ITT 801P5 User's Manual

image

Contents

1. 801P5 SMART SWITCHTM INSTALLATION AND OPERATION MANUAL ITT Industries Engineered for life PN 610 0002 Rev D ECO 71349 WARNING CAUTION NOTE Manual No 610 0002 Rev D Neo Dyn 28150 Industry Drive Valencia CA 91355 Tel 661 295 4000 Fax 661 294 1750 World Wide Web www neodyn com Copyright 2002 ITT Industries Important Information The product warranty applicable to this Neo Dyn instrument is as stated on page 41 of this manual Should any after delivery problems arise please contact ITT Neo Dyn s Customer Service using the information above Our normal business hours are weekdays 7 00 am to 3 30 pm Pacific Time Before installing the Smart Switch become familiar with the installation instructions in Chapter 2 Indicates a hazard which can cause severe personal injury death or substantial property damage if the warning is ignored Indicates a hazard which will or can cause minor personal injury or property damage if the caution is ignored Indicates additional information about a particular item necessary to the operation of the unit This document contains proprietary information which is the property of Neo Dyn a unit of ITT Industries This document may not be reproduced either in part or in full without the consent of ITT Industries 801P5 Smart Switch Page i TABLE OF CONTENTS PAGE CHAPTER 1 INTRODUCTION 1 ABOUT THIS MANUAL r
2. With this option installed you can change the scale factor of the display to read in different units of pressure or in arbitrary numbers that you choose If your system is set up with pressures in bars for example you might want the Smart Switch display to show bars instead of psig The r Hi r Lo and Loc menu functions allow you to scale the readout to your preference In the following example millibars are used You have a scalable 801P5 with the 15psig sensor You want to represent the pressure in millibars The standard conversion unit is psi 68 95 millibars You want to read zero for zero pressure therefore r Lo 0 Full scale output pressure for the 801P5 for this example is 15 psig So r Hi 68 95 x 15 1034 25 millibars which rounds to 1034 Therefore r Hi should be set to 1034 The unit now reads from 0 to 1034 millibars for 0 to 15 psig pressure The accuracy is 2 millibars which is 0 2 of 1034 You can use the scalable readout to set the display to read whatever units are most familiar to you or arbitrary numbers such as 0 to 10 With the 4 digit display you can use positive numbers to 9999 and negative numbers to 999 for fewer digits use leading zeros Page 21 801 5 Smart Switch To change the r Lo and r Hi 1 Press the MENU key and use the UP DOWN ARROW keys to move through the menu selections to r Lo 2 Press SELECT The furthest right digit will blink 3
3. 40 WARRANTY INFORMATION mee 41 801P5 Smart Switch iii CHAPTER 1 INTRODUCTION The Neo Dyn 801P5 Smart Switch is a solid state pressure switch designed for a wide range of applications in pneumatic and hydraulic systems up to 3 000 psig Pressure indication switch status and operational status are continually displayed on the front panel The unit can be configured to display pressure readings in a variety of formats The Smart Switch can be configured on site using the front panel keypad and 4 digit display or remotely via the optional RS 232 connection The 4 20 mA output option offers remote monitoring capabilities A built in password security system prevents unauthorized adjustments When locked pressure can be monitored and set points may be viewed but no adjustments can be made without entering the correct password The Smart Switch may be ordered to operate on 115 VAC 50 60 Hz 230 VAC 50 60 Hz or 18 30 VDC input power The external configuration of the Smart Switch is shown in Figure on the next page Page 1 801P5 Smart Switch Status Indicators Pressure Port Connection Std 1 2 14 NPT 4 19 free leads 22 AWG Figure 1 Model 801P5 Smart Switch Mounting Brackets not Shown Page2 Installation and Operation Manual The standard electrical interface is 22 AWG free leads exiting from a 14 NPT male conduit conne
