Siemens SED2 User's Manual
Contents
1. L kan 7 STAB Hel wide se abi ee hel eer ee ie eee eae 7 Quick COMMISSIONING Ka daa nad d kal kuye naa 8 AOP Applications s k kill al kay k y ka tt ap baya ka ak dava ka a Raa k dka ya awan seed k d duya ua a leas shaveececcee tens 11 Single Drive Control Using the AO P L i i jiE kk kk kk ek kk kk kk k kk k kk K 11 Network Setup RS 485 with Panel Mounting 11 Network Setup PC MOde Eu keke ek kek kek kek kk Ka kk KAKA KAKA KAKA KARA KARA KARA 12 Editing Parameters ccsseccecsseeeceessneeceenseeeeeenseeeeensneeeeensueeseessneeeeenseeeeeenseaeeeenseeeeeess 13 Parameter Access Levels M L kk kak AKA kk AA AKA KAKA kK KAWA WA 13 Editing Conventional Para meterS L iiuiiiEEEEEk 13 Editing Indexed Parameters ccccceeeeeseceeeenneeeceneeeeeeaeeeeeeaaeeeseeaaeeeeeeaaeeeeseaeeeeneaas 14 AOP Stored 5 15 15 Editing AOP Stored Parameter Sets 15 Editing Internal AOP Parameter 15 Parameter Upload Upread 16 Wait ROQUOS tii ete eed fw a eee E 17 Parameter Download
2. Data Description STOPPED Indicates the motor connected to the SED2 is not running pulses disabled RUNNING Indicates the motor connected to the SED2 is running pulses enabled FAULT Indicates a fault condition has occurred The SED2 is not running A fault described by the AOP under the Diagnostics menu is preventing operation WARNING problem in normal operation and is informing you of the INHIBIT A previously occurring fault or OFF condition is preventing SED2 operation Sending an OFF1 command from the currently active command source clears this condition r0000 Indicates a read only parameter Drive Display 0000 is the normal operating display F 0 00 Hz Indicates the frequency at which the SED2 VFD motor is running S 0 00 Hz Indicates the speed frequency when the motor last stopped l 0 0 A Indicates the output current RPM 0 Indicates the speed of the motor M 0 Indicates the current torque of the motor V 0 0 V Indicates the output voltage Vdc 0 0V Indicates the dc link voltage 8 Simultaneously press these keys at any time to display the main menu v Simultaneously press these keys to display the help screens E Press P to select the parameter access screen A ana 3 Navigation keys to scroll through information on the display an Indicates the direction of the running motor 10 Siemens Building Technologies AOP Applications AOP Application
3. TYPO YY DD 25 Start FONN kin lone aa e ko a e e Me a be yon 26 Welcome LON weeks r yo e van pon aa ke ene 26 User Defined T X aliyaye k l k Ey dll needed need ened daki a kw W We ant 26 Parameter Set 27 Set Time Date vo ie ate ye da xin y nakan M a E d h kany V du d ek da Mian 27 P OPA n EEE NY N teres A A T Ke 28 AOP Faults 8 Warnings suni ek k kl n uk e le e Eu Ek l wa ka da bu uu a ww ek wek de 29 Fault Indication Fault SCr en iiiiiE kk kk kek kk k KAKA KAKA KAR KAYA 29 Warning Indication Warning Screen 29 ye e r kek are e H V RA Re 30 Multiple WarningS toye yi H ka ke a x von e k ate ahead ted 30 Simultaneous Faults and WarningS ccccccecceseeeeeeeeeceeeeeseaeeeeaaeseeeeeseaeeesaeeseneeseaes 30 SED2 VFD Fault Warning Record 0947 30 ii Siemens Building Technologies How to Use this Manual How to Use this Manual The Advanced Operator Panel AOP enhances the user interface and communications capability of the SED2 Variable Frequency Drives SED2 VFD Manual Organization This manual contains the following sections How to
4. to highlight the Large Numbers option on the setup menu Press to confirm the selection The AOP displays a large number screen 2 Use to select either an OFF or ON large number display Press to confirm the selection NOTE When you select OFF for no large number display the AOP returns to the setup menu 3 Select a requested delay time 4 through 250 seconds Press B to confirm the selection and to return to the main menu Cursor Type 1 Use highlight the Cursor Type option on the setup menu Press confirm the selection The AOP displays a cursor type screen Siemens Building Technologies Inc 25 SED2 AOP Operating Instructions 2 Use to select the desired cursor type blinking underline or inverse video default Press to confirm the selection and the AOP returns to the setup menu NOTE Simultaneously press LA at any time to display relevant help screens Start Help NOTE default the Start Help function is set ON To change this setting select Start Help from the setup menu 1 Use highlight the Start Help option on the setup menu Press M to confirm the selection The AOP displays a start help screen 2 Use to select either an OFF or ON start help function Press to confirm the selection and the AOP returns to the setup menu NOTE Simultaneously press any time to display relevant help screens Welcome Text
5. 1 Simultaneously press El and A at any time to return to the main menu 2 Simultaneously press E and KA at any time to display the parameter help screens AOP Stored Parameter Sets The AOP contains a battery backed storage facility for storing up to 10 parameter sets that are identified numerically from 00 to 09 Only a parameter set containing parameter data can be edited If the selected parameter set does not contain parameter data the AOP asks if the default parameter set should be copied to the selected parameter set When you confirm this request the AOP copies only the editable parameters to the selected parameter set read only parameters are accessed from the original parameter location Editing AOP Stored Parameter Sets Use the following procedure to edit a parameter set 1 From the main menu use and to scroll through the list of options and to highlight the Mode item Press confirm the selection The AOP displays a mode menu so you can select the operating mode 2 Use 9 to scroll through the list of mode options and to highlight the Internal item Press to confirm the selection The AOP displays an internal mode menu so you can select the internal mode function 3 Press again to confirm the selection and to return to the main menu 4 Use to scroll through the main menu and to highlight the Parameters item Press to confirm the selection The AOP displays an internal edi
6. Use the following procedure to edit the welcome text that displays on the AOP at power up 1 Use highlight Welcome Text option on the setup menu Press to confirm the selection The AOP displays a welcome text screen 2 Use and to select an ON or OFF welcome text status Press to cancel this selection and to return to the setup menu Press to confirm the selection and the AOP displays a text screen with the first character highlighted The text string can contain a maximum of 20 characters Use and to scroll through the characters until the desired character is shown Press to accept the character and to advance to the next character Repeat this step until the desired text is entered 4 Press and hold 8 to except the text string and to return to the setup menu Press and hold to cancel the text entry restore the original text string and to return to the setup menu NOTE Simultaneously press and at any time to display relevant help screens User Defined Text With the following procedure you can enter a user defined text in the AOP 1 Use to highlight User Defined Text option on the setup menu Press confirm the selection The AOP displays a user text screen 26 Siemens Building Technologies AOP Setup 8 Configuration 2 Use and to select an ON or OFF user text status Press to cancel this selection and to return to the setup menu Press to confirm the s
