Home
LST MM-55000-833 User's Manual
Contents
1. Mini Monitor Module UMM 55000 833 e ADM loop technology with Apollo Discovery protocol e One line monitored input e Integration of contact detectors into the ADM loop e Output for optional remote indicator e Setting of module address by means of address switch e Small design Description The addressable Monitor Module UMM 55000 833 serves for the line monitored integration of contact de tectors such as manual call points sprinkler system contacts or supervising contacts into the bidirectional communication on the ADM loop with Apollo Discovery Specificatior protocol The address is easily selected by means of an integrated DIL switch which is accessible through an opening in the case The module provides 6 wires for establishing the desired connections An optional remo te indicator can be connected to the module Operating voltage Supply through loop voltage Current consumption 1mA quiescent Ambient temperature 20 C to 70 C Dimensions L x W x H 76 x 47 x 14 mm Colour white Weight 46g Order number 249061 Order name Monitor Module Anal XP95 Apo MM 55000 833 Building Safety Building Security d LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH A 1231 WIEN WIEGELESTRASSE 36 TEL 43 1 52114 0 FAX 43 1 52114 27 OFFICE LST AT WWW LST AT ALL RIGHTS RESERVED UMM 55000 833_DBL_LST_EN_0804 PDF PAGE 1