Home
Fisher FB1000-2 User's Manual
Contents
1. 0 9999 volt hour timed run Automatic restart if loss of AC power if enabled Large LCD display Unpacking the Power Supply When unpacking your FB1000 power supply be sure you have received the following items e FB1000 unit e AC line cord e This manual Inspect your equipment and packaging material for signs of damage Damage to the shipping container may indicate rough handling which could cause internal damage to the power supply If you suspect shipping damage to the power supply contact your carrier for instructions on filing a claim If you are missing any of the above items contact your supplier for instructions FB1000 2 MANUAL Page 3 7608177 Rev A 8 9 02 Specifications AC input Power 85 265VAC 50 60Hz 350VA Max Environmental Operating temperature 0 40 C 0 95 R H non condensing Altitude 2000m Overvoltage category I IEC664 Pollution degree 2 IEC664 DC output Power 5 1000VDC 250W Max 1 500mA 250W Max Ripple 1 Drift 1 after 30 minute warm up FB1000 2 MANUAL Page 4 7608177 Rev A 8 9 02 Getting Started Select a location that allows for 3 clearance behind the power supply and comfortable reach of the front panel controls and cell connections Do not block the vented area of the case on the front bottom of the unit or the fan area at the rear Connect the power supply to a 3 prong grounded AC outlet using the AC cord provided with the unit only Connect the electrophoresis appa
2. The time value displays elapsed time for an untimed run or time left for a timed run The volt hour value displays the accumulated volt hour value for the run Constant Voltage Operations From the mode selection screen select constant voltage operation by pressing the appropriate function key located to the right of the display To get to the selection screen from an operating screen press Exit or cycle the control logic off and then back on by pressing the gray ON OFF key and selecting MANUAL The FB1000 will display the last saved values for constant voltage mode To switch between volts current power and time volt hours press function key F1 To change a parameter press the function key located to the right of the display next to the parameter you wish to change The FB1000 will allow a new value to be entered using the keypad numeric keys Press the function key labeled Enter to complete the new setting Press Clear to erase previous keystrokes Press Exit to cancel entering a new value The FB1000 will not accept a voltage setpoint outside of the allowed range Press Clear to re enter an appropriate value The limit parameters are normally set to the power supply maximum values The FB1000 will not accept a limit parameter outside of the allowed range In addition the FB1000 will never exceed the maximum power output specification of 250W Constant Current Operations From the mode selection screen select constant current operat
3. um einen geeigneten Wert einzugeben Wenn alle Parameter des Schritts wie gew nscht eingestellt sind dr cken Sie Exit Beenden um zum Schritte Bildschirm zur ckzukehren Die neu eingetragenen Parameter werden im gew hlten Schritt angezeigt Um einen Schritt nach dem gew hlten hinzuzuf gen dr cken Sie die Funktionstaste mit der Beschriftung ADD Hinzuf gen Geben Sie die Parameter f r den Schritt genau wie f r EDIT Bearbeiten ein und dr cken Sie nach Beendigung der Eingabe Exit Beenden Zum L schen eines Programms oder eines Schrittes dr cken Sie je nach Bedarf die Clear Taste L schen des Programms oder des Schritte Bildschirms Nach der Best tigung l scht das FB1000 das gew hlte Programm oder den Schritt aus dem Ger tespeicher N Methodennummer Method 1 Next Navigations und A 2 steps Prev a Bearbeitungstasten Anzahl der Schritte Edit Abbildung 2 Programmbildschirm Method 1 1 2 Next No 100V 200mA Prev 4 Bearbeitungstasten 150W Add Schrittparameter 7 0 10 Edit der Vorgabewe ist reverses Video Abbildung 3 Schritte Bildschirm FB1000 2 MANUAL Page 9 7608177 Rev A 8 9 02 Reinigung Vor dem Reinigen des Ger tes sollten Sie stets sicherstellen dass das Ger t Netzschalter befindet sich auf der Riickseite ausgeschaltet und das Netzkabel abgetrennt ist Die Vorderseite des Ger tes ist abgedichtet und kann mit einem mit mildem Rei
4. A 8 9 02 key and selecting MANUAL The FB1000 will display the last saved values for constant power mode To switch between volts current power and time volt hours press function key F1 To change a parameter press the function key located to the right of the display next to the parameter you wish to change The FB1000 will allow a new value to be entered using the keypad numeric keys Press the function key labeled Enter to complete the new setting Press Clear to erase previous keystrokes Press Exit to cancel entering a new value The FB1000 will not accept a power setpoint outside of the allowed range Press Clear to re enter an appropriate value The limit parameters are normally set to the power supply maximum values The FB1000 will not accept a limit parameter outside of the allowed range In addition the FB1000 will never exceed the maximum power output specification of 250W Timed Operations It is possible to enter an amount of time for the power supply to provide power after which it will automatically shut off Use this feature for timed runs Set up a constant mode setpoint and limits as described above Enter a time duration of 0 99 hours 59 minutes A time duration of zero effectively disables timed run mode When running a timed run the time parameter displays the time remaining in the run When running a non timed run the time parameter displays the elapsed time during the run Volt Hour Operations It is possib
5. Commandes du panneau avant Utilisation de l alimentation lectrique Appuyez sur la touche gris fonc qui se trouve sur le devant de l appareil pour activer d sactiver les circuits logiques de commande L cran d affichage cristaux liquides s allume et permet de s lectionner le mode de fonctionnement MANUEL ou PROGRAMME ainsi que d activer d sactiver le red marrage automatique en cas de panne de courant Activez ou d sactivez la fonction de red marrage automatique en cas de panne de courant en appuyant sur la touche de fonction situ e en haut droite de l cran S lectionnez le mode MANUEL ou PROGRAMME en utilisant les touches de fonction qui se trouvent a droite de l cran voir la section Programmation pour une description du mode de programmation En mode manuel le FB1000 pr serve la valeur de consigne constante chaque fois que vous commencez une ex cution Le param tre constant est sauvegard ind pendamment pour chaque mode tension intensit et puissance constante FB1000 2 MANUAL Page 5 7608177 Rev A 8 9 02 Pour changer le mode de contr le appuyez sur la touche de sortie Exit partir de l cran qui appara t s lectionnez le nouveau param tre constant l aide des touches de fonction qui se trouvent droite de l cran Une fois que vous avez s lectionn le mode de contr le et d fini les param tres de limite et de dur e si vous le souhaitez appuyez sur la touche
6. Parameter zu ndern dr cken Sie an der rechten Seite der Anzeige die Funktionstaste neben dem zu ndernden Parameter Auf dem FB1000 kann der neue Wert ber die Zahlentastatur eingegeben werden Dr cken Sie die Funktionstaste mit der Beschriftung Enter um die neue Einstellung zu akzeptieren Zum L schen der eingegebenen Zahlen dr cken Sie Clear L schen Zum Abbrechen der Eingabe eines neuen Wertes dr cken Sie Exit Beenden Das FB1000 akzeptiert keinen Spannungsvorgabewert der au erhalb der zugelassenen Grenze liegt Dr cken Sie Clear um einen geeigneten Wert einzugeben Die Grenzwerte sind normalerweise auf den H chstwert des Netzteils eingestellt Das FB1000 akzeptiert keinen Grenzparameter au erhalb des zul ssigen Bereichs Au erdem berschreitet das FB1000 niemals die maximale Ausgangsleistung von 250 W Betrieb bei Dauerstrom Auf dem Modusauswahlbildschirm w hlen Sie unter Verwendung der entsprechenden Funktionstaste an der rechten Seite der Anzeige den Dauerstrom Um auf diesen Auswahlbildschirm von einer Betriebsanzeige aus zuzugreifen dr cken Sie Exit Beenden oder Sie schalten die Steuerlogik durch Dr cken der grauen ON OFF Taste aus und dann wieder ein FB1000 2 MANUAL Page 6 7608177 Rev A 8 9 02 und w hlen dann den MANUELLEN MODUS Das FB1000 zeigt die zuletzt gespeicherten Werte f r den Dauerstrommodus an Um zwischen den Betriebsmodi Volt Strom Leistung sowie zeitgesteuert Voltstunden zu wechs
7. nderung im 22 Laststrom registriert berpr fen Sie die Einrichtung und die Anschl sse des Ger tes 04 Netzstromausfall PF deaktiviert und nicht durchgef hrt Das FB1000 hat einen Netzstromausfall registriert wobei die Ausf hrung nicht abgeschlossen wurde da PF deaktiviert war 05 Netzstromausfall Ausf hrung nicht zeitgesteuert Das FB1000 hat einen Netzstromausfall registriert 06 99 Das FB1000 hat einen internen Fehlerzustand registriert Wenden Sie sich f r weitere Anweisungen an den technischen Kundendienst Vor dem Reinigen des Ger tes sollten Sie stets sicherstellen dass das Ger t ausgeschaltet Netzschalter befindet sich auf der R ckseite und das Netzkabel abgetrennt ist Das FB1000 Netzteil erfordert keine regelm ige Wartung und sollte jahrelang problemlos betrieben werden k nnen Gehen Sie wie folgt vor wenn eine Sicherung ausgewechselt werden muss Auswechseln einer Sicherung VORSICHT Das FB1000 ist mit zwei doppelpoligen Sicherungen ausgestattet Schalten Sie das Ger t aus Netzschalter befindet sich auf der R ckseite und trennen Sie das Netzkabel ab Stemmen Sie den Sicherungshalter mit einem kleinen Schraubenzieher heraus Wechseln Sie immer beide Sicherungen und verwenden Sie folgende Ersatzsicherungen 5A 250V 5 X 20 mm Typ T Sicherung TSA 250V Fisher Katalognr FB FUSE 3 FB1000 2 MANUAL Page 11 7608177 Rev A 8 9 02 FB1000 Garantieerkl rung Die Fisher Scient
8. y presenta las condiciones justo antes de la parada Para hacer una pausa en un proceso en curso presione la tecla Pause Pausar La pantalla cambiar a PAUSE Pausar indicando que la salida ya no est activada y que se puede reanudar el proceso Si se presiona la tecla Run Procesar o Pause Pausar se reanudar el funcionamiento desde el punto previo es decir para un proceso temporizado S lo se puede reiniciar un proceso que se ha pausado Despu s de detener un proceso o para cambiar los par metros de un proceso pausado primero active y luego desactive la l gica de control presionando la tecla gris de Activar Desactivar Durante un proceso la pantalla mostrar los valores actuales del voltaje la corriente la potencia y la temperatura El valor de tiempo muestra el tiempo transcurrido para un proceso no temporizado o el tiempo remanente para un proceso temporizado El valor de voltios hora muestra el valor acumulado de voltios hora para el proceso Operaciones a voltaje constante En la pantalla de selecci n de modos elija operaci n a voltaje constante presionando la tecla de funci n apropiada situada a la derecha de la pantalla Para ir a la pantalla de selecci n desde una pantalla de operaci n presione Exit Salir o primero desactive y luego active la l gica de control presionando la tecla gris de Activar Desactivar y seleccionando MANUAL El FB1000 mostrar los ltimos valores guardados para el modo de voltaje c
9. F Fisher Scientific FB1000 2 Electrophoresis Power Supply Operator s Manual Fisher Biotech FB1000 Electrophoresis Power Supply Table of Contents Safety Considerations 2 Introduction 3 Unpacking the Power Supply 3 Specifications 4 Getting Started 5 Using the Power Supply 5 Constant Voltage Operations 6 Constant Current Operations 6 Constant Power Operations 6 Timed Operations 7 Volt Hour Operations 7 Automatic Power fail Restart 7 Programming 8 Cleaning 9 Troubleshooting and Error Indications 10 FB 1000 Warranty Statement 11 Compliance 11 Replacement Parts 11 FB1000 2 MANUAL Page 1 7608177 Rev A 8 9 02 Safety Considerations Read and understand this manual completely before attempting to set up or use this instrument This equipment has been designed and tested to conform to IEC1010 1 safety standards as applicable to laboratory instrumentation This applies only to the FB1000 when used as specified in the documentation in its intended applications with Fisher Biotech approved electrophoresis apparatus only Usage in any other manor may not provide similar performance or safety protection This equipment is provided with a 3 conductor grounded AC line cord The protective earth ground is necessary for safe operation Do not use any other AC line cord with this instrument The FB 1000 is a high voltage power supply capable of generating dangerous levels of voltage and current during operation Exercise cautio
10. FUSE 3 FB1000 2 MANUAL Page 11 7608177 Rev A 8 9 02 Declaraci n de garant a del FB1000 Fisher Scientific Company Fisher garantiza al comprador directo del FB1000 contra defectos de material y mano de obra durante el per odo de garant a especificado Durante tal per odo Fisher reparar o sustituir el producto u otorgar un cr dito a su sola discreci n siempre que se le notifique de inmediato y se cumplan sus instrucciones Para las fuentes de alimentaci n FB1000 dicho per odo especificado es de 48 meses contados desde la fecha de fabricaci n Salvo que se acuerde lo contrario la garant a quedar limitada al pa s en el que se vendi el producto Ning n empleado agente o representante de Fisher tiene autoridad para obligar a Fisher por ninguna representaci n o garant a oral relativa a cualquier producto vendido Cualquier representaci n o garant a oral ofrecida antes de la compra y que no se haya hecho constar por escrito y firmar por un funcionario debidamente autorizado de Fisher no podr ser exigida por el comprador FISHER RECHAZA EXPRESAMENTE CUALQUIER OTRA GARANT A EXPRESA O IMPL CITA INCLUYENDO LA GARANT A IMPL CITA DE COMERCIABILIDAD Y APTITUD PARA UN PROP SITO PARTICULAR La nica responsabilidad de Fisher y el remedio exclusivo del comprador por cualquier reclamo que surja de la compra de cualquier producto listado anteriormente es la reparaci n el reemplazo o el cr dito seg n se desc
