Crestron electronic Green Light 120 Volt User's Manual

image

Contents

1. ONLY Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming gt 5 Architectural Dimmin CRESTRON GREEN LIGHT Feed Wiring Section A Feed Wiring for MLO and MCB Applications MLO BREAKER DETAIL MCB BREAKER DETAIL A NEUTRAL LUG 6 A 4 A B PHASE c PHASE NEUTRAL LUG PHASE ve Nia NEUTRAL BUS NEUTRAL BUS PHASE K ee a B ien N PHASE 5 NUE Leu id PHASE GROUND LUG GROUND LUG a 4 GROUND BARS GROUND BARS 8 5 EI Refer to the following table for information on wiring the feed to the panel Feed Wire Information 120 Volt Models 277 Volt Models TERMINAL CONNECTOR MAX TORQUE Max CONNECTOR MAX TORQUE Max WIRE RANGE Current WIRE RANGE Current Neutral and 10 2 0 AWG CU or 15 lb ft 6 350 kemil CU or AL 275 300 Ib in Main Lugs 6 2 0 AWG AL 20 3 Nm 1 0 750 kemil CU or AL 31 1 33 9 Nm 6 300 CU or AL 21 lb ft 28 5 Nm 225 250 Neutral Bus 14 10 AWG CU or 20 lb in Amps 14 6 AWG CU or AL 24 35 Ib in INTEG 12 10 AWG AL 2 3 Nm P 2 7 4 0 Nm P 8 AWG CU or AL 25 lb in 14 2 0 AWG CU or AL 40 50 2 8 Nm 4 5 5 6 Nm 6 4 AWG CU or AL 35 Ib in 4 0 Nm Use copper or aluminum conductors only rated 75 C WARNING Failure to properly tighten lugs may result in poor electrical connection and overheating of the terminals Installation Guide DOC 6688A 6 e CREST
2. A Setting Module Net IDs The following procedure will normally be performed by an authorized Crestron representative as part of the System Commissioning phase For system wiring and basic testing as described on pages 5 and 11 it is not necessary to perform this step Only perform this step if instructed by an authorized Crestron representative or when replacing modules on a system that have already been commissioned in the latter case the Net ID should be set to match the Net ID of the module being replaced The Net ID of each module in the cabinet can be changed from the front panel of each module The Net IDs of each module in the system must be unique To set the Net ID using the front panel 1 Press the recessed SETUP button to enter the Setup mode The SETUP LED illuminates 2 As shown in the following diagram press the left button under the NET ID display to change the left digit of the Net ID or press the right button under the NET ID display to change the right digit of the Net ID number Changing the Net ID LABEL FOR NET ID LEFT DIGIT RIGHT DIGIT 08 z 5 i CHANGES CHANGES SETUP LEFT DIGIT RIGHT DIGIT BUTTON amp LED 3 When the desired Net ID is displayed press the SETUP button to exit the Setup mode The SETUP LED extinguishes If the SETUP button is not pressed the Setup mode will time out after one minute activity and the Net ID will revert back to its original v
3. D blinks to indicate the new override settings have been stored System Operation and Commissioning This cabinet has been designed as a component of a programmed Crestron system System commissioning by an authorized Crestron representative must be performed to ensure system operation Once the cabinet has been wired and the modules have been tested contact Crestron at 1 888 CRESTRON 1 888 273 7876 to schedule commissioning 12 e CRESTRON GREEN LIGHT Architectural Dimming Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming Problem Solving Troubleshooting The following table provides corrective action for possible trouble situations If further assistance is required please contact a Crestron customer service representative Troubleshooting TROUBLE POSSIBLE CAUSE S CORRECTIVE ACTION Module s does not Power not delivered to the If the module is powered internally verify that function module the circuit breaker connected to the first channel on the module is on and delivering power to the module If module is powered externally verify that the POWER port is correctly wired and receiving power System commissioning not Arrange for system commissioning complete Module s PWR LED is AC power not present on L1 Check that the branch breaker feeding L1 has flashing not tripped Note that unit will continue to function but will draw power from the backup Cresnet power supply Unit cannot
