Home

Teledyne EHE User's Manual

image

Contents

1. Cuve thermal HOOL Q LA SENSOR PV 24V PSW N Capteur de MVO temp rature de l eau REMOTE CONNECTOR Connecteur distance LIMIT LIMIT BK _ Limiteur Limiteur DS N Ww PRESSURE SWITCH WATER Manostat eau W ELECTRICAL BK TS FUSE Fusible Rs Ne als lt 1 ie FIREMAN YBK Y SWITCH s gt 115V CONNECTION pire rh 60Hz Interrupteur Ce NN pompier R W TRANSFORMER COMB 7 Transformateur w FAN R Ventilateur a a combustion SIGN120 fo ere IGNITER Jek gt F2 0 Allumeur lt Ou 24V VENTURI PRES SWITCH L2 IND O Interrupteur a pression Pz IGN IGNITION diff rentielle W CONTROL BK Black Noir Y BK Commande W White Blanc f OTH d allumage BR Brown Brun nee ae BURNERICIMIT VX 257 OVAL FENWALL R Red Rouge imiteur de d j Limiteur du br leur BR OGND 05 33 Y Yellow Jaune va N N G Green Vert loo BR lo BRA CE y N Y BK MANUAL SINGLE USE FACTORY WIRED 24V RESET Uniservice FACTORY WIRED 115V Remise z ro DANS FIELD WIRED 115V Y J IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE HEATER MUST BE Y REPLACED APPLIANCE WIRING MATERIAL RATED FOR 105 C MUST BE USED GAS VALVE Soupage de gaz Figure 14 Wiring Diagram Hi E2 Pool Heater Page 10 NW TELEDYNE LAARS regardless of air density Good quality combustion and high efficiency are assured without spec
2. 3B Temperature Controls The Hi E2 heater has a dual temperature control which allows either of two different temperature settings to be selected with the rotary switch on the control panel The owner can set one control for normal use and the other for standby or one might be set for a pool and the other for a spa Setting the rotary switch to the middle position turns the heater off see Figure 25 Fi lexTemp ELECTRONIC TEMP CONTROL Hi E2 POOL NW TELEDYNE LAARS Figure 25 Temperature Control Panel The temperature controls on the Hi E2 cover a range from approximately 70 F 21 C to approximately 104 F 40 C Always use an accurate pool thermometer to test the pool water temperature Once the correct position for the control knob is determined use the TEMP LOK to keep it from going any higher by positioning the tab next to the knob and then tightening the screw Note that the heater should not be used to maintain pool or spa temperature below 70 F IMPORTANT The temperature controls cannot be calibrated in the field If the temperature control does not work shut down the heater and replace the temperature control DO NOT use the temperature control to shut the heater off Remove the access door and turn the main gas valve to OFF Hi E2 Page 17 GAS CONTROL KNOB SHOWN IN ON POSITION Figure 26 Gas Valve 3C Lighting and S
3. Before treatment its pH is typically in the 3 5 to 6 0 range Handling and disposal of condensate is not complicated but it must be done correctly to prevent problems or complaints A trap neutralizer assembly is provided with the heater to simplify installation This assembly is easily installed in the base of the heater Figure 11 illustrates its installation and the routing of drain tubes To install the condensate assembly first install the short length of 5 8 I D tubing on the barbed fitting on the bottom of the condensate collector Then drop the condensate tray into the opening in the base pan of the heater bending the 5 8 tubing as necessary to get the tube into the tray Readjust the 5 8 tubing so that its lower end is 1 4 3 8 above the bottom of the tray The tray can be positioned with the outlet fitting to the right as shown in Figure 11 or with the fitting to the left depending on the direction required for condensate disposal Connect the piece of 1 2 I D tubing to this outlet fitting and route it out of the heater through the hole in the side of the base panel This tube carries condensate to the drain If this disposal tube is routed to the left remove the plug button from the hole on the left side of the base panel and push it into the hole on the right side Connect the remaining short piece of 3 8 I D tubing to the barbed tee fitting in the tubing immediately in front of the blower Position this
4. fo fi CONDENSATE COMBUSTION BLOWER Figure 29 Combustion System Diagram properly adjusted Also be sure that the combustion air filter is clean and that there is no blockage of the vent or combustion air inlet See later section on combustion air filter service 4B Induced Draft Combustion System The Hi E2 pool heater has an advanced combustion system which makes it highly efficient and reliable This system is illustrated in Figure 29 A special corrosion resistant high speed blower pulls flow through the system and exhausts it to the outdoors Air is pulled into the system through a 3 combustion air supply duct when provided and through an air filter into a venturi The venturi functions much like an automobile carburetor venturi i e when air is forced through it a negative pressure is created at the venturi throat This negative pressure pulls gas through a metering orifice resulting in an optimal mixture of air and fuel gas The air and gas are thoroughly mixed in the venturi tailpipe pulled through a special burner and ignited in the combustion chamber Hot combustion products are then pulled through a highly efficient downward flow heat exchanger Combustion products are cooled below their dew point and condensate water is formed and drained away Flow then enters the blower where it is forced out of the heater at the vent terminal or through a vent pipe to the outdoors 4C Heater Component
5. investigate air flow per section 4F 3 Note that when the heater is operated with the gas valve off it will eventually lock out because the ignition control does not sense flame Normally there will be enough time to obtain the measurement 4F 2b Gas Pressure Offset Note that an equalizer tube is connected from a port on the front of the venturi inlet to the vent of the gas valve regulator This is a very important component which allows the regulator to track air pressure even when abnormal things occur such as blockage of the combustion air Before firing confirm that this tube and the venturi pressure switch tubes are in place and firmly connected Turn the heater off at the Flex Temp control Turn the gas valve knob back to On With the manometer connections remaining as they were See Figure 34 start the heater at the Flex Temp control When the burner fires the manometer should read 0 2 0 1 WC i e gas pressure is 0 2 WC less than venturi inlet pressure If the offset is incorrect adjust the gas pressure regulator to the correct pressure This can usually be done while the heater is firing but the burner may go off when the regulator seal cap is removed In any case the offset pressure measurement must be read when the heater is operating and the seal cap is firmly in place Note that a special tool is required to remove the regulator cap Figure 36 shows the gas pressure offset reading when a U Tube ma
6. Swimming Pool Energy Savings Tips Teledyne Laars suggests the following to help conserve fuel and minimize the cost of operating your pool heater without sacrificing comfort 1 Set the heater temperature control no higher than 78 F 26 C The American Red Cross maintains that the healthiest water temperature for swimming is 78 F 26 C is Be certain you are using an accurate pool thermometer because a variance of 4 degrees from 78 to 82 F 26 to 28 C will use as much as 40 more gas 2 Carefully monitor the water temperature of your pool in the summer time because heater usage can be reduced due to warmer air temperatures 3 Find the proper setting on the pool heater temperature control and use the TEMP LOK to discourage further adjustments 4 Setthe filter time clock to start the pump no earlier than 6 00 AM during the pool heating season This is the time when nightly heat loss stabilizes 5 Ifthe pool is only going to be used on weekends reduce the heater temperature control setting by 8 or 10 degrees during the week It should be reset to the 78 F 26 C level before expected usage keeping in mind to allow enough lead time for the water to reach the desired temperature 6 During the winter shut down the heater by following the lighting and shutdown instructions in Section 3A When on vacation for longer than a week make sure the heater is shut off at the temperature control panel 7 Where possible s
7. condensate water until vent drainage provides the seal see Section 2L Start Up and Adjustment The installer must be sure to take whatever measures are necessary to prevent property damage by condensate overflow If the heater location is such that this water can directly or indirectly damage a building furnishings or other property an overflow pan or other appropriate preventative measure should be provided 21 Gas Supply and Piping Before installing gas piping check the rating plate on the heater to be sure that the heater is for use with the correct available gas Make sure that gas supply pressure is adequate per the requirements in Table 4 Note that the system must be capable of providing these pressures while the heater is operating Supply Pressure Minimum Maximum Natural Gas 5 Inches WC 10 5 Inches WC 125 mm WC 265 mm WC LP Gas 11 Inches WC 14 Inches WC 280 mm WC 350mm WC Table 4 Gas Supply Pressure Requirements Gas piping must be large enough to provide the required gas flow rate without excessive pressure drop Table 5 specifies pipe sizes which will limit pressure drop to 0 5 In WC 125 Pa based on the National Fuel Gas Code ANSI 2223 1 Natural NatralGas LP Gas Model ee 50 100 100 200 0 50 50 100 100 200 0 15m 15 30m 30 60m 0 15m 15 30m 30 60m 220 a tear tvar ECS e ava Table 5 Required Gas Pipe Size Support gas piping properly s
8. section of the venturi casting A gas pressure port is provided on the outlet face right side of the gas valve To evaluate system operation requires accurate measurement at these ports A digital manometer known to be accurately calibrated is ideal Other instruments may be used but the positive negative nature of the readings must be very clear Also gas pressure offset measurements are at very low levels 0 2 WC and the instrumentation must be capable of determining it accurately 4F 2 Venturi System Checkout 4F 2a Unfired Venturi Differential Pressure Before firing the unit determine if air flow through the system is normal by operating the system with the gas valve turned off Connect the positive side of the manometer to the venturi inlet port which is at the bottom on the right side Connect the negative side of the manometer to the outlet pressure port of the gas valve See Figure 33 Turn the gas valve knob to Off Turn the heater on by selecting Pool or Spa at the Flex Temp control and adjusting the temperature setting high The blower will start immediately and the manometer will indicate the unfired venturi differential pressure This is the pressure difference created by airflow through the venturi It should be approximately 4 7 0 3 at sea level See Section 4F 5 for other elevations If the reading is normal proceed to gas pressure offset measurement per the following section If not
9. ETE E asservie nn A eet Meh ede 20 4B Induced Draft Combustion System 21 4C Heater Components and Their Operation 21 4D Combustion Air Filter 22 4E Electrical Trouble Shooting eseeeeeeeeeeeeeeeeeeen 22 4E 1 115V Electrical Power Supply 0 0 eee 22 4E 2 Control Circuit Trouble Shooting 23 4 E 2a Transformer 23 A 2b FuSe fn tent der nets T 23 4E 2c Fireman Switch and External Interlocks 24 4E 2d Limit Switches 00 0 eee eeeeeseeeeeeeeeeeteneeeeeeeeaes 24 4E 2e Water Pressure Flow Switch 24 4E 2f Temperature Control cecceeseeseeeeeeeteeeeeeeetens 24 4E 2g Venturi Pressure Switch 24 4E 2h Ignition Control 24 4E 2i Burner Limit Switch 25 4E 2j Vent Limit Switch eee eeeeeeeeeeeeeeeeeeaes 25 4E 2k Combustion Blower ccceeeeeeseeeeteeeeeeeeeeeaes 25 AE 21 Ignite sta cis ete in aan int nn 25 4F Venturi Combustion Flow System 25 4F 1 Pressure Measurement Ports 25 4F 2 Venturi System Checkout ccceeeeereeeeeeeeeeeee 26 4F 2a Unfired Venturi Differential Pressure 26 4F 2b Gas Pressure Offset 26 4F 2c Gas Orifice Differential 26 4F 3 Air Flow Investigation 27 4F 8a Combustion Air Flow 27 4F 3b Flow in Heater and Vent 28 4F 4 Fuel Gas Type and Gas Orifice Size 28 4F 5 High Elevation Opera
10. contact a Teledyne Laars representative A WARNING When the heater is fired for the first time the combustion chamber refractory binder material is driven out by the heat of the flame White smoke and or sharp odors may be emitted from the vent during this period Do not inhale combustion product fumes at any time and especially when these fumes are being emitted This burn in period will last only a few minutes A Caution The pressure switch should be adjusted to turn the heater off when the pump is off Setting the switch to close at too low of a flow can damage the appliance 2L 3 Condensate If there is no water in the condensate trap the heater s combustion blower will pull air into the lower drain hose and normal drainage of combustion condensate will not occur This water will accumulate to blower inlet level and will temporarily be blown out of the vent Eventually it will drain back to the tray Pry off cap to adjust Figure 23 Adjustment of Pressure Switch Hi E2 Page 15 To adjust the pressure switch proceed as follows see Figure 23 The pool filter must be clean before making this adjustment The heater does not have to be firing 1 Turn the Flex Temp switch to OFF and make sure the pressure switch is at its lowest setting This is done by rotating the adjuster counterclockwise as far as it will go 2 Start the filter pump and confirm by means of an