4. SPECIFICATIONS This section shows the standard specifications and available options for the Neo Dyn 801P5 Smart Switch STANDARD Interface The Smart Switch weighs approximately 6 pounds 2 7 kg e 14 NPT Conduit Connection with 22 AWG Free Leads 18 NPT Female Pressure Port Two independent Solid State or Relay Switches Temperature Range Operating 15 F 26 C to 140 F 60 C Storage 30 F 34 C to 1 70 F 72 C Input power 115 VAC 50 60 Hz 230 VAC 50 60 Hz 18 30 VDC Page 37 801P5 Smart Switch Part Number The part number contains information about which configurations and options are included in your Smart Switch To determine the pressure range electrical rating and options compare the part number of your unit with the information below 801 5 H X X X Model Series J Wetted Material Range Number Input Power Switch Type Options Figure 10 Part Number Breakdown Pressure Rating Information Range Operating Increasing Deadband Minimum Max Proof No Range Range Decreasing Operating Pressure Percent of Setpoint Pressure psig psig Full Scale psig psig psig 02 0 5 10 5 1 99 05 12 5 25 04 0 15 30 15 1 99 15 37 5 75 05 0 30 60 30 1 99 30 75 150 07 0 100 2 100 1 99 1 250 500 09 0 250 5 250 1 99 2 5 625 750 11 0 500 10 500 1 99 5 1250 1500 12 0 1000 20 1000 1 99 10 2500 3000 14 0 3000 60 3000 1 99 30 3000 7500
5. 18 Installation and Operation Manual CHANGING THE SET POINTS To change the set points press the MENU key See Figure 7 The first menu item is for Set point 1 increasing To change a set point 1 If you want to change a set point other than SP 11 select the set point by pressing the arrow keys then press SELECT The furthest right digit will blink Use the SELECT key to move to the digit you want to change Use the UP DOWN ARROW keys to change the value of the digit When the value is correct press the SELECT key to move to another digit Repeat this until you have the correct value for this set point Use the STORE key to temporarily save the changes and return to the main menu Press RUN and then SELECT to permanently save the setting and return to On Line operation If you have set an invalid set point the error message EROR will be displayed Possible causes for errors are INCREASE value is equal to or lower than DECREASE value Values exceed range limits Deadband is less than 1 of F S O Page 19 801P5 Smart Switch ADDITIONAL FEATURES To alter the settings of the Smart Switch press the MENU key and use the UP DOWN ARROW keys to move through the menu Mode MOD Mode allows you to choose between Standard and Window Mode After MOD is displayed use the SELECT key to enter the Mode submenu and use the UP DOWN ARROW keys to toggle between STD and WIN
6. Page38 Installation and Operation Manual Range Operating Increasing Deadband Minimum Max Proof No Range Range Decreasing Operating Pressure Percent of Setpoint Pressure bar bar Full Scale bar bar 22 0 350 7 350 1 99 3 5 mB 0 86 1 7 mB mB 24 0 1000 20 1000 1 99 10 mB 2 6 5 1 mB mB 25 0 2 0 04 2 1 99 0 02 52 10 3 27 0 6 5 0 013 6 5 1 99 0 065 17 2 34 4 29 0 17 0 34 17 1 99 0 17 43 1 51 7 31 0 35 0 7 35 1 99 0 35 103 103 32 0 65 13 65 1 99 0 65 172 206 34 0 200 4 200 1 99 2 206 344 Range Operating Increasing Deadband Minimum Proof No Range Range Decreasing Operating Pressure Percent of Setpoint Pressure in H2O inH O Full Scale in H O psig psig 72 0 100 2 100 1 99 1 12 5 25 74 0 415 83 415 1 99 4 15 37 5 75 Total Accuracy 0 2 F S O including linearity hysteresis repeatability and temperature Page 39 801P5 Smart Switch Standard Electrical Ratings are Electrical Rating Code Input Power A 90 130 VAC 50 60 Hz E 180 260 VAC 50 60 Hz D 18 30 VDC The Switch Types are Switch Code Switch Type Switch Rating Leakage Current A Solid State 12 140 VAC 5 mA max SPDT 3 Amp Resistive D Solid State 5 60 VDC mA max SPDT 3 Amp Resistive R Relay SPDT 115 VAC N A 24 VDC 3 Amp Resistive OPTIONS The 801P5 options are listed below You can combine these options but every option ordered should b
7. 1 Display Shows 0 The MENU key has been pressed and the unit has a password other than 0000 Use the UP DOWN ARROW keys to set the first digit at the correct value Use the SELECT key to move to the next digit Repeat this process until the display shows the correct password Press the STORE key to enter the programming menu Page 29 801P5 Smart Switch Display Shows EROR This message might appear while programming the 801P5 Smart Switch The meaning depends on what is being programmed Following are the possible causes and solutions Incorrect password entered You have entered an incorrect password Re enter the correct password If you have lost or forgotten the password contact Neo Dyn Customer Service for assistance Incompatible switch set points You have entered incompatible set points Switch 1 and Switch 2 are independent of each other however the following rules apply to each switch The increasing set point must be at or below the Full Scale Output F S O value it cannot be less than 2 of F S O and it must be at least 1 of F S O above the decreasing set point The decreasing set point must be no lower than 1 of F S O it can be no higher than 99 of F S O and it must be at least 1 of F S O below the increasing set point The minimum deadband is 196 of F S O Re enter the set points to conform to the requirements 30 Installation and Operation Manual NOTE NOTE