7. 17 AOP Operating 19 Selecting an Operating Mode u kk kk kk keka kk kk kk KAK kk KRA 19 Operating in Local mila ayak y kinn d kla len er bee i 1na aba kan e eken 20 Operating in Master Mode Individual Control of SED2 20 Operating in Master Mode Broadcast Operation 21 Communications kk kk kk KE KAKE KAKA KAKA KA KA A KA RA 21 Displaying Drive Status aa xn yin ni nd ya yin aa W sea ia i Alaye yaya kiy 21 Verifying Drive Type e aki rans asa ok asa EA ne Kaka kad d K ye K u ad E Kak AA Ve r se K L KARA d 21 TIMEHEUNC MON e X dinin pa krab n kur an diha Sa P Ka KU ake ki Kawa Ku KE ekspe Ve He KUR HERRE E a Ku hes 22 Setting the AOP EEE kek kek keke kk kk kk KA KA KAKA A KA KA KA KA KA KH KA KA KA 22 Siemens Building Technologies i SED2 AOP Operating Instructons AOP Setup amp nannan nnanonnnannnnaaannanannnann 24 S L NEN W an eke 24 de fata aden ag Ta N di ba di peta pi d n A ka e RAA dude feta pie van 24 SELSSN GONUA Ske is at ka ka aie ks kak eten r ke rada pena de ea 25 Large Number Display renccer e 25
8. Commissioning parameter P0010 Press to confirm the selection and the cursor advances to the parameter value Use and amp to set P0010 0 0 Ready to exit the quick commissioning mode Press f9 to confirm the setting and the cursor returns to the parameter Use and 9 to scroll through the parameters and to highlight USS Telegram Off Time P2014 Press to confirm the selection and the cursor advances to the parameter index Use and 9 to scroll through the indexes for P2014 and to highlight P2014 1 index 1 Serial Interface BOP Link Press confirm the selection and the cursor advances to the parameter value Use and 9 to set P2014 1 5000 USS on BOP AOP local link to prevent unexpected drive operation In this mode removal of the AOP from the SED2 VFD causes a timeout to occur in 5 seconds Press to confirm the setting and the cursor returns to the parameter Press to return to r0000 Press to display the standard operate screen Press to switch the SED2 to hand mode 10 Press Dro start the SED2 11 Use 9 to increase the output Use to decrease the output Siemens Building Technologies Inc 9 SED2 AOP Operating Instructions The AOP display the current status of the SED2 and motor The following table explains information on this display STOPPED r0000 F 0 00Hz 1 0 0A RPM 0 M 0 V 0 0V Table 1 Status Information of an AOP Display with an Operating SED2
9. Press to confirm the selection On display of the mode menu select Master mode Press f9 to confirm the selection Press to return to the main menu Select Operate from the main menu The AOP lists all SED2 VFDs on the network For each connected SED2 VFD drive an O appears indicating normal operation NOTE If there is a fault with a connected drive an appears indicating a fault condition Use and to select the drive and to clear the fault Select a single SED2 VFD and press to confirm the selection or select and press Bio enter the Broadcast Mode of operation At any time amp will exit the Broadcast Mode of operation Press to start the selected SED2 VFD motor Press stop the selected SED2 VFD motor For more information see AOP Operating Modes Network Setup PC Mode The AOP can be configured as an RS 232 to RS 485 converter to allow a PC that is running software to connect to a network of SED2 VFDS To use this configuration use a null modem lead to connect the PC to the PMK At the AOP main menu select Mode At the mode menu select PC Mode Enter the desired baud rate of operation Siemens Building Technologies Editing Parameters Editing Parameters Parameter Access Levels You can edit SED2 VFD parameters via the AOP Access levels control access to the SED2 VFD parameters A higher access level corresponds to a more sophisticated level of control techniques availa
10. Press to confirm the selection Press to cancel the download process The AOP displays a download menu NOTE In master mode the AOP prompts for selection of a specific SED2 VFD from a list of the networked SED2 VFDs 2 Use and KA to scroll through the list of parameter sets and to highlight the parameter set from which information will be copied Press B to confirm the selection 3 AOP displays a confirmation screen Press to confirm the selection Press to cancel the download process 4 The AOP displays a wait screen while the download process occurs 5 On completion of the download process the AOP returns to the main menu NOTES If the download fails perform the following 1 Reset VFD parameters Commissioning Parameter P0010 30 for factory settings and Factory Reset Parameter PO970 1 to reset all parameters to their default values 2 Cycle VFD power off on 3 Repeat the download process 18 Siemens Building Technologies AOP Operating Modes AOP Operating Modes Selecting an Operating Mode The mode menu allows you to select the desired AOP operating mode The following table summarizes the AOP operating modes and lists associated main menu items Main Menu Items Operating Mode Operate Diagnostics Parameters Mode Upload Download Language Setup e Master e e Internal e Timer Engineering Description In Local mode the AOP
11. Use this Manual describes the organization of this manual and symbols used throughout this manual AOP Overview shows the AOP main menu and details the AOP function keys AOP Startup amp Initialization describes AOP power on and initialization procedures and discusses using the AOP for single drive control or for control of a network of drives AOP Applications describes different applications of the AOP controlling just a single SED2 drive or a network of up to 31 SED2 drives Editing Parameters describes how to edit parameters and provides procedures to upload and download a parameter set AOP Operating Modes discusses the AOP operating modes local master or slave and the functions of the Operate menu Timer Function explains how to use the AOP timer much like a 7 day time of day on off controller AOP Setup amp Configuration explains how to customize the AOP via the Setup menu such as screen contrast large number display and cursor type AOP Faults and Warnings discusses reporting of AOP fault and warning conditions Siemens Building Technologies 1 SED2 AOP Operating Instructons Manual Notations Notation Symbol Meaning DANGER Indicates that personal injury or loss of life may occur if you do not perform a procedure as specified WARNING Indicates that equipment damage or loss of data may occur if you do not perform a procedure as specified CAUTION Indicates that equipmen
