of range  temp  lt  35 F  or temp  gt  95 F            5 Reaction  The default Hl set SA  temp cooling setpoint becomes the active  SA temp cooling setpoint     Reset R
177. on line at pressures dictated by  local codes  and using the following  guidelines    1  Charge enough refrigerant and dry    SCXG SVX01B EN    nitrogen into the system to raise the  pressure to 100 psig    2  Use a halogen leak detector  halide  torch  or soap bubbles to check for  leaks  Check interconnecting piping  joints  the evaporator coil connections   and all accessory connections    3  If a leak is detected  release the test  pressure  break the connections and  reassemble it as a new joint  using  proper brazing techniques    4  If no leak is detected  use nitrogen to  increase the test pressure to 150 psig  and repeat the leak test  Also  use soap  bubbles to check for leaks when  nitrogen is added    5  Retest the system to make sure new  connections are solid    6  If a leak is suspected after the system  has been fully charged with refrigerant   use a halogen leak detector  halide  torch  or soap bubbles to check for  leaks     Evacuation   For field evacuation  use a rotary style  vacuum pump capable of pulling a  vacuum of 100 microns or less     When connecting the vacuum pump to a  refrigeration system  it is important to  manifold the pump to both the high and  low side of the system  Follow the pump  manufacturer   s directions     A CAUTION    Do not use a Meg ohm meter or  apply power to the winding of a  compressor while it is under a  deep vacuum  This may damage  the motor windings        Refrigerant Charging   After leak testing and evacuating the  
178. one CSP input returns to its allowable  range for 10 continuous seconds  or after  a different valid occupied zone CSP  selection source is user defined     119    e TRANE    A       After Shipment    Accessory Model  Number 8  Air Filters 98  Air Cooled Condensers 88  Airside Economizer Installation 48  Airside Economizer Interface 88  Airside Economizer Interface with  Comparative Enth 88  Airside Economizer Option 87  Airside Economizers with Trag Damper  87  Ambient Temperature and Humidity  Limits 58  Annual Maintenance 110  Auto Changeover 94  Auto Reset S A Static Pressure Limit  112          Basic Water Piping 84  BAYSENO20 Icon Descriptions 72  BAYSENSOOS8 Description 50  BAYSENSO 10 Description 52  BAYSENSO 13 Description 52        5    5014 Description 52  BAYSENSO017B Description 51        5    5019 64  BAYSENSO19 Description 55  BAYSENSO19 Icon Descriptions 71  BAYSENSO19 Keypad and Display  Explanation 64  BAYSENSO20 Keypad and Display  Explanation 65  BAYSENSO20 Description 55  BAYSENSO 21 Description 51  Brazing Procedures 36    C    Cautions 59   Changeover 94   Chemical Cleaning of Condenser and  Economizer Coil 108   Cleaning the Condenser 108   Cleaning the Flow Switch 109   CO  sensor 87   CO  Sensor Failure 112   Coil Fin and External Cleaning 107   Common HVAC Acronyms 2   Communication Link  Shielded Twisted                   120    Pair  Wiring 61  Communication Wiring 62  Comparative Enthalpy Control 87  Component Overview 63  Compressor Circuit Brea
179. oper performance and normal   operating life  Installation must be in an   area where it will be protected from      Direct sunlight  rain or moisture      Corrosive gases or liquids    e Vibration  airborne dust  or metallic  particles     For effective cooling as well as proper  maintenance  install the VFD vertically to  the ground using four mounting screws   There must be a minimum eight inch  clearance above and below the VFD  A  minimum two inch clearance is required  on each side     Also  allow enough clearance for opening  the VFD cabinet door  This will ensure  sufficient air space for cooling     Refer to the  Dimensions and Weights   sections on pages 28 30 for VFD  dimensions and weights     VFD Electrical Installation Procedure  Refer to the National Electric Code   section 310 16 for sizing wires 4B   9B  All  other control wires should be twisted  shielded or twisted pair shielded  20   14  AWG  with lead length not to exceed 164  feet  When using shielded wire  the shield  sheath must be connected at the VFD  only  The connection on units with VFD  only is J13 S  On units with VFD w   bypass  the connection is ITB1 10     47    e TRANE    Airside Economizer Installation    Unit Handling   1  Hoist the damper cabinet to the  installation location with straps  positioned under the skid as shown in  Figure I PR 12  Use spreader bars to  prevent unit damage during lifting     2  With the damper cabinet at its final  location  near the unit   remove the  screws s
180. ory piping tubing assembly  ASSEMBLY  4        Table I PR 1  Waterside Economizer Ship Separate Parts List  LH  temi Pant Description Factory Item Part   Qty  Description             Assembly  1 Piping  Figure         6  petal view of ship separate B Assembly 2 LeftHand 7001 2 Tube  2 5   7 x 9     tubing assemblies for waterside econo  C Assembly  3 X17110026250 5 Elbow  2 5 s  x 2      mizer left hand piping  D Assembly  4 4003 1 Tube  2 5     x 26 15 6     E Tube  25    x 16 7  4  1     17 BL 5         8 x 8     Tube 2 W  x22 X21040098390 10 ft   Gasket  X21080406030 1  Insulation  2 58    Rubatex  X16120203570 1 Plug  1 1   2    Brass  X17150027060 1 Bushing  2 1   2    ftg  x 1 1 2     X17170031210 1 Tee  2 59     x 2 1 8    x 2 5 8     4738 1  Tube  2 5     x 19 1 16     4007 1 Tube  2 5     x 14 1 2     4006 1 Tube  2 5  x 19 he       SCXG SVX01B EN 43    e TRANE    Installation       Waterside Economizer with  Right Hand Factory Piping  Components    Table I PR 2  Waterside Economizer Ship Separate Parts List  RH       Right Hand 4001 1 Tube  2 5     x 9     4607 1 Tube  2 5     x 17   X17110026250 5 Elbow  2       x 2 5 s   4605 2 Tube  2 55  x 9 1 2     X153301770100 1 Water Valve  4008 1  Tube  2   s  x 20 1 4     X17170031210 1 Tee  2 9     x 2 1 8    x 2 8   X16120203570 1 Brass Plug  1 1 2     X17150027060 1 Bushing  2 s  ftg  x 1 1 2     4007 1 Tube  2 5    x 14 1 2     4606 1 Tube  2 5    x 62  4603 1  Tube  2 5       x 11 34   4006 1 Tube  2 9s  x 19 34   446
181. out of range for the circuit   1  2  3  or 4 saturated condenser  temperature sensor   temp     55 F or  temp  gt  209 F            5 Reaction  A    Lockout Ckt    1  2  3   or 4  request is issued to the compressor  staging control function     Reset Required   PAR  An automatic reset  occurs after the circuit 1  2  3  or 4  condenser temp input returns to its  allowable range within 10 seconds     D    Dirty Filter  Problem  There is a dirty filter     Reason for Diagnostic  The filter switch  input on the RTM is closed for more than  60 seconds continuously     UCM s Reaction  An information only  diagnostic is set     Reset Required   INFO  An automatic  reset occurs after the dirty filter input  reopens for 60 continuous seconds     E    ECEM Communications Failure  Problem  The RTM has lost  communication with the ECEM     Check  Field unit wiring between RTM  and ECEM module     Reason for Diagnostic  The RTM has lost  communication with the ECEM    UCM s Reaction  If the unit has the  comparative enthalpy option  the  economizer enable r e  enthalpy function  will revert to level 2 enthalpy  comparison     SCXG SVX01B EN    Reset Required   PAR  An automatic reset  occurs after communication has been  restored     Emergency Stop  Problem  The emergency top input is  open     Reason for Diagnostic  An open circuit  has occurred on the emergency stop  input caused either by a high duct temp t   stat trip  or the opening of field provided  contacts  switch  etc     UCMs 
182. ove the MWU  terminate setpoint     91    e TRANE    92    Owner       Timed Ovenide Activation   ICS      This function is operational whenever the  units RTM module is used as the zone  temperature sensor source  which can be  set at the HI panel  When this function is  initiated by the push of the override  button on the zone sensor  the unit will  switch to the occupied mode  Unit  operation  occupied mode  during timed  override is terminated by a signal from  Tracer      Timed Override Activation   Non ICS  This function is active whenever the unit s  RTM module board is selected as the  zone temperature source  which can be  set at the human interface panel  When  this function is initiated by the push of the  override button on the zone sensor  the  unit will switch to the occupied mode   Automatic cancellation of the timed  override mode occurs after three hours  of operation     VAV Drive Max Output   This is a single pole  double throw relay  rated at a maximum voltage of 24 vac  2  amps max  The relay contacts of this  relay switch when the unit goes from the  occupied mode to the unoccupied mode  by means of the unoccupied binary input   night setback zone sensor  or Tracer  Summit    The contacts will stay switched  during the unoccupied and morning  warmup mode  They will return to the  position shown on the unit wiring  diagram when the unit returns to the  occupied mode  The intent of this binary  output is to signal the VAV boxes or other  terminal devices t
183. p Button   Shifts controller to temporary manual  override  and begins temperature  override     7  Fan Button  Toggles the fan controller between on  and auto mode     8  Mode Button   Toggles the controller through its four  modes  off  heat  cool  and auto  if HP  version  also emer  emergency      9    e Indicates day of the week   e Indicates begin time in program menu  Indicates time setting in temporary  override mode     SCXG SVX01B EN    BAYSENS020          INDICATES TIME  OF DAY BY HOUR         Installation       MornDayEveNite       AND MINUTE SuMoTuWeThFrSa _      od  INDICATES               SUPPLY AIR       MORNING OR          WARM UP   I 1  AFTERNOON MODE Yam      INDICATES ROOM TEMP    OVERRIDE TIME   AND OCCUPIED  OR UNOCCUPIED  PERIODS    INDICATES  KEYPAD  LOCKOUT STATUS     OFF    BAYSENSO20 Keypad and Display  Explanation    1  Up and Down Buttons     Increases or decreased programmed  temperature settings in program menu    e Shifts to temporary manual override in  normal run mode    elncreases or decreases temperature  while in temporary override menu      Pressed together  toggles between  unoccupied occupied setting     2  Time Adjust Button   Used to set the correct time of day  Used  to set programmed time for temperature  variations     SCXG SVX01B EN        AUTO    OPTION    INDICATES  ROOM  TEMPERATURE                      Figure       2  BAYSENS020 Keypad and display configuration     3  Program Button  Toggles between the display control    scre
184. page 32  Level or repair the  floor before positioning the unit if  necessary        Allow minimum recommended  clearances for routine maintenance and  service  Refer to unit submittals for  dimensions        Allow three fan diameters above the  unit for the discharge ductwork  Return  air enters the rear of the unit and    conditioned supply air discharges  through the top        Electrical connection knockouts are on  the top  left side of the unit        Allow adequate space for piping  access and panel removal  Condenser  water piping  refrigerant piping  and  condensate drain connections are on  the lower left end panel     Note  Unit height and connection locations  will change if using vibration isolators  The  unit height may increase up to 57     with   spring type isolators        Electrical supply power must meet  specific balance and voltage  requirements as described in the   Electrical Requirements  section on  page 37     L1 Water cooled units only  The installer  is responsible for providing a condenser  main  standby water pump  cooling  tower  pressure gauges  strainers  and  all components for waterside piping   See the  Water Piping  section on page  34 for general waterside  recommendations     L1 Air cooled units only  The installer is  responsible for providing and installing  the remote air cooled condenser and  refrigerant piping  including filter driers     SCXG SVX01B EN    e TRANE       Installation       HORIZONTAL DISCHARGE OPTION    SCWG SIWG Un
185. peed  modulation  The drives will accelerate or  decelerate as required to maintain the  supply air static pressure setpoint     VFD with Bypass   Bypass control is an option that provides  full nominal airflow in the event of drive  failure  The user must initiate the bypass    Table O GI 9  Supply Fan Horsepower Selections        Unit Model HP       2                  159  140 15 2   25  SXWG2 KKK KK             SXWG 25  30  35 X X X X X X  SXRG 20 X X X X X  SXRG 25  32 X X X X X  SCXG SVX01B EN    mode at the HI panel  When in bypass  mode  VAV boxes need to be fully open   The self contained unit will control  heating and cooling functions to maintain  setpoint from a user defined zone sensor   Supply air static pressure limit is active in  this mode     For more detailed information on VFD  operation  reference the Square D VFD  technical manual that ships with the unit     Airside Economizer Option   Units with the airside economizer option  are equipped with the necessary control  sequences to use outside air for the first  stage of cooling  in occupied or  unoccupied mode and when ambient  conditions are favorable for economizing   Inherent in the unit controller is the ability  to suppress the setpoint below the  normal unit setpoint  This allows the  building to improve comfort levels when  possible  and at the same time  optimize  building mechanical cooling operation for  peak operating efficiency  An outside air  temperature and relative humidity  sensor are pro
186. r   programming the time clock    1  Press    Prog    key  1234567 AM         will appear in display   Pressing    Prog     key again  display will show the number  of free programs    Fr 20      Press again  to RETURN to 1st program    2  Press          key           ON symbol will  appear  Pressing the key again will  toggle to OFF    O     Select ON or OFF  for the program    3  Press    h     to select hour for switching  time    4  Press    m     to select minute for  switching time    5  If the program is to occur every day of  the week   24 hour time control  ignore     Day    key and press    Prog     key to  advance to program    6  For 7 day time control  press    Day     key  123456  Monday through  Saturday  block of days appears in  display  Pressing    Day    key again  123  4 5  Monday through Friday  appears in  display  Repeated presses will cycle  through all days of the week and back  to 1 through 7  Monday through  Sunday   Select day or block of days   desired    7  Press  Prog   key and repeat steps 2  through 6a to enter additional  programs of ON and OFF times   Note  that more than one OFF time may be  programmed  enabling automatic  control or manual overrides     8  Press          key to enter run mode     To review and change programs    1  To review a program at any time  press     Prog     key  Programs display in the  sequence they were entered with  repeated presses of    Prog     key    2  To change a program  select that  program as outlined 
187. r  Install  screws removed in step 3 through the  damper cabinet s side flanges and into  the C channel s corresponding holes     11  Attach ductwork to the top and back  dampers according to local codes     Field Wiring Connections   12  Open the damper cabinet s door and  connect the factory provided plug  from the actuator to the factory   provided plug in the unit s filter  section           Cable with spreoder bar    13  Cabinets withTRAQ    dampers  only  Unroll the two rolls of pneumatic  tubing located inside the damper  cabinet  Route these tubes through the  cabinet s front upper panel  0 25 dia   holes provided   Connect them to the  two pneumatic tubes protruding from  the customer electrical connection  panel on the unit  Be sure to connect like  tubes to each other  black to black   white stripe to white stripe      14  Cabinets with TRAQ    dampers  only  Locate the  bullet  sensor and  rolled up wiring in the unit s filter  section  Route it into the damper  cabinet and insert the sensor into the  sensor mounting clip attached to  underside of one of theTraq    dampers                                            Figure I PR 13  Proper installation of the airside economizer option     SCXG SVX01B EN    Connector For 1 4  Tubing    SCXG SVX01B EN    Installation    e TRANE          Static Pressure Transducer  Installation  VAV units only     Supply air static pressure controls the  inlet guide vane and VFD options  A static  pressure head assembly ships separate 
188. r Summit    or by cycling power to  the RTM     Supply Fan VFD Bypass Enabled   a  Data used  module packet byte  bit    RTM   b  Activation conditions  supply fan VFD  bypass has been activated and supply  fan vfd bypass is installed    c  Time to React  10 sec  lt T  lt  20 sec   d  Diagnostic text  human interface  display    SUPPLY FAN VFD BYPASS ENABLED     e  Actions to be Initiated  NONE   f  Reset  The INFO diagnostic is cleared  when the supply fan VFD bypass is  deactivated     T    TCI Module Comm Failure  Problem  The RTM has lost  communication with the TCI     Check  Check field unit wiring between  RTM and        module     Reason for Diagnostic  The RTM has lost  communication with the TCI module     UCM s Reaction  All active commands  and setpoints provided by Tracer  Summit  through the TCI will be  cancelled and or ignored  And where  Tracer Summit   has been designated as  setpoint source  local HI default setpoints  will be used     Reset Required   PAR  An automatic reset  occurs after communication has been  restored     Tracer Communications Failure  Problem  The TCI has lost  communications with Tracer Summit       Check  Tracer Summit   building control  panel  is powered up and running  properly  If so  check unit wiring between  TCI and Tracer Summit   building control  panel      117    e TRANE    Reason for Diagnostic  The TCI has lost  communications with Tracer Summit   for   gt  15 minutes     UCM s Reaction  All active commands  and setpoint
189. ranged in a staggered  pattern to maximize heat transfer  The  coil has round copper supply and return  headers with removable cleanout and  vent plugs  The optional mechanical  cleanable economizer has removable  cast iron headers to allow easy mechani   cal cleaning of the tubes  The waterside  working pressure is rated for 400 psig   2758 kPa      Waterside Economizer Flow Control  Units equipped with a waterside  economizer can be set from the human  interface panel for variable or constant  water flow        Constant Water Flow   Two way modulating control shutoff  valves are wired  controlled  and installed  in the unit  One valve is located in the  economizer s water inlet  and the other is  in the condenser bypass water inlet   When the waterside economizer enables   the two way valves modulate to maintain  the discharge air temperature setpoint   As the economizer valve opens  the    SCXG SVX01B EN    condenser bypass valve closes  and vice  versa  Full water flow is always  maintained through the condensers  Both  valves will close in the event of a power  failure  See Figures O GI 3 and O GI 5     e Variable Water Flow   Two way modulating control shutoff  valves are wired  controlled  and installed  in the unit  One valve is located in the  economizer s water inlet  and the other is  in the condenser bypass water inlet   When the economizer valve is active  the  condenser bypass valve closes  The  economizer valve modulates  thus water  flow through the unit modul
190. re can be enabled at the HI  and  can be used with factory or field installed  heat  If MWU is not required disable the  function in the setup menu at the HI   MWU transitions the zone from  unoccupied to occupied  It will heat until  the MWU setpoint is met  The unit is then  released to occupied mode  Supply duct  static pressure is maintained during this  sequence  MWU can be set  at the HI  to  function as either full or cycling capacity     Full Capacity Morning Warmup  MWU   Full capacity morning warmup uses full  heating capacity to heat the zone as  quickly as possible  Full heating capacity  is provided until the morning warmup  setpoint is met  At this point  the unit is  released to daytime mode     Cycling Capacity Morning Warmup   MWU    Cycling capacity morning warmup  provides a more gradual heating to  overcome  building sink  as the zone is  heated  Normal zone temperature control  with varying capacity is used to raise the  zone temperature to the MWU zone  temperature setpoint  This method of  warmup is used to overcome the     building sink  effect     Reference Figure O SO 1 for a pictorial  explanation of the cycling MWU se   quence  Cycling capacity MWU will heat  until MWU temperature setpoint is  reached  Next a 60 minute timer begins  If  the building load reaches the MWU  ventilation setpoint  or the 60 minutes  expire  whichever is first  the airside  economizer will control to the minimum  position  MWU will end when the zone  temperature rises ab
191. re servicing the unit   Failure to do so may result in  injury or death from electrical  shock or entanglement in moving  parts        Table         1  SCWG SIWG SCRG SIRG Clearance Requirements       Side Distance Purpose  Front 42 in   1066 mm  NEC code requirement  Left 18 in  Air cooled units only  36 in   914 mm  Refrigeration and waterside component service  77 in  Fan shaft removal  Right 36 in   914 mm  Provides uniform airflow  Inlet 18 in   457 mm  Provides uniform airflow       Air Inlet    18   457 2 mm   Minimum            SeeTable                     I  36  914mm   Minimum       42   1066 8 mm   Minimum    Figure         4  Top view of self contained unit showing recommended service        code    clearances     11    e TRANE    Installation    Rigging and Unit Handling    Before lifting the unit or modular  component  determine the approximate  center of gravity for lifting safety  See  Figure         5 for assembled modular  units and Figure    PC 6 for split apart  units  The center of gravity may vary  slightly within the gravity block  depending on unit options     7 WARNING    Ensure lifting equipment capacity  exceeds unit weight by an  adequate safety factor to prevent  injury  death  or unit damage        Always test lift the unit to determine the  exact unit balance and stability before  hoisting it to the installation location  See  Figures         7 and I PC 8 for typical  rigging procedures and proper rigging  equipment usage        Figure I PC 5  A
192. recommendations     8  Air cooled units only  model SXRG    These units require field installation of a  remote air cooled condenser and  refrigerant piping  See the  Refrigerant  Piping  section on page 36 for general  piping recommendations     SCXG SVX01B EN    SCXG SVX01B EN    Installation    e TRANE          Service Access    See Figure         4 and Table         1 for  recommended service and code  clearances  Access to thermostat unit  controls is through a hinged access panel  door on the front  lower left of the unit s  compressor section     IntelliPak   unit control access is through a  panel on the middle right of the fan  section  The panel is secured with an  automatic latch and quick acting fasten   ers  which require a screwdriver to open     Removable front unit panels provide  access to compressors  fan  motor  inlet  guide vane actuator  and belts     Removable left side panels give access to  drive side  fan bearing  inlet guide vanes   condensers  and waterside economizer  control valve  The compressor  con     denser and fan motor access panels are  secured with quick acting fasteners   Access panels for evaporator coils   expansion and water valves  and left fan  bearing are sheet metal screws  Access  to other components for service requires  removal of panels secured with sheet  metal screws  During operation  sight  glasses are viewable through portholes  on the upper right side panel of the fan  section     Disconnect electrical power  source befo
193. red to one of  these remote zone sensors  wiring must be 18 AWG shielded twisted pair  Belden 8760  or equivalent   Refer to the specific zone sensor for wiring details  It provides the  following features and system control functions      Remote temperature sensing in the zone     Morning warmup sensor     Zone sensor for ICS    systems     Zone temperature averaging    When used as a remote sensor for standard zone sensor  the thermistor sensor must  be disabled     BAYSENS008 Description   This zone sensor module is for use with cooling heating constant volume units  It has  four system switch settings  heat  cool  auto  and off  and two fan settings  on and  auto   The zone sensor provides either manual or automatic changeover control with  dual setpoint capability     BAYSENS008 features and system control functions include      System control switch to select heating mode  HEAT   cooling mode  COOL    automatic selection of heating or cooling as required  AUTO   or to turn the  system off  OFF       Fan control switch to select automatic fan operation while actively heating  or cooling  AUTO   or continuous fan operation  ON       Dual temperature setpoint levers for setting desired temperature  The blue  lever controls cooling  and the red lever controls heating      Thermometer to indicate temperature in the zone  This indicator is factory  calibrated     BAYSENSO 1 Description   This zone sensor module is for use with VAV units without night setback  It allows the  u
194. rmostat     Dirty Filter Sensor Option  A factory installed pressure switch  senses the pressure differential across    86    Owner       the filters  When the differential pressure  exceeds 0 9 inches  23 mm  WG  contact  closure occurs and the HI will display a  diagnostic  The unit will continue to run  until you replace the air filters     A field installed indicator device may be  wired to relay terminals to indicate when  filter service is required  Contacts are  rated at 115 VAC and are powered by a  field supplied transformer     Low Ambient Sensor  Air Cooled Units   The low ambient sensor is field installed  on air cooled units  Position it in a location  subject to ambient temperatures only  and not exposed to direct sunlight or  exhaust fans     The low pressure cutout initiates based  on the ambient temperature  A time  delay on the low pressure cutout initiates  for ambient temperatures between 50   zero minutes  and 0 F  10 minutes   This  helps to prevent nuisance low pressure  cutout trips     Inlet Guide Vane Option   Inlet guide vanes  IGV  are driven by a  modulating 0 10 vdc signal from the RTM  module  A pressure transducer  measures duct static pressure  and the  IGV modulates to maintain the supply air  static pressure within an adjustable user   defined range  The range is determined  by the supply air pressure setpoint and  supply air pressure deadband  which are  set through the HI panel     IGV assemblies installed on the supply  fan inlet regulate
195. roper  adjustment                   the fan rotates freely    LITighten locking screws  bearing set  screws and sheaves                   bearing locking collars do not  wobble when rotated     Ductwork   Olf using return ductwork to the unit   secure it with three inches of flexible  duct connector    LIExtend discharge duct upward without  change in size or direction for at least  three fan diameters    OUse    3  flexible duct connection on  discharge ductwork                   trunk ductwork to        boxes is  complete and secure to prevent leaks    OWVerify that all ductwork conforms to  NFPA 90A or 90B and all applicable  local codes    Water Cooled Unit Piping   LIVerify the condensate drain piping is  complete for the unit drain pan  Install  and tighten the condensate  P  trap  drain plug    Olnstall water piping drain plugs   economizer header  and condenser  vent plugs               return and supply water  connections to the unit and or  waterside economizer piping package  with recommended valves and piping  components  Refer to the  Water  Piping  section on page 34    Olnstall unions to allow waterside  maintenance    Olnstall cooling tower and standby  pumps    LITreat water to prevent algae  slime   and corrosion    LIPrevent refrigerant piping from  rubbing against other objects     Air Cooled Units Only  LIConnect refrigerant lines   Olnstall liquid line filter driers     Units with Hydronic Heat   LIVerify the entering water temperature  sensor is install
196. rride run 7 Intelligent Temperature Recovery 0   Disabled 0  mode  The option value shown is in 1  Enabled  hours  and value selected is five hours  8 Programmable Days Week 0   7 days  M TW TES S  0       1 23 days     5 S  S  When the option menu displays  the only 2   2 days  M F 5 5   active buttons are the T or   arrow and 9     Programmable Periods Day 234 4  the  minus  and    plus    button  The 7 or 10 Programmable Fan Operation 0   Disallowed 0  4 arrow increment through the available 1 Remote Sensor installed   No 0  options by number  1 24   and the 1 Yes     minus    and    plus    button toggles 12 Check Filter Interval 0   Disabled 350  through the various option values 2990 t9 selina  Nour  g    p f increments  associated with each option number  See      Display Zone Temperature 0   No 1  Table       1  1   Yes      14 Keypad Lockout Enabled 0   Disabled 1  Note  On both programmable zone sensor E   2  5                   15 nitial Time Setting      Tempora 1 2 3 4 5  options  changing either option 9 or 10 will Override Mode  bre  ry  erase the current program  To avoid 16 Buzzer Options O KeyPressoniy   1  reprogramming  set options 9 and 10 1   Key Fress e Check filter  I   Key Press  eck Filter   before programming  and System Failures  17 Zone Temperature Calibration Displays current temp  0 offset  with any offsets  18 Baud Rate 0  1024 baud 1  1  1200 baud  19 CV or HP Operation 0 CV 0  1 HP  20 Default Cooling setpoint 45 to 98 F 74F  Def     E E  1  
197. rside Economizer  Waterside economizing enables when  the unit s entering water temperature is  below the unit s entering mixed air  temperature by 4 F plus the user  adjustable economizer approach  temperature  The approach temperature  default is 4 F    Waterside economizing disables when  the unit s entering water temperature is  not below the unit s entering mixed air  temperature by at least the water  economizer approach temperature   default value of 4 F   The economizer  acts as the first stage of cooling  If the  economizer is unable to maintain the  zone or supply air temperature setpoint   the compressor module will bring on  compressors as required to meet the  setpoint     Cooling Airside Economizer   On units with an airside economizer  a call  for cooling will modulate the fresh air  dampers open  The rate of economizer  modulation is based on deviation of the  zone temperature from setpoint  i e   the  further away from setpoint  the faster the  fresh air damper will open  The first stage  of cooling will start after the economizer  reaches full open     Note  The airside economizer will only  function freely if ambient conditions are  below the enthalpy control settings or  below the return air enthalpy If unit has  comparative enthalpy installed  If outside  air is not suitable for  economizing    the  fresh air dampers drive to the minimum  open position  A field adjustable  factory  default setting at the      panel or Tracer  Summit  can provide the input