8. Press the STORE key to temporarily save your setting Delay DELY This menu item allows you to delay the actuation and deactuation of the relay switches controlled by the set points After DELY is displayed use the SELECT key to enter the submenu Use the UP DOWN ARROW keys to cycle through the available delay times Your choices are 0 40 100 300 1000 3000 or 5000 mSec Press the STORE key to temporarily save your settings Display DISP This item sets how often the pressure display is updated This can be useful when there is a lot of fluctuation in the pressure reading After DISP appears use the SELECT key to enter the submenu Use the UP DOWN ARROW keys to cycle through the available display settings This option can be set at OFF 0 5 1 0 2 0 3 0 4 0 or 5 0 seconds Press the STORE key to temporarily save your setting Password PASS The Password function allows you to set a password to limit access to all menu functions After PASS is displayed use the SELECT key to enter the submenu Use SELECT to find the digit of the value you want to change The digit will blink Use the UP DOWN ARROW keys to change the value of the digit When the value is correct press the SELECT key Use this procedure until all digits of the password are changed to the correct values Then press the STORE key to temporarily save your setting Page 20 Installation and Operation Manual Scalable Readout Option Q
9. Pressure Calibration PCAL or Analog Output Calibration 4Cal is incorrect If you change the value for pressure or analog output calibration more than 4 of the F S O from the original factory values this error occurs Contact Neo Dyn Customer Service for assistance If the power to the unit is turned off and then back on the unit will function using the new values However this is not recommended as a calibration error this large indicates imminent component failure Display shows HHHH This indicates that the unit is online and monitoring pressure but the pressure is at or greater than 110 of F S O When the pressure returns to less than 11096 of F S O the display will return to its normal pressure display Display shows LLLL This indicates that the unit is online and monitoring pressure but the pressure is less than 4 of the F S O below zero psig pulling a vacuum When the pressure returns to greater than 496 of the F S O below zero psig the display will return to its normal pressure display An unlikely possibility is that the pressure transducer s connector has been dislodged from the internal circuit card Check to insure that the transducer connector is indeed connected Contact Neo Dyn Customer Service for assistance Page 31 801P5 Smart Switch Display alternates between OPEN and LOOP and the pressure reading The OPEN LOOP message is displayed with the V option 4 20 mA analog output in the followin
10. SELECT The display will show LO C While reading the milliammeter use the UP DOWN ARROW keys to adjust the output to 4 milliamperes Press the STORE key The display will read HI C Use the UP DOWN ARROW keys to adjust the output to 20 mA then press the STORE key to temporarily save the calibration data and return to the main menu Press RUN and SELECT to save the changes and return online If the 0 or Full Scale output has shifted by 4 of F S O or more from the factory calibration EROR will be displayed Page26 Installation and Operation Manual NOTE NOTE 4 20 MILLIAMPERE OUTPUT SCALING The 4 20 mA output is scaleable allowing 4 mA to represent any pressure between 0 and 66 F S O and 20 mA to represent any pressure between 33 and 100 F S O This feature is helpful in systems where the normal operating pressure falls within the pressure range of the unit For example let s assume that the Smart Switch has a pressure range of 0 to 100 PSIG and the process that it is monitoring operates between 20 and 80 PSIG The equipment that is monitoring the 4 20 mA output expects 4 mA to represent 20 PSIG and 20 mA to represent 80 PSIG Using the following instructions by setting SCLO to 20 PSIG and SCHI to 80 PSIG these conditions will be met Scale Low SCLO To set the pressure at which the output equals 4 mA press the UP DOWN ARROW keys until SCLO is displayed Press SELECT to enter the subme
