Home

Cisco Catalyst 6000 2500W DC Power Supply, Spare

image

Contents

1. CAB 7513AC E Connector IEC 60320 C19 I Cordset rating 16 A 250 V Length 14 ft 0 in 4 26 m Plug NEMA 5 20 ZL Cordset rating 20 A 125 V Length 14 ft 0 in 4 26 m Connector IEC 60320 C19 113356 113355 130113 E Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Figure A 36 CAB AC16A CH C Plug GB16C Cordset rating 16A 250V Length 14 ft 0 in 4 26 m Figure A 37 CAB 7513ACSA Plug IEC 884 NAAN Connector IEC 60320 1 C19 Ve mat E Cordset rating 16 A 250 V Length 14 ft 0 in 4 26 m Connector IEC 60320 C19 Figure A 38 CAB ACS 10 Plug SEV 1011 Dl ZL 7 7 Cordset rating 10 A 250 V Length 7 ft 0 in 2 13 m 4 E Connector IEC 60320 C19 4 113358 113357 126792 AC Power Cord Illustrations OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications HAC Power Co
2. Connector IEC 60320 C15 Cay 113342 Catalyst 6500 Series Switches Installation Guide OL 5781 05 E A57 Appendix A Power Supply Specifications HE AC Power Cord Illustrations Figure A 21 CAB AC10A 90L IT isn ZL Cordset rating 10 A 250 V Length 8 ft 2 in 2 5 m Plug CEI 23 16 7 Connector IEC 60320 C15 113343 Figure A 22 CAB AC15A 90L US Z Cordset rating 15 A 125 V Plug NEMA 5 15 Length 8 ft 2 in 2 5 m Connector IEC 60320 C15 113344 Figure A 23 CAB AC10A 90L UK Cordset rating 10 A 250 V Length 8 ft 2 in 2 5 m Plug BS 1363 Connector IEC 60320 C15 113345 Catalyst 6500 Series Switches Installation Guide Pass E OL 5781 05 Appendix A Power Supply Specifications Figure A 24 CAB 7KACR Plug IRAM 2073 Figure A 25 CAB 7KACA li Plug SAA AS 3112 Figure A 26 CAB 7KACE Ci Plug CEE 7 7
3. AC input 18 4 lb 8 3 kg DC input 21 0 Ib 9 5 kg Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 1300 W Power Supply AC Power Cords Table A 8 lists the specifications for the AC power cords that are available for the 1300 W AC input 1300 W AC Input and DC Input Power Supplies power supply The table includes references to power cord illustrations amp Note All 1300 W power supply power cords are 14 feet 4 3 meters in length amp Note All 1300 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 8 Locale Argentina Australia New Zealand Continental Europe Israel Italy Japan North America People s Republic of China South Africa Switzerland United Kingdom Power Cord Part Number CAB 7513ACR CAB 7513ACA CAB 7513ACE CAB AC 2500W ISRL CAB 7513ACI CAB 7513AC CAB AC16A CH CAB 7513ACSA CAB ACS 10 CAB 7513ACU 1300 W Power Supply AC Power Cords Source Plug Type IRAM 2073 SAA AS 3112 CEE 7 7 S116S3 CEI 23 16 7 NEMA 5 20 GB16C IEC 884 1 SEV 1011 BS 13637 1 For Japan ask your local electrical contractor to prepare the NEMA 5 20 power plug 2 Plug contains a 13 A fuse Cordset Rating 10 A 250 VAC 15 A 250 VAC 16 A 250 VAC 16 A 250 VAC 16 A 250 VAC 20 A 125 VAC 16 A 250 VAC 16 A 250 VAC 10 A 250 VAC 13 A 250
4. AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage Low line 120 VAC nominal 85 VAC min to 132 VAC max High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 12 A 120 VAC 6 A 230 VAC AC input frequency 50 60 Hz nominal kVA rating 1 32 kVA OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications WE 950W AC Input and DC Input Power Supplies Table A 3 950 W AC Input and DC Input Power Supplies Specifications continued Item Specification Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit For North America 15 A For International Circuits sized to local and national codes All Catalyst 6500 series AC input power supplies require single phase source AC All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power s
5. Power Supply Specifications FE APPENDIX A This appendix provides specifications for the Catalyst 6500 series power supplies Table A 1 lists the currently available Catalyst 6500 series switch power supplies and the power supply description location Table A 1 Power Supply Rating AC Input Model Product Number Catalyst 6500 Series Power Supplies DC Input Model Product Number Description Location 950 W PWR 950 AC PWR 950 DC 950 W AC Input and DC Input Power Supplies page A 4 1000 W WS CAC 1000W Not Available 1000 W AC Input Power Supply page A 9 1300 W WS CAC 1300W WS CDC 1300W 1300 W AC Input and DC Input Power Supplies page A 13 1400 w PWR 1400 AC Not Available 1400 W AC Input Power Supply page A 18 2500 W WS CAC 2500W WS CDC 2500W 2500 W AC Input and DC Input Power Supplies page A 22 2700 W PWR 2700 AC 4 PWR 2700 DC 4 2700 W AC Input and DC Input Power Supplies page A 28 3000 W WS CAC 3000W Not Available 3000 W AC Input Power Supply page A 34 4000 W WS CAC 4000W US 1 PWR 4000 DC 4000 W AC Input and WS CAC 4000W INT DC Input Power Supplies page A 38 6000 W WS CAC 6000W Not Available 6000 W AC Input Power Supply page A 43 8700 W WS CAC 8700W E Not Available 8700 W AC Input Power Supply page A 48 1 For use with the Catalyst 6503 and Catalyst 6503 E switches only OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A
6. Source DC voltage is OK Input voltage is 40 5 VDC or greater e Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the power supply e Off DC output voltages within acceptable margins Weight e AC input 22 2 Ib 10 1 kg e DC input 30 8 Ib 14 0 kg 4000 W Power Supply AC Power Cords Table A 18 lists the specifications for the AC power cords that are available for the 4000 W AC input power supply Included in the table are references to illustrations of the power cords amp Note The AC power cords for the 4000 W AC input power supply are hardwired directly to the power supply they do not have an IEC 60320 C19 appliance plug and cannot be removed from the power supply Table A 18 4000 W Power Supply AC Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration International WS CAC 4000W INT IEC 60309 32 A 250 VAC Figure A 47 North America Japan WS CAC 4000W US NEMA L6 307 30 A 250 VAC Figure A 48 1 This is the part number for the power supply The AC power cords are hardwired to the 4000 W power supplies 2 For Japan ask your local electrical contractor to prepare the NEMA L6 30 power plug Catalyst 650
