Home

Alliance Laundry Systems 802715 User's Manual

image

Contents

1. 23 5 in 59 7 cm Pn WAY T A A 8 0 in 20 3 cm P 5 25 in EN 13 3 cm LJ KSA 13 1 in 33 3 cm L 28 in 71 1 cm With leveling legs turned into base 1 3 8 in NPT Gas Connection om 75 in 190 5 cm 44 1 in 112 cm 29 6 in 75 1 cm gt 31 1 in 79 cm gt 42 4 in 107 7 cm 37 44 in 95 1 cm 68 3 cm GAS DRYERS 37 08 cm SWD830N 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Before You Start Supplies For most installations the basic supplies you will need DRY2023N Safety Glasses Wood Block Power Cord Electric Models Wrench Screwdriver Level 5 16 Inch Socket Wrench Duct Tape Teflon Tape Gas Models 0 G Gn Q E GMM Figure 1 Any disassembly requiring the use of tools must be performed by a suitably qualified service person NOTE If the the unit is delivered on a cold day below freezing or is stored in an unheated room or area during the cold months do not attempt to operate it until the unit has had a chance to warm up NOTE Some moisture in the wash drum is normal Water is used during testing at the manufacturer
2. NOTE When connecting to a gas line an equipment shut off valve must be installed within 6 feet 1 8 m of the dryer An 1 8 in NPT pipe plug must be installed as shown for checking inlet pressure Refer to Figure 8 D4341 1 New stainless steel flexible connector Use design CSA certified connector Use only if allowed by local codes 2 1 8 in NPT Pipe Plug 3 Equipment Shut Off Valve 4 Black Iron Pipe Shorter than 20 ft 6 1 m Use 3 8 in 9 5 mm pipe 5 3 8 in NPT Gas Connection Figure 8 4 Tighten all connections securely Turn on gas and check all pipe connections internal amp external for gas leaks with a non corrosive leak detection fluid NOTE The dryer and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 45 kPa Refer to Step 12 Check Heat Source L P Liquefied Petroleum Gas 2500 Btu ft 93 1 MJ m service must be supplied at 10 1 5 inch water column pressure For proper operation at altitudes above 3000 feet 915 m the L P gas valve spud orifice size must be reduced to ensure complete combustion Refer to Table 2 L P Altitude Adjustments Altitude Orifice Size Part No feet m No inches mm 3000 915 55 0 0520 1 32 58755 8000 2440 56 0 0465 1 18 503786 Table 2 NOTE DO NOT connect the dryer to L P
3. Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 Installation Step 1 Position Unit Near Installation Area Move unit as close to the desired area of installation as possible Washer and dryer are not designed to be operated as separated side by side units W187 NOTE For best performance and to minimize vibration or movement install washer on a solid sturdy and level floor Some floors may need to be reinforced especially on a second floor or over a basement Do not install the washer on carpeting soft tile a platform or other weakly supported structures Step 2 Connect Fill Hoses Under certain conditions hydrogen gas may be produced in a hot water system that has not been used for two weeks or more HYDROGEN GAS IS EXPLOSIVE If the hot water system has not been used for such a period and before using the washer turn on all hot water faucets and let the water flow from each for several minutes This will release any accumulated hydrogen gas The gas is flammable Do not smoke or use an open flame during this time W029 Water Supply Water supply faucets must fit standard 3 4 inch 19 1 mm female garden hose couplings DO NOT USE SLIP ON OR CLAMP ON CONNECTIONS Water supply faucets should be readily accessible to permit turning them off when washer is not being used Recommended cold water temperature is 60 to 80 Fahrenheit 16 to 27 Celsius Recommended h
4. The dryer is equipped with a cord having an equipment grounding conductor and a 3 prong grounding plug The three prong grounding plug on the power cord should be plugged directly into a polarized three slot effectively grounded receptacle rated 110 120 Volts AC alternating current 15 Amps This dryer is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug Improper connection of the equipment grounding conductor can result in a risk of electric shock Check with a qualified electrician or service person if you are in doubt as to whether the dryer is properly grounded W038 Do not modify the plug provided with the dryer if it will not fit the outlet have a proper outlet installed by a qualified electrician NOTE Have a qualified electrician check the polarity of the wall receptacle If a voltage reading is measured other than that illustrated the qualified electrician should correct the problem Do not operate other appliances on the same circuit when this appliance is operating Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 19 To reduce the risk of an electric shock or fire DO NOT use an extension cord or an adapter to connect the dryer to the electrical power source W037 Plug cord into separatel