11. and Operation Manual INPUT CONTROLS 81 and S2 INCR DECR Push the S1 and S2 INCR and DECR keys to see what values the set points are configured for MENU Use the MENU key to enter program mode UP DOWN ARROW The UP DOWN ARROW keys are used to move through the list of submenus SELECT The SELECT key is used to move into the desired submenu STORE The STORE key is used to temporarily save changes made to the current submenu and return to the main menu RUN The RUN key is used to lock in the programming changes made NOTE After pressing RUN to return to operation mode go back online you must press SELECT Otherwise any programming changes will be lost after 2 minutes DISPLAYING PRESSURE When the Smart Switch is in operation mode system pressure is displayed on the front panel Page 13 801P5 Smart Switch DISPLAYING SET POINTS Programmed set points can be viewed on the front panel display by pressing the corresponding S1 or S2 key To view the increasing value for Switch 1 press ST INCR To view the decreasing value for Switch 2 press S2 DECR Neo Dyn SMART SWITCH 56 52 0 INCR INCR SE 1 52 Figure 7 Press the Incr Decr Buttons to Display Set Points for 51 S2 NOTE After 5 seconds of keypad inactivity the display automatically changes back to the system pressure display While viewing set points the output functions remai
12. no responsibility for the performance or reliability of the unit as a whole In no event shall ITT be liable for indirect incidental or consequential damages nor shall the liability of ITT arising in connection with any products sold hereunder whether such liability arises from a claim based on contract warranty tort or otherwise exceed the actual amount paid by Buyer to ITT for the products delivered hereunder The warranty does not extend to any product manufactured by ITT which has been subject to misuse neglect accident improper installation or to use in violation of instructions furnished by ITT The warranty does not extend to or apply to any unit which has been repaired or altered at any place other than at ITT s factory or service locations by persons not expressly approved by ITT 801P5 Smart Switch Page 41
13. Change the digit s value with the UP DOWN ARROW keys 4 When the value is correct press the SELECT key to move to the next digit and repeat step 3 Repeat for each digit until you have the correct value for r Lo 5 Use the STORE key to temporarily save the changes and return to the main menu 6 Press RUN and then SELECT to permanently save the setting and return to On Line operation 7 Repeat steps 1 through 6 for r Hi The setting should be at least 2 display counts higher than r Lo Decimal Location Loc You can change the location of the decimal point thereby changing the scale of the display by using this function After Loc displays press SELECT to move the location one digit left When the correct location has been reached press STORE to temporarily save your setting NOTE When the decimal point is in the far right location no decimal is displayed during operation Page22 Installation and Operation Manual NOTE NOTE Pressure Calibration PCAL You can do a field pressure calibration using this function After PCAL is displayed use the SELECT key to enter the submenu LO P will be displayed for one second and then the switch s interpretation of the actual pressure will be displayed Apply 0 0 psig to the unit Use the UP DOWN ARROW keys to adjust the pressure display to zero psig Press the STORE key The display will show HI P for one second followed by the switch s interpretation o
14. ction The standard pressure connection is 1 4 18 NPT female a 7 16 20 SAE pressure connection is available as Option E Output options available for the Smart Switch include a 4 20 mA analog output Option V scalable display units Option Q and RS232 communications Option Z The RS232 option can be used to configure and monitor the unit remotely This option includes Windows based software Chapter 7 on page 37 contains complete specifications for the 801P5 Smart Switch Page 3 801 5 Smart Switch ABOUT THIS MANUAL The following paragraphs describe the format conventions used in this manual KEYS Most of the instructions contain directions to press a key which is one of the blue touchpads on the display surface of the Smart Switch When included in instructions the keys are shown in brackets as STORE DISPLAY When shown in the text the LED displays are formatted as 279 3 CUSTOMER SERVICE If you have any questions about the 801P5 Smart Switch that are not covered in this manual you can contact Neo Dyn in several ways The customer service phone number is 661 295 4000 Our customer service department is open from 7 00 am to 3 30 p m Pacific Time Our Internet site is www neodyn com Page4 Installation and Operation Manual WARNING WARNING WARNING WARNING CAUTION CHAPTER 2 INSTALLATION Installation of the Smart Switch is relatively straight
15. e indicated in the part number of the unit Option Description E 7 16 20 SAE Pressure Port Q Scalable Readout V Analog Output 4 20 mA Z RS232 Communications Page40 Installation and Operation Manual WARRANTY INFORMATION A Warranty ITT Industries ITT warrants that at the time of shipment the products manufactured by ITT Neo Dyn and sold hereunder will be free from defects in material and workmanship and will conform to the specifications furnished or approved by ITT B Warranty Adjustment If any defect within this warranty appears the Buyer shall notify ITT immediately ITT agrees to repair or furnish a replacement for but not install any product which within one 1 year from the date of shipment by ITT shall upon test and examination by ITT prove defective within the above warranty No product will be accepted for return or replacement without the written authorization of ITT Upon such authorization and in accordance with instructions by ITT the product will be returned with shipping charges prepaid by the Buyer Replacements made under this warranty will be shipped prepaid C Exclusion from Warranty THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS OR OTHERWISE Components manufactured by any supplier other than ITT shall bear only the warranty made by the manufacturer of that product and ITT assumes
16. ector has solder cups that will take wires as large as 18 AWG See Chapter 4 for operating instructions The RS232 communications option letter Z are connected to the 3 pin connector on the top left of the unit See Figure 5 using the supplied mating connector This mating connector has solder cups that will take wires as large as 18 AWG Cable length must not exceed 50 feet See Chapter 6 for operating instructions All field wiring for the 801P5 must comply with requirements of the NEC or applicable local electrical codes Page 6 Installation and Operation Manual 1 1 1 2 S2 BRN BLK 2 02 0 BLK 115 VAC OR 230 VAC LINE NEUTRAL NEUTRAL GND Figure 2 Schematic for AC Operation 7 801P5 Smart Switch 51 RED vio 1 10 __ NC 2 2 RED BLK BRN BLK 0 2 2 BLK 18 to DC wur RETURN He GND gt Figure 3 Schematic for DC Operation Page 8 Installation and Operation Manual 4 20 Ma RETURN Figure 4 Wiring for 4 20 mA Analog Output 9 801P5 Smart Switch DATA SEND DATA RECEIVE SIGNAL GROUND Figure 5 Wiring for RS 232 Communications Pagel0 Installation and Operation Manual CHAPTER 3 OPERATION amp PROGRAMMING This section describes the regular normal operation of
17. ertert hh reete 4 KEYS oeaves 4 DISPLA 4 CUSTOMER SERVICE y ceteras 4 CHAPTER 2 INSTALLATION 5 MOUNTING reete tenerent re Rm 5 PRESSURE CONNECTION eene nns 5 ELECTRICAL CONNECTIONS eee 6 CHAPTER 3 OPERATION amp PROGRAMMING 11 OPERATION MODES 2425 prete 11 FRONT PANEL CONTROLS see 12 INPUT CONTROLS nter rtm anres 13 DISPLAYING PRESSURE eene eene 13 DISPLAYING SET 8 2 2 0002 00 0022 14 STANDARD VS WINDOW 15 PROGRAMMING eene 17 ENTER PROGRAMMING MODE ee 17 CHANGING THE SET 8 02222222 19 ADDITIONAL FEATURES esee 20 CHAPTER 4 ANALOG e 25 ANALOG OPTION 2 2 44 0 25 TURNING ANALOG OUTPUT ON AND OFF LOOP 25 4 20 MILLIAMPERE OUTPUT CALIBRATION 4CAL 26 4 20 MILLIAMPERE OUTPUT SCALING 27 CHAPTER 5 TROUBLESHOOTING eee 29 ERROR MESSAGES thiet ee ener neenon 29 Pageii Installation and Operation Manual TABLE OF CONTENTS PAGE CHAPTER 6 SERIAL COMMUNICATIONS Z Option 35 thee e HRS 35 WIRING 35 CHAPTER 7 SPECIFICATIONS cece eee 37 STANDARD nenne n REO ECCE ert 37 OPTIONS et PAR