4. LE 3X4 12 35 1 16 891 mm 33 3 4 858 mm 32 3 16 818 mm 1 15 16 50 mm 89 13 16 2282 mm cabinet External Dimensions of CRESTRON GREEN LIGHT Architectural Dimming Cabinets _ W1 7 11 mm MOUNTING w2 _ HOLES ihe A f o a 547 mm ED CRESTRON numen a eana s er was S a 2 H2 IND NA nT nici A sar ram wc CRIT 0 3 sa ram Ae CONCENTRIC TECHNICAL KNOCKOUTS TE H1 81 TOTAL FOR 34 19m 8 33mm CONDUT ine oe e peas as FOR 34 19 mm CONDUIT TYPICAL BOTH SIDES 259 mm 9 9 96960 0 60 69 6 10 ike 0 9 oo 9 154mm 270mm 256 gt 1 DIMENSION GLE 2X2 GLE 3X2 GLE 2X4 Module Spaces 4 6 8 w1 22 7 8 582 mm 22 7 8 582 mm 35 1 16 891 mm W2 21 5 8 550 mm 21 5 8 550 mm 33 3 4 858 mm w3 20 1 16 510mm 20 1 16 510mm 323 16 818 mm H1 1 7 16 37 mm 5 27 mm 1 7 16 37 mm H2 67 13 16 1723 mm 96 2439 mm 67 7 8 1725 mm Installation Guide DOC 6688A 2 e CRESTRON GREEN LIGHT Architectural Dimming CRESTRON GREEN LIGHT Architectural Dimming Interior Dimensions of CRESTRON GREEN LIGHT Architectural Dimming Cabinets GLE XXX Xx2 left GLE XXX Xx4 right w4 7 W3 W3 WIWI GROUND LUG GROUND BA
5. RE BALLASTS olobibbbbobbbbbobbbobb ONLY 9 5 pte 66 JUMPER _ INSTALLED 6 ge i GLX DIM6 TO BRANCH BREAKER PREWIRED TO NEUTRAL BUS PREWIRED 1 5 SD oe GLX HSW8 AND GLX DIMFLV8 _AINSTALLED TO BRANCH BREAKER PREWIRED TO NEUTRAL BUS PREWIRED a a Installation Guide DOC 6688A Architectural Dimmin CRESTRON GREEN LIGHT The GLX DIMFLV8 also requires wiring the terminals for 0 10 VDC control wire Refer to the following diagram when connecting the dimmable ballast Each control wire terminal accepts one 12 28 AWG wire 0 10 VDC Control Wiring for GLX DIMFLVS8 Only JS 9 WS TO ON 4 WIRE LOADS PURPLE 9 ON 4 WIRE LOADS GRAY gt LIS 9 TS 2 Test the circuit for electrical faults by turning on each circuit breaker checking that the breakers do not trip and that power is delivered to the proper loads 3 Turn off the circuit breaker s and remove all jumpers 4 Turn on the circuit breakers Control Wiring Section C The bottom of the cabinet contains Cresnet connections for interfacing to the rest of the Crestron control system It also provides an override input which can be tied to devices such as the GLS PLS 120 277 phase loss sensor or other devices that provide a dry contact closure manual switch fire alarm relay etc NOTE Interface
6. RON GREEN LIGHT Architectural Dimming CRESTRON GREEN LIGHT Architectural Dimming Load Wiring Section B CAUTION Bypass jumpers are provided on each output to allow testing and to protect the module during installation The jumper shorts the L SW and DM terminals so that the load circuit is energized when the branch breaker is on Do not remove the bypass jumper until all feed and load wiring has been completed and the circuits have been tested for electrical faults STRIP LENGTH 3 8 9 mm 5 16 8 mm 5 16 8 mm 3 19 mm TORQUE 5 31 Ib in 0 6 Nm to 7 08 Ib in 0 8 Nm max 4 43 Ib in 0 5 Nm 35 Ib in 4 0 Nm 45 25 Ib in 5 1 2 8 Nm NOTE Use copper conductors only rated 75 C Wire Gauge and Torque Values CONNECTOR MAX WIRE RANGE 26 10 AWG 28 12 AWG 14 10 AWG 14 4 AWG TERMINAL LOAD amp DM OUTPUTS DIM CONTROL GLX DIMFLV8 only GROUND BAR GROUND LUG 1 Each output has a label with the number of the controlling circuit breaker printed on it With the corresponding circuit breaker turned off connect the controlled circuit LOAD wires to the output per the markings on the module as shown in the following diagrams Terminals for load wiring accept one 10 14 CRESTRON GREEN LIGHT Architectural Dimming gt 7 AWG wire Load Wiring for GLX DIM6 GLX DIMFLVS8 and GLX HSWS8 Jumper Installed TO LOAD 3 WI