11. drowsiness which could lead to unconsciousness and subsequently result in drowning 3 Pregnant women beware Soaking in water above 102 F 39 C can cause fetal damage during the first three months of pregnancy resulting in the birth of a brain damaged or deformed child Pregnant women should stick to the 100 F 38 C maximum rule 4 Before entering the spa or hot tub users should check the water temperature with an accurate thermometer spa or hot tub thermostats may err in regulating water temperatures by as much as 4 degrees Fahrenheit 2 C 5 Persons with medical history of heart disease circulatory problems diabetes or blood pressure problems should obtain their physician s advice before using a spas or hot tubs 6 Persons taking medications which induce drowsiness such as tranquilizers antihistamines or anticoagulants should not use spas or hot tubs Prolonged immersion in hot water can induce hyperthermia Hyperthermia occurs when the internal body temperature reaches a level several degrees above the normal body temperature of 98 6 F 37 C Symptoms include dizziness fainting drowsiness lethargy and an increase in the internal body temperature The effects of hyperthermia include Unawareness of impending hazard Failure to perceive heat Failure to recognize need to leave spa Physical inability to leave spa Fetal damage in pregnant women Unconsciousness resulting in a danger of drowning 3F
12. ohmmeter that the pressure switch closes if the switch fails to close replace it with a switch which has a lower minimum setting 3 Turn Flex Temp switch to ON Heater should start 4 Pry out the top rubber dirt plug Use a 7 32 inch Allen wrench to turn the adjustment screw very slowly clockwise until the heater goes off 6 Slowly turn the pressure switch adjustment screw counter clockwise one quarter turn The heater should come back on 7 Check the adjustment by turning the filter pump OFF The heater should shut off immediately If it does not restart the filter pump and repeat Steps 6 and 7 Check the adjustment again 8 Return the pool temperature control to the desired temperature It may be necessary to repeat these steps to get a proper setting The switch must be set so that the heater will not fire unless the pump is running If a proper setting cannot be reached contact the factory service department 2L 6 Water Temperature Rise The Hi E2 pool heater has an internal bypass device which accommodates a wide range of water flow Its purpose is to assure that flow through the heat exchanger is adequate to provide high efficiency operation and prevent overheating even though flow through the filter system may vary Correct water flow should be confirmed upon start up of the heater and in most servicing situations If flow is not normal corrections must be made to the pool system If the system has an exte
13. pipe is to be 13 feet long with three elbows and the vent pipe is to be 9 feet long with one elbow Since the total is 22 feet and four elbows 4 pipe must be used Table 3 indicates that the maximum length of 3 pipe is 11 feet for a system with four elbows 2G 3d Combustion Air and Vent Pipe Installation The Hi E2 must be vented to the outdoors It must not be vented in common with any other appliance even if that appliance is of the condensing type Common venting can result in severe corrosion of the Hi E2 or of the other appliances or their venting or escape of combustion product gases through such appliances or vents Do not vent the Hi E2 to a fireplace chimney or building chase Combustion air ducting when provided must not be shared with any other appliance or with another Hi E2 Doing so may result in flow of air through the other appliances instead of directly from the outdoors The combustion air intake and vent outlet must be located exterior to the building and in the same pressure zone i e both through the roof or both through a side wall The vent terminal must be located in accordance with local codes as applicable and in accordance with the following 1 Locate the vent terminal so that it will not be damaged by pedestrians and other traffic and so that the discharge is not offensive The National Fuel Gas Code requires a through wall vent terminal be at least 7 feet 2 13 m above grade if located at a p
14. supply of propane gas to a heater intended for natural gas If there are no such fundamental problems identify which of the switches is open by temporarily connecting a jumper wire across its terminals Replace a defective limit switch Limit switch access is through the side cover panel on the side of the heater to which water pipes are connected Note that the limit switches have different trip points and it is important that replacements are correct The 150 F switch has a red dot on the side of the brass fitting and must be installed closest to the combustion chamber The 135 F switch has no dot and must be installed in the tapping closest to the water piping connections 4E 2e Water Pressure Switch Touch the voltage probe to point 5 which is the other terminal of the water pressure switch having a black wire is connected to it If there is no voltage the pressure switch contacts are open This is almost always due to a water flow deficiency the most common one being a blocked water filter It may be due to causes cited in the previous paragraph however and sometimes is due to blockage of the copper tube or mis adjustment of the switch Investigate thoroughly referring to the earlier section on Adjustment of Pressure Switch If there is no problem with the pool system or pressure switch adjustment replace the pressure switch 4E 2f Temperature Control Probe for voltage at point 6 which is the terminal of the vent
15. tray to prevent corrosion This material should be replaced once a year to assure its continuous benefit Replacement packages are available from Teledyne Laars or its representatives It is normal that a blue green deposit forms in the neutralizer This is caused by very small concentrations of copper ions present in the condensate By increasing the pH of the condensate the limestone causes this material to precipitate and be retained in the gravel 4H Major Component Service The venturi assembly the burner assembly and the heat exchanger tube assembly can be replaced if necessary but correct procedures and use of only factory provided parts are essential to assure satisfactory service and safe operation Sealing the system with the specified sealers and gaskets is especially important Contact the Teledyne Laars Service Department for information SECTION 5 Capacities and Dimensions 5A General Information NOTES 1 The Hi E2 is design certified by International Approval Services as a swimming pool heater under ANSI Standard Z21 56 for use in the United States and Standard CAN1 4 7 M85 for use in Canada 2 The Hi E2 pool heater is certified for use indoors or outdoors in the United States 3 The Hi E2 pool heater is for use with natural or liquefied petroleum gas Ratings apply to either fuel 4 De rating for elevation is not necessary because of the Hi E2 heater s special combustion system Reduced barometric p
16. tubing so that its bottom end is 1 4 3 8 above the bottom of the condensate tray This tube provides drainage for the vent duct and blower A package of limestone gravel neutralizer is provided with the condensate assembly Place this gravel in the tray after installing and properly positioning all tubes Be sure that a limestone pebble does not plug any of the tubes Place the cover on the tray when this is done It is important that there be no sagging sections of tubing to trap water Drainage to the trap and out of the trap to the drain must be assured by continuous downward routing of these tubes It may be necessary to elevate the heater to provide downward routing The outlet of the disposal tube must be open to the air If a gravity drain is not available a condensate pump must be provided in the field Suitable condensate pumps are available commercially at air conditioning equipment distributors Incorrect installation of the condensate assembly or tubing can result in overflow or waterlogging of the vent In normal operation water accumulates in the tray at the level of the outlet fitting and this provides a water seal which accommodates combustion system pressures Figure 12 illustrates the water seal Note that water is pulled up toward the condensate collector pan and is pushed down slightly by the vent blower drain If there is no water seal air rushes into the collector drain preventing normal drainage of
17. when heater is installed at elevations significantly above sea level For high elevation installations reduce the numbers in Table 6 by 3 per 1000 feet above sea level Minimum Maximum Minimum System Model Temp Rise Temp Rise Flow F C F C GPM 220 12 6 5 17 9 5 30 350 20 11 29 16 30 Table 6 Water Temperature Rise and Flow Rates Measured at Return Header In a system without external bypass it may be necessary to make changes If temperature rise is too low a manual bypass must be installed If temperature rise is too high there is inadequate flow possibly requiring a change to the piping system or a larger pump Before proceeding with either remedy verify proper heater operation Low gas input results in low temperature rise and vice versa A problem with the heater internal bypass assembly also affects measured temperature rise SECTION 3 Operating Instructions Lighting and shutdown instructions are posted inside the heater Page 16 NW TELEDYNE LAARS Figure 24 Temperature Rise Measurement at Return Header AAWARNING Do not attempt repairs on the gas control or appliance Tampering is dangerous and voids all warranties AAWARNING LP GAS To avoid possible injury fire and explosion read and follow these precautions and all instructions on this appliance before starting the heater LP propane gas is heavier th
18. 0 53 Blower Vent Duct Sleeve A R0308600 Key Model ORDER 54 Blower Vent Duct Clamp All R0308800 No Description No PARTNO 55 Vent Duct Assembly All R0303100 56 Vent Duct Heater Top Gasket or MAINTENANCE AND SERVICE COMPONENTS Heater Top Indoor Vent Collar Gasket Al R0309100 Limestone Gravel Condensate Neutralizer All R0306200 x PEA aT aP Om Oor Anau Grille Gasket Re Combustion Air Filter All R0308000 u Pepe ree EN 59 Indoor Vent Collar Not Shown Al R0307900 JACKET ASSEMBLY 60 Condensate Trap Assembly A R0303300 1 Base Panel 220 350 R0301703 05 61 Limestone Gravel A R0306200 2 Frame Support Assembly 220 350 R0301503 05 62 Condensate Trap Cover A R0213300 Back Panel 220 350 R0300703 05 3 ESR ier All R0300500 Venturi Hardware Kit Note 1 A R0322200 5 Right Side Panel A R0300800 Mixing Chamber Hardware Kit Note 1 A R0322100 6 Temperature Control Panel Assembly All R0301603 05 7 Door 220 350 R0301103 05 ELECTRICAL COMPONENTS AND CONTROLS 8 Inlet Outlet Header Panel Al R0301000 63 Transformer Al R0061100 9 Right Top Side Panel A R0300900 64 In Line Fuse Holder Assembly Al R0325600 10 Return Header Panel A R0300600 65 Ignition Control Al R0202900 11 Front Kick Panel 250 350 R0213403 05 66 Wire Harness Ignition Control Al R0302700 12 Top Panel 220 350 R0300103 05 67 Igniter Assembly All R0016400 68 Igniter Gasket Al R0205300 Jacket Hardware Kit Note 1 A R0302100 Ber ead Blak Ai R0301300 Internal Hardware Kit Note 1 A R0302500 70 High Limi
19. ARNING Do not store any chemicals cleaners or other corrosive material near combustion air openings or in the room Avoid location of dryer vents in the vicinity of combustion air openings Failure to prevent corrosive materials from mixing with combustion air can result in reduced heater life and unsafe heater operation 2G 3 Two Pipe Installation Direct Vent This section specifies installation requirements for combustion air and vent piping for two pipe installations A two pipe system provides isolation of the Hi E2 combustion system from the space in which the heater is installed It has not only a vent pipe but also a combustion air pipe to provide air directly from the outdoors Research studies have shown that contaminants which may corrode internal heater parts are typically at much lower levels in outdoor air than in air from indoors Figure 4 Connection of combustion air pipe to heater 2G 3a Connection of Combustion Air Pipe A collar for combustion air pipe connection is provided in the heater at the inlet of the filter box As shown in Figure 4 the combustion air pipe is routed through the side of the heater to the filter box connection Remove the cover plate from the left side panel to provide access for the air pipe 2G 3b Piping Materials Vent piping must be corrosion resistant because combustion condensate is usually present on its internal surfaces Only the following
20. H0205000A Installation and Operating Data eee FOR YOUR SAFETY This product must be installed and serviced by authorized person nel qualified in pool spa heater installation Improper installation and or operation can create carbon monoxide gas and flue gases which can cause serious injury property damage or death Improper installation and or operation will void the warranty Installation and Operation Manual Hi E2 Model EHE Gas Fired Pool and Spa Heater A WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier oY TELEDYNE LAARS An Allegheny Teledyne Company TABLE OF CONTENTS SECTION 1 General Information 1A INTOGDUCHION Sst ss eter niet Rees 1 1B Description 121 8 tienne 1 1C Warranty ieee ee nf menant tnt 1 SECTION 2 Installation Instructions 2A General Requiremen