12. and the cursor returns to the parameter 3 Use to scroll through the parameters and to highlight Commissioning Parameter P0010 Press to confirm the selection and the cursor advances to the parameter value Use and amp to set P0010 1 Quick Commissioning Press to confirm the setting and the cursor returns to the parameter 8 Siemens Building Technologies AOP Start Up amp Initialization 9 Use and to scroll through the parameters to highlight Command Source P0700 Press to confirm the selection and the cursor advances to the parameter index Use to scroll through the indexes for P0700 and to highlight PO700 1 index 1 Press confirm the selection and the cursor advances to the parameter value Use EY and to set 0700 1 4 USS on BOP AOP local link Press to confirm the setting and the cursor returns to the parameter Use to scroll through the parameters and to highlight Selection of Frequency Setpoint P1000 Press to confirm the selection and the cursor advances to the parameter index Use and 9 to scroll through the indexes for P1000 and to highlight P1000 1 index 1 Press to confirm the selection and the cursor advances to the parameter value Use and amp to set P1000 1 1 motor potentiometer MOP setpoint Press to confirm the setting and the cursor returns to the parameter Use and 9 to scroll through the parameters and to highlight
13. at any time to return to the main menu 2 Simultaneously press amp and at any time to display the parameter help screens Editing Indexed Parameters Use the following procedure to view and edit parameters with indexes 1 certain you in the expert access level PO003 3 2 From the main menu use to scroll through the list of options and to highlight the Parameters item Press M to confirm the selection The AOP displays a parameter screen so you can select the desired parameter group or access level 3 Use and to scroll through the groups access levels and to highlight the desired parameter group Press to confirm the selection When you select a parameter group the AOP displays the first parameter in ascending numerical order 4 Use KA to scroll through the list of parameters and to highlight the desired parameter Press confirm the parameter selection 5 Press again to access the parameter index Use and J to scroll through the indexes and to highlight the desired index 14 Siemens Building Technologies Editing Parameters 6 Press to access the index value Use E and to scroll through the index values and to highlight the desired index value 7 Press to confirm the new index value The AOP returns to the parameter selection screen so you can select another parameter if desired 8 To edit another indexed parameter repeat Steps 3 to 6 NOTES
14. the AOP as the command source the drive control buttons 0 a and can control the drive at all times NOTES Parameter editing bit field indicator When editing a bit field type parameter the AOP increments the display value as a binary number Inhibit When the AOP displays Inhibit the SED2 VFD is in an inhibit mode of operation as reported by the USS message This inhibit status clears when the SED2 VFD receives a valid start stop command from the AOP On first power up send an OFF1 command to the SED2 before trying to run the VFD this must also be done when the VFD is under Automatic Timer Control Power on and Initialization 1 On initial power up the AOP performs internal self tests and displays a welcome screen 2 After establishing initial AOP to SED2 VFD communications the Start Help screen s appear lf the current AOP display language is acceptable continue with the Start Help section If you need to change the current AOP display language continue with the Language Selection section Siemens Building Technologies AOP Start Up amp Initialization Language Selection 1 The AOP provides the capability to display information in five different languages NOTE Prior to language selection the AOP has no control over the SED2 VFD CAUTION A Memory Limitation The delivered AOP supports five European languages English German French Spanish and Italian Due to internal memory
15. the highlighted SED2 VFD The following table describes the icons NOTE To configure SED2 VFDs for network operation set Command Source 0700 1 5 USS on Com link set USS Telegram Off Time for Serial Interface Com Link P2014 0 5000 and USS Address for Serial Interface Com Link P2011 0 a unique number for each drive on the network Icon Description Indicates the SED2 VFD is active and communicating Indicates no active slave icon is blank F Indicates a SED2 VFD fault has been recorded and the SED2 VFD has tripped A Indicates a SED2 VFD with active warnings Ei Indicates a SED2 VFD with communications problems Indicates non SED2 VFD parameter upload only 20 Siemens Building Technologies AOP Operating Modes Operating in Master Mode Broadcast Operation In master mode the network controls the SED2 VFDS either individually or by broadcast operation A broadcast operation can simultaneously start or stop all networked SED2 VFDs While in broadcast operation note the following AOP functions e Since parameters can not be edited globally does not function in a broadcast operation and still function in a broadcast operation For example it would be possible to change the speed of a motor simultaneously across all networked SED2 VFDs e Failure displays the screen also indicates which slave SED2 VFD is not working correctly Press
16. 59 Press to confirm the input Simultaneously press and to return to the main menu Siemens Building Technologies Inc 23 SED2 AOP Operating Instructions AOP Setup 8 Configuration Setup Menu Using the Setup option from the Main Menu of the AOP you can personalize the following characteristics of the AOP e Backlighting e Welcome Text Screen Contrast e Parameter Set Names Expert Level and above only e Large Numbers e User Defined Text Cursor Type Set Time Date Service Level only e Start Help e AOP Reset Use the following procedure to access the Setup menu 1 From the main menu use and to scroll through the list of options and to highlight the Setup item Press to confirm the selection The AOP displays a setup menu Use and to scroll through the setup menu and to highlight the desired option Press to confirm the selection NOTE Simultaneously press and at any time to display relevant help screens Backlighting To activate the backlighting option on the AOP the following procedure should performed 1 24 Use 9 highlight the Backlighting option on the setup menu Press to confirm the selection The AOP displays a backlighting selection screen Use 0 and 8 to select either an OFF or ON backlighting status Press to confirm the selection NOTE When you select OFF for no backlighting the AOP returns to the setup menu When you se
17. A to delete any previously stored data in that parameter set Set Software While viewing a stored parameter set press a to display the software version of that Version parameter set lli A n ae Press v to scroll through text on a display consisting of more than four lines Siemens Building Technologies AOP Overview Key Function Change Single Parameter Digit Functional Description Quickly change a single digit of a parameter value as follows 1 Ensure you are in the parameter value changing level Press and the right hand digit blinks If desired press a or v to change the value of this digit 2 3 4 Press again and the next digit blinks 5 Perform steps 3 and 4 until the required value appears 6 Press to leave the parameter value changing level Siemens Building Technologies Inc SED2 AOP Operating Instructions AOP Start Up amp Initialization Important Notes A CAUTION You can mount or remove the AOP while power is applied to the SED2 VFD e You must set Command Source PO700 1 4 USS on BOP link or AOP before the AOP can start or stop an attached SED2 VFD e On setting the AOP as the command source you must set USS Telegram Off Time for Serial Interface BOP Link P2014 1 5000 5 seconds to prevent unexpected drive operation In this mode removal of the AOP from the SED2 VFD causes a timeout to occur 5 seconds e On setting