5. 5 08 cm or 1 1 2 in 4 cm Figure 5 7 Laundry Tub Installation For this type of installation the drain hose MUST be secured to the stationary tub to prevent hose from dislodging during use Refer to Figure 7 Use the beaded strap supplied in accessories bag to secure NOTE End of drain hose must be below 24 in hose 61 cm Wall Installation For installations of this type the drain hose MUST be secured to one of the fill hoses using the beaded strap from accessories bag Refer to Figure 6 SWD600N Boy 1 Drain Hose 1 Drain Hose 2 Tie Down Strap tape if necessary 2 Beaded Strap tape if necessary 3 Fill Hoses Figure 7 Figure 6 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Step 4 Gas Dryer Only Connect Gas Supply Pipe To reduce the risk of gas leaks fire or explosion s The dryer must be connected to the type of gas as shown on nameplate located in the door recess s Use a new flexible stainless steel connector s Use pipe joint compound insoluble in L P Liquified Petroleum Gas or Teflon tape on all pipe threads s Purge air and sediment from gas supply line before connecting it to the dryer Before tightening the connection purge remaining air from gas line to dryer until odor of gas is detected This step is required to prevent gas valve contamination s Do not use an open flam
6. A Left Dryer Side 0 in 0 cm B Right Dryer Side 1 in 2 54 cm C Dryer Top 6 in 15 24 cm D Dryer Rear 4 in 10 2 cm E Exhaust Duct Clearance to Combustible Materials 2 in 5 1 cm NOTE Shaded areas indicate adjacent structure SWD795N Figure 19 NOTE Use of the dispenser drawer or unit doors as a handle in the transportation of the unit may cause damage to the dispenser or doors Place unit in position on a solid sturdy and level floor Installing the unit on any type of carpeting soft tile a platform or other weakly supported structures is not recommended 16 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 Place a level on the cabinet top and check if the unit is level from side to side and front to back NOTE Level must rest on raised portion of top panel Refer to Figure 20 SWD833N Level Rubber Foot Leveling Leg Locknut Unit Base a E MM Figure 20 If unit is not level tilt unit to access the front and rear leveling legs For easier access to leveling legs prop up unit with a wooden block Refer to Figure 21 Loosen the locknuts and adjust legs by screwing into or out of unit base 802715 SWD832N 1 Wood Block Figure 21 Make sure that the unit does not rock When unit is level and does not rock tighten locknuts securely against bottom of unit base
7. OFF BOX may or may not be fused WALL RECEPTACLE Gi LA T120 12 120 Sy VAC E 2 V A C V A C L1 L2 Li L2 NOTE Use COPPER WIRE only Shorter than 15 ft 4 5 m use 10 AWG POWER CORD CONNECTION DIRECT CONNECTION Longer than 15 ft 4 5 m use 8 AWG D816l 1 3 Wire Grounded Neutral 120 240 Volt 60 Hertz 4 Metallic or Non Metallic Sheathed Cable AC 1 Phase Service Entrance Switch Box Copper Wire Only Refer to NOTE above 5 Power Cord Not supplied with dryer 2 30 Ampere Fuses or Circuit Breaker 6 Neutral 3 Neutral Wire 7 Terminal Block in Dryer Figure 9 1 Disconnect power to dryer 3 Use a strain relief and insert end of power cord 2 Remove access cover from rear of dryer puoueh Powersupply LOK D696 D6951 Figure 11 Figure 10 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 11 4 Use the three screws from the accessories bag to attach the power cord wires to the terminal block Refer to Figure 12 D286l 1 L1 Terminal 2 Neutral Terminal 3 L2 Terminal Figure 12 5 Tighten all screws firmly IMPORTANT Failure to tighten these screws firmly may result in wire failure at the terminal block 6 Secure the strain relief to the power cord or wires where they enter the dryer cabinet 7 Check the continuity of the ground connection bef