7. RS SERVICE SCREWDRIVER x 0 GLE 277 2X2 3X2 2X4 3X4 11 11 16 15 1 16 11 11 16 11 11 16 297 mm 383 mm 297 mm 297 mm 8 8 6 11 16 6 11 16 204 mm 204 mm 170 mm 170 mm 3 7 8 3 7 8 2 9 16 2 9 16 99 mm 99 mm 66 mm 66 mm 2 2 2 2 51 mm 51 mm 51 mm 51 mm 21 1 2 21 1 2 547 mm 547 mm 17 3 8 17 3 8 442 mm 442 mm W2 Wi H1 em aia a W3W3 ROUND LUG l GROUND BARS 1 14 SERVICE SCREWDRIVER G wi W2 1 Interior Dimensions of CRESTRON GREEN LIGHT Architectural Dimming Cabinets 3X4 14 7 8 378 mm 6 13 16 174 mm 4 15 16 126 mm 1 7 8 48 mm 21 5 8 550 mm 19 3 4 502 mm CRESTRON GREEN LIGHT Architectural Dimming gt 3 GLE 120 3X2 2X4 18 1 4 14 7 8 464 mm 378 mm 8 3 16 6 13 16 208 mm 174 mm 6 5 16 4 15 16 161 mm 126 mm 1 7 8 1 7 8 48 mm 48 mm 21 5 8 550 mm 19 3 4 502 mm 2X2 14 7 8 378 mm 8 3 16 208 mm 6 5 16 161 mm 1 7 8 48 mm DIMENSION H1 w1 W2 W3 W4 W5 Installation Guide DOC 6688A Architectural Dimmin CRESTRON GREEN LIGHT Installation Observe the following when installing the cabinet e The cabinet must be mounted by
8. Z CRESTRON CRESTRON GREEN LIGHT Architectural Dimming Introduction CRESTRON GREEN LIGHT architectural dimming cabinets come pre configured with GLX architectural dimming and switching modules already installed In addition branch circuit breakers come preinstalled and prewired to the modules The cabinets only require installation and wiring of feed and load circuits Industry Compliance The cabinet and modules are Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc 7 E227280 cabinet and 3103692 modules Application The following diagram shows CRESTRON GREEN LIGHT architectural dimming cabinets in a lighting application that is controlled by an IPAC system CRESTRON GREEN LIGHT Architectural Dimming Cabinets in a Typical Lighting Application C2N SSC 2 Cm s D O O 6 i SS E Cresnet Ww UN Ry pp ae C2N SDC DC ol Cresnet C2N SDC Color Key Cresnet LAN Control ac 2 Crestron RoomView G gl Crestron Electronics Inc Installation Guide DOC 6688A 15 Volvo Drive Rockleigh NJ 07647 2020963 Tel 888 CRESTRON 02 09 Fax 201 767 7576 Specifications subject to www crestron com change without notice Architectural Dimmin CRESTRON GREEN LIGHT Physical Description This section shows the exterior and interior dimensions of the CRESTRON GREEN LIGHT Architectural Dimming G
9. a licensed electrician in accordance with all national and local codes Refer to the diagram below for specific requirements e Allow adequate clearance in front of the cover for servicing e The cabinet is designed for surface mounting on a wall e Cabinets are intended for indoor use only e The ambient temperature range should be 32 F to 104 F 0 C to 40 C The relative humidity should range WALL Installation Guide DOC 6688A from 10 to 90 non condensing Mounting Location 3 0 9 m MINIMUM REQUIRED CLEARANCE 6 7 2 01 m MAXIMUM HEIGHT OF HIGHEST BREAKER 2 FROM GROUND 4 e CRESTRON GREEN LIGHT Architectural Dimming CRESTRON GREEN LIGHT Architectural Dimming Wiring NOTE All wiring must be installed in accordance with all local and national electrical codes NOTE Refer to the torque settings specified on pages 6 7 and 8 CRESTRON GREEN LIGHT cabinets are shipped with GLX modules installed and prewired to the branch circuit breakers The following must be performed after installation e Connect incoming feed conductors to the breaker panel section A of the following diagram e Connect load wiring to GLX module outputs section B of the following diagram e Connect control wiring section C of the following diagram FEED 3 PHASE 4 WIRE MAIN LUG ONLY TO LOADS 2W GND 16A MAX i A B 6 H a CLASS 2 5 gt CLASS 2 WIRING ONLY g i WIRING
10. alue 14 gt CRESTRON GREEN LIGHT Architectural Dimming Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming Appendix B Module Specifications Specifications for the GLXP modules are listed in the following table GLXP Module Specifications SPECIFICATION GLX DIM6 GLX HSW8 GLX DIMFLV8 Description 6 Channel Dimming Switching 8 Channel High Inrush Switch 8 Channel 0 10V Fluorescent Module Module Dimmer Module Number of Outputs 6 8 8 Cresnet Bowel 5 Watts 5 Watts 5 Watts Usage Input Voltage 100 277 VAC 50 60 Hz 100 277 VAC 50 60 Hz 100 277 VAC 50 60 Hz Supported Load Incandescent magnetic low Incandescent magnetic low Dimmable Loads Types voltage MLV electronic low voltage MLV electronic low 0 10 VDC dimmable voltage ELV neon cold voltage ELV neon cold fluorescent ballasts i e cathode fluorescent ballast cathode fluorescent ballast Advance Mark 7 or other HID motor ballasts that comply with the specifications for control by DC voltage in ANSI C82 11 2002 and IEC60929 2006 Non Dim Loads Incandescent HID magnetic low voltage MLV electronic low voltage ELV neon cold cathode and fluorescent ballasts motor Maximum Load Lighting 16 A per output 16 A per output 16 A per output Motor N A HP 120V HP 120V 1 HP 230V 1 HP 230V 1 HP 277V 1 HP 277V Environmental Temperature 32 to 104 F 32 to 104 F 32 to 104 F 0 t