11. comun quese con la compa a que realiz el transporte para recibir instrucciones sobre c mo presentar el reclamo Si falta alguno de los elementos anteriormente mencionados comun quese con su proveedor para obtener m s instrucciones FB1000 2 MANUAL Page 3 7608177 Rev A 8 9 02 Especificaciones Potencia de entrada de CA 85 a 265 voltios de CA 50 60Hz 350VA max Medioambientales Temperatura de operaci n 0 40 C 0 95 de humedad relativa sin condensaci n Altura 2000 m Categor a de sobrevoltaje II IEC664 Grado de contaminaci n 2 IEC664 Potencia de salida de CC 5 a 1000 voltios de CC 250 vatios m x 1 a 500mA 250 vatios m x Fluctuaci n 1 Desplazamiento 1 despu s de 30 minutos de calentamiento FB1000 2 MANUAL Page 4 7608177 Rev A 8 9 02 Para empezar Seleccione un lugar que permita tener unos 7 5 cm de espacio libre detr s de la fuente de alimentaci n y donde se pueda acceder con facilidad a los controles delanteros del panel de control y las conexiones de las celdas No bloquee el rea de ventilaci n de la caja en la parte inferior delantera de la unidad o el rea del ventilador en la parte posterior Conecte la fuente de alimentaci n a una toma de CA para tres puntas con conexi n a tierra usando solamente el cable de CA que viene con la unidad Conecte el aparato para electroforesis a la fuente de alimentaci n asegur ndose de hacer coincidir el conductor positivo rojo con el enchufe
12. de utilizar este equipo Este equipo s lo se debe usar en interiores FB1000 2 MANUAL Page 2 7608177 Rev A 8 9 02 Introducci n Gracias por escoger una fuente de alimentaci n para electroforesis Fisher Scientific FB1000 Este manual describe el funcionamiento del FB1000 La fuente de alimentaci n que ha adquirido es la unidad m s productiva y f cil de usar que existe en el mercado Este manual deber responder cualquier pregunta que pudiera surgir durante el funcionamiento de la fuente de alimentaci n sin embargo si requiere de ayuda no dude en llamar a nuestra L nea de Asistencia T cnica para Equipos de Laboratorio Fisher al 1 800 943 2006 al 412 490 6260 en los Estados Unidos En otros pa ses llame a su distribuidor local La fuente de alimentaci n FB 1000 se ha dise ado para suministrar voltaje corriente o potencia constantes en ambos modos de operaci n Manual y Programado utilizados usualmente en las aplicaciones de electroforesis Puede conectar en paralelo y poner en funcionamiento simult neamente de uno a cuatro grupos de celdas para electroforesis El FB1000 puede suministrar hasta 250 vatios de potencia de salida total Cuando funciona en cualquier modo constante la fuente de alimentaci n limita autom ticamente los otros par metros bien al m ximo de la fuente de alimentaci n o a un l mite inferior que haya establecido el usuario Si se alcanza cualquiera de los l mites no constantes la fuente de alimenta
13. der schwarzen negativen Buchse angeschlossen wird Wenn Sie mehrere Elektrophorese Ger te gleichzeitig betreiben m chten schlie en Sie diese auf gleiche Weise an Schlie en Sie eine Temperatursonde an den Anschluss auf der R ckseite des FB1000 und an das Elektrophorese Ger t an wenn Sie eine Temperatur berwachung f r eine Ausf hrung durchf hren m chten Schalten Sie das Ger t ein Netzschalter befindet sich auf der R ckseite des Ger tes neben dem Netzkabeleingang Funktionstasten Schwarze neg Buchsen Clear Taste Schwarze neg Buchsen Run e e Rote pos Buchsen Stop Taste Run Taste Pause Taste Rote pos Buchsen Graue ON OFF Taste Abbildung 1 Regler auf dem Bedienfeld Verwenden des Netzteils Dr cken Sie zum Aktivieren Deaktivieren der Steuerlogik die graue Taste an der Vorderseite des Ger tes Die LCD Anzeige leuchtet auf und erm glicht die Wahl des MANUELLEN oder PROGRAMM Betriebsmodus sowie das Aktivieren Deaktivieren des automatischen Neustarts bei Stromausfall Der automatische Neustart bei Stormausfall kann durch Dr cken der obersten Funktionstaste rechts neben der Anzeige umgeschaltet werden W hlen Sie durch Dr cken der Funktionstasten rechts neben der Anzeige den MANUELLEN oder PROGRAMM Modus aus siehe im Abschnitt Programmierung die Beschreibung des Programmiermodus Wenn Sie im manuellen Modus eine Ausf hrung starten speichert das FB1000 jedes Mal den konstanten FB1000 2 MANUAL Pag
14. hembra positivo rojo y el conductor negativo negro con el enchufe hembra negativo negro Conecte de manera similar conecte uno o varios aparatos para electroforesis a la fuente de alimentaci n si piensa hacer funcionar dos o m s en paralelo Si piensa realizar la vigilancia de la temperatura durante el proceso conecte una sonda de temperatura al conector de la parte trasera del FB1000 y al aparato para electroforesis Encienda la unidad usando el interruptor de alimentaci n de CA ubicado en la parte posterior de la unidad al lado de la entrada del cable de alimentaci n de CA Teclas de fimci n Enchufes hembra Enchufes hembra negatives negros me a Tecla Salir Tecla Despejar kun LI e Enchufes hembra positivos rojos Tech Tech Encuhs has Procesar Tecla Parar positivos rojos Pura Tecla gris de Adra Desactivar Figura 1 Controles del panel delantero Uso de la fuente de alimentaci n Presione la tecla gris oscuro en la parte delantera de la unidad para activar desactivar la l gica de control La pantalla de cristal l quido se iluminar y permitir la selecci n del modo de operaci n MANUAL o PROGRAM as como la activaci n desactivaci n autom tica del reinicio en caso de p rdida del suministro Conmute el reinicio autom tico en caso de p rdida de la alimentaci n presionando la tecla de funci n superior de la derecha de la pantalla Seleccione el modo MANUAL o PROGRAM usando las teclas de funci n situadas a la
15. intervalo permitido Presione Clear Despejar para reingresar un valor apropiado Cuando todos los par metros del paso sean los deseados presione Exit Salir para volver a la pantalla de pasos Los par metros que se acaban de introducir se presentar n en el paso seleccionado Para agregar un paso despu s del paso seleccionado presione la tecla de funci n ADD Agregar Introduzca los par metros del paso como en EDIT presionando Exit al completarlos FB1000 2 MANUAL Page 8 7608177 Rev A 8 9 02 Para eliminar un programa o paso presione la tecla Clear Despejar en la pantalla de programaci n o de pasos seg n lo desee Despu s de la confirmaci n el FB 1000 eliminar el programa o paso seleccionado de la memoria FB1000 2 MANUAL Page 9 7608177 Rev A 8 9 02 N mero de m todo N mero de pasos N mero de m todo Par metros de paso el valor xe prefijado es video inverso Limpieza M todo 1 Next Teclas de 2 pasos Prev navegacion y edicion Edit Figura 2 Pantalla Program Paso 1 de 2 M todo 1 1 2 Next Teclas de navegaci n y 100V 200mA Prev 7 edici n 150W Add 0 10 Edit Figura 3 Pantalla Paso Antes de limpiar la unidad siempre aseg rese de desconectar la alimentaci n de CA utilizando el interruptor de la parte posterior de la unidad y despu s desconecte el cable de alimentaci n de CA La parte delantera de la unidad est sellada y se puede limpiar frot ndola con cua
16. jeux de cellules d lectrophor se peuvent tre connect s en parall le et fonctionner simultan ment Le FB1000 peut produire jusqu 250 W de puissance de sortie totale Lorsqu elle fonctionne en mode constant quel qu il soit l alimentation lectrique limite automatiquement les autres param tres au maximum de l alimentation lectrique ou une limite inf rieure si une telle limite a t d finie par l utilisateur Si une limite non constante est atteinte l alimentation lectrique changera automatiquement de mode de contr le contr lant le param tre de limite De cette fa on le FB1000 prot ge vos cellules d lectrophor se contre toute condition de suralimentation susceptible de provoquer des d g ts L alimentation lectrique FB1000 permet galement de programmer un fonctionnement dur e d termin ou en volts heures dans tous les modes de contr le et permet une ex cution automatique dans le cas d une coupure de courant si cette fonction a t activ e Caract ristiques 5 1000 V ajustable par pas de 1 volt 1 500 mA ajustable par pas de 1 mA 1 250 W ajustable par pas de 1 W 0 90 C ajustable par pas de 1 C Commutateur automatique de mode de contr le Cycle programm de 0 99 heures 59 minutes Cycle programm de 0 9999 volts heures Red marrage automatique en cas de coupure de l alimentation en CA si activ Grand cran d affichage cristaux liquides D ballage de l aliment
17. para el modo de corriente constante Para cambiar entre voltios corriente potencia y tiempo voltios hora presione la tecla de funci n F1 Para cambiar un par metro presione la tecla de funci n situada a la derecha de la pantalla pr xima al par metro que desea cambiar El FB1000 permitir la entrada de un valor nuevo usando las teclas num ricas del teclado Presione la tecla de funci n con el nombre Enter Introducir para completar la nueva configuraci n Presione Clear Despejar para borrar la secuencia de teclas previas FB1000 2 MANUAL Page 6 7608177 Rev A 8 9 02 Presione Exit Salir para cancelar la entrada de un valor nuevo El FB1000 no aceptar un valor prefijado de corriente fuera del intervalo permitido Presione Clear Despejar para reingresar un valor apropiado Los par metros de l mite normalmente se establecen a los valores m ximos de la fuente de alimentaci n El FB1000 no aceptar un par metro de l mite fuera del intervalo permitido Adem s el FB1000 nunca exceder la especificaci n de potencia de salida m xima de 250 vatios Operaciones a potencia constante En la pantalla de selecci n de modos elija operaci n a potencia constante presionando la tecla de funci n apropiada situada a la derecha de la pantalla Para ir a la pantalla de selecci n desde una pantalla de operaci n presione Exit Salir o primero desactive y luego active la l gica de control presionando la tecla gris de Activar Desactiv
18. program Use the function keys to the right of the display to move through the 9 possible programs To run the program starting from step 1 press the Run key To edit a program including adding a first step to an empty program press the function key labeled EDIT The FB1000 will display the step screen which shows the parameters for the selected step except when the program is empty in which case the FB1000 automatically starts entering the first step as follows Use the function keys to the right of the display to move through the 9 possible steps To run the program starting from the selected step press the Run key To edit a step press the function key labeled EDIT The FB1000 displays the mode selection screen Select a constant mode of operation by pressing the appropriate function key located to the right of the display To switch between volts current power and time volt hours press function key F1 To change a parameter press the function key located to the right of the display next to the parameter you wish to change The FB 1000 will allow a new value to be entered using the keypad numeric keys Press the function key labeled Enter to complete the new setting Press Clear to erase previous keystrokes Press Exit to cancel entering a new value The FB1000 will not accept any parameter outside of the allowed range Press Clear to re enter an appropriate value When all the parameters of the step are as desired press Exit to return to the
19. tension en appuyant sur la touche grise MARCHE ARR T Au cours d une ex cution l cran affiche les valeurs effectives de tension d intensit de puissance et de temp rature Le temps affich repr sente le temps coul pour une ex cution sans dur e d termin e ou le temps restant pour une ex cution dur e d termin e La valeur de volts heures affiche les volts heures accumul s pour l ex cution Op rations tension constante partir de l cran de s lection de mode s lectionnez un fonctionnement tension constante en appuyant sur la touche de fonction appropri e droite de l cran Pour passer d un cran op rationnel l cran de s lection appuyez sur Exit ou teignez et rallumez les circuits logiques de commande en appuyant sur la touche grise MARCHE ARR T et en s lectionnant MANUEL Le FB1000 affiche les derni res valeurs sauvegard es pour le mode de tension constante Pour alterner entre tension intensit puissance et dur e volts heures appuyez sur la touche de fonction F1 Pour changer un param tre appuyez sur la touche de fonction situ e droite de l cran en face du param tre que vous d sirez changer Le FB1000 permet d entrer une nouvelle valeur l aide des touches num riques du clavier Appuyez sur la touche de fonction libell e Enter pour valider le nouveau param tre Appuyez sur la touche Clear pour effacer les frappes pr c dentes Appuyez sur la touc