18. Bio acknowledge the warning condition If the warning condition occurs again the AOP assumes it is not connected to the SED2 VFD and returns you to the main menu Communications Failure If communications between the AOP and a SED2 VFD fails a warning screen displays Press f3 to acknowledge the warning condition If the warning condition occurs again the AOP assumes it is not connected to the SED2 VFD and returns you to the main menu If the AOP fails to establish initial communications with a SED2 VFD any attempt to select Operate from the main menu results in an warning screen Press to acknowledge the warning condition and to return to the main menu Displaying Drive Status The AOP can monitor the status of its associated SED2 VFD and motor The screen displays the current activity of the SED2 VFD and motor including any fault conditions Verifying Drive Type The AOP can verify the type of its associated SED2 VFD If the SED2 VFD type is incompatible with the AOP it inhibits operation and returns to the main menu Siemens Building Technologies Inc 21 SED2 AOP Operating Instructions Timer Function NOTES 1 Before using the timer function as a control method set the AOP real time clock as described in the Set Time Date section Setting a timing event for every day configures the same event for each day of the week separately To clear an every day event you must clear the event individually fro
19. SIEMENS SED2 Advanced Operator Panel AOP O perating Instructions SED SIEMENS SED2 AOP Operating Instructions Rev 1 0 September 2002 NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies Inc Siemens Building Technologies Inc assumes no responsibility for any errors that may appear in this document All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license WARNING This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area may cause interference in which case users at their own expense will be required to take whatever measures may be required to correct the interference SERVICE STATEMENT Control devices are combined to make a system Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation All Siemens Building Techno
20. ble for the SED2 VFD applications User Access Level parameter P0003 sets the access level as follows e P0003 0 User Defined List e 0003 1 Standard Parameters e P0003 2 Extended Parameters e 0003 3 Expert Parameters The access level defined for a SED2 VFD not the AOP determines the access to the various levels of parameters Extended level parameters permit access to all Standard level parameters as well as several others Expert level parameters permit access to all Extended and Standard level parameters as well as indexed parameters Parameter indexes provide subsets of a particular parameter function The indexes group together closely related parameter type information Editing Conventional Parameters NOTE All parameters that are changed using the following procedures are changing the physical parameters on the SED2 connected to the AOP Use the following procedure to change parameters in the SED2 VFD that connects to the AOP 1 From the main menu use and to scroll through the list of options and to highlight the Parameters item Press to confirm the selection The AOP displays a parameter screen so you can select the desired parameter group or access level 2 Use and to scroll through the groups access levels and to highlight the desired parameter group Press f9 to confirm the selection When you select a parameter group the AOP displays the first parameter in ascending numerical order Use t
21. el the text entry restore the original text string and to return to the setup menu NOTE Simultaneously press and at any time to display relevant help screens Set Time Date 1 Use and amp to highlight the Set Time Date option on the setup menu Press confirm the selection The AOP displays a set time screen and highlights the first time field hours Use 9 and 9 to scroll through the digits until the desired hour 0 23 displays Press to confirm the entry The cursor advances to the next time field minutes 0 59 and then seconds 0 59 Repeat this step until the desired time hours minutes seconds is set Siemens Building Technologies Inc 27 SED2 AOP Operating Instructions 3 The AOP displays a set day date screen and highlights the first field day of week Use 3 to scroll through and highlight the desired day of week Press to confirm the entry The cursor advances to the first date field day of month 4 Use and to scroll through the digits until the desired day of the month 01 31 displays Press to confirm the entry The cursor advances to the next date field month 01 12 and then year 2000 2250 Repeat this step until the desired date day month year is set 5 Press and hold the f9 key to accept the Day Date settings and to return to the setup menu AOP Reset WARNING The AOP reset function enables the deletion of all parameter sets and settings internal fault
22. election NOTES e If the selected parameter set already contains information the AOP prompts to clear the existing parameter set e Simultaneously press and when uploading to delete the existing parameter set e When viewing stored parameter sets press and display the software version number of the uploaded parameter set 3 The AOP prompts for confirmation Press confirm the process Press to cancel the upload process 4 The AOP displays a wait screen while the upload process occurs 5 Oncompletion of the upload process the AOP returns to the main menu Wait Request Certain tasks that the SED2 performs take longer than other tasks If this occurs a screen such as the following displays to inform you that the SED2 is completing a task Upread To Param Set 00 Please wait Parameter Download The download procedure writes a parameter set stored in the AOP to any SED2 VFD connected in local mode or to a single specified SED2 VFD on a network of SED2 VFDs connected in master mode In master mode the download procedure must select a specific SED2 VFD as the recipient SED2 VFD The download cannot simultaneously occur in all networked SED2 VFDs Use the following procedure to download a parameter set Siemens Building Technologies Inc 17 SED2 AOP Operating Instructions 1 From the main menu use and to scroll through the list of options and to highlight the Download item