7. 120 VAC nominal INPUT connected to high line 230 VAC nominal INPUT 2 not connected INPUT 1 not connected INPUT 2 connected to high line 230 VAC nominal INPUT connected to high line 230 VAC nominal INPUT 2 connected to low line 120 VAC nominal INPUT 1 connected to low line 120 VAC nominal INPUT 2 connected to high line 230 VAC nominal e 6000 W maximum with the following source AC arrangements INPUT 1 and INPUT 2 both connected to high line 230 VAC nominal Note The 6000 W power supply will not power up if you have only one power cord plugged into either INPUT 1 or INPUT 2 and source AC is low line 120 VAC nominal System power dissipation 7034 W OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HZ 6000W AC Input Power Supply Table A 19 6000 W AC Input Power Supply Specifications continued Specification Description Branch circuit requirement AC input Each power supply input should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits should be sized according to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can
8. 16 A 250 VAC 10 A 250 VAC 16 A 250 VAC 13 A 250 VAC 1400 W AC Input Power Supply W Power Cord Reference Illustration Figure A 30 Figure A 31 Figure A 36 Figure A 32 Figure A 40 Figure A 41 Figure A 33 Figure A 34 Figure A 35 Figure A 42 Figure A 43 Figure A 37 Figure A 38 Figure A 44 Figure A 29 PH tpe r Plug contains a 13 A fuse For operation in Japan ask your local electrical contractor to prepare the NEMA 5 20 power plug For operation in Japan ask your local electrical contractor to prepare the NEMA 6 20 power plug For operation in Japan ask your local electrical contractor to prepare the NEMA L6 20 power plug OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications WE 2500W AC Input and DC Input Power Supplies 2500 W AC Input and DC Input Power Supplies amp The 2500 W AC input power supply WS CAC 2500W and 2500 W DC input power supply WS CDC 2500W are supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6506 E e Catalyst 6509 e Catalyst 6509 E e Catalyst 6509 NEB e Catalyst 6509 NEB A e Catalyst 6513 The 2500 W power supplies shown in Figure A 9 and Figure A 10 share the same form factor as the 1000 W 1300 W 3000 W 4000 W and 6000 W AC input power supplies Note Note With a fully populated Catalyst 6513 switch two 2500 W power supplies are not fully redundant I
9. 2500 W 3000 W 4000 W and 6000 W power supplies amp Note Because of the form factor difference when you install an 8700 W power supply in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB chassis you must relocate the system ground connection from the chassis ground pad connection to the two system ground studs located on the 8700 W power supply faceplate Installing an 8700 W power supply in the other Catalyst 6500 series chassis do not require that you move the chassis system ground connection to the power supply Catalyst 6500 Series Switches Installation Guide A 438 OL 5781 05 Appendix A Power Supply Specifications 8700 W AC Input Power Supply W The 8700 W power supply cannot be installed in the Catalyst 6503 Catalyst 6503 E and Catalyst 6504 E switch chassis Figure A 17 8700 W AC Input Power Supply System ground studs Cable retention device AC power tes connection 1 gt oe AC power connection 2 gt AC power connection 3 gt Power switch Qe OUTPUT on 29900 6 fia Status LEDs gt 662m aL 182076 cisco SYSTEMS mg sume a Remote power on off Captive installation feature relay switch screw Remote power on off feature terminal block 8700 W Power Supply Specifications Table A 22 lists the specifications for the 8700 W AC input power supply Table A 22 8700 W AC Input Power Supply
10. Mi JL Plug SEV 5934 2 Type 23 fla of ey Connector IEC 60320 C19 Cordset rating 16 A 250 V Length 8 ft 2 in 2 5 m 113364 113362 113363 AC Power Cord Illustrations OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications HAC Power Cord Illustrations Figure A 45 CAB AC 16A AUS J Cordset rating 16 A 250 V Plug AU20S3 Length 14 ft 0 in 4 26 m TH Connector IEC 60320 C19 Figure A 46 CAB C19 CBN Connector Cordset rating 16 A 250 V IEC 60320 C20 Length 9 ft 0 in 2 7 m Figure A 47 WS CAC 4000W INT Cordset rating 32 A 250 V Length 12 ft 0 in 3 65 m Plug IEC 60309 Connector IEC 60320 C19 Hardwired to power supply 113365 140586 140587 Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Figure A 48 WS CAC 4000W US Power Supply Redundancy W Cordset rating 30 A 250 V Hardwired to Length 12 ft 0 in 3 65 m power supply Plug NEMA L6 30 113366 Power Supply Redundancy Catalyst 6500 series switching modules have different power requi
11. Power Supply Specifications HI Power Supply Compatibility Matrix amp This appendix also includes a description of power supply redundancy Note amp The Catalyst 6500 series switches allow you to mix AC input and DC input power supplies in the same chassis Note Many telco organizations require a 48 VDC power supply to accommodate their power distribution systems From an operational perspective the DC input power supply has the same characteristics as the AC input version Power Supply Compatibility Matrix Table A 2 lists the compatibility of the power supplies with the Catalyst 6500 switch chassis Table A 2 Catalyst 6500 Series Switch Supported Power Supply Configurations Platform Supported Power Supplies Restrictions Catalyst 6503 e 950 W AC input and DC input e The 950 W AC input power 1400 W AC input supply requires a PEM 15A AC Power Entry Module PEM The 1400 W AC input power supply requires a PEM 20A AC Power Entry Module PEM Catalyst 6503 E 950 W AC input and DC input 1400 W AC input The 950 W AC input power supply requires a PEM 15A AC Power Entry Module PEM The 1400 W AC input power supply requires a PEM 20A AC Power Entry Module PEM Catalyst 6504 E 2700 W AC input and DC input Catalyst 6506 1000 W AC input 1300 W AC input and DC input 2500 W AC input and DC input 3000 W AC input 4000 W AC input and DC input 6000 W AC inpu