20. 00 Temperature Probe 0 90 C FB TEMP FB1000 2 MANUAL Page 11 7608177 Rev A 8 9 02 Alimentation lectrique pour lectrophorese Fisher Biotech FB1000 Table des mati res Consid rations de s curit 2 Introduction 3 Deballage de l alimentation lectrique 3 Sp cifications 4 Mise en route 5 Utilisation de l alimentation lectrique 5 Op rations tension constante 6 Op rations intensit constante 6 Op rations puissance constante 7 Op rations dur e d termin e 7 Op rations en volts heures 7 Red marrage automatique en cas de coupure de courant 8 Programmation 8 Nettoyage 10 D pannage et indications d erreur 11 Garantie du FB1000 12 Conformit 12 Pi ces de rechange 12 FB1000 2 MANUAL Page 1 7608177 Rev A 8 9 02 Consid rations de s curit Lisez et comprenez compl tement ce manuel avant d entreprendre d installer ou d utiliser cet instrument Cet appareil a t congu et test pour tre conforme aux normes de s curit CSA1010 telles qu elles s appliquent aux instruments de laboratoire Ceci s applique uniquement au FB1000 lorsqu il est utilis de la mani re sp cifi e dans la documentation dans le cadre des applications auxquelles il est destin uniquement avec un appareil d lectrophor se agr par Fisher Biotech Une utilisation dans d autres circonstances peut ne pas donner les m mes performances ou la m me protection de s curit Cet appareil est fourni ave
21. 000 Park Lane Pittsburgh PA 15275 EE UU Cable de alimentaci n de CA FB CORD 3 Fusible T5A 250V FB FUSE 3 FB1000 2 MANUAL Page 13 7608177 Rev A 8 9 02 F Fisher Scientific Instruction Manual FB1000 2 Electrophoresis Power Supply Part No 7608177 Rev A 8 02
22. 1000 compl te l tape interrompue puis passe l tape suivante du programme Programmation Le FB1000 peut enregistrer 9 programmes contenant chacun 9 tapes Une tape de programme est une valeur de consigne de tension intensit ou puissance constante avec tous les param tres de limite associ s et surtout une valeur de dur e et ou volts heures Lors de l ex cution d une tape de programme une fois la limite de dur e ou de volts heures atteinte le FB1000 ex cutera automatiquement l tape de programme suivante s il y en a une Une fois ex cut es toutes les tapes d un programme le FB1000 s teindra N importe quelle s quence de mode de contr le et d tapes dur e d termin e ou en volts heures peut tre contenue dans un programme Notez qu une tape de programme peut contenir un z ro pour les param tres de dur e et de volts heures auquel cas le FB1000 continuera maintenir ind finiment cette valeur de consigne comme si le r glage avait t effectu partir du mode MANUEL Pour entrer en mode de programmation partir d un cran op rationnel teignez et rallumez les circuits logiques de commande en appuyant sur la touche grise MARCHE ARR T et en s lectionnant PROGRAMME Le FB1000 affichera l cran des programmes qui montre le nombre d tapes contenues dans le programme s lectionn Utilisez les touches de fonction droite de l cran pour vous d placer parmi l
23. Neustart bei Stromausfall aktiviert ist durchf hren Zum Aktivieren des automatischen Neustarts bei Stromausfall dr cken Sie auf dem Modusauswahlbildschirm MANUELLER oder PROGRAMM MODUS die obere Funktionstaste Mit jedem Tastendruck wird die Funktion f r den automatischen Neustart entweder aktiviert oder deaktiviert Wenn der Netzstrom w hrend einer Ausf hrung bei der der Neustart bei Stromausfall aktiviert ist wiederhergestellt wird erscheint POWER FAIL RESTART ca 10 Sekunden lang auf der Anzeige um auf den anstehenden Neustart bei Stromausfall hinzuweisen W hrend dieser Zeit wird der Ausgang nicht gespeist um ein sicheres Stoppen der Ausf hrung durch Dr cken von RUN zu erm glichen Wenn die Zeitverz gerung f r den anstehenden Neustart bei Stromausfall abgeschlossen ist steigt der Netzteilausgang auf den entsprechenden Vorgabewert und die Ausf hrung l uft von diesem Zeitpunkt an weiter Die Anzahl der Stromausf lle w hrend einer Ausf hrung f r diese Funktion ist unbegrenzt Wenn ein automatischer Neustarts bei Stromausfall w hrend der Ausf hrung des Programms stattfindet f hrt das FB1000 den unterbrochenen Schritt komplett aus und f hrt dann mit dem n chsten Schritt im Programm fort Programmierung Das FB1000 kann 9 Programme mit jeweils 9 Schritten speichern Bei einem Programmschritt handelt es sich um einen Vorgabewert f r Dauerspannung Dauerstrom oder Dauerleistung mit allen dazugeh rigen Grenzparamete
24. Voltstunden zu wechseln dr cken Sie die Funktionstaste Fl Um einen Parameter zu ndern dr cken Sie an der rechten Seite der Anzeige die Funktionstaste neben dem zu ndernden Parameter Auf dem FB1000 kann der neue Wert ber die Zahlentastatur eingegeben werden Dr cken Sie die Funktionstaste mit der Beschriftung Enter um die neue Einstellung zu akzeptieren Zum L schen der eingegebenen Zahlen dr cken Sie Clear L schen Zum Abbrechen der Eingabe eines neuen Wertes dr cken Sie Exit Beenden Das FB1000 akzeptiert keinen Leistungsvorgabewert der au erhalb der zugelassenen Grenze liegt Dr cken Sie Clear um einen geeigneten Wert einzugeben Die Grenzwerte sind normalerweise auf den H chstwert des Netzteils eingestellt Das FB1000 akzeptiert keinen Grenzparameter au erhalb des zul ssigen Bereichs Au erdem berschreitet das FB1000 niemals die maximale Ausgangsleistung von 250 W Zeitgesteuerter Betrieb Am Netzteil kann eine bestimmte Betriebdauer eingestellt werden Nach Ablauf dieser Zeit schaltet sich das Ger t automatisch aus Verwenden Sie diese Funktion f r zeitgesteuerte Ausf hrungen Richten Sie einen Dauermodus Vorgabewert und Grenzparameter wie oben beschrieben ein Geben Sie eine Dauer von 0 99 Stunden 59 Minuten ein Wenn Sie die Betriebzeit auf Null stellen wird der zeitgesteuerte Ausf hrungsmodus automatisch deaktiviert W hrend einer zeitgesteuerten Ausf hrung zeigt der Zeitparameter die noch verb
25. a 99 horas y 59 minutos Una duraci n de tiempo igual a cero inhabilita efectivamente el modo de proceso temporizado Al ejecutar un proceso temporizado el par metro de tiempo muestra el tiempo de proceso remanente Al ejecutar un proceso no temporizado el par metro de tiempo muestra el tiempo transcurrido durante el proceso Operaciones en voltios hora Es posible definir una cantidad de voltios hora para que la fuente de alimentaci n suministre energ a despu s del cual se apagar autom ticamente Voltios hora es la integraci n del voltaje en el transcurso del tiempo Use el control de voltios hora para proporcionar uniformidad entre procesos Establezca un valor prefijado de modo constante y l mites tal como se describi anteriormente Introduzca una duraci n de voltios hora de 0 a 9999 voltios hora Una duraci n de voltios hora igual a cero desactiva efectivamente el modo de proceso en voltios hora Durante un proceso el valor voltios hora muestra el valor acumulado en voltios hora del proceso Reinicio autom tico tras un fallo en la alimentaci n La capacidad de reinicio autom tico tras un fallo en la alimentaci n permite el reinicio autom tico de un proceso temporizado o de voltios hora interrumpido por la p rdida de alimentaci n de CA de manera que se cumplan el tiempo voltios hora totales programados para el proceso NOTA La p rdida de la alimentaci n de CA incluye la desconexi n de la unidad utilizando el interru
26. ar y seleccionando MANUAL El FB1000 mostrar los ltimos valores guardados para el modo de potencia constante Para cambiar entre voltios corriente potencia y tiempo voltios hora presione la tecla de funci n F1 Para cambiar un par metro presione la tecla de funci n situada a la derecha de la pantalla pr xima al par metro que desea cambiar El FB1000 permitir la entrada de un valor nuevo usando las teclas num ricas del teclado Presione la tecla de funci n con el nombre Enter Introducir para completar la nueva configuraci n Presione Clear Despejar para borrar la secuencia de teclas previas Presione Exit Salir para cancelar la entrada de un valor nuevo El FB1000 no aceptar un valor prefijado de potencia fuera del intervalo permitido Presione Clear Despejar para reingresar un valor apropiado Los par metros de l mite normalmente se establecen a los valores m ximos de la fuente de alimentaci n El FB1000 no aceptar un par metro de l mite fuera del intervalo permitido Adem s el FB1000 nunca exceder la especificaci n de potencia de salida m xima de 250 vatios Operaciones temporizadas Es posible definir un per odo de tiempo para que la fuente de alimentaci n suministre energ a despu s del cual se apagar autom ticamente Use esta funci n para procesos temporizados Establezca un valor prefijado y l mites para el modo constante tal como se describi anteriormente Introduzca una duraci n de tiempo de 0
27. ation lectrique Lorsque vous d ballez votre alimentation lectrique FB1000 v rifiez que vous avez re u les l ments suivants e L appareil FB1000 e Le cordon d alimentation en CA e Ce manuel Inspectez votre appareil et le carton d emballage pour vous assurer qu ils ne sont pas endommag s Si le carton d emballage est ab m cela peut indiquer un manque de pr caution au cours de la manutention qui pourrait avoir provoqu des d g ts internes l alimentation lectrique Si vous soup onnez que l alimentation lectrique a t endommag e au cours du transport contactez votre transporteur pour obtenir des instructions sur la proc dure suivre pour faire une r clamation S il vous manque l un des articles ci dessus contactez votre fournisseur pour obtenir des instructions FB1000 2 MANUAL Page 3 7608177 Rev A 8 9 02 Sp cifications Courant d entr e CA 85 265 V CA 50 60 Hz 350 VA Max Environnement Temp rature de fonctionnement 0 40 C 0 95 humidit relative sans condensation Altitude 2000 m Cat gorie de surtension II IEC664 Degr de pollution 2 IEC664 Courant de sortie CC 5 1000 V CC 250 W Max 1 500 mA 250 W Max Ondulation 1 Derive 1 apr s 30 minutes de mise temp rature FB1000 2 MANUAL Page 4 7608177 Rev A 8 9 02 Mise en route S lectionnez un emplacement qui permette de laisser un espace de 7 8 cm derri re l alimentation lectriq
28. c un cordon d alimentation en CA 3 fils offrant une connexion la terre Le fil de terre de protection est n cessaire la s curit lors du fonctionnement N utilisez aucun autre cordon d alimentation en CA avec cet instrument Le FB1000 est une alimentation lectrique haute tension capable de g n rer des tensions et des intensit s dangereuses lors de son fonctionnement Soyez prudent lorsque vous travaillez proximit et avec les connexions lectriques de cet appareil V rifiez toujours les connecteurs lectriques les fils et les appareils associ s pour vous assurer qu ils ne sont ni us s ni endommag s avant de les utiliser avec cet appareil Veillez utiliser uniquement un appareil d lectrophor se qui corresponde aux valeurs nominales de tension et d intensit de l alimentation lectrique FB1000 La sortie de l alimentation lectrique FB1000 est pr vue uniquement pour une connexion un appareil d lectrophor se lectriquement isol Utilisez la uniquement avec un appareil d lectrophor se lectriquement isol muni d une isolation minimum de 1000 V Ne connectez aucune borne de sortie du FB1000 la terre Ceci pourrait affecter la protection de s curit fournie par l appareil ou endommager l appareil La sortie haute tension de l alimentation lectrique FB1000 met un certain temps d cliner lorsqu elle est d charg e ou l g rement charg e Attendez au minimum 60 seco
29. ci n Proceda con cuidado al trabajar cerca de este equipo y con sus conexiones el ctricas Siempre verifique que los conectores el ctricos alambres y aparatos asociados no presenten signos de desgaste o da o antes de usarlos con este equipo Aseg rese de utilizar solamente equipo para electroforesis de potencia adecuada para las capacidades de voltaje y corriente de la fuente de alimentaci n FB 1000 La salida de la fuente de alimentaci n FB 1000 est dise ada solamente para la conexi n con aparatos para electroforesis el ctricamente aislados Usese solamente con aparatos para electroforesis el ctricamente aislados que tengan un aislamiento m nimo de 1 000V No conecte ning n terminal de la salida del FB1000 a la conexi n de tierra Esto puede afectar la protecci n de seguridad proporcionada por el equipo o causarle da o La salida de alto voltaje de la fuente de alimentaci n FB 1000 tarda un poco para decaer cuando est descargada o ligeramente cargada Espere un m nimo de 60 segundos despu s de parar un proceso antes de tocar los cables de la fuente de alimentaci n Este equipo tiene una corriente de fuga a tierra de protecci n de 0 5 mA a 120 voltios de CA y de 1 mA a 230 voltios de CA Aunque es bastante menor que la limitaci n de 3 5 mA de los instrumentos de laboratorio algunas aplicaciones e instalaciones requieren una corriente de fuga menor que 0 5 mA Verifique los requerimientos espec ficos de su aplicaci n antes
30. ci n cambiar autom ticamente los modos de control controlando el par metro de l mite As el FB1000 protege sus celdas para electroforesis contra da o a causa de las condiciones de la alimentaci n La fuente de alimentaci n FB 1000 tambi n ofrece la capacidad de operaciones temporizadas y en voltios hora en todos los modos de control y permite completar autom ticamente el proceso en caso de fallo en la alimentaci n si se ha activado la funci n Caracter sticas 5 a 1000 voltios ajustable en incrementos de 1 voltio 1 a 500mA ajustable en incrementos de ImA 1 a 250 vatios ajustable en incrementos de 1 vatio 0 a 90C ajustable en incrementos de 1 grado C Conmutaci n autom tica del modo de control Proceso temporizado de 0 a 99 horas 59 minutos Proceso temporizado de 0 a 9999 voltios hora Reinicio autom tico si ocurre p rdida de alimentaci n de CA si se ha activado Pantalla LCD de cristal l quido grande Desembalaje de la fuente de alimentaci n Al desembalar la fuente de alimentaci n FB1000 aseg rese de haber recibido los siguientes elementos e La unidad FB1000 e El cable de alimentaci n de CA e Este manual Inspeccione el equipo y el material de embalaje para ver si presentan se ales de da o El da o a la caja de embarque puede indicar manipulaci n brusca lo que puede causar da o interno a la fuente de alimentaci n Si sospecha que se ha da ado la fuente de alimentaci n durante el transporte