23. election and the AOP displays a text screen with the first character highlighted The text string can contain a maximum of 20 characters Use and to scroll through the characters until the desired character is shown Press to accept the character and to advance to the next character Repeat this step until the desired text is entered Press and hold except the text string and to return to the setup menu Press and hold to cancel the text entry restore the original text string and to return to the setup menu NOTE Simultaneously press and any time to display relevant help screens Parameter Set Names Use the following procedure to edit the names associated with the ten AOP parameter sets NOTE This editing option is not available in the standard access level Use amp to highlight the Parameter Set Names option on the setup menu Press confirm the selection The AOP displays a parameter set name screen Use and to scroll through the parameter sets and to highlight the name needing editing Press to confirm the selected parameter set name and the AOP highlights the first character Use and to scroll through the characters until the desired character is shown Press to accept the character and to advance to the next character Repeat this step until the desired text is entered Press and hold except the text string and to return to the setup menu Press and hold to canc
24. erter In PC mode you can modify only the communications baud rate function 1 At the mode menu use EY and to scroll through the list of options until the desired operating mode is highlighted Siemens Building Technologies 19 SED2 AOP Operating Instructions 2 Press to confirm the selected operating mode press to return to the main menu NOTE To exit an operating mode either follow the on screen instructions or return to the main menu and select the mode menu to choose a different operating mode Operating in Local Mode On initial power up or after a reset the AOP defaults to the Local operating mode The Local mode operates only with one SED2 You can change the operating mode via the mode menu You can control the SED2 VFD by accessing all normal SED2 and AOP internal parameters Operating in Master Mode Individual Control of SED2 VFD In Master mode the AOP can control up to 31 SED2 drives that connect in a multi drop network arrangement Full operator control of each SED2 is possible with access to all normal SED2 parameters Control of the SED2 drives can be individually or by broadcast method 1 In master mode selecting Operate from the main menu displays an operation screen 2 Use to select a slave SED2 VFD A two digit number on the left hand side of the screen identifies each SED2 VFD In the top left hand corner of the screen an icon indicates the current operating status of
25. ing table describes the main menu items Menu Item Description Operate Displays the current status of the SED2 VFD motor Diagnostics Displays a recent fault history Parameters Allows you to select a parameter group similar to Parameter Filter POOO4 and to configure individual parameters Mode Allows you to select the AOP mode of operation as follows Local Master Internal Slave PC Mode Upread Allows you to read a parameter set from a SED2 VFD to the AOP upload Download Allows you to write a parameter set from the AOP to a SED2 VFD Language Allows you to select a new language for the AOP display Setup Allows you to customize the configuration of the AOP Timer Allows you to set a start and stop time for SED2 VFD operation 1 Use to scroll through the list of options and to highlight the Parameters item Press M to confirm the selection The AOP prompts to select the desired parameter group Use and Mo scroll through the list of options and to highlight the All parameters item Press f9 to confirm the selection NOTE AOP Parameters provides an overview of parameter access levels and a procedure for editing parameters 2 Use to scroll through the parameters and to highlight User Access Level P0003 Press to confirm the selection and the cursor advances to the parameter value Use 9 and 9 to set P0003 3 Expert Press to confirm the setting
26. lect ON for backlighting the AOP displays a backlighting timer screen The backlighting timer turns off the AOP backlighting after a specified time period of inactivity in seconds Use 9 and 9 to select either an OFF or ON timer function Press to confirm the selection NOTE When you select OFF for the backlighting timer the AOP returns to the setup menu and the AOP backlighting functions continuously Siemens Building Technologies AOP Setup 8 Configuration 4 When you select ON for backlighting timer the AOP displays a backlighting time setting screen Use to set the timer period of inactivity in seconds Press to confirm the setting and the AOP returns to the setup menu NOTE Simultaneously press LA at any time to display relevant help screens Screen Contrast 1 Use to highlight the Screen Contrast option on the setup menu Press confirm the selection The AOP displays a contrast screen 2 Use amp to adjust the contrast level Press to confirm the selection and the AOP returns to the setup menu Large Number Display You can configure the AOP for a large number display of the SED2 VFD frequency In the Large Number Display mode you can temporarily switch to normal display mode 4 lines with the keys and A After an adjustable time delay the display switches back to large characters Use the following procedure to activate the large number display 1 Use
27. limitations you should delete one of these languages in order to upload the specified ten parameter sets that can be held on the AOP To Delete a Language Select Language from the main menu highlight the language you want to delete and then press NOTE Once a language has been removed it cannot be restored Language selection is performed with the AOP online and connected to the SED2 After initial power up or after a reset and after the AOP performs internal self tests the AOP prompts you to select a language 1 From the main menu use to scroll through the list of options and to highlight the Language item Press confirm the selection The AOP displays the language selection screen 2 Use and 8 to scroll through and highlight the desired language Press to confirm the selection The AOP returns to the main menu Start Help 1 completion of the initial AOP self tests or if the Start Help feature is ON then the on line help screens display 2 If desired use to scroll through the help screens An arrow on the left hand side of the screen indicates if more information is available and the direction in which to navigate Use to move past the help screens and to go to the main menu Siemens Building Technologies Inc 7 SED2 AOP Operating Instructions Quick Commissioning NOTE Simultaneously press 8 and 8 at any time to display the main menu The follow
28. logies Inc branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous trouble free system performance For further information contact your nearest Siemens Building Technologies Inc representative CREDITS Product or company names mentioned herin may be the trademarks of their respective owners Copyright 2002 by Siemens Building Technologies Inc TO THE READER Your feedback is important to us If you have comments about this manual please submit them to technical editor sbt siemens com Printed in U S A C Ou LISTED European Low Voltage Directive The SED2 VFD product range complies with the requirements of the Low Voltage Directive 73 23 EEC as amended by Directive 98 68 EEC The units are certified for compliance with the following standards EN 60146 1 1 Semiconductor VFDs General requirements and line commutated VFDs EN 60204 1 Safety of machinery Electrical equipment of machine European Machinery Directive The SED2 VFD series does not fall under the scope of the Machinery Directive However the products have been fully evaluated for compliance with the essential Health amp Safety Requirements of the directive when used in a typical machine application A Declaration of incorporation is available on request European EMC Directive When installed according to the recommendations described in this guide the SED2 VFD fulfils all requiremen
