Hitachi MK-97RD6679-00 User's Manual

image

Contents

1. Hitachi Universal Storage Platform VM Installation Planning Guide FASTFIND LINKS Document Organization Product Version Getting Hel Contents Hitachi Data Systems MK 97RD6679 00 Copyright 2007 Hitachi Data Systems Corporation ALL RIGHTS RESERVED Notice No part of this publication may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying and recording or stored in a database or retrieval system for any purpose without the express written permission of Hitachi Data Systems Corporation hereinafter referred to as Hitachi Data Systems Hitachi Data Systems reserves the right to make changes to this document at any time without notice and assumes no responsibility for its use Hitachi Data Systems products and services can only be ordered under the terms and conditions of Hitachi Data Systems applicable agreements All of the features described in this document may not be currently available Refer to the most recent product announcement or contact your local Hitachi Data Systems sales office for information on feature and product availability This document contains the most current information available at the time of publication When new and or revised information becomes available this entire document will be updated and distributed to all registered users Hitachi Data Systems is a registered trademark and
2. Icon Meaning Description A Note Calls attention to important and or additional information Tip Provides helpful information guidelines or suggestions for performing tasks more effectively Caution Warns the user of adverse conditions and or consequences e g disruptive operations WARNI NG Warns the user of severe conditions and or consequences e g destructive operations DANGER Provides information about how to avoid physical injury to yourself and others ELECTRIC SHOCK Warns the user of electric shock hazard Failure to take appropriate HAZARD precautions e g do not touch could result in serious injury ESD Sensitive Warns the user that the hardware is sensitive to electrostatic discharge ESD Failure to take appropriate precautions e g grounded wrist strap could result in damage to the hardware Convention for Storage Capacity Values viii Physical storage capacity values e g disk drive capacity are calculated based on the following values 1 KB 1 000 bytes 1 000 bytes 1 000 bytes 1 TB 1 000 bytes 1 PB 1 000 bytes 1 MB 1 GB Logical storage capacity values e g logical device capacity are calculated based on the following values 1 KB 1 024 bytes 1 024 bytes 1 024 bytes 1 TB 1 024 bytes 1 PB 1 024 bytes 1 block 512 bytes 1 MB 1 GB Preface Hitachi Universal Storage Platform VM Installation Planning Guide Getting Help If you need to
3. Table 2 9 lists the vibration and shock tolerance data for the Universal Storage Platform VM The USP VM can be subjected to vibration and shock up to these limits and still perform normally The user should consider these requirements if installing the storage system near large generators located on the floor above or below the storage system Generators or any other source of vibration if not insulated or shock mounted can cause excessive vibration that may affect the sto Table 2 9 Parameter Operating Vibration 5 10 Hz 0 25 m 10 300 Hz 0 49 rage system Vibration and Shock Tolerances Condition Non Operating 5 10 Hz 2 5 mm 10 70 Hz 4 9m s 70 99 Hz 0 05 mm 99 300 Hz 9 8m s m m s Sine Vibration Random Vibration Shipping or Storage 2 4 9 m s 5 min At the resonant frequency with the highest displacement found between 3 and 100 Hz 3 0 147 m s 30 min 5 100 Hz Shock Notes 1 The vibration specifications 2 3 4 an Inclined Impact Tester Shipping Cases and Crates 78 4 m s 15 ms apply to all three axes Installation Requirements Horizontal Incline Impact 4 ft s 1 22 m s Vertical Rotational Edge 0 5 ft 0 15 m See ASTM D999 91 Standard Methods for Vibration Testing of Shipping Containers See ASTM D4728 01 Test Method for Random Vibration Testing of Shipping Containers See ASTM D5277 92 Standard Test Methods fo
4. 1 Hitachi Universal Storage Platform VM Installation Planning Guide Responsibilities The responsibilities for installation planning are shared by the customer and the Hitachi Data Systems account team The required installation planning tasks must be scheduled and completed to ensure successful and efficient installation of the Universal Storage Platform VM Customer Responsibilities You are responsible for e Performing the installation planning tasks described in this document e Verifying that all installation requirements have been met by completing the Installation Planning Checklist in this document e Providing the customer supplied hardware that is required for storage system installation e g electrical connectors and receptacles e Observing all applicable safety requirements at all times Hitachi Data Systems Responsibilities 1 2 Your Hitachi Data Systems account team will assist you throughout the installation planning process The Hitachi Data Systems account team is responsible for e Assisting you as needed during the installation planning process for your specific site and operational configuration e Coordinating Hitachi Data Systems resources to ensure smooth installation and configuration of the Universal Storage Platform VM Planning for Installation Hitachi Universal Storage Platform VM Installation Planning Guide Installation Planning Tasks The customer is responsible for performing the f