11. be taken out of Short contact closure exists Determine the reason for the short Remove or Override mode between G and OVR terminals remedy the short e g GLS PLS 120 277 phase on any of the OVERRIDE loss sensor may not have been installed terminals present at bottom of properly or actual phase loss has been the cabinet detected Load does not dim Mode switch is set to Set switch to DIM NON DIM Module is not wired correctly Verify that module is wired for dimming Fluorescent lamps stay at Or wires are reversed or Verify polarity of and wires at ballasts and minimum intensity 0 10V shorted GLXP DIMFLV8 dimmable fluorescents only Fluorescent lamps stay at Or wires are not connected Verify polarity of and wires at ballasts and maximum intensity 0 10V GLXP DIMFLV8 dimmable fluorescents only Further Inquiries If you cannot locate specific information or have questions after reviewing this guide please take advantage of Crestron s award winning customer service team by calling Crestron at 1 888 CRESTRON 1 888 273 7876 You can also log onto the online help section of the Crestron website www crestron com onlinehelp to ask questions about Crestron products First time users will need to establish a user account to fully benefit from all available features Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming gt 13 Architectural Dimmin CRESTRON GREEN LIGHT Appendix
12. connectors for NET x2 POWER x3 and OVERRIDE x3 ports are provided Wire Gauge and Torque Values TERMINAL CONNECTOR MAX TORQUE STRIP WIRE RANGE LENGTH NET 26 12 AWG ries a a ra POWER 26 12 AWG ie w 0 An OVERRIDE 26 12 AWG oe ra 6 0 8 e CRESTRON GREEN LIGHT Architectural Dimming Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming Connector Wiring POWER 24 VDC JUMPERED FROM NET PORT or EXTERNAL SUPPLY PROVIDES CRESNET POWER TO THE MODULES fe 3 f il i MODULES 5 RED GLX MODULES NET IC BLOE 5 TO CONTROL SYSTEM AND eae OTHER CRESNET DEVICES WHITE OVERRIDE FROM OTHER CABINET FROM ALARM ETC OPTIONAL TO OTHER CABINET S IF NECESSARY 30148340 NET Port Wiring When wiring the supplied NET connectors for connection to a Crestron control system or other device on the Cresnet network use Crestron certified wire such as CRESNET NP or CRESNET P To ensure optimum performance over the full range of your installation topology use Crestron certified wire Failure to do so may incur additional charges if support is required to identify performance deficiencies because of using improper wire When daisy chaining connections between NET ports strip the ends of the wires carefully to avoid nicking the conductors Twist together the ends of the wires that share a pin on the network connector insert the connection into the Cresnet con
13. e the PWR LED will flash OVERRIDE Port Wiring Low voltage input devices such as the Crestron GLS PLS 120 277 phase loss sensor or any device that provides a dry contact closure can be connected to the supplied OVERRIDE connector on the bottom of the cabinet When a dry contact closure is applied to the OVERRIDE terminals all modules in the cabinet will enter into Override mode In this mode they will recall their override levels and will ignore any external commands e g from keypads touchpanels or timeclock events until the override contacts are removed For more details refer to Override Mode on page 11 10 gt CRESTRON GREEN LIGHT Architectural Dimming Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming Testing Manual Control A lighting module can be manually controlled from its front panel Switch Function The GLX HSWS8 is a power switching module that can be used to turn loads on and off The GLX DIM6 and the GLX DIMFLV8 are dimming modules whose outputs can be set to operate as dimmable or non dimmable outputs The state of each output can be manually controlled from the front panel To use a module s switch function e Ensure that the output s mode switch is set to NON DIM GLX DIM6 and GLX DIMFLV8 only The DIM LED will be off e Press the A button to turn the output on The corresponding ON LED illuminates and the output state is shown on the NET ID display On