29. m each day When multiple events must be cleared from the Timer function it may be easier to reset the AOP as described in the AOP Reset section When in Master mode of operation and viewing the connected SED2 drives a T displays in the top left corner to indicate that the connected SED2 drives are under timed remote control and may start or stop unexpectedly Setting the AOP Timer When in local or master mode you can access the timer feature from the main menu The timer operates as a 7 day time of day on off controller much like a central heating controller but with the addition of a possible multi VFD selection Function Moves down through the available choices of the highlighted field Moves up through the available choices of the highlighted field Press this key to confirm a changed field and to move the cursor to the next field Press this key for several seconds to move the cursor back to the previous field Cancels the entire timer event currently displayed Available USS SED2 drive network settings In Master mode 0 through 31 are selectable when the AOP detects the SED2 at that address Allows the programmed timing event to be communicated to all connected SED2 drives in broadcast mode This is the ON symbol and indicates that the currently viewed or programmed event is when the SED2 drive is switched on This is the OFF symbol and indicates that the currently viewed or
30. mounts directly onto one SED2 VFD and then scans its RS 232 and RS 485 ports to establish communications with the first port that answers You can control the SED2 VFD by accessing all normal SED2 and AOP internal parameters Local mode is the default of the AOP on initial power up or after a reset In Master mode the AOP can control up to 31 SED2 VFDs which connect in a multi drop arrangement An operator can control each SED2 VFD by accessing all normal SED2 and AOP internal parameters In Master mode the network controls the SED2 VFDS either individually or by broadcast operation A broadcast operation can simultaneously start or stop all networked SED2 VFDs In the Internal mode you can access the stored parameter sets in an AOP You can not access any parameter sets stored in the SED2 VFDs In the Internal mode the main menu includes an Engineering item This menu item allows you to view a USS message log of the last 1k bytes of messages between the AOP and the connected SED2 VFDs In Slave mode the AOP communicates with a PC using the AOP Desk Mounting Kit In this configuration the AOP acts as a slave to the PC At the PC you can upload and access parameter sets or the AOP internal parameter set as a USS address numbered 1 through 10 PC Mode Upload al 5 In PC mode the AOP is used with a Panel Mounting Kit to control a network or SED2 VFDs In this configuration the AOP acts as an RS 232 RS 485 conv
31. o scroll through the list of parameters and to highlight the desired parameter Press to confirm the parameter selection and the cursor advances to the parameter value 4 The AOP displays the values associated with the selected parameter Use and to change the parameter value as desired NOTE The AOP only accepts parameter values within a predefined range An out of range value is rejected and the AOP prompts you to enter a correct value Siemens Building Technologies 13 SED2 AOP Operating Instructions 5 Press to confirm the new parameter value The AOP returns to the parameter screen so you can select another parameter if desired Press to return to the r0000 display Press again to return to the previous menu Press for several seconds to return to the status screen normal operating mode The parameter value that has been changed is retained within the AOP s internal memory but not sent to the SED2 Should power to the SED2 or AOP be interrupted all changes are lost TIP How to quickly change parameter values To quickly change a parameter value use the following procedure to change the single digits of the display 1 Press and the right hand digit blinks 2 Press KO or to change the value of this digit 3 Press again and the next digit blinks 4 Perform Steps 2 and 3 until the desired value displays 5 Press to exit the parameter value NOTES 1 Simultaneously press 8 and 8
32. programmed event is when the SED2 drive is switched off 22 Siemens Building Technologies Timer Function In general use the following keys to set the timer Press to confirm the input and to scroll through input ranges Press to cancel the input and to return to the previous entry From the main menu use and to scroll through the list of options and to highlight the Timer item Press to confirm the selection The AOP displays the timer screen Use and amp to enable ON or disable OFF the AOP timer function lf the timer is enabled the cursor advances to the day of week field Continue with the next step If the timer is disabled simultaneously press and to return to the main menu Use J to scroll through and highlight the desired day of the week individually Sunday through Saturday or Every Day Press to confirm the selection and the cursor advances to the drive selection field Use and either input a drive number or select B for broadcast operations Press to confirm the input and the cursor advances to the time display divider field Use 9 to either select a diamond shape or a vertical line as the time display divider Press confirm the selection and the cursor advances to the time of day fields Use and amp increment the time of day input in the format HH MM SS where HH Hours 0 23 MM Minutes 0 59 and SS Seconds 0
33. s NOTES 1 If the AOP is the command source for the SED2 set USS Telegram Off Time for Serial Interface BOP Link P2014 1 5000 5 seconds To do this first set PO003 3 The P2014 1 5000 setting causes the drive to trip if communications with the AOP control source is lost 2 If you have problems connecting to the SED2 drives set the Auto Baud to OFF and the default baud rate to the same as the SED2 Single Drive Control Using the AOP Per default the AOP is configured to work with only one SED2 in Local mode In Local mode the AOP normally mounts directly onto the SED2 The RS 232 and RS 485 ports handle communications Full operator control of the SED2 is available with access to all normal drive and AOP internal parameters To configure a single SED2 VFD with the AOP as the control source follow the procedure in the Quick Commissioning section of this manual Network Setup RS 485 with Panel Mounting Kit The AOP has the capability to control up to 31 SED2 VFDs connected as a network In a network configuration a unique two digit number identifies each VFD When the AOP connects to a network of SED2 VFDs there are two Master Modes of operation e The AOP can access a single SED2 VFD on the network with full control parameter access e The AOP can use the Broadcast mode to simultaneously start stop all drives on the network Use the following procedure to set up a network of SED2 VFDs under control of an AOP 1 Use the s
