Kidde TM0098 User's Manual
Contents
1. 2 or Dry Powder is available during the test It is the responsibility of the person carrying out the tests to ensure that the electrical equipment used is maintained at all times for safety In particular the correct fuse is fitted and that a power cord with suitable local approvals is used If in doubt please seek guidance from a qualified electrician 3 0 Equipment Set Up Ensure that the fuse fitted has the correct rating If the fuse is not the correct rating for the supply voltage in use then it must be replaced as follows 1 Turn the unit off and disconnect the power supply cord 2 Eject the fuse drawer 3 Remove the existing fuse and replace with one of the correct rating See section 8 4 Re insert the fuse drawer The timer must be in mode C with the scale set to min minutes and the scale showing from O to 3 maximum of three minutes operation The timer should appear like this TMO098 Page 2 of 4 Issue 1 00 It is recommended that the accuracy of the burn period is confirmed using a stopwatch with the red indicator on the timer before conducting any live tests Applicable code wire burn recommendations e BS6266 1992 recommends a burn time of 60 seconds for one metre wire lengths and 180 seconds for 2 metres e The NFPA 76 standard also recommends the same tests with an additional test with a burn time of 60s using 2 x 1m wires connected in parallel 4 0 Operation a Connect the IDE power cabl
2. A g Kidde Fire Protection HOT WIRE TEST BOX USER GUIDE TMO0098 WARNING Please read this guide fully before attempting to operate the unit 1 0 Introduction This Guide describes the use of the Kidde Fire Protection Hot Wire Test Box part number 1 53836 K237 to test aspirating smoke detection systems The unit provides 6V AC output from 220 240V AC mains supply High current at low voltage is passed through a cable in order to heat it which causes its insulation to burn giving off smoke A timer is incorporated to provide a selectable burn period of up to 3 minutes The timer also helps to prevent the unit being inadvertently left on for an extended period The unit must never be left on unattended The unit must be operated for no more than three 3 minutes continuously and must be left off immediately after operating fora period of at least six 6 minutes to allow it to cool The unit is protected against over temperatures by a thermal switch Once tripped the thermal switch will not allow operation for an extended period up to an hour regardless of power being present or not The thermal switch cannot be by passed or reset manually Hot Wire Test Unit TMO0098 Page 1 of 4 Issue 1 00 2 0 Preparation and Precautions When performing a hot wire test ensure that all local standards practices and regulations are understood and have been adhered to where applicable Also ensure that the detection equipment being
3. between the output terminals and lay it on a supporting non combustible platform It is important to ensure that there are no cross overs of the wire It may be helpful to first coil the wire using a pen or pencil as a temporary former and then lay it out Alternatively an arrangement to support the wire may be used with the precaution of a fire blanket positioned beneath the wire If the equipment is in a high airflow area then it may be required to shield the wire from the airflow At no time is it appropriate to open the Test Box There are no user serviceable parts inside 6 0 Smoke Test Ensure that the local fire panel is isolated from the external fire reporting equipment and that any automatic extinguishing or suppressant systems are similarly isolated Connect power to the Test Box and press the green push button switch At this point 6V AC is applied across the test wire the red Out indicator will illuminate continuously and the green Power indicator will flash The test wire will become hot and a quantity of smoke will be generated The test wire becomes very hot during the test and will cause burns if in contact with skin Care must be taken throughout this test process to protect both personnel and property from the hot wire TMO0098 Page 3 of 4 Issue 1 00 The current to the wire is turned off automatically after the set period is complete Smoke will have been generated and the time for it to be detected should be recorded
