        Liebert GXTTM User's Manual
         Contents
1.   and allow at least  150mm  6inches  free space around the UPS  with a minimum of 300mm   12inches  at the back to enable easy operator access to the rear panel mounted  input output battery circuit breakers    Air vents are located at the front and the rear of the UPS  Do not position the  UPS in an enclosed space where airflow is restricted    Optional battery cabinets are designed to be placed on either side of the UPS   Electrical maintenance servicing requires access to both sides of the UPS   provide the necessary free space or use a flexible wiring system to allow the  UPS to be pulled forward    Maintain an ambient temperature range of 0    40   centigrade  32 104    F   NOTE  UPS operation in temperatures above 25  C  77  F  reduces battery life     16    AIRFLOW   DISSIPATION OUTPUT INPUT CURRENT    RATING Amps max  Cim   mh   Watts   KBtuhr   VA   Watts   vari Monina narge       130 221 504 1 7 6000 4200 GXT6000   33 amps  270 459 840 2 8 10000 7000 GXT10000  54 amps    ELECTRICAL INSTALLATION CONSIDERATIONS    This UPS must be installed by competent electrical personnel and wired in  accordance with local national electrical codes     The following information is provided for your guidance                                      WARNING  HIGH EARTH LEAKAGE CURRENT  EARTH CONNECTION IS  ESSENTIAL BEFORE CONNECTING THE MAINS SUPPLY  Earth in  accordance with local electrical codes           CAUTION  This UPS is fitted with EMC suppression filters  Earth leakage  excee
2.   through more than 100  service centres around the world  and a 24   hour Customer Response Centre     28     1 614 841 6755   1 614 841 5471     44 1628 403 200   33 1 4 360 26 19   49 21669649340   39 2 98250 1    00 31 475 504050  upstech liebert com  http   www  liebert com    While every precaution has been taken to  ensure accuracy and completeness of this  literature  Liebert Corporation assumes no  responsibility  and disclaims all liability for  damages resulting from use of this information  or for any errors or omissions           2001 Liebert Corporation All rights reserved  throughout the world  Specifications subject  to change without notice       Liebert and the Liebert logo are registered  trademarks of Liebert Corporation  All names  referred to are trademarks or registered  trademarks of their respective owners     SLI 23445  3 01  Rev  2    
3.  Operation at   and sound an alarm  51 75  loading   The display template indicates the   percentage of load on the output    CAUTION  The BYPASS power path does not protect the connected equipment  from disturbances on the mains supply         o T Bypass                      STARTING THE UPS    1  Ensure the load equipment is turned off  and all loads are properly  connected to the UPS output    2  Check that the mains wall isolator is ON  Turn On  Close  the Battery circuit  breaker  the Input and Output circuit breakers in that order   The UPS will now automatically start up and default to BYPASS mode once  the UPS is connected to an active AC mains supply and the Battery and Input  circuit breakers are closed  At the end of the startup sequence the BYPASS  LED should be lit    3  TO PROTECT YOUR LOAD YOU MUST NOW PRESS THE UPS  ON ALARM  BATTERY TEST BUTTON TO GO TO UPS MODE   4  Press the UPS ON ALARM  BATTERY TEST button for at least one half  second until you hear the audible alarm give a    Beep    to signal acceptance of  the command  After a delay of about 10 seconds  the BYPASS LED will  extinguish and the UPS ON LED should light  The UPS will then initiate a  self test and a battery test  When these tests are complete  the UPS is ready  for NORMAL UPS operation  Connected load equipment may now be started     POWERING DOWN THE UPS    1  Check to ensure that all connected load equipment is shutdown  Press the  OUTPUT OFF  BYPASS button until a    Beep    is heard  
4.  bypass due to output overload  beep every half second   A On bypass due to over temperature condition   beep every 4 seconds   B  On bypass due to DC bus over voltage  beep every 4 seconds   On bypass due to PFC failure  beep every 4 seconds   E  On bypass due to inverter failure  beep every 4 seconds   A amp C  UPS failed battery test  long beep every minute   Cae  UPS shutdown due to command from communication port     SNMP   no beep    The fault indicators will be illuminated indefinitely while battery charger is  operational  or for a maximum of 5 minutes while battery charger is not  operational  If a problem persists consult your dealer  or contact Technical    Support  World Wide Technical Support numbers are located at the end of this  manual     11    AUDIBLE ALARM CONDITIONS                            CONDITION ALARM  Battery mode  utility failure  One short beep every ten seconds  Low battery Two short beeps every five seconds  Output overload  bypass  One short beep every half second  Over temperature  bypass  One second beep every four seconds  DC Bus over voltage  bypass  One second beep every four seconds  PFC failure  bypass  One second beep every four seconds  Inverter failure One second beep every four seconds  Battery Test failure Two second beep every minute             TROUBLESHOOTING GUIDE       PROBLEM CAUSE SOLUTION  UPS fails to start when   UPS is short circuited   Ensure UPS is off  Disconnect  on button is pressed or overloaded all loads and ensur