18. essure with electrical current If your Smart Switch includes this option the 4 20 mA output can be scaled see page 27 ANALOG OPTION WIRING The 4 20 mA output connections are provided by the two pin connector located on the top right of the unit Pin A is the positive output Pin B is the negative output The 801P5 generates its own loop power and it can operate with a load resistance of 600 ohms maximum TURNING ANALOG OUTPUT ON AND OFF LOOP Current Loop LOOP This menu item enables or disables the current 4 20 mA output To use this item 1 Press MENU 2 Press the UP DOWN ARROW key until LOOP displays the press the SELECT key to enter the submenu 3 Press either ARROW key to change the display from OFF to ON and vice versa 4 Press STORE to temporarily save your changes then press RUN followed by SELECT to lock in changes and return online Page 25 801P5 Smart Switch NOTE 4 20 MILLIAMPERE OUTPUT CALIBRATION 4CAL The 801 5 is factory calibrated to generate 4 mA when the pressure sensor is at 0 psig and 20 mA when rated pressure is applied Tolerances in your signal conditioning equipment may result in readings varying from these values so you can calibrate the 4 20 mA output as follows to correct these readings l 2 Connect a calibrated milliammeter to the 4 20 mA output Press MENU then press the UP DOWN ARROW key until 4CAL is displayed Press
19. f the actual pressure applied Apply Full Scale pressure to the unit Use the UP DOWN ARROW keys to set the display equal to Full Scale pressure Press the STORE key to return to the main menu A pressure source is required for this operation In addition calibration equipment used must have an accuracy of at least 0 02 F S O of the switch being calibrated If re calibration results in zero or Full Scale readings that have shifted by 4 F S O or more from the factory calibration an error code of EROR will be displayed Reset rSET This command resets the Smart Switch to factory default settings After rSET appears press SELECT STORE RUN and SELECT to reset the unit to factory defaults These are as follows r Hi returns to factory F S O r Lo is set to zero Spli is set to 60 of the full range SPld is set to 4096 of the full range SP2i is set to 70 of the full range SP2d is set to 30 of the full range Switch delay is set to 0 mSec Display update time is set to 0 5 seconds Page 23 801 5 Smart Switch NOTE If you have the 4 20 mA analog option there are three additional menu items that are reset These are LooP is set to on ScHi is set to F S O ScLo is set to zero These three menu items are discussed in Chapter 4 Analog Option Page24 Installation and Operation Manual NOTE CHAPTER 4 ANALOG OPTION The analog option V option for the 801P5 allows you to equate pr
20. forward However the Smart Switch must be installed by a qualified electrician in compliance with all local and national electrical codes Electrical Hazard Do not make electrical connections while power is on Always check for multiple circuits Always make sure grounding is adequate MOUNTING The Smart Switch can be mounted directly to the pressure connection or it can be attached to a flat surface such as a wall near the connection to be monitored For surface mounting slide the two mounting brackets into the slots on the back of the Smart Switc and use 10 190 in dia fasteners PRESSURE CONNECTION The standard pressure connection for the 801P5 Smart Switch is a 4 18 NPT female pipe thread A 7 16 20 SAE boss 15 also available as Option E When installing the Smart Switch always e Make sure that the unit and your system have the same fittings e Use the wrench flats provided e Sealall joints with pipe joint sealing compound Avoid excessive torque on all threaded connections Page 5 801 5 Smart Switch ELECTRICAL CONNECTIONS Units are supplied with 22 AWG free leads exiting from a 27 14 NPT male conduit connection The leads are color coded and marked See Figure 2 for AC operation and Figure 3 for DC operation 4 20 mA output option letter V is connected to the 2 pin connector on the top right of the unit per Figure 4 using the supplied mating connector This mating conn