12. Specifications Specification Description AC input type 3 AC inputs per power supply High line input with power factor correction PFC included Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max One phase AC input current 16 A each input KVA rating 10 4 kVA AC input frequency 50 60 Hz nominal 3 for full range Catalyst 6500 Series Switches Installation Guide OL 5781 05 N Appendix A Power Supply Specifications HI 8700W AC Input Power Supply Table A 22 Specification 8700 W AC Input Power Supply Specifications continued Description Power supply output capacity 2800 W operation 4200 W operation The power supply output capacity is dependent on the number of AC power cords 1 2 or 3 attached and the source AC voltage 110 VAC or 220 VAC applied to the power supply inputs Note The 8700 W AC input power supply is limited to 4000 W maximum output when it is installed in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB switch chassis The power supply is limited to 4500 W maximum output when it is installed
13. VAC Power Cord Reference Illustration Figure A 30 Figure A 31 Figure A 32 Figure A 33 Figure A 34 Figure A 35 Figure A 36 Figure A 37 Figure A 38 Figure A 39 OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications His 1400 W AC Input Power Supply 1400 W AC Input Power Supply The 1400 W AC input power supply PWR 1400 AC can be installed in the Catalyst 6503 switch and Catalyst 6503 E switch chassis only Due to form factor differences the 1400 W AC input power supply cannot be installed in any other Catalyst 6500 series switch chassis The 1400 W power supplies see Figure A 7 do not connect directly to source AC but use power entry modules PEMs located on the front of the Catalyst 6503 and Catalyst 6503 E switch chassis to connect the site power source to the power supply located in the back of the chassis The AC input PEM PEM 20A AC shown in Figure A 8 provides an input power connection on the front of the router chassis to connect the site power source to the power supply The PEMs have an illuminated power switch current protection surge and EMI suppression and filtering functions Figure A 7 1400 W AC Input Power Supply PWR 1400 AC Status LEDs 3 3 5 Captive installation screws Figure A 8 1400 W AC Input PEM PEM 20A AC IEC 60320 C19 connector AC power switch 130057 Captiv
14. a C20 connector OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications WE 2700W AC Input and DC Input Power Supplies 2700 W AC Input and DC Input Power Supplies The 2700 W AC input power supply PWR 2700 AC 4 and 2700 W DC input power supply PWR 2700 DC 4 are supported only in the Catalyst 6504 E switch See Figure A 11 for the 2700 W AC input power supply and Figure A 12 for the 2700 W DC input power supply amp Note The 2700 W AC input power supply needs 220 VAC to deliver 2700 W of power When powered with 110 VAC it delivers only 1350 W In addition the power supply needs 16 A regardless of whether it is plugged into 110 VAC or 220 VAC Figure A 11 2700 W AC Input Power Supply 154028 A Status LEDs 1 Power ON OFF switch 2 Power supply fan a AC In receptacle 3 Captive installation screw Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Figure A 12 2700 W DC input Power Supply 2700 W AC Input and DC Input Power Supplies W e nA a Se 2 Aevaeoy OK ON OUTPUT e son Veov Fal Oy 132219 Ground terminal block 1 Captive installation screw 7 Cable holder cover 2 DC power cable terminal block 8 Cable holder 3 Status LEDs 9 Tie wrap 4 DC power cable terminal block cover 10 Cable holde
15. and DC input 6000 W AC input 8700 W AC input Both the 6000 W and the 8700 W are limited to 4500 W maximum output when they are installed in the Catalyst 6509 NEB A switch chassis Catalyst 6513 2500 W AC input and DC input 3000 W AC input 4000 W AC input and DC input 6000 W AC input 8700 W AC input The 8700 W AC input power supply is limited to 6000 W maximum output when it is installed in the Catalyst 6513 switch chassis OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications Hi 950W AC Input and DC Input Power Supplies 950 W AC Input and DC Input Power Supplies The 950 W AC input PWR 950 AC and DC input PWR 950 DC power supplies can be installed in the Catalyst 6503 and Catalyst 6503 E switch chassis only Due to form factor differences the 950 W AC input and DC input power supplies cannot be installed in any other Catalyst 6500 series switch chassis The 950 W power supplies see Figure A 1 do not connect directly to source AC or source DC but use power entry modules PEMs located on the front of the Catalyst 6503 and Catalyst 6503 E switch chassis to connect the site power source to the power supply located in the back of the chassis The form factor is the same for the AC input and DC input power supplies The AC input PEM shown in Figure A 2 and DC input PEM shown in Figure A 3 provide an input power connection on the front of the
