Honeywell IPGSM-4GC User's Manual

image

Contents

1. 2 mH 2 CD ERTH GND Q mmm m RM GRN TX YEL RX Q ours g2 Hp RED E u E 2 EE o z 33 ee 2 feo l5 JB ga BLK De 0 aa GNU a d OUT e asa Dc 5 Pc our JE S ee Commuicator AC ON GRA 2 EMI uu I DC G og STATUS mw g N U L ii FACTORY 55 6 UT m USE ONLY barre 1 C bE o gr CELLULAR FUSE gt o2am UAR STATUS E PROGRAMMER LED q D PN 100 02415 PORT TB 1 1 15 l avin RSSI MODE O i 2 END INDICATORS Tee eae H BATTERY 6 ECP Out T SWITCH MODE o 7AH 18 SWITCH 9 oH not supplied 10 NETWORK Use a Honeywell 712BNP CONDUIT DII CONNECTIVITY P7 UA ivl as E LEDs Yuasa NP7 12 or equivalent TN To Router To Fire Panel To Fire Panel IPGSM 4GC 007 VO NOTES e All circuits are power limited except the backup battery which is non power limited e Non power limited wiring must be separated from the power limited wiring by at least 1 4 inch e If desired use a Honeywell 955WH Tamper Switch with the 28 2 bracket FEDERAL COMMUNICATIONS COMMISSION STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User s Manual Unauthorized changes or modifications could void the user s authority to operate the equ
2. Data Out amp joeeg PWRI O O GREEN C Dialer Capture Module Communicator a S E oO o E S D He csl el el LO O 3o s z 6j i iB OTe o S 65 5 a e 6 ee BATTERY FUSE PN 100 02415 BATTERY 7AH not supplied Wiring for Grounds Power and RF TO Cabinet Ground Post GND IPGSM 4GC 001 VO IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide Wiring the 659EN Line Fault Monitor Required for ULC The IPGSM 4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor also known as the HFS 659EN is installed Note the wire colors may vary 1 2 3 4 Refer to the installation guide for the 659EN Mount the 659EN on the lower left side of the IPGSM 4GC cabinet DO NOT cut the 659EN s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper Complete the interface wiring as shown below YEL to Dialer Capture Module Terminal Tip 2 ORG to Dialer Capture Module Terminal Ring 2 RED to Power Boost 1 Terminal OUTPUT 1 DC BLK e to Power Boost 1 Terminal OUTPUT 1 DC GRN gt to Power B
3. Program Device Y N Press Shift then Y then 7 Com Path Choice IP amp GSM Press Space to scroll choices IP amp GSM IP or GSM When IP or GSM or IP amp GSM is chosen the IPGSM 4GC functions as an active communication system At choice press 7 Primary City ID Enter number 01 99 then press 7 Primary CS ID Enter number 01 FE then press Primary Sub ID Enter number 0001 9999 then press 7 Note If a Com Path Choice of IP amp GSM or IP was selected prompt 9 will appear Use DHCP Y N Y If your router is configured for DHCP press Shift then Y then press 7 Note If DHCP is not selected your router is set for a static IP prompts 10 through 13 will appear Use the Space key to advance to the next address part NIC IP Address Enter choice then press 4 Follow the prompts 255 255 255 255 Subnet Mask Enter choice then press Follow the prompts 255 255 255 255 Gateway IP Address Enter choice then press Follow the prompts 255 255 255 255 DNS Serv IP Addr Enter choice then press Follow the prompts 255 255 255 255 Review Y N Enter choice then press Follow the prompts Create Password Y N Enter choice then press Follow the prompts Exit Prog Mode Y N Press Shift then Y then press DONE Notes e If an error i
4. Steady ON Messages exist in buffer RED Flashing No messages to be sent Waiting for messages GREEN Steady ON Normal Indication GREEN Blinks every 2 sec PowerBoost1 communication problem GREEN Blinks twice every sec Connection with the Communicator is lost GREEN Blinks 10 times every sec PowerBoosti and Communicator connections are lost Tip2 Ring 2 n zi LLI Telco 2 Telco 1 e ZN EOL EOL ZN PWR GND C Dialer Capture Module Note Telco ports 1 primary dialer and 2 secondary dialer may be used instead of the terminal board Tpi Ring 1 Data Out Whichever connection method is used both Telco paths must be connected to the Fire Panel o e GREEN iPGSM COM 004 VO LED Display Information Status LED Indicator RADIO TROUBLE Yellow ON when radio trouble is present zn e Both IP and GSM communication paths are lost RADIO TROUBLE e Communicator radio is not registered 5 e Old Alarm Time has been exceeded Message has not been N delivered within the fixed 10 minute window 8 Buzzer Upon loss of AC power this will beep once every 10 LOW BATTERY O seconds o t used LOW BATTERY Yellow ON when battery is low 11 5VDC meee S8 SETS AC Loss LO e