31. d ex cution Run pour mettre sous tension la sortie de l alimentation lectrique La sortie de l alimentation lectrique cro t progressivement jusqu la valeur de consigne appropri e sans permettre qu un param tre de limite soit d pass Si un param tre de limite est atteint l alimentation lectrique change de mode de contr le et le param tre de limite devient la nouvelle valeur de consigne de contr le L cran du mode d ex cution affiche le param tre contr l en surbrillance et change automatiquement si une inversion de mode a eu lieu Pour arr ter une ex cution en cours appuyez sur la touche d ex cution Run sur la touche Stop ou sur la touche grise MARCHE ARRET L cran affiche STOP indiquant que la sortie n est plus aliment e et affiche les conditions juste avant l arr t Pour suspendre une ex cution en cours appuyez sur la touche Pause L cran affiche PAUSE indiquant que la sortie n est plus aliment e mais qu une reprise de l ex cution est possible Le fait d appuyer sur Run ou Pause reprend l ex cution partir du point pr c dent par exemple pour une ex cution dur e d termin e Seule une ex cution qui a t mise en pause peut tre red marr e Apr s avoir arr t une ex cution avec la touche Stop ou pour changer les param tres d une ex cution suspendue vous devez mettre hors tension les circuits logiques de commande et les remettre sous
32. dem FB1000 erscheint der Schritte Bildschirm auf dem die Parameter f r den ausgew hlten Schritt angezeigt werden au er wenn das Programm leer ist wobei das FB1000 automatisch den ersten Schritt wie folgt eingibt Verwenden Sie die auf der rechten Seite der Anzeige FB1000 2 MANUAL Page 8 7608177 Rev A 8 9 02 befindlichen Funktionstasten um auf die 9 m glichen Programme zuzugreifen Zum Ausf hren des Programms beginnend mit dem ausgew hlten Schritt dr cken Sie die Run Taste Ausf hrung Zum Bearbeiten eines Schrittes driicken Sie die Funktionstaste mit der Beschriftung EDIT Bearbeiten Auf dem FB1000 erscheint der Modusauswahlbildschirm Wahlen Sie unter Verwendung der entsprechenden Funktionstaste an der rechten Seite der Anzeige einen Dauerbetriebsmodus Um zwischen den Betriebsmodi Volt Strom Leistung sowie zeitgesteuert Voltstunden zu wechseln driicken Sie die Funktionstaste F1 Um einen Parameter zu andern dr cken Sie an der rechten Seite der Anzeige die Funktionstaste neben dem zu ndernden Parameter Auf dem FB1000 kann der neue Wert tiber die Zahlentastatur eingegeben werden Dr cken Sie die Funktionstaste mit der Beschriftung Enter um die neue Einstellung zu akzeptieren Zum L schen der eingegebenen Zahlen dr cken Sie Clear L schen Zum Abbrechen der Eingabe eines neuen Wertes driicken Sie Exit Beenden Das FB1000 akzeptiert keinen Parameter der au erhalb der zugelassenen Grenze liegt Dr cken Sie Clear
33. derecha de la pantalla v ase la descripci n del modo de programaci n en la secci n Programaci n En el modo manual el FB 1000 mantiene el valor prefijado constante cada vez que se inicia un proceso El par metro FB1000 2 MANUAL Page 5 7608177 Rev A 8 9 02 constante se guarda de forma independiente para cada modo voltaje corriente y potencia constantes Para cambiar el modo control presione la tecla Exit Salir En la pantalla resultante seleccione el nuevo par metro constante usando las teclas de funci n situadas a la derecha de la pantalla Despu s de seleccionar un modo de control y establecer los par metros de l mite y temporizaci n del proceso presione si lo desea la tecla Run Procesar para excitar la salida de la fuente de alimentaci n La salida de la fuente de alimentaci n aumentar hasta el valor prefijado apropiado sin permitir que se exceda ning n par metro de l mite Si se excediera alg n par metro de l mite la fuente de alimentaci n conmutar los modos de control de transici n convirtiendo al par metro de l mite en el nuevo valor de control prefijado La pantalla de modo de proceso mostrar resaltado el par metro controlado y cambiar autom ticamente si ha ocurrido una conmutaci n Para detener un proceso en ejecuci n presione la tecla Run Procesar la tecla Stop Parar o la tecla gris de Activar Desactivar La pantalla cambiar a STOP Parar indicando que la salida ya no est activada
34. die H chstgrenze des Netzteils bzw auf eine vom Benutzer eingestellte niedrigere Grenze Wenn eine nicht konstante Grenze erreicht wird schaltet das Netzteil automatisch auf einen anderen Betriebsmodus um wodurch der Grenzparameter geregelt wird Dadurch schiitzt das FB1000 Ihre Elektrophorese Zellen vor sch digender Uberspannung Das FB1000 Netzteils ist au erdem f r zeitgesteuerten und Voltstunden Betrieb in allen Betriebsmodi ausgestattet Bei einem Stromausfall kann somit das Verfahren abgeschlossen werden wenn diese Funktion vorher aktiviert wurde Funktionen 5 1000 V in 1 Volt Inkremten einstellbar 1 500 mA in Inkrementen von 1 mA einstellbar 1 250 W in Inkrementen von 1 W einstellbar 0 90 C in Inkrementen von 1 C einstellbar Automatisches Umschalten der Betriebsmodi 0 99 Stunden und 59 Minuten zeitgesteuerte Ausf hrung 0 9999 Voltstunden zeitgesteuerte Ausf hrung automatischer Neustart bei Stromausfall falls aktiviert GroBe LCD Anzeige Auspacken des Netzteils Stellen Sie beim Auspacken des FB1000 Netzteils sicher dass die folgenden Artikel im Lieferumfang enthalten sind e FB1000 Ger t e Netzkabel e Handbuch Untersuchen Sie Ihr Ger t und die Verpackung auf jegliche Anzeichen von Sch den Eine besch digte Verpackung weist oftmals auf unsachgem e Handhabung w hrend des Transports und eventuell auf einen dadurch entstandenen internen Ger teschaden hin Wenn Sie glauben dass das Netzteil w hrend des V
35. e 5 7608177 Rev A 8 9 02 Vorgabewert Der Dauerparameter wird f r jeden Modus Dauerspannung strom oder leistung unabh ngig gespeichert Zum ndern des Steuermodus driicken Sie die Exit Taste Beenden Auf dem darauf hin angezelgten Bildschirm w hlen Sie unter Verwendung der Funktionstasten an der rechten Seite der Anzeige den neuen Dauerparameter Nach dem Ausw hlen eines Steuermodus und dem Einstellen der Grenzwerte sowie der zeitgesteuerten Parameter falls erw nscht dr cken Sie auf die Run Taste Ausf hrung um den Netzteilausgang zu aktivieren Der Netzteilausgang steigt nun auf den entsprechenden Vorgabewert an ohne einen der Grenzparameter zu berschreiten Wenn einer der Granzparameter tiberschritten wird schaltet das Netzteil auf einen anderen Steuermodus um wobei der Grenzparameter zum neuen Steuervorgabewert wird Die Anzeige im Ausf hrungsmodus zeigt den Steuerwert hervorgehoben an und schaltet bei einer Uberschreitung automatisch um Dr cken Sie auf die Run Taste Ausf hrung die Stop Taste oder die graue ON OFF Taste Netzschalter um eine laufende Ausf hrung zu stoppen Es wird nun STOP angezeigt um anzuzeigen dass der Ausgang nicht mehr stromf hrend ist und um die Bedingungen direkt vor dem Stoppen anzuzeigen Zum kurzfristigen Anhalten einer Ausf hrung dr cken Sie die Pause Taste Es wird nun PAUSE angezeigt um anzuzeigen dass der Ausgang nicht mehr stromf hrend ist und die Ausf hrun
36. e conforme la Directive 73 23 CEE sur les basses tensions et aux normes de s curit IEC 1010 1 concernant le mat riel lectrique pour le contr le des mesures et l utilisation en laboratoire Pi ces de rechange Pour des pi ces de rechanges contactez Fisher Scientific Fisher Scientific 2000 Park Lane Pittsburgh PA 15275 USA Cordon d alimentation en CA FB CORD 3 Fusible T5A 250V FB FUSE 3 FB1000 2 MANUAL Page 12 7608177 Rev A 8 9 02 Fisher Biotech FB1000 Elektrophorese Netzteil Inhaltsverzeichnis Sicherheitstechnische Hinweise 2 Einf hrung 3 Auspacken des Netzteils 3 Technische Daten 4 Einstieg 5 Verwenden des Netzteils 5 Betrieb bei Dauerspannung 6 Betrieb bei Dauerstrom 6 Betrieb bei Dauerleistung 7 Zeitgesteuerter Betrieb 7 Voltstundenbetrieb 7 Automatischer Neustart bei Stromausfall 8 Programmierung 8 Reinigung 10 Fehlersuche und Fehlermeldung 11 FB1000 Garantieerkl rung 12 Kompatibilit t 12 Ersatzteile 12 FB1000 2 MANUAL Page 1 7608177 Rev A 8 9 02 Sicherheitstechnische Hinweise Vor dem Einrichten und dem Gebrauch des Ger tes sollten das Handbuch sorgf ltig gelesen und die Informationen verstanden werden Dieses Ger t wurde gem f der CSA1010 Sicherheitsrichtlinien fiir Laborger te entwickelt und gepr ft Dies gilt nur f r das FB1000 wenn es gem der Dokumentation in seinen vorgesehenen Anwendungen ausschlieBlich mit den von Fisher Biotech zugelassenen Elektrophorese Ger ten
37. eln driicken Sie die Funktionstaste F1 Um einen Parameter zu andern dr cken Sie an der rechten Seite der Anzeige die Funktionstaste neben dem zu ndernden Parameter Auf dem FB1000 kann der neue Wert ber die Zahlentastatur eingegeben werden Dr cken Sie die Funktionstaste mit der Beschriftung Enter um die neue Einstellung zu akzeptieren Zum L schen der eingegebenen Zahlen dr cken Sie Clear L schen Zum Abbrechen der Eingabe eines neuen Wertes driicken Sie Exit Beenden Das FB1000 akzeptiert keinen Stromvorgabewert au erhalb des zugelassenen Bereichs Dr cken Sie Clear um einen geeigneten Wert einzugeben Die Grenzparameter sind normalerweise auf den H chstwert des Netzteils eingestellt Das FB1000 akzeptiert keinen Grenzparameter der au erhalb des zul ssigen Bereichs liegt Au erdem berschreitet das FB1000 niemals die maximale Ausgangsleistung von 250 W Betrieb bei Dauerleistung Auf dem Modusauswahlbildschirm w hlen Sie unter Verwendung der entsprechenden Funktionstaste an der rechten Seite der Anzeige den Betrieb bei Dauerleistung Um auf diesen Auswahlbildschirm von einer Betriebsanzeige aus zuzugreifen dr cken Sie Exit Beenden oder Sie schalten die Steuerlogik durch Dr cken der grauen ON OFF Taste aus und dann wieder ein und w hlen dann den MANUELLEN MODUS Das FB1000 zeigt die zuletzt gespeicherten Werte f r den Dauerleistungsmodus an Um zwischen den Betriebsmodi Volt Strom Leistung sowie zeitgesteuert
38. ent agr de Fisher ne sera pas applicable par l acheteur FISHER REJETTE FORMELLEMENT TOUTES LES AUTRES GARANTIES EXPRESSES OU TACITES Y COMPRIS LA GARANTIE TACITE QUE LE PRODUIT EST PROPRE LA VENTE OU ADAPT UN USAGE PARTICULIER La seule responsabilit de Fisher et le recours exclusif de l acheteur pour toute revendication survenant suite l achat d un produit quelconque mentionn ci dessus le cas ch ant est la r paration le remplacement ou le remboursement comme d crit ci dessus En aucun cas 1 le co t du recours exclusif ne pourra d passer le prix d achat 2 Ficher ne sera responsable pour des dommages sp ciaux indirects ou exemplaires quelle que soit la mani re dont ils surviennent m me si Fisher a t avis de la possibilit de tels dommages Chaque article fourni par Fisher sera conforme aux sp cifications crites donn es dans ce manuel ou celles d un mod le am lior ult rieur Des modifications sont fr quemment apport es aux informations du manuel et seront incorpor es dans les ditions ult rieures Conformit En ce qui concerne les mod les FB1000 1 FB1000 2 EMC Cet appareil lorsqu il est utilis conform ment au manuel d instructions est conforme la Directive EMC 89 336 CEE et la Norme EMC EN61326 concernant le mat riel lectrique pour le contr le des mesures et l utilisation en laboratoire IEC Cet appareil a t con u et test pour tr
39. ente de alimentaci n 3 Especificaciones 4 Para empezar 5 Uso de la fuente de alimentaci n 5 Operaciones a voltaje constante 6 Operaciones a corriente constante 6 Operaciones a potencia constante 7 Operaciones temporizadas 7 Operaciones en voltios hora 7 Reinicio autom tico tras un fallo en la alimentaci n 7 Programaci n 8 Limpieza 10 Diagn stico e indicaciones de error 11 Declaraci n de garant a del FB1000 12 Conformidad 12 Piezas de repuesto 13 FB1000 2 MANUAL Page 1 7608177 Rev A 8 9 02 Consideraciones de seguridad Antes de intentar instalar o utilizar este instrumento lea y comprenda completamente este manual Este equipo ha sido dise ado y probado para ajustarse a las normas de seguridad CSA1010 seg n corresponda a instrumentos de laboratorio Esto se aplica solamente al FB1000 cuando se utiliza tal como se especifica en la documentaci n en las aplicaciones previstas y solamente con aparatos para electroforesis aprobados por Fisher Biotech El uso de cualquier otra manera podr a no proporcionar el mismo rendimiento o la protecci n de seguridad Este equipo viene con un cable de alimentaci n de CA de 3 conductores con conexi n a tierra La protecci n con conexi n a tierra es necesaria para la operaci n segura No use ning n otro cable de alimentaci n de CA con este instrumento El FB1000 es una fuente de alimentaci n de alto voltaje capaz de producir niveles peligrosos de voltaje y corriente durante su opera
