Home

Honeywell T8602A-C User's Manual

image

Contents

1. 25 Set the Program Schedule and Heating Temperatures 25 Set the Cooling Temperatures 27 Set the System and Fan Switches eren entente tnnt emen nnn nnnnennn nennen nnnm nme eee 29 OPERATING THE THERMOSTAT nun a 5 5 222 30 Temporarlly Changing the Program 30 Permanently Changing the Program ssssscsssssessssnsnssssnceseneereusnnatncnnsneaneenennsaranacccncanssasaesaeaeaeasner tent ane 30 Operating the Thermostat Manually 30 Canceling Program Settings eere a terne entente tnnt nen nennen nnn tennessee ete tee EEE eA 31 Checking the Program Times and Temperatures eeennnnn entente nnnm 31 Checking the Current Temperature Setting eren 31 TROUBLESHOOTING entm uu uuu u u u ane nn nn atn 32 GLOSSARY REM t EE 33 TYPICAL HOMEOWNER QUESTIONS
2. 34 This equipmentis a Class B digital apparatus which complies with Canadian Radio Interference Regulations CRC c 1374 35 68 0056 1 Honeywell Inc International Sales Offices in all principal cities of the world Manufacturing in 1885 Douglas Drive N Australia Canada Finland France Germany Japan Mexico Netherlands Q x Golden Valley MN 55422 4386 Spain Taiwan United Kingdom U S A PRINTED IN U S A QUALITY IS KEY
3. IMPORTANT If your system needs isolating relay and one is not installed no hazard will exist but the system will not operate The thermostat will not be damaged unless you connect it directly to 120 Vac If the current draw of the primary control is below 0 08A a 202394B Resistor should be installed on the furnace terminal strip to increase the current draw of the primary contro to 0 08A or greater This would alleviate any compatibility problem between the T8600 Thermostat and the system due to a low current draw For installation details refer to instructions packed with the resistor The T8601 T8602 and T8603 Thermostats are com patible with other control systems without the need for an isolating relay WHEN INSTALLING THIS PRODUCT 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Checkthe ratings given on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 Allow thermostat to warm to room temperature be fore programming 5 After installation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply to prevent electrical shock or equipment damage LOCATION Install thermostat and wallplate about 5 ft 1 5 m above the floor in an area with good air circulation at room temperature Do not i
4. Program the RETURN time and temperature if desired Program the SLEEP time and temperature if desired ie gt O A D COOLE and m gt lt m Qu gt O le Q m I 23 P 5 Ir A o O O r m SLEEP 100 If display reads SAT or SUN press and hold until MON TUE WED THU FRI appears Press and hold until the display shows the desired starting time Press and hold until the display shows the desired temperature lf the display starts to blink while holding down TEMPERATURE WARMER or COOLER the setting limit has been reached If thermo stat can switch automatically between heating and cooling the heating temperature must be at least 3 degrees below the air condi tioning temperature For example if the cooling setting is 75 F the maximum heating setting is 72 F Press and release The display shows LEAVE but no time or temperature Press and hold until the display shows the desired starting time Press and hold until the display shows the desired temperature Press and release The display shows RETURN but no time or temperature Press and hold until the display shows the desired starting time Press and hold until the display shows the desired temperature Press and release The display shows SLEEP and the prepro grammed time and temperature Press and hold until the display shows the desired starting
5. energy My thermostat has ENRG SAV and SYSTEM lights Why do they both go on at the same time For example during the sleep period During Adaptive Intelligent Recovery when you recover gradually to a next set point you will stay in the energy saving mode until the next programmed time is reached But the system will operate intermittently to gradually raise the temperature to your desired comfort level before the time you ve set as your WAKE time You will always be saving energy until the next period s actual set point is reached Why don tall thermostat models have AUTO auto matic changeover from heating to cooling Most parts of the country don t have wide temperature swings during a 24 hour period so it is not necessary Desert climates such as Phoenix are the exception because of wide variations in temperature which may require both the air conditioner and furnace to run during different times within a given 24 hour period Sometimes my Chronotherm Ill thermostat doesn t allow the house temperature to drop to my SLEEP setting before it starts bringing the furnace on Why When you start your SLEEP period the thermostat will turn off your furnace and your house temperature will start to fall After that the thermostat is out of the picture until the house temperature falls all the way to your SLEEP temperature setting or until recovery starts In mild weather or with good insulation your house
6. 17 T8600C COOLING CIRCUIT IN SINGLE ANISOLATING RELAY WITH CHANGEOVER TRANSFORMER SYSTEM WITH ELECTRIC TERMINALS O B SEE TABLE Ill FOR US COOLING AGE HEATING COOLING WALLPLATE HEATING COOLING WALLPLATE ADD JUMPER COOLING DAMPER COOLING COOLING CONTACTOR CHANGEOVER HEATING DAMPER HEATING CHANGEOVER HEAT PUMP COMPRESSOR RELAY N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD 77 PROTECTION AS REQUIRED JN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CURRENT DRAW FOR W OR Y MUST BE 0 08A OR GREATER W PLUS G OR Y PLUS MUST BE 1 2AORLESS 12 378 CONNECT VALVE TO O FOR CHANGEOVER ON COOLING OR B FOR CHANGEOVER ON HEATING FIG 1 6 T8600C SUPER TRADELINE HEATING A CURRENT DRAW FOR W PLUS G MUST BE BETWEEN 0 080 A COOLING CIRCUIT IN A SINGLE TRANS ANES M1377 FORMER SYSTEM WITH ELECTRIC HEAT ELECTRIC COOLING AND CHANGEOVER TERMINALS 0 B THERMOSTAT CON TROLS FAN IN HEAT AND COOL TYPICAL SINGLE SPEED FAN APPLICATIONS SEE FIG 18 T8600C HEATING COOLING CIRCUIT FOR A TABLE IV TO SET FAN OPERATION SINGLE STAGE ELECTRIC HEAT PUMP SWITCH WITH CHANGEOVER TERMINALS O B 10 HEATING COOLING WALLPLATE HEATING COOLING PRIMARY CONTACTOR CONTROL 08 mud A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE CURRENT DRAW FOR W OR Y PLUS G MU
7. 51 BATTERY PLACEMENT Power Outages T8600 T8601 T8603 ONLY Backup batteries will hold the programming and keep the display on during most power outages Once the power is restored the system will resume normal operation If the display goes off when power is lost either the backup batteries need to be replaced or are not installed When power is restored the display will flash 1 00 PM to remind you to reprogram will control at preprogrammed temperature until then MOUNTING THE THERMOSTAT Hang the thermostat on the tabs at the top of the base Fig 52a Swing down and press on lower edge until thermostat snaps in place Fig 52b Open cover and tighten the captive mounting screws Fig 52c When 24 V system power is present on T8600 T8601 T8603 the room temperature will be displayed SETTING DAY AND TIME Set present day and time as follows SET Press 59x J Press TIME or to set the current time Press PR SENT DAY TIME to set the current day Each press of the key advances the display one day NOTE On the T8600 T8601 T8603 when 24 V is first applied to power unit display will flash 1 00 PM and 32 for a minute or less followed by 1 00 and the room tem perature flashing 68 0056 1 FIG 52 MOUNTING THERMOSTAT ON WALLPLATE On the T8602 when thermostat is first turned on the display will read 1 00 PM and room temperature It will go off for only a few seconds th
8. HEATING ONLY WALLPLATE A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED J 24 VAC TRANSFORMER FOR THERMOSTAT POWER M338A FIG 43 T8603A B HEATING ONLY CIRCUIT IN AN OIL SYSTEM 68 0056 1 S86 MODULE VR8440 VALVE TERMINALS A y 24 V 4 2 Q345 Q346 Q348 PILOT BURNER A A L1 ae IGNITER SENSOR 4 HOT 4 2 A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD TO VR8440 Eros OUTLET PROTECTION AS REQUIRED A MAXIMUM PILOT BURNER IGNITER SENSOR CABLE LENGTH 30 in 0 8 m A FOR MODELS WITH ON AUTO FAN SWITCH A FACTORY INSTALLED WIRES DO NOT REMOVE N 24 VAC TRANSFORMER FOR THERMOSTAT POWER JN CONTROLS IN TRANSFORMER CIRCUIT MUST NOT BE IN GROUNDED LEG A FOR SINGLE TRANSFORMER SYSTEMS M340A FIG 44 T8603A B HEATING ONLY CIRCUIT IN A HONEYWELL INTERMITTENT PILOT GAS BURNER IGNITION SYSTEM ZONE 1 ZONE 2 ZONE 3 ZONE 4 HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE A A w 69 w G9 9 w 9 Au Ed a RE ET T L DS REEL a HAE R8239A1052 AN R8222B1067 R822281067 R8222B 1067 5 E c E bu q 11 URGERE B 3 SEM ZONE 1 VALVE OR ZONE 2 VALVE OR ZONE 3 VALVE OR ZONE 4 VALVE OR DAMPER MOTOR DAMPER MOTOR DAMPER MOTOR DAMPER MOT