5. Secondary Communication Path Supervision E350 C0952 R350 C0952 Periodic GSM Comm Path Test Failure E358 C0803 N A We do not send a restoral R358 C0803 we send a failure message every day after the radio attempts to test and fails Trouble Reporting E380 E351 E352 N A When a single fault open or short IP GSM suppression low missing battery Codes as AC loss occurs and the communicator is programmed for an IP amp GSM appropriate communication path multiple alarm Codes and their appropriate Restore Codes are reported to the Central Station IPGSM 4GC communicator fault The Fire Panel sends out a E380 and E352 message via Telco 1 these are then relayed to the central station via the IPGSM 4GC Telco line 1 fault The Fire Panel sends out a E380 and E351 message via Telco 2 these are then relayed to the central station via the IPGSM 4GC Telco line 2 fault Fire Panel sends out a E380 and E352 via Telco 1 these are then relayed to the central station via the IPGSM 4GC Test 5555 5555 9 N A Iur Specific to COMMERCIAL Control Panels Such as the VISTA 32FB and VISTA 128FBP 250FBP series Communicator Trouble low battery ECP bus network Possible E333 C0803 R333 C0803 Compromise Indication Radio Loss of Signal E357 C0803 R357 C0803 or Possible Compromise Indication R380 C0803 Radio Fault low battery tamper ECP Bus E333 C0803 R333 C0803 AlarmNet Messages Communication failure 5555 1555 6 5555 3555 6 Possib
6. active 950mA Environment Operating temperature 209 to 55 C for ULC installations 0 C to 49 C Storage temperature 409 to 70 C Humidity 0 to 95 relative humidity non condensing for ULC installations 0 to 93 Altitude to 10 000 ft operating to 40 000 ft storage Supervision The Radio communicator battery and AC power conditions are monitored by the cabinet indicator LEDs RADIO TROUBLE lights when any of these conditions exist e Both IP and GSM communication paths are lost e Communicator radio is not registered e Old Alarm Time has been exceeded Message has not been delivered within the fixed 10 minute window LOW BATTERY lights when the battery voltage is less than 11 5VDC AC LOSS lights when the AC power is less than 90VAC 13 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide NOTES 14 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide NOTES 45 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide NOTES 16 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide NOTES 17 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide NOTES 18 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide NOTES 49 IPGSM 4GC Commercial Fire Communicator Installation
7. and Setup Guide NOTES 20 Wiring Diagram The wiring diagram below is depicted for point to point electrical connection checks used for troubleshooting or component replacement It is not intended to show the physical routing of wires When replacing a wire or component ensure the wire is routed in the same manner as the original factory wire Note Wire colors may vary 1451 UL9 WIRED ANTENNA TRANSFORMER WIRES MUST BE RUN IN CONDUIT 2 FACILITY POWER 120VAC 60Hz 850mA 18 VAC F 72 VA TO Cabinet Ground Post GND i BLU TO PowerBoost1 Es DO NOT REMOVE these knockouts Buzzer OPTIONAL CABINET WHT LO BATT j TAMPER SWITCH LED Display RADIO PowerBoost1 TROUBLE CABINET DOOR Buzzer g Tip2 Ring 2 amp Data Out YEL Data in GRN amp 12V In RED HiL ECP o LOW BATT not used AC LOSS H c VIO 1 BLK WHT RED BRN i YEL GRA AC ON k E A D m e a a 2 8 El 8 GREEN C Dialer Capture Module Tin wire ends W NN
8. any password that may have been entered Set Default Press Y to reset factory default values YIN Press N to cancel this function Press Shift then Y then 4 The Create Password prompt appears follow the prompts then exit STEP 6 Confiqure the Fire Panel 1 Ensure the Phone Line Supervision or Telco Fault on the panel is enabled Then choose a setting that is no higher than 90 seconds or as close to that as the panel allows 2 Ensure no more than 1 pause character usually a comma is programmed into the dialing string usually 2 seconds Note this is necessary since the Dialer Capture Module waits only 3 seconds after the phone number is dialed Having more than 3 seconds of pause time will cause it to think the phone number is complete and cause it to generate the high low tones at an incorrect moment STEP 7 Test the System 1 Close the 1451 UL9 Wired Transformer enclosure then close and lock the cabinet cover 2 Refer to the fire panel s installation operation guide for the testing procedure 3 Notify the monitoring station that a test will be conducted Test the system to ensure it is operating 4 Verify communications with the monitoring station is successful by sending several events Also get confirmation that these events were received IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide Dialer Capture Module Information LED Indicator STATUS RED