5.  minimum 10 min  minimum           Recharge Time   Internal Batteries Only     7 hours to 95  capacity after full discharge into 100   load       ENVIROMENTAL       Operating Temperature    0  C to  40  C   32  F to  104   F        Storage Temperature     15  C to  50  C   5  F to  122 F        Relative Humidity    0  to 95   non condensing       Operating Elevation    Up to 3000 m  10 000 ft   at 40   C without derating       Storage Elevation    15 000 m  50 000 ft   maximum                               Audible Noise  lt 55 dB  A  at 1 metre  lt 65 dB  A  at 1 metre  AGENCY   Safety EN50091 1 1  TUV GS Listed  CE Low Voltage Directive  EMI EMC EN50091 2  Class A  CE EMC Directive  Immunity IEC 801 2  Level 4   IEC 801 3        Level 3    26    IEC 801       Level 4   IEC801 5 Level 3                LIMITED WARRANTY    Liebert Corporation extends the following LIMITED WARRANTY to  the purchaser and to its customer  collectively referred to as the   Purchaser      the enclosed Uninterruptible Power System  UPS  and  components are free from defects in materials and workmanship  under normal use  service  and maintenance FOR A PERIOD OF  TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from  Liebert or the Liebert dealer or retailer  THE FOREGOING  WARRANTY IS THE ONLY WARRANTY GIVEN AND NO OTHER  WARANTY IS PROVIDED  EXPRESS OR IMPLIED  INCLUDING  WITHOUT LIMITATION  MERCHANTABILITY OR FITNESS FOR A  PARTICULAR PURPOSE  Certain aspects of disclaimers are not  applicable to consu
6. EC 364 ELECTRICAL INSTALLATION  OF BUILDINGS    4  ELECTROMAGNETIC COMPATIBILITY  This UPS complies with the  requirements of the EMC Directive 89 336 EEC and the published technical  standards  Continued compliance requires installation in accordance with  these instructions and the use of manufacturer approved accessories only   WARNING  This is a CLASS A     Uninterruptible Power System Product  Ina  domestic environment  this may cause radio interference  in which case the  user may be required to take additional measures    5  Operate the UPS in an indoor environment only in an ambient temperature  range of 0  C to  40  C  32  F to  104  F   Install it in a clean environment  free  from moisture  flammable liquids  gasses  or corrosive substances    6  This UPS contains no user serviceable parts  The UPS ON OFF pushbuttons  do not electrically isolate internal parts  Under no circumstances attempt to  gain access internally  due to the risk of electric shock or burn   Do not continue to use the UPS if the front panel indications are not in  accordance with these operating instructions  or the UPS performance alters  in use  Refer all faults to your dealer    7  Only trained engineers authorised by Liebert should perform troubleshooting   To replace batteries  refer all servicing to qualified service personnel   PROPER DISPOSAL OF BATTERIES IS REQUIRED  REFER TO YOUR  LOCAL LAWS AND REGULATIONS FOR DISPOSAL REQUIREMENTS    8  Never block or insert any object into the vent
7. Low Voltage Directive  EMI EMC EN50091 2  Class A  CE EMC Directive  Immunity IEC 801 2  Level 4   IEC 801 3        Level 3    25    IEC 801       Level 4   IEC801 5 Level 3          SPECIFICATIONS    MODEL NUMBER    GXT6000T 230X GXT10000T 230X       MODEL RATING VAW  max     6000   4200 10000   7000       DIMENSIONS  mm  in                       Unit 260 x 555 x 803 340 x 650 x 960  WxDxH  10 5 x 22 0 x 31 5   13 5 x 25 5 x 38 0   Shipping 400 x 850 x 1065 510 x 840 x 1235  WxDxH  16 0 x 33 5 x 42 0   20 0 x 33 0 x 48 5   WEIGHT  kg  Ibs    Unit 139  306  244  538   Shipping 170  374  284  626        Input Output Connections    Hardwire terminal block       INPUT AC PARAMETERS        Voltage Range  typical     230 VAC nominal  variable based upon output load       100    90  Loading    186 VAC to 280 VAC   5 0 VAC       90    70  Loading    159 VAC to 280 VAC   5 0 VAC        70    30  Loading    139 VAC to 280 VAC   5 0 VAC        30    0  Loading    119 VAC to 280 VAC   5 0 VAC        Frequency    46 6     52 4 Hz or 57 1   62 9 Hz  auto sensing       OUTPUT AC PARAMETERS       Voltage    208 220 230 240 VAC  switch selectable    7        Frequency    50 Hz or 60 Hz  auto sensing       Waveform    Sinewave       Main Mode Overload    200  for 8 cycles  130  for 10 seconds with transfer to  bypass       BATTERY PARAMETERS        Type    Valve regulated  nonspillable  lead acid       Qty  x Voltage x Rating    20 x 12V x 7 0 Ah 40 x 12V x 7 0 Ah       Back up Time    Z min 
8. MiLiebert    UPStation GXT       6  amp  10 kVA                230V       USER MANUAL  English    i                IMPORTANT SAFETY INSTRUCTIONS    1  SAVE THESE INSTRUCTIONS  THIS MANUAL CONTAINS IMPORTANT  SAFETY INSTRUCTIONS  Read all safety and operating instructions before  operating the Uninterruptible Power System  UPS   Adhere to all warnings on  the unit and in this manual  Follow all operating and user instructions  This  equipment can be operated by individuals without previous training    2  This product is designed for Commercial Industrial use only  It is not intended  for use with life support and other designated    critical    devices  Maximum  load must not exceed that shown on the UPS rating label  The UPS is  designed for data processing equipment  If uncertain  consult your dealer   See Limited Warranty    3  This UPS is designed for use on a properly earthed  grounded   208 240  VAC  50Hz or 60Hz supply  for installation by qualified personnel  A qualified  electrician must review and approve customer supplied wiring  circuit  breakers  intended loads  and verify correct input  output and earth  connections to ensure compliance with technical standards and local  electrical codes of practice  Installation instructions and warning notices only  for use by qualified personnel are located after the UPS operator instructions  in this manual    WARNING  This UPS should not be supplied from electrical power systems  of the    IT     Imp  dance aTerre  type   I
9. Release the button  and then immediately press for at least one second  The UPS ON LED will  extinguish and the BYPASS LED will light for a short period then extinguish     When the AC input LED and the bottom LED of the BATTERY LOAD array  are lit and the UPS ON and BYPASS LED s extinguish  the output is powered  down    2  If necessary to isolate the UPS  set the input  output and battery breakers on    the rear of the UPS to OFF position  Finally for complete isolation turn OFF  the wall mounted mains isolator     SWITCHING FROM OUTPUT OFF TO UPS or UPS to BYPASS to OFF    1  Ifthe UPS is in OUTPUT OFF condition  with all rear mounted breakers in the  ON position  and the AC input LED and the bottom LED of the  BATTERY LOAD array lit  To go to UPS mode  press the UPS ON ALARM  IBATTERY TEST button until a    Beep    is heard  The UPS will then go  through its start up routine ending up after approximately 10 seconds with the  UPS LED lit       If the UPS is operating in UPS mode and there is a need to go to BYPASS   mode  press the OUTPUT OFF BYPASS button until a beep is heard  The  UPS ON LED will extinguish and the BYPASS LED will be lit    WARNING  In BYPASS mode your connected load is NOT PROTECTED  from mains disturbances    If you are in BYPASS mode and want to set the OUTPUT to OFF  Press the  OUTPUT OFF  BYPASS button for a least 1 second  twice  within a 4 second  time interval  There is no audible    Beep    on this action     OPERATION IN BATTERY MODE    If in 