9. a enne tenente nnne nnn nnnnn nennen teen nnrnnnm ene rmen memet 20 Installing Batteries 21 Mounting the Thermostat 21 Setting Day and Time 21 CHECKOUT U CEN 22 Heating I U u uuu uuu snon entente sse tan nna en nette tnnte nennen ennt ntn nnnn nnne nn enn en nennen nme mreennetm 22 Cooling eccecnssscessecnsnecserseessssonsncnnsesovensentensacenecaeenesususorsssansnsanenseacensaccnsoreoronennasessesunenurnssancrrararenseasnraarascaseseesenescnnsts 22 ORBE Edad ME 23 Installer Self Test optional J J U u tnn enne nette nnne nnne nennen ette tatnen nnnm nnnm ennenn nnnm 23 ABOUT ADAPTIVE INTELLIGENT RECOVERY M 24 RECOVERY SETTING sa 24 PROGRAMMING THE THERMOSTAT sssscecsssscecsssesnenseescensnsesencesenssesssnsessnesanncnenenaensnnsearcosaccasssrenensernse se 200 25 Set the Current Day and Time
10. AAA alkaline batteries are provided as backup to prevent program loss in case of power outage Batteries are included with thermostat Install batteries in back of thermostat as shown in Fig 51 Without battery backup the program will remain about 30 seconds in event of power loss IMPORTANT When batteries are first installed in the T8600 T8601 and T8603 the display will flash AC until the thermostat is powered from the system wir ing f AC power is lost during operation the display will show AC instead of temperature On the T8602 Thermostat power is supplied for the thermostat by three AA alkaline batteries Batteries are included with thermostat Install batteries in back of thermostat as shown in Fig 51 The display will flash 1 00 PM and room temperature When the batteries are low the thermostat display will flash REPL BAT If device has system switch set to OFF Remove the thermostat from the wallplate and install three new alkaline batteries Install new batteries within approxi mately 30 seconds from time the batteries are removed to prevent program loss and necessity to reprogram IMPORTANT On the T8602 the low battery warning will be dis played about two months before batteries are dead When the batteries are dead the system will shut down After batteries are replaced thermostat will require reprogramming 21 BATTE PLACEMENT NOTE CORRECT PLUS AND MINUS DIRECTION FIG
11. AND RC FOR SINGLE TRANSFORMER SYSTEM JUMPER AND RC M319A FIG 38 T8602C SUPER TRADELINE HEATING FIG 39 T8602C HEATING COOLING CIRCUIT IN A COOLING CIRCUIT IN A TWO TRANS TWO TRANSFORMER ONE FOR HEATING FORMER SYSTEM GAS HEATING ELEC ONE FOR COOLING SYSTEM WITH GAS TRIC COOLING SEE TABLE iV TO SET HEAT ELECTRIC COOLING RC AND R FAN OPERATION SWITCH TERMINALS HEATING COOLING WALLPLATE HEATING PRIMARY CONTROL COOLING CONTACTOR AN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL SUCH AS GAS VALVE ELECTRONIC IGNITION MODULE OR HEATING CONTACTOR 12 169B FIG 40 T8602C HEATING COOLING CIRCUIT IN A SINGLE TRANSFORMER SYSTEM WITH GAS HEAT ELECTRIC COOLING OR ELEC TRIC HEAT ELECTRIC COOLING THERMO STAT CONTROLS FAN IN COOLING ONLY TYPICAL MULTISPEED FAN APPLICA TION HEATING COOLING WALLPLATE OIL PRIMARY 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 12 1704 FIG 41 T8602C HEATING COOLING CIRCUIT IN AN OIL HEATING ELECTRIC COOLING SYS TEM HEATING TRANSFORMER IS IN OIL PRIMARY 17 HEATING ONLY WALLPLATE A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VAC TRANSFORMER FOR THERMOSTAT POWER FOR MODELS WITH ON AUTO FAN SWITCH A FOR SINGLE TRANFORMER SYSTEMS FIG 42 T8603A B HEATING ONLY CIRCUIT IN A CONTINUOUS PILOT GAS SYSTEM
12. DISPLAY GOES BLANK WHEN POWER 15 TURNED OFF DISPLAY FLASHES WHILE PROGRAMMING BATTERIES ARE DEAD IMPROPER PROGRAM SEQUENCE AUTOMATIC THERMOSTAT HEATING OR COOLING TEMPERATURE CAN NOT BE SET CLOSER THAN 3 F DISPLAY FLASHES DURING PROGRAMMING HAS BEEN LOST gt OPERATION BECAUSE OF A POWER OUTAGE REPLACE BATTERIES REPROGRAM ACCORDING TO PROGRAMMING INSTRUCTIONS MAKE SURE BATTERIES ARE INSTALLED M1383 32 Adaptive Intelligent Recovery Recovery automatically starts early enough so house is at the comfort setting by the time chosen Comfort temperature The temperature wanted in the morning and evening when people are home Conventional Recovery Recovery starts at the time programmed into the thermo stat house reaches comfort temperature shortly thereaf ter Energy saving temperature The lower heating or higher cooling temperature that allows savings on heating and cooling costs when asleep or away Also called the setback heating or setup cool ing temperature Period key One of the four keys WAKE LEAVE RETURN or SLEEP to check or program the start time and tempera ture for a time period Preprogrammed schedule This is the schedule programmed into your thermostat at the factory It sets a night program that provides energy savings if homeowner doesn t set program or if personal program is lost for any reason The program which is th
13. FAN OPERATION SWITCH SUPER TRADELINE models include a fan operation switch on the back of the thermostat on the lower left corner Fig 50 See Table IV below to determine correct setting of fan operation switch CAUTION Thefanoperation switch inthe SUPER TRADELINE models is factory set to the NON ELEC position If the system requires direct thermostat control of the fanin heat mode the switch must be settothe ELEC position See Table IV TABLE IV SUPER TRADELINE FAN OPERATION SWITCH SETTING FAN OPERATION Fan controlled directly by thermostat in heat mode typically electric furnaces Fan has independent control in heat mode typically gas oil and some electric furnaces FAN OPERATION SWITCH SETTING 4A FIG 50 COMMENTS Set to ELEC position Set to NON ELEC position Use only 1 system transformer jumper R and RC System may have 1 or 2 transformers if 1 transformer jumper R and RC RECOVERY SELECTION ADAPTIVE IN INTELLIGENT FACTORY SETTING CONVENTIONAL OUT 172 TO 1 TURN N or X SJT SYSTEM GRAVITY AIRWATER HOT WATER GAS OIL WARM AIR ELECTRIC WARM AIR OUT 1 2 TO 1 TURN IN IN FACTORY SETTING IN TO 1 TURN N SCREWS 2A 2B AVAILABLE ON SOME MODELS ONLY A SWITCH 4A AVAILABLE ON SUPER TRADELINE MODELS ONLY M2082B TO t TURN FIG 50 CYCLE RATE ADJUSTMENT INSTALLING BATTERIES On the T8600 T8601 and T8603 thermostats three
14. If a lower cooling setting is desired the heating setting must first be lowered accordingly Program the LEAVE temperature if Press and release The display desired E shows LEAVE the time pro G30 18 grammed for heating and 78 F MON TUE WED THU FAI COOL LEAVE Press and hold until the display Miam shows the desired temperature 835 m B Program the RETURN temperature Press and release The display ran TT it desired RETURN shows RETURN the time pro M iLiew MON TUE WED THU FRI CooL RETURN grammed for heating and 78 F OG Press and hold until the display ST Ups shows the desired temperature Q Q r m 8 Program the SLEEP temperature if rt desired Press and release 7 Ltem DB r m m v s WU z L2 8 4 pea xo Press and hold until the display LFL l shows the desired temperature Qo Q o m a Press and hold until SAT appears on the display Set the cooling temperatures for the SATURDAY schedule Use the same procedure as for weekdays Press WAKE LEAVE RETURN or SLEEP to select the time period LEAVE RETURN i ai p DAY WARMER Use the WARMER COOLER keys to set the temperature 28 ae ASE Day EER 1 ex UT a Te TI Cv Tu Set the cooling temperat
15. MODELS WITH ON AUTO FAN SWITCH oil heat electric coo zone valves incompatible or 3 wire zone valves Honeywell or electric heat electric cool Fow Cg Ne 41 45 46 compatible 2 wire gas heat electric cool thermostat controlled fan 49 HEATING ONLY WALLPLATE OIL PRIMARY N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A CURRENT DRAW MUST BE BETWEEN 0 08 A AND 1 2 A 12 145 FIG 7 T8600A B HEATING ONLY CIRCUIT IN AN OIL SYSTEM VR8440 VALVE TERMINALS S86 MODULE PILOT BURNER Q345 Q346 Q348 GROUND A PILOT BURNER der IGNITER SENSOR j TO 440 PILOT OUTLET 12 1398 FIG 8 T8600A B T8602A B HEATING ONLY CIRCUIT IN A HONEYWELL INTERMITTENT PILOT GAS BURNING IGNITION SYSTEM 68 0056 1 HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE R8239D1015 SYSTEM TRANSFORMER BIMETAL RESISTANCE SWITCH HEATER SWITCH HEATER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 12 138A N PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRIC HEAT PRIMARY 12 146A FIG 9 T8600A B HEATING ONLY CIRCUIT USING FIG 10 T8600A B HEATING ONLY CIRCUIT IN AN AN R8239D ISOLATING RELAY SEE TABLE ELECTRIC BASEBOARD OR CEILING Ill FOR USAGE CABLE SYSTEM ZONE 1 ZONE 2 ZONE 3 Z
16. SLEEP program is set only for the heating season so family members can sleep in summer Weekday program schedule The schedule of WAKE LEAVE RETURN and SLEEP period start times and temperatures that homeowner pro grams to run Monday through Friday 68 0056 1 1 Why do some models of this thermostat have lights Battery operated thermostats do not have indicator lights to conserve battery power Others may have one or two indicator lights depending upon the exact model and application The temperature displayed on the thermostat doesn t always match the room temperature on an other thermostat located right next to it Why The thermostat is a very accurate instrument designed to sense both air temperature and wall temperature much as your body does It gives an average reading over a period of time Can control when the furnace comes on in the morning When the thermostat is set for Adaptive Intelligent Re covery it will turn on the furnace as early as neces sary to reach your desired comfort temperature at the programmed time The earliest it will be is 24 minutes per degree setback ahead of your WAKE time but it will vary depending on your system the weather and how much the temperature dropped in the house at night If you want to control the start time yourself just switch the thermostat to conventional recovery following the directions on page 25 This way the furnace won t come on