8. Refer to Figure 3 IMPORTANT Do not cross thread or overtighten couplings This will cause them to leak Turn water on and check for leaks If leaks are found turn off the water unscrew hoses and reinstall them until there are no leaks IMPORTANT Turn off water supply whenever there will be an extended period of non use TLW1976N Water Faucet Fill Hose Plain Rubber Washer Hose Coupling Filter Screens a E GM Figure 2 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT IMPORTANT Hoses and other natural rubber parts deteriorate after extended use Hoses may develop cracks blisters or material wear from the temperature and constant high pressure they are subject to All hoses should be checked on a yearly basis for any visible signs of deterioration Any hose showing the signs of deterioration listed above should be replaced immediately All hoses should be replaced every five years WATER MIXING VALVE SWD596N Water Faucets Cold Water Connection Hot Water Connection Water Fill Hoses Z GM Figure 3 IMPORTANT Turn off water supply faucets after check out and demonstration Owner should turn off water supply whenever there will be an extended period of non use NOTE Longer fill hoses are available as optional equipment at extra cost if the hoses supplied with the wash
9. W053 The following information applies to the state of Massachusetts USA e This appliance can only be installed by a Massachusetts licensed plumber or gas fitter e This appliance must be installed with a 36 inch 91 cm long flexible gas connector e A T Handle type gas shut off valve must be installed in the gas supply line to this appliance e This appliance must not be installed in a bedroom or bathroom Copyright 2006 Alliance Laundry Systems LLC All rights reserved No part of the contents of this book may be reproduced or transmitted in any form or by any means without the expressed written consent of the publisher 2 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 Dimensions 75 in 190 5 cm 44 1 in 112 em 23 5 in 59 7 cm Pa fy Y CQA A N 8 0 in 20 3 cm 5 25in _ asl 13 3 cm UJ WW zl in 33 3 cm 28 in 71 1 cm With leveling legs turned into base 39 1 cm 31 1 in 79 cm 37 44 in 95 1 cm 29 6 in 75 1 cm ELECTRIC DRYERS 37 08 cm SWD829N 45 4 in 1 39 1 cm
10. exhaust duct two feet 61 cm from dryer check with dryer running and no load e Exhausting dryer in hard to reach locations can be done by installing 521P3 Flexible Metal Vent Kit available as optional equipment at extra cost e Sufficient make up air must be supplied to replace the air exhausted by the dryer The free area of any opening for outside air must be at least 40 in 260 cm e Failure to exhaust dryer properly will void warranty NOTE Venting materials are not supplied with the dryer obtain locally IMPORTANT DO NOT block the airflow at the bottom of the dryer s front panel with laundry rugs etc Blockage will decrease airflow through the dryer thus reducing the efficiency of the dryer 14 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 Exhaust Direction The dryer can be exhausted to the outdoors through the back left right or bottom of the dryer EXCEPTION Gas dryers cannot be vented out the left side because of the burner housing Dryer is shipped from factory ready for rear exhaust Exhausting the dryer through sides or bottom can be accomplished by installing a Directional Exhaust Kit 528P3 available as optional equipment at extra cost Exhaust System heavy snowfall can occur For best drying results recommended maximum length of exhaust system is shown in Table 3 To prevent backdraft when dryer is not in operation outer end of exhaust pipe m
11. Gas Service without converting the gas valve Install L P Gas Conversion Kit 649P3 available at extra cost Step 5 Electric Dryer Only Connect Electrical Plug Dryer requires 120 240 Volt or 120 208 Volt 60 Hertz 3 or 4 wire electrical suppy Refer to serial plate for specific electrical requirements NOTE The wiring diagram is located behind the control panel inside the control cabinet To reduce the risk of fire electric shock serious injury or death all wiring and grounding MUST conform with the latest edition of the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 and such local regulations as might apply It is the customer s responsibility to have the wiring and fuses installed by a qualified electrician to make sure adequate electrical power is available to the dryer W521 10 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Grounding Information This dryer must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the dryer The dryer has its own terminal block that must be connected to a separate branch 60 Hertz single phase circuit AC alternating current circuit fused at 30 Amperes the circuit must be fused on both sides of the line Electrical service for the dryer should be of maximum rated