10. Station GXT provides an alternate path for mains power to the connected  load  in the unlikely event of a UPS malfunction  Should the UPS have an  overload  over temperature  or UPS failure condition  the UPS automatically  transfers the connected load to BYPASS providing the bypass voltage is within  specification  BYPASS operation is indicated by an alarm and an illuminated  BYPASS LED  other LED s may be illuminated to indicate the diagnosed  problem   To manually transfer the connected load from the inverter to BYPASS  power  press the output OFF button once    NOTE  The BYPASS power path does NOT protect the connected equipment  from disturbances on the mains supply and its range of operation is limited to      15  of the nominal input supply voltage     AUTO RE START   Upon restoration of the mains AC power after a mains power outage and  complete battery discharge  the UPS will automatically restart and supply power  to the critical load and the battery charger automatically recharges the battery     CONTROLS AND INDICATORS    Fault Indicator                UPS ON     D BYPASS  Alarm Silence    Manual Battery Test    ves on  Output OFF   D BATTERY  Bypass             D ac neur       Load   Battery Level  Indicators    Fault Indicator  Red    The Fault indicator is illuminated if the UPS has detected a problem  Also  one or  more of the load battery level indicators may be illuminated  refer to  Troubleshooting Guide      BYPASS Indicator  Amber    The BYPASS indicator 
11. TEST pushbutton to  carry out battery test and ensure the load can be supported  Note  Full  battery capacity will not be available until a battery recharge cycle has been  completed    The UPS is now ready for service In case of problems refer to the fault finding  section or call your local distributor for advice     23    Battery Run Times                                                                         Load   6kVA 6kVA    1  6kVA    2   GXT240VBATT _GXT240VBATT  10  69 250 360  20  58 197 301  25  52 174 278  30  48 155 248  40  33 117 190  50  23 88 140  60  17 73 110  70  14 60 94  75  12 54 85  80  11 50 77  90  9 42 68  100  8 37 59  Load Yo 10kVA 10KVA    1  10KVA    2   GXT240VLRT GXT240VLRT  10  71 480 900  20  60 390 730  25  55 345 655  30  49 305 585  40  39 230 450  50  29 164 335  60  23 129 265  70  20 105 225  75  18 93 205  80  17 85 190  90  14 70 155  100  12 60 125                      Note  All run times are in minutes  assume fully charged batteries  and  are typical at 25  C  77  F  with resistive loads     24    SPECIFICATIONS    MODEL NUMBER    GXT6000T 230 GXT10000T 230       MODEL RATING VA W  max     6000   4200 10000   7000       DIMENSIONS  mm  in                       Unit 260 x 555 x 803 340 x 650 x 960  WxDxH  10 5 x 22 0 x 31 5   13 5 x 25 5 x 38 0   Shipping 400 x 850 x 1065 510 x 840 x 1235  WxDxH  16 0 x 33 5 x 42 0   20 0 x 33 0 x 48 5   WEIGHT  kg  Ibs    Unit 99  218  187  412   Shipping 130  288  227  500        Input Output C
12. box   see outline drawing  The cable box can be  removed to enable knockouts to be removed or new holes drilled  to secure the  cables    The cable sizes and distribution methods used during installation are subject to  local  national electrical codes of practice   and therefore are not detailed here   However  table 1 gives details of the input current and the UPS rating plate gives  details of the output current according to output voltage selected     The terminals will accept wire sizes up to the values below     GXT6000   10 mm   GXT10000   16mm     18    Connecting the UPS Power cables   Power cables connect to screw terminals on a terminal block that is located  behind the rear mounted cable box  see figure   The cables enter the UPS  through a Gland Plate attached to the rear of the UPS  The Gland Plate must first  be removed and drilled to suit the glands or bushes for the cables used  Ensure  that the glands are sized so that they hold the cables securely        UPS Power Section                                                                                                       1  11  5 G  aw    INPUT OUTPUT EXTERNAL BATTERY  Oinie N L TT    To Mains To Load To External Battery    Optional   6kVA 10kVA   aan Se       GXT 6 10 kVA Connection Diagram  Connection of optional remote battery cabinets     Full installation instructions are provided with these cabinets  Safety EMC  certification limits the use of these terminals to Liebert supplied options     Output co
13. ds 35mA  Transient and steady state earth leakage currents   which may occur when starting the UPS  should be taken into  account when selecting instantaneous RCCB or RCCD devices  Note  also that the earth leakage currents of the load will be carried by this  RCCB or RCCD           WARNING  This UPS does not incorporate automatic backfeed protection   A warning label must be fitted to all primary power isolators stating   ISOLATE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON  THIS CIRCUIT              On start up  the UPS will take a half cycle inrush current of up to 3 times the  rated current  This must be taken into account when selecting the overload  protection device at the input mains supply distribution point  To avoid random  tripping on start up  we recommend that the input mains supply be protected with  an MCB capable of withstanding this initial inrush  An MCB specified as being     TYPE 4     British standard  or    CURVE D     IEC standard  is suitable for this  purpose     The mains input supply cable must be connected to the UPS via a wall mounted  double pole circuit breaker  rated to carry the current in table 1 and be capable of  breaking the maximum prospective short circuit current of this branch circuit  The  breaker is to be mounted within two metres of the UPS and be readily accessible  to the operator     17    ELECTRICAL CONNECTIONS    The UPS is supplied with an input output  battery terminal block assembly on the  rear of the UPS within a cable 
