Emerson Rosemount 1151 Pressure Transmitter User's Manual

image

Contents

1. 4 Replace the housing cover Write Protect Switch In the ON position the write protect switch prevents changes to the configuration data 1 Remove the housing cover 2 Move the write protect switch to the OFF 3 Verify transmitter configuration see Verify Transmitter Configuration 4 Move the write protect switch to the ON 5 Replace the housing cover Figure 3 Switch Locations Failure Mode Switch Write Protection Switch PRESS BOTH THE SAME TIME Zero Adjustment 1151 SMART B n rosenounr LE P N 01151 0934 0204 Rosemount 1151 Quick Installation Guide 00825 0100 4593 Rev BA July 2009 STEP 5 CALIBRATE THE TRANSMITTER Verify Transmitter Configuration NOTE A check Vv indicates the basic configuration parameters At minimum these parameters should be verified as part of the configuration and startup procedure Table 1 HART Communicator Fast Key Sequence Function Analog Output Analog Output Alarm Burst Mode Control Burst Operation Calibration Characterize Damping Date Descriptor Digital to Analog Trim 4 20 mA Output Field Device Information Full Trim Keypad Input Loop Test Lower Range Value Lower Sensor Trim Message Meter Type Number of Requested Preambles Percent Range Poll Address Pressure Y Range Values Rerange Scaled D A Trim 4 20 mA Output Self Test Transmitter Sensor Information Sensor Trim Points Status Y Tag v Tran
2. Loctite 222 Small Screw Threadlocker on the threads to ensure a watertight seal on the housing NOTE If the desired position cannot be attained within the 90 limit the transmitter will need to be disassembled See the Rosemount 1151 reference manual document number 00809 0100 4360 for further instruction Housing Lock Nut Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 STEP 3 CONNECT THE WIRING AND POWER UP Use the following steps to wire the transmitter 1 Remove the housing cover on the side marked TERMINALS on the nameplate 2 Connect the positive lead to the terminal and the negative lead to the terminal Figure 1 Field Wiring Diagram Power Supply O EE Optional Indicator R 2 250 0 Installation of the transient protection terminal block does not provide transient protection unless the 1151 case IS properly grounded 3 Ensure proper grounding It is important that the instrument cable shield e be trimmed close and insulated from touching the transmitter housing e be connected to the next shield if cable is routed through a junction box be connected to a good earth ground at the power supply end NOTE Do not connect the powered signal wiring to the test terminals Power could damage the test diode in the test connection Twiste
3. OSEMOUNT C Schedule No RMD 1020 Rev El PED Notified Body Det Norske Veritas DNV Notified Body Number 00575 Veritasveien 1 N 1322 Hovik Norway ATEX Notified Bodies for EC Type Examination Certificate Baseefa Notified Body Number 1180 Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom CESI Notified Body Number 0722 Via Rubattino 1 20134 Italy ATEX Notified Body for Quality Assurance Baseefa Notified Body Number 1180 Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom ad EMERSON Page 3 of 3 K Prodapp EUCDOCSV 151_RMDi020E1 doc 21 Rosemount 1151 22 Quick Installation Guide 00825 0100 4593 Rev BA July 2009
4. Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 Rosemount 1151 Pressure Transmitter with 4 20 mA HART Protocol Product Discontinued Start Step 1 Mount the Transmitter Step 2 Consider Housing Rotation Step 3 Connect the Wiring and Power Up Step 4 Set Switches Step 5 Configuration Step 6 Trim the Transmitter Product Certifications CE ROSEMOUNT EMERSON www rosemount com Process Management Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 A WARNING Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Please review the approvals section of the 1151 reference manual for any restrictions associated with a safe installation e Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices e In an Explosion Proof Flame Proof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death e To avoid process leaks only use the o ring designed to seal with the corresponding flange adapter Electrical shock can result in death or serious injury e Avoid contact with the leads and
5. be exceeded 2 It is a condition of safe use that when the optional transient protection is used its metallic housing shall be bonded to the system earth Combination Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types C6 Combination of l6 and E6 CSA Explosion Proof and Intrinsic Safety Approval Factory Sealed K5 Combination of FM Explosion Proof Intrinsic Safety and Non incendive Approvals K6 Combination of E6 16 11 and E8 18 Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 CE EC Declaration of Conformity No RMD 1020 Rev E Rosemount Inc 8200 Market Boulevard Chanhassen MN 55317 9685 USA declare under our sole responsibility that the product Model 1151 Smart Pressure Transmitter manufactured by Rosemount Inc 200 Market Boulevard Chanhassen MN 55317 9685 USA to which this declaration relates is in conformity with the provisions of the European Community Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Community notified body certification as shown in the attached s