9. charged 12V battery 2 Attach the Antenna Mounting Adapter RF cable and Antenna see illustration on page 6 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide Temporarily wire the battery s negative terminal to TB1 4 on the communicator then wire the battery s plus terminal to TB1 2 on the communicator Wait about one minute for the communicator to initialize Position the assembly near a suitable mounting position and observe the RSSI display Look for a mounting position that yields at least 3 bars lit solid For optimal performance 4 or 5 bars are better B K K K sev HR Y Y GGG Verify the signal strength remains steady for a few minutes then mark that mucosa mounting position Disconnect the battery STEP 4 Mount and Wire e For ULC compliant installations refer to the topic on ULC Compliance in this manual e For ULC compliant installations the Telco line wiring and the Power Transformer wiring must be routed through conduit e For Dry Indoor use only e Additional cabinet wiring may be routed through conduit if desired This communicator comes partially assembled with all the components mounted except the external Antenna LED Display board and PowerBoost1 To protect certain components on the PowerBoost1 it is shipped un mounted All internal wiring is complete 10 Note Refer to the diagram on page 6 and to the Wiring Diagram on the inside of the b
10. Honeywell IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide RADIO TROUBLE LOW BATT AC Loss AC ON 800 12458 7 12 Rev C Contents lem Impensis a E A AE E 1 Package OES AEE EEEE EEE EEE T E A 1 Compatible Fire PaPe S 3 5 1 5 8 a Sal ee a ee ee ae 1 OPS AU OM cates 260 26 052 E E A T E T 1 Installatiohh zielt at wade eet ete a ee es ah es eae aaaeaii ididiin 1 ULC Compliance EU 1 STEP Setup th Customer ACCOUHE 5 222 exis Eesti Ceo eet od EE ete LIAE CREE LE LEE ELIGE CES ELLE aaea 2 STEP 2 Register the Communicator with AlarmNet eeeeeeeeeee ener 2 STEP 3 Determine the Signal Strength and Select a Location eeseeeeeeenneennne 2 STEP 4 Mount and Wire 5 25 20 ere cte ete cas eeepc t o ene een pana Pn e eae nne nuin a9 aaea easa iaa ea iari 3 Wiring the 659EN Line Fault Monitor if required eseeeeeeeeeeeennnnen nnn 6 STEP 5 Program the Communicator eeeeeseeeeee eee eene nennen nnn nnn nnn nnn nnn nara 7 STEP 6 Config re the Fire Panels iii eiiis ie ri Eee et Eso ea teed eee e cg cu ee eo ded de ep esed e erg es ede cree ede 8 STEP 7 Test the Systemae ie iae eea TIT 8 Dialer Capture Module Informatiofi 22 25 32 1 22 a a a aaa adiada 9 LED Display Information eeeeeeeeeeee eene nennen nennen a a nnn nnn nnn nnn nna aada N
11. V technician for help INDUSTRY CANADA CLASS B STATEMENT This Class B digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe B est conforme a la norme NMB 003 du Canada FCC IC STATEMENT This device complies with Part 15 of the FCC Rules and RSS210 of Industry Canada Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation Cet appareil est conforme a la partie 15 des r gles de la FCC amp de RSS 210 des Industries Canada Son fonctionnement est soumis aux conditions suivantes 1 Cet appareil ne doit pas causer d interf rences nuisibles 2 Cet appareil doit accepter toute interf rence recue y compris les interf rences causant une r ception ind sirable RF Exposure Warning The antenna s used for this transmitter must be installed to provide a separation distance of at least 20 cm 7 8 inches from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter DOCUMENTATION AND ONLINE SUPPORT For the latest documentation and online support information please go to http www honeywellpower com Contact Technical support at 1 800 778 9958 Ext 3131 WARRANTY For the latest warranty information please go to http www honeywellpower com warranty html Honeywell 10 Whi