14. e nothing is    lodged in output terminal block   Ensure loads are not defective  or shorted internally    Internal fuse is blown    Do not attempt to open or  indicating internal fault   service the UPS  Contact your  dealer or technical support                 Breaker not closed or   Close breaker or remove  has tripped  overload   Battery indicator is UPS input not UPS is operating from battery  illuminated connected mode  make certain UPS is  securely connected to source   UPS input protection UPS is operating from battery  has opened mode  Save data and close    applications  Replace UPS  input fuse or reset input  breaker  then restart UPS   Mains voltage out of UPS is operating from battery  UPS input range  mode  Save data and close  applications  Ensure mains  supply voltage is within  acceptable limits for UPS                             UPS has reduced Batteries not fully Apply input voltage for at least  battery time charged 24 hrs to recharge batteries   UPS is overloaded Check load level display and  reduce load level  Batteries may not be Replace batteries  Contact  able to hold a full your dealer or technical  charge due to age Support     12    TROUBLESHOOTING GUIDE                         PROBLEM CAUSE SOLUTION   Fault and Bypass UPS overloaded or load   Check load level display and   indicators andallload   equipment is faulty remove non essential loads    level LED s are Recalculate load VA and   illuminated reduce number of loads  connected to UPS  Check 
15. e snaps closed with the cable  routed inside the ferrite bead   s case     22    COMMISSIONING THE UP     Output Voltage Selector Switches    The Output Voltage Selector Switches  located on the rear of the UPS  are  designed to allow selecting or changing the desired output voltage to match the  mains  The settings to choose from are 208  220  230  and 240 VAC output        230  amp  230X Units    208 V A    both switches up   220 V AN  first switch up  second down   230 V VV   both switches down  Factory Default   240 V YA   first switch down  second up       NOTE  NEVER change the switch settings while UPS is on and powering  connected loads     NOTE  Setting output voltage to 208 VAC will cause UPS unit to be derated to  90  of the VA and Watt rating listed in specification section     1  Adjust the output voltage switch settings to the desired value     2  Follow the instructions for Powering up the UPS referenced earlier in this  manual  Sequence through the operating modes  using the front panel  pushbuttons  in accordance with operating instructions to check functionality  of the UPS     3  Set the UPS to UPS mode  Check on the output terminals of the UPS  for the  correct output voltage for the voltage rating of the intended loads    4  Check operation of the remote shutdown circuit  If fitted     5  In UPS mode  power up customers load and check that it is within the UPS  rating by observing the front panel LED   s    6  In UPS mode  press the UPS ON ALARM  BATTERY 
16. ed in the following  pages  however  you should give some consideration to the proposed  environment in which the UPS is to be installed  and carry out some preparatory  work     INSPECTION    Before you install the UPS  give it a thorough visual examination to ensure it has  not been subjected to shipping damage  If it is not in perfect condition  you  should advise both the shipper and the supplier immediately  DO NOT  ATTTEMPT TO INSTALL A DAMAGED UPS     Check the UPS rating plate that the UPS is suitable for operation on your mains  voltage and load voltage requirements   Before disposing of the UPS packaging  check that you have removed to a safe    place the user manual and any other items shipped with the unit to be used in its  installation        CAUTION   GXT6000 UPS weighs up to 139kg   GXT10000 UPS weighs up to 244kg   Use adequate handling aids when moving or installing the UPS   The UPS is fitted with castor wheels for easy movement  Take care when the  UPS is removed from its packing and being wheeled across an uneven floor  without the stabilisers fitted  that it does not tip over  See notes on  adjustment of levelling feet and stablisers              LOCATION    Locate the UPStation GXT indoors in a controlled environment  where it cannot  be accidentally disconnected  Locate it in an area with unrestricted airflow  away  from water  flammable liquids  gases  corrosives  or conductive contaminants   Give consideration to the airflow requirements   see below 
17. fication    Timed and delayed shutdown of the UPS     Logging of power disturbances and anomalies    Consult your local Liebert sales representative for more information about  SiteNet   2 software     UPS INTELLISLOT    COMMUNICATIONS    The UPStation GXT UPS contains an Intellislot    communications port for the  optional internal MultiPort 4 card  AS400 card  or Ethernet SNMP card  Optional  SiteNet   SNMP Manager software is available to allow communication through  several network management systems to be used in conjunction with the  Intellislot SNMP card  Contact your local Liebert representative  dealer  or  reseller     14    MAINTENANCE    The UPStation GXT UPS requires very little maintenance  The batteries are  valve regulated  non spillable  lead acid  and should be kept charged to obtain  their designed life  The UPS continuously charges the batteries when connected  to the mains supply     When storing the UPS for any length of time  it is recommended to apply power  to the UPS for at least 24 hours every four to six months to ensure full recharge  of the batteries  In no case should the unit be stored in excess of nine months  without recharge  Periodically  examine the vents on the front and rear of the  cabinet  and remove any obstructions from the surface of the vents     15    INSTALLATION INSTRUCTIONS    These instructions are for use by competent personnel only     INSTALLATION CONSIDERATIONS   Detailed instructions to help you install the UPS are provid