14. e mode is not enabled Override Mode The Override mode overrides the control system program and sets all of the output states to the stored override values For instructions on saving override settings refer to Save Override Settings on page 12 To enable Override mode press and release the OVR button The OVR LED flashes slowly NOTE If the Override mode was enabled from an external device i e a contact closure is present on the OVERRIDE terminals the OVR LED will flash quickly Pressing the OVR button has no effect To disable Override mode press the OVR button again The OVR LED extinguishes and the outputs return to the states set by the control system program NOTE If override states have not been stored the factory default override state is all loads on Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming gt 11 Architectural Dimmin CRESTRON GREEN LIGHT Save Override Settings The state of each output can be saved as an override setting which can be automatically recalled when the Override mode is enabled NOTE The control system program has a setting that can prevent locally saving the override state If this setting is enabled the display shows Er when trying to save override states For more information refer to the SIMPL Windows help file To save the state of all of the outputs as an override setting press and hold the OVR button for three seconds The OVR LE
15. for on for two seconds after the button is released e Press the V button to turn the output off The corresponding ON LED extinguishes and the output state is shown on the NET ID display oF for off for two seconds after the button is released NOTE The control system program may change the settings if the Override mode is not enabled Dimming Function GLX DIM6 and GLX DIMFLV8 Only The lighting level of each of the outputs can be manually controlled from the front panel e Ensure that the output s mode switch is set to DIM GLX DIM6 and GLX DIMFLV8 only e Press the A button to turn the output on 100 The corresponding ON and DIM LEDs illuminate and the output state is shown on the NET ID display On for on for two seconds after the button is released e Press the V button to turn the output off The corresponding ON LED extinguishes and the output state is shown on the NET ID display oF for off for two seconds after the button is released e To ramp the lighting level up or down until it reaches 100 or turns off press and hold the output s A or button The corresponding ON LED illuminates while the load is ON The DIM LED illuminates while the output level is less than 100 The output level is shown on the NET ID display as a percentage 01 99 oF for off or On for on for two seconds after the button is released NOTE The control system program may change the settings if the Overrid
16. nector and tighten the retaining screw Repeat the procedure for the other three conductors POWER Port Wiring Low voltage 24 VDC power must be supplied to the modules either internally via devices connected to the NET port or externally via a Cresnet power supply connected to the POWER port To power the modules internally from line power install a jumper from the INT pin on the supplied POWER connector to the EXT pin on the POWER connector as shown in the following diagram Providing Cresnet Power Internally When a lighting module is powered from line power the module s PWR LED will illuminate Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming gt 9 Architectural Dimmin CRESTRON GREEN LIGHT To power the modules externally from a Cresnet 24 VDC power supply