Home
Greenheck Fan M9185D User's Manual
Contents
1. Bracket Linkage Adjustment Pin Mounting Plate 1 4 in E Ring 1 4 20 x 1 2 in Threadstud Drive Link 1 4 20 x 3 4 in Threadcutting Screw Stand Off Bracket 1 4 20 Spinlock Nut 1 4 in 20 x 1 2 in Thread Cutting Screw 1 2 in Crankarm Ball Bearing 5 16 18 x 11 2 in Bolt 221455A Crankarm 5 16 18 Spinlock Nut 10 Tek Screw 1 in Crankarm 1 4 in 20 x 1 2 in Hex Bolt 3 8 16 x 21 2 in Carriage Bolt l aj aj 2 3 4 5 6 10 7 8 9 AINI amp po po PM M hy O Instructions These installation instructions assume the damper is already mounted in a duct or sleeve with the damper shaft extending beyond the sleeve or duct 6 inches i Install the stand off bracket item 16 Dampers with a jackshaft 1a Mount the stand off bracket onto the jackshaft bracket with 4 1 4 20 X 1 2 in thread cutting screws item 17 Use the orientation shown on this page Note The bracket must be perpendicular to the damper on the duct or sleeve and the bracket s shaft hole must be centered on the jackshaft Dampers without a jackshaft Shaft Extension 1b Mount the stand off bracket item 16 spanning across the damper frame flanges Use the orientation shown to the right Fasten to the damper frame with 4 14 Tek screws supplied in the field Be sure not to run the screws into the damper linkage w
2. Part 454200 A GREENHECK Gf INSTALLATION INSTRUCTIONS Honeywell Modutrol IV Series Actuators Models M4182 M9185D amp M8182 UL Listed Electric Actuators with Two Position Control These instructions apply to the external field installation of Honeywell actuators on Greenheck model VCD Control Dampers FSD Fire Smoke Dampers and SMD Smoke Dampers when they are duct mounted or sleeved Tools Required Honeywell actuators rotate to their energized position when power Wrenches is applied and spring return to their fail position when power is 1 3 s 2 1 2 1 9 16 1 7 16 and 1 8 16 interrupted except for the M9185D which is a modulating actuator 1 Hammer that spring returns to the fail position when power is interrupted The M9185 model actuator when installed on model FSD fire smoke and SMD smoke dampers in accordance with these instructions complies with the requirements of NFPA 90A and UL Standards 555 and 555S Smoke or Fire Smoke dampers are normally arranged to operate automatically in response to heat signals from a heat or smoke detector or a building alarm system Installation must be acceptable to the authority having jurisdiction These parts are for 10 Z use with a 1 in shaft Note These actuator models require field calibration for the zero and span setting Part Number Quantity Description Part Number Quantity Actuator 3 8 16 Spinlock Nut Mounting
3. V 3 6 21 6 Ratings for 40 VA pilot duty 120 240 VAC on opposite contact IGREENHECK Copyright 2005 Greenheck Fan Corporation 454200 Honeywell M4182 M8182 M9185 IOM P O Box 410 Schofield WI 54476 0410 715 359 6171 greenheck com Rev 5 August 2005
4. d nuts are to be positioned as in the exploded view For dampers with 1 in shafts The 1 in crankarm item 10 must be in the position shown in the encircled exploded view shown above left Position the bolt and nut as shown in the same diagram For dampers with 1 2 in shafts Insert a linkage adjustment pin through both of the crankarm slots Position it 3 in from the center of the damper shaft Secure it there with a 1 4 20 spinlock nut item 6 For dampers with 1 in shafts Insert a linkage adjustment pin through the 1 in crankarm item 10 slot Position it 3 in from the center of the damper shaft Secure it there with a 1 4 20 spinlock nut item 6 Attach the drive link to the damper shaft crankarms by inserting the linkage adjustment pin through one of the drive link s holes and fastening it with an E ring item 14 Attach the drive link to the actuator crankarm with the linkage adjustment pin a spinlock nut and an E ring item 14 Set the linkage adjustment pin 21 8 in from the actuator shaft center and secure it there with the spinlock nut Fasten the other end through the empty drive link hole with the E ring item 14 Note the damper shaft rotation for fail direction and orient the linkage appropriately as shown in the linkage illustration The damper linkage is now in its fail position Position the damper blades to their proper position open or closed Tighten the bolts 8 Wire the actuator accordin