198. s needed to keep  the switch operational     To clean the paddle assembly  remove it  following the procedure below    1  Remove the switch from the unit    2  The paddle assembly and wire retainer    clip holds the paddle assembly in the  switch body    3  Remove the wire retainer clip by  reaching down past the paddle with a  pair of slim nosed pliers and gripping  the end of the wire  Pull up on the wire  clip and remove it    4  After removing the wire clip  use the  pliers to pull the paddle assembly out of  the switch barrel  Clamp the pliers onto  the end of the paddle and remove the  paddle assembly  It will slide straight  out    5  Clean the ferrous particulate from the  magnet using a rag or tack cloth  The  particulate is attracted to the magnet   So it is necessary to pull it off  It will not  simply wipe off    6  After cleaning the magnet  replace the  paddle assembly into the switch body s  barrel  However  it is important to  position the paddle perpendicular to the  arrow on the switch s side and place the  paddles flat side facing the opposite  direction or the arrow  Push the paddle  assembly in until it hits the barrel cavity  bottom    7  Place the spring clip into the switch  barrel and push it down with a small   flat blade screwdriver until the spring  clip engages the groove in the switch  barrel    8  When replacing the paddle assembly   check the operation by pushing on the  paddle   s flat side  The paddle should  swing freely in the direction of 
199. s provided      the RTM 45 22 85 110 4 66  board for installation of a field supplied 50 19 96 120 376  normally closed  N C   switch to use   Ea A  Aes  during emergency situations to shut 65 13 49 150 205  down all unit operations  When open  an 66 13 15 160 1 69  immediate shutdown occurs  An 67 12 82 170 140  emergency stop diagnostic enters the 68 1250 180 117  human interface and the unit will require 69 12 19 190 0 985  a manual reset  Refer to the unit wiring 70 11 89 200 0 830       diagrams  attached to the unit control  panel for the proper connection  terminals  The switch must be rated for  12 ma   24 VDC minimum  This input  will override all VOM inputs  if the VOM    option is on the unit  Table O GI 3  RTM Setpoint Analog Inputs                                         Box Option     quu pepe 2   using             Resistance  ohms   To interlock VAV box operation with 40 10 1084  evaporator fan        heat cool modes  45 45 992   wire the VAV boxes air valves to VAV box so 50 899  control connections on the terminal block  55 55 796  Supply Duct Static Pressure Control       gt   The RTM relies on input from the duct 70 70 500  pressure transducer when a unit is 75 75 403  equipped with        or VFD to position the 80 80 305  IGV or set the supply fan speed to NA 85 208  maintain the supply duct static pressure NA 90 111       to within the static pressure setpoint                deadband          Sensors   Table         4  RTM Resistance Value vs  System Oper
200. s provided by Tracer  Summit  through the TCI will be  cancelled and or ignored  And where  Tracer vSummit  has been designated as  the setpoint source  local HI default  setpoints are used     Reset Required   PAR  An automatic reset  occurs after communication between  Tracer Summit   and the TCI is restored     U    Unit HI Communications Failure  Problem  The RTM has lost  communication with the unit mounted   local  human interface  HI      Check  Field unit wiring between RTM  hand local HI     Reason for Diagnostic  The RTM has lost  communication with the unit mounted  human interface            Reaction  A fail safe function in the   HI will cause the following sequence    a  disallow any interaction between the HI  and the RTM  or any other modules     b  render all HI keystrokes ineffective   c  cause the following message to display  on the unit mounted HI display     Local  HI communications loss  Check comm  link wiring between modules     If the  unit has a remote HI option  then this  diagnostic will display as any other  automatic reset diagnostic     Reset Required   INFO  An automatic  reset occurs after communication is  restored between the RTM and the HI   When the failure screen clears  the  general display restores to allow the HI to  interact with the RTM again     Unoccupied Zone Cool Setpoint Failure  Problem  The unoccupied zone cooling  setpoint input is out of range    Reason for Diagnostic  The input    118    Diagnostic  Troubleshooting       d
201. s without  night setback  It has four system switch settings  heat  cool  auto  and off   two fan  settings  on and auto   and four LED s  The zone sensor provides either manual or  automatic changeover control with dual setpoint capability  In addition  it can be used  with       5    5017     BAYSENS010 features and system control functions include    e System control switch to select heating mode  HEAT   cooling mode  COOL    automatic selection of heating or cooling as required  AUTO   or to turn the system  off  OFF     e Fan control switch to select automatic fan operation while actively heating or cooling   AUTO   or continuous fan operation  ON     e Dual Temperature setpoint levers for setting desired temperature  The blue lever  controls cooling  and the red lever controls heating      Thermometer to indicate temperature in the zone  This indicator is factory calibrated    e Function status indicator lights    e SYSTEM ON glows continuously during normal operation  or blinks if  system is in test mode    e COOL glows continuously during cooling cycles  or blinks to indicate     cooling system failure    e HEAT glows continuously during heating cycles  or blinks to indicate     heating system failure    e SERVICE blinks or glows to indicate a problem  These signals vary  depending on the particular equipment being used     Integrated Comfort    Systems Sensors for CV and VAV  Applications    These zone sensor options are for use with cooling heating Integrated Comfor
202. ser to control system operation and monitor unit operating status from a remote  location  The sensor has a system switch  a S A temperature setpoint indicator  a local  sensor  and four LED s     BAYSENSO21 features and system control functions include     Temperature sensing in the zone   e System control switch with mode setting for  AUTO  and  OFF      Supply air single temperature setpoint   e Function status indicator lights      SYS ON    glows continuously during normal operation  or blinks if system is in  test mode      COOL    glows continuously during cooling cycles  or blinks to indicate a  cooling system failure      HEAT    glows continuously during heating cycles  or blinks to indicate a  heating system failure    SERVICE  blinks or glows to indicate a problem  These signals vary  depending on the particular equipment being used     51    e TRANE    CV Unit Zone Sensor Option    p A    Figure I PR 18 BAYSENS010   Dual setpoint  manual automatic  changeover sensor with system function  lights  Accessory Model Number Digit 6   F       CV and VAV Unit Zone  Sensor Options     6        Figure         19  BAYSENS014   Zone temperature sensor w timed override  and local setpoint adjustment    Accessory Model Number Digit 6            Figure         20  BAYSENSO13  Zone temperature sensor w timed override    Accessory Model Number Digit 6   B    52    Installation    BAYSENS010 Description   This zone sensor module is for use with cooling heating constant volume unit
203. signal that is out of range for    113    e TRANE    this input  temp  lt   55 F or temp  gt  209 F      UCM s Reaction  The functions that  designated the heat module auxillary  temperature input as their input are  disabled     Reset Required   PAR  An automatic reset  occurs after the heat module auxillary  temperature input returns to its allowable  range for 10 seconds     Heat Module Comm Failure  Problem  The RTM has lost  communication with the heat module     Check  Check field unit wiring between  RTM and heat module     Reason for Diagnostic  The RTM has lost  communication with the heat module     UCMS Reaction  An  all heat off  request  is sent to the heat operation function     If the unit has staged gas or electric heat   all heat module outputs will be zeroed  and deenergized     If the unit has hydronic heat or chilled  water installed  the unit will turn off the  supply fan and close the outside air  damper upon the occurrance of a heat  module comm failure  A failsafe function  in the heat module will cause all water  valves to be set to 10096 to provide full  water flow  Unless used for switching  purposes  air handlers with chilled water  and mod gas  or chilled water and  hydronic heat  all binary outputs will be  deenergized     Reset Required   PAR  An automatic reset  occurs after communication has been  restored     L    Low Air Temp Limit Trip   Problem  The low air temp limit has  tripped   Units with steam or hot water  heating  or air handlers w
204. ssembled unit gravity block location     Table         2  Gravity Block Dimensions    Re 2  0                 SXWG 36 14 38 12  To prevent injury or death and SXRG 36 16 40 12    unit damage  always test lift the  unit to determine actual center of  gravity  See Figures I PC 5 and I   PC 6              Fan Section Only                Figure         6  Split apart unit gravity block location     12 SCXG SVX01B EN    e TRANE       Installation       Rigging and Handling                             Spreader Bars   Unit Shipping   1  Position rigging sling under wood  shipping skid    2  Use spreader bars to avoid unit  damage    3  When using a forklift  exercise caution  to prevent unit damage    4  Use the standard fork length to lift one  end and drag or pull unit while skidding  the opposite end    5  The unit center of gravity will fall within  center of gravity block at various  locations depending on unit options    6  Use hooks to lift fan section only  Do not  hook into open channels to lift unit    7  See unit nameplate for unit weight    8  Do not stack units     A  CAUTION    Do not use hooks to lift unit or  hook into open channels to lift  unit  This could cause unit  damage         Spreader Bars    INSERT HOOK AS  SHOWN  TYPICAL  FOR 4 PLACES     Compressor Section Fan Section       Figure         8  Split apart modular unit proper rigging     SCXG SVX01B EN    e TRANE    installation    Split Apart Unit Assembly    1  Ensure the tagging information on the  fan se
205. ssure exceeded the S A static  pressure limit setpoint for at least one  second continuously     UCM s Reaction  A  supply air pressure  shutdown  signal is sent to the following  functions    a  Compressor staging control    b  Economizer actuator control    c  Heat operation    d  Supply fan control    e  IGV VFD control    f  Exhaust fan control    g  Exhaust actuator control    Reset Required   PAR  An automatic reset  occurs after the IGV close  The supply fan  is not allowed to restart for 15 seconds  after the diagnostic occurs  An auto reset  will also occur if the unit cycles out of  occupied mode and back     C    CO  Sensor Failure  Problem  The VCM CO  sensor input  signal is out of range     Check  Check field unit wiring between  sensor and VCM     Reason for Diagnostic  The unit is reading  a signal that is out of range for the CO   sensor transducer input     UCM s Reaction  The CO  reset function  disables     112    Diagnostic  Troubleshooting       Reset Required   PAR  An automatic reset  occurs after the CO  sensor transducer  input receives a signal that is within range  for ten continuous seconds     Compressor Contactor Fail   Circuit 1  2   3 or 4   Problem  The compressor contactor for  Ckt  1  2  3  or 4 has malfunctioned     Reason for Diagnostic  The circuit  compressor proving input is detected  closed continuously for more than three  seconds while neither compressor output  on that circuit closes            Reaction  A  lockout ckt  1  2  3  or
206. subbase enable  or disable applicable functions  i e   morning warmup  economizer minimum  CFM override during unoccupied status   Fahrenheit or Centigrade  supply air  tempering  remote zone temperature  sensor  12 24 hour time display  smart  fan  and computed recovery     During an occupied period  an auxiliary  relay rated for 1 25 amps   30 volts AC  with one set of single pole double throw  contacts activates        Figure         24  BAYSENS019  Programmable  night setback sensor  Accessory Model  Number Digit 6   G    Variable Air Volume Zone Sensor    BAYSENS020B Description   This seven day programmable sensor  with night setback has four periods for  occupied unoccupied programming per  day  Either one or all four periods can be  programmed  If power is interrupted  the  program retains in permanent memory  If  power is off longer than 2 hours  only the  clock and day may have to be reset     The zone sensor keypad allows you to  select occupied unoccupied periods with  two temperature inputs  cooling supply  air temperature and heating warmup  temperature  per occupied period  The  occupied cooling setpoint ranges be   tween 40 and 80 F The warmup setpoint  ranges between 50        90 F with a 2  degree deadband  The unoccupied  cooling setpoint ranges between 45 and  98 EThe heating setpoint ranges be   tween 43 and 96 F    The liquid crystal display  LCD  displays  zone temperature  setpoints  week day   time  and operational mode symbols     The DIP switches on
207. system  charge liquid refrigerant into the  system through the liquid line valve  After  some refrigerant has entered each  circuit  charge gaseous refrigerant into  the suction line shrader valve with the  compressors running     SCXG SVX01B EN    Owner    e TRANE            CAUTION    Caution  Do not operate the  compressors without some  refrigerant in each circuit  Failure  to do so may damage the  compressors           Charge refrigerant into the system by  Refrigerant System    Special Note on Refrigerant Emissions  Follow the Trane recommended  procedures on operation  maintenance   and service to endure refrigerant  conservation and emission reduction   Also  pay specific attention to the  following    e When removing refrigerant from air  conditioning or refrigerating equipment  recover for reuse  recycling   reprocessing  reclaim   or properly  destroy it    e Always determine possible refrigerant  recycling or reclaiming requirements  before beginning recovery  Questions  about recovered refrigerants and  acceptable refrigerant quality  standards are addressed in ARI  Standard 700      Use approved containment vessels and  safety standards when shipping  refrigerant containers    eTo minimize emissions while recovering  refrigerant  use recycling equipment   Always attempt to use methods that  will pull the lowest possible system  vacuum while recovering and  condensing refrigerant into  containment    e When leak checking with trace  refrigerant and nitrogen  use 
208. t 10 10 B AB A AB MCM  SXRG 20  SXWG 30 Independent 15 10                            SXRG 25  SXWG 35 Independent 15 15 B AB A AB MCM  SXRG 32  SCXG SVX01B EN 95    e TRANE    96    Owner       Compressor Safety Devices   The compressors have motor  temperature cutout switches in the motor  windings  These switches are provided to  take the compressors off line during high  motor winding temperature conditions     If a compressor low pressure cutout  opens during compressor start up  the  UCM will not shut the compressor off  during the first two to three minutes after  start up  This prevents possible nuisance  trips during low ambient start conditions   See Table O SO 2     Each compressor s discharge line  contains a high pressure cutout  Under  abnormal operating conditions  the cutout  will open to stop compressor operation     Table O SO 2  Pressure Cutouts              Unit High Pressure Low Pressure  Model Cutout Cutout  SXWG 360 270 20 35  SXRG 425 350 12 27  Step Control    Steps of mechanical cooling are control  based on supply air or zone temperature   See Table O SO 1 on page 95 for  compressor staging     Capacity is based on an integrating  control concept  The unit capacity  matches the existing load and maintains  an average supply air temperature within  the supply air setpoint temperature    control band region     The supply air temperature control band  is centered around supply air tempera   ture setpoint and is adjustable from 2 to  12 F In a steady st
209. t System   ICS     systems     BAYSENSO 14 Description  This electronic analog sensor features single setpoint capability and timed override  with override cancellation     BAYSENSO 4 features and system control functions include      Remote temperature sensing in the zone     A timed override button to move an ICS    or a building management system from its     unoccupied    to  occupied  mode    e Thumbwheel for local setpoint adjustment   e A cancel button to cancel the    unoccupied override  command     BAYSENSO 13 Description  This electronic analog sensor features single setpoint capability and timed override  with override cancellation  It is used with a Trane Integrated Comfort    system     BAYSENS013 features and system control functions include    e Remote temperature sensing in the zone   e A timed override button to move an ICS  or a building management system from its     unoccupied    to    occupied    mode    e Cancel button to cancel the    unoccupied override    mode     SCXG SVX01B EN       Figure         21  Standard zone sensor         5    5017 ships with all units     SCXG SVX01B EN    Installation    e TRANE       Zone Sensor Installation    All sensor options ship in the main control  panel and are field installed   Programmable option installation  procedures are on page 55     Mounting Location   Mount the sensor on the wall in an area   with good air circulation at an average   temperature  Avoid mounting space   temperature sensor is areas subjec
210. t nameplate identifies the unit  model number  appropriate service  literature  and wiring diagram numbers  It  is mounted on the left end of the unit  control panel     e TRANE    Model Number Description    Installation    Each self contained unit has a multiple character model number unique to that unit  To determine a unit s specific options  reference  the model number on the unit nameplate using the model number explanation below     SC WGN 20 4 2           2    10    065 B A 1    010 AACF A 1    10   20       123 4 5 67 8 9 1011 12 13 14 1516 1718 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36       Digit 1   Unit Model  S   Self Contained    Digit 2   Unit Type  C   Commercial      Industrial    Digit 3   Condenser Medium  W   Water Cooled  R   Remote AirCooled    Digit 4   Development Sequence  G   Modular Series    Digit 5   Refrigerant Circuit Configuration  N   Independent    Digit 6  7   Unit Nominal Capacity  20   20Tons  Water or Air Cooled   25   25Tons  Water or Air Cooled   30   30Tons  Water Cooled Only   32   32Tons  Air Cooled Only    35   35Tons  Water Cooled Only     Digit 8   Unit Voltage   6   200Volt 60 Hz 3 ph  4   460 Volt 60 Hz 3 ph  5   575Volt 60 Hz 3 ph    Digit 9   Air Volume Temp Control  1   l Pak  amp  IGV and Supply AirTemp  Ctrl   2     Pak  amp VFD and Supply Air  Temp Ctrl       Pak  amp  VFD w  Bypass         Supply AirTemp Ctrl       Pak w o Vol  CTRL  w  Zone Temp  Cool       Pak w o Vol  CTRL  w  ZoneTemp  Heat Cool   6   l P
211. t to   the following conditions    e Drafts or    dead    spots behind doors or  in corners     Hot or cold air from ducts     Radiant heat from the sun or appliances     Concealed pipes and chimneys   e Unheated or non cooled surfaces  behind the sensor  such as outside walls     Airflows from adjacent zones or other  units    To mount the sensors  remove the dust  cover and mount the base on a flat  surface or 2  x 4  junction box  Sensors  ship with mounting screws     Mounting the Subbase   Remove the zone sensor cover from  subbase  and mount subbase on the wall  or on a 2 x 4 junction box  Route wires  through the wire access hole in the  subbase  See Figure I PR 22 on page 54   Seal the hole in the wall behind the  subbase     Wiring    A WARNING    Disconnect all electric power  including remote disconnects  before servicing  Failure to do so  before servicing may cause severe  personal injury or death           Note  Guidelines for wire sizes and  lengths are shown in Table         7 The total  resistance of these low voltage wires  must not exceed 2 5 ohms per conductor   Any resistance greater than 2 5 ohms may  cause the control to malfunction due to  excessive voltage drop     Note  Do not run low voltage control  wiring in same conduit with high voltage  power wiring     1  Run wires between the unit control  panel and the zone sensor subbase  To  determine the number of wires  required  refer to the unit wiring  diagrams     2  Connect the wiring to the appropr
212. tained Ship With Accessory Model Number Description    P 5 Ww G S    A 1 1 0 AO       1 2 3 4 5    6 7 8 9    10 11       Digit 1   Parts Accessories  P   Parts Accessories    Digit 2   Unit Model   S  Self Contained   Digit 3   Shipment   W   With Unit   Digit 4   Development Sequence    F   Signature Series  G   Modular Series    Digit 5   Sensors and Other Accessories  S   Sensors    Digit 6   Sensors and Thermostats  field   installed    A   BAYSENS017   Zone Temp Only  CV  and VAV         BAYSENS013   Zone Temp with  Timed Override Button  CV and VAV     SCXG SVX01B EN    C  BAYSENS014   Zone Temp with  Timed Override Button  Setpoint Dial   CV                  D   BAYSENS023   Remote Min  Position  Potentiometer Control  OA Damper    E   BAYSENS008   CV Zone Sensor   F   BAYSENS010   CV Zone Sensor with  Indicator Lights   G   BAYSENS019   CV Programmable   Night Setback Sensor   H   BAYSENS021          Zone Sensor   with Indicator Lights   J   BAYSENS020   VAV Programmable   Night Setback Sensor   K   Remote Sensor Kit   L   Outside Air Temperature Sensor Kit   M   Outside Air Humidity Sensor Kit   N   BAYSTAT010   2 Heat 2 Cool   Thermostat    Digit 33   Control Interface Options        Generic BAS Module  GBAS    B   Ventilation Override Module  VOM   C z Tracer Comm  Interface Module  TCI   D  Remote Human Interface  RHI    E  GBAS and TCI   F  VOM and TCI   G   GBAS and VOM        GBAS and RHI              and RHI   K   TCI and RHI   L   GBAS  VOM  and TCI   M   GB
213. tandard current rating of over  current protective device  use the next  lower standard rating for the marked  maximum rating     For units with the dual power option   there are two circuits that need calcula   tions using the formulas above     circuit  1   fans  circuit  2   compressors    If the rating value determined does not  equal a standard current rating of over  current protective device  use the next  lower standard rating for the marked  maximum rating     38    Installation    Table I ER 1  Number of Compressors per Unit       SCWG SIWG 20 25 30 35   SCRG SIRG 20 25 32  10 HP 2 2 1    15 HP   1 2       Table         2  SCWG SIWG Compressor Motor Data                                                    200V 460V 575V  HP RLA LRA RLA LRA RLA LRA  10  33 1 269 14 4 117 11 5 94  15 46 9 409 20 4 178 16 4 143  Table  ER 3  SCRG SIRG Compressor Motor Data  200V 460V 575V  HP RLA LRA RLA LRA RLA LRA  10 38 4 269 16 7 117 13 4 94  15 55 0 409 24 1 178 19 1 143  Table         4  Fan without VFD  200V 460V 575V  HP LRA  5 16 1 105 67 46 5 4 37  7 5 25 0 152 10 8 66 82 54  10 32 9 193 142 84 11 4 66  15 448 290 20 3 126 16 2 102  20 61 0 373 25 0 162 20 0 132  25 74 0 469 31 0 204  24 2 162  Table         5  Fan with VFD  200V 460V  HP      LRA      LRA  75 29 0 152 14 3 66  10 38 3 193 18 2 84  15 42 7 290 25 3 126  20 55 2 373 32 0 162  25 67 8 469 32 7 204  Table         6  Electric Heat   Single Stage  SCWG SIWG SCRG SIRG Heat 200V 460V  Size Size Kw Amps Amps  20 20 16
214. temporary manual  override settings      Depressing either the up or down arrow  keys while in temporary manual  override run mode will cause the ZSM  to toggle to temporary manual override  menu      The erase button will turn off the check  filter icon if displayed    e Simultaneously depressing and holding  the positive and negative sides of the  minus plus key for four seconds will lock  out the keypad    eTime is not adjustable in this mode     OVERRIDE    OCCUPIED       ROOM TEMP                   Figure       7 Temporary manual override run  mode screen     SCXG SVX01B EN    e TRANE    installation                                                                               Option Menu and Keypad Operation Table       1  Zone Sensor BAYSENS019 Option Menu Settings   The operation menu sets all    MENU C RUN A 2     224 Option   Description Value Factory Setting  programmable options built into your      B B   1 Morning Warmu 0   Disabled 0  ZSM  All options are retained in i P 1 Enabled  permanent EEPROM memory  2 Economizer minimum 0   Disabled 1       Position override 1  Enabled  To access the option menu display  3 Temperature Scale 0   Fahrenheit 0  simultaneously depress and hold the 1 Enabled  mode button and program button forfour 4 Supply AirTempering 22 Deed 0  seconds  See Figure       8  i Tame Ci           5  The example in Figure       8 shows option 1224 hours  15 displayed and indicates the initial timer 5 Smart Fan      1  setting In the temporary ove
215. ter   and abnormally high condensing tem   peratures  To maintain maximum  condenser efficiency  the condenser must  remain free of built up scale and sludge   Clean the condenser either mechanically  or chemically     Mechanical Cleaning of Condenser and   Economizer Coils   1 Turn off the condenser supply water   Remove drain plugs discussed in the     Draining the Coil    section on page 94     2  Remove the condenser   s left side to  expose the condenser tubes    3  Rotate a round brush through the tubes  to loosen contaminant    4  Flush tubes with water to push the  sludge out through the drain opening in  the bottom of the supply header and  the return pipe    5 To clean the economizer tubes  remove  the cast iron header plates at the coil s  right end between the inlet and outlet  headers  4 row coils  2 row coils do not  have cover plates at right end   Rotate  round brush through tubes from left  end to loosen contaminants  Flush  tubes with water    6  Replace condenser end plates and  clamps  The end plates must be  centered when tightening the clamp    7  Replace coil headers with gaskets and  torque bolts to 50 ft  Ib    8  Replace drain and vent plugs     Chemical Cleaning of Condenser and  Economizer Coil   Chemical cleaning removes scale  deposits built up by minerals in the water   For a suitable chemical solution  consult a  water treatment specialist  The  condenser water circuit is composed of  copper  steel  and cast iron     The chemical supply house s
216. thalpy Control  Comparative enthalpy controls the  economizer operation and measures  temperature and humidity of both return  air and outside air to determine which  source has lower enthalpy  This allows  true comparison of outdoor air and return  air enthalpy by measurement of outdoor  air and return air temperatures and  humidities  A factory installed control  board  with field installed outside and  return air temperature and relative  humidity sensors  allows monitoring of  outside and return air     Note  If comparative enthalpy is not  ordered  the standard method compares  outdoor air enthalpy with the fixed  reference enthalpy  The reference  enthalpy is set at the human interface  panel     Units with comparative enthalpy control  are equipped with the necessary control  sequences to allow using outside air for  the first stage of cooling  in occupied or  unoccupied mode and when ambient  conditions are favorable for economizing   Inherent in the unit controller is the ability  to suppress the setpoint below the  normal unit setpoint  This allows the  building to improve comfort levels when  possible  and at the same time  optimize  building mechanical cooling operation for  peak operating efficiency     Economizer operation enables when the  outside air enthalpy is    BTU S Ib  less  than the return air enthalpy  During  occupied mode  the outside air damper  opens to 15   adjustable 0 100   for  ventilation purposes  Also  the ability to  alter the outside air d
217. the  arrow This action confirms that the  paddle assembly is properly installed    9  Replace the switch into the unit piping  using a good pipe thread sealer  Tighten  the switch so that its final position has  the arrow parallel to the water pipe and  pointing toward the left end of the unit   arrow is pointing in the direction of the  water flow      109    e TRANE    Periodic Maintenance  Checklists    Monthly Checklist   The following check list provides the  recommended maintenance schedule to  keep the unit running efficiently     Disconnect power source and  allow all rotating equipment to  stop completely before servicing  or inspecting the unit  Failure to  do so may result in injury or  death        1  Inspect unit air filters  Clean or replace  if airflow is blocked or if filters are dirty    2  Inspect coils for excess moisture or  icing  Icing on the coils may indicate low  airflow supply  restricted airflow from  dirty fins  evaporator frost protection  sensor problems  or a shortage of  refrigerant flowing through the coil    3  Check that condensate from the  evaporator and economizer coils flows  freely through the condensate piping   traps  drain pan  and drainage holes   Remove algae and or any airflow  obstructions    4  Check the condition and tension of fan  belts  Adjust tension if belts are floppy  or squeal continually  Replace worn or  fraying belts in matched sets     Note  Check and adjust belt tension at  least twice daily the first days of new b
218. tion are either partially  50    or  completely disabled  100   to save  energy  The demand limit definition is  user definable at the HI panel  Demand  limit binary input accepts a field supplied  switch or contact closure  When the need  for demand limiting discontinues  the  units cooling heating functions become  fully enabled again     GBAS Analog Inputs   The GBAS accepts external setpoints in  the form of analog inputs for cooling   heating  supply air pressure  Refer to the  unit wiring diagram for GBAS input  wiring and the various desired setpoints  with the corresponding DC voltage input     82    Owner       Any of the setpoint or output control  parameters can be assigned to each of  the four analog inputs on the GBAS  module  Also  any combination of the  setpoint and or output control param   eters can be assigned to the analog  inputs through the HI To assign the  setpoints apply an external 0 5 vdc  signal   1  directly to the signal input terminals  or  2  to the 5 vdc source at the GBAS  module with a 3 wire potentiometer     Note  There is a regulated 5        output on    the GBAS module that can be used with a  potentiometer as a voltage divider  The  recommended potentiometer value is  1000 100 000 ohms     The setpoints are linear between the  values shown in Table O GI 6 on page 83   Reference Table O GI 7 on age 83 for  corresponding input voltage setpoints   Following are formulas to calculate input  voltage or setpoint  SP   setpoint  IPV    input 