40. eration of the FB1000 The power supply that you have purchased is the most productive and easy to use unit available anywhere This manual should answer any questions that might arise in operating your power supply however don t hesitate to call our Fisher Lab Equipment Technical Support Hotline at 1 800 943 2006 or 1 800 926 0505 if you need any assistance The FB1000 power supply is designed to provide constant voltage current or power in both Manual and Programmed modes of operation commonly used in electrophoresis applications One to four sets of electrophoresis cells can be connected in parallel and run simultaneously The FB1000 can deliver up to 250W of total output power When operating in any constant mode the power supply automatically limits the other parameters to either the power supply maximum or a lower limit if set by the user If any non constant limit is reached the power supply will automatically switch control modes controlling the limit parameter In this way the FB1000 protects your electrophoresis cells from damaging over power conditions The FB1000 power supply also provides for timed and volt hour operation in all control modes and allows an automatic completion in the event of a power loss if enabled Features 5 1000V adjustable in 1 volt steps 1 500mA adjustable in 1mA steps 1 250W adjustable in 1W steps 0 90C adjustable in 1degree C steps Automatic control mode crossover 0 99 hour 59 minute timed run
41. ersands besch digt wurde wenden Sie sich bitte an den Spediteur f r Anweisungen zum Einreichen eines Schadensformulars Wenn Artikel aus der obengenannten Liste fehlen wenden Sie sich bitte an Ihren H ndler FB1000 2 MANUAL Page 3 7608177 Rev A 8 9 02 Technische Daten Netzeingangsleistung 85 265 V AC 50 60 Hz max 350 VA Umfeldbedingungen Betriebstemperatur 0 40 C 0 bis 95 relative Luftfeuchtigkeit nicht kondensierend H henlage max 2000 m berspannungskategorie II IEC664 Verschmutzungsgrad 2 IEC664 Gleichstromausgangsleistung 5 1000 V DC max 250 W 1 500 mA max 250 W Klirrfaktor 1 Drift 1 nach 30 Minuten langem Warmlaufen FB1000 2 MANUAL Page 4 7608177 Rev A 8 9 02 Einstieg Wahlen Sie eine geeignete Stelle aus an der Sie das Netzteil aufstellen und die Regler auf dem Bedienfeld und die Zellenanschl sse bequem erreichen k nnen Zwischen der R ckwand des Instruments und der Wand bzw anderen Objekten sollte ein Freiraum von ca 75 mm freigelassen werden Blockieren Sie nicht die L ftungsbereiche am Geh use diese Bereiche befinden sich an der Unterseite des Ger tes vorne oder auf der R ckseite Schlie en Sie das Netzteil an den Netzstrom an Verwenden Sie dazu nur das im Lieferumfang enthaltene Netzkabel Schlie en Sie das Elektrophorese Ger t an das Netzteil an Achten Sie hierbei darauf dass der rote positive Leiter an der roten positiven Buchse und der schwarze negative Leiter an
42. es Nettoyage Avant de nettoyer l appareil veillez toujours couper l alimentation en CA l aide de l interrupteur qui se trouve au dos de l appareil puis d brancher le cordon d alimentation en CA L avant de l appareil est scell et peut tre essuy l aide d un chiffon imbib d une solution dilu e d un d tergent quelconque vitez les produits de nettoyage abrasifs tant donn qu ils peuvent d t riorer la surface des touches membrane tactile FB1000 2 MANUAL Page 10 7608177 Rev A 8 9 02 D pannage et indications d erreur Le FB1000 d tecte et rapporte plusieurs v nements et conditions qui sont consid r s comme des erreurs Le FB1000 arr te toute ex cution en cours et affiche ERROR XX o XX est l une des erreurs figurant dans la liste ci dessous Lorsque le FB1000 affiche une indication d erreur appuyez sur la touche grise de MARCHE ARR T pour effacer l erreur et revenir au mode de configuration ou appuyez sur la touche Run pour reprendre l ex cution apr s avoir corrig la cause de l erreur Notez qu une coupure de l alimentation en CA au cours d une ex cution est consid r e comme une condition d erreur Arr tez toujours une ex cution avant de couper l alimentation en CA du FB1000 XX Condition et rem de possible 00 Courant de charge minimum d tect La sortie n est pas connect e ou 20 l appareil d lectrophor se n e
43. es 9 programmes possibles Pour ex cuter le programme en commen ant par l tape 1 appuyez sur la touche d ex cution Run Pour modifier un programme y compris ajouter une premi re tape un programme vide appuyez sur la touche de fonction libell e EDIT Le FB1000 affichera l cran des tapes qui montre les param tres pour l tape s lectionn e sauf lorsque le programme est vide auquel cas le FB1000 commence automatiquement entrer la premi re tape comme suit Utilisez les touches de fonction droite de l cran pour vous d placer parmi les 9 tapes possibles Pour ex cuter le programme en commen ant par l tape s lectionn e appuyez sur la touche d ex cution Run Pour modifier une tape appuyez sur la touche de fonction libell e EDIT Le FB1000 affiche l cran de s lection de mode S lectionnez un mode de fonctionnement constant en appuyant sur la touche de fonction FB1000 2 MANUAL Page 8 7608177 Rev A 8 9 02 appropri e droite de l cran Pour alterner entre tension intensit puissance et dur e volts heures appuyez sur la touche de fonction F1 Pour changer un param tre appuyez sur la touche de fonction situ e droite de l cran en face du param tre que vous d sirez changer Le FB1000 permet d entrer une nouvelle valeur l aide des touches num riques du clavier Appuyez sur la touche de fonction libell e Enter pour valider le nouveau param tre Appuyez sur la
44. esde el paso 1 presione la tecla Run Procesar Para editar un programa incluyendo la adici n del primer paso a un programa vacio presione la tecla de funci n EDIT Edici n El FB1000 presentar la pantalla de pasos donde se muestran los par metros del paso seleccionado excepto cuando el programa est vacio y el FB1000 arranca autom ticamente introduciendo el primer paso como se indica a continuaci n Use las teclas de funci n situadas a la derecha de la pantalla para desplazarse por los 9 pasos posibles Para ejecutar el programa empezando desde el paso seleccionado presione la tecla Run Procesar Para editar un paso presione la tecla de funci n EDIT El FB1000 presenta la pantalla de selecci n de modo Seleccione un modo constante de operaci n presionando la tecla de funci n apropiada situada a la derecha de la pantalla Para cambiar entre voltios corriente potencia y tiempo voltios hora presione la tecla de funci n F1 Para cambiar un par metro presione la tecla de funci n situada a la derecha de la pantalla pr xima al par metro que desea cambiar El FB1000 permitir la entrada de un valor nuevo usando las teclas num ricas del teclado Presione la tecla de funci n con el nombre Enter Introducir para completar la nueva configuraci n Presione Clear Despejar para borrar la secuencia de teclas previas Presione Exit Salir para cancelar la entrada de un valor nuevo El FB1000 no aceptar ning n par metro fuera del
45. exclusive remedy for any claim arising out of the purchase of any product listed above is repair replacement or credit as described above where applicable In no event 1 shall the cost of the exclusive remedy exceed the purchase price 2 shall Fisher be liable for any special indirect incidental consequential or exemplary damages howsoever arising even 1f Fisher has been advised of the possibility of such damages Each article that Fisher furnishes will conform to the written specifications given in this manual or those of a further improved model Changes are made often to the information in the manual and will be incorporated into future editions Compliance Pertaining to models FB1000 1 FB1000 2 EMC This equipment when used in accordance with the instruction manual conforms to EMC Directive 89 336 EEC and EMC Standard EN61326 as applicable to electrical equipment for measurement control and laboratory use IEC This equipment has been designed and tested to conform to Low Voltage Directive 73 23 EEC and IEC 1010 1 Safety Standards as applicable to electrical equipment for measurement control and laboratory use Replacement Parts For replacement parts contact Fisher Scientific at Fisher Scientific 2000 Park Lane Pittsburgh PA 15275 1 800 766 7000 Technical Support 1 800 943 2006 or 1 800 926 0505 AC line cord FB CORD 3 Fuse T5A 250V FB FUSE 3 Accessories Adapter for Cells FBAD 1 Under Counter Bracket FBUB30
46. g wieder aufgenommen werden kann Wenn Sie noch einmal auf die Run oder Pause dr cken wird mit der Ausf hrung vom vorherigen Punkt z B f r eine zeitgesteuerte Ausf hrung fortgefahren Nur eine durch Pause angehaltene Ausf hrung kann fortgesetzt werden Nach dem Stoppen einer Ausf hrung oder zum ndern der Parameter einer angehaltenen Pause Ausf hrung muss die Steuerlogik durch Dr cken der grauen ON OFF Taste aus und dann wieder eingeschaltet werden W hrend einer Ausf hrung werden auf der Anzeige die tats chlichen Werte f r Spannung Strom Leistung und Temperatur angezeigt Der Zeitparameter zeigt die abgelaufene Zeit f r eine nicht zeitgesteuerte Ausf hrung und die verbleibende Zeit f r eine zeitgesteuerte Ausf hrung an Der Voltstundenwert zeigt die abgelaufenen Voltstunden f r die Ausf hrung an Betrieb bei Dauerspannung Auf dem Modusauswahlbildschirm w hlen Sie unter Verwendung der entsprechenden Funktionstaste an der rechten Seite der Anzeige die Dauerspannung Um auf diesen Auswahlbildschirm von einer Betriebsanzeige aus zuzugreifen dr cken Sie Exit Beenden oder Sie schalten die Steuerlogik durch Dr cken der grauen ON OFF Taste aus und dann wieder ein und w hlen dann den MANUELLEN MODUS Das FB1000 zeigt die zuletzt gespeicherten Werte f r den Dauerspannungsmodus an Um zwischen den Betriebsmodi Volt Strom Leistung sowie zeitgesteuert Voltstunden zu wechseln dr cken Sie die Funktionstaste Fl Um einen
47. he Exit pour annuler la saisie d une nouvelle valeur Le FB1000 n accepte pas une valeur de consigne de tension en dehors de la gamme autoris e Appuyez sur la touche Clear pour entrer une valeur appropri e Les param tres de limite sont normalement r gl s sur les valeurs maximales de l alimentation lectrique Le FB1000 n accepte pas un param tre de limite en dehors de la gamme autoris e De plus le FB1000 ne d passera jamais la sp cification de puissance de sortie maximale de 250 W Op rations intensit constante partir de l cran de s lection de mode s lectionnez un fonctionnement intensit constante en appuyant sur la touche de fonction appropri e droite de l cran Pour passer d un cran op rationnel l cran de s lection appuyez sur Exit ou teignez et rallumez les circuits logiques de commande en appuyant sur la touche grise MARCHE ARR T et en s lectionnant MANUEL Le FB1000 affiche les derni res valeurs sauvegard es pour le mode d intensit constante Pour alterner entre tension intensit puissance et dur e volts heures appuyez sur la touche de fonction FB1000 2 MANUAL Page 6 7608177 Rev A 8 9 02 F1 Pour changer un param tre appuyez sur la touche de fonction situ e a droite de l cran en face du param tre que vous d sirez changer Le FB1000 permet d entrer une nouvelle valeur l aide des touches num riques du clavier Appuyez sur la touche de fonction libel
48. ific Company Fisher garantiert dem Erstk ufer die angegebene Garantie dass das FB1000 frei von Material und Verarbeitungsfehlern ist W hrend dieser Zeit verpflichtet sich Fisher das Produkt nach eigenem Ermessen zu reparieren zu ersetzen oder eine Gutschrift f r dieses auszugeben wenn die Firma sofort benachrichtigt und die Handhabung des Ger tes gem der Anleitung erfolgte F r FB1000 Netzteile betr gt diese Garantiezeit 48 Monate ab Herstellungsdatum Falls nicht anderweitig vereinbart beschr nkt sich die Haftung unter dieser Garantie auf das Land in dem das Produkt verkauft wurde Kein Stellvertreter Mitarbeiter oder Vertreter von Fisher ist berechtigt Fisher f r m ndliche Zusagen und Gew hrleistungen in Zusammenhang mit einem verkauftem Ger t haftbar zu machen Alle m ndlichen Zusagen und Gew hrleistungen die vor dem Kauf eines Produktes gemacht und nicht schriftlich dargelegt und von einem berechtigten Mitarbeiter von Fisher unterschrieben wurden k nnen vom K ufer nicht geltend gemacht werden FISHER GIBT KEINE GEW HR WEDER AUSDR CKLICH NOCH STILLSCHWEIGEND IN BEZUG AUF DAS PRODUKT AUCH STILLSCHWEIGENDE ZUSAGEN IN BEZUG AUF DIE MARKTG NGIGKEIT ODER EIGNUNG F R EINEN BESTIMMTEN ZWECK SIND AUSGESCHLOSSEN Die Haftung unter dieser Garantie von FISHER und der Rechtsbehelf des K ufers beschr nkt sich ausschlie lich auf die Reparatur den Ersatz oder die Ausgabe einer Gutschrift f r das betroffene Produkt In
49. ion by pressing the appropriate function key located to the right of the display To get to the selection screen from an operating screen press Exit or cycle the control logic off and then back on by pressing the gray ON OFF key and selecting MANUAL The FB1000 will display the last saved values for constant current mode To switch between volts current power and time volt hours press function key F1 To change a parameter press the function key located to the right of the display next to the parameter you wish to change The FB1000 will allow a new value to be entered using the keypad numeric keys Press the function key labeled Enter to complete the new setting Press Clear to erase previous keystrokes Press Exit to cancel entering a new value The FB1000 will not accept a current setpoint outside of the allowed range Press Clear to re enter an appropriate value The limit parameters are normally set to the power supply maximum values The FB1000 will not accept a limit parameter outside of the allowed range In addition the FB1000 will never exceed the maximum power output specification of 250W Constant Power Operations From the mode selection screen select constant power operation by pressing the appropriate function key located to the right of the display To get to the selection screen from an operating screen press Exit or cycle the control logic off and then back on by pressing the gray ON OFF FB1000 2 MANUAL Page 6 7608177 Rev