6. c Compatibility EMC 2004 108 EC All models EN 61326 1 2006 EN61326 2 3 2006 Hazardous Locations Certifications North American Certifications Factory Mutual FM Approvals FM Explosion Proof tag is standard Appropriate tag will be substituted if optional certification is selected Explosion Proof Class I Division 1 Groups B C and D T5 Ta 85 C Dust Ignition Proof Class Il Division 1 Groups E F and G Class Ill Division 1 T5 Ta 85 C Indoor and outdoor use Enclosure Type 4X Factory Sealed 15 Intrinsically safe for Class I Il and III Division 1 Groups A B C D E F and G T4 hazardous locations in accordance with entity requirements and Control drawing 01151 0214 Non incendive for Class I Division 2 Groups A B C and D T4 hazardous locations Enclosure Type 4X For entity parameters see control drawing 01151 0214 15 Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 Canadian Certifications Canadian Standards Association CSA Approvals E6 Explosion Proof for Class I Division 1 Groups C and D Class II Division 1 Groups E F and G Class Ill Division 1 Hazardous Locations Suitable for Class I Division 2 Groups A B C and D CSA enclosure type 4X Factory Sealed Intrinsically safe for Class Division 1 Groups A B C and D hazardous locations when connected per Drawing 01151 2575 For entity parameters see control drawing 01151 2575 Temperatu
7. chedule signature March 6 2007 Robert J Karschnia date of issue name printed Vice President Technology EM ERSON function name printed Mra NA hea ibi iili 19 Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 CE Schedule No RMD 1020 Rev El EMC Directive 2004 108 EC Model 1151 Smart Pressure Transmitter EN 61326 1997 with amendments Al A2 and A3 PED Directive 97 23 EC Model 1151GP9 0 1151HP4 5 6 7 8 Pressure Transmitters QS Certificate of Assessment EC No PED H 100 Module H Conformity Assessment All other model 1151 Smart Pressure Transmitters Sound Engineering Practice Transmitter Attachments Diaphragm Seal Process Flange Manifold Sound Engineering Practice ATEX Directive 94 9 EC Model 1151 Smart Pressure Transmitter BAS99ATEX1294X Intrinsically Safe amp Dust Certificate Equipment Group II Category 1 GD Ex ia HC T4 T5 EN50014 1997 Al A2 EN50020 1994 EN50284 1999 EN 50281 1 1 1998 BAS99ATEX3293X Type n amp Dust Certificate Equipment Group II Category 3 GD Ex nL HC T4 T5 EN50021 1998 EN 50281 1 1 1998 CESIO3ATEX037 Flameproof Certificate Equipment Group II Category 1 2 G E d IIC T4 T6 EN50014 1997 Al A2 EN50018 2000 Al ENS0284 1999 EMERSON Protest Merged Page 2 of 3 K ProdappnEUCDOCS 1151_RMD1020E1 doc 20 Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 R
8. d pair cable should be used for best results In high EMI RFI environments use either transient terminal block or shielded signal wiring Use 12 to 24 AWG wire and do not exceed 5 000 feet 1500 meters 4 Plug and seal unused conduit connections 5 If applicable install wiring with a drip loop Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing 6 Replace the housing cover Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 STEP 3 CONTINUED Power Supply The dc power supply should provide power with less than two percent ripple The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller indicator and related pieces Note that the resistance of intrinsic safety barriers if used must be included Figure 2 Load Limitation Rmax Operating Region Vmin Vs Vmax Rmax STU AEC CERAS S 12 45 0 1650 Ri 43 5 Vs 12 1 A minimum of 250 Q is required for communication Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 STEP 4 CONFIGURE THE TRANSMITTER Failure Mode Alarm Switch 1 Remove the housing cover 2 Locate the failure mode switch see Figure 3 3 Move the switch to the desired alarm setting To set the failure mode to high alarm position the switch toward HI To set the failure mode to low alarm position the switch to LO
9. iguration buttons simultaneously for two seconds 6 Replace the LCD Display cover Table 2 LCD Display Modes Relationship between Input Signal and Digital Display Lin Linear Lin F Linear with five second filter Srt Square root SrtF Square root with five second filter Square root function relates to the digital display The bar graph output remains linear with the current signal Square root response digital display will be proportional to the square root of the input current where 4 mA 0 and 20 mA 1 0 scaled per the calibration procedure The transition point from linear to square root is at 25 of full scale flow Filter response operates upon present input and input received in the previous five second interval in the following manner Display 0 75 x previous input 0 25 x present input This relationship is maintained provided that the previous reading minus the present reading is less than 25 of full scale NOTE The meter displays for approximately 7 5 seconds while the information is being stored 11 Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 STEP 5 CONTINUED Set the Display Equivalent to a 4 mA Signal 1 2 3 4 5 Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover Press the left button for two seconds To decrement the display numbers press the left configuration button and to increment the numbers p