17. are now programmed Go on to Step 2 IMPORTANT Before beginning STEP 2 determine if thermostat is set for Adaptive Intelligent Recovery or conventional recovery See pages 24 25 If set for Adaptive Intelligent Recovery program the times for when home should be comfortable The thermo stat will decide how early to begin the temperature changes If set for conventional recovery program the times earlier allowing home to reach the comfort temperature by the time owner is home or wakes up Some trial and error may be required to arrive at the best starting times STEP 2 SET THE PROGRAM SCHEDULE AND HEATING TEMPERATURES Start by programming the WAKE SET time and temperature for weekdays HEAT COOL The thermostat requires a program for WAKE Program LEAVE RETURN and SLEEP or not as desired Press and release Note that the display shows WAKE and the EYLI LI ALES p y MON TUE WED THU FRI HEAT preprogrammed time and tempera inis ture If system has air conditioning and J 9 Goce re the display reads COOL press and release to switch to HEAT MON TUE THU FRI HEAT KE 25 68 0056 1 NOTE The display shows Adaptive Intelligent Recovery setting in the following instructions Program the LEAVE time and temperature if desired NOTE If desired cancel the LEAVE RETURN or SLEEP program by holding down the period key until the time and temperature disappear from the display
18. on your furnace or air conditioner it considers 1 air temperature 2 the temperature of the wall and 3 when you want the comfort temperature established W During Adaptive Intelligent Recovery the thermostat increases the control temperature gradually and turns the equipment on and off several times to save energy by avoiding overshooting the comfort temperature See the current control temperature anytime during recovery by pressing the PRESENT SETTING key On some models both the SYSTEM and ENERGY SAVING lights may be lit at the same time during recovery This smart control learns from experience Each day it checks how closely it hit the target and adjusts the recovery start time accordingly It typically takes four to eight days after installation for this thermostat to adjust to the weather life style home construction and heating cooling system The thermostat calculates the LEAVE RETURN recovery separately from the SLEEP WAKE recovery B With this thermostat choose Adaptive Intelligent Re covery or conventional recovery Use Adaptive Intelli gent Recovery to choose the exact time that the room reaches comforttemperature Use conventional recovery to choose the exact time furnace or air conditioner comes on to start recovery System Operating in Comfort Mode fs X oa Recovery Continues Recovery Begins E any 9 oe MP AM E un w m w a um TEMP
19. tem perature may not fall all the way to your SLEEP tem perature setting and the thermostat won t turn on your furnace until the time to recover back up to your comfort setting SPECIFICATIONS 2 cccosscecsscescecocecneccsnenssnsesnetnsosnnercnssesanennuunnseconennasenccsnaesscastsnerneuenacecusce 2 ORDERING INFORMATION s ecccessscecesensecrensssnsssnsessansensensusesenensesaransnassasansousnosnesacsasanansesasenansasannanenaananaanaaseess 2 INSTALLATION AME E 4 Compatibility emere reor uuu uuu tn nntnn tentent nette 4 Location I mE cede 4 Mounting Wallplate eee l llu u uuu JJ J J nana enne nnn tn nnne entm en snetnntenten nennen nter ener 4 Wiring enne reser enn entente sentent ensem en tta tant uu uuu a a s nutu senses nt rmm 5 Cycle Rate Adjustment rennen tenete nnno nenne enn sese ennt enn nennt entren nennen nnne 20 Adaptive Intelligent Recovery Conventional Recovery Conversion 20 Time Temperature Conversion Some Models eren nnne nennen nnne nnnm nnnm 20 Fan Operation Switch U Ullu ua uu u
20. temperature will normally vary slightly from the comfort temperature setting with the cycling of the furnace or air conditioner The equipment cycles off and on as room temperature approaches the set point The cycle rate of this thermostat is set for heating at six cycles per hour and for cooling at three cycles per hour as shipped from the factory The cooling cycle rate can not be adjusted The heating cycle rate can be adjusted by turning one or both cycle rate adjustment screws located on the back of the thermostat See Fig 50 The screws should only be backed out about one half to one turn or beturned in until tight ADAPTIVE INTELLIGENT RECOVERY CONVENTIONAL RECOVERY CONVERSION The thermostat is factory set for Adaptive Intelligent Recovery but may be converted to conventional recov ery using screw 3A on the back of the thermostat as indicated in Fig 50 With Adaptive Intelligent Recovery the room will reach the comfort temperature at the exact time pro grammed into the thermostat The control temperature will increase gradually and turn the equipment on and off severaltimes to reach the comfort temperature slowly and on time With conventional recovery the start time should be programmed to be earlier than the desired comfort time TIME TEMPERATURE CONVERSION SOME MODELS The display readout may be converted between 12 and 24 hour clock or C and F using screws 2A and 2B as indicated in Fig 50
21. to ribbed area surround ing terminals Fig 5 to assure thermostat wallplate contact 68 0056 1 FOR STRAIGHT INSERTION FOR WRAPAROUND STRIP 5 16 in 8 mm STRIP 7 16 in 11 mm QDOOA a WIRING TO THIS AREA R Ro Y O FRONT VIEW OF TERMINAL AREA WIRING TO BE BELOW TOP SURFACE THIS SURFACE OF WALLPLATE CROSS SECTIONAL VIEW OF TERMINAL AREA 12 1324 FIG 4 JUMPER RC AND FOR SINGLE TRANS FIG 5 KEEP WIRING RESTRICTED TO RIBBED FORMER STRIP WIRE 3 4 in 19 mm AREA SURROUNDING TERMINALS List of Wiring Diagrams Fg No o Fig No T8600A B heat only gas or central electric electric decentralized 10 oil zone valves incompatible or 3 wire 11 Intermittent Pilot zone valves Honeywell or 12 isolating relay compatible 2 wire T8600C heat cool gas heat electric cool electric heat electric cool electric heat electric cool thermostat controlled fan 16 oil heat electric cool electric cool only 17 isolating relay single stage electric heat pump 18 T8600C D heat cool gas heat electric cool single transformer 19 oil heat electric cool 21 gas heat electric cool two transformer 20 isolating switching center 22 T8601A B heat only zone valves incompatible or 3 wire gas or central electric zone valves Honeywell or compatible 2 wire oil Intermittent Pilot 27 T8601C heat cool gas heat electric cool electric
22. transformer requires a E KNEE MEME NAE 00 independently controlled two wires to system T8601C HEAT OFF COOL ON AUTO fan in heat ideal for transformer backup T8601D 1 1 HEAT OFF ON AUTO construction installation batteries included COOL AUTO T8602A sss ee Gas oil or electric 24 V Powered by three AA b Lee s systems with indepen alkaline batteries eee EMEN Sdn dently controlled fan in included T8602C 1 HEAT OFF COOL ON AUTO heat T8603A 1 Gas oil or electric 24 V Powered from a T8603B ON AUTO systems with indepen separate transformer EB With positive OFF Heat only with fan control Typical single stage heat pump with external fan control applications jumper W and Y LIGHT EMITTING DIODES LEDs Two included on T8600 T8601 T8603 models SYSTEM LED lights up during thermostat ON cycle and ENRG SAV LED lights up during the LEAVE and SLEEP time periods VOLTAGE RATING 15 to 30 Vac CURRENT RATING For T8600 0 08 A minimum to 1 2 A maximum Current draw must be 0 08 A to 1 2 A in the W or Y circuit when the fan switch is in the ON position or 0 08 A to 1 2 A total in the Y plus G circuits when the fan switch is in the AUTO position For T8601 T8602 T8603 1 6 A maximum OPERATING HUMIDITY RANGE 5 to 90 percent relative humidity OPERATIVE AMBIENT TEMPERATURE RANGE 40 F to 110 F 4 C to 43 C SET POINT RANGE 45 F to 88 F 7 C t
23. AS REQUIRED AN CURRENT DRAW FOR W OR Y MUST BE 0 08 A OR GREATER W OR Y PLUS G MUST BE 1 2 A OR LESS 12 1408 AN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AN CURRENT DRAW FOR W OR Y MUST BE 0 08 A OR GREATER W OR Y PLUS G MUST BE 1 2 A OR LESS 12 148B FIG 13 T8600C HEATING COOLING CIRCUIT IN A SINGLE TRANSFORMER SYSTEM WITH GAS HEAT ELECTRIC COOLING OR ELEC FIG 14 T8600C HEATING COOLING CIRCUIT IN AN TRIC HEAT ELECTRIC COOLING AND CHANGEOVER TERMINALS O B THERMOSTAT CONTROLS FAN IN COOL ING ONLY TYPICAL MULTISPEED FAN APPLICATIONS OIL HEATING ELECTRIC COOLING SYSTEM WITH CHANGEOVER TERMINALS 0 B HEATING TRANSFORMER IS IN OIL PRI MARY ALSO SEE FIG 21 RC R TERMI NALS 68 0056 1 HEATING COOLING WALLPLATE HEATING COOLING WALLPLATE HEATING PRIMARY CONTROL NPOWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED SYSTEM SWITCH MUST BE IN COOL POSITION TO PREVENT DRAIN ON BATTERIES 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD POWER SUPPLY PROVIDED ON COOLING ONLY APPLICATION EQUIPMENT MUST BE POWERED YEAR ROUND N PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE A A CURRENT DRAW FOR Y MUST BE 0 08 A OR GREATER CURRENT DRAW FOR W OR Y MUST BE 0 08 A OR GREATER CREADO OR T MUTTET Y PLUS G MUST BE LESS THAN 1 2 A ane FIG 15 T8600C HEATING COOLING CIRCUIT USING FIG