21. OPER SERVICE HAZARD The Hi E2 pool heater incorporates unique design features Incorrect service of this heater can result in personal injury or damage to property To avoid such hazards the heater must be serviced only by a qualified professional service technician 4A General A qualified professional technician must service the Hi E2 pool heater using Teledyne Laars service procedures Before calling for service however the owner should check for obvious problems The other components in the pool system including pump filters and strainers water valves gas supply electrical power and time clocks have an effect on heater operation Confirm that the Flex Temp heater control is set to pool or spa and that the corresponding temperature knob is set high enough to make the heater operate Make sure the pump is operating that the filter and strainers aren t clogged that there are no mis positioned water valves that the gas or electric power supplies aren t shut off and that time clocks are Hi E2 Page 21 BURNER AIRIGAS MIXTURE wv GAS ORIFICE GAS VALVE WITH NEGATIVE PRESSURE REGULATOR GAS ea AE iN A i VENTURI 6 PRESSURE EQUALIZER SWITCH rhe TUBE N el is A N 7 tl Ke L AIR IN gt 2 AIR FILTER j CONDENSATE ZA Anse NZ V EXHAUST 5 F vA
22. agging Sagging can trap condensate water and block the vent ee we NX 4 N if a A K WN S V we NN ria Se ee j NK A ou a Fd en A N PVC Adapter when required yA LES a is cae LA 4 PVC Pipe Field provided Clamping Connector with Neoprene Nitrile or EPDM Sleeve Figure 7 Indoor Vent Connection Hi E2 Pool Heater Special Insect Screens Installed See Fig 10 Combustio Grade level lt _ or normal snow to maximum ai level Figure 8 Vent and Combustion Air Terminals at Exterior Wall Hi E2 Page 7 Vent Exhaust Insect Screens Pip Installed Elbow See Fig 10 Combustion Plumbing vent roof boot A Maximum snow accumulation level plus 12 Figure 9 Vent and Combustion Air Terminals at Roof Vent Exhaust Combustion Air Pipe Install special _ insect screen at end of pipe inside coupling or elbow Cut to size as necessary Drain Blower Drain Trap Neutralizer Figure 11 Condensate Drainage Components Figure 10 Installation of Insect Screens Both combustion air and vent piping joints must be sealed Metal combustion air pipe joints should be fastened with screws and sealed with permanent sealer or tape Plastic vent pipe joints must be made with solvent cement listed for
23. allation Condensate drainage should be observed routinely and if necessary the flow ways should be cleaned In normal operation condensate drains from the condensate collector behind the combustion fan A 5 8 I D drain tube conducts this water into the condensate trap neutralizer where a water seal prevents room air from being pulled into the system A smaller amount of condensate may drain from the vent duct and blower The water seal of the trap prevents vent gases from being discharged into the room See Figures 11 and 12 in the Condensate Disposal section of the installation instructions During start up condensate from the collector cannot reach the trap unless the water seal is established This can be done by pouring water into the trap The heater will self prime by driving water into the vent outlet from which it will eventually drain into the trap However it is better to avoid this by manually priming the trap Hi E2 Page 29 If condensate is not draining from the system check for improper routing of the drainage tubes or blockage in the drainage system Tubing must be installed with a continuous fall in the direction of condensate flow Sags may trap water defeating the intended operation Check for blockage by disconnecting drainage tubes at the collector and the vent diffuser Probe these openings with a tool or wire hook to dislodge any debris Limestone gravel neutralizer is required in the condensate
24. an air and will remain at ground level if there is a leak Before lighting sniff at ground level If you smell gas follow these rules 1 DO NOT light matches DO NOT turn electric lights or switches on or off in area DO NOT use an electric fan to remove the gas from area 2 Shut off gas at LP tank 3 Telephone gas company and fire department for instructions Give your name address and phone number If your LP tank runs out of fuel turn off gas at the appliance After the tank is refilled the appliance must be re started according to the instructions located on the inside of the door 3A Start Up Procedure With any new pool or spa installation run the filter pump with the heater off long enough to completely clean the water This removes any installation residue from the water Clean the filter at the end of this operation before starting the heater Do not operate the heater unless the pool is properly filled with water When raising the temperature of water in a cold pool remove all time clock settings This lets the filter system and heater operate continuously until the water reaches the temperature setting on the thermostat When that happens the heater will shut off automatically but the filter pump will keep running ACaution Keep all objects off the top of the heater and do not obstruct louvre openings in heater sides Blocking ventilation air flow may damage the heater and void the warranty
25. anometer to the collector pressure tap as shown in Figure 38 leaving the positive side open to ambient This requires a pressure tap with a 1 4 NPT thread When the heater is operating the pressure at this location should be about 3 5 0 5 WC less than ambient for a model 220 and 2 8 0 5 WC less than ambient for a model 350 If a greater reading is observed i e more negative flow is restricted within the heater most likely at the burner or the heat exchanger If the reading is substantially less i e less negative the combustion blower is not operating properly or flow is blocked after the blower possibly in the vent Correct any such problems and verify normal operation by returning to the venturi system checkout procedures Pressure readings will be less if the heater is located at an elevation significantly above sea level 4F 4 Fuel Gas Type and Gas Orifice Size The Hi E2 venturi combustion system requires only a gas orifice change to change from natural to propane gas or vice versa Required venturi system and gas pressures are the same for either gas Required gas orifices are listed in the replacement parts list Teledyne Laars configures its heaters for natural gas with 0 60 specific gravity and 1035 Btu Ft or for propane gas with 1 52 specific gravity and 2500 Btu Ft3 Consult your Teledyne Laars representative if the available gas is substantially different 4F 5 High Elevation Operation The venturi combusti
26. at point 11 touch the free probe to point 2 This is the terminal block screw attached to the red wire from the in line fuse and absence of voltage indicates a defective fuse If there is no voltage inspect the rest of the wiring to be sure that there is no short such as contact of a terminal with the heater chassis or another terminal Correct any such condition and replace the fuse Page 24 NW TELEDYNE LAARS 4E 2c Fireman Switch and External Interlocks Probe for voltage at point 3 the other connection of the terminal block which has a white wire connected to it If there is no voltage the time clock switch or other external interlock may be mis adjusted mis connected or defective Correct this external problem 4E 2d Limit Switches Probe for voltage at point 4 which is the water pressure switch terminal with the white wire connected to it This switch is mounted on the end of a copper tube and is about 2 in diameter Absence of voltage at this point indicates that one of the limit switches is open This is normally due to excessive water temperature which should be thoroughly investigated before replacement of limit switches Water flow deficiency may be due to obvious problems such as a defective pump or blocked water filter Alternatively it may be due to overfiring or to a problem with the water piping or the heater s internal bypass control Overfiring might be a result of an incorrect gas orifice or
27. at subject to Page 14 NW TELEDYNE LAARS continued water flow and satisfactory operation of the system 9 When the FlexTemp control stops calling for heat the ignition control shuts off the gas valve and the flame goes out 10 The ignition control continues to operate the combustion blower for a post purge period after which it is turned off The process is repeated upon the next call for heat If ignition is unsuccessful or if the flame fails during normal operation the ignition shuts off the gas valve It imposes a post purge and two more ignition cycles and it shuts down the system if ignition is not achieved in three cycles 2L 2 Start up Before operating the heater pour water into the condensate tray and verify that it drains properly Confirm that pool water is flowing normally through the pool system and equipment Start the heater in accordance with the Operating Instructions section of this manual with particular attention to the lighting and shutdown instructions and temperature control operation The heater may not start on the first try Air in the gas line or other start up situations may cause it to recycle It will lock out if ignition is not achieved in three attempts To provide three additional attempts turn the pool spa selector switch off and then back on When the heater starts immediately feel the outlet header of the heater to confirm that there is adequate water flow The header
28. d by chemical concentration is not covered by the Teledyne Laars Warranty See Table 7 for guidelines on pool water chemistry DRAIN CHANGEOVER VALVE 3WAY VALVE NE PUMP FILTER MANUAL BY PASS _ SKIMMER A8 FROM SKIMMER MAIN POOL RETURN BALANCING VALVES AND DRAIN 3 WAY MANUAL BY PASS DETAIL MANUAL BY PASS IS USED WHEN FILTRATION RATE EXCEEDS 125 GALLONS PER MINUTE Figure 20 Typical Water Piping Hi E2 Page 13 Method For Installing Any Threaded Pipe AR Use Plastic lt Sleeve For Nonthreaded Pipe or Tube Discard Plastic Sleeve Figure 21 Piping to Heater Figure 22 Pressure Relief Valve Installation IMPORTANT If an automatic chlorinator is being used equip the chlorinator with an anti siphoning device so that chlorine will not siphon into the heater after the pump shuts off Wire an electric chlorinator so that it cannot operate unless the filter pump is running If the chlorinator has an independent clock control synchronize it with the filter clock If the chlorinator is equipped with its own pump install it so that it introduces the chlorine downstream from the heater and if possible below the level of the heater outlet fitting 2L Start up and Adjustment 2L 1 Normal Operation The Hi E2 pool heater operates automatically It provides heat in response to the sel
29. e copper tubing from the pressure switch fitting see Figure 27 6 Cover the vent grille so that snow will not accumulate in the combustion blower where it may freeze To reactivate the heater in the spring have a qualified professional technician reassemble the heater as follows 1 Attach the pressure switch fitting to the copper tubing see Figure 27 2 Tighten the drain plugs in the headers 3 Clean the condensate drainage system and condensate trap 4 Replace the combustion air filter Uncover the vent grille 6 Turn on the main supply gas cock outside the heater jacket 7 Turn on the heater according to the lighting and shutdown instructions inside the top cover Page 19 Right Side Remove Plug Figure 27 Water Header Draining 3H Periodic Inspection AAWARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide or flue gases which could result in severe injury property damage or death 3H 1 Owner Inspection Teledyne Laars has designed and constructed the Hi E2 heater to provide long performance life when installed and operated properly under normal conditions The following basic guidelines should be maintained 1 Keep the top of the heater clear of all debris and make sure there is no collecting of flammable materials leaves paper etc around or beneath the heater 2 Keep the pool heat
30. ector switch and temperature settings on the FlexTemp control panel on the front of the heater The heater has internal controls to sense adequate water flow and to handle any abnormal condition Normal operation is as follows 1 The pool spa system filter pump provides water flow A pressure flow switch in the heater detects water flow and enables the FlexTemp control to operate the heater If the recommended fireman switch has been provided it must also enable operation 2 Ifthe FlexTemp selector switch is set to Pool or Spa and if the water temperature is not warm enough the FlexTemp control signals the combustion system to start 3 The ignition control starts the combustion blower 4 When the venturi pressure switch detects combustion air flow and when a suitable pre purge time has been allowed the ignition control energizes a hot surface igniter 5 The igniter is allowed to reach ignition temperature at which it glows bright red orange This is visible through the combustion chamber view port 6 The gas valve is opened and gas flows into the combustion air The gas air mixture flows through the burner into the combustion chamber It is ignited by the igniter 7 The ignition control electronically senses successful ignition by flame rectification and the gas valve is allowed to stay on The igniter is de energized 8 The heater operates for as long as the FlexTemp control demands he