12. If these locknuts are not tight unit will move out of position during operation Leveling legs can be adjusted from inside the unit with a 7 8 inch deep well socket All four legs must rest firmly on the floor so the weight of the unit is evenly distributed The unit must not rock and must be level from side to side and front to back NOTE Do not slide unit across floor once the leveling legs have been extended Legs and base could become damaged Place rubber feet supplied in accessories bag on all four leveling legs Refer to Figure 20 Verify that unit does not rock Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 17 Step 8 Washer Only Remove the Shock Sleeves and Shipping Brace Remove front access panel by removing the two screws at the bottom of the panel Remove the five bolts and lockwashers from shipping brace with 9 16 inch wrench and remove brace Refer to Figure 22 Four bolts are located on the unit base and one is holding the brace to the weight Remove all four shock sleeves by pulling on the yellow rope Refer to Figure 22 IMPORTANT The shipping brace bolts lockwashers and shock sleeves should be saved and MUST be reinstalled whenever the unit is moved more than 4 ft 1 22 m Do not lift or transport unit from front or without shipping materials installed Refer to the Washer User s Guide for proper instructions on reinstalling the shipping materials Store the shipping ma
13. Installation Instructions for Stacked Washers and Dryers SIG EE E E eee les ISTR SION TTT 2 Before You Start THT 4 Wn Stal PELA LON E EENAA EEN E E A ET ETS 5 Installer Checklist sss Back Cover Date Purchased Model Number Serial Number Para bajar una copia de estas instrucciones en espa ol visite www comlaundry com Keep these instructions for future reference If this machine changes ownership this manual must accompany machine lllance Part No 802715 Laundry Systems www comlaundry com December 2006 FOR YOUR SAFETY the information in this manual must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or death W033 s Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance s WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Clear the room building or area of all occupants Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department s Installation and service must be performed by a qualified installer service agency or the gas supplier FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance
14. OTE The wiring diagram is located behind the control panel inside the control cabinet To reduce the risk of fire electric shock serious injury or death all wiring and grounding MUST conform with the latest edition of the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 and such local regulations as might apply It is the customer s responsibility to have the wiring and fuses installed by a qualified electrician to make sure adequate electrical power is available to the dryer W521 When plugging in the dryer e Do not overload circuits e Do not use an adapter s Do not use an extension cord e Do not operate both a washer and gas dryer on the same circuit Use separetely fused 15 amp circuits 802715 The dryer is designed to be operated on a separate branch polarized three wire effectively grounded 120 Volt 60 Hertz AC alternating current circuit protected by a 15 Ampere fuse equivalent fusetron or circuit breaker The three prong grounding plug on the power cord should be plugged directly into a polarized three slot effectively grounded receptacle rated 120 Volts AC alternating current 15 Amps Refer to Figure 26 to determine correct polarity of the wall receptacle Grounding Information The dryer must be grounded In the event of malfunction or breakdown grounding will reduce the risk of electric shock by providing a path of least resistance for electric current