24. ATING COOLING WALLPLATE OA CHANGEOVER COOLING DAMPER EX COOLING REL COOLING CHANGEOVER CONTACTOR HEATING PRIMARY CONTROL DAMPER LI HEATING POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD 7 PROTECTION AS REQUIRED 2N PRIMARY CONTROL SUCH AS GAS VALVE ELECTRONIC IGNITION MODULE OR HEATING CONTACTOR A O B TERMINALS ON SOME MODELS 12 1578 FIG 28 T8601C HEATING COOLING CIRCUIT IN A SINGLE TRANSFORMER SYSTEM WITH GAS HEAT ELEC TRIC COOLING OR ELECTRIC HEAT ELECTRIC COOLING AND CHANGEOVER TERMINALS THERMOSTAT CONTROLS FAN IN COOLING ONLY TYPICAL MULTISPEED FAN APPLICATIONS HEATING COOLING WALLPLATE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED N O 8 TERMINALS ON SOME MODELS 12 156A FIG 29 T8601C HEATING COOLING CIRCUIT IN AN OIL HEATING ELECTRIC COOLING SYSTEM OIL PRIMARY HAS ITS OWN TRANSFORMER HEATING COOLING WALLPLATE HEATING COOLING WALLPLATE COOLING DAMPER COOLING COOLING CHANGEOVER CONTACTOR HEATING DAMPER HEATING CHANGEOVER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD JIN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PROTECTION AS REQUIRED 12 159A gt CONNECT VALVE TO O FOR CHANGEOVER ON COOLING OR B FOR CHANGEOVER ON HEATING ere FIG 31 T8601C HEATING COOLING CIRCUIT FORA FIG 30 T8601C HEATING COOLING CIRCUIT FOR A CENTRAL ELECTRIC FUR
25. E ON WALL TABLE lll T8600 THERMOSTAT AND SYSTEM COMPATIBILITY not applicable to T8601 T8602 T8603 Manufacturer Model No Compatible Solution ELECTRIC HEAT RELAYS Honeywell R841C Klixon 51172 GAS SYSTEMS Direct Spark Ignitlon Module Honeywell 8825C yes Honeywell 58250 Honeywell S87B lt oio Fenwal 05 162426 R8239D1015 Fenwal 05 21 R8239D1015 Intermittent Pilot Module non 100 shutoff Honeywell S86A yes Honeywell S86C Honeywell S86D Robertshaw SP 710 929 yes Robertshaw SP 730 929 Robertshaw SP 712 series yes White Rodgers yes 36084 50A22 Camstat SIG 24 Spectrol 990 195 Johnson Penn Baso R8239D1015 G60RHL Johnson Penn Baso DNE R8239D1015 CSAA42A Y 79 Johnson Penn Baso yes CSA42A Powerpile se f powered millivolt All Models no R8239D1015 Manufacturer Model No Compatible Solution Standing Pilot Honeywell all OIL SYSTEMS Interrupted Ignition Honeywell R8404A Honeywell R8185E Robertshaw J4001 2001 White Rodgers 669 430 Constant Ignition Honeywell R8184G Robertshaw SJ4007 204 White Rodgers 668 430 VENT DAMPERS Honeywell D80B D Robertshaw AVD E 780 90 Johnson Penn Baso yes M15AC 1 Flair SPG 5 21 ZONE CONTROL Hot Water Valves Honeywell V8043F d es lt D o o R8239D1015 lt D o R8239D1015 D lt lt D o R8239D1015 B D o Taco 571 2 R8239A1052 Flair VJ100 R8239A1052 Electr
26. ERATURE System Operating in Energy Savings Mode bantam D 00 C TO UL B TIME RECOVERY SELE CTION ADAPTIVE INTELLIGENT IN F AC TORY SETTING lourwe TO 1 TURN GONVENTIONAL 2119 t 76 AM wrt he w va w ENERGY SAVINGS RECOVERY FROM ENERGY SAVINGS pep PERIOD 24 x axe COMFORT PERIOD THE THERMOSTAT USES THE SAME SCHEME TO RETURN GRADUALLY TO LOWER COMFORT TEMPERATURE DURING THE COOLING SEASON M171 This thermostat includes a screw on the back marked 3A allowing for the Adaptive Intelligent Recovery con ventional recovery choice This thermostat was shipped from the factory with the screw positioned for Adaptive Intelligent Recovery The installer may have left the screw in this position or may have changed it to conventional recovery Before pro gramming it is important to know for which recovery method the thermostat has been set With Adaptive Intelligent Recovery the dwelling will reach the comfort temperature at the exact time pro grammed into the thermostat See page 24 for detailed explanation of Adaptive Intelligent Recovery With conventional recovery the programmed time will mark the start of recovery therefore program the start time to be earlier than the desired comfort time It may require some trial and error to arrive at the best starting time and the best starting time w
27. Honeywell THE T8600 T8601 T8602 T8603 CHRONOTHERM III PRO GRAMMABLE FUEL SAVER THERMOSTATS PROVIDE AUTOMATIC CONTROL OF SINGLE STAGE HEATING OR HEATING COOLING SYSTEMS AND OFFER USERS THE HIGHEST STANDARD OF COMFORT AND CONVENIENCE AVAILABLE WITH ENERGY SAVINGS T8600 thermostats are powered through the heating cooling system controls ideal for replacement application t T8601 thermostats are powered direct from transformer requiring two wires to system transformer ideal for new con struction installation T8602 thermostats are powered by three AA alkaline batter ies suitable for 100 percent control compatibility T8603 thermostats are powered direct from transformer and include additional terminals for one two or three trans former systems Thermostats include a wiring wallplate Digital clock liquid crystal display indicates continuous time day current period and room temperature Upon inquiry provides program times and program set points All thermostats provide 4 different temperature settings per daily schedule to optimize user comfort and energy savings O Different daily schedules may be selected for weekdays Saturday and Sunday C SAV and SYSTEM light emitting diodes LEDs included on T8600 T8601 T8603 models C Models available with automatic heat cool changeover 1 Batteries packed with devices provide power to maintain clock and memory during power failures
28. ING ONLY CIRCUIT IN AN ELECTRIC BASEBOARD OR CEILING CABLE SYSTEM 15 68 0056 1 DEP CMM Poem es eim Pt SERIO Ug D ZONE 1 ONE 2 ZONE 3 ZONE 4 HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE d x ANE RENE R8239A1052 2 R8222B1067 R8222B1067 R8222B1067 EAR ZONE 4 VALVE OR DAMPER MOTOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD AN USE ONE R8239 FOR EVERY FOUR ZONES A USE FOR 3 WIRE ZONE VALVE OR DAMPERS PROTECTION AS REQUIRED 12 150A FIG 37 T8602A B CIRCUIT FOR CONTROLLING INCOMPATIBLE OR 3 WIRE ZONE VALVES OR DAMPERS HEATING OR COOLING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE FOR HONEYWELL OR COMPATIBLE 2 WIRE VALVES SEE FIG 12 HEATING COOLING WALLPLATE COOLING FAN COOLING DAMPER RELAY CONTACTOR HEATING HEATING PRIMARY DAMPER CONTROL HEATING COOLING WALLPLATE p FAN COOLING Aes oM RELAY CONTACTOR A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PRO TECTION AS REQUIRED PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE AN CURRENT DRAW FOR WOR Y PLUS G MUST BE LESS THAN 1 6 A 12 142B A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR SYSTEMS WHERE THERMOSTAT MUST CONTROL FAN DIRECTLY IN HEATING SET FAN OPERATION SWITCH TO ELEC POSITION USE ONLY ONE TRANSFORMER AND JUMPER R
29. IONER INOPERATIVE INSTRUCTIONS PARTIAL DISPLAY INOPERATIVE THERMOSTAT REPLACE THERMOSTAT CHECK THAT HEAT OR COOL SYSTEM POWER IS ON SEE INSTALLATION INSTRUCTIONS FOR CORRECT NO DISPLAY NO POWER TO THERMOSTAT THERMOSTAT MOUNTED INCORRECTLY ON BASE MOUNTING NO OR VERY SHORT FURNACE SYSTEM NOT COMPATIBLE CHECK COMPATIBILITY CHART UNDER INSTALLATION CYCLES 18600 ADD R8239 OR 2023948 IF NECESSARY PRESENT SETTING APPEARS THERMOSTAT IS IN RECOVERY NORMAL OPERATION THERMOSTAT TURNS ON INACCURATE MODE HEATING COOLING EARLY TO MEET TEMPERATURE SETTING AT PROGRAMMED TIMES RECOVERY CAN BE ENDED BY PUSHING WARMER COOLER KEYS REPROGRAM FOR WEEKENDS PER INSTRUCTIONS THERMOSTAT TEMPERATURE WARMER COOLER KEYS BEING REPROGRAM THERMOSTAT TO MAKE PERMANENT NEEDS TO BE ADJUSTED ON A USED TO ADJUST CHANGE IN PROGRAM WARMER COOLER KEYS ARE REGULAR BASIS TEMPERATURE TEMPORARY UNLESS PERIOD KEY IS PRESSED FIRST REMOVE AND REPLACE PER MARKINGS ON THERMOSTAT REPLACE BATTERIES REMOVE AND REPLACE PER MARKINGS ON THERMOSTAT REPLACE BATTERIES CHECK PROGRAMMING INSTRUCTIONS FOR CORRECT PROGRAM SEQUENCE ROOM TEMP IS NOT WHAT IS EXPECTED ON WEEKENDS THERMOSTAT NOT PROGRAMMED FOR WEEKENDS LOW BATTERY INDICATOR JS FLASHING BATTERIES ARE INCORRECTLY INSTALLED BATTERIES ARE DEAD BATTERIES ARE INCORRECTLY INSTALLEO PROGRAM 15 LOST DUE TO POWER OUTAGE OR
30. N HEATING SYSTEM POWER MUST BE ON YEAR ROUND FOR T8600D 12 147C FIG 22 T8600C D HEATING COOLING CIRCUIT US ING AN R8239D ISOLATING SWITCHING CENTER 68 0056 1 HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE R8239D1015 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 Vac TRANSFORMER SUPPLIES THERMOSTAT POWER IF ONE ADDITIONAL WIRE C CANNOT BE BROUGHT TO THERMOSTAT LOCATION USE T8600A OR B OIL PRIMARY FOR MODELS WITH ON AUTO FAN SWITCH 12 155B POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VAC TRANSFORMER FOR THERMOSTAT POWER IF ONE ADDITIONAL WIRE C CANNOT BE BROUGHT TO THERMOSTAT LOCATION USE T8600A OR B A FOR MODELS WITH FAN SWITCH ONLY 12 152B FIG 23 T8601A B HEATING ONLY CIRCUIT IN CON TINUOUS PILOT GAS OR CENTRAL ELEC FIG 24 T8601A B HEATING ONLY CIRCUIT IN AN TRIC SYSTEM OIL SYSTEM CONNECTION VR8440 MAIN VALVE MV TH S86 MODULE VR8440 VALVE TERMINALS HEATING ONLY WALLPLATE LIM CONTROLLER BURNER GROUND PILOT BURNER 2 Q345 Q346 Q348 IGNITER SENSOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED I TO VR8440 MAXIMUM PILOT BURNER IGNITER SENSOR CABLE LENGTH PILOT OUTLET 30 in 0 8 m FACTORY INS ALLED WIRES DO NOT REMOVE CONTROLS IN TRANSFORMER CIRCUIT MUST NOT BE iN GROUNDED LEG FOR MODEL