31. ed earlier in this manual 9 Burner Temperature Limit Switch This is a single use switch which detects abnormal burner temperature It is a disc type switch which is held against the burner plenum by a sheet metal bracket It has the appearance of an automatic reset switch in that it has no reset button However it will reset only if cooled to 31 F and therefore will not recycle The burner limit switch prevents or interrupts burner operation if the burner plenum becomes too hot 10 Vent Limit Switch The vent limit switch protects the vent system from excessive exhaust temperature It is located on the vent diffuser above the combustion blower It interrupts burner operation if temperature becomes too hot for the plastic materials used to vent the heater See the earlier section entitled Start up and Adjustment for the normal sequence of operation 4D Combustion Air Filter The combustion air filter is a rectangular foam filter located in a box near the bottom of the control compartment The filter removes lint and large scale dust particles to prevent blockage of the burner media Figure 30 Air Filter Replacement The filter should be replaced annually in normal service Heavy use of the heater or operation in adverse environments may dictate more frequent replacement however It can be removed through the bottom of the filter box as illustrated in Figure 30 Remove the wing nuts retaining the botto
32. er area clean and free of all combustible materials gasoline and other liquids and vapors 3 Do not use the heater if any part has been under water Immediately call a qualified professional technician to inspect the heater and replace any part of the control system and any gas control which has been under water 4 Check for spider webs and other debris at the combustion air inlet and vent outlet especially at spring start up Page 20 NW TELEDYNE LAARS 3H 2 Professional Inspection Inspection by a qualified professional technician performed at least once a year by a qualified professional technician are required to keep the heater operating efficiently through the years The following basic checks should be performed 1 Inspect the condensate disposal system to be sure that condensate flows freely 2 Replace combustion air filter 3 For heaters installed with combustion air or vent piping inspect screens at the inlet or outlet of these pipes Clean screens as necessary to assure free flow See illustrations in combustion air and vent pipe installation section 4 Make sure that the pressure switch operates properly by shutting the filter pump off and ona few times The burner should go off immediately after the pump stops An ignition sequence should start shortly after the pump is turned back on 5 Make a visual check of the main burner flame The flame can be seen in a mirror viewport arrangement
33. f of purchase model number serial number and date of installation The installer will contact the factory for instructions regarding the claim and to determine the location of the nearest designated service center If the dealer is not available you can locate a service center in your area by visiting www jandy com or by calling our technical support department at 707 776 8200 extension 260 All returned parts must have a Returned Material Authorization number to be evaluated under the terms of this warranty H0205000A d i i A Water Pik Technologies Company 6000 Condor Drive Moorpark CA USA 93021 707 776 8200 Fax 707 763 7785 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 Fax 905 844 2635 Litho in USA Water Pik Technologies 0401
34. helter the pool from prevailing winds with well trimmed hedges or other landscaping cabanas or fencing 8 Always use a pool cover when practical Besides providing a valuable safety feature a pool cover will reduce heat loss conserve chemicals and reduce the load on filter systems Hi E2 3G Seasonal Care 3G 1 Spring and Fall Operation During periods when the pool is only going to be used once in a while turn the temperature control to the MIN setting This prevents the pool from becoming chilled yet still requires the least amount of time to raise the water back up to swimming temperature If the heater is not going to be used for a long period of time shut it down completely following the instructions in Section 3C 3 Shutdown or the lighting and shutdown instructions posted inside the heater 3G 2 Winterizing If you don t plan to use the pool or spa over the winter and your area is subject to freezing temperatures have a qualified professional technician perform the following steps to protect the heater 1 Shut off the heater s gas valve according to the lighting and shutdown instructions 2 Shut off the main supply gas cock outside the heater jacket 3 Completely drain the heater before the first frost To drain the heater remove the side panel and remove the drain plug see Figure 27 4 Grease the threads of the drain plug and return it to the manifold but do not tighten 5 Disconnect th
35. her loads Hi E2 Page 23 Electronic Temp Control Water Temp Sensor Pressure Switch Water Y Y BK Switch 115V 60Hz Connection Blower Gas Valve Ignition Control Figure 31 Wiring Diagram with Test Points such as air conditioning compressors or to an electric utility company problem Arrange for correction of the voltage as appropriate 4E 2 Control Circuit Trouble Shooting The heater controls are in a 24V 60 Hz circuit with operating and safety controls basically arranged in a series circuit Trouble shooting is done by probing for voltage at various points in the circuit to determine which component is preventing operation Check points are indicated on Figure 31 The recommended procedure steps through the circuit in a sequential way but verifying voltage at any of the numbered points confirms that all prior components are OK Experienced technicians may be able to shorten the process by going directly to one of the intermediate test points 4E 2a Transformer Attach one lead of the voltmeter to the transformer terminal with a yellow wire attached to it which is point 11 on Figure 31 This lead can be left in place for most of the testing Touch the free lead of the meter to the transformer terminal with a red wire point 1 The meter should show 20 28 volts If there is no voltage replace the transformer 4E 2b Fuse Leaving the common voltmeter lead in place
36. hutdown 3C 1 Lighting the Heater Lighting and shutdown instructions are listed on the label attached to the inside of the service door and also on the inside of the control compartment door Lighting instructions are as follows 1 Turn off all electrical power to the heater at the main junction box 2 Open the control compartment door and turn the gas valve to OFF 3 Turn the rotary switch on the temperature control panel to OFF 4 Wait 5 minutes before trying to start the heater SA Turn the gas valve control knob counterclockwise to ON see Figure 26 Replace the control compartment door Turn on electrical power to the heater Turn on the filter pump SOP ee EE ON Turn the rotary switch to either SPA or POOL Set the temperature control to the desired setting The ignition control automatically lights the burner when the thermostat calls for heat 10 Set the time clock if one is installed 3C 2 Shutdown Complete shutdown instructions are as follows 1 Set both temperature controls to the lowest setting 2 Turn the rotary switch on the control panel to OFF 3 Turn off all electrical power to the heater at the main junction box 4 Open the control compartment door and turn the gas valve knob clockwise to OFF 5 Turn external gas valve off 3D Water Chemistry 3D 1 Pools The mineral content of swimming pool water increases daily due to natural evaporation and the addition of sanit
37. ial adjustment or changes to the heater 2J Electric Wiring 2J 1 Electrical Power The Hi E2 requires electrical power from a 115V 60 Hz source Wiring connections must be made exactly as shown in the wiring diagram See Figure 14 Grounding must be provided as required by the prevailing electrical code Connect wiring inside the junction box which is on the right side of the heater and is accessible through the door opening Line voltage connections must be made within this box A labeled green grounding screw is provided in the junction box for a grounding wire see Figure 15 Wiring should include a means to prevent operation of the heater when there is no water flow This is typically done with a time clock Fireman s Switch as discussed in Section 2J 3 ATTACH GROUNDING WIRE TO GREEN GROUNDING SCREW Figure 15 Field Wiring Connections TO LIMIT SWITCHES TO LIMIT SWITCHES FIELD PROVIDED WIRING WHITE FACTORY D INSTALLED WIRE T LOW VOLTAGE SWITCH TIME CLOCK WHITE HEATER WIRING BEFORE MODIFICATION MODIFIED HEATER WIRING WITH TIME CLOCK INSTALLATION Figure 16 Typical Time Clock Wiring Terminal Block Figure 17 Terminal Block for Fireman s Switch or Remote Control Wiring 2J 2 Bonding The National Electrical Code and most other codes require that all metallic components of a pool structure including reinforcing steel metal f
38. in the upper part of the heater The flame should be light blue and the burner surface should be dark with only a few glowing fibers see Figure 28 6 Inspect the gas and electronic controls including the following a High temperature limit switch b Water pressure switch c Venturi pressure switch d Automatic gas valve e Burner temperature limit switch f Ventlimitswitch g Temperature control h Control circuit fuse 7 Perform a temperature rise test in accordance with Section 2L 8 If the heater is equipped with a pressure relief valve clean any accumulated corrosion and make sure that water runs freely through it 9 Inspect the outside of the combustion chamber and burner for corrosion and indication of improper operation 10 Regularly inspect electrical controls for deterioration Repair and replace as necessary NOTE Keep this manual in a safe place for future reference by you and your professional technician when inspecting and servicing the heater Figure 28 Burner Flame visible near top of heater in mirror SECTION 4 Maintenance and Service WARNING SERVICING SAFETY Some of the servicing procedures for the Hi E2 pool heater are hazardous because they involve fuel gas electricity moving parts and procedures which require testing or temporary bypass of safety controls For this reason the heater must be serviced only by a qualified professional service technician IMPR
39. inging air directly to the heater s combustion system Section 2G 2 specifies requirements for provision of combustion and ventilation air for one pipe installations Section 2G 3 covers two pipe installation An important consideration in selecting one or two pipe installation is the quality of the combustion air Indoor air is sometimes contaminated with various household or pool sanitation chemicals which can cause corrosion in the heater combustion system Unless the indoor air is known to be free of these materials two pipe installation is strongly recommended 2G 1 Preparation of Heater For Indoor Installation If the Hi E2 is to be installed indoors its exhaust discharge grille must be converted to an exhaust pipe configuration The necessary vent collar gasket and screws are shipped packaged within the heater The 5 Figure 3 Vent collar assembly for indoor installation Page 4 NW TELEDYNE LAARS conversion can be done quite simply as follows see Figures 2 and 3 1 Remove the vent exhaust grille by removing the four screws which retain it The grille its gasket and the screws may be discarded 2 Place the vent collar gasket on the top of the heater aligning its center hole and screw holes with those in the top of the heater 3 Place the vent collar over the gasket and fasten it in place with the screws and lockwashers provided Be sure that all components a
40. ittings and above ground equipment be bonded together with a solid copper conductor not smaller than a number 8 wire The heater along with pumps and other such equipment must be connected to this bonding grid A special labeled bonding lug is provided on the right side of the heater to accommodate this requirement 2J 3 Auxiliary Time Clock Wiring If a time clock is provided to control the pool filter pump it should have a separate low voltage Fireman s switch for the heater Route the heater s 24 VAC control circuit through this switch as shown in Figures 16 and 17 To do this remove the jumper from the terminal block in the heater control compartment Connect two wires to this terminal block and route them to the Fireman s switch at the time clock Provide wiring of at least 18 gauge with insulation at least 3 64 thick and having a temperature rating of at least 90 C 2J 4 Remote Operation The Hi E2 pool spa heater controls can be wired for remote operation Teledyne Laars and Jandy remote controls are available through the local dealer or distributor The CS 02 remote control switches between the two temperature controllers and turns the heater on and off The CS 04 has the same controls as the CS 02 and includes a remote temperature controller An interrupt On Off type remote control can be connected by removing the jumper wire on the terminal block located in the control compartment see Figure 17 and connecti
41. izing chemicals If the mineral concentration in the pool gets too high the excess minerals will deposit on the walls of the pool in the filter system and in the heater tubes It is important to keep the pH factor of the pool water between 7 4 and 7 6 See Table 7 for guidelines on other chemical measurements 3D 2 Spas The proper chemical balance in spa water is more critical than in a swimming pool heater operation Due to the spa s size high water temperature and heavy usage chemical values in a spa can vary greatly This chemical imbalance can result in unsanitary water conditions and affect the life of the heater 3D 2a Spa Water Chemistry Maintaining safe water conditions in a spa can only be done by regular water changes and the proper addition of sanitizing chemicals Kits are available from your local pool supply dealer for making the various tests for mineral content One of these kits will detect copper in the system This is usually a warning that corrosion is taking place possibly due to a low pH value combined with other chemistry problems The condition can be corrected by changing the spa water and closely monitoring the pH factor and chemical properties of the water see Table 7 Test Recommended Level Free Chlorine or 1 0 to 3 0 ppm Total Bromine 2 0 to 4 0 ppm pH 7 2t07 6 Total Alkalinity TA 100 to 150 ppm Calcium Hardness CH 200 to 400 ppm Langelier Saturation Index SI 0 5 to 0 5 Cya