connect the external power supply to the EXT and G pins on the POWER supplied connector as shown in the following diagram Providing Cresnet Power Externally CRESTRON 24 VDC POWER SUPPLY G 24 When properly connected and receiving 24 VDC power externally the green LED next to the MODULES port will light Under normal operation each lighting module will draw power from the line voltage on circuit 1 In this case the green PWR LED on the module will be lit If AC power to circuit 1 is interrupted for some reason e g because the breaker trips the module will automatically draw power from the 24VDC supply if available In this cas
17. o 40 C 0 to 40 C 0 to 40 C Humidity 10 to 90 RH 10 to 90 RH 10 to 90 RH non condensing non condensing non condensing Heat Dissipation 10 BTU Hr 10 BTU Hr 10 BTU Hr Power usage will be zero whenever AC power is present on circuit 1 on the module Use of Cresnet power is optional Installation Guide DOC 6688A CRESTRON GREEN LIGHT Architectural Dimming gt 15 Architectural Dimmin CRESTRON GREEN LIGHT Return and Warranty Policies Merchandise Returns Repair Service 1 No merchandise may be returned for credit exchange or service without prior authorization from CRESTRON To obtain warranty service for CRESTRON products contact an authorized CRESTRON dealer Only authorized CRESTRON dealers may contact the factory and request an RMA Return Merchandise Authorization number Enclose a note specifying the nature of the problem name and phone number of contact person RMA number and return address 2 Products may be returned for credit exchange or service with a CRESTRON Return Merchandise Authorization RMA number Authorized returns must be shipped freight prepaid to CRESTRON 6 Volvo Drive Rockleigh N J or its authorized subsidiaries with RMA number clearly marked on the outside of all cartons Shipments arriving freight collect or without an RMA number shall be subject to refusal CRESTRON reserves the right in its sole and absolute discretion to charge a 15 restocking fee plu
18. r In no event shall CRESTRON be liable for incidental or consequential damages of any kind property or economic damages inclusive arising from the sale or use of this equipment CRESTRON is not liable for any claim made by a third party or made by the purchaser for a third party CRESTRON shall at its option repair or replace any product found defective without charge for parts or labor Repaired or replaced equipment and parts supplied under this warranty shall be covered only by the unexpired portion of the warranty Except as expressly set forth in this warranty CRESTRON makes no other warranties expressed or implied nor authorizes any other party to offer any warranty including any implied warranties of merchantability or fitness for a particular purpose Any implied warranties that may be imposed by law are limited to the terms of this limited warranty This warranty statement supersedes all previous warranties Trademark Information All brand names product names and trademarks are the sole property of their respective owners Windows is a registered trademark of Microsoft Corporation Windows95 98 Me XP Vista and WindowsNT 2000 are trademarks of Microsoft Corporation 16 gt CRESTRON GREEN LIGHT Architectural Dimming Installation Guide DOC 6688A
19. s shipping costs on any products returned with an RMA 3 Return freight charges following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from the date of purchase from CRESTRON with the following exceptions disk drives and any other moving or rotating mechanical parts pan tilt heads and power supplies are covered for a period of one 1 year touchscreen display and overlay components are covered for 90 days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended or if it has been subjected to misuse accidental damage modification or improper installation procedures Furthermore this warranty does not cover any product that has had the serial number altered defaced or removed This warranty shall be the sole and exclusive remedy to the original purchase