15. T COPY or TRANSMIT 21 After the dryer has operated for approximately five minutes observe burner flame through lower front panel Adjust the air shutter to obtain a soft uniform blue flame A lazy yellow tipped flame indicates lack For personal safety lower front panel must of air A harsh roaring very blue flame indicates too be in place during normal operation much air Adjust the air shutter as follows wo46 1 Loosen the air shutter lockscrew After the dryer has operated for approximately three 2 Turn the air shutter to the left to get a luminous minutes exhaust air or exhaust pipe should be warm yellow tipped flame then turn it back slowly to the right to obtain a steady soft blue flame 3 After the air shutter is adjusted for proper flame tighten the air shutter lockscrew securely 4 Reinstall the lower front panel 4 D7021 1 Air Shutter Lockscrew 3 Air Shutter 2 Appliance Main Gas Valve 4 1 8 in 3 1 mm Pipe Plug For checking manifold pressure Figure 28 22 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 Installer Checklist Fast Track for Installing the Unit Refer to the manual for more detailed information I Position Unit Near Installation Area s Connect Fill Plain Hoses S Washers Filter E Screen St e Connect Drain Hose to Drain Receptacle Gas Only e Connect Gas Supply Pipe e Check for Gas Le
16. TE When installing the white wire loop the free eyelet end of the ground wire removed in Step 3 and attach along with the white wire to the neutral center terminal on the terminal block 7 Tighten all screws firmly IMPORTANT Failure to tighten these screws firmly may result in wire failure at the terminal block 8 Secure the strain relief to the power cord or wires where they enter the dryer cabinet 9 Check the continuity of the ground connection before plugging the cord into an outlet Use an acceptable indicating device connected to the center grounding pin of the plug and the green screw on the back of the cabinet 10 Reinstall access cover and screw 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 13 Step 6 Connect Dryer Exhaust System To reduce the risk of fire and combustion gas accumulation the dryer MUST be exhausted to the outdoors To reduce the risk of fire and the accumulation of combustion gases DO NOT exhaust dryer air into a window well gas vent chimney or enclosed unventilated area such as an attic wall ceiling crawl space under a building or concealed space of a building This gas appliance contains or produces a chemical or chemicals which can cause death or serious illness and which are known to the State of California to cause cancer birth defects or other reproductive harm To reduce the risk from substances in the fuel or from fuel combustion ma
17. aks Electric Only s Connect Electrical D679IEOA e Connect Dryer Exhaust s Position and Level the Unit Washer Only s Remove the Shock Sleeves and Shipping Brace Wipe Out Inside of Washer and Dryer lt u fl 9 Sy D2751 ELECTRIC DRYERS GAS DRYERS AND WASHERS e Check Heat Source CHECK TT 449N
18. e to check for gas leaks Use a non corrosive leak detection fluid e Any disassembly requiring the use of tools must be performed by a suitably qualified service person 1 Make certain your dryer is equipped for use with the type of gas in your laundry room Dryer is equipped at the factory for Natural Gas with a 3 8 inch NPT gas connection NOTE The gas service to a gas dryer must conform with the local codes and ordinances or in the absence of local codes and ordinances with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 National Gas Installation Code Natural Gas 1000 Btu ft 37 3 Mm service must be supplied at 6 5 1 5 inch water column pressure For proper operation at altitudes above 3000 feet 915 m the natural gas valve spud orifice size must be reduced to ensure complete combustion Refer to Table 1 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Natural Gas Altitude Adjustments Altitude Orifice Size S Part No feet m No inches mm 3000 915 43 0 0890 2 26 503778 6000 1830 44 0 0860 2 18 58719 8000 2440 45 0 0820 2 08 503779 9000 2740 46 0 0810 2 06 503780 10 000 3050 47 0 0785 1 99 503781 Table 1 2 Remove the shipping cap from the gas connection at the rear of the dryer Make sure you do not damage the pipe threads when removing the cap 3 Connect to gas supply pipe
19. er are not long enough for the installation Order hoses as follows No 20617 Fill Hose 8 feet 2 44 m No 20618 Fill Hose 10 feet 3 05 m 802715 Risers Risers or air cushions may have to be installed if the pipes knock or pound when flow of water stops The risers are more efficient when installed as close as possible to the water supply faucets refer to Figure 4 woos 1 Water Supply Faucets 2 Risers Air Cushions Figure 4 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Step 3 Connect Drain Hose to Drain Receptacle Remove the drain hose from its shipping position on the rear of the washer by unhooking the hose from the retainer clamp and by removing the shipping tape Install the drain hose into the drain receptacle standpipe wall or laundry tub following the instructions below IMPORTANT Drain receptacle must be capable of handling a minimum of 1 1 4 inch 32 cm outside diameter drain hose Standpipe Installation Place the drain hose into the standpipe Remove the beaded strap from accessories bag and place around standpipe and drain hose and tighten strap to hold hose to standpipe Refer to Figure 5 This will prevent the drain hose from dislodging from drain receptacle during use SWD598N 1 Drain Hose 2 Beaded Tie Down Strap 3 Standpipe 2 in
20. ke sure this appliance is installed operated and maintained according to the instructions in this manual W115 To reduce the risk of fire DO NOT use plastic or thin foil ducting to exhaust the dryer e DO NOT use plastic or thin foil ducting Rigid metal duct is recommended Refer to Figure 18 SA JO NO IOR OZ 7 DO we DON T SWD449N Figure 18 e Locate dryer so exhaust duct is as short as possible e Be certain old ducts are cleaned before installing your new dryer e Use 4 inch 102 mm diameter rigid or flexible metal duct e The male end of each section of duct must point away from the dryer e Use as few elbows as possible e Use duct tape or pop rivets on all duct joints DO NOT use sheet metal screws or fasteners on exhaust pipe joints which extend into the duct e Ductwork that runs through unheated areas must be insulated to help reduce condensation and lint build up on pipe walls e In mobile home installations dryer exhaust duct must be secured to mobile home structure e Dryer exhaust duct MUST NOT terminate under mobile home e Dryer exhausts 220 cfm measured at back of dryer e DO NOT install flexible duct in concealed spaces such as a wall or ceiling e Static pressure in exhaust duct should not be greater than 6 inches water column 1 5 cm measured with manometer placed on
21. ore plugging the cord into an outlet Use an acceptable indicating device connected to the center grounding pin of the plug and the green screw on the back of the cabinet 8 Reinstall access cover and screw Connecting Power Cord with Four Wire Plug NOTE Four wire cord is required for mobile homes or where codes do not permit grounding through neutral DRY2016N Typical Four Wire Receptacle Power Cord Not Supplied with Dryer Strain Relief Nut Strain Relief Z GM Figure 13 1 Disconnect power to dryer 2 Remove access cover from rear of dryer D6951 Figure 14 12 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 3 Remove ground screw and save for use in Step 5 Remove wire and use in Step 6 5 Attach power cord ground green wire to rear bulkhead using ground screw removed in Step 3 D6971 1 Ground Screw Figure 15 4 Use a strain relief and insert end of power cord through power supply hole D696l DRY1920N White L2 Terminal Black Green Red Neutral Terminal L1 Terminal NO of WD Figure 16 Figure 17 6 Use the three screws from the accessories bag to attach the remaining power cord wires to the terminal block as follows a Red wire to L1 terminal b Black wire to L2 terminal c White wire to Neutral terminal NO
22. ot water temperature is 120 to 140 Fahrenheit 49 to 60 Celsius Warm water is a mixture of hot and cold water Warm water temperature is dependent upon water temperature and pressure of both the hot and cold water supply lines Water pressure must be a minimum of 20 to a maximum of 120 pounds per square inch 138 to 827 kPa static pressure measured at the faucet NOTE Water pressure under 20 pounds per square inch 138 kPa will cause an extended fill time in the washer and may not properly flush out the detergent dispenser Turn on the water faucets and flush the lines for approximately two minutes to remove any foreign material that could clog the screens in the water mixing valve NOTE When installing in newly constructed or renovated buildings it is very important to flush the lines since build up may have occurred during construction 802715 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Connecting Hoses Remove the two plain rubber washers and two filter screens from the accessories bag Install them into each end of the fill hoses as shown in Figure 2 The screen must be facing outward Screw hose couplings with the filter screens onto the water faucets until they are finger tight Then using a pliers screw approximately 1 4 turn Screw hose couplings from other end of hoses onto the water mixing valve until they are finger tight Then using a pliers screw approximately 1 4 turn