219. tion box  in order to accommodate the  emergency heat mode on the ZSM heat  pump version    12  Fan mode selection box    13  Displayed in normal run mode when  displaying the actual room  temperature    14  Displayed in option setting mode only    15  Digits used to display temperature    16  HEAT and COOL have two functions   they indicate UCM status in normal run  mode and indicate which type of  setpoint is DESIRED during  programming and override setting    17  Only used during programming and  override setting to indicate the  DESIRED setpoint temperature    18  Flashes when check filter timer is  elapsed    19  Flashing cooling fail status indicator    20  Only used during UCP self test mode    21  Flashing service status indicator and  fan failure    22  Flashing heating fail status indicator    23  Operating MODE selection box     71    e TRANE    Installation                                                    1 22 21 20  2  oN MornDay EveNite 19     Su Mo Tu We Th Fr Sa TEST  70 00 Check Filter 18   amp             nc Desired 17  s    eme 1  6      om   PUT  WM    I i   16           Whe Als fy       7 UNOCCUPIED   I i 15  MODE  8 m        v  qi me          10  14  11 12 13    Figure       10  BAYSENS020 complete icon display     BAYSENO2O Icon Descriptions   Refer to Figure I P 10 for a pictorial view   of the written descriptions below    1  The four periods of the day used only  during programming mode    2  The seven days of the week used  during programming and 
220. tric  mm           Unit Circuit 1 Circuit 1 Circuit 2 Circuit 2  Size Liquid Line Discharge Line Liquid Line Discharge Line  CXRC 20  25  29  30 g 1 7  s 1    16   29   16   29        SCXG SVX01B EN    Input Devices and System  Functions    Following are basic input device and  system function descriptions used within  the UCM network on IntelliPak   self   contained units  Refer to the unit wiring  diagrams for specific connections     Water Purge   During the unoccupied mode  water   cooled units will periodically circulate  water through the condensers and  waterside economizer if the user has  enabled the purge function at the HI     The water purge function circulates  water to introduce fresh water treatment  chemicals and help prevent water  stagnation  The number of hours be   tween each periodic purge  or purge  duration  is user defined at the HI  between 1 999 hours  If the periodic  purge timer expires while the unit is in  occupied mode  it will wait for the next  available unoccupied time before  initiating water purge  Contrary  if a  request for cooling occurs during a purge  sequence  purge will terminate and  cooling will commence     Compressor Circuit Breakers   The compressors are protected by circuit  breakers that interrupt the compressor  power supply if the current exceeds the  breakers    must trip    value  During a  request for compressor operation  if the  compressor module  MCM or SCM   detects a problem outside of it s normal  parameters  it tur
221. ts    2  Level the unit by adjusting the isolator  heights  Unit weight may cause the    Top View  Upper  Housing  Side View  gt   1 4  1 2   Clearance    Lower  Housing          upper housing of the spring isolators to  rest on the lower housing  Maintain  clearances between 1 4 to 1 2  To  increase the clearance  lift the unit off  the isolator and turn the leveling bolt  counterclockwise  Verify that the unit is  level and the housing clearances are  correct  The maximum allowable  difference between isolator heights is  14   Shim as required under the  isolators     Note  The unit is equipped with a posi     tively sloped drain pan to help indoor air  quality        and does not require one  corner of the unit to be pitched     l  23 4    1 2  Dia  Positioning Pin           Leveling Bolt    Unloaded  Height    Neoprene Pad    Figure I PR 3  Optional spring flex vibration isolator  type CP 1  for unit isolation     SCXG SVX01B EN    e TRANE       Pre Startup  Installation Requirements       Plenum Treat field cut holes to prevent fiberglass  Before installing the plenum attach the from entering the airstream    insulation strip that ships with the plenum   See Figure I PR 4 for proper insulation  location  Align the plenum front with the  control panel side of the unit  Using the  strips and screws provided  secure the  plenum to the unit     A CAUTION    Do not remove more than two  nonadjacent panels at one time   Failure to do so will cause the  plenum frame to collapse
222. ture is  being used for    Preheat Function     issue  a    Disable    request to    Preheat  Function       f  Reset  An automatic reset occurs after  the Mixed AirTemp  input returns to  within range continuously for 10 seconds     Water Flow Fail   a  Data used  module packet byte  bit    WSM  01 19 05   b  Activation Conditions  The water flow  input is detected open     1  at the end of precool water flow  initiation state  or   2  continuously for five minutes while     water side economizer is open 100       presetting of a Head Pressure Valve  or     demand for mechanical cooling    Unit must be  a  configured with water  cooled condenser and or water  economizer and b  have water flow  switch installed    c Time to React  immediate   e  Actions to be Initiated  A  Lockout All  Ckts  request is issued to the   Compressor Staging Function    f  Reset  An automatic reset occurs after  the Water Flow input returns to within  range continuously for 3 seconds  the  water pump is requested OFF or the  water flow switch becomes not installed     Z    Zone Cool Setpoint Failure  Problem  The occupied zone cooling  setpoint is out of range     Reason for Diagnostic  The input  designated as occupied zone cooling  setpoint source is out of range  temp      45 F or temp    94 F      UCM s Reaction  The active occupied  zone cooling setpoint reverts to the  default occupied zone cooling setpoint     Reset Required   PAR  an automatic reset  occurs after the designated occupied  z
223. ture reset signal     Morning warmup sensor temperature     Entering air temperature    Analog inputs     Cooling and heating setpoints   e VAV discharge air temperature  setpoints     Supply air pressure setpoint     Cooling and heating enable disable     Air economizer enable disable     Airside economizer minimum position     Unit priority shutdown    77    e TRANE    Unit Control Components    The Modular Series IntelliPak   self   contained unit is controlled by a  microelectronic control system that  consists of a network of modules  These  modules are referred to as unit control  modules  UCM   In this manual  the  acronym UCM refers to the entire control  system network     These modules perform specific unit  functions using proportional integral  control algorithms  They are mounted in  the unit control panel and are factory  wired to their respective internal compo   nents  Each module receives and  interprets information from other unit  modules  sensors  remote panels  and  customer binary contacts to satisfy the  applicable request  i e   economizing   mechanical cooling  heating  ventilation   Following is a detailed description of each  modules function     RTM Module Board   Standard  on all Units    The RTM responds to cooling  heating   and ventilation requests by energizing the  proper unit components based on  information received from other unit  modules  sensors  remote panels  and  customer supplied binary inputs  It  initiates supply fan  exhaust fan 
224. ture setpoint     Using a field installed CO  sensor with  CO  reset enabled  as the CO  concentra   tion increases above the CO  reset start  value  the VCM modifies the minimum  outside air CFM setpoint to increase the  amount of fresh air entering the unit  The  setpoint adjusts upward until reaching the  CO  maximum reset value  The maxi   mum effective  reset  setpoint value for  fresh air is limited to the system s  operating CFM  As the CO  concentration  decreases  the effective  reset  setpoint  value adjusts downward toward the  minimum outside air CFM setpoint  See  Figure O GI 6 on page 88 for an airflow  cfm vs  CO  concentration curve     87    e TRANE    Standard Two Position Damper Interface  Units with the two position damper  interface are provided with a 0 10 VDC  control output suitable for controlling a  field provided modulating actuator  In  occupied mode  the output drives to the  maximum position     Airside Economizer Interface   Units with airside economizer interface  are equipped with the necessary control  sequences to allow using outside air for  the first stage of cooling  in occupied or  unoccupied mode and when ambient  conditions are favorable for economizing   Inherent in the unit controller is the ability  to suppress the setpoint below the  normal unit setpoint  This allows the  building to improve comfort levels when  possible  and at the same time  optimize  building mechanical cooling operation for  peak operating efficiency  An outsid
225. ty Flow Ring    Tube From Low Side  of Velocity Flow Ring    Figure         2  Velocity Pressure Trans   ducer Solenoid Assembly     81    e TRANE    Generic Building Automation  System Module Option    The generic building automation system  module  GBAS  provides broad control  capabilities for building automation  systems other than Trane s Tracer   system  A field provided potentiometer  or a 0 5 vdc signal can be applied to any  of the inputs of the GBAS to provide the  following points     GBAS Analog Inputs  Four analog inputs that can be configured  to be any of the following    1  Occupied zone cooling   2  Unoccupied zone cooling   3  Occupied zone heating   4  Unoccupied zone heating   5  SA cooling setpoint   6  SA heating setpoint   7  Space static pressure setpoint   8  SA static pressure setpoint    GBAS Binary Outputs   Five binary outputs to provide  diagnostics  signaling up to five alarms   Each of the five  5  relay outputs can be  mapped to any all of the available  diagnostics  Each output contains a dry  N O  and N C  contact with aVA rating of 2  amps at 24 VAC     GBAS Binary Input   One binary input for the self contained  unit to utilize the demand limit function   This function is operational on units with a  GBAS and is used to reduce electrical  consumption at peak load times  Demand  limiting can be set at either 50  or  100   When demand limiting is needed   mechanical cooling and heating  with  field provided 2 stage electric heat only   opera