12. aS nnn nan 9 PowerBoostt Information e cei a whic einen be kie et M OEC E Se dd d ee 10 Communicator INFOMATION ease cere coe cue near ene n adacedecedaccdegedace ecedacudecedacsvtcedaceacaseasulasavassvegstasiset 11 adgiejo io iIe io ace 12 Central Station Messages 2 7 ene retener ig ta s etes cup c ies ga a do erga aa Ry DE ee EXER aasa de ane gay Eo aUa 12 IPGSM 4GC Trouble Detection Information seeeeeeesesessseseseeeeeeeeeeennnnn nennen nnn nnns 13 IPGSM 4GC SpecificatiOns 25 22 7 ceridatecadacetacedacedecudecetucedacadecesecctacedusadecssscetnccdugadecescccceccdaustecsvers 13 MT IncabIr Te ep EEG Inside of Back Cover IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide General Information The IPGSM 4GC Commercial Fire Communicator henceforth referred to as IPGSM 4GC includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path and uses a GSM cellular reporting path as a backup In addition the communicator s power module PowerBoost1 monitors and reports AC power loss and low battery conditions NOTE When programmed for an IP or GSM or IP amp GSM reporting path this product functions as an ACTIVE communication system Package Contents e Red Fire Cabinet and Back Plate e Antenna and Mounting Adapter e Mounting Rails for above e Cam Lock with Key e Powe
13. ack cover of this manual for wiring and component identification Remove knockouts from cabinet to accommodate the power input wires and wiring to the fire panel DO NOT REMOVE the two knockouts directly above the PowerBoost1 Then mount the cabinet securely to the wall using 4 screws or bolts Use screws or bolts that are suitable for the material being anchored to Ensure the cabinet door lock is installed Install the two plastic mounting rails for the LED Display board They simply snap into the back plate holes Connect the LED Display board to its connector then slide the board into the mounting rails Refer to the LED Display Information topic if a wire is detached from its connector Carefully remove the packaging material that surrounds the PowerBoost1 Mount the PowerBoost1 on the three unused standoffs Use the two metal screws and lock washers to fasten the left side of the circuit board Ensure the lock washers are located between the circuit board and the head of the two metal screws The right side of the board just snaps in place on the upper right standoff Use the 1451 UL9 Wired Transformer directly connected to un switched facility power Connect and route 14AWG minimum insulated wire from facility ground to the 1451 UL9 enclosure ground post and through the conduit to the IPGSM 4GC cabinet ground post Route wire minimum 18AWG from the transformer secondary through the conduit to the cabinet Pass the wires throu
14. cation mode with the control panel LED 3 yellow OFF MODULE S STATUS When the Mode Switch IS depressed LED 1 will be OFF e LEDs 4 5 and 6 indicate the module s Status LED 4 green LED 5 green LED 6 green ON Connected to ON GPRS service ON Module registered no second Internet available site available OFF Not connected OFF No GPRS service OFF Module not registered with to Internet available network carrier FAST BLINK GPRS in SLOW BLINK Module registered use second site available and low signal strength NORMAL BLINK Module registered second site available acceptable signal strength FAST BLINK Module registered second site available excellent signal strength IPGSM 4GC 012 VO 11 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide RF Specifications Frequency Bands 2G GSM GPRS EDGE Quad Band 850 900 1800 1900 MHz 3G 4G UMTS HSPA Band V Band II Output Power 2G GPRS 33dBm GMSK modulation EDGE 27dBm 8 PSK modulation 3G UMTS 24dBm QPSK modulation WCDMA 24dBm QPSK modulation 4G HSPA 24dBm 64 QAM modulation WCDMA 24dBm 64 QAM modulation Central Station Messages Alarm Condition Alarm Code Restore Code Power On Reset E339 C0803 N A ECP Supervision Compromise Indication E355 C0000 R355 C0000 Primary Communication Path Supervision E350 C0951 R350 C0951
15. gh the Ferrite Filter then loop the wires back through again making a loop Ensure the wire ends that connect to the PowerBoost1 are tinned or equivalently arranged Connect the wires to the PowerBoost1 AC terminals At this time DO NOT apply power Ensure all ground connections are tight Connect the Ethernet cable and the Telco 1 and Telco 2 lines If you choose to use an optional Cabinet Tamper Switch if the fire panel supports it mount and wire it 3 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide 11 Verify the PowerBoosti DIP switches are configured as shown below PowerBoost1 T ur 3 ni Els Switch handle white iPGSM COM 008 VO 12 Ensure the following e LED Display board is fully seated e All wiring terminals and connectors are tight e All wiring has been completed and secured with cable ties 13 Install the battery not supplied Apply power to the 1451 UL9 Wired Transformer and attach the battery cable IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide ANTENNA N NUT WASHER ANTENNA MOUNTING ADAPTER N CABINET DOOR J TO Facility Ground J CONDUIT E FEL 13 TO 24 HR FACILITY POWER 120VAC 60Hz 850mA 1451 UL9 WIRED WIRES MUST BE TRABSEORMER RUN IN CONDUIT TO PowerBoost1 a DO NOT REMOVE these knockouts