18. il mechanically unlatched by hand     Note   The wiring for remote stop contacts pins 5 and 6 of the DB9 connector are  defined as SELV   When connecting to a stop button interfacing with other mains  emergency stop circuits  keep wiring segregated from other power wiring     21    FERRITE BEAD INSTALLATION    When using either of the options below  to reduce the risk of radio interference  fit  the ferrite assemblies supplied with the UPS as follows     Serial Communications    Attach the smaller enclosed ferrite bead clamp to the communication cable as  shown in the drawing using the following directions     e Open the ferrite bead   e Place the communication cable  inside the ferrite bead groove      e Position the ferrite beads as  close as possible to the end of  the cable that connects to the  DB9 connector of the UPS   e Close the ferrite bead so that the  gt   ferrite bead   s case snaps closed  with the cable routed inside the  ferrite bead   s case     Clamp bead with cable  nn enclosed       SNMP Installation   When fitted    Attach the larger enclosed ferrite d   bead clamp to the network cable as   shown in the drawing using the   following directions  Wrap cable once    around ferite bead  Open the ferrite bead     Place the network cable inside the ferrite bead groove    Wrap the cable once around the bead    Position the ferrite cable as close as possible to the end of the cable that  connects to the UPS    Close the ferrite bead so that the ferrite bead s cas
19. ilation holes or other openings    9  DO NOT CONNECT equipment that could overload the UPS or demand DC  current from the UPS  for example  electric drills  vacuum cleaners  laser  printers  hairdryers or any appliance using half wave rectification     10 Storing magnetic media on top of the UPS may result in data loss or  corruption     11 Turn the UPS off and isolate the UPS before cleaning  Use only a soft cloth   never liquid or aerosol cleaners     OSSARY OF SYMBO    Indicates AC Input    Indicates Caution  Note the accompanying instruction       Indicates the position of a fuse    Requests the user to consult the manual for additional  information        Indicates AC Output     AA               gt     gt  bid Indicates that the unit contains a valve regulated lead acid battery       INTRODUCTION AND SYSTEM DESCRIPTION    Congratulations on your choice of the UPStation GXT    Uninterruptible Power  System  UPS   It provides conditioned power to microcomputers and other  sensitive electronic equipment     Upon generation  AC power is clean and stable  However  during transmission  and distribution it may be subject to voltage sags  spikes  or complete power  failure  which may interrupt computer operations  cause data loss  or even  damage equipment  The UPStation GXT protects equipment from these  disturbances     The UPStation GXT is a compact     on line    UPS  An    on line    UPS continuously  conditions and regulates its output voltage  whether the mains power is p
20. ions  network servers  or UNIX hosts via the DB 9  socket located on the rear of the UPS    This capability is used in applications requiring the UPS to provide status and  power monitoring information to the computer system  For example  during a  mains power failure  the information can be used by the computer s operating  system or application program to automatically save information in buffers  to  close files  and shut down operations prior to battery capacity depletion   Monitoring of the UPS via a computer is as easy as downloading SiteNet    MultiLink    free from our web site  www liebert com   A MultiLink cable may also  be built by following instructions provided on our web page  You may also  purchase a Liebert SiteNet   1 shutdown kit  sold separately   Consult your local  Liebert representative to determine the correct software kit for your application   The kit includes shutdown software and a special purpose cable     UPS INTELLIGENT COMMUNICATIONS    The UPStation GXT UPS has the capability to communicate intelligently with  stand alone computers  network workstations  network servers  or UNIX hosts via  the DB 9 socket located at the rear of the UPS  By purchasing the optional  Liebert SiteNet   2 software package  sold separately   intelligent  communications allows the following capabilities       Guantitative monitoring of mains and UPS power     Quantitative monitoring of internal UPS parameters     Periodic tests of battery quality and replacement noti
21. is illuminated when the UPS is operating from BYPASS  power  An alarm will sound indicating the UPS detected a problem  or manually  set to BYPASS     UPS ON Indicator  Green   The UPS On indicator is illuminated when the UPS inverter is operating and  supplying power to your connected loads     Battery Indicator  Amber   The Battery indicator is illuminated when the UPS is operating from the battery  system     AC Input Indicator  Green   The AC Input indicator is illuminated when mains power is available and within  the input specification     Load Battery Level Indicators  4 Green  1 Amber    The Load Battery Level indicators have dual functions  During NORMAL mode  operation LED indicators display the approximate electrical load placed upon the  UPS  and during battery mode operation LED indicators display approximate  battery capacity     The UPStation GXT is equipped with automatic and remote battery test features   The automatic test occurs every 14 days if a manual battery test has not been  performed or if mains has not been interrupted  14 day timer resets if unit goes to  battery   Should the battery fail this test  the fault indicator along with the A and  C diagnostic LEDs will illuminate and an alarm will sound  refer to  Troubleshooting Guide   The remote test feature functions with either SiteNet   2  or SiteNet   SNMP Manager software and can remotely initiate the battery test     UPS ON Alarm Silence Manual Battery Test Button   This button controls output p