4. e supplied to the power input socket at the rear of the unit b Switch on using the rocker switch above the power input socket This will illuminate red when in the on position The green Power indicator on the timer will illuminate continuously c Set the timer to the required test period d Press the green push button switch to the left of the timer The red Out indicator will illuminate continuously and the green Power indicator will flash 6V AC will be delivered to the two screw terminals on the front of the unit e At the end of the time period the Out indicator goes out and the green Power indicator will become steady f Torepeat the process press the green push button switch again having set a different test period if required g On completion of the tests switch the unit off using the rocker switch above the power input socket and remove the power cable 5 0 Preparation and Connection of the Test Wire The test wire samples should be carefully measured and cut to the required length The ends should be stripped at approximately 15mm using a suitable tool If in doubt please seek guidance from a qualified electrician Only use the recommended test wire Under no circumstances should test wires be shorter than 60cm or 2x1m in parallel This is likely to age or blow the inlet fuse and may cause damage to the unit Ensure that no power is connected to the Test Box Insert the test wire
5. ge 4 of 4 Issue 1 00
6. proved tested is isolated from both the local fire authority notification alerts and any suppressant actioning devices The hot wire test is intended to trigger a response from the High Sensitivity Smoke Detectors under test Ensure that the consequences of this activation are understood and under control Precautions must also be taken to ensure that all personnel present are aware that the test is being conducted and that those who are required to remain in the immediate vicinity of the test are suitably attired for the smoke levels about to be created Avoid inhaling the smoke plume as it contains small quantities of hydrogen chloride The wire burn tests particularly the 1m and 2 x 1m tests produce sufficiently high temperatures to generate small quantities of hydrogen chloride However test personnel are unlikely to be exposed to concentrations of hydrogen chloride that exceed the Occupational Exposure Standard OES of Sppm in a 15 minute period unless they are directly exposed to the smoke plume It is strongly recommended that personnel wear appropriate protective equipment such as an E1 respirator conforming to EN140 and goggles without ventilation conforming to EN166 in the following situations e Multiple tests are required e Personnel are within the immediate vicinity e g 2m of the smoke source Due to the nature of hot wire tests there is a minor fire hazard It is essential that an appropriate type of fire extinguisher e g C0
7. to ensure that transport and alarm times are within the local regulatory requirements f References Note that appropriate guidance should be sought from all local and applicable standards and regulations such as BS5389 Part1 2002 BS6266 1992 BS6266 2002 which cross references to the BFPSA Code of Practice NFPA 76 2002 BFPSA Code of Practice for Category 1 Aspirating Smoke Detection Systems Appendix A This Appendix is published on the BFPSA British Fire Protection Systems Association website at www bfpsa org uk 8 Specifications Hot Wire Test Box Part Number 1 53836 K237 Voltage Input 220 240V AC 50Hz Input Rating 1 6A 240V AC 50Hz Fuse 220 240V AC T Anti surge 1 6A Output 6V AC nominal 20A Operating Time Maximum on time 3 minutes 180 seconds Minimum off time between tests 6 minutes 360 seconds Ingress Protection IP 30 Indoor use only This product is not to be used in the presence of moisture Wire Part Number 1 21888 K033 Description 100 metres 10 0 1 mm strands insulated with PVC to a radial thickness of 0 3mm and the cross sectional area of the conductor being 0 078 mm 9 Compliance Safety EN 61558 1 1997 Safety of power transformers power supply units and similar EN61558 2 6 1997 Particular requirements for safety isolating transformers for general use EMC EN 50081 1 EMC Generic Emissions EN 50082 1 EMC Generic Immunity FCC Part 15 Class A Emissions TMO0098 Pa
Download Pdf Manuals
Related Search
Related Contents
Medfusion-3500-Technical-Manual Boss Audio Systems CAP100CR capacitor Manual de Instruções PRO MIXER DJX700 Com a PHOTOELECTRIC BEAM SENSOR - Hotron I Automatic Door Sensors 1 - Palm Husqvarna YTH18542 User's Manual COMPACTAIR-CMC/CMH Manuel d`installation et de 369-M__XT3 configuration manual User`s Manual Part Number: 161-123417-023 Sales MultiBoard User Manual Copyright © All rights reserved.