50. keinem Fall 1 darf die R ckerstattung f r den ausschlie lichen Rechtsbehelf den tats chlichen Kaufpreis berschreiten 2 haftet Fisher f r indirekte Sonder Neben oder Folge oder sonstige Sch den auch wenn Fisher ber die M glichkeit solcher Sch den informiert wurde Jeder Artikel den Fisher zur Verf gung stellt entspricht den schriftlichen Spezifikationen in diesem Handbuch oder denen von weiterentwickelten Modellen nderung der Daten vorbehalten Solche nderungen werden in die neueren Versionen implementiert Kompatibilit t Betrifft Modelle FB1000 1 FB1000 2 EMV Bei Verwendung gem der Gebrauchsanweisung erf llt dieses Ger t die Anforderungen der EMV Richtlinien 89 336 EEC und des EMV Standards EN61325 f r elektrische Ger te zur Messungskontrolle und f r Laborzwecke IEC Dieses Ger t wurde entsprechend konzipiert und gepr ft und erf llt die Anforderungen der Niederspannungsrichtlinien 73 23 EEC und den Sicherheitsstandards IEC 1010 1 f r elektrische Ger te zur Messungskontrolle und f r Laborzwecke Ersatzteile Wenden Sie sich f r Ersatzeile an Fisher Scientific unter folgender Adresse Fisher Scientific 2000 Park Lane Pittsburgh PA 15275 USA Netzkabel FB CORD 3 Sicherung T5A 250 V FB FUSE 3 FB1000 2 MANUAL Page 12 7608177 Rev A 8 9 02 Fuente de Alimentaci n para Electroforesis Fisher Biotech FB1000 Contenido Consideraciones de seguridad 2 Introducci n 3 Desembalaje de la fu
51. l e Enter pour valider le nouveau param tre Appuyez sur la touche Clear pour effacer les frappes pr c dentes Appuyez sur la touche Exit pour annuler la saisie d une nouvelle valeur Le FB1000 n accepte pas une valeur de consigne d intensit en dehors de la gamme autoris e Appuyez sur la touche Clear pour entrer une valeur appropri e Les param tres de limite sont normalement r gl s sur les valeurs maximales de l alimentation lectrique Le FB1000 n accepte pas un param tre de limite en dehors de la gamme autoris e De plus le FB1000 ne d passera jamais la sp cification de puissance de sortie maximale de 250 W Op rations a puissance constante partir de l cran de s lection de mode s lectionnez un fonctionnement puissance constante en appuyant sur la touche de fonction appropri e droite de l cran Pour passer d un cran op rationnel l cran de s lection appuyez sur Exit ou teignez et rallumez les circuits logiques de commande en appuyant sur la touche grise MARCHE ARR T et en s lectionnant MANUEL Le FB1000 affiche les derni res valeurs sauvegard es pour le mode de puissance constante Pour alterner entre tension intensit puissance et dur e volts heures appuyez sur la touche de fonction F1 Pour changer un param tre appuyez sur la touche de fonction situ e droite de l cran en face du param tre que vous d sirez changer Le FB1000 permet d entrer une nouvelle valeu
52. le to enter an amount of volt hours for the power supply to provide power after which 1t will automatically shut off Volt hours is the integration of voltage over time Use volt hour control to provide consistency between runs Set up a constant mode setpoint and limits as described above Enter a volt hour duration of 0 9999 volt hours A volt hour duration of zero effectively disables volt hour run mode During a run the volt hour value displays the accumulated volt hour value for the run Automatic Power fail Restart Automatic power fail restart capability allows a timed or volt hour run which is interrupted by loss of AC power to be restarted automatically so that the total time volt hour programmed for the run will be met NOTE Loss of AC power includes switching off the unit using the power switch located at the rear of the unit When performing timed or volt hour runs with power fail restart enabled always use the front panel controls to stop a run in progress To enable power fail restart press the top function key when in the mode selection screen MANUAL or PROGRAM The state of power fail restart will toggle from off to on or on to off with each keypress When AC power is restored during a run in which power fail restart is enabled the display will show POWER FAIL RESTART for approximately 10 seconds indicating power fail restart pending During this time the output is not energized to allow safely stopping the run by pre
53. leibende Zeit der Ausf hrung an Bei einer nicht zeitgesteuerten Ausf hrung zeigt der Zeitparameter die abgelaufene Zeit w hrend der Ausf hrung an Voltstundenbetrieb Am Netzteil kann eine bestimmte Anzahl von Voltstunden eingestellt werden Nach Ablauf dieser Zeit schaltet sich das Ger t automatisch aus Voltstunden ist die Integration von Spannung ber einen bestimmten Zeitraum Verwenden Sie die Voltstundensteuerung um Einheitlichkeit zwischen den Ausf hrungen zu gew hrleisten FB1000 2 MANUAL Page 7 7608177 Rev A 8 9 02 Richten Sie einen Dauermodus Vorgabewert und Grenzparameter wie oben beschrieben ein Geben Sie eine Voltstundenzeit von O 9999 Stunden ein Wenn Sie die Voltstundenzeit auf Null stellen wird der Voltstunden Ausf hrungsmodus automatisch deaktiviert W hrend einer Ausf hrung zeigt der Voltstundenwert die abgelaufenen Voltstunden der Ausf hrung an Automatischer Neustart bei Stromausfall Durch den automatischen Neustart bei Stromausfall kann eine zeitgesteuerte oder Voltstunden Ausf hrung nach einem Stromausfall automatisch neu gestartet werden sodass die programmierte Gesamtzeit Voltstunden f r die Ausf hrung trotzdem eingehalten werden kann HINWEIS Bei einem Stromausfall wird auch der auf der R ckseite befindliche Netzschalter ausgeschaltet Verwenden Sie stets die Regler auf dem Bedienfeld zum Stoppen einer Ausf hrung wenn Sie eine zeitgesteuerte Voltstunden Ausf hrung bei der der automatische
54. lquier soluci n de detergente suave Evite los limpiadores o agentes fuertes que puedan deteriorar la superficie de las teclas de membrana t ctil FB1000 2 MANUAL Page 10 7608177 Rev A 8 9 02 Diagn stico e indicaciones de error El FB1000 detecta y reporta varios eventos y condiciones que se consideran errores El FB1000 detendr cualquier proceso en ejecuci n y mostrar ERROR XX donde XX es uno de los errores indicados a continuaci n Cuando el FB1000 muestra una indicaci n de error presione la tecla gris de Activar Desactivar para despejar el error y regresar al modo de configuraci n o presione la tecla Run Procesar para reanudar el proceso despu s de corregir la causa del error Observe que la p rdida del suministro de CA durante un proceso se considera una condici n de error Siempre detenga el proceso antes de desconectar la alimentaci n de CA al FB1000 XX Condici n y posible soluci n 00 Se ha detectado corriente de carga m nima La salida no est conectada o 20 el aparato de electroforesis no se ha instalado correctamente Revise la instalaci n y las conexiones 01 Se ha excedido la corriente de carga m xima La salida est cortocircuitada 21 o el aparato de electroforesis no se ha instalado correctamente Revise la instalaci n y las conexiones 02 Cambio grande en la corriente de carga El FB1000 ha detectado un cambio grande en la corriente de carga Revise la instalaci n y las co
55. n when working around and with the electrical connections of this equipment Always check electrical connectors wires and associated apparatus for any signs of wear or damage before using with this equipment Be sure to use only electrophoresis equipment that is suitably rated for the voltage and current capabilities of the FB 1000 power supply The output of the FB1000 power supply is intended for connection to electrically isolated electrophoresis apparatus only Use only with electrically isolated electrophoresis apparatus with minimum isolation of 1000V Do not connect any terminal of the FB1000 output to earth ground This may impair the safety protection provided by the equipment or cause equipment damage The high voltage output of the FB1000 power supply takes some amount of time to decay when unloaded or lightly loaded Wait a minimum of 60 seconds after stopping a run before touching the power supply leads This equipment has a protective ground leakage current of 0 5mA at 120VAC and 1mA at 230VAC While significantly below the 3 5mA limitation for laboratory instrumentation some applications and locations require a leakage current below 0 5mA Check the specific requirements of your application before using this equipment This equipment is for indoor use only FB1000 2 MANUAL Page 2 7608177 Rev A 8 9 02 Introduction Thank you for selecting a Fisher Scientific FB1000 Electrophoresis power supply This manual describes the op
56. ndes apr s l arr t d une ex cution avant de toucher les fils de l alimentation lectrique Cet appareil a un courant de fuite la terre de 0 5 mA 120 V CA et 1 mA 230 V CA Bien que cela soit nettement inf rieur la limite de 3 5 mA applicable aux instruments de laboratoire certaines applications et certains endroits exigent un courant de fuite inf rieur 0 5 mA V rifiez les besoins sp cifiques de votre application avant d utiliser cet appareil Cet appareil ne doit pas tre utilis l ext rieur FB1000 2 MANUAL Page 2 7608177 Rev A 8 9 02 Introduction Merci d avoir choisi une alimentation lectrique pour lectrophor se Fisher Scientific FB1000 Ce manuel d crit le fonctionnement du FB1000 L alimentation lectrique que vous avez achet e est le dispositif le plus productif et le plus facile a utiliser actuellement sur le march Ce manuel devrait r pondre toutes les questions qui peuvent survenir lors du fonctionnement de votre alimentation lectrique Cependant n h sitez pas appeler notre ligne directe d assistance technique pour les instruments de laboratoire Fisher au 1 800 943 2006 ou au 1 800 926 0505 si vous avez besoin d assistance L alimentation lectrique FB1000 est con ue pour fournir une tension une intensit ou une puissance constante dans les modes de fonctionnement Manuel et Programm couramment utilis s dans les applications d lectrophor se Un quatre
57. nexiones 04 P rdida de alimentaci n de CA la funci n de fallo en la alimentaci n est desactivada y no se ha completado el proceso El FB1000 ha detectado una p rdida de alimentaci n de CA no se complet el proceso debido a que no se hab a activado la funci n de fallo en la alimentaci n 05 P rdida de alimentaci n de CA proceso no temporizado El FB1000 ha detectado una p rdida de alimentaci n de CA 06 99 El FB1000 ha detectado una condici n de error interno Contacte al soporte t cnico para recibir instrucciones Antes de realizar servicio a la unidad siempre cerci rese de desconectar la alimentaci n de CA usando el interruptor de la parte posterior de la unidad y a continuaci n desconectando el cable de la l nea de CA El suministro de energ a FB1000 no requiere mantenimiento peri dico y debe proporcionar muchos a os de funcionamiento sin problemas Si tuviera que sustituir los fusibles proceda de la manera siguiente Sustituci n de un fusible CUIDADO El FB1000 utiliza protecci n con fusibles en neutro de doble polo Desconecte la alimentaci n de CA utilizando el interruptor de la parte posterior de la unidad y a continuaci n desconecte el cable de la l nea de CA Quite el portafusibles usando un peque o destornillador de pala Siempre reemplace los dos fusibles con los fusibles de recambio correctos fusible de 5A 250V 5x20mm tipo T TSA 250V N mero de cat logo de Fisher FB
58. nigungsmittel getr nkten Tuch abgewischt werden Verwenden Sie keine scharfen Reinigungsmittel die die Oberfl che der taktilen Membranentasten besch digen k nnten FB1000 2 MANUAL Page 10 7608177 Rev A 8 9 02 Fehlersuche und Fehlermeldung Das FB 1000 registriert und meldet mehrere Ereignisse und Zust nde die als Fehler bezeichnet werden Das FB1000 stoppt die laufende Ausf hrung und zeigt ERROR XX an wobei XX einer der unten aufgef hrten Fehler ist Wenn das FB1000 eine Fehlermeldung anzeigt dr cken Sie den grauen Netzschalter um den Fehler zu l schen und zum Einrichtungsmodus zur ckzukehren Sie k nnen auch die Run Taste Ausf hrung dr cken um mit der Ausf hrung nachdem der Fehler behoben wurde fortzufahren Wenn w hrend einer Ausf hrung der Netzstrom ausf llt wird dies ebenfalls als Fehlerzustand eingestuft Stoppen Sie immer erst die Ausf hrung bevor Sie das FB1000 ausschalten XX Zustand Fehler und m gliche L sung 00 Mindestladestrom registriert Der Ausgang ist nicht angeschlossen oder das Elektrophorese Ger t ist nicht ordnungsgem eingerichtet berpr fen Sie 20 die Einrichtung und die Anschl sse des Ger tes 01 Maximaler Laststrom berschritten Der Ausgang hat einen Kurzschluss oder das Elektrophorese Ger t ist nicht ordnungsgem eingerichtet berpr fen 21 Sie die Einrichtung und die Anschl sse des Ger tes Stufenlaststrom Ver nderung Das FB1000 hat eine starke Ver
59. onstante Para cambiar entre voltios corriente potencia y tiempo voltios hora presione la tecla de funci n F1 Para cambiar un par metro presione la tecla de funci n situada a la derecha de la pantalla pr xima al par metro que desea cambiar El FB1000 permitir la entrada de un valor nuevo usando las teclas num ricas del teclado Presione la tecla de funci n con el nombre Enter Introducir para completar la nueva configuraci n Presione Clear Despejar para borrar la secuencia de teclas previas Presione Exit Salir para cancelar la entrada de un valor nuevo El FB1000 no aceptar un valor prefijado de voltaje fuera del intervalo permitido Presione Clear Despejar para reingresar un valor apropiado Los par metros de l mite normalmente se establecen a los valores m ximos de la fuente de alimentaci n El FB1000 no aceptar un par metro de l mite fuera del intervalo permitido Adem s el FB1000 nunca exceder la especificaci n de potencia de salida m xima de 250 vatios Operaciones a corriente constante En la pantalla de selecci n de modos elija operaci n a corriente constante presionando la tecla de funci n apropiada situada a la derecha de la pantalla Para ir a la pantalla de selecci n desde una pantalla de operaci n presione Exit Salir o primero desactive y luego active la l gica de control presionando la tecla gris de Activar Desactivar y seleccionando MANUAL El FB1000 mostrar los ltimos valores guardados