16. grammed Devices GSM T Search for the account using the Account Information or MAC ID Under the Actions column use the pulldown menu and choose Register OR e After the IPGSM 4GC is installed and programmed you can register the communicator by clicking the Tamper Switch 3 times OR e After the IPGSM 4GC is installed and programmed you can register the communicator using the 7720P Programming tool Simply Press Shift then press Please wait for Registration SUCCESS message STEP 3 Determine the Signal Strength and Select a Location IMPORTANT Do Not mount this device outdoors RF Exposure Warning The antenna s used for this transmitter must be installed to provide a separation distance of at least 20 cm 7 8 inches from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter When choosing a suitable mounting location understand that signal strength is very important for proper operation For most installations using the supplied antenna mounting the unit as high as practical and avoiding large metal components provides adequate signal strength for proper operation In this procedure you will use the Communicator to determine signal strength in order to find a suitable mounting location Note Since the SIM is already activated the RSSI signal strength indicators will indicate signal strength 1 Forthis procedure you will need a fully
17. he fire panel The fire panel then sends the contact ID reports to the IPGSM 4GC which in turn sends a kiss off after the report is successfully received from the fire panel Within the IPGSM 4GC the Dialer Capture Module sends the contact ID reports over the ECP bus to the Communicator When all the reports are sent the fire panel goes on hook The IPGSM 4GC then transmits the messages to the central station either over the internet or the GSM network Installation ULC Compliance This product is compliant with CAN ULC S559 Equipment for Fire Signal Receiving Centers and Systems To meet this specification ensure the following e IPGSM 4GC must be installed in accordance with Canadian Electrical Code Part 1 e IPFSM 4GC must be used with compatible Fire Panels that have the 659EN Line Fault Monitor installed e IPGSM 4GC must be mounted in the same room and within 20 feet of the fire panel e The Telco line wiring and the Power Transformer wiring must be routed through conduit e IPGSM 4GC and all equipment used for the IP connection such as the router hub modem etc shall be listed must be powered from an un switched branch circuit and be provided with appropriate standby power e IPGSM 4GC must use a 7AH battery not supplied to provide 24 hour backup capability 1 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide STEP 1 Setup the Customer Account The communicator requires a subscr
18. iber account customer account to be setup with AlarmNet Direct This is accomplished by registering the communicator with AlarmNet Registering enables the fire panel to send reports To setup the customer account you will need to contact the central monitoring station to get account information and have access to the AlarmNet Direct website To access the AlarmNet Direct website visit https services alarmnet com AlarmNetDirect If you do not wish to use the AlarmNet Direct website you may call AlarmNet to setup the account just phone 800 222 6525 then select option 1 Monday Friday 8 00 am to 9 00 pm Saturday 9 00 am to 5 30 pm EST Have the following information ready e Primary City ID two digits obtained from your e Primary Subscriber ID four digits obtained from monitoring station your monitoring station e Primary Central Station ID two digits obtained from e Communicator s MAC ID and MAC CRC number your monitoring station located on outside of box and inside the communicator Note The SIM supplied for the IPGSM 4GC is already activated Therefore no SIM activation is necessary STEP 2 Register the Communicator with AlarmNet Registering the communicator activates the account with AlarmNet and enables the fire system s control panel to send reports There are three methods that can be used to register the communicator e Register the communicator by logging into AlarmNet Direct and choosing Show Pro