16. be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output e 2900 W operation one 220 VAC source or two 110 VAC sources 25 A 433V 12A 12V 63 6 A 42 V e 6000 W operation two 220 VAC sources 25 A 3 33 V 12A 12V 137 4 A 42 V Output holdup time 20 ms minimum Heat dissipation 23 812 BTU hour approx Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Table A 19 Specification 6000 W AC Input Power Supply 6000 W AC Input Power Supply Specifications continued Description Front panel LEDs INPUT OK 1 and INPUT OK 2 FAN OK OUTPUT FAIL Green Source voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off Green Power supply fan is operating properly Off Power supply fan failure is detected Red Problem wit
17. conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications His 1400 W AC Input Power Supply Table A 9 1400 W Power Supply Specifications continued Specification Description AC input frequency 50 60 Hz nominal 3 Hz for full range Power supply output capacity 1400 W Power supply output e ISA 41 5V e 25A 43 3V e 274A 50V Output holdup time 20 ms minimum Heat dissipation 5976 BTU hour approx Front panel LEDs INPUT OK FAN OK OUTPUT FAIL e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off e Green Power supply fan is operating properly e Off Power supply fan failure is detected e Red Problem with one or more of the DC output voltages of the power supply is detected e DC output voltages within acceptable margins Weight 7 8 Ib 3 5 kg 1400 W Power Supply AC Power Cords Table A 10 l
18. inputs which means that power cord can be plugged into phase A and power cord 2 can be plugged into phase B AC input frequency 50 60 Hz nominal 3 for full range Power supply output capacity e 1300 W maximum 100 120 VAC e 2500 W maximum 200 240 VAC e 2500 W maximum 48 to 60 VDC System power dissipation 3520 W total input power or 3 6 KVA high line operation DC input voltage 48 VDC to 60 VDC continuous DC input current e 80A 40 5 VDC e 70A 48 VDC e 55 A 60 VDC E Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 2500 W AC Input and DC Input Power Supplies W Table A 11 2500 W Power Supply Specifications continued Specification Description Power supply output AC supply 100 120 VAC operation 15 5 A 3 3 V 5A 5V 10A 12V 27 5 A 42 V 200 240 VAC operation 15A 3 3 V 5A 5V 10A 12V 55 5 A 42 V Power supply output DC supply 15 A 3 3 V 5A 5V 10 A 12 V 55 5 A 42 V DC input terminal block Accepts 2 14 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Terminal block material rated at 150 C Output holdup time 20 ms minimum AC input power supply 4 ms DC input power supply Heat dissipation 10 939 BTU hour approx AC input power supply 11 377 B
19. phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B DC input voltage Note 48 VDC nominal 37 A in North America operating range 40 5 VDC to 56 VDC 60 VDC nominal 29 A for International operating range 55 VDC to 72 VDC The 4000 W DC input power supply requires two source DC inputs to be connected it cannot operate with only one positive negative source DC terminal pair installed DC input current 40 A per each DC input three inputs Note For multiple DC input power supplies each DC input must be protected by a dedicated circuit breaker or a fuse The circuit breaker or the fuse must be sized according to the power supply input power rating and any local or national electrical code requirements Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Table A 17 Specification 4000 W AC Input and DC Input Power Supplies W 4000 W AC Input and DC Input Power Supplies Specifications continued Description Power supply output capacity e 4000 W with three inputs active e 2700 W with two inputs activ
20. power supply e I5A 33V e 5A 5V e 6A 12V e 289A 42V DC input terminal block Accepts 3 10 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Terminal block material is rated at 120 C Output holdup time e 20 ms minimum AC input power supply e 8 ms DC input power supply Heat Dissipation e 5478 BTU hour approx AC input power supply e 6447 BTU hour approx DC input power supply OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications M1300 W AC Input and DC Input Power Supplies Table A 7 1300 W AC Input and DC Input Power Supplies Specifications continued Specification Front panel LEDs INPUT OK FAN OK OUTPUT FAIL Description AC input power supplies Green Source AC voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply turned off DC input power supplies Green Source DC voltage is OK Input voltage is 40 5 VDC or greater Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off Green Power supply fan is operating properly Off Power supply fan failure is detected Red Problem with one or more of the DC output voltages of the power supply is detected Off DC output voltages within acceptable margins Weight
21. router chassis to connect the site power source to the power supply You can connect the DC input power supply to the power source with heavy gauge wiring connected to a terminal block The actual wire gauge size is determined by local electrical codes and restrictions amp Note The system NEBS ground serves as the primary safety ground for Catalyst 6503 and Catalyst 6503 E chassis that are equipped with 950 W DC input power supplies and DC input PEMs The DC input power supplies for these chassis do not have a separate ground The PEMs have an illuminated power switch AC input only current protection surge and EMI suppression and filtering functions Figure A 1 950 W AC and DC Input Power Supplies Status LEDs g 3 3 3 B Captive installation screws Figure A 2 950 W AC Input PEM PEM 15A AC IEC 60320 C15 connector z AC power switch 130058 Captive installation screws Catalyst 6500 Series Switches Installation Guide Mna E OL 5781 05 _ Appendix A Power Supply Specifications 950 W Power Supply Specifications Figure A 3 DC Power Entry Module PEM Catalyst 6503 DC PEM Captive installation screws 79980 950 W AC Input and DC Input Power Supplies W Table A 3 lists the specifications for the 950 W AC input and DC input power supplies Table A 3 950 W AC Input and DC Input Power Supplies Specifications Item Specification