5. 4 Facilities Requirements iii oi rr 2 5 Physical Specifications and Requirements r 2 6 Dimensions and Weight ici 2 7 Service Clearance Floor Cutout and Floor Load Rating 2 10 Contents iii Hitachi Universal Storage Platform VM Installation Planning Guide Power Specifications and ReQUIFTEMENES i 2 13 Power Specifications and Power Supplies n 2 13 Breaker C nflguratIionS u u u aerea 2 15 Power Connection lia 2 16 Input Voltage and Input Frequency n 2 18 Circuit Breakers and PlugS daensaceuds diancactninciancindudeds 2 18 Environmental Specifications and RequirementSs esse eeeeeeeeeeeeeees 2 19 Temperature Humidity and Altitude rr 2 19 Heat Output Power Consumption and Air FIOW a 2 20 LOUUNESS lara velo 2 21 Vi r ti n and Shocker iaia 2 21 Operational REQUIFEMEeNIs niate ieri 2 22 Units and lama A 1 Acronyms and Abbreviations iv Contents Hitachi Universal Storage Platform VM Installation Planning Guide Preface This document provides installation and configuration planning information for the Hitachi Universal Storage Platform VM USP VM storage system Please read this document carefully to understand the installation requirements for the Universal Storage Platform VM and maintain a copy for reference This preface
6. Clearance a b depends on the floor load rating and clearance c See Table 2 4 for floor load rating and clearance requirements Allow clearance of 100 mm on both sides of the storage system when the stabilizer plate s are to be attached after the storage system is installed The stabilizer plates have dimensions H x W x D of 74 mm x 500 mm x 220 mm or 2 9 inches x 19 6 inches x 8 6 inches When storage systems of the same type are to be installed adjacent to each other the minimum clearance between the storage systems is 100 mm 2 When installing a second rack be sure to leave a 10 mm space 2 12 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Power Specifications and Requirements This section describes the power specifications and requirements for the Universal Storage Platform VM storage system e Power Specifications and Power Supplies e Breaker Configurations e Power Connection e Input Voltage and Input Frequency e Circuit Breakers and Plugs Power Specifications and Power Supplies Table 2 5 lists the power specifications for the Universal Storage Platform VM including inrush current leakage current input current and steady current Figure 2 6 shows the locations of the power supplies Table 2 5 Current Specifications Inrush Current Notes 1 This is the maximum current when there is only one AC input power line n
7. If you plan to attach external storage to the Universal Storage Platform VM be sure to include the appropriate power and space requirements in your planning Table 2 10 FED Cable Length Requirements Maximum Cable Length Data Transfer Rate ESCON 3 km FICON Short Wave 50 125 um multimode 500 m 100 MB s 300 m 200 MB s 150 m 400 MB s 62 5 125 um multimode 300 m 100 MB s 150 m 200 MB s 75 m 400 MB s FICON Long Wave 10 km Fibre Channel Short Wave 50 125 um multimode 500 m 100 MB s 300 m 200 MB s 150 m 400 MB s 62 5 125 um multimode 300 m 100 MB s 150 m 200 MB s 75 m 400 MB s Fibre Channel Long Wave 10 km Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Units and Unit Conversions Table A 1 provides conversions for metric and standard U S units of measure associated with the Hitachi Universal Storage Platform VM storage system For information on physical and logical storage capacity values on the USP VM storage system see Convention for Storage Capacity Values Table A 1 Conversions for Metric and Standard U S Units of Measure British thermal units BTU 0 251996 Kilocalories kcal British thermal units BTU 0 000293018 Kilowatts KW Inches in 2 54000508 Centimeters cm Feet ft 0 3048006096 Meters m Square feet ft 0 09290341 Sq
8. Initial release supersedes and replaces MK 97RD6079 Changes in this Revision e Added information on the 750 GB hard disk drive Table 2 2 Table 2 8 Document Organization The following table provides an overview of the contents and organization of this document Click the chapter title in the left column to go to that chapter The first page of each chapter provides links to the sections in that chapter Chapter Description Planning for Installation Describes the responsibilities and tasks involved in installation planning for the Universal Storage Platform VM Provides the Installation Planning Checklist for the Universal Storage Platform VM Installation Requirements Provides the installation requirements for the Universal Storage Platform VM Units and Unit Conversions Provides conversions for standard U S and metric units of measure associated with the Universal Storage Platform VM Acronyms and Abbreviations Defines the acronyms and abbreviations used in this document Referenced Documents e Hitachi Universal Storage Platform V VM User and Reference Guide MK 96RD635 Preface vii Hitachi Universal Storage Platform VM Installation Planning Guide Document Conventions The term Universal Storage Platform VM refers to all models of the Universal Storage Platform VM storage system unless otherwise noted This document uses the following icons to draw attention to information
9. inches 2 134 meters overall height including palette Width 42 inches 1066 8 mm Depth 55 inches 1397 mm See Service Clearance Floor Cutout and Floor Load Rating for the dimensions of the USP VM product uncrated and unpacked See Dimensions and Weight for the dimensions of the USP VM components Weight The floors elevators stairs and ramps must be able to support the weight of the delivered equipment as it is moved to the installation location Spreader plates may be required to distribute the load and or protect the floor as the equipment is moved to the installation location The weight of the delivered equipment depends on the storage system configuration The weight for a maximally configured storage system could reach 1600 or 1700 pounds 726 to 771 kilograms See Dimensions and Weight for the weight specifications for the Universal Storage Platform VM components Installation Requirements 2 3 Hitachi Universal Storage Platform VM Installation Planning Guide Storage Requirements 2 4 If the delivered equipment needs to be stored after delivery and prior to installation the storage location must meet the environmental requirements for the Universal Storage Platform VM see Table 2 1 Table 2 1 Environmental Specifications for Storage Shipping amp Storage Parameter Low High Temperature F C 5 25 140 60 Relative Humidity 5 95 Max Wet Bulb F C 84 29 Temp
10. includes the following information rn nr n nn Safety and Environmental Notices Intended Audience Product Version Document Revision Level Changes in this Revision Document Organization Referenced Documents Document Conventions Convention for Storage Capacity Values Getting Help Comments Notice The use of the Hitachi Universal Storage Platform VM and all other Hitachi Data Systems products is governed by the terms of your agreement s with Hitachi Data Systems Preface v Hitachi Universal Storage Platform VM Installation Planning Guide Safety and Environmental Notices Federal Communications Commission FCC Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment ina residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense EINE LEICHT ZUGANGLICHE TRENN VORRICHTUNG MIT EINER KONTAKT OFFNUNGSWEITE VON MINDESTENS 3mm IST IN DER UNMITTELBAR
11. service mark of Hitachi Ltd and the Hitachi Data Systems design mark is a trademark and service mark of Hitachi Ltd Dynamic Provisioning Hi Track Shadowl mage TrueCopy and Universal Star Network are registered trademarks or trademarks of Hitachi Data Systems All other brand or product names are or may be trademarks or service marks of and are used to identify products or services of their respective owners Hitachi Universal Storage Platform VM Installation Planning Guide Contents iL ARRE RO V Safety and Environmental Notices rr vi ntended Audience spreca vi ROUCA ue vii Document REVISION LEVEL vii Changes in this REVISION ail vii DECUMEntOgahiza bizze vii Referenced DOEUMEnNb Labirinti vii Document Conventi NS ararac e a a e a ae viii Convention for Storage Capacity Values rr vili Getting Helga IX Connessi IX Panning Gee ln 1 1 Responsibiliti eS sian nani 1 2 Customer Responsibilities nr 1 2 Hitachi Data Systems Responsibilities 1 2 Installation Planning Tasks rn rn Sysivaadebicvbes 1 3 Installation Planning Checklist teh cntibinidiawiieldutevadenedetureeeieetts 1 4 Installation Requirements RR 2 1 Safety ReQUIPermehntS alari ia 2 2 Delivery Reguireme tS hua alii 2 3 Storage Requirements rn 2
12. 13 445 800 84 DKC F6151 LGAB 11 DKC F6151 PLUC 2 0 DKC F6151 PHUC 4 0 DKC F6151 PLEC 15 a DKC F6151 PHEC 2 5 Di DKC F6151 UCO 3 2 DKC F6151 UC1 2 1 DKC F6151 EXCO 6 2 DKC F6151 SX 1 2 DKC F6151 S4GQ 0 08 DKC F6151 DKA 2 6 _ DKC F6151 CX 2 2 DKC F6151 C4G 0 08 _ dai DKC F6151 C8G 0 08 Sa DKC F6151 8S 2 7 DKC F6151 8MFS 3 0 DKC F6151 8MFL 3 0 DKC F6151 8FS 2 8 A DKC F6151 16FS 3 0 DKC F6151 1FL 0 02 A DKC F6151 1FS 0 02 DKC F6151 SVP 4 1 ca DKC F6151 MDM 0 07 DKC F6151 72KS 0 9 DKC F6151 146KS 0 9 DKC F6051 300KS 0 9 DKC F6051 0R7HS 0 9 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Service Clearance Floor Cutout and Floor Load Rating This section specifies the service clearance requirements a b for the Universal Storage Platform VM storage system based on the floor load rating and the clearance c and the required floor cutouts for cabling e Figure 2 4 shows the service clearance and floor cutout requirements for the single rack configuration Table 2 3 shows the floor load rating and clearance requirements for this configuration e Figure 2 5 shows the service clearance and floor cutout requirements for the twin rack configuration Table 2 4 shows the floor load rat
13. EN NAHE DER VERBRAUCHERANLAGE ANZUORDNEN 4 POLIGE ABSCHALTUNG Maschinenlarminformationsverordnung 3 GSGV 18 01 1991 Der h chste Schalldruckpegel betr gt 70 db A oder weniger gem ISO 7779 CLASS 1 LASER PRODUCT CLASS 1 LASER PRODUCT LASER KLASSE 1 WARNING This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures WARNUNG Dies ist ein Produkt der Klasse A In nichtgewerblichen Umgebungen k nnen von dem Ger t Funkst6rungen ausgehen zu deren Beseitigung vom Benutzer geeignete Ma nahmen zu ergreifen sind Intended Audience vi This document is intended for system administrators Hitachi Data Systems representatives and authorized service providers who are involved in installation planning for the Hitachi Universal Storage Platform VM This document assumes the following e The user has a background in hardware installation for computer systems e The user is familiar with the location where the Universal Storage Platform VM will be installed including knowledge of physical characteristics power systems and specifications environmental specifications Preface Hitachi Universal Storage Platform VM Installation Planning Guide Product Version This document revision applies to Universal Storage Platform VM microcode 60 02 0x and higher Document Revision Level MK 97RD6679 00 November 2007
14. Single Rack 1 Clearance a b depends on the floor load rating and clearance c See Table 2 3 for floor load rating and clearance requirements Leave clearance of 100 mm on both sides of the storage system when the stabilizer plate s are to be attached after the storage system is installed When storage systems of the same type are to be installed adjacent to each other the minimum clearance between the storage systems is 100 mm 2 Dimensions in parentheses show allowable range of the floor cutout dimensions Position the floor cutout in the center of the storage system The position may be off center if the cutout allows smooth entrance of an external cable Check the relation between the positions of the cutout and the opening on the bottom plate of the storage rack and verify that it is within the allowable range 3 This dimension varies depending on the floor cutout dimensions Installation Requirements 2 11 Hitachi Universal Storage Platform VM Installation Planning Guide Unit mm 110 en a 7 KA j 575 655 835 1050 DKC515 1050 PAN Tool IS 190163 200 or more o n 1100 601 lt Front c 1 DKC615 DKC615 DK Floor cutout area for cables Screw jack Caster I i Service clearance G Grid panel over 450mm x 450mm Figure 2 5 Service Clearance and Floor Cutouts Two Racks Notes 1
15. achi TagmaStore Network Storage Controller so the air flow requirements are decreased Table 2 8 Component Specifications Heat Output Power Consumption and Air Flow Heat Output kW Power Consumption kVA Air Flow m min DKC6151 5 0 0291 0 30 4 3 DKC F6151 B2 0 233 0 24 5 0 DKC F6151 SBX 0 012 0 013 1 3 DKC F6151 LGAB 0 015 DKC F6151 PLUC sa DKC F6151 PHUC DKC F6151 PLEC DKC F6151 PHEC DKC F6151 UCO DKC F6151 UC1 i DKC F6151 EXCO DKC F6151 SX 0 005 0 005 DKC F6151 5S4GQ 0 013 0 013 sa DKC F6151 DKA 0 097 0 100 DKC F6151 CX 0 005 0 005 DKC F6151 C4G 0 015 0 015 DKC F6151 C8G 0 019 0 020 DKC F6151 8S 0 146 0 150 DKC F6151 8MFS 0 146 0 150 DKC F6151 8MFL 0 146 0 150 DKC F6151 8FS 0 130 0 135 DKC F6151 16FS 0 146 0 150 DKC F6151 1FL DKC F6151 1FS i DKC F6151 SVP 0 073 0 075 DKC F6151 MDM 0 006 0 006 DKC F6151 72KS 0 020 0 021 DKC F6151 146KS 0 020 0 021 DKC F6151 300KS 0 020 0 021 DKC F6051 0R7HS 0 018 0 019 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Loudness The acoustic emission values loudness in dB A for the Universal Storage Platform VM storage system are Front rear 65 Both sides 65 Vibration and Shock dB A dB A
16. call the Hitachi Data Systems Support Center make sure to provide as much information about the problem as possible including e The circumstances surrounding the error or failure e The exact content of any error message s displayed on the host system s e The service information messages SIMs including reference codes and severity levels displayed by Storage Navigator The Hitachi Data Systems customer support staff is available 24 hours a day seven days a week If you need technical support please call e United States 800 446 0744 e Outside the United States 858 547 4526 Comments Please send us your comments on this document Make sure to include the document title number and revision Please refer to specific section s and paragraph s whenever possible e E mail doc comments hds com e Fax 858 695 1186 e Mail Technical Writing M S 35 10 Hitachi Data Systems 10277 Scripps Ranch Blvd San Diego CA 92131 Thank you All comments become the property of Hitachi Data Systems Corporation Preface ix Hitachi Universal Storage Platform VM Installation Planning Guide Preface Hitachi Universal Storage Platform VM Installation Planning Guide Planning for I nstallation This chapter describes the requirements and procedures for planning to install the Universal Storage Platform VM O Responsibilities O Installation Planning Tasks O Installation Planning Checklist Planning for Installation 1
17. connections when the AC input lines are connected directly to the power facility e Power connection through UPS Figure 2 10 shows the power connections when half of the AC input lines are connected to an uninterruptible power supply UPS and the other half of the AC input lines are connected directly to the power facility A Caution When installing the USP VM be sure to connect the AC cables between the PDUs and PDPs correctly If these cables are connected incorrectly a system failure will occur when one of the AC inputs is interrupted Figure 2 9 illustrates the correct connections drawing on the left and the incorrect connections drawing on the right Correct Connections Incorrect Connections Primary Rack Primary Rack PDU PDU 19 204 da PDU 19 20A PDU 19 204 Connect to same PDP AC Input Line Incorrect Connection PDP Power Distribution Panel 2 If connected incorrectly the two PDUs cannot supply power to the entire rack which causes a system failure 1 When connected correctly two of the four PDUs can supply power to the entire rack Figure 2 9 Direct Power Connection 2 16 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Branch Distribution Box PDP Power Distribution Panel Primary Rack Secondary Rack N To UPS ToPDP For the AC input power c
18. de Power Cable Input 2 Plugs for 30A Breakers USA NEMA L6 30P Europe IEC 309 Breaker Configurations For both racks AC power is supplied to each power distribution unit PDU from the breaker Figure 2 7 and Figure 2 8 show the breaker configurations for the primary and secondary racks respectively PDU PRC gt PDU 19 204 19 20A 19 204 19 204 Regardless of the number of disk chassis the number of 20A breakers is the same 30A breaker Configuration with one disk chassis DKC F6151 B2 installed Configuration with two disk chassis DKC F6151 B2 installed Figure 2 7 Breaker Configurations for the Primary Rack PDU PDU PDU 19 204 PDU 19 204 19 204 19 204 PDU PDU PDU PDU 19 204 19 204 19 204 19 204 When adding a disk chassis add two 20A breakers Configuration with one disk chassis DKC F6151 B2 installed Configuration with two disk chassis DKC F6151 B2 installed Figure 2 8 Breaker Configurations for the Secondary Rack Installation Requirements 2 15 Hitachi Universal Storage Platform VM Installation Planning Guide Power Connection The AC power input for the Universal Storage Platform VM has a duplex PDU structure This duplex structure enables the entire rack to remain powered on in the event that power is removed from one of the two power distribution panels PDPs e Direct connection to power Figure 2 9 shows the power
19. erature Deviation F hour C hour 36 20 For storage the equipment should be packed with factory packing Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Facilities Requirements The customer site must meet the following facilities requirements General The data center must be fully operational e g power air conditioning cabling fire protection system Floor The data center must have a tiled raised floor ESD The data center must provide adequate protection from electrostatic discharge ESD Electrical interference The data center must provide adequate protection from electrical radio frequency interference Dust pollution and particulate contamination The data center must provide adequate protection from dust pollution and particulate contamination Acoustics The data center must provide adequate acoustic insulation for operation of the Universal Storage Platform VM Customer supplied hardware The customer supplied hardware e g connectors receptacles must be available and ready for installation of the Universal Storage Platform VM Installation Requirements 2 5 Hitachi Universal Storage Platform VM Installation Planning Guide Physical Specifications and Requirements Figure 2 1 shows a physical overview of the Universal Storage Platform VM The physical specifications and requirements for the USP VM include e Dimensions and Weight e Ser
20. es is checked for all entries will ensure smooth and efficient installation of the Universal Storage Platform VM Definition of terms Data center The room at the customer site in which the Universal Storage Platform VM will be installed Equipment The hardware delivered to the customer site that includes the Universal Storage Platform VM storage system components and rack s Location The specific location in the data center area or footprint on the floor where the Universal Storage Platform VM will be installed Customer Information pater Company Address Contact Phone Mobile E mail Contact Phone Mobile E mail Hitachi Data Systems I nformation Contact Phone Mobile E mail Contact Phone Mobile E mail Notes 1 4 Planning for Installation Hitachi Universal Storage Platform VM Installation Planning Guide Installation Planning Checklist Safety Yes No Is the data center equipped to protect equipment from fire Is the data center free of hazards e g cables that obstruct access Delivery Is the receiving area adequate for equipment delivery and unloading overall height 84 in 2 134 m Does the equipment fit through doors halls elevators and stairs Do the floors elevators stairs and ramps support the weight of the equipment Storage If the equipment will be stored afte
21. ing and clearance requirements for this configuration Notes A e For safe and efficient maintenance operations clearance c should be made as large as possible e Actual clearances for installation should be determined after consulting with the site facilities manager as the clearances could vary depending on the building conditions Table 2 3 Floor Load Rating and Clearances Single Rack Required Clearance a b m Floor Load Rating Clearance c m kg m Ib ft c 0 c 0 2 c 0 4 C 0 6 C 1 0 500 102 4 0 2 0 2 0 2 0 2 0 2 450 92 2 0 2 0 2 0 2 0 2 0 2 400 81 9 0 2 0 2 0 2 0 2 0 2 350 71 7 0 3 0 2 0 2 0 2 0 2 300 61 4 0 6 0 4 0 3 0 2 0 2 Table 2 4 Floor Load Rating and Clearances Two Racks Required Clearance a b m Floor Load Rating Clearance c m kg m lb ft c 0 C 0 2 C 0 4 C 0 6 C 10 500 102 4 0 2 0 2 0 2 0 2 0 2 450 92 2 0 2 0 2 0 2 0 2 0 2 400 81 9 0 2 0 2 0 2 0 2 0 2 350 71 7 0 4 0 3 0 2 0 2 0 2 300 61 4 0 8 0 6 0 5 0 4 0 2 2 10 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Figure 2 4 Notes DKC615 200 or more DKC615 1050 00 601 Front Floor cutout area for cables Screw jack Caster Service clearance Grid panel over 450mm x 450mm Service Clearance and Floor Cutouts
22. it degrees Celsius cache channel adapter another name for front end director decibel A weighted disk adapter another name for back end director disk controller disk unit electrostatic discharge Federal Communications Commission front end director acceleration of gravity 9 8 m s unit used for vibration and shock gigabyte see Convention for Storage Capacity Values Hitachi Data Systems Hertz International Electrotechnical Commission inch es kilobyte See Convention for Storage Capacity Values kilocalorie kilogram kilometer kilovolt ampere kilowatt local area network pound logical device Acronyms and Abbreviations Acronyms 1 Hitachi Universal Storage Platform VM Installation Planning Guide LW mA max MB ms NEMA PB PDP PDU PS sec SIM SVP SW TB UPS USP VM VA VAC Acronyms 2 long wavelength meter milliampere maximum megabyte see Convention for Storage Capacity Values millimeter millisecond National Electrical Manufacturers Association petabyte see Convention for Storage Capacity Values power distribution panel power distribution unit power supply second service information message service processor switch short wavelength terabyte see Convention for Storage Capacity Values uninterruptible power supply Hitachi Universal Storage Platform VM volt ampere volts AC watt Acronyms and Abbreviations Hitachi Unive
23. llation Planning Guide Safety Requirements 2 2 The safety requirements for Universal Storage Platform VM installation are Safety regulations The data center must comply with all applicable safety regulations standards and requirements Fire protection The data center must have an operational fire protection system Hazards The data center must be free of hazards e g cables on the floor that obstruct access Observe the following general safety requirements Cabling Do not obstruct walkways when routing cables Do not place heavy materials on cables Do not place cables near any possible source of heat Warning labels Obey all warning labels When warning labels become dirty or start peeling off replace them Authorized personnel Allow only qualified and authorized personnel e g certified electrician to perform tasks that may be hazardous to persons and or equipment Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Delivery Requirements The customer site must accommodate the delivery and movement of the equipment to the installation location in the data center The delivery requirements for Universal Storage Platform VM installation are Dimensions The loading bay hallways doors elevators and stairs must be large enough to allow the delivered equipment to be moved to the installation location The shipping crate dimensions are Height 84
24. ollowing tasks with assistance as needed from the Hitachi Data Systems account team to prepare for installation of the Universal Storage Platform VM storage system 1 Read this document carefully to understand the installation requirements for the Universal Storage Platform VM You will use the information in this document to determine the specific requirements for your installation Review the User and Reference Guide MK 96RD635 to familiarize yourself with the components features and functions of the Universal Storage Platform VM storage system Complete the Checklist in this document before equipment delivery to verify that all installation requirements are met If any requirements are not met make the changes required to meet the requirements Be sure to allow enough time to complete the required changes so that the site is ready when the equipment arrives Provide the customer supplied hardware that is required for installation and configuration e g connectors receptacles Work with your Hitachi Data Systems account team during the installation planning process for the Universal Storage Platform VM Planning for Installation 1 3 Hitachi Universal Storage Platform VM Installation Planning Guide Installation Planning Checklist Complete the checklist below online or hardcopy to verify that all installation requirements for the Universal Storage Platform VM have been met Successful completion of this checklist Y
25. on redundant configuration Power Supply Input 1st 2nd 1st 0 p Leakage Input Steady Location Power 0 p 0 p Time 25 Current Current Current DKCPS11 12 1 phase 10 5 A 7 0A 0 2 ms 0 29 mA 5 6A 2 8A DKCPS21 22 1 phase 10 5 A 7 0A 0 2 ms 0 29 mA 5 6 A 2 8A DKUPSx 01 11 21 31 1 phase 12 5A 5 0 A 0 2 ms 0 2 MA 2 4A 12A DKUPSx 00 10 20 30 1 phase 12 5A 5 0A 0 2 ms 0 2 mA 2 4A 12A 2 This is the maximum current when there are two AC input power lines redundant configuration Hitachi Universal Storage Platform VM Installation Planning Guide Installation Requirements 2 13 Primary Rack Secondary Rack DKU PS PST CLI PS12 CL2 PS21 PS22 Power Cable AC Input 1 Plugs for 30A Breakers USA NEMA L6 30P International IEC 309 Figure 2 6 2 14 Power Cable AC Input 2 DKC PS DKU R3 Psso x15 E3 Pssi Ps20 F x15 gt Ps2t PS10 x15 Pst Power Cable AC Input 1 Plugs for 30A Breakers USA NEMA L6 30P International IEC 309 Plugs for 30A Breakers USA NEMA L6 30P International IEC 309 Power Supply Locations Installation Requirements AC Hitachi Universal Storage Platform VM Installation Planning Gui
26. onnect one of the duplexes PDUs to the UPS and the other one to the PDP Figure 2 10 Power Connection through UPS Installation Requirements 2 17 Hitachi Universal Storage Platform VM Installation Planning Guide Input Voltage and nput Frequency Table 2 6 lists the input voltage and input frequency requirements for the Universal Storage Platform VM Table 2 6 Input Voltage and nput Frequency Requirements 60Hz 2Hz 200V 208V or 230V 1 Phase 6 or 8 2 Wire Ground 50Hz 3Hz 200V 220V 230V or 240V 1 Phase 6 or 8 2 Wire Ground Circuit Breakers and Plugs The PDU plugs are appropriate for the power sources at the installation sites e For installations within the U S the plugs are NEMA L6 30P which are rated as 30A and 250V and have two 16A circuit breakers with 20A trip values e For installations outside the U S the plugs are IEC 309 which are rated as 32A and 250V and have two 16A circuit breakers with 20A trip values 2 18 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Environmental Specifications and Requirements The environmental specifications and requirements for the Universal Storage Platform VM include e Temperature Humidity and Altitude e Heat Output Power Consumption and Air Flow e Loudness e Vibration and Shock Temperature Humidity and Altitude Table 2 1 specifies the temperature humidity and altitude requi
27. r Performing Programmed Horizontal Impacts Using See ASTM D6055 96 Standard Test Methods for Mechanical Handling of Unitized Loads and Large 2 21 Hitachi Universal Storage Platform VM Installation Planning Guide Operational Requirements 2 22 The operational requirements for the Universal Storage Platform VM include LAN connection or RJ 11 analog phone line for Hi Track The Hi Track maintenance support tool monitors the operation of the Universal Storage Platform VM collects hardware status and error data and transmits this data via LAN or modem to the Hitachi Data Systems Support Center In the event of a component failure Hi Track reports the failure to the Support Center with no action required on the part of the user Hi Track enables most problems to be identified and fixed prior to actual failure and the advanced redundancy features enable the storage system to remain operational even if one or more components fail LAN for Storage Navigator Hitachi Storage Navigator communicates directly with the Universal Storage Platform VM via LAN to obtain system configuration and status information and send user requested commands to the storage system Storage Navigator serves as the integrated interface for all Resource Manager components Cable length for front end directors Table 2 10 lists the cable length requirements for the front end directors FEDs in the Universal Storage Platform VM External storage
28. r delivery and prior to installation does the storage location meet the environmental requirements for the USP VM Facilities Is the data center fully operational e g power air conditioning cabling fire protection system Does the data center have a tiled raised floor Does the data center provide adequate protection from ESD Does the data center provide adequate protection from electrical radio frequency interference Does the data center provide adequate protection from dust pollution and particulate contamination Does the data center provide adequate acoustic insulation for operation of the USP VM Is the customer supplied hardware e g connectors receptacles cables ready for the installation Physical Does the location meet the requirements for service clearance and cable routing e g floor cutouts Does the location meet the requirements for floor load rating Power Does the data center meet the AC input power requirements Does the data center meet the circuit breaker and plug requirements Does the data center meet the requirements for connection to UPS Environmental Does the data center meet the requirements for temperature Does the data center meet the requirements for humidity Does the data center meet the requirements for altitude Does the data center meet the requirements for air flow Does the data center meet the
29. rements for the Universal Storage Platform VM The recommended operational room temperature is 21 24 C 70 75 F Table 2 7 Environmental Specifications Operating 1 Non Operating Shipping amp Storage Parameter Low High Low High Low High Temperature F C 60 16 90 32 14 10 109 43 5 25 140 60 Relative Humidity 20 80 8 90 5 95 Max Wet Bulb F C 79 26 81 27 84 29 Temperature Deviation 18 10 18 10 36 20 F hour C hour Altitude Notes 60 m to 3 000 m 1 The requirements for operating condition should be satisfied before the storage system is powered on Maximum temperature of 90 F 32 C should be strictly satisfied at air inlet portion 2 Non operating condition includes both packing and unpacking conditions unless otherwise specified 3 For shipping storage the product should be packed with factory packing 4 No condensation in or around the drive should be observed under any conditions Installation Requirements 2 19 Hitachi Universal Storage Platform VM Installation Planning Guide Heat Output Power Consumption and Air Flow 2 20 Table 2 8 lists the power consumption and heat output specifications and the air flow requirements for the Universal Storage Platform VM These data generally apply to both 60 Hz and 50 Hz storage systems The Universal Storage Platform VM requires less power and puts out less heat than the Hit
30. requirements for vibration and shock Operational Does the data center provide a LAN or phone line for Hi Track Does the data center provide a LAN for Storage Navigator Does the location meet the cable length requirements for the front end directors Does the location meet the requirements for attaching external storage to the USP VM Planning for Installation Hitachi Universal Storage Platform VM Installation Planning Guide 1 5 Planning for Installation Hitachi Universal Storage Platform VM Installation Planning Guide Installation Requirements This chapter provides the installation requirements for the Universal Storage Platform VM storage system O Safety Requirements Delivery Requirements Storage Requirements Facilities Requirements Physical Specifications and Requirements Power Specifications and Requirements Environmental Specifications and Requirements Operational Requirements OOodOdagageo g Note The general information in this chapter is provided to assist in installation planning and may not be complete The installation and maintenance documents used by Hitachi Data Systems personnel e g Maintenance Manual contain complete specifications The exact electrical power interfaces and requirements for each site must be determined and verified to meet the applicable local regulations Installation Requirements 2 1 Hitachi Universal Storage Platform VM Insta
31. rsal Storage Platform VM Installation Planning Guide Hitachi Universal Storage Platform VM Installation Planning Guide Hitachi Data Systems Corporate Headquarters 750 Central Expressway Santa Clara California 95050 2627 U S A Phone 1 408 970 1000 www hds com info hds com Asia Pacific and Americas 750 Central Expressway Santa Clara California 95050 2627 U S A Phone 1 408 970 1000 info hds com Europe Headquarters Sefton Park Stoke Poges Buckinghamshire SL2 4HD United Kingdom Phone 44 0 1753 618000 info eu hds com Hitachi Data Systems MK 97RD6679 00
32. uare meters m Cubic feet per minute ft3 min 0 028317016 Cubic meters per minute m min Pound Ib 0 4535924277 Kilogram kg Kilocalories kcal 3 96832 British thermal units BTU Kilocalories kcal 1 16279 x 103 Kilowatts kW Kilowatts kW 3412 08 British thermal units BTU Kilowatts kW 859 828 Kilocalories kcal Millimeters mm 0 03937 Inches in Centimeters cm 0 3937 Inches in Meters m 39 369996 Inches in Meters m 3 280833 Feet ft Square meters m 10 76387 Square feet ft Cubic meters per minute m min 35 314445 Cubic feet per minute ft min Kilograms kg 2 2046 Pounds Ib Ton refrigerated 12 000 BTUs per hour BTU hr Degrees Fahrenheit F First subtract 32 then multiply Degrees Celsius C C F 32 x 0 555556 Degrees Celsius C First multiply then add 32 Degrees Fahrenheit F F C x 1 8 32 Degrees Fahrenheit per hour F hour 0 555555 Degrees Celsius per hour C hour Degrees Celsius per hour C hour 1 8 Degrees Fahrenheit per hour F hour Units and Unit Conversions A 1 Hitachi Universal Storage Platform VM Installation Planning Guide A 2 Units and Unit Conversions Hitachi Universal Storage Platform VM Installation Planning Guide ASTM BED BTU C ca CHA dB A DKA DKC DKU ESD FCC FED Acronyms and Abbreviations ampere American Society for Testing and Materials back end director basic power supply British thermal un
33. vice Clearance Floor Cutout and Floor Load Ratin Rack SZ Rack Do Disk Chassis DKU R1 Disk Chassis DKU RO Disk Chassis gt DKU R3 Additional SVP Battery Disk Chassis Chassis I DKU R2 Operator Panel Disk Controller DKC Figure 2 1 Physical Overview of the Universal Storage Platform VM 2 6 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Dimensions and Weight Figure 2 2 shows the dimensions of the single rack configuration Figure 2 3 shows the dimensions of the twin rack configuration Table 2 2 lists the dimension and weight specifications for the Universal Storage Platform VM components TOP VIEW 1046 mm 601 mm REAR VIEW FRONT VIEW 2001 mm Figure 2 2 Physical Dimensions Single Rack Configuration Installation Requirements 2 7 Hitachi Universal Storage Platform VM Installation Planning Guide TOP VIEW 1046 mm 0 mms lt 601 mm gt lt TBD FRONT VIEW i Figure 2 3 Physical Dimensions Twin Rack Configuration Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide Table 2 2 Component Specifications Weight and Dimension Dimension mm Model Number Weight kg Width Depth Height DKC6151 5 70 445 800 438 DKC F6151 B2 80 5 445 647 522 DKC F6151 SBX

Download Pdf Manuals

image

Related Search

Related Contents

LG 50PM4700 Energy Guide : Free Download, Borrow, and Streaming : Internet Archive  Projektierungshandbuch  Altronix RB30 power relay  SCR`T 取イ寸・取扱説明書  Lire un extrait  Belle Foret BF90217 Installation Guide  Compost Troubleshooting If you are having problems making good  URC2069 - Universal Electronics Remote Control Support  VITOLIG 200 Bedienungsanleitung  ClubKart STD - PLAY iT! Amusements  