22. justment Diagram    20    COMMUNICATIONS INTERFACE PORT    The UPStation GXT UPS contains a standard DB 9 socket located on the rear of  the UPS unit  Several signals are provided on this port and are assigned as  follows     PIN ASSIGNMENT DESCRIPTION    Low Battery  open collector   UPS TxD  typical RS 232 levels    UPS RxD  typical RS 232 levels    Remote Shutdown  5 12V   battery operation   Common   Remote Shutdown  short to pin 5  UPS mode  all modes  of operation  Low Battery  open emitter    Mains Fail  open emitter    Mains Fail  open collector                                      co I lo ja  a fo fro f        PIN ASSIGNMENT COLLECTOR TO EMITTER               Maximum voltage and current on pins 1 7 8 9 is 80V DC  10 0 mA     CAUTION  TO MAINTAIN SAFETY  SELV  BARRIERS AND FOR  ELECTROMAGNETIC COMPATABILITY  SIGNAL CABLES SHOULD BE  SEGREGATED AND RUN SEPARATE FROM ALL OTHER POWER CABLES   BY 25mm WHERE APPLICABLE     UPS Remote shutdown option     Shorting pins 5 and 6 on the DB9 connector will shutdown the UPS output in any  mode of operation  Removing the short circuit  the UPS will automatically auto   restart     Where there is a requirement for a remote shutdown of the UPS to meet fire or  other local safety codes  it is necessary to interrupt  at the same time with the  same pushbutton  all mains input supplies to the UPS  The pushbutton that  provides the UPS remote shutdown must be of the stay down type   Latching  to  keep a short circuit on pins 5 and 6 unt
23. load  equipment for faults    Fault and Bypass UPS intemal fan hasa   Press Alarm silence button    indicators and problem or UPS Once the temperature is   diagnostic LED Aare   shutdown due to reduced  the UPS will restart   illuminated temperature condition    and transfer the connected   Load is on bypass equipment to inverter power  power  automatically    Fault and Bypass UPS Internal DC bus UPS requires service  Contact   indicators and over voltage your dealer or technical   diagnostic LED B are support    illuminated   Fault and Bypass UPS PFC fault  UPS requires service  Contact   indicators and your dealer or technical   diagnostic LED D are support    illuminated   Fault and Bypass UPS inverter fault  UPS requires service  Contact   indicators and your dealer or technical   diagnostic LED E are support    illuminated   Fault indicators and UPS failed the battery   Replace batteries  Contact   diagnostic LEDA  amp C   test  your dealer or technical   are illuminated support    Fault indicators and UPS shutdown due toa   Your UPS has received a   diagnostic LED C  amp E   command from the signal or command from the   are illuminated communications port s    attached computer  If this was  inadvertent  ensure the  communication cable used is  correct for your system  For  assistance  contact your dealer  or technical support                 13    UPS MONITORING    The UPStation GXT UPS has the capability of being monitored with stand alone  computers  network workstat
24. mer products acquired by individuals and used for  personal  family  or household purposes  as distinguished from  industrial or other purposes   Local laws may not allow limitations on  how long an implied warranty lasts  so the above limitation may not  apply to you  This warranty gives you specific legal rights  and you  may have other rights which vary according to local law     Certain repairs or services are the responsibility of the Purchaser and  the Purchaser is expected to pay for them  This warranty does not  extend either to products with removed or altered serial numbers or to  any losses or damages due to act of God or source external to the  product  misuse  accident  abuse  neglect  negligence  unauthorised  modification  alteration  or repair  use beyond rated capacity  or  improper installation  maintenance  application or use  including   without limitation  use in a manner contrary to the accompanying  instructions or applicable codes  WARNING  Warranty is void if the  battery is allowed to discharge below the minimum battery cut off  point  The battery must be recharged every four  4  to six  6  months  when not in use     If the UPS fails to conform with the above warranty within the two year  warranty period  Liebert will repair or replace the UPS  at Liebert s  option  Repairs or replacements are warranted for the remainder of  the original warranty period  Purchaser  to make a warranty claim   should call to obtain a Returned Goods Authorisation numbe
25. nnections GXT 6000 10000 X models only    Models whose part number ends with an    X    are fitted with an isolating output  transformer  The output of this transformer is referenced to earth at the neutral  terminal  remove this earth neutral link when required by local electrical codes     19    Stabilisers Levelling Feet    When the UPS is located in its final position before or after wiring  it is necessary  to fit stabiliser brackets and  if necessary  adjust the levelling feet  If the UPS is  wired using a rigid wiring system  then movement of the UPS must be prevented  by winding down the 4 levelling feet under the UPS as shown below  For UPS  wired with flexible cables  this is optional  Note  Access to the levelling feet is  obstructed by the stabiliser brackets  on the GXT10000 models     Adjust the levelling feet as necessary using a 12mm open ended   spanner wrench  DO NOT LOOSEN THE LARGER NUT ABOVE  AS THIS   FIXES THE LEVELLING FEET TO THE CHASSIS    Attach the stabilising brackets as follows    GXT6000 models    1  Using a Phillips head screwdriver  remove the screws 4  from each of the  bottom corners of the side panels    2  Attach the stabilising brackets to each corner using screws just removed     GXT10000 models     1  Using a Phillips head screwdriver  remove the three inner most screws at  the base of both side panels    2  Attach the stabilisers fixing with the screws just removed     im   Ni    6 kVA                                  Levelling Feet Ad