10. int Verify that the output is 20 mA 4 20 mA Output Trim A 4 20 mA output trim adjusts the transmitter milliampere output to match plant standards This procedure is used to trim the transmitter using a current meter Using the HART Communicator HART Fast Keys Steps 22 sere 1 Equalize or vent the transmitter and connect HART communicator 2 At the menu input the HART Fast Key sequence 3 Follow the commands to perform a full trim 14 Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 PRODUCT CERTIFICATIONS Approved Manufacturing Locations Rosemount Inc Chanhassen Minnesota USA Fisher Rosemount GmbH amp Co Wessling Germany Emerson Process Management Asia Pacific Private Limited Singapore Beijing Rosemount Far East Instrument Co Limited Beijing China European Directive Information The EC declaration of conformity can be found on page 19 The most recent revision can be found on www emersonprocess com rosemount ATEX Directive 94 9 EC Emerson Process Management complies with the ATEX Directive European Pressure Equipment Directive PED 97 23 EC 1151GP9 0 1151HP4 5 6 7 8 Pressure Transmitters QS Certificate of Assessment EC No PED H 20 Module H Conformity Assessment All other 1151 Pressure Transmitters Sound Engineering Practice Transmitter Attachments Diaphragm Seal Process Flange Manifold Sound Engineering Practice Electro Magneti
11. n into account when installing the apparatus Australian Certifications Standards Association of Australia SAA Certification E7 Flameproof Certificate Number Aus Ex 494X Ex d IIB H T6 DIP T6 IP65 Special Conditions for safe use x For transmitters having NPT PG or G cable entry threads an appropriate flameproof thread adaptor shall be used to facilitate application of certified flameproof cable glands or conduit system Intrinsic Safety Certificate Number Aus Ex 122X Ex ia I IIB T4 T 60 C T5 IP66 Special Conditions for Safe Use x 1 It is a condition of safe use that the following parameters shall be taken into account during installation 2 It is a condition of safe use that the transmitter must be supplied from a resistive current limiting barrier 3 It is a condition of safe use that when the optional transient protection is used its metallic housing shall be bonded to the system earth 4 It is a condition of safe use that only the stainless steel case version can be labeled as suitable for Group I Table 3 Entity Parameters U 30V 125 mA P 1 0 W T4 or 0 67W T5 Ci 14 8 nF E 20 uH 17 Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 N7 Type N Certificate Number Aus Ex 122X Ex n IIC T5 T 80 C T6 IP66 Special Conditions for safe use x 1 Itis a condition of safe use that a nominal voltage of 30 V for Ex n application shall not
12. nt 1151 STEP 1 CONTINUED C O rings with Flange Adapters A WARNING Failure to install proper flange adapter O rings may cause process leaks which can result in death or serious injury The two flange adapters are distinguished by unique O ring grooves Only use the O ring that is designed for its specific flange adapter as shown below Rosemount 3051S 3051 2051 3001 3095 PTFE Based u 5 Elastomer Rosemount 1151 Flange Adapter AN Whenever the flanges or adapters are removed visually inspect the o rings Replace them if there are any signs of damage such as nicks or cuts If you replace the o rings re torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o ring Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 STEP 2 CONSIDER HOUSING ROTATION To improve field access or to better view the optional LCD display 1 Loosen the housing lock nut 2 Rotate the housing clockwise to the desired position up to 90 from its original position Over rotating will damage the transmitter 3 If the desired position is attained tighten the housing lock nut 4 If the desired position cannot be reached because the housing will not rotate further rotate the housing counterclockwise until in the desired position up to 90 from its Original position 5 Tighten the housing lock nut to 420 in lb Use a sealing compound
13. re Code T2D Measurement Canada Approvals C5 Accuracy Approval to the Electricity and Gas Inspection Act for the purchase and sale of natural gas European Certifications E8 ATEX Flameproof 16 Certification Number CESIO3ATEX037 ATEX Marking II 1 2 G EEx d IIC T6 40 C lt Tamb lt 40 C EEx d IIC T4 40 C lt Tamb lt 80 C CE 1180 V 60 Vdc maximum ATEX Intrinsic Safety and Combustible Dust Certification Certification Number BAS99ATEX1294X ATEX Marking Il 1 GD Ex ia IIC T5 60 C lt Tamp lt 40 C Ex ia IIC T4 60 C lt Tamp lt 80 C Dust Rating T90 C Tamb 20 C to 40 C IP66 CE 1180 Entity Parameters U 30V 125 mA P 1 0 W T4 or 0 67 W T5 C 0 034 uF Li 20 uH Special Conditions for safe use x The apparatus is not capable of withstanding the 500V insulation test required by EN60079 1 This must be taken into account when installing the apparatus Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 N1 ATEX Type N and Dust Certification Certificate Number BAS99ATEX3293X ATEX Marking II 3 GD Ex nL IIC T5 40 C lt Tamp lt 40 C EX nL IIC T4 40 C lt Tamb lt 80 C Dust Rating T90 C Tamp 20 C to 40 C Ui 45 Vdc maximum IP66 Special Conditions for safe use x The apparatus is not capable of withstanding the 500V insulation test required by EN60079 1 This must be take