22. series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 12 A 120 VAC e 6A 230 VAC AC input frequency 50 60 Hz nominal KVA rating 1 25 kVA Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit e For North America 15 A or 20 A e For International Circuits sized to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord can be plugged into phase A and power cord 2 can be plugged into phas
23. 0 Series Switches Installation Guide a OL 5781 05 Appendix A Power Supply Specifications 6000 W AC Input Power Supply W 6000 W AC Input Power Supply The 6000 W AC input WS CAC 6000W power supply is supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6506 E e Catalyst 6509 e Catalyst 6509 E e Catalyst 6509 NEB e Catalyst 6509 NEB A e Catalyst 6513 amp Note When the 6000 W AC input power supply is installed in a Catalyst 6506 Catalyst 6509 Catalyst 6509 NEB or Catalyst 6509 NEB A chassis the power supply output is limited to 4000 W The 6000 W AC input power supply shown in Figure A 16 shares the same form factor as the 1000 W 1300 W 2500 W 3000 W and 4000 W power supplies The 6000 W power supply cannot be installed in the Catalyst 6503 Catalyst 6503 E and Catalyst 6504 E switch chassis Figure A 16 6000 W AC Input Power Supply Cable retention device AC power connection 1 gt AC power connection 2 130056 Power switch Status LEDs Captive installation screw Catalyst 6500 Series Switches Installation Guide OL 5781 05 E Appendix A Power Supply Specifications HI 6000W AC Input Power Supply 6000 W Power Supply Specifications Table A 19 lists the specifications for the 6000 W AC input power supply Table A 19 6000 W AC Input Power Supply Specifications Specification Description AC input typ
24. 0 VAC is not present or the PEM is turned off DC input power supplies e Green Source DC voltage is OK 40 5 VDC or greater e Off Source DC voltage falls below 33 VDC or is not present at the PEM Green Power supply fan is operating properly Off Power supply fan failure is detected Red Problem with one or more of the DC output voltages of the power supply is detected Off DC output voltages within acceptable margins Weight e AC input 8 2 lb 3 7 kg e DC input 8 4 1b 3 8 kg OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications Hi 950W AC Input and DC Input Power Supplies 950 W Power Supply AC Power Cords Table A 4 lists the 950 W AC input power supply AC power cords specifications These power cords plug into the 950 W PEM PEM 15A AC not directly into the power supply The table includes references to power cord illustrations amp Note All 950 W power supply power cords are 8 feet 2 inches 2 5 meters in length Note All 950 W power supply power cords have an IEC60320 C15 appliance connector at one end The appliance connector has a 90 left bend Table A 4 950 W AC Input Power Supply Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Australia New Zealand CAB AC10A 90L AU SAA AS 3112 10 A 250 VAC Figure A 19 Cont
25. 00 series AC input power supplies require single phase source AC All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 1300 W AC Input and DC Input Power Supplies W Table A 7 1300 W AC Input and DC Input Power Supplies Specifications continued Specification Description AC input frequency 50 60 Hz nominal 3 Hz for full range Power supply output capacity e 1300 W maximum AC input e 1360 W maximum DC input DC input voltage 48 VDC to 60 VDC continuous DC input current e 39 A 48 VDC e 31A 60 VDC Power supply output AC input power supply e 1I5A 43 3V e SA H 5V e 6A 12V e 27 46 A 42 V Power supply output DC input
26. 16 A 250 VAC Figure A 41 Israel CAB AC 2500W ISRL S116S3 16 A 250 VAC Figure A 33 Japan North America CAB AC 2500W US1 NEMA 6 20 16 A 250 VAC Figure A 42 200 240VAC operation nonlocking plug Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 43 200 240VAC operation locking plug Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 35 100 120VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 45 1 DR IEC 60320 C20 South Africa CAB 7513ACSA IEC 884 1 16 A 250 VAC Figure A 37 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 44 1 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications HI 3000W AC Input Power Supply 3000 W AC Input Power Supply The 3000 W AC input power supply WS CAC 3000W is supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6506 E e Catalyst 6509 e Catalyst 6509 E e Catalyst 6509 NEB e Catalyst 6509 NEB A e Catalyst 6513 The 3000 W power supply see Figure A 13 shares the same form factor as the 1000 W 1300 W 2500 W 4000 W and 6000 W AC input pow
27. AC Power Cord Illustrations W 7a Cordset rating 10 A 250 V Length 8 ft 2 in 2 5 m Connector IEC 60320 C15 113346 7 i Cordset rating 15 A 250 V Length 8 ft 2 in 2 5 m Connector IEC 60320 C15 113347 m z il Cordset rating 16 A 250 V Length 8 ft 2 in 2 5 m Connector IEC 60320 C15 113348 OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HAC Power Cord Illustrations Figure A 27 CAB 7KACI ot TE Cordset rating 10 A 250 V Length 8 ft 2 in 2 5 m Plug CEI 23 16 7 Connector IEC 60320 C15 Ag 113349 Figure A 28 CAB 7KAC 15 72 et Cordset rating 15 A 125 V Plug NEMA 5 15 Length 8 ft 2 in 2 5 m Connector IEC 60320 C15 Ad 113350 Figure A 29 CAB 7KACU wwe E Cordset rating 10 A 250 V fuse Length 8 ft 2 in 2 5 m Plug BS 1363 Con