26. ocedures on connected loads before pressing this  button twice     GXT 6  amp  10 kVA    Component Diagram  230  amp  230X Models Shown    Intellistot     Communications  Port    DB 9  Communications  Port    Er     Output Voltage    Selector Switches          Input  Breaker    Battery Output  Breaker Breaker                                              Hardwire  Terminal Blocks                         Intellislot    DB 9  Communications Communications  Port     Port             a    Output Voltage  Selector Switches        Breakers                               Battery   Input Output    Breaker 7 o te                      Hardwire  Terminal Blocks                   E    Adjustable levels    OPERATING MODES    NORMAL MODE OPERATION  UPS mode    During normal operation  mains power provides energy to the UPS  The filters     the power factor correction circuit and  the inverter process this power to  provide computer grade power to  connected loads  The UPS maintains  the batteries in a fully charged state     The four green LED   s indicate an  approximate level of load in 25   increments  If the UPS becomes  loaded beyond full rating  the fifth   amber  LED indicator will illuminate  and sound an alarm     The display template indicates the  percentage of load on the UPS output     BATTERY MODE OPERATION  Battery mode occurs in event of an  extreme input voltage condition or  complete mains failure  The battery  system supplies power through the  DC DC converter to the inver
27. onnections    Hardwire terminal block       INPUT AC PARAMETERS        Voltage Range  typical     230 VAC nominal  variable based upon output load       100    90  Loading    186 VAC to 280 VAC   5 0 VAC       90    70  Loading    159 VAC to 280 VAC   5 0 VAC        70    30  Loading    139 VAC to 280 VAC   5 0 VAC        30    0  Loading    119 VAC to 280 VAC   5 0 VAC        Frequency    46 6     52 4 Hz or 57 1   62 9 Hz  auto sensing       OUTPUT AC PARAMETERS       Voltage    208 220 230 240 VAC  switch selectable    3        Frequency    50 Hz or 60 Hz  auto sensing       Waveform    Sinewave       Main Mode Overload    200  for 8 cycles  130  for 10 seconds with transfer to  bypass       BATTERY PARAMETERS        Type    Valve regulated  nonspillable  lead acid       Qty  x Voltage x Rating    20 x 12V x 7 0 Ah 40 x 12V x 7 0 Ah       Back up Time    Z min  minimum 10 min  minimum           Recharge Time   Internal Batteries Only     7 hours to 95  capacity after full discharge into 100   load       ENVIROMENTAL       Operating Temperature    0  C to  40  C   32  F to  104   F        Storage Temperature     15  C to  50  C   5  F to  122 F        Relative Humidity    0  to 95   non condensing       Operating Elevation    Up to 3000 m  10 000 ft   at 40  C without derating       Storage Elevation    15 000 m  50 000 ft   maximum                                Audible Noise  lt 55 dB  A  at 1 metre  lt 65 dB  A  at 1 metre  AGENCY   Safety EN50091 1 1  TUV GS Listed  CE 
28. ower to connected load s  and has three functions   UPS ON  Alarm Silence  and Manual Battery Test   To start the UPS  while in the BYPASS mode  press this button until the  command is acknowledged by a beep from the audible alarm  This will provide  conditioned and protected power into the output terminal block    To silence alarms  press this button for at least one half second while alarm  conditions are present  After the alarm is silenced  the UPStation GXT will  reactivate the alarm system to alert of additional problems    NOTE  The low battery and BYPASS reminder alarms cannot be silenced   BATTERY TESTING  To initiate a manual battery test  press this button for at  least one half second while operating in normal UPS mode power and no alarm  conditions are present  If the bottom two LED s do not illuminate during a Battery  Test  allow the UPS to recharge the batteries for 24 hours  After 24 hours  retest  the batteries  If the batteries have been re tested and the bottom two LED s still  do not illuminate  contact your dealer or Global Services for a battery  replacement     OUTPUT OFF BYPASS Button   This button controls output power to connected load s  and has dual functions   OUTPUT OFF and Bypass    CAUTION  Pressing this button once during normal operation will cause the load  to be transferred to BYPASS power  Pressing this button a second time within 4  seconds will result in loss of power to the output and connected loads  Perform  all necessary shutdown pr
29. r and  shipping instructions  Return transportation costs to Liebert are the  responsibility of the Purchaser      LIFE SUPPORT  APPLICATIONS    Due to the diversity of applications and considerations to be applied in  each case  Liebert does not recommend or knowingly sells its  products for such use    The responsibility for risk assessment and management in applications  where the malfunction or failure of the UPS could be reasonably  expected to give rise to a risk of human life shall be the sole  responsibility of the purchaser  Liebert accepts no liability for  consequential harm in such applications           27       MiLiebert    UPStation GXT          6  amp  10 kVA  230 V          Technical Support       Worldwide Support  Worldwide Fax Tech Support    UK    France  Germany  Italy  Netherlands  E mail  Web site    The Company Behind The Products    With more than 500 000 installations around  the globe  Liebert is the world leader in  computer protection systems  Since its  founding in 1965  Liebert has developed a  complete range of support and protection  systems for sensitive electronics     Environmental systems  close control air  conditioning from 1 5 to 60 tons     Power conditioning and UPS with power  ranges from 250 VA to more than 1000 KVA     Integrated systems that provide both  environmental and power protection in a  single  flexible package    Monitoring and control     on site or remote      from systems of any size or location   Service and support