21. g circumstances The analog loop is turned on but nothing is connected to the analog output connector In this case press the MENU key to enter the programming mode Use the UP DOWN ARROW keys to set this option to OFF Press the STORE key to temporarily save the change Press the RUN key followed by the SELECT key to save the change permanently and return on line The analog loop is turned on and connected but the connection has been broken In this case repair the broken connection or turn the loop off using the method described in the previous paragraph Load resistance exceeds 600 ohms In this case reduce the resistance Display is blank Press the 1 INCR key If the display illuminates and displays the increasing set point for Switch 1 then the Disp display update option has been set to OFF If the display does not react there has been an internal component failure Contact Neo Dyn Customer Service for assistance Display shows E 95 This code indicates that the internal manufacturing data which is saved in the nonvolatile RAM has become corrupt Power down the unit and then turn the power back on If the unit continues to show E 95 contact Neo Dyn Customer Service for assistance 32 Installation and Operation Manual Display shows E 96 This code indicates an internal A D reading that is out of its allowable tolerance Although this can indicate an internal component failure the most c
22. n active Page 14 Installation and Operation Manual STANDARD VS WINDOW MODE The terms Standard and Window describe two methods for setting up the Smart Switch to monitor pressure Standard Mode In Standard Mode illustrated in Figure 8 the or SP2i set point actuates when the pressure being monitored goes above the set value At this point the Smart Switch might turn off whatever electrical power is being applied to a pump for example which is increasing or maintaining the pressure The switch de actuates or resets when the pressure drops below the preset decreasing set point 5 or SP2d At this time the electrical power to the pump would be turned back on SWITCH ACTUATES INCREASING SET POINT DEADBAND SWITCH DEACTUATES DECREASING SET POINT Figure8 Standard Mode Page 15 801P5 Smart Switch Deadband The deadband is the separation between the increasing set point and the decreasing set point as shown in Figure 8 The deadband can be anywhere from 1 to 99 of Full Scale Output F S O In the case above where the Smart Switch is controlling a pump a wider deadband reduces the frequency at which the pump cycles on and off Window Mode This mode is useful when you want to maintain pressure within a certain range and want to be notified when pressure either goes above or falls below that range In Window Mode the Smart Switch starts out act
23. nu Use the SELECT key to move from digit to digit and use the UP DOWN ARROW keys to adjust each digit Once you have set the pressure press STORE to save your setting The range of adjustment for this function is zero psig to 66 of F S O The difference between the SCLO setting and the SCHI setting must be at least 33 of F S O Scale High SCHI To adjust the pressure at which the output equals 20 mA use the UP DOWN ARROW keys until SCHI is displayed Use the SELECT key to enter the submenu Use the SELECT key to move from digit to digit and use the UP DOWN ARROW keys to adjust each digit Once you have set the pressure that should equal 20 mA output press the STORE key to save your setting The range of adjustment for this function is 33 F S O to 100 of F S O The difference between the SCLO setting and the SCHI setting must be at least 33 of F S O Page 27 801P5 Smart Switch Page28 Installation and Operation Manual CHAPTER 3 TROUBLESHOOTING It is unlikely that you ll have any problems with the Smart Switch However just in case this chapter contains information to help diagnose and correct any error messages you may see ERROR MESSAGES Below are error messages that you may see during operation or programming along with brief descriptions of how to correct them If you see an error that is not listed here contact Neo Dyn Customer Service The contact information is located in Chapter
24. ommon cause of this error is vacuum applied to the pressure port of the unit If the cause 1s vacuum once the pressure returns to near zero the unit will return to monitoring and controlling If the cause is internal component failure contact Neo Dyn Customer Service for assistance Display shows E 97 This error indicates that the internal user data saved in the nonvolatile RAM has become corrupt Press the SELECT key to cause the unit to reboot If the unit continues to show E 97 contact Neo Dyn Customer Service for assistance Page 33 801P5 Smart Switch Page34 Installation and Operation Manual CHAPTER 6 SERIAL COMMUNICATIONS Z Option GENERAL The Smart Switch with the Z Option installed is capable of RS232 communications with an IBM compatible computer This option includes Windows 3 x 95 98 2000 compatible software which allows remote monitoring and programming of the Smart Switch as well as data tracking functions To install the software follow the Setup instructions on the diskette label Once it is installed the Help menu provides detailed operating instructions The default BAUD rate is 9600 but it may be set to 2400 BAUD for noisy environments WIRING Smart Switch Function DB9 Connection DB25 Connector Pin Pin Connection Pin Transmit 2 3 B Receive 3 2 Page 35 801P5 Smart Switch Page 36 Installation and Operation Manual CHAPTER 7