42. lly operating heater the pressure will be 0 2 to 0 6 WC less than the ambient pressure The reading for a model 220 with clean filter and no combustion air duct will be near the low end of this range For a model 350 with clean filter and no combustion air duct the reading will be near the middle If combustion air is ducted to the heater the reading will be near the high end If an excessive reading is observed i e more negative flow is probably restricted by a dirty filter or blockage in the combustion air supply system To Venturi Inlet Service Port a 0 2 WC 4 To Gas Valve Service Port Figure 36 Gas Pressure Offset Measurement with U Tube Manometer iy Figure 34 Gas Pressure Offset Measurement Figure 37 Venturi Inlet Pressure Measurement Page 28 NW TELEDYNE LAARS Shh Figure 38 Collector Pressure Measurement Correct any such problems and verify normal operation by returning to the venturi system checkout procedures Pressure readings will be less if the heater is located at an elevation significantly above sea level 4F 3b Flow in Heater and Vent If the venturi inlet pressure reading is normal or less than normal flow may be blocked within the heater or in the exhaust venting or the combustion blower may be operating below standard To evaluate this connect the negative side of the m
43. m panel and remove the panel Grasp the bottom edge of the filter and pull it downward and to the right Replace it only with the specified part available from a Teledyne Laars representative Push the replacement filter into the tracks at the front and rear of the filter box 4E Electrical Trouble Shooting This section describes procedures for checking the electrical power and control components of the heater one at a time and in the order they appear in the control circuit These procedures require a Volt Ohm meter with 0 150 VAC VAC range and 0 1000 Ohm resistance range Figure 31 shows the power and control circuits and where to take measurements Location numbers in circles have been added and will be referenced in the following sections As stated at the beginning of this manual some of these procedures are hazardous Only a qualified service technician should service the heater 4E 1 115V Electrical Power Supply The electrical components of the Hi E2 pool heater are designed to operate with supply voltage ranging from 103V to 126V at 60 Hz Measure supply voltage at the hot and neutral wirenut connections in the heater electrical junction box identified as points A and B on the wiring diagram If no voltage is present correct this external to the heater Circuit breakers time clock settings or similar devices may be the problem Voltage outside of the above range may be due to poor wiring poor connections ot
44. materials are acceptable for vent piping PVC Class 100 Class 125 or Schedule 40 CPVC Schedule 40 29 4C Stainless steel venting materials listed for venting of condensing gas fired appliances 29 4C is a trademark of Allegheny Teledyne Hi E2 Page 5 Total Length 42 Total Elbows 5 4 2 Vent Combustion Air Pipe 7 Ni Comb Air Vent Total Length 13 9 22 Elbows 3 1 4 EHE220 Figure 6 Two pipe installation Combustion air piping may be single wall galvanized steel pipe or any of the above materials 2G 3c Size and Length of Combustion Air and Vent Piping Piping for combustion air and venting must be large enough to avoid restriction of the heater combustion system Pipe diameter number of elbows and length of pipe determine how much it restricts flow to or from the heater Also a large heater requires larger pipe than a small heater because it operates with higher flow of combustion air and exhaust products Table 3 specifies the allowable length of piping for various situations The following examples illustrate use of table 3 1 A Model 350 heater is to be installed in a one pipe system see Figure 5 The vent pipe is 42 feet long and has five elbows Per Table 3 5 piping must be used Only 16 feet of 4 vent pipe would be allowable 2 A Model 220 heater is to be installed in a two pipe system see Figure 6 The combustion air
45. means to sense ignition and flame condition so that unburned gas will not escape After the burner is shut off it continues blower operation to provide a post purge period Page 22 NW TELEDYNE LAARS 5 Igniter The hot surface igniter is a ceramic element which becomes very hot when electrical power is applied to it It functions both as an igniter and as flame sensor As a sensor it is the electrode through which the ignition control detects rectification of current passed through the flame Inadequate rectification indicates an unsatisfactory flame condition The ignition control responds to the flame signal provided by the ignitor 6 Venturi Pressure Switch This switch verifies that air is flowing through the combustion system by sensing pressure reduction at the venturi throat relative to pressure at the venturi inlet It shuts off the heater if air flow is inadequate 7 Limit Switches Two limit switches prevent excessive water temperature one within the heat exchanger and one for water leaving the heater If either senses excessive temperature burner operation is interrupted 8 Water Pressure Switch This control senses whether or not water is available to the heater by measuring back pressure inside of the heat exchanger If the pool water pump fails or the water filter is blocked the pressure switch prevents operation of the burner It can be affected by the installation conditions as discuss
46. mical Feeders 12 2L Start Up and Adjustment 13 2L 1 Normal Operation 13 2L 2 StartUp vis eme ane QU An hast 14 2L 3 Condensate iiinis iise ii 14 2L 4 Gas Pre SUr isnan iaaeao a ea uatan reiti 14 2L 5 Adjustment of Water Pressure Switch 14 2L 6 Water Temperature Rise 15 SECTION 3 Operating Instructions 3A Start Up Procedure ccceeceesceeseeeeeeeteeeeeeeteeees 16 3B Temperature Controls 16 3C Lighting and Shutdown sssseeeeeeeeeeeereeeeeeeeeee 17 3C 1 Lighting the Heater ceeeceeeeseseeeeeteeeeneeeaee 17 3C 22 SIMULA OWN remis hante tuer fardeau 17 3D Water Chemistry ccceecceesceeeeeeeeeeeeeeeseeeeneeteas 17 3D 1 POOIS SES eet ah RAR An NA tk 17 3D22 SPAS AN a N E epee ten 17 3D 2a Spa Water Chemistry 17 3D 2b Water Changing c eeceeeeeeseeeeeeeeeeeteeeeeeeeaes 17 3D 26 COOS Oa ae a ts ner an a aao her sine 18 3D2d Testing in ed a ae ne ee 18 3E Spa Hot Tub Safety Rules 18 3F Swimming Pool Energy Saving Tips 18 3G Seasonal Care eeceecceeeceeseeseeeeeeeeseeeeseeeeeeteaees 19 3G 1 Spring and Fall Operation 19 3G 2 Winterizing re 19 3H Periodic Inspection 19 3H 1 Owner Inspection eecceeeceeeeeeeeeeeeeeeneeeeaeeeneetees 19 3H 2 Professional Inspection 20 SECTION 4 Maintenance and Service 4A
47. mit switch 4E 2j Vent Limit Switch Probe for voltage at point 10 which is the gas valve terminal having a brown wire connected to it As in the preceding case this terminal will have voltage present only during a trial for ignition or during normal operation If voltage is not found the vent limit switch is open indicating that the exhaust temperature has been too high Normal vent temperature is between 100 F and 140 F Excessive temperature might be due to excessive water temperature or overfiring of the system Investigate water temperature and possible water flow deficiency Confirm that the heater is equipped for the correct fuel gas especially that propane gas is not being provided to a heater configured for natural gas To confirm correction of the problem re set the switch by pushing the red button If vent temperature is normal and the switch will not allow operation replace it WARNING The combustion blower the igniter and some terminals of the ignition control utilize 115V power and require appropriate servicing precautions Note that wires and terminals of these components may be hot even when the component is not operating 4E 2k Combustion Blower The combustion blower operates when it is provided with 115V 60 Hz power Confirm this by connecting the voltmeter between the neutral wirenut and point C which is the terminal marked F2 on the ignition control Unless the system is in l
48. n Clearance Requirements NOTE See Outdoor Installation section regarding roof overhang These clearances are the minimum acceptable Whenever possible larger clearances should be provided to assure adequate room for service operations Note that gas piping must be provided through the left side of the unit and that the combustion air duct when provided also enters through the left side See later section on combustion air and also the section on water piping Do not install the heater on carpeting or similar material 2E Outdoor Installation Locate the heater in an open unroofed area and maintain the clearances shown in Table 1 Do not locate the heater below or adjacent to any doors windows louvers or grates etc which connect in any way with an inhabited area of a building even through another building such as a garage or utility room see Figure 1 Do not locate the heater below an outdoor deck unless treated as an indoor installation with adequate clearances and proper venting to a location away from the deck Hi E2 Page 3 USA 4 ft 1 22 m CANADA 10 ft 3 05 m lt gt Figure 1 Outdoor heater location If the heater is installed close to a structure protect it from rain water runoff by means of gutters roof water diverters or similar measures Do not locate the heater close to irrigation sprinklers Water from spri
49. nce wall or other permanent barrier When pool equipment is located below the pool surface a leak from any component can cause large scale water loss or flooding Teledyne Laars cannot be responsible for such water loss or flooding or resulting damage Location of the heater below or above the pool deck affects operation of its water pressure switch See sections on water piping and heater start up for more information about this WARNING When pool equipment is located below the pool surface a leak from any component can cause large scale water loss or flooding Teledyne Laars cannot be responsible for such water loss or flooding or resulting damage Locate the heater in an area where water leakage will not result in damage to the area around the appliance or to a structure If forced to locate the heater where water leakage may cause damage provide a suitable pan with drain under the heater This pan must not restrict air flow or heater functions In selection of a location disposal of combustion condensate must also be considered The heater can produce three gallons of condensate water per hour under some operating conditions Means to drain this condensate must be available or special provisions such as a condensate pump must be provided See later section on condensate disposal 2D Installation Clearances Clearances between the heater and combustible material must be per Table 1 en Table 1 Installatio
50. ng the two wires from the remote to the two terminals on the terminal block This type of remote control will turn the heater on or off but will not switch between the two temperature controllers on the Flex Temp control panel Hi E2 Page 11 To connect a three wire remote control harness not supplied with the heater order an E0120000 wire harness assembly which connects to the Flex Temp control panel Installation instructions are included with the wire harness assembly 2K Water Piping 2K 1 Reversal of Heater Water Connections The Hi E2 is shipped with water connections on the right side but it can be modified in the field to provide left side water connections This is done by removing the water headers and re installing them opposite to their original location Some of the heater wiring and control components must be relocated so this change must be done only by a trained service technician Water connection reversal is illustrated in Figures 18 and 19 Proceed as follows 1 Remove the vent exhaust grille by removing the four screws which retain it Retain these and all other parts for later reassembly 2 Remove the top cover by removing the screws around the edges under the overhang 3 Remove the header covers Note that the return header cover is retained by wing nut fasteners inside the heater 4 Disconnect the pressure switch wires and remove the pressure switch tube from the inlet outlet header by
51. nklers may damage controls and electronic components Because the Hi E2 is very efficient combustion system exhaust gases are moist Do not locate the heater such that this exhaust will impinge on structures or vegetation which may be damaged by combustion condensate AAWARNING In United States Do not install the heater with the vent within 4 feet 1 22 m of any opening into a building In Canada Do not install the heater with the vent within 10 feet 3 05 m of any opening into a building 2F Outdoor Shelter Installation Canada An outdoor shelter is an unoccupied enclosure which does not communicate directly with occupied areas The Hi E2 may be installed in such a shelter only when the installation is in accordance with local codes and the most recent edition of Standard CAN CGA B 149 These codes and standards and Teledyne Laars require that the heater be properly vented as outlined in this manual Other requirements also apply such as provision of ample uncontaminated air for combustion and ventilation 2G Indoor Installation The Hi E2 can be located indoors when provided with one pipe or two pipe systems for combustion air and combustion product venting A one pipe installation has only a vent pipe and air for combustion must be provided to the room the heater is located in A two pipe system sometimes referred to as direct vent or sealed combustion has a vent pipe plus a pipe br