30. resent  or not  It supplies connected equipment with clean sinewave power  Sensitive  electronic equipment operates best from sinewave power  The GXT  6000 10000T 230X models have an additional output isolation transformer     For ease of use  the UPStation GXT contains a light emitting diode  LED  display  to indicate either    load percentage    or    battery capacity  depending upon the  mode of operation  It also provides self diagnostics  a combination On Alarm  Silence Manual Battery Test button  a combination Off Bypass button  and two  levels of alarms when the unit is operating on battery     The UPStation GXT has an interface port for communications between the UPS  and a LAN server or other computer system  This port provides detailed  operating information including voltages  currents  and alarm status to the host  system when used in conjunction with the SiteNet   2 software  SiteNet   2  software can also remotely control UPS operation     MAJOR COMPONENT     Output Transformer    HZ an    Battery   4  Charger                                                             TRANSIENT VOLTAGE SURGE SUPPRESSION  TVSS  AND EMI RFI  FILTERS    These UPS components provide surge protection  and filter both electromagnetic  interference  EMI  and radio frequency interference  RFI   They minimize any  surges or interference present in the mains line and keep the sensitive  equipment protected     RECTIFIER POWER FACTOR CORRECTION  PFC  CIRCUIT   In normal operation  the rec
31. ter to  generate power for the connected  load    During battery mode an alarm sounds  every 10 seconds  This will change to  2 beeps every 5 seconds when battery  runs low  approximately 2 minutes  remaining   The AC Input LED will  extinguish  and the Battery LED will  illuminate to warn that a mains problem    N  Fat        e    Bypass       Dang ups             Is          Normal Mode Operation at  51 75  loading    N il Fault       To    pypass       Jo  l ups          Bows Deartery       Joon          AC    Hoss INPUT    Battery Mode Operation at  81 100  battery capacity    has occurred  Each load battery level indicator represents a 20  capacity level   As capacity decreases  fewer indicators remain illuminated  Refer to the    Troubleshooting Guide     To increase this time  turn off non essential pieces of equipment  such as idle  computers and monitors  or add an optional external battery cabinet     CAUTION  Turning off the UPS while in battery mode will result in loss of output    power     Once mains power is restored  the UPS resumes normal operation  At this time   the Battery Charger begins recharging the battery     BYPASS MODE OPERATION N 0 Fault  During BYPASS operation  mains  power provides energy to your load  and maintains the batteries in a fully  charged state    The four green LED s indicate an  approximate level of load in 25   increments  If the BYPASS becomes  loaded beyond full rating  the fifth   amber  LED indicator will illuminate Bypass Mode
32. the absence of the mains power it is essential for the UPS output to be made  available for a critical operation  then the following procedure should be followed     N    1  To start the UPS in BATTERY mode  press the UPS ON ALARM  BATTERY  TEST button for at least one half second until you hear the audible alarm  gives a double    Beep    to signal acceptance of the command  After a short  delay  the BATTERY LED should light  The UPS will then initiate a self test  and approximately 10 seconds after these tests are completed  the UPS ON  LED will light  Connected load equipment may now be started     PLEASE NOTE  duration of output power will be limited to remaining battery  capacity shown by the battery LED s     To power down the UPS  Press the OUTPUT OFF  BYPASS button until the  audible alarm    Beeps     The UPS will now shutdown and all LED   s extinguish     N    TROUBLESHOOTING    The information below indicates various symptoms a user may encounter in the  event the UPStation GXT develops a problem  Use this information to determine  whether external factors cause the problem and how to remedy the situation     1  The fault indicator will illuminate indicating the UPS detected a problem   2  An alarm will sound  alerting that the UPS requires attention     3  One or more additional load battery level LED indicators will be illuminated to  provide a diagnostic aid to the operator  as described below           Load Battery  Level Indicator                      All  On
33. tifier power factor correction  PFC  circuit converts  mains AC power to regulated DC power for use by the inverter  while ensuring  that the wave shape of the input current used by the UPS is near ideal   Extracting this sinewave input current achieves two objectives  the mains power  is used as efficiently as possible by the UPS  and the amount of distortion  reflected on the mains is reduced  This results in cleaner power being available  to other devices in the building not being protected by the UPStation GXT     INVERTER   In normal operation  the inverter utilises the DC output of the power factor  correction circuit and    inverts    it into precise  regulated sinewave AC power   Upon a mains power failure  the inverter receives its required energy from the  battery through the rectifier   PFC  In both modes of the operation  the UPS  inverter is on line and continuously generating clean  precise  regulated AC  output power     BATTERY CHARGER   The battery charger utilises energy from the Rectifier   PFC and precisely  regulates it to continuously    float    charge the battery system  The battery system  charges whenever the UPStation GXT is connected to mains power     BATTERY  The UPStation GXT employs valve regulated  non spillable  lead acid batteries   At typical room temperatures and with the UPS float charging  the battery system    will last many years  Optional external battery cabinets are available to provide  extended run times     STATIC BYPASS   The UP
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  Long Term Financial Planning - User Manual  Refrigerator  Firmware Release Notes DriveLogix5720 Controller (12.20)  Zenoah BC2602 (EU) User's Manual  Bosch V1.0 User's Manual    Cisco RCKMNT-1RU  KTM 450 SMR 2008 User's Manual  NanoFoil Users Guide [4ページ、上記ユーザーガイドと同一]    Copyright © All rights reserved. 