Honeywell BRAUKMANN F74C User's Manual

image

Contents

1. CLEAN SCREEN F74C1023 M17656 Fig 2 F74C Pressure drop vs flow Connections Union on inlet and outlet External NPT threaded or sweat Inlet outlet assembly can be rotated to fit on vertical or horizontal piping Screen Sizes Shipped with Device 100 microns MV876 Automatic Backwash Control MV876B1018 Bayonet mounted shaft of 24 Vac motor and timer replaces ball valve manual control for automatic backwash at preprogrammed intervals 24V transformer not included For use with F74C and F76S Filters only Specifications Power 4 VA Current 170 mA Voltage 24 Vac Cycle time 20 seconds approximate Timer Variable See Table 3 Accessories for F74C AF74 1A Replacement filter assembly for F74C 3 4 in and 1 in 100 micron includes the filter insert complete O ring mesh with mesh support impeller sump O ring mounted between the filter housing and the sump KF74 1A Replacement sump assembly for the F74C includes the sump assembly complete ball valve plastic air gap adaptor sump O ring mounted between the filter housing and the sump TBD Opaque sump cover for F74C 3 4 in and 1 in U76S5015 3 4 in sweat tailpiece U76S5023 1 in sweat tailpiece U76T1014 3 4 in NPT tailpiece U76T1022 1 in NPT tailpiece 901444 Union gasket for F74 3 4 in 10 gaskets in package 901445 Union gasket for F74 1 in 10 gaskets in package ZR 10 K 34 Double ring wrench for removing filter bowl
2. F74C REVERSE RINSING FILTER MV876 AUTOMATIC BACKWASH CONTROLS Table 2 Flow Capacity of F74C in Gallons per Minute gpm Pressure Drop in psi Model Size 1 2 3 4 5 15 Cv F74C1015 3 4 9 0 12 7 15 6 18 0 20 1 34 9 9 F74C1023 1 10 1 14 3 17 5 20 2 22 6 39 1 10 1 Table 3 MV876B Timer Selections Program Value Backwash Interval 4 minutes 8 minutes 16 minutes 32 minutes 1 hour 2 hours 4 hours 8 hours 17 hours o CO Nl j a A oj N gt 0 34 hours 11 3 days 12 6 days 13 11 days 14 23 days 15 45 days 16 3 months Planning the Installation The F74C should be sized based on the required flow rate and the resulting pressure drop across the filter As a guideline for most applications the F74C should be sized fora pressure drop between 3 psi and 7 psi EXAMPLE What size F74C is required to provide a flow rate of 20 gom Reading Table 2 at 20 gpm a 3 4 in model has 5 psi drop and a 1 in model has 4 psi drop As both models meet the 3 to 7 psi range the selection should be based on size preference An increased pressure drop across the filter results when higher velocities are maintained to increase the capacity through any given size filter Severe pressure drops will be encountered as capacity approaches that of the pipe size To ensure the backwash cycle operates properly and cleani
3. Honeywell Braukmann F74C Reverse Rinsing Filter MV876 Automatic Backwash Controls MV876B1018 Bayonet fitting for F74C APPLICATION The F74C Reverse Rinsing Water Filters used at point of entry POE to remove sediment and debris from residential or commercial water systems ensure a continuous supply of filtered water The fine filter prevents the ingress of foreign bodies such as rust particles and grains of sand The flow filtering capacity and ease of cleaning make the F74C the ideal filter for the most demanding applications Both horizontal and vertical installations are possible The MV876 Automatic Backwash Control is available as an accessory This control is fitted to the drain valve and is programmed by the user to automatically perform the backwash function according to the desired interval U S Registered Trademark Copyright 2001 Honeywell All Rights Reserved INSTALLATION INSTRUCTIONS SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore units may not exactly match the listed specifications Also products are tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed F74C Models Water filters with 100 micron screens and hose connections F74C1015 3 4 in sweat and NPT threaded tailpieces F74C1023 1 in swea