19. ipment CLASS B DIGITAL DEVICE STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use The FCC requires the following statement for your information This equipment generates and uses radio frequency energy and if not installed and used properly that is in strict accordance with the manufacturer s instructions may cause interference to radio and television reception It has been type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures If using an indoor antenna have a quality outdoor antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits Consult the dealer or an experienced radio T
20. le Compromise Indication Authorized Radio Substitution 00D0 010C 0 N A Unauthorized Radio Substitution Attempt 00D0 010E 0 N A Service Termination 00D0 020E 0 N A 12 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide IPGSM 4GC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM 4GC and Telco 2 is used by the IPGSM 4GC to report faults to the Fire Panel If Telco 1 is not operational the Fire Panel will use Telco 2 to report events if there are no faults in the Communicator Fault Condition Indication to Fire Panel PowerBoost1 fault Telco 2 is cut Communicator fault e Failure of the communications path when Telco 2 is cut IP only or GSM only is programmed as a communications path e Failure of both communications paths Telco 1 and 2 are cut when IP amp GSM is programmed as a communications path Dialer Capture Module buffer is full Hang up Panel will retry giving the buffer a chance to empty IPGSM 4GC Specifications ITEM SPECIFICATION Cabinet Dimensions Width 12 3 4 inches Height 14 7 8 inches Depth 3 inches Transformer 1451 UL9 Primary 120VAC 60Hz 850mA Secondary 18VAC 72VA Battery 12V 7Ah sealed lead acid type not supplied Use a Honeywell 712BNP Yuasa NP7 12 or equivalent Battery Charging Current maximum 1A Battery Discharge Current standby 230mA
21. llow not use AC ON O AC LOSS Yellow ON when no AC is present lt 90VAC AC ON Green ON when AC is present Note If a wire pulled out of the LED Board Connector Violet LED Board refer to the diagram on right and reinsert wire ensuring Black Connector the connector pin is locked in White Red Brown Yellow Gray IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide PowerBoost1 Information LED Indicator STATUS AC green AC power available ACTIVE green Cyclical flashing normal communications Repetition of 3 flashes loss of communications LOW BATT yellow Missing or low battery TROUBLE yellow One or more trouble conditions exist such as overload output supervision ground fault or charger failure Notes e If AC power is lost and the battery voltage falls below 10v the PowerBoost1 output voltage will be turned off The output power is turned back on when AC power is restored e You must use the DIP switch settings shown below LowpBaTTLED PowerBoostl TROUBLE LED INDICATOR p a ecl INDICATOR B Configure DIP switch as shown ON 12345 Switch handle white AC LED Mo INDICATOR X ACTIVE LED INDICATOR iPGSM COM 003 VO 410 IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide Communicator Information ON NOT registered with Alar
22. mNet Cellular Status LED OFF Registered with AlarmNet Voice Session FAST BLINK Download session with Compass fl Short blink every second in progress SLOW BLINK In unison with yellow LED Senna i p registration in progress B Xo ort blink every 2 seconds ON Message transmission pending UN Connected to Cell network QUICK PERIODIC BLINK Normal Short blifik every f sec nds FAST BLINK Message waiting for network ACK No or deactivated SIM SLOW BLINK Idle power abnormal Long blink every second SLOW BLINK In unison with green LED registration in progress ON No contact with network PLN OFF Normal RSSI Mode SLOW BLINK Loss of communication with the and Dialer Capture Module ECP fault status LEDs FAST BLINK No network contact AND loss of communi cation with the Dialer Capture Module Note If all LEDs FAST BLINK in unison with the RSSI LEDs this indicates a Hardware Error ON 100 MB S link to Internet Link Speed OFF 10 MB S link to Internet GREEN ON Link detected Ethernet Link Activity OFF No link detected GREEN FAST BLINK Network activity MODULE S RECEIVED SIGNAL STRENGTH RSSI When the Mode Switch is NOT depressed LED 1 will illuminate red e The remaining LEDs indicate RSSI Received Signal Strength nli MODULE S OPERATION MODE When the Mode Switch IS depressed LED 1 will be OFF e LEDs 2 and 3 indicate the module s communi