23. t circuit protected by a 15 Amp fuse equivalent fusetron or circuit breaker The three prong grounding plug on the power cord should be plugged directly into a polarized three slot effectively grounded receptacle rated 110 120 Volts AC alternating current 15 Amps Refer to Figure 27 to determine correct polarity of the wall receptacle To reduce the risk of an electric shock or fire DO NOT use an extension cord or an adapter to connect the washer to the electric power source Grounding Information The washer must be grounded In the event of malfunction or breakdown grounding will reduce the risk of electric shock by providing a path of least resistance for electric current The washer is equipped with a cord having an equipment grounding conductor and a 3 prong grounding plug The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances Improper connection of the equipment grounding conductor can result in a risk of electric shock Check with a qualified electrician or service person if you are in doubt as to whether the washer is properly grounded Do not modify the plug provided with the washer if it will not fit the outlet have a proper outlet installed by a qualified electrician NOTE Have a qualified electrician check the polarity of the wall receptacle If a voltage reading is measured other than that in Figure 27
24. terials in the accessories bag Save materials for use whenever the unit is moved Remove label from front side of front access panel and place on back side of front access panel for future reference FLW2048N Shock Sleeves Motor Mount Hooked End of Shipping Brace Bolts and Lockwashers kh OND Figure 22 Reinstall front access panel IMPORTANT DO NOT tip washer more than 6 inches 152 4 mm in any direction after shipping brace has removed Shock absorbers may separate and damage to unit may result For leveling purposes the unit may be tilted a maximum of 6 inches 152 4 mm in any direction Step 9 Wipe Out Inside of Washer Drum and Dryer Drum Before using the washer and dryer for the first time use an all purpose cleaner or a detergent and water solution and a damp cloth to remove shipping dust from inside the drums SWD834N SWD603N Figure 24 18 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 Step 10 Plug In the Washer and Dryer Electric Dryer Connect the dryer to an electrical power source Refer to Step 4 for information on connecting power cord Connect to 30 Amp circuit D2751 Figure 25 Gas Dryer Dryer requires 120 Volt 60 Hertz electrical supply and comes equipped with a 3 prong grounding plug Refer to serial plate for specific electrical requirements N
25. the qualified electrician should correct the problem This unit is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug Step 11 Recheck steps 1 10 Refer to Installer Checklist on the back cover of this manual and make sure that unit is installed correctly Run washer through one complete cycle to make sure it is operating properly Step 12 Check Heat Source Electric Dryers Close the loading door and start the dryer in a heat setting refer to the Dryer User s Guide supplied with the unit After the dryer has operated for three minutes the exhaust air or exhaust pipe should be warm Gas Dryers IMPORTANT This operation is to be conducted by qualified personnel only To view the burner flame remove the lower front panel of the dryer Close the loading door start the dryer in a heat setting refer to the Dryer User s Guide supplied with the unit the unit will start the igniter will glow red and the main burner will ignite IMPORTANT If all air is not purged out of gas line gas igniter may go off before gas is ignited If this happens after approximately two minutes igniter will again attempt gas ignition IMPORTANT If igniter does not light make sure gas is turned on 802715 Copyright Alliance Laundry Systems LLC DO NO