34. s and message logs stored in the AOP 1 Use to highlight the AOP Reset option on the setup menu Press confirm the selection The AOP displays an AOP reset screen 2 Use and amp to select ON or OFF to enable or disable the AOP reset function respectively Press confirm the selection Press to cancel this selection and to return to the setup menu 3 When you select OFF the AOP disables the AOP reset function and returns to the setup menu When you select ON the AOP displays the parameter reset screen Press to confirm the AOP reset function and to delete all parameter sets internal faults and message logs The AOP then restarts Press to cancel this selection and to return to the setup menu without deleting any information The AOP then restarts NOTE Simultaneously press and at any time to display relevant help screens 28 Siemens Building Technologies AOP Faults 8 Warnings AOP Faults amp Warnings NOTE If a fault warning condition occurs on a SED2 VFD s to which an AOP connects a fault warning code displays with a description of the relevant fault warning For a list of fault warning codes see the SED2 VFD Operations amp Maintenance Manual Document No 125 3202 Fault Indication Fault Screen 1 If a fault condition occurs on a connected SED2 VFD s the AOP provides a fault message with specific information about the fault condition such as Identity of the SED2 VFD wi
35. ssioning with P3900 1 or all downloaded parameters are reset to their default values Memory Limitation The delivered AOP supports five European languages English German French Spanish and Italian Due to internal memory limitations you should delete one of these languages in order to upload the specified ten parameter sets that can be held on the AOP To Delete a Language Select Language from the main menu highlight the language you want to delete and then press NOTE Once a language has been removed it cannot be restored The upload upread procedure reads a parameter set from a SED2 VFD and stores that parameter set in the internal memory of the AOP The AOP can read from a single SED2 VFD in local mode or from one specific SED2 VFD on a network of SED2 VFDs in master mode Use the following procedure to upload upread a parameter set from a SED2 to the AOP 16 Siemens Building Technologies Editing Parameters 1 From the main menu use and to scroll through the list of options and to highlight the Upread item Press to confirm the selection Press to cancel the upload process The AOP displays an upload upread menu NOTE In master mode the AOP prompts for selection of a specific SED2 VFD from a list of the networked SED2 VFDs 2 Use and KA to scroll through the list of parameter sets and to highlight the parameter set into which information will be written Press confirm the s
36. synopsis of the SED2 VFD Bypass product line and technical data Siemens Building Technologies AOP Overview AOP Overview AOP Menu Structure The menus available on the AOP display depend on the currently active operating mode The following diagram shows the menu structure when the AOP is in either the Local or Master operating mode MAIN MENU Local and Master Modes OPERATE DIAGNOSTICS PARAMETERS MODE LOCAL 1 Drive UPREAD MASTER gt 1 Drive DOWNLOAD INTERNAL SLAVE PC MODE LANGUAGE _ ENGLISH GERMAN FRENCH SPANISH ITALIAN SETUP BACKLIGHTING TIMER SCREEN CONTRAST LARGE NUMBERS CURSOR TYPE START HELP WELCOME TEXT USER DEFINED TEXT PARAMETER SET NAMES SET TIME DATE AOP RESET Siemens Building Technologies SELECT GROUP ALL PARAMETERS NOT DEFINED INVERTER MOTOR SPEED SENSOR TECHNICAL APPLICATION UNIT NOT DEFINED COMMANDS BIN I O ADC AND DAC NOT DEFINED SETPOINT CHANNEL RFG NOT DEFINED DRIVE FEATURES MOTOR CONTROL NOT DEFINED NOT DEFINED NOT DEFINED NOT DEFINED NOT DEFINED NOT DEFINED COMMUNICATION ALARM WARNING MONITOR TECHNICAL CONTROLELR SED2 AOP Operating Instructions Key Functions NOTE Key Function this symbol is used throughout this manual to indicate a special keypad function Functional Description Stops the motor OFF1 Press this button to stop the SED2 within the selected ramp down time As part of the factory setting
37. t damage or loss of data may occur if you do not NOTES perform a procedure as specified no symbol Provides other important information or helpful hints Where To Send Comments Your feedback is important to us If you have comments about this manual please submit them to technical editor sbt siemens com Reference Documents The following SED2 VFD documentation is available from your local Siemens Building Technologies representative SED2 AOP Operation 8 Maintenance Manual 125 3202 operating instructions and procedures for the SED2 Variable Frequency Drive VFD SED2 VFD Operation 8 Maintenance Manual Addendum 125 3205 additional operation and maintenance information for the SED2 VFD such as use of filters and EMC compatibility SED2 VFD Installation amp Startup Guide 125 3201 a brief guide to operation offers fast access to all basic information necessary to install set up commission and operate a SED2 VFD SED2 VFD Technical Overview 153 026P25 a summary of the SED2 VFD product line and accessories features and functions and a list of technical data SED2 VFD Submittal Sheet 154 042 a two page synopsis of the SED2 VFD product line accessories and technical data SED2 VFD Bypass Options Technical Overview 153 170P25 a summary of the SED2 VFD Bypass product line features and functions and a list of technical data SED2 VFD Bypass Options Submittal Sheet 154 044 a two page
38. t history Simultaneously press and to display the help screen which contains details of the relevant corrective action Press and hold return to the main menu 30 Siemens Building Technologies AOP Faulis 8 Warnings Siemens Building Technologies Inc 31 SED2 AOP Operating Instructions Siemens Building Technologies Inc 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 Tel 1 847 215 1000 Fax 1 847 215 1093 Siemens Building Technologies Ltd 2 Kenview Blvd Brampton Ontario Canada L6T 5E4 Tel 1 905 799 9937 Siemens Building Technologies AG Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 Fax 41 41 724 35 22 Siemens Building Technologies Ltd 16 F Laford Centre 838 Lai Chi Kok Road Kowloon Hong Kong Tel 852 2917 5700 Fax 852 2904 1126 www sbt siemens com
39. t parameter set menu so you can select the desired parameter set 5 Use to scroll through the list of parameter sets and to highlight the desired parameter set number You can now edit parameters associated with the selected parameter set Editing Internal AOP Parameter Set 1 Set POOO3 3 expert parameter access level Siemens Building Technologies Inc 15 SED2 AOP Operating Instructions 2 Inthe Internal mode scroll through the list of parameter sets until the AOP parameter set appears Press to confirm the selection 3 Press again to select All parameters 4 Use to access the internal AOP parameters Internal parameters that display AOP information include Parameter Description Parameter Description P0964 Software Version Information P8562 Free Memory P8552 Base slave address P8563 Enable Text Scrolling P8553 Default baud rate P8564 RS 232 Error count P8564 Enable Autobaud P8565 RS 485 Error count P8560 Battery level P8566 Null USS Responses P8561 Enable Backlight P8567 USS Timeouts Parameter Upload Upread CAUTION 4 Upload Download Limitations The AOP will normally only upload and download parameters up to and including Level 3 When copying parameter sets between VFDs you must again complete the quick commissioning to re adjust the motor parameters Exit quick commissioning with P3900 3 for only motor data Do not exit quick commi