28. B 7513AC NEMA 5 20 16 A 125 VAC Figure A 35 100 120VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 46 3 ey IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 44 1 The 6000 W power supply operating on two 110 VAC inputs delivers 2900 W 2 When operating with 100 120VAC you must use two AC power cords and the power supply output is limited to 2900 W 3 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector 8700 W AC Input Power Supply Catalyst 6500 series switch support for the 8700 W AC input WS CAC 8700W E power supply along with any power supply output restrictions are listed in Table A 21 Table A 21 Catalyst 6500 Series Chassis Chassis Support for the 8700 W Power Supply 8700 W Power Supply Restriction Catalyst 6506 Output limited to 4000 W Catalyst 6506 E No restrictions Catalyst 6509 Output limited to 4000 W Catalyst 6509 E No restrictions Catalyst 6509 NEB Output limited to 4000 W Catalyst 6509 NEB A Output limited to 4500 W Catalyst 6513 Output is limited to 6000 W The 8700 W AC input power supply shown in Figure A 17 shares a similar but not identical form factor as the 1000 W 1300 W
29. O type of relay Positions 2 and 3 are used when the relay controller box contains a normally closed NC type of relay Relay Controller Box Switch The relay controller box switch located next to the terminal block allows you to match the power supply power control signal s active state with the type of relay contained in the external relay controller box either a normally open type of relay or a normally closed type of relay Ferrite Bead A plastic bag containing one ferrite bead and two 4 inch plastic ties is included with the 8700 W power supply AC power cords The ferrite bead is a passive device that limits high frequency interference on interface and control cables and it is only required when you install the remote power cycling feature that is supported by the 8700 Watt power supply The ferrite bead is installed on the two control wires that come from the relay controller box to the terminal block on the 8700 W power supply The ferrite bead should be installed as close as possible to the power supply terminal block for the bead to be effective You do not need the ferrite bead for 8700 Watt power supply installations that do not include the remote power cycling feature If you need to install the ferrite bead refer to Installing the Ferrite Bead procedure on page 4 77 Remote Power Cycling Operation This feature allows you to remotely power cycle the Catalyst 6500 series switch using any appropriate third party relay c
30. TU hour approx DC input power supply I OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 2500W AC Input and DC Input Power Supplies Table A 11 2500 W Power Supply Specifications continued Specification Front panel LEDs INPUT OK FAN OK OUTPUT FAIL Description AC input power supplies Green Source AC voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off DC input power supplies Green Source DC voltage is OK Input voltage is 40 5 VDC or greater Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off Green Power supply fan is operating properly Off Power supply fan failure is detected Red Problem with one or more of the DC output voltages of the power supply Off DC output voltages within acceptable margins Weight AC input 17 0 lb 7 7 kg DC input 20 2 lb 9 2 kg Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 2500 W Power Supply AC Power Cords Table A 12 lists the specifications for the AC power cords that are available for the 2500 W AC input 2500 W AC Input and DC Input Power Supplies power supply The table includes references to power cord illustrations amp Note All 2500 W
31. VDC max For 12 VDC output 10 5 11 5 VDC min 12 6 13 0 VDC max For 42 VDC output 38 0 40 0 VDC min 45 0 52 0 VDC max e Off All DC output voltages are within normal operating ranges Weight 39 7 1b 18 kg Remote Power Cycling Feature The 8700 W power supply is equipped with a remote power cycling feature that allows you to remotely turn on or turn off the power supply through an external relay controller box Figure A 18 shows a typical remote power on off setup A three position terminal block and a switch located on the lower right quadrant of the power supply faceplate see Figure A 17 provide the interface to the external relay controller box OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 8700W AC Input Power Supply Figure A 18 Remote Power On Off Feature Components toe 8 AAT ey th LN dh LN dh ty th eae CH plese lee 218082 f2 Remote power on off fh terminal block Relay controller Relay controller box switch Relay controller power Ferrite bead 181878 Terminal Block The terminal block has three contacts labeled 1 2 and 3 Two control wires from an external relay controller box attach to either positions 1 and 2 or positions 2 and 3 Positions 1 and 2 are used when the relay controller box contains a normally open N
32. cations Specification Description AC input type High line input with power factor correction PFC included Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 23 A AC input frequency 50 60 Hz nominal 3 for full range Power supply output capacity AC power 4000 W maximum supply Catalyst 6500 Series Switches Installation Guide OL 5781 05 EN Appendix A Power Supply Specifications Hi 4000W AC Input and DC Input Power Supplies Table A 17 4000 W AC Input and DC Input Power Supplies Specifications continued Specification Description Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit For North America 30 A For International Circuits should be sized according to local and national codes All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC
33. e Note The 4000 W power supply cannot operate with only one source DC input connected kVA rating 5 4 kVA maximum System power dissipation DC power supply 5200 W total input power Power supply output AC power supply e 1I5A 43 3V e SA 4 5V e 10A 12V e 90 36 A 42 V Power supply output DC power supply e 15A 3 3 VDC e 5A 5 VDC e 12A 12 VDC e 90 63 A three inputs or 59 68 A two inputs 42 VDC Note The 4000 W power supply cannot operate with only one source DC input connected DC input terminal block Accepts 4 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Output holdup time e 20 ms minimum AC input power supply e 8 ms DC input power supply Heat dissipation e 17 065 BTU hour approx AC input power supply e 17 730 BTU hour approx DC input power supply OL 5781 05 Catalyst 6500 Series Switches Installation Guide A Appendix A Power Supply Specifications Hi 4000W AC Input and DC Input Power Supplies Table A 17 4000 W AC Input and DC Input Power Supplies Specifications continued Specification Description Front panel LEDs INPUT OK AC input power supplies e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off sSource AC voltage falls below 70 VAC is not present or the power supply is turned off DC input power supplies e Green
34. e 2 AC inputs per power supply High line input with power factor correction PFC included Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 16 A each input KVA rating 7 5 kVA AC input frequency 50 60 Hz nominal 3 for full range Catalyst 6500 Series Switches Installation Guide Anaa OL 5781 05 Appendix A Power Supply Specifications 6000 W AC Input Power Supply W Table A 19 6000 W AC Input Power Supply Specifications continued Specification Description Power supply output capacity The 6000 W power supply can operate at either 2900 W or 6000 W depending on the number of AC power cords attached and the source AC voltage Note The 6000 W AC input power supply is limited to 4000 W maximum output when it is installed in a Catalyst 6506 Catalyst 6509 or Catalyst 6509 NEB switch chassis The power supply is limited to 4500 W maximum output when it is installed in the Catalyst 6509 NEB A switch chassis e 2900 W maximum with the following source AC arrangements INPUT 1 and INPUT 2 both connected to low line
35. e B Catalyst 6500 Series Switches Installation Guide PA10 i OL 5781 05 Appendix A Power Supply Specifications 1000 W AC Input Power Supply W Table A 5 1000 W Power Supply Specifications continued Specification Description Power supply output capacity 1000 W Power supply output e 1I5A 43 3V e 5A 5V e 6A 12V e 20 3 A 42 V Output holdup time 20 ms minimum Heat Dissipation 4213 BTU hour approx Front panel LEDs INPUT OK FAN OK OUTPUT FAIL Green Source AC voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off Green Power supply fan is operating properly Off Power supply fan failure is detected Red Problem with one or more of the DC output voltages of the power supply is detected Off DC output voltage with acceptable margins Weight 14 8 1b 6 7 kg OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 1000W AC Input Power Supply 1000 W Power Supply AC Power Cords Table A 6 lists the specifications for the AC power cords that are available for the 1000 W AC input power supply The table includes references to power cord illustrations amp Note All 1000 W power supply power cords are 8 feet 2 inches 2 5 meters in length amp Note All 1000 W power supply power cord
36. e installation screws Catalyst 6500 Series Switches Installation Guide PAs E OL 5781 05 Appendix A Power Supply Specifications 1400 W Power Supply Specifications 1400 W AC Input Power Supply W Table A 9 lists the specifications for the 1400 W AC input power supply Table A 9 1400 W Power Supply Specifications Specification AC input type Description Autoranging input Power Factor Correction PFC included Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 16A 120 VAC e 8A 230 VAC kVA rating 1 75 kVA Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot
37. equal wattage Enabled Both power supplies initially come online For the Catalyst operating system if the difference between the two power supply s output wattage is less than 10 of the higher output wattage power supply redundancy is enabled If the difference is greater than 10 the lesser wattage power supply is disabled For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply Equal or unequal wattage Disabled The total power available to the system is approximately 167 percent of the lower wattage power supply The system powers up as many modules as the combined capacity allows If the higher wattage power supply fails the lower wattage supply might also shut down due to overcurrent protection to prevent damage to the lower wattage power supply Table A 26 Effects of Power Supply Configuration Changes Configuration Change Effect Redundant to nonredundant System log and syslog messages are generated System power is increased to approximately 167 percent of the lower wattage power supply The modules marked as power deny in the show module Status field are powered up if there is sufficient power Nonredundant to redundant System log and syslog messages are generated System power is the power capability of the higher wattage supply If there is not enough power for all previously powered up modules some modu
38. er supplies amp Note The 3000 W AC input power supply needs 220 VAC to deliver 3000 W of power When operating with 110 VAC it delivers only 1400 W In addition the power supply needs 16 A regardless of whether it is plugged into 110 VAC or 220 VAC Figure A 13 3000 W AC Input Power Supply AC power connection 105069 Power switch External power Captive installation Status LEDs 3 connector cover screw Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 3000 W Power Supply Specifications 3000 W AC Input Power Supply W Table A 15 lists the specifications for the 3000 W AC input power supply Table A 15 3000 W Power Supply Specifications Specification Description AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 16 A 200 VAC 3000 W output e 16A 100 VAC 1400 W output Branch circuit requirement AC input Each chassis power supply should have it