52. nometer is used WARNING In order to discourage incorrect adjustment by unqualified persons the gas valve regulator cap requires a special tool for removal Contact your Teledyne Laars representative about a special tool for this cap 4F 2c Gas Orifice Differential Turn off the heater disconnect the manometer tubes and replace the plug at the venturi inlet Reconnect the tubes with the positive side of the manometer connected to the gas valve outlet and the negative side to the venturi throat as shown in Figure 35 Turn on the heater The manometer will read zero until the gas valve opens Thereafter it should read 4 0 0 3 WC See the sections on Air Flow Investigation and High Elevation Operation if this is not the case Hi E2 Page 27 Figure 33 Unfired Venturi Differential Measurement Figure 35 Gas Orifice Differential Measurement WARNING When servicing is complete be sure to replace pressure service port plugs and assure that pressure switch and equalizer tube connections are unaltered and firmly in place 4F 3 Air Flow Investigation If unfired venturi differential or gas orifice differential are abnormal check air flow through the system per the following sections 4F 3a Combustion Air Flow Begin by connecting the negative side of the manometer to the venturi inlet and leaving the positive side open to ambient as shown in Figure 37 Ina norma
53. nuric Acid 80 to 150 ppm Total Dissolved Solids TDS Less than 1500 ppm Copper 0 ppm As recommended by IPSA Table 7 Chemical concentration levels 3D 2b Water Changing Teledyne Laars recommends changing of spa water every 60 days if usage is light and every 30 days during heavy usage Be sure to stabilize the water chemistry after every water change Page 18 NW TELEDYNE LAARS 3D 2c Corrosion The corrosive action of pool spa water is increased by the following 1 Low pH acidity 2 Low Total Alkalinity bicarbonates 3 Low Calcium hardness soft water NOTE Teledyne Laars does not warrant heat exchangers damaged by corrosive water 3D 2d Testing Teledyne Laars recommends that spa owners purchase a test kit and use it regularly A minimum kit is one which will measure chlorine and pH levels The pool spa owner will find it helpful to have a qualified professional technician perform more extensive chemical testing and water changing ona regular basis 3E Spa Hot Tub Safety Rules The following Safety Rules for Hot Tubs recommended by the U S Consumer Product Safety Commission should be observed when using the spa 1 Spa or hot tub water temperature should never exceed 104 F 40 C A temperature of 100 F 38 C is considered safe for a healthy adult Special caution is suggested for young children 2 Drinking of alcoholic beverages before or during spa or hot tub use can cause
54. o its weight does not bear on the heater Install a drip leg a non restrictive shutoff valve and a union on the gas supply line outside of the heater see Figure 13 Before operating the heater test the gas supply system including all connections for leaks using a soap solution Do not use a flame or any ignition source for leak detection Disconnect the heater and its individual gas shutoff valve during pressure testing if the test pressure is higher than 1 2 psig 3 34 kPa If the pressure is 1 2 psig 3 45 kPa or lower close the manual valve on the heater gas control during testing Hi E2 Heater When the heater is started check the supply pressure to verify that it is adequate during heater operation Undersize piping a restrictive fitting or an can cause low operating pressure undersize gas meter High Elevation To assure good combustion and general operation gas appliances are normally de rated when installed at high elevation This is not necessary with the Hi E2 because it has a special venturi type combustion system which self compensates for changes in barometric pressure Air flow through the venturi pulls the correct flow of gas into the burner temp rature ELECTRONIC TEMP CONTROL R gulation lectronique de N WATER TEMP
55. ockout 115V should be present at point C whenever a call for heat reaches the venturi pressure switch i e 24V at point 6 To be sure that a lockout condition is not in effect turn the heater off and then back on at the Flex Temp control If 24V is present at point 6 but 115V does not appear at point C and there is no lockout the ignition control is defective If 115V power is available at point C and the combustion blower does not run the blower is defective and should be replaced Note however that the blower has an internal overtemperature limit and before replacing it confirm that the environment of the heater is not excessively hot If so ventilation of the heater room may be necessary 4E 2I lgniter The igniter should glow during ignition attempts as outlined in the earlier section on ignition control If it does not connect the voltmeter between terminals marked D and E on the ignition control If 115V is present during the igniter on portion of the ignition sequence but there is no glow the igniter is probably defective If voltage is not found the ignition control is defective and should be replaced An igniter which will not glow should be checked by disconnecting the wires from the ignition control and measuring the igniter resistance A cold igniter should have resistance in the range of 40 to 75 ohms Replace the igniter if resistance is outside of this range 4F Venturi Combustion Flow System Verifying proper o
56. ologies manufacturer of Jandy products including Laars pool and spa heaters warrants all parts to be free from manufacturing defects in materials and workmanship for a period of one year from the date of retail purchase with the following exceptions e AquaLink RS units installed with Jandy Surge Protection Kits will be covered for two years e NeverLube valves are warranted for the life of pool and or spa on which they were originally installed This warranty is limited to the first retail purchaser is not transferable and does not apply to products that have been moved from their original installation sites The liability of Water Pik Technologies shall not exceed the repair or replacement of defective parts and does not include any costs for labor to remove and reinstall the defective part transportation to or from the factory and any other materials required to make the repair This warranty does not cover failures or malfunctions resulting from the following 1 Failure to properly install operate or maintain the product s in accordance with our published Installation Operation and Maintenance Manuals provided with the product s 2 The workmanship of any installer of the product s 3 Not maintaining a proper chemical balance in your pool and or spa pH level between 7 2 and 7 8 Total Alkalinity TA between 80 to 120 ppm Total Dissolved Solids TDS less than 2000 Abuse alteration accident fire flood lightning rodent
57. on flow system completely compensates for installation at elevations other than sea level Gas orifice changes are not necessary Unlike conventional systems with open type burners and positive pressure regulators the gas orifice differential pressure is created by the air flow and it is automatically reduced when air density decreased A Hi E2 heater commissioned at sea level will operate at nearly the same air gas mixture when operated at higher elevation Its firing rate will decrease about 3 per 1000 feet due to the barometric pressure change In servicing a Hi E2 heater at high elevation be aware that the input will be naturally reduced by this amount and that the differential pressures as discussed in prior sections will also be reduced Pressure readings at various elevations will be approximately as follows Elevation Gas Orifice Unfired Venturi Ft m Differential Differential Sea Level 4 0 102mm WC 4 7 119 mm WC 2000 610 3 7 94 4 3 109 4000 1220 3 4 86 4 0 102 6000 1830 3 2 81 3 7 94 8000 2440 2 9 74 3 5 89 10000 3050 2 7 69 3 2 81 The gas pressure offset is determined by the regulator spring adjustment not air density It is not affected by elevation change 4G Combustion Condensate The condensate disposal system of the Hi E2 pool heater is quite simple but must be properly installed and maintained See the installation instructions for information on correct tubing inst
58. ow of the igniter through the combustion chamber sight glass and then voltage at point 8 If the blower Hi E2 Page 25 does not operate or the igniter doesn t glow investigate as outlined in a later sections If both of these components operate normally but voltage doesn t appear at point 8 during the trial for ignition replace the ignition control If voltage appears at point 8 but there is no ignition proceed to analysis of other components 4E 2i Burner Limit Switch The burner limit switch is located on the front surface of the burner plenum near the top of the heater Servicing this switch normally requires removal of the top of the heater but it can be checked by probing for voltage at point 9 on the vent limit switch Point 9 is the terminal of the vent limit switch to which is connected a brown wire coming down from above The vent limit switch is mounted on the vent outlet diffuser above the combustion blower Voltage will be present at point 9 only during normal operation or during a trial for ignition If necessary restart the heater using the Flex Temp control to obtain one of these conditions If voltage does not appear at point 9 the burner limit switch is open This may be due to burner mis adjustment incorrect gas orifice size or similar problems which should be investigated as outlined in later sections If there are no such problems and there is no evidence of excessive burner temperature replace the burner li
59. pe can be connected directly to the heater using the rubber donut gaskets provided with the heater 2 PVC or metal pipe can be threaded directly to the flanges and 1 1 2 schedule 40 metal pipe can be used with the rubber donut gaskets see Figure 21 Page 12 NW TELEDYNE LAARS Figure 19 Water Connection Reversal 2K 4 Pressure Relief Valve A pressure relief valve is mandatory in any installation in which the water flow can be shut off between the heater outlet and the pool spa A pressure relief valve is not supplied with the Hi E2 in the United States however it may be required by local codes A pressure relief valve must be provided in Canada To install a pressure relief valve remove the 3 4 brass plug from the top of the inlet outlet header See Figure 22 Install the pressure relief valve in the opening Provide a short length of brass or stainless steel pipe as necessary to position the valve above the sheet metal cover Turn the valve or route discharge piping as necessary to assure that hot steam will not endanger persons near the heater The valve setting should be at or below the maximum working pressure of any component in the filter system The working pressure of the Hi E2 heater is 75 psig 2K 5 Automatic Chlorinators Chemical Feeders A high concentration of chlorine and many similar chemicals in the pool heater can be very destructive Heater damage cause
60. peration of the combustion flow system has two aspects air flow and gas flow Air flow is checked by measuring pressures at service ports on the venturi Gas flow is checked by evaluating venturi pressures plus the regulator offset pressure and the gas orifice size In a venturi flow system the difference between various pressures is far more important than their gauge value relative to the room The gas pressure offset and the gas orifice pressure differential are especially important concepts The following sections illustrate these and related information 4F 1 Pressure Measurement Ports Figure 32 shows venturi and gas control components and service port locations Air flow enters the venturi from below through the filter box It is pulled through a converging section to the throat where pressure is reduced substantially Gas flow is pulled into the throat through an orifice inside the pipe between the throat and the elbow Air and gas are Page 26 NW TELEDYNE LAARS VENTURI THROAT VENTURI INLET SERVICE PORT GAS VALVE SERVICE PORT Figure 32 Venturi Flow System Components combined in the throat and mix thoroughly as they proceed through the venturi tailpipe to the burner Service ports are provided at three places On the right side of the venturi an inlet service port is provided just above the air filter box Also on the right side a throat service port is provided at the narrowest