14. ress the right configuration button Set the numbers between 999 and 1000 To store the information press both configuration buttons simultaneously for two seconds Replace the LCD display cover Set the Display Equivalent to a 20 mA Signal 1 2 3 12 Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover Press the right button for two seconds To decrement the display numbers press the left configuration button on the display and to increment the numbers press the right configuration button Set the numbers between 999 and 9999 The sum of the 4 mA point and the span must not exceed 9999 To store the information press both configuration buttons simultaneously for two seconds The LCD display is now configured Replace the LCD Display cover Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 STEP 6 TRIM THE TRANSMITTER NOTE Transmitters are shipped fully calibrated per request or by the factory default of full scale Span upper range limit Full Trim A full trim is a two point sensor calibration where two end point pressures are applied and the transmitter process variable output is adjusted to agree with the pressure input Using the HART Communicator HART Fast Keys Steps 1 2 3 3 1 Equalize or vent the transmitter and connect HART communicator 2 At the menu input the HART Fast Key sequence 3 Follow the commands to perform a full trim Zero T
15. rim A zero trim is a single point adjustment used for compensating mounting position effects When performing a zero trim ensure that the equalizing valve is open and all wet legs are filled to the correct level If zero offset is less than 3 of true zero follow the Using the HART Communicator instructions below If zero offset is greater than 3 of true zero follow the Using the Transmitter Zero Adjustment Buttons instructions Using the HART Communicator HART Fast Keys Steps 1 2 3 3 1 1 Equalize or vent the transmitter and connect HART communicator 2 At the menu input the HART Fast Key sequence 3 Follow the commands to perform a zero trim 13 Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 STEP 6 CONTINUED Using the Transmitter Zero Adjustment Buttons Perform the following steps to perform a rerange using the zero adjustment buttons see Figure 3 1 Apply a pressure equivalent to the lower calibrated value on the high side of the transmitter 2 Remove the circuit side cover to expose the span and zero buttons Hold both the span and zero buttons down simultaneously for at least five seconds to activate the controls 3 Press the zero button for five seconds to set the 4 mA point Verify that the output is 4 mA 4 Apply a pressure equivalent to the higher calibrated value to the high side of the transmitter 5 Press the span button for five seconds to set the 20 mA po
16. sfer Function Setting Output Type Transmitter Security Write Protect Trim Analog Output Y Units Process Variable Upper Range Value Upper Sensor Trim Zero Trim 10 Fast Key Sequences PrRHFWAWONHNNNANWWWANAHASA MWWARWORA DHA WWOWW ARAO RO eg N X rer rm NO OnmwA KRW KR OW OS A N MONNWAONWAWWNNFNNNW NURA 0R WWW NVON N N aN NA lt a Q gt gt SO A S S S S gt Ss Ss os St Sl a D w w w w W Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 STEP 5 CONTINUED Configure LCD Display Figure 4 Sample 1151 LCD Display a Digital Bar Graph Retaining Ring Left Configuration Button Right Configuration Button NOTE The LCD display time out is approximately 16 seconds If keys are not pressed within this period the indicator reverts to reading the signal Position the Decimal Point and Select the Meter Function 1 Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover 2 Press the left and right configuration buttons simultaneously and release immediately 3 To move the decimal point to the desired location press the left configuration button Note that the decimal point wraps around 4 To scroll through the mode options press the right configuration button until the desired mode is displayed see Table 2 5 Press both conf
17. the terminals High voltage that may be present on leads can cause electrical shock A IMPORTANT NOTICE This installation guide provides basic guidelines for Rosemount 1151 transmitters It does not provide instructions for configuration diagnostics maintenance service troubleshooting Explosion Proof Flame Proof or intrinsically safe I S installations Refer to the Rosemount 1151 reference manual document number 00809 0100 4360 for more instruction This manual is also available electronically on www emersonprocess com rosemount Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 STEP 1 MOUNT THE TRANSMITTER A Applications Liquid Flow Applications 1 Place taps to the side of the line 2 Mount beside or below the taps Gas Flow Applications 1 Place taps in the top or side of the line 2 Mount beside or above the taps Steam Flow Applications 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Quick Installation Guide 00825 0100 4593 Rev BA Rosemount 1151 July 2009 STEP 1 CONTINUED B Optional Mounting Brackets When installing the transmitter to one of the optional mounting brackets torque the bracket bolts to 125 in lbs 0 9 N m Pipe Mount 1 Panel bolts are customer supplied Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemou