1.  mbar droop   Integral Two Stage  30 psig   2 07 bar and 2 inches w c    5 mbar droop   Integral Two psig Service Regulator  30 psig   2 07 bar inlet pressure and 2096 droop   First Stage  30 psig   2 07 bar inlet pressure and 20  droop   2  Also available with vent opposite gauge taps   3  Integral First Stage Vent size  7 16 24 UN thread for 1 4 inch OD copper tube inverted flare fitting        R122H  R222  R232A  and R232E Series    LP Gas Regulators       Figure 3  Tank Installation    Installation    All vents should be kept open to permit free  flow of air in and out of the regulator  Protect  vent openings against the entrance of rain   snow  ice formation  paint  mud  insects  or  any other foreign material that could plug the  vent or vent line     LP Gas may discharge to the atmosphere  through the vent  An obstructed vent  which limits air or gas flow can cause  abnormally high pressure that could result  in personal injury or property damage     The Types R232A  R232E  and R122H are  not suitable for indoor installations  Never  use the Types R122H and R232E  pounds to  pounds  regulators on low pressure  inches  of water column  service because personal  injury or property damage could occur     General Installation Instructions    Before installing the regulator       Check for damage  which might have occurred  in shipment       Check for and remove any dirt or foreign material   which may have accumulated in the regulator body       Replace old pigtails  Blow 
2.  years from  date of manufacture or sooner should  inspection reveal the need     Visually inspect the regulator each time a  gas delivery is made for     Improper installation  vent not pointed vertically down or  under a cover  no vent tube on underground systems     Plugged or frozen vent     Wrong regulator or no regulator in the system     Internal or external corrosion     Flooded Regulator  water in spring case  regulator  submersed on underground tanks    Regulator age     Any other condition that could cause the uncontrolled  escape of gas     Failure to do the above could result in personal injury or  property damage     Vent Opening    Make sure the regulator vent  vent assembly  or vent tube  does not become plugged by mud  insects  ice  snow   paint  etc  The vent screen aids in keeping the vent from  becoming plugged  and the screen should be clean and  properly installed     Water inside Regulators from Floods   Weather  or Water Table on  Underground Systems    Replace any regulator that has been flooded or   has been submersed below the water table of an  underground tank  has had water in the spring case  or show evidence of external or internal corrosion   Checking for internal corrosion on the Types R222   R232A  and R232E second stage portion can be  done by removing the closing cap and with the aid of  a flashlight observing the condition of the relief valve  spring  main spring  and internal spring barrel area  A  more detailed examination will require 
3. 2H  R232A  and R232E Series   250 psig   17 2 bar  R222 Series  10 psi   0 69 bar    Maximum Emergency Inlet Pressure  R122H  R232A  and R232E Series   250 psig   17 2 bar  R222 Series     75 psi   5 2 bar when used with a  Fisher   Type R122H or R622H first stage regulator   40 psi   2 8 bar when used with any other first  stage regulator     Temperature Capabilities  R122H  R222  R232A  and R232E Series    20 to 160  F    29 to 71  C     Pressure Registration  Internal    Outlet Pressure Standard Setpoint  R122H Series  10 psi   0 69 bar  R222 Series  Second Stage  11 inches w c    27 mbar  R232A Series  First Stage  approximately 9 psig    0 62 bar at 100 psig   6 9 bar  50 SCFH   1 42 Nm  h  Second Stage  11 inches w c    27 mbar  R232E Series  9 psig   0 62 bar at 100 psig    6 9 bar  50 SCFH   1 42 Nm  h  Second Stage  2 psig   0 14 bar    Outlet Pressure Spring Ranges  R122H Series  10 psig   0 69 bar     1 psig   0 07 bar   non adjustable   R222 Series  Second Stage  9 5 to 13 inches w c     24 to 32 mbar  R232A Series  First Stage  non adjustable  Second Stage  10 2 to 13 inches w c    25 to 32 mbar  R232E Series  First Stage  non adjustable  Second Stage  1 to 2 2 psig   0 07 to 0 15 bar    Approximate Weights  R122H Series  1 2 lbs   544 grams  R222 Series  1 4 lbs   635 grams  R232A and R232E Series with POL   1 9 Ibs   865 grams  R232A and R232E Series with NPT fitting   1 5 Ibs   671 grams    1  In the event the R222 Series malfunctions during a Maximum Emergenc
4. A  and R232E Series  LP Gas Regulators    TO APPLIANCE      VENT ASSEMBLY            E              L             VENT LINE VENT OPENING MUST BE AT  LEAST 3 FEET    0 9 meter HORIZONTALLY  V i FROM ANY BUILDING OPENING  l BELOW IT  BASEMENT      pe o  5       FROM FIRST STAGE  REGULATOR    Figure 4  Basement Installation    END OF REGULATOR VENT TUBE  LOCATED AT TOP INSIDE OF HOUSING  DOME COVER    GRADE GROUND DOWNWARD AND   SLOPING AWAY FROM HOUSING DOME    THIS PREVENTS WATER COLLECTING   AND RUNNING INTO OR STANDING   AROUND HOUSING DOME  2 INCHES   5 1 cm  MINIMUM    REGULATOR ADJUSTMENT CLOSURE  CAP MUST BE TIGHT    WATER MARK LEFT IN HOUSING DOME AT LEVEL ABOVE REGULATOR VENT  OR END OF VENT TUBE  REQUIRES REPLACEMENT OF REGULATOR  THEN CORRECT INSTALLATION    Figure 5  Underground Installation    R122H  R222  R232A  and R232E Series    LP Gas Regulators    Regulators Subjected to Heavy  Snow Conditions    Some installations  such as in areas with heavy snowfall   may require a hood or enclosure to protect the regulator  from snow load and vent freeze over     Horizontally Installed Regulators    Horizontally mounted regulators  such as found in single  cylinder installations and ASME tanks  must be installed  beneath a protective cover or under the ASME tank  dome  refer to Figure 3  If possible  slope or turn the vent  down sufficiently to allow any condensation to drain out of  the spring case  Be careful that the slot in the tank dome  or protective cover for the r
5. Instruction Manual R122H  R222  R232A  and R232E series    October 2012    R122H  R222  R232A  and R232E Series  Instruction Manual       Failure to follow these instructions or   to properly install and maintain this  equipment could result in an explosion  and or fire causing property damage and  personal injury or death     Fisher   equipment must be installed   operated  and maintained in accordance  with federal  state  and local codes and  Fisher instructions  The installation in most  states must also comply with NFPA No  54  and 58 standards     Only personnel trained in the proper  procedures  codes  standards  and  regulations of the LP Gas industry should  install and service this equipment        Type R122H    Things to tell the gas customer     1  Show the customer the vent or vent assembly or  vent tube  Stress that this opening must remain  unobstructed at all times  Tell the customer to check  the vent opening after a freezing rain  sleet storm  or Type R222 Type R232E  snow to make sure ice has not formed in the vent        Figure 1  R122H  R222  R232A  and R232E Series Regulators  2  Show the customer the shutoff valve on the g g    container  The customer should close this valve  immediately if gas is smelled  appliance pilot lights    fail to stay on or appear higher than usual or any regulators  which includes first stage  second stage  integral  other abnormal situation occurs  two stage  and integral two psig service regulators used    on LP Gas vapor s
6. egulator   s outlet piping does  not expose the vent to the elements  The first stage vent  on the Types R232A and R232E should be pointed down     Indoor Installations    The Types R122H  R232A  and R232E regulators  are not recommended for indoor installations  The  Type R222 regulator may be installed indoors as follows     By code  regulators installed indoors have limited inlet  pressure  and they require a vent line to the outside of the  building  see Figure 4  Avent assembly  such as   Fisher   Y602 Series  should be used on the end of the  vent line  The same installation precautions  previously  discussed throughout this manual for the regulator vent   apply to the end of the vent tube assembly  Vent lines  must not restrict the gas flow from the regulator   s internal  relief valve  Vent lines should be at least 3 4 inch NPT  pipe or 3 4 inch NPT size  Gray PVC Schedule 40 Rigid  Non metallic Electrical Conduit for above Ground Service   per Underwriters Laboratories  UL    651  To install the  vent line  remove the vent screen and apply a good grade  of pipe dope to the male threads of the line  Vent lines  should be as straight as possible with a minimum number  of bends     Underground Installations    Types R232A and R232E integral regulators  require 2 vent tubes  one on the first stage  vent and one on the second stage vent   when installed on underground tanks   Failure to use 2 separate vent tubes can  result in early regulator failure and or over  pressuri
7. er of the regulator when  corresponding with the factory     The type number  orifice size  and spring range are   on a label attached to the spring barrel  The date of  manufacture is stamped on the regulator  Always provide  this information in any correspondence with your Fisher  Distributor regarding replacement parts or technical  assistance  If construction changes are made in the field   be sure that the regulator marking is also changed to  reflect the most recent construction     The Emerson logo is a trademark and service mark of Emerson Electric Co  All other marks are the property of their prospective owners  Fisher is a mark owned by Fisher Controls International LLC   a business of Emerson Process Management     The contents of this publication are presented for informational purposes only  and while every effort has been made to ensure their accuracy  they are not to be construed as warranties or  guarantees  express or implied  regarding the products or services described herein or their use or applicability  We reserve the right to modify or improve the designs or specifications of such  products at any time without notice     Emerson Process Management Regulator Technologies  Inc  does not assume responsibility for the selection  use or maintenance of any product  Responsibility for proper selection  use and  maintenance of any Emerson Process Management Regulator Technologies  Inc  product remains solely with the purchaser      gt  w  S    EMERSON       Eme
8. ervice applications  They are not to be    3  Tell the customer to call your company to service the used on liquid service     regulator if the regulator vents gas or a leak develops  in the system  Only a qualified gas service person  should install or service the regulator  Description    Introduction Second Stage Low Pressure Regulator    The Type R222 second stage regulator provides low  Scope of the Manual pressure  inches of water column  delivery pressure  It   is set at 11 inches w c    27 mbar pressure and comes  This Instruction Manual covers installation and maintenance with a high capacity internal relief valve  The regulator is  for the R122H  R222  R232A  and R232E Series painted PALM GREEN     E         EMERSON     D450141T012    R122H  R222  R232A  and R232E Series    LP Gas Regulators    Specifications    Specifications and Tables 1 and 2 list the specifications for these regulators  Contact the factory if the regulator is to be  used on any service other than LP Gas  natural gas  or air  The following information is located on the spring case  type    number  orifice size  spring range  and date of manufacture     Pressure Taps Size Restriction  1 8 NPT   54   0 055 inch Drill on outlet and inlet    Orifice Sizes  R122H Series  0 15 inch   3 8 mm  R222 Series  0 14 inch   3 6 mm  R232A and R232E Series  0 193 inch   4 9 mm    Wide Open C  for Relief Sizing  R122H Series  23  R222 Series  18  R232A and R232E Series  19    Maximum Allowable Inlet Pressure  R12
9. for a  high pressure burner  The regulator is painted RED     R122H  R222  R232A  and R232E Series  LP Gas Regulators          3 FEET    VENT POINTED DOWN 0 9 meter          Figure 2  Regulator with Vent Pointed Down    Table 1  Relief Valve Specifications    MAXIMUM OUTLET PRESSURE WITH DISC REMOVED  TYPICAL SETPOINT NOMINAL RELIEF VALVE  TYPE START TO DISCHARGE Inlet Pressure Maximum Outlet Pressure    1  For integral two stage regulators  the second stage disc is removed        Table 2  Capacity  Connection Sizes  and Vent Orientation    eecuaron   nme   SAGT   wer   comer   a   S NCHFNPY SCREENED  APPLICATION NUMBER PROPANE    CONNECTION CONNECTION SETTING LOCATION    First Stage R122H AAJ 1 100 000 1 4 inch FNPT 1 2 inch FNPT 10 psig   0 69 bar Over Outlet     R222 BAF Over Inlet  Second Stage 650 000 1 2 inch FNPT 1 2 inch FNPT    R222 BAFXA   BAFXA Over Outlet    R232A BBF   1 4 inch FNPT     1 4 inch FNPT   FNPT   j  3    E a   aooo 000 1 2 inch FNPT 11 inches w c    First stage   Down  Integral R232A HBF FPOL 27 mbar Second Stage  Over Outlet    Two Stage R232A BBFXA TERRA  somo  eer 1 4 inch FNPT First Stage  Opposite Gauge Taps  550 000 i    1 2 inch FNPT Second Stage     R232A HBFXA     Fa   Opposite Gauge Taps    R232E BBH 1 4 inch FNPT  3    ntegra  TWO psig 500 000 1 2 inch FNPT 2 psig   0 14 bar   Mord ip    Service   R232E HBH     R232E HBH       FPO   econd Stage  Over Outlet    1  Capacities Based on   Second Stage  10 psig   0 69 bar with 2 inches w c    5
10. ng the second stage that could  result in fires or personal injury     A regulator installed in the dome of an underground  container requires a vent tube to prevent water from  entering the regulator spring case  see Figure 5     The Type R122H will require one vent line and if the  Types R232A and R232E integral regulators is installed   on an underground tank the use of 2 vent tubes are  required  one for the first stage vent  1 4 inch OD copper  tube inverted flare connection  7 16 24 UN thread  and the  other for the second stage vent  3 8 NPT  of the regulator   are required     Remove the vent screen s  and install a vent tube s   The  vent tube must be run from the regulator vent s  to above  the maximum water table  The vent tube opening s  must  terminate at the extreme top inside of the dome cover   Make sure the regulator   s closing cap is on tightly  and  maintain drainage away from the dome at all times     Adjustment    Each regulator is factory set  If it becomes necessary to  increase the outlet pressure  remove the closing cap and  turn the adjustment screw clockwise  Turn the adjusting  screw counterclockwise to decrease the outlet pressure   The first stage portion of the Types R232A and R232E  integral regulators is non adjustable     The inlet and outlet pressure tap plugs on the R122H  R222   R232A  and R232E Series regulators may be removed  using a 7 16 inch   11 mm hexagon wrench  The  pressure tap Is restricted  so the plug can be removed  with pre
11. ount of internal relief protection provided varies with  the regulator type and the cause for the overpressure  relief valve operation  see Table 1  When the internal  relief valve opens  gas escapes to the atmosphere  through the regulator s vent     Some type of additional external overpressure protection  must be provided if the outlet pressure in an overpressure  condition exceeds the inlet pressure rating of the gas  system or downstream equipment  Common methods   of external overpressure protection include relief   valves  monitoring regulators  shutoff devices  and   series regulation     Maintenance       To avoid personal injury or equipment  damage  do not attempt any maintenance  or disassembly without first isolating   the regulator from system pressure and  relieving all internal pressure     Regulators that have been disassembled  for repair must be tested for proper  operation before being returned to service   Only parts manufactured by Fisher   should  be used for repairing Fisher regulators   Relight pilot lights according to normal  startup procedures     Due to normal wear or damage that  may occur from external sources   these regulators must be inspected and  maintained periodically  The frequency  of inspection and replacement of the    LP Gas Regulators    regulators depends upon the severity of  service conditions or the requirements of  local  state  and federal regulations  Even  under ideal conditions  these regulators  should be replaced after 20
12. out any debris  dirt or    copper sulfate in the copper tubing and the pipeline     Apply pipe compound to the male threads of the pipe  before installing the regulator     Make sure gas flow through the regulator is in the  same direction as the arrow on the body   Inlet  and     Outlet    connections are clearly marked     Installation Location    The installed regulator should be adequately  protected from vehicular traffic and damage from  other external sources     Install the regulator with the vent pointed vertically  down  see Figure 2  If the vent cannot be installed   in a vertically down position  the regulator must be  installed under a separate protective cover  Installing  the regulator with the vent down allows condensation to  drain  minimizes the entry of water or other debris from  entering the vent  and minimizes vent blockage from  freezing precipitation     Do not install the regulator in a location where there can  be excessive water accumulation or ice formation  such  as directly beneath a down spout  gutter  or roof line   of building  Even a protective hood may not provide  adequate protection in these instances     Install the regulator so that any gas discharge through  the vent or vent assembly is over 3 feet   0 9 meters  horizontally from any building opening below the level  of discharge     Install the regulator high enough above ground level   at  least 18 inches   46 cm   so that rain splatter cannot  freeze in the vent     R122H  R222  R232
13. rson Process Management Regulator Technologies  Inc   2005  2012  All Rights Reserved    
14. shutting down the  gas system and the complete removal of the adjusting  screw  The Type R122H regulator must be completely  disassembled by a qualified person to look for internal    R122H  R222  R232A  and R232E Series    LP Gas Regulators    corrosion  Closely examine regulators installed with    their vent horizontal for signs of corrosion  Correct any    improper installations     Regulator Replacement    Older regulators are more likely to catastrophically fail  because of worn or corroded parts  Replace R222   R232A  R232E  and R122H Series regulators over   20 years of age  Other service or environmental  conditions may dictate replacement of the regulator  before it becomes 20 years old  Regulators that are  installed on underground systems and in areas that are  subject to sea salt  coastal  atmospheres should be  inspected annually for external and internal corrosion  and may require replacement sooner  Refer to Fisher    Bulletin LP 32 for additional information     LP Gas Equipment    Emerson Process Management  Regulator Technologies  Inc     USA   Headquarters   McKinney  Texas 75069 1872  USA  Tel   1 800 558 5853   Outside U S   1 972 548 3574    For further information visit www fisherregulators com    Regulator Repair    Regulators that have been disassembled for repair  must be tested for proper operation before being  returned to service  Only parts manufactured by Fisher  should be used to repair Fisher regulators  Be sure to  give the complete type numb
15. ssure in the regulator  Install a pressure gauge to  determine the regulator s inlet pressure and outlet setting  during adjustment   Actual pressure at the second stage  regulator may be less due to line loss    After setting  add  thread sealant to the pipe plug and reinstall it  Replace  the closing cap  Check the plug for leakage     Overpressure Protection       Some type of overpressure protection is  needed if actual inlet pressure can exceed  the outlet pressure rating  Overpressuring  any portion of this equipment above the  limits shown in the Specifications may  cause damage to regulator parts  leaks   in the regulator  or personal injury due to  bursting of pressure containing parts or  explosion of accumulated gas     R122H  R222  R232A  and R232E Series    If any portion of the regulator is exposed  to an overpressure condition that exceeds  the limits in the Specifications  it must   be inspected for damage that may   have occurred     Large volumes of gas may discharge  through the regulator vent during internal  relief valve operation  which can  if not  controlled  result in fire or explosion from  accumulated gas     The R222  R232A  R232E  and R122H Series regulators   except for the first stage of the Types R232A and R232E   contain internal relief valves  The internal relief valve   in all units will give overpressure protection against  excessive build up resulting from seat leakage due to  worn parts or chips or foreign material on the orifice  The  am
16. y Inlet Pressure condition these inlet pressures and the R222 Series relief performance will limit downstream    pressure to 2 psi   0 14 bar or less     2  Product has passed Fisher testing for lockup  relief start to discharge and reseal down to  40  F    40  C     Integral Two stage Regulator    The Type R232A integral two stage regulator contains   a non adjustable first stage regulator on the inlet  The  second stage provides 11 inches w c    27 mbar outlet  pressure  The second stage portion has a high capacity  internal relief valve construction  The first stage does not  have an internal relief valve  The regulators are painted  GRAY with a BLACK CAP     Integral Two psig Service Regulator    The Type R232E integral two psig service regulator  contains a non adjustable first stage regulator on the  inlet  The second stage provides 2 psig   0 14 bar outlet    pressure  The second stage portion has a high capacity  internal relief valve construction  The first stage does  not have an internal relief valve  The regulators are  painted GRAY with a WHITE CAP     First Stage Regulators    Type R122H regulators are designed for high pressure   pounds per square inch  vapor service  These  regulators have high capacity internal relief valves     When used on first stage service  the Type R122H regulator  reduces container pressure to approximately 10 psig     0 69 bar inlet pressure to a second stage regulator  On final  stage service the regulator reduces container pressure 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
invent  Bill Clinton est appelé au chevet de la paix menacée au Proche  La médiation familiale et le droit religieux au Liban  CN245 Series controlador Guía del usuario  Mode d`emploi du Mini Jukebox Wurlitzer  SDA-15B User Manual  Documentación  Page 1 Page 2 ご~イ吏用前に必ず本取扱説明害をよくお読みく ださい  USER MANUAL - GBS Sound Shop  Aditivo para la fabricación de morteros ignífugos y mejora de    Copyright © All rights reserved. 