5. g to the appropriate wiring illustration that identifies the actuator s electrical connections Wiring should be per an approved project or job wiring diagram and must comply with all applicable electrical codes Note Tape or wire nut all unused leads 9 Apply power to the actuator The damper blades should fully open or close and return to the fail position when power is disconnected if they do not adjustments can be made by resetting the crankarm position on the damper or actuator shaft or by adjusting the 3 in dimension on the damper shaft crankarms N C Yellow Red N C Blue Auxiliary Switch Wiring Connections All colors are tracers on white wire White 120 v lt 280v lt Violet 240v lt Orange Com lt Black Transformer o e Model M4182 Wiring Connections Note Model M8182 is a 24 Volt actuator with no transformer Connections must be made directly to T1 and T2 Control Device L1 Hot L2 Transformer Model M9185 Wiring Connections Note This is a modulating actuator that requires a control signal to operate Electrical Ratings Without Transformer o a With Internal Transformer E wn A Controller Type Two wire on off switching action Auxiliary Switch Ratings Amperes Full Load Locked Rotor 120V 240
6. hich is between the flanges Note The bracket must be perpendicular to the damper on the duct or sleeve and the bracket s shaft hole must be centered on the shaft extension Fasten the mounting plate item 3 to the mounting bracket item 2 using 4 1 4 20 x 1 2 in thread studs item 4 and 4 1 4 20 spinlock nuts item 6 through the matching four hole pattern on the mounting bracket labeled A on the illustration Note that the mounting bracket has only one pattern that will match the mounting plate pattern Mount the mounting bracket item 2 to the stand off bracket using 4 1 4 20 x 1 2 in bolts item 21 and 4 1 4 20 Spinlock nuts item 6 included with this kit Use the outer four holes of the mounting bracket for jackshafted models and the inner four holes for directly driven models If the damper has a 1 2 in dia damper shaft mount the ball bearing item 18 into the mounting bracket with two 10 Tek screws item 20 The Tek screws are required to keep the thrust forces from pushing the bearing out of the mounting bracket If the damper shaft is 1 in in diameter then no ball bearing is required Mount the actuator to the mounting plate in the corresponding holes using 3 1 4 20 x 3 4 in thread cutting screws item 5 Note that the actuator must be mounted with the shaft in the horizontal position Orientation of Stand Off Orientation of Stand Off Bracket for a jackshaft Bracket for a directly dr
7. iven driven damper damper Damper O O O O O A O O WA A S O O O O O Mounting Plate Damper Shaft i 21 8 Power Position Return ____ Power Fail Position Counter Clockwise to Fail Position Steps 6a b for dampers with 1 in shafts place of 7 8 9 amp 13 Steps 6a b for dampers with 1 2 in shafts 21 8 Power Position Return ___ Power Fail Position Clockwise to Fail Position substitute these parts in 6 6b 6c 6d Assemble the linkage Parts needed for dampers with 1 2 in shafts Qty 2 1 2 in crankarms item 7 Qty 2 5 16 18 x 11 2 in bolts item 8 Qty 2 5 16 18 spinlock nuts item 9 Qty 1 Drive link item 15 Qty 2 Linkage adjustment pin item 13 Qty 2 1 4 20 spinlock nuts item 6 Qty 1 Actuator crankarm item 19 Qty 2 1 4 in E Ring item 14 Parts needed for dampers with 1 in shafts Qty 1 1 in crankarm item 10 Qty 1 3 8 16 x 21 2 in bolts 11 Qty 1 3 8 16 spinlock nut 12 Qty 1 Drive link 15 Qty 2 Linkage adjustment pin 13 Qty 2 1 4 in 20 spinlock nuts 6 Qty 1 Actuator crankarm 19 Qty 2 1 4 in E Ring 14 Assemble the shaft crankarms For dampers with 1 2 in shafts The damper shaft crankarms must be placed as mirror images of each other meaning the like sides face each other The bolts an