226. unit  during storage and transportation   Remove the skids before placing the unit  in its permanent location     Remove the skids using a forklift or jack   Lift one end of the unit off of the skids   See Figure l PC 5 and I PC 6 on page 12  for unit gravity block location  Slide the  skids out and lower the unit at the  installation location     Note  External isolation is not necessary    since units are internally isolated  Consult a  vibration specialist before  double   isolating  the unit     External Unit Isolation    If your job requires external vibration  isolation  two options are available   isopads or spring type isolators  Isopads  should be placed under the unit at  locations indicated on the factory   provided isolator sheet     Set the spring type isolators  Figure I PC   9  in position after the unit is removed  from skids before making electrical   piping  or duct connections  All units  require a minimum of four isolators per  unit  But some may require six isolators   depending upon unit options  Note  The  Trane Company strongly recommends  you consult a vibration specialist before  double isolating the unit  Double isolation  is not recommended     If you decide to externally isolate the unit   use spring flex  type CP isolators  The  spring number is marked on the outer  housing  See Figure I PC 9     To install external isolators  complete the   following procedure    1  Locate the isolators under unit base at  the locations indicated on the factory 
227. unit to dry completely before  putting it back into service    8  Ensure that contaminated material  does not contact other areas of the unit  or building  Properly dispose of all  contaminated materials and cleaning  solution     Determine the cause of any microbial  growth  mold  and take action to ensure it  does not reoccur     SCXG SVX01B EN    Owner    e TRANE       Supply Fan    Fan Drive   Perform the following procedures  according to the    Periodic Maintenance  Check List    on page 110     Disconnect electrical power  source to prevent injury or death  from electrical shock        1  Rotate the fan wheel to be sure it turns  freely in the proper direction and is not  rubbing on the fan housing  inlet  or inlet  guide vanes  If necessary  center the  fan wheel again    2  Check the position of both shafts  Fan  and motor shafts should operate  parallel to each other for maximum belt  and bearing life  Shim as necessary  under the motor or fan bearings to  obtain proper alignment    3  Check the fan motor sheave alignment  with straight edge or a tightly pulled  string  For sheaves of different widths   place a string in the center groove of    each sheave and pull it tight for a center  line  See Figure O M 2 on page 100 for  recommended torques    4  Once the sheaves are properly aligned   tighten sheave set screws to proper  torque    5  Check belt tension  Refer to the   Measuring BeltTension  section on  page 100    6  If required  adjust belt to the minimum  r
228. vided to allow monitoring  of reference enthalpy and are field  installed     If the unit has the ECEM board  econo   mizer operation enables when the  outside air enthalpy is less than 25 BTU s   Ib  default  adjustable 19 28 BTU S Ib     During occupied mode  the outside air  damper opens to 15   adjustable 0   100  at the HI  for ventilation purposes   Also  the ability to alter the outside air  damper position to compensate for VAV  supply air modulation is inherent in the  unit controls  and can be enabled by the  operator     If the unit does not have an ECEM board   it will economize when the O A tempera   ture falls below the O A economizer  setpoint     The mixing box fabrication is 16 gauge  galvanized steel  Opposed low leak  damper blades are fabricated from 16   gauge galvanized steel and rotate on  rustproof nylon bushings  A factory  installed 24V modulating spring return  actuator controls both damper positions     When outdoor conditions are not suitable  for economizer cooling  the enthalpy  control disables the economizer function    SCXG SVX01B EN    Owner    e TRANE       and permits the outdoor air damper to  open only to the minimum position     On water cooled units  compressor  operation lockout will not occur at low  ambient air temperatures  However   lockout will still occur via low condenser  water temperature     The outdoor air dampers drive fully  closed whenever the supply air fan is off   provided there is power to the unit     Comparative En
229. voltage     If the setpoint range is between 50 90 F   IPV    SP   50   0 1    0 5  SP     IPV   0 5  0 1    50    If the setpoint range is between 40 90 F   IPV    SP   40  0 8    0 5  SP     IPV   0 5  0 08    40    If the setpoint range is between 40 180  F   IPV    SP   40  0 029    0 5   SP     IPV   0 5  0 029    40    If the static pressure range is between  0 03 0 3 iwc    IPV    SP   0 03  14 8    0 5   SP     IPV   0 5  14 8    0 03    If the static pressure range is between  0 0 5 0                      SP  0 8    0 5   SP    IPV  0 8   0 5      GBAS Demand Limit Relay  Binary Input   The GBAS allows the unit to utilize the  demand limit function by using a  normally open  N O   switch to limit the  electrical power usage during peak  periods  Demand limit can initiate by a  toggle switch closure  a time clock  or an    ICS    control output  These contacts must    be rated for 12 ma   24 VDC minimum     When the GBAS module receives a  binary input signal indicating demand    limiting is required  a command initiates  to either partially  50   or fully  100    inhibit compressor and heater operation   This can be set at the HI using the setup  menu  under the    demand limit definition  cooling    and    demand limit definition  heating    screens  A toggle switch  time  clock  or building automation system  control output can initiate demand  limiting    If the cooling demand limit is set to 50    half of the cooling capacity disables when  the demand limit binar
230. wo  2  screws located on the right  hand side of the key pad     e  Carefully slide the key pad plate  upward from the bottom  releasing the  extruded hinge pin from its socket at  the top     f  Set the microprocessor aside until  mounting is complete     3  Remove the junction box knockout in  the back of the enclosure     SCXG SVX01B EN    Installation    e TRANE       Note  The top of the enclosure is marked     TOP       4  With the enclosure in the correct  position  align the mounting holes  around the knockout in the enclosure  with the screw holes in the electrical  handy box and secure with the  appropriate screws     5  Replace the microprocessor within the  enclosure as follows     a  Verify that the terminal block jumpers  are connected properly     b  Slide the extruded hinge pin at the top  left of the key pad plate into the hole  located at the top left hand side of the  enclosure     c  Slide the bottom of the plate into place   aligning the two  2  clearance holes  with the screw holes on the right  Install  the screws but do not tighten at this  time     Note  If the two screws are not installed as  called out in the previous step  hold  against the key pad plate while installing  the door in the next step  to prevent it from  faling out     d  Slide the extruded hinge pin at the top  left of the door into the hole located  under the bottom left side of the display     e  Install and tighten the hinge screw  located at the bottom left side of the  enclosure
231. y   programming      Each day can be programmed with  different times  temperatures  and  occupied status      Each day can be programmed with up  to four periods  Although four periods  are available each day  you can  program just one of the four    e Each period        be programmed for  occupied or unoccupied     To begin programming  follow these  steps       Determine which periods during the day  will be occupied and unoccupied       Write your daily schedule on the sheet  enclosed with the zone sensor       Enter your program by following the  steps below     To program time periods and setpoints   for a day      Press the program button to enter  program mode      Press the day button to select first day to  be programmed     To set the  begin  time for the first  period of the day  press the minus or  plus keys     To set the temperature setpoint for that  period  use f or 4      Press the program button to move to  the next period for that day     To program time periods and setpoints  for the next day  press the day button    e When finished  press and hold the  program button for two seconds to  return to the normal run mode     SCXG SVX01B EN    Note  Blank temperature settings may be  entered at any of the four daily periods   When a setpoint is left blank and in       occupied condition  the ZSM will default to  the last occupied setpoint  When a  setpoint is left blank and in an unoccupied  condition  the ZSM will default to the last  unoccupied setpoint     
232. y input closes  The  heating demand limit definition can only  be set at 100   unless the unit has field   provided two stage electric heat  In that  case  if the heating demand limit is set to  50   half or one stage of heating disables  when the demand limit binary input  closes  If the demand limit definition is set  to 100   all cooling and or heating will  disable when the demand limit input  closes     GBAS Diagnostics  Binary Outputs   The GBAS can signal up to five alarm  diagnostics  which are fully mappable  using the setup menu on the HI  These  diagnostics  along with the alarm output  on the RTM  allow up to six fully  mappable alarm outputs     Each binary output has a NO and NC  contact with a rating of 2 amps at 24VAC   The five binary outputs are factory preset  as shown on the unit wiring diagram  on  the unit control panel door   However   these outputs can be field defined in a  variety of configurations  assigning single  or multiple diagnostics to any output    For a complete listing of possible diagnos   tics  see the  ntelliPak  Self Contained  Programming Guide  PKG SVPO1B EN   For terminal strip locations  refer to the  unit wiring diagram for the GBAS     SCXG SVX01B EN    SCXG SVX01B EN    e TRANE       Owner       Table         6  GBAS Analog Input Setpoints                            Control Parameter Signal Range Setpoint Range   Occupied Zone Cooling Setpoint 0 5 to 4 5 vde 50 to 90 F    CV units only    Unoccupied Zone Cooling Setpoint 0 5 to 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
医薬品・医療機器等安全性情報NO322  2003 forester service manual quick reference index engine 2 section  WLA532 Access Point Hardware Documentation  Obrazkovy manual_T4A_en  Service manual - Kaeser Kompressoren    GeoMax Zenith10/20 - Geomax Calabria GPS e Stazioni Totali  Mode d`emploi  USER`S MANUAL  ZIMPL User Guide    Copyright © All rights reserved. 
   Failed to retrieve file