31. NACE ELECTRIC SINGLE STAGE ELECTRIC HEAT PUMP COOLING TYPICAL SINGLE SPEED FAN FAN CONTROLLED BY THERMOSTAT APPLICATIONS 14 Potest merase aria remercie emet 0s HEATING COOLING WALLPLATE Qo HEATING PRIMARY COOLING CONTROL CONTACTOR FAN RELAY ev VN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE 12 160A FIG 32 T8601D HEATING COOLING CIRCUIT IN A SINGLE TRANSFORMER SYSTEM WITH GAS HEAT ELECTRIC COOLING HEATING COOLING WALLPLATE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 12 151A FIG 33 T8601D HEATING COOLING CIRCUIT IN AN OIL HEATING ELECTRIC COOLING SYS TEM OIL PRIMARY HAS ITS OWN TRANS FORMER HEATING ONLY WALLPLATE GAS VALVE OR HEAT RELAY FAN RELAY N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED J MODELS WITH ON AUTO FAN SWITCH FIG 34 T8602A B HEATING ONLY CIRCUIT IN CON TINUOUS PILOT GAS SYSTEM HEATING ONLY WALLPLATE OIL PRIMARY N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 15938 FIG 35 T8602A B HEATING ONLY CIRCUIT IN AN OIL SYSTEM HEATING ONLY WALLPLATE BIMETAL RESISTANCE SWITCH HEATER SWITCH HEATER 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 12 138A FIG 36 T8602A B HEAT
32. ONE 4 HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE R822281067 R8222B1067 R822281067 P 9 g NI ZONE 1 ZONE 4 VALVE VALVE O B on O e DAMPER DAMPER MOTOR MOTOR JIN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2N USE ONE R8239 FOR EVERY FOUR 2ONES USE FOR 3 WIRE ZONE VALVE OR DAMPERS 12 1504 FIG 11 T8600A B CIRCUIT FOR CONTROLLING INCOMPATIBLE OR 3 WIRE ZONE VALVES OR DAMPERS HEATING OR COOLING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE ZONE 4 HEATING ONLY WALLPLATE ZONE 3 HEATING ONLY WALLPLATE ZONE 2 HEATING ONLY WALLPLATE ZONE 1 HEATING ONLY WALLPLATE VALVE OR DAMPER MOTOR VALVE OR DAMPER MOTOR VALVE OR DAMPER MOTOR DAMPER MOTOR A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A USE ONE 38 VA TRANSFORMER FOR EVERY FOUR ZONES HONEYWELL AT72D OR EQUIVALENT FIG 12 T8600A B T8602A B CIRCUIT FOR CONTROLLING HONEYWELL OR COMPATIBLE 2 WIRE ZONE VALVES OR DAMPERS HEATING OR COOLING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE HEATING COOLING WALLPLATE HEATING COOLING WALLPLATE COOLING CONTACTOR HEATING DAMPER HEATING CHANGEOVER HEATING PRIMARY CONTROL N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
33. OR N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD A 24 VAC TRANSFORMER FOR THERMOSTAT POWER PROTECTION AS REQUIRED FOR SINGLE TRANSFORMER SYSTEMS USE ONE R8239 FOR EVERY FOUR ZONES M333A FIG 45 T8603A B CIRCUIT FOR CONTROLLING INCOMPATIBLE OR THREE WIRE ZONE VALVES OR DAMPERS HEATING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE 18 ZONE 4 HEATING ONLY WALLPLATE ZONE 3 HEATING ONLY WALLPLATE ZONE 2 HEATING ONLY WALLPLATE ZONE 1 HEATING ONLY WALLPLATE 21 24V DAMPER MOTOR DAMPER MOTOR DAMPER MOTOR DAMPER MOTOR A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A TRANSFORMER VA RATING DETERMINED BY CONNECTED LOAD USE MULTIPLE TRANSFORMERS IF NEEDED FIG 46 T8603A B CIRCUIT FOR CONTROLLING HONEYWELL OR COMPATIBLE TWO WIRE ZONE VALVES OR DAMPERS HEATING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE HEATING COOLING WALLPLATE 0 Co 9 69 COOLING CONTACTOR HEATING PRIMARY CONTROL JN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AA PRIMARY CONTROL SUCH AS GAS VALVE ELECTRONIC IGNITION MODULE OR HEATING CONTACTOR A 24 VAC TRANSFORMER FOR THERMOSTAT POWER NOTE FOR SUPER TRADELINE MODEL FAN OPERATION SWITCH 4A SHOULD BE SET FOR CORRECT FAN OPTION A
34. S INSTRUCTED IN TABLE IV FIG 47 T8603C HEATING COOLING CIRCUIT IN A SINGLE TRANSFORMER SYSTEM WITH GAS HEAT ELECTRIC COOLING OR ELEC TRIC HEAT ELECTRIC COOLING THERMO STAT CONTROLS FAN IN COOLING ONLY OR HEAT AND COOL TYPICAL MULTI SPEED FAN APPLICATIONS HEATING COOLING WALLPLATE COOLING CONTACTOR A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A 24 VAC TRANSFORMER FOR THERMOSTAT POWER NOTE FOR SUPER TRADELINE MODEL FAN OPERATION SWITCH 4 SHOULD BE SET FOR CORRECT FAN OPERATION AS INSTRUCTED IN TABLE IV M1373 FIG 48 T8603C HEATING COOLING CIRCUIT IN AN OIL HEATING ELECTRIC COOLING SYS TEM OIL PRIMARY HAS ITS OWN TRANS FORMER 68 0056 1 HEATING COOLING WALLPLATE A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A A 24 VAC TRANSFORMER FOR THERMOSTAT POWER FOR HOOKUP TO SYSTEM TRANSFORMER WHEN SEPARATE TRANSFORMER FOR THERMOSTAT POWER IS NOT USED NOTE FOR SUPER TRADELINE MODEL FAN OPERATION SWITCH 4A SHOULD BE SET TO NON ELEC POSITION SEE TABLE 2 FIG 49 T8603C HEATING COOLING CIRCUIT FOR ELECTRIC HEAT ELECTRIC COOLING OR GAS HEAT ELECTRIC COOLING THERMO STAT CONTROLS FAN IN COOL ONLY TYPICAL SINGLE STAGE FAN APPLICA TIONS TWO SYSTEM TRANSFORMERS PLUS THERMOSTAT SUPPLY TRANS FORMER SHOWN CYCLE RATE ADJUSTMENT NOTE MOST APPLICATIONS WILL NOT REQUIRE A CHANGE IN CYCLE RATE The room air
35. S WITH ON AUTO FAN SWITCH gt gt gt gt 12 154 FIG 25 T8601A B HEATING ONLY CIRCUIT IN HONEYWELL INTERMITTENT PILOT GAS BURNING IGNITION SYSTEM 12 ZONE 1 ZONE 2 ZONE 3 ZONE 4 HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE R8239A1052 A a R8222B1067 R8222B1067 R8222B1067 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD A USE FOR 3 WIRE ZONE VALVE OR DAMPERS PROTECTION AS REQUIRED A USE ONE R8239 FOR EVERY FOUR ZONES 12 1538 FIG 26 T8601A B CIRCUIT FOR CONTROLLING INCOMPATIBLE OR 3 WIRE ZONE VALVES OR DAMPERS HEATING OR COOLING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE FOR HONEYWELL OR COMPATIBLE 2 WIRE VALVES SEE FIG 27 ZONE 1 ZONE 2 ZONE 3 ZONE 4 HEATING ONLY HEATING ONLY HEATING ONLY HEATING ONLY WALLPLATE WALLPLATE WALLPLATE WALLPLATE ZONE 1 ZONE 2 ZONE 3 ZONE 4 VALVE OR VALVE OR VALVE OR VALVE OR DAMPER MOTOR DAMPER MOTOR DAMPER MOTOR DAMPER MOTOR A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A USE ONE 38 VA TRANSFORMER FOR EVERY FOUR ZONES HONEYWELL AT72D OR EQUIVALENT FIG 27 T8601 A B CIRCUIT FOR CONTROLLING HONEYWELL OR COMPATIBLE TWO WIRE ZONE VALVES OR DAMPERS HEATING OR COOLING EQUIPMENT IS OPERATED BY AN END SWITCH ON THE ZONE VALVE OR MOTOR OR BY A THERMOSTAT IN A MASTER ZONE 13 68 0056 1 HE
36. SETTING 15 see note a following SKIP NEXT PERIOD blank CHANGE TO LAST PERIOD 03 blank COOLER 02 blank WARMER 06 blank BACK oa oan AHEAD o birk RETURN 00 blank LEAVE ban SLEEP 08 biam WAKE 12 see note b following SETHEAT COOL 09 blank DAY 13 micro processor mask number and revision number HOLD blank SET PRESENT DAY see note c TIME 14 following RUN PROGRAM 11 normal operating display 23 EXEC OL OL SUN MON TUE WED THU FRI SAT COOL ONHEAT ON WAKE LEAVE RETURN SLEEP TEMPORARY L DA 671 A IN E FIG 53 ALL SEGMENTS ON DISPLAY ajf the system switch is in COOL or AUTO the cooling system and system LED come on when the key is re leased Press and releasetoturn cooling system and LED off Do not operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s recom mendations PA four digit code number will appear when the key is released The four digits of the code represent the follow ing options HEATING CYCLES PER HOUR AT 50 ON TIME SET FOR Gravity Air Water Hot Water Electric Warm Air Gas Oil Warm Air RECOVERY TYPE Conventional Conventional Adaptive Intelligent Adaptive Intelligent Conventional Conventional Adaptive Intelligent Adaptive Intelligent SECOND DIGIT CLOCK HR 12 12 12 12 THIRD SYSTEM
37. ST BE BETWEEN 0 08 AND 1 2 A A ON T8600D HEATING SYSTEM POWER MUST BE ON YEAR ROUND M1382 FIG 19 T8600C D HEATING COOLING CIRCUIT IN A SINGLE TRANSFORMER SYSTEM WITH GAS HEAT ELECTRIC COOLING RC ANDR TERMINALS HEATING COOLING WALLPLATE HEATING PRIMARY CONTROL N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE A CURRENT DRAW FOR W OR Y MUST BE 0 08 A OR GREATER W OR Y PLUS G MUST BE 1 2A ORLESS ON T8600D HEATING SYSTEM POWER MUST BE ON YEAR ROUND M1378 FIG 20 T8600C D HEATING COOLING CIRCUIT IN A TWO TRANSFORMER ONE FOR HEATING ONE FOR COOLING SYSTEM WITH GAS HEAT ELECTRIC COOLING RC AND R TERMINALS 11 HEATING COOLING WALLPLATE N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A CURRENT DRAW FOR W OR Y PLUS G MUST BE BETWEEN 0 08 A AND 1 2 A ON 786000 HEATING SYSTEM POWER MUST BE ON YEAR ROUND M1380 FIG 21 T8600C D HEATING COOLING CIRCUIT IN AN OIL HEATING ELECTRIC COOLING SYSTEM HEATING TRANSFORMER IS IN OIL PRIMARY RC AND R TERMINALS HEATING COOLING WALLPLATE HEAT ING PRIMARY CONTROL A AN POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE A CURRENT DRAW FOR Y MUST BE 0 08 A OR GREATER Y PLUS G MUST BE LESS THAN 1 2 A A
38. SWITCH THERMOSTAT TYPE DIGIT POSITION 0 Heat Cool Off or Auto 1 Heat Only Off 2 Heat Cool Cool 4 Heat Cool Heat 5 Heat Only Heat or No Switch 68 0056 1 AUTO OR FOURTH DIGIT THERMOSTAT MANUAL CHANGEOVER T8602 T8602 T8602 T8600 T8601 T8603 T8600 T8601 T8603 T8600 T8601 T8603 O SYSTEM SWITCH Manual or Heat Only All Positions Auto Heat Off Cool Auto Auto Manual or Heat Only All Positions Auto Heat Off Cool Auto Auto Cif the system switch is in HEAT or AUTO the heating system and system LED come on when the key is released Press and release again to turn heating system and LED off M People perceive temperature from a variety of sources not only from the air in the room but also from their surroundings walls windows and furnishings M Human beings feel differences in temperature as slight as two degrees Fahrenheit B Common household thermometers and standard thermostats sense only air temperature which may or may not reflect how hot or cold the room actually feels to a human being W This thermostat reads the temperature of the wall as well as the air and responds to temperature changes as little as one degree Fahrenheit so room temperature is more likely to feel right THE OPTIMUM COMFORT AND ENERGY SAVINGS SOLUTION This thermostat is actually a small but powerful com puter When calculating the exact time to turn
39. de ENRG SAV light This light glows during the LEAVE and SLEEP periods SYSTEM light This light glows whenever the thermo stat is calling for heating or air conditioning Sunday program schedule The schedule of WAKE LEAVE RETURN and SLEEP period start times and temperatures that homeowner pro grams to run on Sundays Time period One of four program periods WAKE LEAVE RETURN and SLEEP available with the thermostat One period begins when the previous period ends WAKE For conventional recovery the time the recov ery tothe comfortable temperature begins for Adaptive Intelligent Recovery the time period when home owner wants the house at a comfortable temperature while the family gets up and gets ready to leave for work or school This is the only period that must contain a time and temperature LEAVE The time period when you can set back winter or up summer the temperature for energy savings because the family is usually away from home RETURN For conventional recovery the time the re covery to the comfortable temperature begins for Adaptive Intelligent Recovery the time period when homeowner wants the house at a comfortable tempera ture for family activities in the evening before bedtime SLEEP The time period when homeowner can set back winter or up summer the temperature for en ergy savings because the family is sleeping Set it to start at your family s normal bedtime Often the
40. e same for all days of the week is Start Temperature Period Time Heating Cooling WAKE 6 00AM 70 F 78 F LEAVE No program RETURN No program SLEEP 10 00 PM 60 F 78 F Program The times and temperatures set to define the comfort and energy savings periods for each schedule weekdays Saturday Sunday Hecovery The time when the thermostat operates the heating or air conditioning equipment to return the house from the en ergy savings to the comfort temperature If thermostat is set for Adaptive Intelligent Recovery the thermostat starts the recovery period early so the house will be at the comfort setting by the time chosen Saturday program schedule The schedule of WAKE LEAVE RETURN and SLEEP period start times and temperatures that homeowner pro grams to run on Saturdays Setback Reducing the temperature in the house for a set period every day in winterfor energy savings The lower tempera ture is the energy savings temperature 33 Set point The temperature set on the thermostat The thermostat turns the heating or cooling equipment on and off to maintain this temperature at the thermostat location until another temperature setting goes into effect Setup Raising the temperature in the house for a set period every day in summerfor energy savings The highertemperature is the energy saving temperature Status lights Lights on some models that show system operating mo
41. e of stocking ease of handling and maximum replacement value Specifications of SUPER TRADELINE and TRADELINE controls are the same except as noted below TABLE I SUPER TRADELINE MODELS NUMBER HEAT COOL SYSTEM FAN APPLICATION POWER METHOD Tg600c HEAT OFF ON AUTO Gas oil or electric Powered through the heating or COOL 24 V systems cooling system controls backup with option of in batteries included T8602C 1 HEAT OFF ON AUTO dependent or Powered by three AA alkaline COOL thermostat controlled fan in batteries T8603C 1 HEAT OFF ON AUTO heat COOL Powered direct from transformer includes additional terminals for one two or three transformer Typical single stage heat pump with external fan control applications jumper W and Y bincludes 250 ohm 10 W resistor for low current draw below 0 08 A system compatibility Typical older and commercial electric heat and water coil applications systems backup batteries included SUPER TRADELINE FEATURE Fan operation switch on back of thermostat to select either independent or direct thermostat control of fan in heating WHEN PURCHASING REPLACEMENT AND MODERNIZATION PRODUCTS FROM YOUR TRADELINE WHOLESALER OR YOUR DISTRIBUTOR REFER TO THE TRADELNE CATALOG OR PRICE SHEETS FOR COMPLETE ORDERING NUMBER OR SPECIFY 1 Model number SUPER TRADELINE if desired 2 Number of heat and cool stages desired 3 System fan switchin
42. en begin to flash on and off If the display will not come on check mounting of thermostat to wallplate If loose or misaligned remove thermostat and reinstall on the wallplate making sure it is firmly attached 12 180B e check to see that heat or cool system power is on T8600 T8601 T8603 check voltage between R and W or RC R and Y on the T8600 between R and Con the T8601 between C and B C on the T8603 should be 24 to 30 Vac Display will show AC if no 24 30 Vac checkforfresh and correctly installed batteries in the T8602 NOTE On models without system or fan switch disregard instruction regarding moving of switch HEATING Move the system switch to HEAT or AUTO and the fan switch to AUTO Press WARMER key until the setting is about 10 F 6 C above room temperature Heating should start and the fan should run may be a short delay on forced air systems Press COOLER key until the setting is about 10 F 6 C below room temperature The heating equipment should shut off followed by the fan NOTE On an AUTO changeover thermostat T8600D T8601D T8602D the cooling temperature must be set at least 3 F 2 C above the heating temperature or display will flash 22 COOLING CAUTION Do not operate cooling if outdoor temperature is below 50 F 10 C Refer to manufacturer s recom mendations NOTE When cooling setting is changed thermostat will wait up to 5 min
43. equires time and LEAVE temperature settings in the WAKE period but any of the others can be canceled Weekday Saturday and RETURN Sunday settings are canceled separately RUN PROGRAM Press and hold the desired period key until the time and temperature T clear from the display about 3 E seconds Press and release to return to r r normal operation won TUE WD rm CHECKING THE PROGRAM TIMES AND TEMPERATURES It is possible to check all the stored SLEEP settings without affecting the permanent program LEAVE RETURN RUN PROGRAM lt Press and release the desired I zl tem period key The start time and MON TUE WED THU FN temperature setting will appear on the display Press and release to display the next daily time and temperature for that period Press and release to return to normal operation CHECKING THE CURRENT PRESENT TEMPERATURE SETTING SETTING Press a single key to compare current room temperature to the settings at any time Press and release The display will I HS show the current temperature HEAT setting for several seconds then revert to the room temperature Applicable if thermostat is set for Adaptive Intelligent Recovery During recovery from energy savings the setting displayed will not match the programmed setting This is because the thermostat gradually changes the temperature setting during recovery to provide most efficient use
44. g desired 4 Application IF YOU HAVE ADDITIONAL QUESTIONS NEED FURTHER INFORMATION OR WOULD LIKE TO COMMENT ON OUR PRODUCTS OR SERVICES PLEASE WRITE OR PHONE 1 YOUR LOCAL HONEYWELL RESIDENTIAL SALES OFFICE CHECK WHITE PAGES OF YOUR PHONE DIRECTORY 2 RESIDENTIAL DIVISION CUSTOMER SERVICE HONEYWELL INC 1885 DOUGLAS DRIVE NORTH MINNEAPOLIS MINNESOTA 55422 4386 612 542 7500 IN CANADA HONEYWELL LIMITED HONEYWELL LIMITEE 740 ELLESMERE ROAD SCARBOR OUGH ONTARIO M1P 2V9 INTERNATIONAL SALES AND SERVICE OFFICES IN ALL PRINCIPAL CITIES OF THE WORLD TRADELINE MODELS TRADELINE models are selected and packaged to replacement value provide ease of stocking ease of handling and maximum TABLE II TRADELINE MODELS ee STAGES SWITCHING MODEL NUMBER HEATICOOL SYSTEM FAN APPLICATION POWER METHOD T8600A 1 l l Gas oil or electric 24 V Powered through a systems with indepen heating or cooling LX p ee HEAT OFF BE ia dently controlled fan in system controls 3 ONAUTO heat backup bateries T8600C HEAT OFF COOL ON AUTO included T8600C 4 1 HEAT OFF COOL ON AUTO 24 V systems with thermostat controlled fan on heat and cool T8600D 1 1 HEAT OFF ON AUTO Gas oil or electric 24V COOL AUTO systems with independ ently controlled fan in heat T8601A Pa Gas oil or electric Powered direct from _ 24 systems with
45. heat electric coo oil heat electric cool 31 T8601D heat cool gas heat electric cool oil heat electric coo 33 T8602A B heat only gas or central electric oil Intermittent Pilot electric decentralized zone valves incompatible or 3 wire zone valves Honeywell or compatible 2 wire T8602C heat cool gas heat electric cool two transformer 38 with fan operation switch List of Diagrams continued T8602C heat cool gas heat electric cool two transformer gas heat electric cool electric heat electric cool T8603A B heat only gas oil Intermittent Pilot T8603C heat cool gas heat electric cool electric heat electric cool oil heat electric cool HEATING ONLY WALLPLATE GAS VALVE FAN OR HEAT RELAY RELAY A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CURRENT DRAW MUST BE BETWEEN 0 08 A AND 1 2 A MODELS WITH ON AUTO FAN SWITCH M1381 FIG 6 T8600A B HEATING ONLY CIRCUIT IN CON TINUOUS PILOT GAS OR CENTRAL ELEC TRIC SYSTEM A A HOT LIMIT CONTROLLER Q A RELAY HEATING ONLY WALLPLATE 1N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AN MAXIMUM PILOT BURNER IGNITER SENSOR CASLE LENGTH 30 in 08ml 3 FACTORY INSTALLED WIRES DO NOT REMOVE IN CONTROLS IN TRANSFORMER CIRCUIT MUST NOT BE IN GROUNDED LEG A
46. ill vary as the seasons change To determine which type of recovery is set into the thermostat make sure thermostat is powered with fresh batteries oris mounted and powered on the wall see page 22 RUN Press Ipnocnan Check thermostat display INDICATES THERMOSTAT IS SET FOR CONVENTIONAL RECOVERY if the O shows in the lower right hand corner see illustration the thermostat is set for conventional re covery For Adaptive Intelligent Recovery remove thermostat from wallplate turn screw 3A on back of thermostat clockwise N until it bottoms DO NOT OVERTIGHTEN Ifthe O does not show the thermostat is set for Adaptive Intelligent Recovery For conventional recovery remove thermostat from waliplate turn screw 3A on back of thermostat out LN 1 2 to 1 turn SET PRESENT DAY TIME STEP 1 SET THE CURRENT DAY AND TIME You can program this thermostat either on the wall or in hand Always press the keys with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard NOTE Check the glossary page 33 for definitions of unfamiliar words Press and release The display ELI Liem shows 1 00 PM Mon Press and hold until the current day alee appears in the display Press and hold until the current time 5 appears the display Be sure AM ie or PM appears as desired The current day and time
47. in T8600 T8601 T8603 and supply power for operation in T8602 Thermostat can be programmed in hand or after mounted on wall batteries must be installed C Temporary program override available by using WARMER and COOLER keys SKIP next program key CHANGE to last program key O HOLD TEMP key provided for indefinite program override vacation holiday 1 Adaptive Intelligent Recovery function brings room tem perature to programmed temperature at programmed time maximizing comfort and energy savings O Adaptive Intelligent Recovery conventional recovery se lection screw included on back of thermostat Fan operation switch included on back of SUPER TRADE LINE models to select either independent or direct thermostat control of fan in heating S M Form Number 68 0056 1 Rev 4 90 Honeywell Inc 1990 CHRONOTHERM Ii FUEL SAVER IMPORTANT THE SPECIFICATIONS GIVEN IN THIS PUBLICATION DO NOT INCLUDE NORMAL MANUFACTURING TOL ERANCES THEREFORE THIS UNIT MAY NOT MATCH THE LISTED SPECIFICATIONS EXACTLY ALSO THIS PRODUCT IS TESTED UNDER CLOSELY CONTROLLED CONDITIONS AND SOME MINOR DIFFER ENCES IN PERFORMANCE CAN BE EXPECTED IF THOSE CONDITIONS ARE CHANGED a SUPER TRADELINE MODELS SUPER TRADELINE controls offer features on available on TRADELINE models and are designed to replace a wide range of Honeywell and competitive controls TRADELINE models are selected and packaged to provide eas
48. lectric heat systems Then set the system switch pue s HEAT The thermostat controls MEAT OFF COOL AUTO your heating system Bm OoOO OFF Both the heating and cooling HEAT OFF COOL AUTO COOL The thermostat controls HEAT OFF COOL AUTO your air conditioning system a AUTO The thermostat controls HEAT OFF COOL AUTO either heating or air conditioning system depending on room temperature The programming of the thermo stat is finished Read on to learn about the operat If thermostat was removed from the j ing flexibility that makes this wall to program replace it following Et thermostat THE SMART CHOICE the procedure on page 22 2 29 5 68 0056 1 op E 1 dp i EKI pofi ye uis i dos i MN oM an A PN DUCTA IN E M no ewe tp os a PROGRAM These features allow the program to be custom tailored for those times when someone comes home early or stays up late or plans to be out for the evening To keep the current temperature through the next program period SKIP NEXT PERIOD CHANGE TO LAST PERIOD To go back to the temperature of the previous program period To temporarily raise or lower the temperature for the current period only To change back AUN PERMANENTLY CHANGING THE PROGRAM If schedule changes or a different temperature is desired it is possible to update any setting without affecti
49. ng the rest of the program SLEEP RUN PROGRAM gt lt OPERATING THE THERMOSTAT MANUALLY E p Q m D m z This feature is particularly useful when going on vacation or other extended absence It does not cancel the program Press and release The name of the period to be skipped will flash in the display until the next regularly scheduled period starts Press and release The display will show the name of the previous period and flash temporary until the next regularly scheduled period starts Press and hold until the desired temperature is reached The display will flash temporary until the next programmed time period starts Press and release to cancel any of the temporary settings Press and release the desired period key Press and hold until the desired schedule day shows on the display Press and hold the Time or Temperature keys until the display shows the desired new program Press and release to return to normal operation Press and release Press and hold to change the temperature setting After a few seconds the display will show the current temperature 30 EE a RUN PROGRAM Press and release to check the 10 temperature setting Press and release to cancel manual control NOTE Moving the system switch also cancels hold CANCELING PROGRAM SETTINGS xd The thermostat r
50. nstall the thermostat where it may be affected by drafts or dead spots behind doors in corners or under cabinets hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas behind the thermostat such as an outside wall If Replacing An Existing Thermostat Turn thermostat power off at furnace or boiler A mul TG586A Locking Cover 202384B Resistor for T8600 REPLACEMENT PART 220529A Replacement Door Assembly tiple transformer system may require turning off multiple switches or disconnects Remove any existing wallplate or subbase from wall Label each wire with or write down the letter or number on the wiring terminal as the wire is removed to avoid miswiring later If New Installation Runcableto ahole atthe selected wall location and pull about 3 in 76 mm of wire through the opening Color coded 18gauge thermostat cable with at least one conduc tor for each wiring terminal is recommended Good service practice recommends selection of cable with one or two more conductors than the immediate application requires MOUNTING WALLPLATE Remove thermostat from wallplate Fig 2 FIG 2 REMOVING THERMOSTAT FROM WALL PLATE WIRES THROUGH WALL OPENING ANCHORS 2 HOLES 3 Z yx 2 WALLPLATE D MOUNTING SCREWS 2 1N USE TWO MOUNTING HOLES THAT BEST FIT APPLICATION 12 134 FIG 3 MOUNTING WALLPLAT
51. o 31 C CALIBRATION Self calibrating thermostat and ther mometer to 1 F SHIPPING TEMPERATURE minus 20 F to plus 120 F minus 29 C to plus 49 C CYCLES PER HOUR ADJUSTMENT Heating factory set at 6 cph adjustable to 1 3 or 9 cph for special systems Cooling factory set at 3 cph not field adjustable FINISH Beige matte over decorative brushed metal faceplate requiring extra wire s to thermostat backup batteries included Typical older and commercial electric heat and water coil applications eln freezing climates be sure the cooling compressor has adequate cold start protection dently controlled fan in heat DIMENSIONS Thermostat mounted on wallplate 7 in 178 mm long 4 1 16 in 103 mm high 1 3 4 in 44 mm deep See Fig 1 for wallplate dimensions FIG 1 T8600 T8601 T8602 T8603 WALLPLATE MOUNTING DIMENSIONS IN in mm IN BRACKETS 68 0056 1 ACCESSORIES 193121A Cover Plate Assembly includes cover plate adapter ring and screws Covers marks left by old thermostat Allows mounting on vertical or horizontal outlet box 6 9 10 in x 4 3 4 in 175 mm x 121 mm COMPATIBILITY The T8600 Thermostats will replace most heating or heating cooling system thermostats and are designed to be part of a Honeywell control system They can be used with other control systems but an isolating relay may be needed in the thermostat control circuit See Table Ill