26. ust have a weather hood with hinged dampers obtain locally NOTE Weather hood should be installed at least 12 inches 30 5 cm above the ground Larger clearances may be necessary for installations where Number of Weather Hood Type 90 Elbows Recommended Use Only for Short Run installations CA 4in E 10 2 cm 10 2 cm KS D673I 2 1 2 in D8021 6 35 cm Maximum length of 4 in 10 2 cm diameter rigid metal duct 0 65 feet 19 8 m 55 feet 16 8 m 1 55 feet 16 8 m 47 feet 14 3 m 2 47 feet 14 3 m 41 feet 12 5 m 3 36 feet 11 0 m 30 feet 9 1 m 4 28 feet 8 5 m 22 feet 6 7 m Maximum length of 4 in 10 2 cm diameter flexible metal duct 0 45 feet 13 7 m 35 feet 10 7 m 1 35 feet 10 7 m 27 feet 8 2 m 2 30 feet 9 1 m 21 feet 6 4 m 3 25 feet 7 6 m 17 feet 5 2 m 4 20 feet 6 1 m 15 feet 4 5 m NOTE Deduct 6 feet 1 8 m for each additional elbow 802715 Table 3 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 15 Step 7 Position and Level the Unit Position unit so it has sufficient clearance for installation and servicing Refer to Figure 19 C D Pa Pa gt _TE LE Pa ry A lt x B e Dryer and Exhaust Duct Clearances Area Description Minimum Clearance
27. voltage listed on the nameplate Do not connect dryer to 110 115 or 120 volt circuit Heating elements are available for field installation in dryers which are to be connected to electrical service of different voltage than that listed on nameplate such as 208 Volt If branch circuit to dryer is 15 feet 4 57 m or less in length No 10 AWG wire copper wire only or as required by local codes If over 15 feet 4 57 m use No 8 AWG wire copper wire only or as required by local codes Allow sufficient slack in wiring so dryer can be moved from its normal location when necessary The power cord connection between wall receptacle and dryer terminal block IS NOT supplied with dryer Type of power cord and gauge of wire must conform to local codes 802715 Connecting Power Cord with Three Wire Plug NOTE Four wire cord is required for mobile homes or where codes do not permit grounding through neutral NOTE The power cord is NOT supplied with the electric dryer Type of power cord and gauge of wire must conform to local codes and instructions POWER SUPPLY POWER SUPPLY The method of wiring the dryer is optional and subject to local code requirements NOTE Connect the dryer to the power supply with the MAXIMUM RATED VOLTAGE listed on the nameplate A typical 30 Amp INTERMEDIATE Three Wire FUSE BOX may Receptacle be omitted if NEMA Type service entrance 10 30R box is fused INTERMEDIATE SHUT
28. y fused 15 Amp circuit DRY2022N 4 Ground Neutral Neutral Side Round Grounding Prong a E GMM Figure 26 Washer Washer requires 120 Volt 60 Hertz electrical supply and comes equipped with a 3 prong grounding plug Refer to serial plate for specific electrical requirements NOTE The wiring diagram is located behind the control panel inside the control cabinet Standard 120 Volt 60 Heriz 3 Wire Effectively Grounded Circuit DRY2022N L1 Ground Neutral Side Round Grounding Prong Neutral Q E GM Figure 27 To reduce the risk of fire electric shock serious injury or death all wiring and grounding MUST conform with the latest edition of the National Electrical Code ANSI NFPA No 70 and such local regulations as might apply It is the customer s responsibility to have the wiring fuses and circuit breakers installed by a qualified electrician to make sure adequate electrical power is available to the washer 20 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 802715 When plugging in the washer e DO NOT overload circuits s DO NOT use an extension cord s DO NOT use an adapter s DO NOT operate both a washer and gas dryer on the same circuit Use separately fused 15 Amp circuits The washer is designed to be operated on a separate branch polarized three wire effectively grounded 120 Volt 60 Hertz AC alternating curren

Download Pdf Manuals

image

Related Search

Related Contents

Errata for UltraSPARC-IIe and UltraSPARC  American Standard Princeton 2392.202 ICH User's Manual  Massive Top Selection Wall light 34104/48/10    Guida per l`utente  INSTRUÇÕES PARA A CAPA LIFEPROOF FRÉ PARA IPHONE  アルインコの特定小電力無線システム  Eurosil max laB Hard 85 sHorE a 2  Facilities Services Construction Standards June 2012  ASUS TP500LA User's Manual  

Copyright © All rights reserved.
Failed to retrieve file