60. ps coul depuis le d but de l ex cution Op rations en volts heures Il est possible d entrer une valeur de volts heures pour quantifier le courant que fournira l alimentation lectrique apr s quoi elle s teindra automatiquement Les volts heures repr sentent l int gration de la tension au cours du temps Utilisez le contr le des volts heures pour assurer l uniformit entre les ex cutions Fixez une valeur de consigne et des limites pour un mode constant de la mani re d crite ci dessus Entrez une dur e en volts heures comprise entre 0 et 9999 volts heures Une dur e en volts heures de z ro a pour effet de d sactiver le mode d ex cution en volts heures FB1000 2 MANUAL Page 7 7608177 Rev A 8 9 02 Au cours d une ex cution la valeur de volts heures affiche les volts heures accumul s pour l ex cution Red marrage automatique en cas de coupure de courant La capacit de red marrage automatique en cas de coupure de courant permet qu une ex cution dur e d termin e ou en volts heures qui est interrompue par une coupure de l alimentation en CA red marre automatiquement de mani re ce que la dur e totale ou le nombre de volts heures programm pour l ex cution soit respect REMARQUE Une coupure de l alimentation en CA comprend une mise hors tension de l appareil l aide de l interrupteur de mise sous tension qui est situ au dos de l appareil Lorsque vous effectuez des e
61. ptor de alimentaci n ubicado en la parte posterior de la unidad A ejecutar procesos temporizados o de voltios hora teniendo activada la funci n de reinicio tras un fallo en la alimentaci n siempre use los controles del panel delantero para detener un proceso en ejecuci n FB1000 2 MANUAL Page 7 7608177 Rev A 8 9 02 Para activar el reinicio autom tico tras un fallo en la alimentaci n presione la tecla de funci n superior cuando se encuentre en la pantalla de modo de selecci n MANUAL O PROGRAM El estado del reinicio tras un fallo en la alimentaci n conmutar de apagado a encendido o viceversa cada vez que se presione una tecla Cuando se restablezca la alimentaci n de CA durante un proceso en el que se ha activado la funci n de reinicio tras un fallo en la alimentaci n la pantalla mostrar POWER FAIL RESTART Reinicio tras un fallo en la alimentaci n durante aproximadamente 10 segundos indicando que est pendiente un reinicio Durante este tiempo la salida de energ a no est activada para permitir detener el proceso de manera segura presionando Run Despu s de completar la espera del reinicio pendiente tras un fallo en la alimentaci n la salida de la fuente de alimentaci n subir al valor prefijado y el proceso continuar cont ndose desde ese punto Durante la completaci n de un proceso puede ocurrir cualquier n mero de interrupciones de alimentaci n Si ocurriera un reinicio tras un fallo en la alimentaci n d
62. r l aide des touches num riques du clavier Appuyez sur la touche de fonction libell e Enter pour valider le nouveau param tre Appuyez sur la touche Clear pour effacer les frappes pr c dentes Appuyez sur la touche Exit pour annuler la saisie d une nouvelle valeur Le FB1000 n accepte pas une valeur de consigne de puissance en dehors de la gamme autoris e Appuyez sur la touche Clear pour entrer une valeur appropri e Les param tres de limite sont normalement r gl s sur les valeurs maximales de l alimentation lectrique Le FB1000 n accepte pas un param tre de limite en dehors de la gamme autoris e De plus le FB1000 ne d passera jamais la sp cification de puissance de sortie maximale de 250 W Op rations dur e d termin e Il est possible d entrer une dur e pendant laquelle l alimentation lectrique fournira du courant apr s quoi elle s teindra automatiquement Utilisez cette fonction pour les ex cutions dur e d termin e Fixez une valeur de consigne et des limites pour un mode constant de la mani re d crite ci dessus Entrez une dur e comprise entre 0 et 99 heures 59 minutes Une dur e de z ro a pour effet de d sactiver le mode de dur e d termin e Lorsque vous effectuez une ex cution dur e d termin e le param tre de temps affiche le temps restant dans l ex cution Lorsque vous effectuez une ex cution sans dur e d termin e le param tre de temps affiche le tem
63. r Sie die Netzteilleiter ber hren Dieses Ger t bietet einen Erdschluss Leckstrom von 0 5 mA bei 120 V AC bzw 1 mA bei 230 V AC Obwohl dieser Wert deutlich unter der zugelassenen Grenze von 3 5 mA f r Laborger te liegt erfordern manche Anwendungen und Standorte einen Leckstrom unter 0 5 mA Pr fen Sie vor der Anwendung dieses Ger tes die spezifischen Anforderungen f r Ihre Anwendung Diese Ger t darf nicht im Freien verwendet werden FB1000 2 MANUAL Page 2 7608177 Rev A 8 9 02 Einf hrung Vielen Dank f r den Kauf eines FB 1000 Elektrophorese Netzteils von Fisher Scientific In diesem Handbuch wird der Betrieb des FB1000 beschrieben Das von Ihnen erworbene Netzteil ist das produktivste Ger t mit einfacher Handhabung auf dem Markt In diesem Handbuch werden nahezu alle Fragen zum Betrieb des Netzteils beantwortet Wenn Sie jedoch weitere Fragen haben wenden Sie sich bitte an die Fisher Lab Equipment Technical Support Hotline unter dieser Nummer 1 800 943 2006 oder 412 490 6260 Das FB1000 Netzteil ist f r Dauerspannungs Dauerstrom oder Dauerleistungsausgabe sowohl im MANUELLEN als auch im PROGRAMM Modus f r Ger te die bei Elektrophorese Anwendungen verwendet werden bestimmt Bis zu vier Elektrophorese Zellens tze k nnen parallel angeschlossen und gleichzeitig betrieben werden Das FB1000 kann bis 250 W Gesamtleistung abgeben Beim Betrieb in einem der Dauermodi beschrankt das Netzteil die anderen Parameter automatisch auf
64. ratus to the power supply making sure to match the red positive lead to the red positive jack and the black negative lead to the black negative jack Similarly connect a second or more electrophoresis apparatus to the power supply if you plan to run more than one in parallel Attach a temperature probe to the FB1000 rear located connector and the electrophoresis apparatus if you intend to perform temperature monitoring for a run Power the unit on using the AC power switch located at the rear of the unit next to the AC line cord entry Function keys black negative jacks gt lt Clear key black negative jacks Run o e red positive jacks Run key Stop key red positive jacks Pause key gray ON OFF key Figure 1 Front Panel Controls Using the Power Supply Press the dark gray key on the front of the unit to enable disable the control logic The LCD display will illuminate and allow selection of MANUAL or PROGRAM mode of operation as well as enable disable automatic power fail restart Toggle automatic power fail restart by pressing the topmost function key to the right of the display Select MANUAL or PROGRAM mode using the function keys to the right of the display see Programming section for programming mode description In manual mode the FB1000 preserves the constant setpoint each time you start a run The constant parameter is saved independently for each mode constant voltage current and power To change the control mode press the E
65. ribi anteriormente cuando sea aplicable En ning n caso 1 podr el costo del remedio exclusivo ser mayor que el precio de compra 2 ser Fisher responsable de cualquier da o especial indirecto incidental emergente o ejemplar como quiera que surja incluso si se le hubiera advertido a Fisher de la posibilidad de tales da os Cada art culo que proporcione Fisher cumplir con las especificaciones escritas indicadas en este manual o aquellas de un modelo mejorado nuevo A menudo se realizan cambios a la informaci n contenida en el manual y stos se incorporar n en las ediciones futuras Conformidad Conformidad EMC Compatibilidad electromagn tica Pertinente a los modelos FB200 1 FB200 2 Cuando este equipo se utiliza observando lo indicado en el manual de instrucciones cumple con la Directiva EMC 89 336 EEC y la Norma EMC EN61326 seg n corresponda a equipos el ctricos para control de medidas y uso en laboratorio Conformidad con la IEC International Electrotechnical Commission Pertinente a los modelos FB 1000 1 FB1000 2 Este equipo ha sido dise ado y probado para cumplir la Directiva sobre Bajo Voltaje 72 73 EEC y las Normas de Seguridad IEC 1010 1 seg n corresponda a equipos el ctricos para control de medidas y uso en laboratorio FB1000 2 MANUAL Page 12 7608177 Rev A 8 9 02 Piezas de repuesto Para obtener piezas de repuesto contacte a Fisher Scientific en la siguiente direcci n Fisher Scientific 2
66. rn und besonders wichtig mit einer Zeit und oder Voltstundeneinstellung Beim Ausf hren eines Programmschritts f hrt das FB1000 automatisch den n chsten Programmschritt falls vorhanden aus nachdem eine Zeit oder Voltstundengrenze erreicht wurde Nachdem alle Programmschritte in einem Programm ausgef hrt wurden schaltet sich der FB1000 aus Jede Steuermodussequenz und alle zeitgesteuerten Voltstundenschritte k nnen in ein Programm aufgenommen werden Beachten Sie bitte dass in einem Programmschritt eine Null f r die Zeit und Voltstundenparameter enthalten sein kann wodurch das FB1000 in diesem Fall diesen Vorgabewert auf unbegrenzte Zeit beibeh lt genauso als ob die Einstellung vom MANUELLEN MODUS ausgef hrt wurde Um von der Betriebsanzeige auf den Programmiermodus zuzugreifen schalten Sie die Steuerlogik durch Dr cken der grauen ON OFF Taste aus und dann wieder ein und w hlen dann den PROGRAMM MODUS Das FB1000 zeigt nun den Programmbildschirm an auf dem die Anzahl der Schritte im gew nschten Programm enthalten sind Verwenden Sie die auf der rechten Seite der Anzeige befindlichen Funktionstasten um auf die 9 m glichen Programme zuzugreifen Zum Ausf hren des Programms beginnend mit Schritt 1 dr cken Sie die Run Taste Ausf hrung Zum Bearbeiten eines Programms einschlie lich dem Hinzuf gen eines ersten Schrittes zu einem leeren Programm dr cken Sie die Funktionstaste mit der Beschriftung EDIT Bearbeiten Auf
67. s the gray ON OFF key to clear the error and return to setup mode or press the Run key to resume the run after correcting the cause of the error Note that loss of AC power during a run is considered an error condition Always stop a run before turning off AC power to the FB1000 XX Condition and possible remedy 00 Minimum load current detected The output is not connected or the 20 electrophoresis apparatus is not set up properly Check your setup and connections 01 Maximum load current exceeded The output is short circuit or the 21 electrophoresis apparatus is not set up properly Check your setup and connections 02 Step load current change The FB1000 has detected a large change in load current Check your setup and connections 04 Loss of AC power automatic recovery from power fail disabled run not completed The FB1000 detected loss of AC power and didn t complete run 05 Loss of AC power run not timed The FB1000 detected loss of AC power 06 99 The FB1000 detected an internal error condition Contact technical support for instructions Before servicing the unit be sure to always turn off AC power using the switch at the rear of the unit and then disconnecting the AC line cord The FB1000 power supply requires no periodic servicing and should provide years of trouble free operation Should you need to replace the fuses proceed as follows Replacing a fuse CAUTION The FB 1000 uses double pole neu
68. ssing Run After the power fail restart pending delay is completed the power supply output will ramp up to the setpoint value and the run will continue from that point Any number of power interruptions can occur during the completion of a single run If a power fail restart occurs during the running of a program the FB1000 will complete the interrupted step and then advance to the next step in the program Programming The FB 1000 can store 9 programs each containing 9 steps A program step is a constant voltage current or power setpoint with any associated limit parameters and most importantly a time FB1000 2 MANUAL Page 7 7608177 Rev A 8 9 02 and or volt hour setting When running a program step after the time or volt hour limit is reached the FB 1000 will automatically run the next program step if there is one After all program steps are completed in a program the FB1000 will shut down Any sequence of control mode and timed volt hour steps can be contained in a program Note that a program step can contain a zero for the time and volt hour parameters in which case the FB1000 will continue to maintain that setpoint indefinitely just like the setting had been run from MANUAL mode To enter programming mode from an operating screen cycle the control logic off and then back on by pressing the gray ON OFF key and selecting PROGRAM The FB1000 will display the program screen which shows the number of steps contained in the selected
