1. SOIPVE START UP OF GAS FIRED WATER HEATERS FOR DETAILED INFORMATION SEE INSTALLATION amp MAINTENANCE MANUAL a Visually inspect water heater and components for damage and proper installation Check all electrical connections for tightness and proper voltage Check water heater tank to make sure it is full of water Remove air through T amp P valve Pull nozzle assembly from burner and check gap settings on electrodes see I amp M While nozzle is removed look inside through burner for obstructions Check fan rotation Check air shutter setting guideline on burner tag ON OAR WD Drill hole in vent pipe 12 to 24 from heater flue outlet but below draft regulator for analysis equipment 9 Attach voltmeter to controller to record flame signal 10 Check inlet static gas pressure before gas train see rating on heater decal 11 Attach manometer to manifold to read pressure tapping closest to burner 12 Turn off main manual gas valve and start burner on pilot if burner has separate pilot a Set pilot to give good flame signal with just enough gas to reliably light pilot NOTE If there is no pilot set gas pressure guideline on burner tag b Slowly open main gas and set gas pressure guideline on burner tag c Check flame signal should be in range called for by control 13 Check inlet flow gas pressure before gas train NOTE Should meet or exceed minimum rating listed on heater decal 14 Check ven
2. r _ Outdoor Primary operating voltage VAC Voltage from neutral to earth ground should be zero Thermostat Setting F Thermostat Setting oF Hi Limit Setting F T amp P Relief Valve s plumbed to a suitable drain Yes No WATER HEATER INSTALLATIONS Type of piping connected to heater CI Copper Brass Galvanized Is there a check valve in the supply water piping LI Yes LI No Is there a water softener on the cold water supply LI Yes L No Operational Yes No Is there a mixing valve on the hot water supply If yes temperature setting F LI No Is there expansion relief in the cold water supply If yes what type _ tank valve LI No Is there a recirculation loop _ Yes Circulating pump horsepower LI No Is there a floor drain in the room _ Yes L No VENTING and COMBUSTION AIR Vent Material Vent Type L Through the roof _ Through Sidewall Vent Diameter inches Vent Length feet Does vent have elbows _ Yes Qty LI No Does vent have condensate drain Yes _ No Does vent contain any of these devices _ Power Vent _ Draft Inducer _ Draft Regulator _ Flue Damper Combustion air louvers or openings _ Yes Qty Size LI No Interlocked _ Yes No Have direct ducted combustion air _ Yes duct diameter inches Duct length feet CI No Duct Material Does duct have elbows _ Yes Qty CI No PV 17 8 05 817 335 9531 e 800 433 5654 e FAX 800 880 2019 e ww
3. t draft in stack should be negative 02 to negative 06 W C 15 Perform flue gas analysis after achieving water temperatures above 120F NOTE Modulating burners should be checked at 25 increments Net stack temperature should be 3 00F 400 F read in stack all units 2 2 O2 should be from 4 to 7 atmospheric units tested below draft diverter O I Nf CO2 should be from 8 to 10 atmospheric units tested below draft diverter Q CO should not exceed 200 PPM atmospheric units tested below draft diverter NOTE A complete and proper start up includes checking the operation of all controls and limits i e airflow switch LWCO thermostats and modulating controls and filling out the entire start up report All discrepancies should be reported to the PVI Customer Service Department 800 433 5654 from the job site and detailed on the comment section of the start up report Attach notes to report if needed Also please call if you have any questions or need assistance PVI Industries Incorporated Start Up of Gas Fired Water Heaters May 1998 PV 17 A OPVI START UP REPORT GAS FIRED NON CONDENSING WATER HEATERS Atmospheric MAXIM TURBOPOWER Warning Startup must be performed by a qualified service installer service agency or the gas supplier Model Number Serial Number Job Name Address GENERAL INFORMATION Restart Yes C No Installation is New _ Replacement Renovation Indoo
4. w pvi com Page 1 of 2 PVE Model Number Serial Number GAS SUPPLY Type of gas Natural C LP Gas Supply Pipe Size inches Inlet Static Gas Pressure W C 14 W C maximum Inlet Flow Gas Pressure W C See data label Combination Gas Pressure Switch Setting High Low____ W C COMBUSTION ANALYSIS BURNER MODEL NO BURNER SERIAL NO Low Fire Mid Fire High Fire For fixed rate burner use High Fire column Pilot Gas Pressure Manifold Gas Pressure Carbon Dioxide CO 8 9 Oxygen O 5 7 Carbon Monoxide CO less than 200 ppm Nitrogen Oxide NOx if available Vent Pressure 02 to 06 W C Gross Vent Temperature F less Room Temperature F Net Vent Temperature F Important You must submit the original copy of the completed form to your PVI representative before the warranty will become effective on this product Contact Customer Service for assistance at 1 800 433 5654 Comments Service Company Name Phone Service Company Address Start up Performed By Date Customer Representative Date PV 17 8 05 817 335 9531 e 800 433 5654 e FAX 800 880 2019 www pvi com Page 2 of 2

Download Pdf Manuals

image

Related Search

Related Contents

技術部Newsletter Vol.1    Clicca qui per scaricare il manuale dell`inserto a legna  08 0061.2130 HP_HPC_WEST_BA HP/HPC 12/04  (ICS) User Manual  未命名 -1 - Bclose  msk 528 ADDENDUM - Oehme  Frigidaire FFSG5115PA Product Specifications Sheet  SYBA SY-EXP15026  RCB7004  

Copyright © All rights reserved.
Failed to retrieve file