40. tandard panel mounting kit to connect RS 485 communications as follows a Correct wiring for PMK and SED2 VFD is as follows Pin 3 24V Pin 4 0V Pin 29 and 30 RS 485 communications b Use twisted pair cable or shielded cable preferred c The end of line SED2 VFD must have a 120 ohm terminating resistor across RS 485 Pins 1 and 2 Use a common ground for all SED2 VFDs and the e For the first issue of the PMK for correct communications DIP Switch 1 UP or ON on the PMK board Siemens Building Technologies 11 SED2 AOP Operating Instructions 6 7 Configure the SED2 VFDs for network use a Set the Command Source PO700 1 5 USS on Com link This sets the control over the USS link on the communications port b Assign each drive a unique RS 485 USS address in the range of 0 to 30 To do this set User Access Level P0003 3 expert and use USS Address for Serial Interface Com Link P2011 0 to assign a unique address to each SED2 VFD If using the AOP as the normal control means for the SED2 VFD it is recommended that USS Telegram Off Time for Serial Interface BOP Link P2014 1 5000 To do this first set User Access Level PO003 3 expert The P2014 1 5000 setting causes the drive to trip if communications with the AOP control source are lost With the SED2 VFDs powered up on the network connect and power up the AOP on the PMK On start up of the AOP select Mode from the main menu
41. ter to acknowledge each fault message Multiple Warnings If a SED2 VFD or network of SED2 VFDs reports more than one warning condition the AOP displays all warning messages by cycling through them until the conditions causing the warning messages cease to exist Simultaneous Faults and Warnings If a SED2 VFD or network of VFDs reports a fault condition and a warning condition the AOP displays all messages by cycling through them The AOP first displays a fault message and then a warning message separated by a 2 second interval This cycle continues until all fault and warning messages display The cycle repeats itself until all fault messages are either acknowledged or cleared and the conditions causing the warning messages cease to exist SED2 VFD Fault Warning Record P0947 For a VFD that connects to an AOP the diagnostic menu provides access to recent fault history In master mode a two digit USS slave address identifies each SED2 VFD NOTE Regarding fault history the AOP time display function is only available if the AOP was connected to the SED2 VFD at the time of the fault Use the following procedure to access the AOP diagnostics facilities 1 From the main menu use EY and to scroll through the list of options and to highlight the Diagnostics item Press confirm the selection 2 If no fault history exists press to return to the main menu If fault history exists use E and to scroll through the faul
42. th the fault condition Fault code number Plain text explanation of the fault condition 2 Proceed by doing one of the following Press to acknowledge the fault or Press to clear the fault and perform a manual restart of the SED2 VFD Clearing the fault may depend on the fault condition It may be necessary to investigate the cause of the fault Simultaneously press 9 to display a fault specific help screen to facilitate diagnosing the fault condition NOTE The AOP can only clear a fault if Command Source P0700 1 4 USS on BOP link or AOP Warning Indication Warning Screen 1 If a warning condition occurs on a connected SED2 VFD s the AOP provides a warning message with specific information about the warning condition such as Identity of the VFD with the warning condition Warning code number Plain text explanation of the warning condition 2 There is no requirement for you to acknowledge a warning message The message displays as long as the SED2 VFD reports the warning condition Simultaneously press and B to display a warning specific help screen to facilitate diagnosing the warning condition Siemens Building Technologies 29 SED2 AOP Operating Instructions Multiple Faults If a SED2 VFD or network of VFDs reports more than one fault condition the AOP displays all fault messages by cycling through them until they are all cleared See Fault Indication Fault Screen in this chap
43. this function is enabled for manual mode OFF2 Press this button twice or once with sustained pressure to cause the motor to coast freely to a standstill This function is enabled in the manual and automatic operating modes Starts the motor As part of the factory setting this function is enabled for manual mode Places the SED2 VFD in HAND mode Places the SED2 VFD in AUTO mode Increases the display value During parameterization this button increases the current value In manual mode this button increases the speed internal motor potentiometer Decrease the display value During parameterization this button decreases the current value In manual mode this button decreases the speed internal motor potentiometer Accesses the parameters Also exits a parameter by accepting its value Error Acknowledgement When a fault occurs and the SED2 VFD trips use this button to acknowledge the error Jump Function Press this key from any parameter rAXXX or PXXXX to return to the 0000 display Press this key again to return to the previous screen Press this key for several seconds to return to the status screen normal operating mode Main Menu Simultaneously press a at any time to display the main menu Help Simultaneously press ka at any time to display the relevant help screens Delete x Parameter While uploading a parameter set press and
44. ts of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems EN50082 2 Underwriters Laboratories UL and CUL LISTED POWER CONVERSION EQUIPMENT 5B33 for use in a pollution degree 2 ISO 9001 Siemens plc operates a quality management system which complies with the requirements of ISO 9001 Table of Contents Table of Contents How to Use this 1 Manual Organization Ss eee da Avka PE bay mas ka wae KERG 1 Manual 2 Where Send KA KA KA KAKA KA KA A KAR 2 Reference DOCUMENMS kalek kk y K ye kun HENA y KA cen ke dR RA ka H ka K hen HEKA k 2 AOP OVOHVIOW Ey ko kon kak at DEY yo SES VE ki dw L T 3 AQP Menu Structures Suya ala voi ao a tee ote OE 3 Koy FUNCUONS eee te tete nen kele bri adv an en tad ata dad edly bri a ra K kak 4 AOP Start Up amp Initialization 6 Mike net eden ieee nde sd aa Dean a din 6 Power on and Maliza orerar i R Hele a b ka k e b na KAW DIR 6 Language Selection
Download Pdf Manuals
Related Search
Related Contents
ASAHI Type 57 Butterfly Valve with Series 92 Electric Actuator USER GUIDE SPECIAL FUNCTIONS CONTROLS Super Talent Technology RAIDDrive II Plus Istruzioni per l`uso 1-AA-MD - Little Giant example: s 7 l – 3 RR 5200S - Crown Equipment Corporation bonsaiDRIVE manual - Rosendahl Studiotechnik Copyright © All rights reserved.