61. r High Limit Switch A R0319700 Requires field supplied 3 4 NPT x 3 brass nipple 89 Combustion Blower Wire Harness A R0308100 Heat Exchanger Hardware Kit Note 1 220 350 R0319103 05 Inlet Outlet Header Hardware Kit Note 1 Al R0319300 Return Header Hardware Kit Note 1 Al R0319200 Touch Up PE E O COMPONENTS A X0021100 COMBUSTION SYSTEM ASSEMBLY High Temperature Silicone Sealant Al R0322800 31 Gas Valve All R0200100 32 Anti Rotation Bracket Not Shown Al R0309900 Notes 33 Orifice Holder A R0320000 1 All ER a contain ai pieces necessary for assembly 34 Gas Orifice NAT 220 350 R0309303 05 including gaskets Not shown ifi 220 R 4 2 ae rie Assembly A 0 390 cue 2 Gaskets and hardware are included in all kits that involve the 36 Combustion Air Filter A R0308000 removal of a gasket as part of the procedure to replace a part 37 Venturi Inlet 220 350 R0320303 05 38 Venturi O ring A R0320400 39 Venturi Plenum A R0320500 40 Venturi Tailpipe Gasket A R0320600 41 Mixing Chamber Tail Pipe Assembly A R0307300 42 Mixing Chamber Burner Gasket Al R0320800 43 Burner Assembly 220 350 R0305903 05 44 Burner Combustion Chamber Gasket 220 350 R0305803 05 45 Combustion Chamber Assembly 220 350 R0305103 05 46 Refractory Tile Set 220 350 R0305303 05 47 Sight Glass Assembly All R0305400 Page 31 Hi E2 Exploded View of the Hi E2 LIMITED WARRANTY Thank you for purchasing Jandy pool and spa products Water Pik Techn
62. re properly aligned Screws must be tightened enough to assure a sealed joint without deforming the vent collar 2G 2 Combustion Air Requirements for One Pipe Installation One pipe indoor installations must have specific provisions for supply of combustion and ventilation air to the room in which the heater is located Two air openings must be provided one near the ceiling and one near the floor When air is provided directly through an outside wall each opening must have at least one square inch 6 5 square cm of area per 4000 BTU h of heater input When air is provided indirectly through ducts from the outside the openings and passages must have at least one square inch of area per 2000 Btu h of heater input These requirements are interpreted in Table 2 Required net free area in square inches sq cm for each of 2 openings one near ceiling and one near floor Directly Through an Exterior Wall Through Horizontal Ducts 110 710 175 1130 Table 2 Required Net Free Area of Openings for Combustion and Ventilation Air Note that the numbers indicate the net free area after allowing for the blockage of grille bars etc See applicable local codes and the previously cited national codes for details Even though codes may permit it Teledyne Laars does not recommend installations with only infiltration as the means for provision of combustion air See Section 2G 3c for vent pipe sizing AAW
63. reparation or assembly in the field In all cases condensate tubing and fittings which are provided with the heater must be connected and routed Water connections are provided on the right side of the heater but can be changed to the left side by reversal of the water headers It is best to handle these preparations before the heater is in its final location Instructions are provided in subsequent sections of this document Installation at High Elevation The Hi E2 has a venturi type combustion system which does not require modification for operation at high elevation In this type of system air and fuel gas density changes are automatically compensated for assuring proper air fuel mixture Heating capacity is reduced about 3 percent per 1000 feet 305 meters above sea level In general efficiency at high elevation is equal to or better than at sea level 2C Heater Location The Hi E2 may be installed indoors or outdoors as outlined in later sections When installed indoors combustion air will often be piped to the heater and this requirement may affect the choice of location see later section on air for combustion and ventilation Both indoor and outdoor installations require provision of means for disposal of combustion condensate per section 2H Install the heater at least 5 feet 1 52 meters from the inside wall of the pool or spa unless the heater is separated from the pool or spa by a five foot 1 52 meter high solid fe
64. ressure at high elevations naturally decreases input and output by approximately three percent per 1000 feet above sea level 5 Heaters require 115V 60Hz electrical power 6 Working pressure 75 psig 231 2 gt 3 7 Vent Collar 146 ft W 5 Ati 87 A 341 7 ms eae A e CH 215 gt 18 bel LI tt 21 8 Se gt a Model Width Input Shipping 3 No W Weight 220 225 8 220 000 206 Ibs 350 317 8 350 000 252 Ibs Page 30 TELEDYNE LAARS SECTION 6 Key Model ORDER R t P t No Description No PART NO acement Farts ep 48 Combustion Chamber Strip Set 220 350 R0213103 05 Not Shown 49 Combustion Chamber Collector Gasket 220 350 R0305703 05 6A Parts List Venturi Hardware Kit Note 1 All R0322200 To order or purchase parts for the Teledyne Mixing Chamber Hardware Kit Note 1 All R0322100 Laars Hi E2 pool spa heater contact your nearest Burner Hardware Kit Note 1 220 350 RO319403 05 Teledyne Laars dealer or distributor If they cannot EXHAUST ASSEMBLY supply you with what you need contact the Customer 50 Collector 220 350 R0303203 05 PP yy y 51 Blower Collector Gasket A R0308700 Service Manager at Teledyne Laars 52 Combustion Blower A R030820
65. rizontal direction when on a wall and vertically upward when on a roof Both should terminate at least 12 30 5cm above the snow accumulation level In locations with freezing climate extension of the vent pipe outside of the building should be minimized The insect screens provided with the heater must be installed at the combustion air and vent pipe openings as shown in Figure 10 Insect screens are sized to fit the inside of a5 PVC pipe fitting Trim them as necessary for smaller pipe sizes Connect the vent pipe to the heater vent collar with an air tight corrosion resistant clamp The connection must not allow leakage of combustion products into the space but should be removable for service See Figure 7 Connect the combustion air pipe to collar of the air filter box For this combustion air pipe only sheet metal pipe is most convenient and can be screwed directly to the collar Seal the joint with silicone sealer or similar mastic material Install vent piping with a continuous rise of at least 1 4 per foot 20 mm per meter away from the heater This will assure that any condensate forming in the vent pipe will flow back to the heater where it can be disposed of properly Support vent piping with suitable hangers so its weight does not bear on the heater or building penetration and so that piping joints are not strained Support horizontal runs at intervals no greater than 6 feet 1 82 meters and closer if necessary to avoid s
66. rnal flow bypass because of very high filter system flow it should be adjusted to provide proper flow through the heater Flow is evaluated by determining the water temperature rise through the heat exchanger Before checking temperature rise be sure the pool filter is clean If necessary clean the filter Temperature rise is measured at the return header which is on the side opposite to the inlet outlet header For access remove the side cover which is held in place by wing nut fasteners inside the heater Remove the brass plug on the top surface of the header and install a pocket thermometer see Figure 24 Proceed as follows 1 If the piping system has a manual bypass valve close it 2 Turn off the heater by moving the Flex Temp switch on the temperature control panel to Off 3 After three minutes note and record the thermometer reading This is the pool temperature 4 Start the heater and let it operate for at least five minutes Note and record the thermometer reading The difference between this reading and the first one is the temperature rise 5 If the piping system has a manual bypass valve gradually open it until the temperature rise is in the range required by Table 6 6 Scribe a line on the bypass valve shaft and case to mark the correct adjustment position Wire the handle to the pipe to prevent tampering Note that temperature rise is somewhat less when the water is hot spa application and
67. rom back siphoning of water which can result in dry starts If there is any chance of back siphoning provide a check valve between the pool and the filter pump inlet Arrangement of pool system components other than as illustrated in these diagrams can affect the operation of the heater s water pressure switch Location of the heater above or below the pool water surface can also affect operation of the switch In general the pressure switch can be adjusted to accommodate this effect if the heater water connections are no more than six feet below the pool water surface and no more than 15 feet above it See instructions for pressure switch adjustment in the heater start up section of this manual for more information about this Note that when pool equipment is located below the pool surface a leak can result in large scale water loss or flooding Teledyne Laars cannot be responsible for such water loss or flooding or the damage caused by it Do not install a shutoff valve or any kind of variable restriction in the water piping between the heater outlet and the pool spa Pool systems with water flow rates higher than 125 GPM require an adjustable external bypass at the heater See the section on start up and adjustment for this information 2K 3 Connections at Heater The Hi E2 has a universal water header and flange design With this feature a variety of piping materials and sizes can be used at the heater 1 1 2 PVC or 2 copper pi
68. s insects negligence or acts of God Scaling freezing or other conditions causing inadequate water circulation Operating the product s at water flow rates outside the published minimum and maximum specifications Use of non factory authorized parts or accessories in conjunction with the product s Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing chemicals upstream of the heater and cleaner hose or through the skimmer Overheating incorrect wire runs improper electrical supply collateral damage caused by failure of O Rings DE grids or cartridge elements or damage caused by running the pump with insufficient quantities of water LIMITATION OF LIABILITY This is the only warranty given by Water Pik Technologies No one is authorized to make any other warranties on Water Pik Technologies behalf THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY WATER PIK TECHNOLOGIES EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL INCIDENTAL INDIRECT OR PUNITIVE DAMAGES FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY This warranty gives you specific legal rights You may also have other rights which vary by state or province WARRANTY CLAIMS For prompt warranty consideration contact your dealer and provide the following information proo
69. s and Their Operation 1 Gas valve Regulator The gas valve controls gas flow into the venturi It provides flow only when the temperature control require heat and only if all safety controls enable operation It is also a negative pressure regulator It regulates the gas pressure to 0 2 WC less than the air pressure at the venturi inlet This is necessary for proper operation of the venturi system and cannot be done with common positive pressure gas valves Combustion blower The combustion blower is a specially designed to handle moist combustion products having special plastic housing and impeller It is powered by a brushless DC motor Temperature Control The Teledyne Laars Flex Temp control is an electronic control which senses water temperature by means of a thermistor and controls heater operation to bring the water to that selected It has two temperature setting knobs which are typically used to set pool and spa temperatures A selector switch determines which setting is chosen Ignition Control The ignition control provides energy for ignition of the air gas mixture monitors the flame and controls the combustion blower and gas valve When the temperature control requires heat the ignition control starts the blower providing a pre purge of the combustion chamber Then it applies electrical power to a hot surface igniter When the igniter is hot enough it opens the gas valve It has sophisticated
70. should not be hot Normally water temperature will rise only a few degrees as it passes through the heater and a hot header or pipe indicates low water flow and will prime the trap To avoid this wet start up simply pour water into the tray before starting the heater as indicated earlier reach the blower and will temporarily be blown into the vent and may be thrown into the air around the heater 2L 4 Gas Pressure Confirm that gas supply pressure is correct Measure it at the heater by connecting a manometer to the supply pressure port on the inlet side of the gas valve With the heater firing the pressure must be within the range shown in Table 4 Also check the pressure with the heater off Checking of gas pressure at the outlet of the gas valve requires knowledge of the venturi system of the Hi E2 pool heater Do not attempt to adjust this pressure without thorough understanding of its operation and settings as outlined in the maintenance section of this manual 2L 5 Adjustment of Water Pressure Switch The pressure switch is pre set at the factory for normal pool installations Do not adjust it unless the heater water connections are more than three feet above or below the pool surface If they are not in this range the pressure switch must be adjusted This can be done in the field if the water connections are no more than six feet above the pool surface and no more than ten feet below it For other situations