23. n programming occurs set the factory defaults see next topic and reprogram e The IP Fault Time and the GSM Fault Time are each fixed at 1 minute and are not programmable IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide To exit the programming mode press N in response to the Review prompt Then press Y to the Exit Prog Mode prompt Upon exiting the root file is updated to log the changes made A message is displayed telling the user that this step is being executed When complete the message DONE is displayed to indicate the file was successfully uploaded Note If critical configuration changes were made such as the mode of operation the communicator will reset to ensure that the programming features are enabled If the file is not successfully uploaded one of the following prompts will be displayed Follow the steps shown below until the upload is successful Display Description What to do Cannot Upload Communicator is not yet initialized Wait for RSSI indicator LEDs to be lit Try Again Y N Press Y Failed to Update Network problem or you answered N to Initiate the Force Server Update Root File Cannot Upload Try Again prompt Command by pressing the 0 key Setting Factory Defaults To reset the programming options to factory default values at the Exit Prog Mode prompt press Shift plus ESC Note setting the factory defaults will also erase
24. oost 1 Terminal ERTH GND Wire to a Zone on the Fire Panel Y Y IPGSM 4GC 013 VO IPGSM 4GC Example wiring for an addressable fire control panel IPGSM 4GC FIRE LITE Addressable Fire Alarm Control Panel Commercial Fire Communicator MS 9050UD To next device YEL to Dialer Capture Module Terminal Tip 2 on SLC Loop MMF 300A i i i ORG 3 to Dialer Capture Module Terminal Ring 2 Monitor Module o r Braided shield Drain RED gt to Power Boost 1 Terminal OUTPUT 1 DC BLK gt to Power Boost 1 Terminal OUTPUT 1 DC GRN gt to Power Boost 1 Terminal ERTH GND 1j ONES P ADDRESS 47K 1 2 watt S sie B A B A A B NO NC C RELAY 1 SLC Loop ALARM CONTACTS IPGSM 4GC 014 VO IPGSM 4GC Commercial Fire Communicator Installation and Setup Guide STEP 5 Program the Communicator You must use the 7720P Programming tool to program the IPGSM 4GC When using the 7720P Programming tool the values given below are for most installations Press the key to accept the displayed default value xxx or enter the new value and press the key for the next prompt Use the Space key to scroll through a list of options no display Connect the 7720P You can use the Shift A key to check the software revision 7720P PROGRAMMER Press Strt Prog Mode Y N Press Shift then Y then
25. rBoost1 e Hardware Bag e Dialer Capture Module e Battery harness fuse 100 02415 e Transformer 18VAC e Communicator e Ferrite Filter 1451 UL9 e 50 ohm cable assembly for antenna e LED Display board Compatible Fire Panels The IPGSM 4GC is compatible with all ULC Listed Fire Panels that use the Contact ID communication format as described in the SIA DC 05 Standard and have the model 659EN Line Fault Monitor installed After completing the field installation verify communications with the central station is successful by sending several events Also get confirmation that these events were received IMPORTANT For a fire panel that has more than 9 active zones or partitions the first 9 zones are reported to the central station uniquely Beyond 9 zones only the 2nd digit of the zone is reported along with a leading zero example partition 14 is reported as 04 The installer must inform the central station of this condition Operation The IPGSM 4GC replaces the fire panel s POTS communications path When an event occurs the fire panel goes off hook to dial the central station The IPGSM 4GC detects the off hook condition and provides the fire panel with a dial tone When the fire panel detects the dial tone it begins dialing the central station The IPGSM 4GC considers the three second period after dialing as the number dialing has been completed After the dialing is completed the Dialer Capture Module returns a handshake to t
26. tmore Road Woodbridge Ontario L4L 7Z4 Canada TR T Copyright 2012 Honeywell International Inc 800 12458 7 12 Rev C www honeywellpower com