25. the Smart Switch as it monitors pressure after installation and initial setup and the Programming Mode for changing the settings Both modes rely on the front panel for information and input See Figure 6 on the next page OPERATION MODE To begin operation apply correct power to the appropriate free leads there is no on off switch In normal operation mode the display shows e Online LED green indicates operation mode e SI and S2 LED s red indicate the switch status illuminated when the relay coil is energized or the solid state switch is actuated e System pressure is displayed You can also check the set points in operating mode all other actions are done in programming mode However If you have the RS232 option you can program the unit remotely using its Windows software on a personal computer see Chapter 6 Page 11 801 5 Smart Switch FRONT PANEL CONTROLS Neo Dyn SMART SWITCH INCR INCR AN nas 51 52 Figure 6 The Front Panel with Function Keys Below the Display Indicators Display The display shows the actual system pressure in normal operation 1 and 52 Switch Indicators The S1 and S2 red LED s indicate switch status illuminated with the relay coil energized or the solid state switch actuated Online Indicator The Online indicator green LED is lit when the unit is online and active If the indicator is not lit the unit is offline 12 Installation
26. uated then deactuates when it reaches its lower set point SP1d or SP2d As pressure continues to increase the switch actuates again when it reaches the upper set point SP1i or SP2i This range between the lower and upper set points is the window When pressure decreases the sequence reverses with a deadband of 1 of F S O at each of the set points See Figure 9 In this mode the Smart Switch might be wired to say an alarm bell which would sound if the pressure either rose above or fell below SP1d NO CLOSED UPPER BOUNDARY INCREASING SET POINT NO OPEN LOWER BOUNDARY DECREASING SET POINT NO CLOSED Figure 9 Window Mode Page 16 Installation and Operation Manual NOTE PROGRAMMING MODE In Programming Mode you can e Change the set points e Perform field pressure calibration e Program Window or Standard Mode e Change the password e Program display update time e Program delays for both switches e Scale the readout e Reset the Smart Switch to factory defaults If your unit includes the 4 20 mA option you can e Activate 4 20 mA mode e Calibrate the 4 20 mA e Scale the 4 20 mA output If your unit includes the RS232 option you can Set the BAUD rate The unit will not function as a switch while in programming mode ENTER PROGRAMMING MODE To access the programming mode press the MENU key See Figure 7 On the initial startup no password is required If you ha
27. ve previously set up a password you must enter it at this time 1 When the displays show O press the UP DOWN ARROW keys to set the first digit 2 Press SELECT to move to the next digit 3 Repeat this process until display shows the correct password 4 Press STORE to enter programming mode Page 17 801 5 Smart Switch NOTE You can now use the arrow keys to move throughout the menu system Then l When the menu item you want to change is displayed press SELECT After changing the value use the STORE key to temporarily save the changes If you make a mistake while entering values press the MENU key to return to the menu system and restart To change another item press the UP DOWN ARROW keys to display that item and repeat steps 1 and 2 After you are done press the RUN key to lock in the changes Then press the SELECT key to return online You must press the SELECT key when RUN is displayed to permanently save any changes you have made If you do not all changes will be lost after two minutes of inactivity When RUN is displayed you have two additional choices REDO and UNDO Use the UP DOWN ARROW keys to scroll through the menu Press the SELECT key to make your choice REDO puts the unit back into program mode to allow further changes UNDO returns the unit online without making the changes you may have entered RUN returns the unit online saving all changes