71. st or in the vent In improperly installed vent may trap condensate water for example restricting flow If there is no obvious problem analyze venturi operation as outlined in a later section of this manual If flow is normal replace the Venturi pressure switch 4E 2h Ignition Control There will be voltage at point 8 which is the MVP terminal of the ignition control only when there is an attempt to ignite the burner or when the ignition control s flame sensing system has determined that it is OK to allow burner operation Even if voltage has been confirmed at point 7 the trial for ignition sequence is imposed by the ignition control This sequence consists of a 15 second period of pre purge blower operation a 20 second period for heatup of the igniter and a 7 second trial for ignition during which there is voltage at point 8 If satisfactory ignition is not achieved the igniter is turned off and the blower is operated for a 45 second post purge The system may go through this cycle as many as three times but thereafter it is locked out by the ignition control Additional attempts will be made only if the call for heat is interrupted by turning off electrical power or setting the Flex Temp control to Off To trouble shoot the ignition control connect the voltmeter probe at point 8 and set the Flex Temp control to call for heat Observe that the normal sequence takes place by noting blower operation the gl
72. such use Joints in 29 4C stainless steel pipe must be sealed in accordance with its listing Connection of combustion air and vent piping to the heater should be serviceable i e removable for heater service 2G 3e Room Ventilation The room a Hi E2 is installed in must be provided with adequate ventilation Like other gas fired appliances the Hi E2 releases heat to its environment and a room with no ventilation may become too warm In one pipe installations the normal code required provisions for combustion air also assure reasonable ventilation of the room If a two pipe system is installed ventilation must be provided by Condensate From Vent Blower Drains Condensate From Collector Drain N f PN y i f PA fe Water Level PY PushedDown ff Slighti Water Level f gmy Pulled Up Pie Y Overflow 2 3 AL To 50 75mm Disposal Trap p 4 3 8 6 10mm A Figure 12 Condensate Drain and Trap other means such as through grilles or openings or with a small fan 2H Condensate Disposal In a high efficiency combustion process combustion product gases are cooled so much that liquid water is condensed Flow of this condensate can be quite high When pool water is very cold as much as two or three gallons of condensate can be produced in an hour Condensate is mildly acidic Page 8 NW TELEDYNE LAARS
73. t cccccceeeeeeeeeeeeeereees 1 2B Heater Assembly and Preparation eeen 2 2C Heater Location e ee eeeeeeeeeeeeseeeeeeeeseeeeeeeeeeeeaes 2 2D Installation Clearances eeceeeeeeeeeeeeeeeeeeeeeeaes 2 2E Outdoor Installation 2 2F Outdoor Shelter Installation Canada 3 2G Indoor Installation 3 2G 1 Preparation of Heater For Indoor Installation 3 2G 2 Combustion Air Requirements for One Pipe Installation 4 2G 3 Two Pipe Installation Direct Vent eee 4 2G 3a Connection of Combustion Air Pipe 4 2G 3b Piping Materials 4 2G 3c Size and Length of Combustion Air and Vent Piping eeeeessseeesereeeeeneeeeeneeeee 5 2G 3d Combustion Air and Vent Pipe Installation 5 2G 3e Room Ventilation 7 2H Condensate Disposal ccceceeeeeseteeeeeeeeneees 7 2l Gas Supply and Piping c ceeeeeeeeeeeeeeeeeeeeee 8 2J Electric Wiring snrisgeennnr 10 2J 1 Electrical Power 10 2J 2 BONnGIng sree ses rhinite died eit re N 10 2J 3 Auxiliary Time Clock Wiring eeeeeeeeeeeeeeeeteee 10 2J 4 Remote Operation ecceeeeeeeeeeseeeeeeeeeeeeeeeeeeees 10 2K Water PIPING irriaren nie Gini a 11 2K 1 Reversal of Heater Water Connections 11 2K 2 Pool Spa Piping Systems 11 2K 3 Connections at Heater 11 2K 4 Pressure Relief Valve 12 2K 5 Automatic Chlorinators Che
74. t Switch Set All R0322700 71 High Limit Switch 135 F Al R0302400 WATER SYSTEM 72 High Limit Switch 150 F Al R0302300 13 Heat Exchanger Assembly Complete 220 350 R0303803 05 73 High Limit Switch Wire Harness Al R0322600 14 Heat Exchanger Tube Assembly 220 350 R0304103 05 Not Shown 15 Inlet Outlet Header Alt R0303900 74 Pressure Switch amp Siphon Loop Assembly Al R0322900 16 Return Header N Re 75 Pressure Switch 2 PSI All R0013200 17 Gasket Header 0304300 76 Pressure Switch Siphon Loop Al R0307800 18 By Pass Valve Assembly All R0304400 77 Temperature Control Assy Electronic Al R0011700 19 Flow Control Cap All 10557400 78 Temperature Sensor Not Shown Al R001 1800 20 By Pass Valve Gasket All R001 1400 79 Temperature Sensor Gasket All E0116400 21 By Pass Valve Spring All R0304500 80 Temperature Sensor Plastic Sleeve Al 10444900 22 By Pass Valve Rod All 0304900 81 Temperature Control Knob Al R0010700 23 By Pass Valve Disk All R001 1500 82 Pool Spa Selector Knob A R0099900 24 Flange amp Gasket Assembly 2 Set of 2 All R0055000 83 Temp Lok Disc Al 10583100 25 Flange 2 All 10573500 84 Temperature Sensor Retainer Cli Al 10716701 26 Flange Gasket 2 Al 0078000 Not Shown CER 5i Bange aeee 2 A aaa ed 85 Differential Pressure Switch A R0302000 ange 20 s 86 Differential Pressure Switch Bracket Al R0302200 29 Flange Gasket 1 1 2 2 Al S0078100 87 Exhaust Vent Limit Switch A R0309000 30 Pressure Relief Valve 75 PSI Al A0063300 88 Burne
75. tion csceeceeseeeeeetees 28 4G Combustion Condensate 28 4H Major Component Service 29 SECTION 5 Capacities and Dimensions 5A General Information eccesseeeeeeeeeeeteeeeeeeeaes 29 SECTION 6 Replacement Parts 6A General Information ccceseseseeessssseeeeeees 30 Hi E2 Page 1 SECTION 1 General Information 1A Introduction This manual contains information for the proper installation and operation of the Hi E2 Model EHE pool spa heater Certain sections are specific to United States or Canadian installations and are labeled United States or Canada Procedures in this manual must be followed exactly To obtain a copy of this manual contact Teledyne Laars For address information see back cover 1B Description The Hi E2 is a very efficient gas fired pool and spa heater Its combustion system includes a heat exchanger which extracts 95 of the energy in the gas fuel It has no standing pilot burner It exceeds the requirements of energy conservation regulations such as those in California Hawaii New York Oregon and other states which require that a pool heater have intermittent ignition The heater is designed to operate in conventional swimming pool and spa equipment arrangements It requires 115V 60 Hz electrical power It has the versatile Teledyne Laars FlexTemp dual thermostat control system for pool spa combinations The Hi E2 is certified b
76. ts for pool heaters include the following 1 Appropriate site location and clearances 2 Sufficient supply of clean air for combustion and ventilation Proper venting of products of combustion Properly sized gas pipe Properly sized gas meter Adequate water flow Os Ao D Provision for disposal of combustion condensate water In the United States installation must be in accordance with local codes and the most recent edition of the National Fuel Gas Code ANSI Z223 1 The Code can be obtained from National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 In Canada install the heater in accordance with local codes and the most recent edition of the Installation Codes for Gas Burning Appliances CAN 1 B149 1 amp 2 The Canadian Gas Codes are available from Canadian Gas Association 55 Scarsdale Road Don Mills Ontario M3B 2R3 Special Precautions Liquefied petroleum LP gas is heavier than air Therefore a pool heater using LP gas is subject to special installation rules Consult local codes and fire protection authorities about specific installation restrictions Fuel gas and its combustion products are known to cause cancer or harm the reproductive process Follow these installation instructions and applicable codes exactly to avoid this Page 2 NW TELEDYNE LAARS 2B Heater Assembly and Preparation The Hi E2 can be installed in a variety of ways some of them requiring p
77. ublic walkway Number of Elbows re OT a CS EE ca Total Length of Pipe Feet m 108 racer orcas 47 8 2 5 225 68 6 211 64 3 197 60 184 56 170 51 8 157 47 8 143 43 5 130 39 6 116 35 4 103 31 4 Table 3 Maximum Combined Length of Combustion Air and Vent Piping in Feet Page 6 NW TELEDYNE LAARS 2 Locate the vent terminal so the vent exhaust does not settle on building surfaces and other nearby objects Vent products may corrode such surfaces or objects 3 Locate the vent terminal at a sufficient horizontal distance from any gas or electric metering regulating or relief equipment In the United States this distance must be at least 4 feet 1 21 m In Canada it must be at least 10 feet 3 04 m 4 Locate the vent terminal at a sufficient horizontal distance from any building opening Take special care to assure that combustion products do not enter a building through windows doors ventilation inlets etc In the United States this distance must be at least 4 feet 1 21 m In Canada it must be at least 10 feet 3 04 m As shown in Figures 8 and 9 the combustion air intake and the vent outlet must be installed no closer together than 18 45 7cm and no farther apart than 60 1 5m The combustion air inlet opening must face downward to prevent entry of rain or snow The vent outlet must discharge away from the combustion air inlet normally in a ho
78. unscrewing the brass fitting 5 Remove the temperature control sensor by removing the retainer bracket and its cap screws 6 Disconnect the limit switch wires from the limit switches The limit switches and the short wire between them may be left in place 7 Remove both headers by unscrewing eight cap screws retaining each header 8 Install the inlet outlet header on the left side of the heater and the return header on the right Position gaskets carefully to avoid water leaks 9 Re route the limit switch wires in front of the venturi tailpipe and attach them to the limit switches 10 Re route the temperature sensor wires in front of the venturi tailpipe and insert the sensor into the header When the inlet outlet header is on the left side the sensor opening is at the rear Re install the retainer bracket and screw 11 Re install the pressure switch tube and fitting Relocate fitting 12 Adjust wiring and pressure switch tube routing so that they don t rest on sharp edges or on the hot surfaces of the combustion chamber The combustion chamber is the portion of the assembly just above the heat headers 13 Re assemble all other components and fasteners 2K 2 Pool Spa Piping Systems Figure 20 illustrates typical piping for pool equipment in pool spa combination pools With its Flex Temp temperature control the Hi E2 is particularly suitable for this type of pool installation The heater must be protected f
79. uri pressure switch having a yellow amp black wire connected to it This is the switch mounted on the frame above the blower between the vent diffuser and the venturi tailpipe It is about 4 in diameter Absence of voltage at point 6 indicates that the Flex Temp control is not calling for heat Be sure that knobs are set to call for heat as indicated earlier and as described in the Operating Instructions section of this manual Verify that the thermistor sensor wires are not severed or shorted Check wiring connections by removing the temperature control through the front of the bezel If the control is properly set and all wiring and connections are correct replace the Flex Temp control 4E 2g Venturi Pressure Switch Touch the voltmeter probe to point 7 which is the terminal of the venturi pressure switch having a purple wire connected to it If there is no voltage at point 7 the venturi pressure switch is open indicating inadequate flow through the combustion system The venturi pressure switch is a differential type switch which is activated by the pressure difference created when air flows through the venturi When the combustion blower is not operating the venturi pressure switch must be open and voltage will not be present See following sections on ignition control lockout and combustion blower operation for possible remedies Check for blockage at the combustion air inlet a dirty air filter or blockage at the vent exhau
80. y International Approval Services Inc to comply with latest editions of applicable standards In the United States the applicable standard is ANSI Standard Z21 56 for gas fired pool heaters In Canada it is Standard CAN 1 4 7 M85 The heater has been designed specifically to heat fresh water swimming pools and spas and with proper installation and care it will provide years of reliable service Do not use it to maintain pool or spa water temperature below 70 F Do not use it as a heating boiler or general service water heater or to heat salt water For special applications consult your Teledyne Laars dealer 1C Warranty The Hi E is sold with a limited factory warranty A copy of the warranty is included in a plastic bag inside the heater and on the back cover of this manual The home owner should fill out the warranty registration card included in the plastic bag and return it to Teledyne Laars The warranty does not cover damage caused by improper installation operation or field modification or damage to the heat exchanger caused by corrosive water See Section 3F for guidelines on pool water chemistry WARNING Improper installation or servicing can cause property damage injury or death due to fire asphyxiation or carbon monoxide poisoning SECTION 2 Installation Instructions 2A General Requirements All gas fired products require correct installation to assure safe and satisfactory operation The requiremen

Download Pdf Manuals

image

Related Search

Related Contents

"取扱説明書"  INSTRUCTION MANUAL - Products  interoperability report  Honda F200 User's Manual  LUPUSNIGHT® LE-308 Benutzerhandbuch  Catálogo PDF  

Copyright © All rights reserved.
Failed to retrieve file