4. d ordinances MV876 1 Mount the 24 Vac transformer and wire as shown in Fig 14 2 Reconnect power to the system When the system is powered the MV876 will run through one backwash cycle approximately 20 seconds 3 Set MV876 backwash interval to the desired setting See the Operation section 4 Check MV876 operation by interrupting primary power to the transformer When power is switched back on the MV876 will backwash the F74C once M17353 Fig 12 Installing batteries in the MV876 Y ih A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M16484 Fig 14 Wiring diagram for F74C with MV876 62 0165 6 F74C REVERSE RINSING FILTER MV876 AUTOMATIC BACKWASH CONTROLS F74C REPLACEMENT PARTS LIST SEE FIG 15 Table 4 Parts and Accessories for F74C Letter in Part Number Fig 15 Description Contents U76S5051 A 3 4 in sweat tailpiece Tailpiece U7685023 JA 1 in sweat tailpiece Tailpiece U76T1014 B 3 4 in NPT tailpiece Tailpiece U76T1022 B 1 in NPT tailpiece Tailpiece 901444 Cc Union gasket 3 4 in 10 gaskets in package 901445 Cc Union gasket 1 in 10 gaskets in package AF74 1A D Replacement filter assembly for Includes the filter insert complete O ring mesh with F74C 3 4 in and 1 in 100 micron mesh support impeller sump O ring mounted between the filter housing and the sump KF74 1A E Replacement sump assembly for Includes the s
5. ese instructions and on the product to make sure the product is suitable for your application Make sure the installer is a trained experienced service technician Use these instructions to check out product operation after installation A CAUTION Equipment Damage Hazard Excessive pressure or temperature can damage the device Make sure water temperature and pressure are below maximum ratings specified CAUTION Equipment Damage Hazard Excessive heat can damage internal parts Before sweat soldering separate the tailpieces and nuts from the inlet outlet adapter F74C Installation When installing an F74C use the following procedure 1 Shut off water supply by closing the water supply valve 2 Install inlet outlet adapter so that filter is vertical 3 Install the F74C in the water line with the arrow pointing in the direction of water flow IMPORTANT When using an MV876 stop here and install the MV876 Open a downstream tap Slowly open the water supply valve Once the F74C sump fills with water close the downstream tap and fully open the water supply valve Oop MV876 Installation 1 Open the backwash outlet ball valve Remove the backwash outlet handle Install the MV876 See Fig 9 and 10 When you rotate the MV876 on installation it closes the backwash outlet ball valve 4 Connect the MV876 to a 24 Vac power supply See fig 14 Open a downstream tap Slowly open the water sup
6. ke sure the connecting cable is protected from damage when the MV876 cover is removed Remove the MV876 cover See Fig 11 Insert four AA alkaline batteries See Fig 12 Replace the cover Replace and tighten the four housing screws To avoid unnecessary battery drainage connect the MV876 to power as soon as possible after inserting new batteries 7 To ensure the availability of battery power replace the batteries after a power loss If the 800 mA fuse blows replace it as follows A WARNING Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installing the batteries or fuses PaPon 1 Unscrew the four housing screws and set them aside see Fig 11 IMPORTANT make sure that the connecting cable is protected from damage while the MV876 cover is removed Remove the MV876 cover Remove and discard the old fuse see Fig 13 Insert a new 800 mA fuse Replace the cover Replace and tighten the four housing screws Reconnect the power supply Noapwn 5 62 0165 F74C REVERSE RINSING FILTER MV876 AUTOMATIC BACKWASH CONTROLS M17351 Fig 13 Replacing the MV876 fuse WIRING WARNING Fig 11 Removing the MV876 cover Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before wiring IMPORTANT All wiring must comply with applicable codes an
7. ng action is not reduced follow all recommendations in Fig 3 Refer to Fig 3a for an ideal installation All filter installations are different The size type and amount of dirt and debris and the flow rate must always be considered when choosing a screen and deciding to install multiple F74C Water Filters in parallel M17705 Fig 3 Ideal F74C installation A funnel mounted directly under the backwash port is the best installation layout Fig 4 Make sure the inlet pipe is not downsized M17707 Fig 5 Make sure the backwash outlet pipe is not downsized long or crimped Instead install a short oversized pipe on the backwash outlet Do not use a low capacity solenoid valve to automate the backwash cycle 62 0165 F74C REVERSE RINSING FILTER MV876 AUTOMATIC BACKWASH CONTROLS M17708 Fig 6 Make sure the backwash outlet is not raised above the F74C If the backwash outlet must be raised above the F74C increase the inlet pressure 5 psi for every 10 feet that it is raised M17709 Fig 7 Make sure the F74C is not used with an undersized pump An undersized pump may not provide proper pressure or flow M17704 Fig 8 Make sure the F74C is not installed in a bypass across a pump INSTALLATION When Installing this product Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 62 0165 Check ratings given in th
8. ply valve Once the F74C sump fills with water close the downstream tap and fully open the water supply valve 8 Program the desired backwash interval by pushing the program button until the desired interval number appears in the display ad Nog F74C REVERSE RINSING FILTER MV876 AUTOMATIC BACKWASH CONTROLS M16481 Fig 9 Installing the MV876 M16483 Fig 10 Final position of MV876 and F74C As the F74C operates screens become plugged Backwash the F74C when the pressure gauge measures about five psi lower than when first installed However each installation is different Residential applications can require backwash only once a week or once every few weeks For residential applications backwashing the F74C once a week regardless of need is an excellent guideline to follow to ensure F74C peak operating efficiency Fitting Batteries and Fuses The batteries not included provide power to the MV876 in the event of a power loss This is desirable especially when power loss occurs during the reverse rinsing cycle to provide this the MV876 requires four AA alkaline batteries Install these batteries in the cover of the MV876 as follows A WARNING Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installing the batteries or fuses 1 Unscrew the four housing screws and set them aside See Figure 11 IMPORTANT Ma
9. t and NPT threaded tailpieces Materials of Construction Body Engineered plastic Inlet Outlet Adapter Bronze Sump Engineered plastic Screen Stainless steel Internal Construction Acetal copolymer Seals NBR Ball Valve Brass with PTFE seals Inlet Pressure Minimum 22 psi with unrestricted backwash discharge Maximum 232 psi Medium Water Maximum Operating Temperature 86 F 30 C Pipe Size 3 4 in and 1 in Mounting Position For vertical or horizontal filter bowl always downwards Dimensions See Fig 1 and Table 1 62 0165 F74C REVERSE RINSING FILTER MV876 AUTOMATIC BACKWASH CONTROLS A 4 h H y Y 2 _ D r T Ul M18087 Fig 1 Dimension drawing of F74C Table 1 Dimensions of F74C in in mm Connection Size Dimension 3 4 1 H 12 13 16 324 12 13 16 324 h 11 3 16 285 11 3 16 285 L 6 3 8 162 7 1 4 184 l 3 9 16 90 3 15 16 100 D 4 1 8 105 4 1 8 105 r 1 1 16 27 1 1 16 27 t 2 5 8 66 2 5 8 66 T 5 5 16 150 5 5 16 150 Weight 3 4 in 6 Ib 2 7 kg 1 in 7 Ib 3 2 kg Operating Pressure Drop Versus Flow See Fig 2 Maximum recommended 3 psi to 7 psi with clean screen 62 0165 FLOW GPM 0 3 7 10 20 PRESSURE DROP PSI MAXIMUM RECOMMENDED F74C1015 wave PRESSURE DROP WITH
10. ump assembly complete ball valve F74C plastic air gap adaptor sump O ring mounted between the filter housing and the sump M18212 Fig 15 F74C Exploded View parts are keyed to F74C Replacement parts List 62 0165 Honeywell Home and Building Control Home and Building Control Honeywell Honeywell Limited Honeywell Limit e 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario MIV 4Z9 62 0165 GR 3 01 paper containing at least 10 post consumer paper fibers www honeywell com