52. o Zone RB 4 R8239D1015 HEAT COOL INTERLOCK R8239 with RC R thermostat Lennox GCSI Series 21 Ps ln n The wallplate does not require leveling for operation but for appearance only The wallplate mounts directly onto the wall with the screws and anchors included in the package Use the wallplate as a template and with a pencil mark two of the three mounting holes in the wallplate Fig 3 If drywall con struction plastic anchors must be used use 3 16 in bit to drill holes for anchors Gently tap anchors into holes until they are flush to the wall surface Thread wires through the center opening of the wallplate Then mount the wallplate using two screws provided Gently tighten screws level top surface of wallplate then securely tighten screws WIRING All wiring must comply with local electrical codes and ordinances Disconnect power before wiring to prevent electrical shock or equipment damage The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections Either method is acceptable Fig 5 Push excess wire back into the hole and plug hole with nonhardening caulk putty or insulation to prevent drafts from affecting thermostat operation Refer to Figs 6 49 for typical hookups of wallplate and thermostat For T8600 single transformer system using wallplate with RC R terminals jumper RC and R as shown in Fig 4 NOTE Keep all wiring restricted
53. of the heating or cooling equipment 31 68 0056 1 Start the system by setting the thermostat and observing system response If problem occurs establish symptom and use the following troubleshooting chart to check for possible cause and action SYMPTOM POSSIBLE CAUSE ACTION CHECK POWER TO FURNACE OR AIR CONDITIONER ON OFF SWITCH FUSE OR CIRCUIT BREAKER LOOSE 24 V CONNECTION AT THERMOSTAT AT FURNACE AIR CONDITIONER INCORRECT WIRING CHECK WIRING DIAGRAM ROOM TEMPERATURE DISPLAY IS AC T8600 T8601 T8603 NO ac POWER TO THERMOSTAT CHECK POWER TO FURNACE OR AIR CONDITIONER ON OFF SWITCH FUSE OR CIRCUIT BREAKER LOOSE 24 V CONNECTION AT THERMOSTAT AT FURNACE AIR CONDITIONER INCORRECT WIRING CHECK WIRING DIAGRAM THERMOSTAT INOPERATIVE CONDUCT SELF TEST SEE CHECKOUT ADJUST TEMPERATURE BY PUSHING WARMER COOLER KEYS RESET THERMOSTAT SYSTEM SWITCH FURNACE OR AIR CONDITIONER WON T OPERATE NO ac POWER TO THERMOSTAT PRESENT SETTING TOO LOW HIGH SYSTEM SWITCH ON THERMO STAT IN WRONG POSITION MEM MEE WAIT 5 10 MIN OR USE SELF TEST IN THERMOSTAT SEE CHECKOUT THERMOSTAT IN OPERATION ON COOLING INCORRECT WIRING CHECK CIRCUIT DIAGRAM CHECK COMPATIBILITY CHART UNDER INSTALLATION ADD R8239 OR 202394B IF NECESSARY SYSTEM NOT COMPATIBLE T8600 FURNACE OR AIR CONSULT FURNACE OR AIR CONDITIONER CONDIT
54. time 26 500 MON TUE WED THU FRI E 743 n PLI L MON TUE WED THU FRI WAKE 7M n PLI L ii MON TUE WED THU FRI WAKE MON TUE WED THU FRI LEAVE B30 MON TUE WED THU FRI EAVE B30 MON TUE WED THU FRI LEAVE MON TUE WED THU FRI RETURN SU Lew MON TUE WED THU FRI RETURN ror LI lem MON TUE WED THU FRI LH TI UL MON TUE WED THU FRI SLEEP HEAT re EA des HEAT zo HEAT DDF HEAT B 5 HEAT 7 t LIS MEAT ter HEAT Press and hold until the display pan Gu shows the desired temperature MON TUE WED THU P HEAT Set the SATURDAY schedule Use e Press and hold until SAT appears nmn ne the same procedure as for week 7T on the display Ma MM days SLEEP Press WAKE LEAVE RETURN or SLEEP to select the time period LEAVE Use the AHEAD BACK keys to set the time and the WARMER COOLER keys to set the tempera BACK ture b Set the SUNDAY schedule Use the a Press and hold until SUN appears Imo ne same procedure as for weekdays DAY on the display SUN A A Press WAKE LEAVE RETURN or SLEEP to select the time period LEAVE Use the AHEAD BACK keys to set a the time and the WARMER COOLER keys to set the tempera E3 The setting of the program sched ule and heating temperatures has been completed If system has air conditioning go to Step 3 NOTE Some models will show AC RUM If system does not have air condi
55. uino nr _ indicating the thermostat is operat tioning press and release to start M bau d ing on backup batteries until the the program Go to Step 4 thermostat is mounted on the wallplate and the system is pow ered STEP 3 Press and release The display criti TMO SET THE COOLING TEMPERA shows WAKE and the time and j 4 TURES IF SYSTEM HAS AIR temperature programmed for CONDITIONING heating The program times are the same for both heating and cooling Only the cooling temperatures need to be SET Press and release so COOL shows cerita TIS programmed if thermostat has HEAT COOL on the display along with the QUUM already been programmed for preprogrammed cooling tempera me heating To set times as you ture program the cooling temperatures use the TIME AHEAD and BACK keys as described in Step 2 If display reads SAT or SUN press First program the WAKE tempera DAY and hold until MON TUE WED THU EN ture for weekdays FRI appears 27 68 0056 1 Press and hold until the display Waaa db shows the desired temperature sci TUEWED THUR lf the display blinks while holding down TEMPERATURE WARMER or COOLER the setting limit has been reached If thermostat can switch automatically between heating and cooling the cooling temperature must be at least 3 degrees higher than the corre sponding heating temperature For example if the heating setting is 70 F the minimum cooling setting is 73 F
56. until your programmed WAKE time but of course it will take a little while for your house to heat up to the comfort temperature Remember whichever way you set your thermostat if it is so cold outside that your house drops to your sleep temperature the furnace will turn on and off at night to control the temperature at that setting What does the HOLD key do It bypasses all program settings and holdsthe tempera ture at the present setting To increase or decrease the temperature while on HOLD use the WARMER COOLER keys Touching RUN PROGRAM will return the device to programmed operations How long does the HOLD key hold Forever The HOLD key will hold the temperature in definitely The only way to release it is to push the RUN PROGRAM key orchange the system switch positions if applicable For a temporary temperature change simply press WARMER or COOLER key This tempo 34 rary setting will last until the next scheduled program begins How can this thermostat save energy when it comes on and off so many times early in the morn ing hours Two ways First it saves energy and money by setting back the temperature for blocks of time during the day or night Second it conserves energy by recovering gradually to the desired temperature This prevents overshooting your comfort set point and wasting en ergy or undershooting the comfort set point and forc ing you to change the thermostat setting also wasting
57. ures forthe Press and hold until SUN appears SUNDAY schedule Use the same on the display E procedure as for weekdays EE Press WAKE LEAVE RETURN or SLEEP to select the time period I Use the WARMER COOLER keys to set the temperature The programming of the cooling I temperatures has been completed NOTE Some models will show AC _ m Press and release to start the indicating the thermostat is operat program RS ing on backup batteries until the Go to Step 4 thermostat is mounted on the wallplate and the system is pow ered RI STEP 4 LE FAN ON The fan runs continu EA ON AUTO SET THE SYSTEM AND FAN ously Use for improved air circula MENS SWITCHES IF THERMOSTAT _ tion during special occasions or for 1 HAS THEM more efficient electronic air clean TAR mE ing Depending on thermostat model i some or all of the switch positions FAN AUTO Normal setting for ran ON AUTO 1 shown may be available Note the most homes The fan goes on and S NES positions provided on thermostat off with the air conditioner in then set the switch es as desired summer In winter the fan on most m ibo x 3 systems starts a few minutes after First set the fan switch the furnace comes on It stops a HO pe few minutes after the furnace goes Bo a V deus Ge off The fan starts and stops with uu the furnace in some e
58. utes before turning on the air condi tioner This delay protects the compressor Move the system switch to COOL and the fan switch to AUTO Press COOLER key until the setting is about 10 F 6 C below room temperature The cooling equipment and fan should start Press WARMER key until the setting is about 10 F 6 C above room temperature The cooling equipment and fan should stop NOTE On an AUTO changeover thermostat T8600D T8601D T8602D the heating temperature must be set at least 3 F 2 C below the cooling temperature or display will flash FAN Move the system switch to OFF and the fan switch to ON The fan should run continuously When the fan switch is in the AUTO position fan cycles with the heating or cooling system INSTALLER SELF TEST optional IMPORTANT Five minute time delay on cooling does not function during self test Perform the following test as a check of all thermostat functions f thermostat does not respond as indicated thermostat must be replaced 1 Press AHEAD and BACK keys at the same time While holding keys down all segments of the display should be on Fig 53 2 Set system switch to OFF where applicable Press AHEAD and BACK and PRESENT SETTING keys at the same time to enter self test 3 Press each key as listed below and look for re sponses listed as key is held down and released LOOK FOR THIS RESPONSE KEY PRESS THIS KEY KEY DOWN RELEASED PRESENT

Download Pdf Manuals

image

Related Search

Related Contents

取扱説明書 お客さまへ  SI-5XA0A - Shimano  Table of Contents Introduction ........................................................  Samsung SGH-M150 Benutzerhandbuch  TR128 - カーメイト  DMM 210    KDC-W4037 KDC-W3537 KDC-W3037 KDC-W311 KDC  

Copyright © All rights reserved.
Failed to retrieve file