69. st pas correctement configur V rifiez votre configuration et vos connexions 01 Courant de charge maximum d pass La sortie est en court circuit ou 21 l appareil d lectrophor se n est pas correctement configur V rifiez votre configuration et vos connexions 02 Brusque saut du courant de charge Le FB1000 a d tect un changement important au niveau du courant de charge V rifiez votre configuration et vos connexions 04 Coupure de l alimentation en CA fonction de red marrage apr s coupure de courant d sactiv e et ex cution pas termin e Le FB1000 a d tect une coupure de l alimentation en CA tant donn que la fonction de red marrage apr s coupure de courant n tait pas activ e l ex cution ne fut pas termin e 05 Coupure de l alimentation en CA ex cution sans dur e d termin e Le FB1000 a d tect une coupure de l alimentation en CA 06 99 Le FB1000 a d tect une condition d erreur interne Contactez le service d assistance technique pour obtenir des instructions Avant toute intervention sur l appareil veillez toujours couper l alimentation en CA l aide de l interrupteur qui se trouve au dos de l appareil puis d brancher le cordon d alimentation en CA L alimentation lectrique FB1000 ne n cessite aucun entretien p riodique et devrait fournir des ann es de service sans souci Si toutefois vous deviez remplacer les fusibles proc dez de la fa on sui
70. step screen The newly entered parameters will be displayed in the selected step To add a step after the selected step press the function key labeled ADD Enter parameters for the step as for EDIT pressing Exit when complete To delete a program or step press the Clear key from the program or step screen as desired After confirmation the FB1000 will remove the selected program or step from memory FB1000 2 MANUAL Page 8 7608177 Rev A 8 9 02 Method number Method 1 Next Navigation and 2 steps Prev editing keys Number of steps E Edit Figure 2 Program screen Method number Step 1 of2 Method 1 1 2 Next pre 100V 200mA Prev 7 editing keys 150W Add Step parameters 7 0 10 Edit the setpoint is reverse video Figure 3 Step screen Cleaning Before cleaning the unit be sure to always turn off AC power using the switch at the rear of the unit and then disconnecting the AC line cord The front of the unit is sealed and can be wiped clean with any mild detergent solution Avoid harsh cleaners or agents as they may deteriorate the surface of the tactile membrane keys FB1000 2 MANUAL Page 9 7608177 Rev A 8 9 02 Troubleshooting and Error Indications The FB 1000 detects and reports several events and conditions that are considered errors The FB1000 will stop any run in process and display ERROR XX where XX is one of the below listed errors When the FB1000 is displaying an error indication pres
71. touche Clear pour effacer les frappes pr c dentes Appuyez sur la touche Exit pour annuler la saisie d une nouvelle valeur Le FB1000 n accepte pas une valeur de consigne de tension en dehors de la gamme autoris e Appuyez sur la touche Clear pour r entrer une valeur appropri e Lorsque tous les param tres de l tape sont tels que vous le d sirez appuyez sur Exit pour revenir l cran des tapes Les param tres nouvellement entr s seront affich s dans l tape s lectionn e Pour ajouter une tape apr s l tape s lectionn e appuyez sur la touche de fonction libell e ADD Entrez des param tres pour l tape de la m me mani re que pour EDIT en appuyant sur Exit une fois que vous avez termin Pour supprimer un programme ou une tape appuyez sur la touche Clear partir de l cran des programmes ou des tapes suivant ce que vous d sirez Apr s confirmation le FB1000 retirera le programme ou l tape s lectionn de la m moire FB1000 2 MANUAL Page 9 7608177 Rev A 8 9 02 Num ro de m thode Method 1 Next Touches de 2 steps Prev amp navigation et d dition Nombre d tapes E d Edit Figure 2 cran des programmes Num ro de m thode tape 1 sur 2 Method 1 1 2 Next REN 100V 200mA Prev navigation et 150W Add d edition Parametres de ze 0 10 Edit l tape la valeur de consigne est en vid o invers e Figure 3 cran des tap
72. tral fusing Turn off AC power using the switch at the rear of the unit and then disconnecting the AC line cord Remove the fuse holder assembly using a small flat blade screwdriver Always replace both fuses with appropriate replacement fuses 5A 250V 5X20mm type T fuse T5A 250V Fisher catalog number FB FUSE 3 FB1000 2 MANUAL Page 10 7608177 Rev A 8 9 02 FB1000 Warranty Statement The Fisher Scientific Company Fisher warrants to the direct purchaser that the FB1000 will be free from defects in material or workmanship for a specified warranty period During that period Fisher will repair or replace the product or provide credit at its sole option upon prompt notification and compliance with its instructions For FB1000 power supplies that specified period is 48 months from manufacturing date Unless otherwise agreed the warranty is limited to the country in which the product is sold No Fisher employee agent or representative has the authority to bind Fisher to any oral representation or warranty concerning any product sold Any oral representation or warranty made prior to purchase of any product and not set forth in writing and signed by a duly authorized officer of Fisher shall not be enforceable by the purchaser FISHER EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Fisher s sole responsibility and the purchaser s
73. ue et d atteindre confortablement les commandes du panneau avant et les connexions des cellules Ne bloquez pas la partie ajour e du bo tier en bas l avant de l appareil ni la zone du ventilateur l arri re Connectez l alimentation lectrique une prise secteur munie d une fiche de terre en utilisant uniquement le cordon d alimentation en CA fourni avec Pappareil Connectez l appareil d lectrophor se l alimentation lectrique en veillant faire correspondre le fil positif rouge avec la prise positive rouge et le fil n gatif noir avec la prise n gative noire De m me connectez un deuxi me ou plusieurs appareils d lectrophor se suppl mentaires l alimentation lectrique si vous pr voyez d en faire fonctionner plusieurs en parall le Branchez une sonde de temp rature au connecteur situ l arri re du FB1000 et l appareil d lectrophor se si vous avez l intention d effectuer un contr le de temp rature au cours d un cycle Mettez l appareil en marche l aide de l interrupteur d alimentation en CA situ l arri re de l appareil c t du raccord du cordon d alimentation en CA touches de fonction touche d touche d ffadement prises n gatives noires xit Clear prises n gatives noires CKO 7 prises positives rouges touche d ex cution Run touche Pause touche Stop prises positives touche grise MARCHE ARRET Figure 1
74. urante la ejecuci n de un programa el FB1000 completar el paso interrumpido y despu s avanzar al siguiente paso en el programa Programaci n El FB1000 puede almacenar 9 programas y cada uno de ellos contener 9 pasos Un paso de programa es un valor prefijado constante de voltaje corriente o potencia con un par metro de l mite asociado y fundamentalmente un valor de tiempo y o voltios hora Cuando se ejecuta un paso de programa despu s de alcanzar el l mite de tiempo o volios hora el FB1000 ejecutar autom ticamente el siguiente paso del programa si lo hay Despu s de completar todos los pasos del programa se apagar el FB1000 Un programa puede contener cualquier secuencia de modo de control y pasos de tiempo voltios hora Observe que un paso de programa puede contener un cero para los par metros de tiempo y voltios hora en cuyo caso el FB1000 continuar manteniendo ese valor prefijado indefinidamente tal como si la configuraci n se hubiera procesado desde el modo MANUAL Para entrar en el modo de programaci n desde una pantalla de operaci n desactive la l gica de control y luego activela presionando la tecla gris de Activar Desactivar y seleccionando PROGRAM El FB1000 mostrar la pantalla de programaci n donde se muestra el n mero de pasos que contiene el programa seleccionado Use las teclas de funci n situadas a la derecha de la pantalla para desplazarse por los 9 programas posibles Para ejecutar el programa d
75. vante Remplacement d un fusible ATTENTION Le FB1000 utilise un syst me de fusible neutre double p le Coupez l alimentation en CA l aide de l interrupteur qui se trouve au dos de l appareil puis d branchez le cordon d alimentation en CA Retirez le porte fusibles l aide d un petit tournevis plat Remplacez toujours les deux fusibles avec des fusibles de rechange appropri s fusible de type T de 5 A 250 V 5X20 mm T5A 250V num ro de catalogue Fisher FB FUSE 3 FB1000 2 MANUAL Page 11 7608177 Rev A 8 9 02 Garantie du FB1000 The Fisher Scientific Company Fisher accorde a l acheteur direct une garantie pi ces et main d ceuvre sur le FB1000 pendant une dur e de garantie sp cifi e Pendant cette p riode Fisher r parera ou remplacera le produit ou accordera un remboursement a sa seule discr tion moyennant notification rapide et respect de ses instructions Pour les alimentations lectriques FB1000 cette p riode sp cifi e est de 48 mois a partir de la date de fabrication Sauf mention contraire la garantie est limit e au pays dans lequel le produit est vendu Aucun employ agent ou repr sentant de Fisher n est habilit prendre un engagement oral ou accorder une garantie orale quelconque au nom de Fisher concernant un produit vendu Tout engagement ou garantie accord oralement avant l achat d un produit et pas traduit par crit et sign par un responsable d m
76. verwendet wird Wird das Ger t auf andere Weise verwendet k nnen Leistung und Sicherheit beeintr chtigt werden Im Lieferumfang dieses Ger tes ist ein Netzkabel enthalten Die Schutzerdung ist f r einen sicheren Betrieb erforderlich Verwenden Sie keine anderen Netzkabel mit diesem Instrument Das FB1000 ist ein Hochspannungs Netzteil das wahrend des Betriebs gefahrliche Spannungs und Stromst rken erzeugen kann Seien Sie deshalb beim Arbeiten mit den elektrischen Anschl ssen dieses Ger tes und in deren Umgebung u erst vorsichtig Pr fen Sie stets die elektrischen Anschl sse Kabel und dazugeh rigen Ger te auf jegliche Anzeichen von Verschlei und Besch digung vor dem Gebrauch mit diesem Ger t Stellen Sie sicher dass Sie nur Elektrophorese Ger te verwenden die dem Nennwert der Spannung und des Stroms des FB1000 Netzteils entsprechen Der Ausgang des FB1000 Netzteils ist nur f r den Anschluss an elektrisch isolierte Elektrophorese Ger te bestimmt Verwenden Sie das Ger t nur mit elektrisch isolierten Elektrophorese Ger ten die eine Mindestisolierung von 1000 V besitzen Schlie en Sie keine Anschlussklemmen des FB1000 Ausgangs an die Erdung an Dadurch kann der ger teinterne Schutz unterbrochen oder das Ger t besch digt werden Wenn der Hochspannungsausgang des FB1000 entlastet oder nur leicht belastet wird braucht dieser einige Zeit sich abzubauen Warten Sie mindestens eine Minute nach dem Stoppen einer Ausf hrung bevo
77. x cutions dur e d termin e ou en volts heures et que la fonction de red marrage apr s coupure de courant est activ e utilisez toujours les commandes du panneau avant pour arr ter une ex cution en cours Pour activer la fonction de red marrage apr s une coupure de courant appuyez sur la touche de fonction du haut lorsque vous vous trouvez sur l cran de s lection de mode MANUEL ou PROGRAMME Chaque pression de la touche activera la fonction de red marrage apr s une coupure de courant si celle ci tait d sactiv e ou la d sactivera si elle tait activ e Lorsque l alimentation en CA est r tablie lors d une ex cution au cours de laquelle la fonction de red marrage apr s coupure de courant est activ e l cran affiche POWER FAIL RESTART pendant approximativement 10 secondes indiquant qu un red marrage apr s coupure de courant est en imminent Pendant ce temps la sortie n est pas aliment e afin de permettre d arr ter l ex cution en toute s curit en appuyant sur la touche Run Une fois coul le d lai d attente de red marrage apr s coupure de courant la sortie de l alimentation lectrique augmentera progressivement jusqu la valeur de consigne et l ex cution continuera partir de ce moment l Il peut y avoir plusieurs coupures de courant au cours d une m me ex cution Si un red marrage apr s une panne de courant a lieu lors de l ex cution d un programme le FB
78. xit key From the resulting screen select the new constant parameter using the function keys to the right of the display FB1000 2 MANUAL Page 5 7608177 Rev A 8 9 02 After selecting a control mode and setting the limit and timed run parameters if desired press the Run key to energize the power supply output The power supply output will ramp up to the appropriate setpoint while not allowing any limit parameter to be exceeded Ifany limit parameter should be exceeded then the power supply will crossover control modes making the limit parameter the new control setpoint The run mode display shows the controlled parameter highlighted and will automatically change if a crossover has occurred To stop a run in progress press the Run key the Stop key or the gray ON OFF key The display will change to STOP signifying that the output is no longer energized and display the conditions just before the stop To pause a run in progress press the Pause key The display will change to PAUSE signifying that the output is no longer energized and that the run can be resumed Pressing Run or Pause resumes the run from the previous point i e for a timed run Only a run that has been paused can be restarted After Stopping a run or to change parameters of a paused run you must cycle the control logic off and then back on by pressing the gray ON OFF key During a run the display will show the actual values of voltage current power and temperature