39. er supply The table includes references to power cord illustrations amp Note All 3000 W power supply power cords are 14 feet 4 3 meters in length amp Note All 3000 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 16 3000 W Power Supply AC Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 45 People s Republic of CAB AC16A CH GB16C 16 A 250 VAC Figure A 36 China Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 40 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 41 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 33 Japan North America CAB AC 2500W US1 NEMA 6 20 16 A 250 VAC Figure A 42 nonlocking plug 200 240VAC operation Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 43 locking plug 200 240VAC operation Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 35 100 120VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 46 2 PDU IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 44 1 The 3000 W power supply operating on 110 VAC delivers 1400 W 2 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Cata
40. f the 4000 W power supplies in bay 1 and bay 2 are running in redundant mode the total system power will be 4000 W If power supply 1 is running and you power off or remove power supply 2 the total system power will be 4000 W The system will issue a normal power supply 2 down remove indication warning If you power down power supply 1 while power supply 2 is operating the system will issue a normal power supply 1 down indication warning with another warning asking the user not to remove power supply 1 If power supply 1 is left in the system even if it is powered off the total system power will be 4000 W If you remove power supply 1 from the system a major alarm will be issued to warn that the total system power will be reduced to 2940 W and that any modules or PoE devices that cause the system to exceed 2940 W will power down in 300 seconds 5 minutes If you insert a replacement power supply 1 in the 300 second timeframe no action will be taken Catalyst 6500 Series Switches Installation Guide PA70 i OL 5781 05 Appendix A Power Supply Specifications amp Power Supply Redundancy W Note In systems that are equipped with two power supplies if one power supply fails and the other power supply cannot fully power all of the installed modules system power management will shut down devices in the following order e Power over Ethernet PoE devices The system will power down PoE devices in descending order s
41. f you operate the 2500 W power supply at the low range input 100 to 120 VAC it is not redundant in a fully populated Catalyst 6509 Catalyst 6509 E Catalyst 6509 NEB or Catalyst 6509 NEB A switch The 2500 W AC input power supply needs 220 VAC to deliver 2500 W of power When powered with 110 VAC it delivers only 1300 W In addition the power supply needs 16 A regardless of whether it is plugged into 110 VAC or 220 VAC Figure A 9 2500 W AC Input Power Supply AC power connection Cable retention U device zc 16029 papapapa Power switch Status LEDs Captive installation screw E Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Figure A 10 Terminal block gt cover 2500 W AC Input and DC Input Power Supplies W 2500 W DC input Power Supply looooooooooooo looooooooooooo ooo0o000000000 o0000 00 INPUT FAN OUTPUT OK OK FAIL o_ Captive installation screw 2500 W Power Supply Specifications 16030 Table A 11 lists the specifications for the 2500 W AC input and DC input power supplies Table A 11 2500 W Power Supply Specifications Specification AC input type Description Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the react
42. h one or more of the DC output voltages of the power supply Off DC output voltages within acceptable margins Weight 25 4 lb 11 5 kg 6000 W Power Supply AC Power Cords Table A 18 lists the specifications for the AC power cords that are available for the 6000 W AC input power supply Included in the table are references to illustrations of the power cords Table A 20 6000 W Power Supply AC Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 45 People s Republic of CAB AC16A CH GB16C 16 A 250 VAC Figure A 36 China Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 40 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 41 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 33 Japan North America CAB AC 2500W US1 NEMA 6 20 16 A 250 VAC Figure A 42 nonlocking plug 200 240VAC operation OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 8700W AC Input Power Supply Table A 20 6000 W Power Supply AC Power Cords continued Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 43 locking plug 200 240VAC operation Japan North America CA
43. in the Catalyst 6509 NEB A switch chassis and 6000 W when it is installed in a Catalyst 6513 switch chassis Note The power supply will not power up if you attach only one power cord and the power cord is connected to low line 110 VAC nominal source AC 2800 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e Two AC inputs are connected to low line 110 VAC nominal the third AC input is not connected e One AC input is connected to low line 110 VAC nominal one AC input is connected to high line 220 VAC nominal the third AC input is not connected e One AC input is connected to high line 220 VAC nominal two AC inputs are not connected 4200 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e All three AC inputs are connected to low line 110 VAC nominal e Two AC inputs are connected to low line 110 VAC nominal one AC input is connected to high line 220 VAC nominal Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 8700 W AC Input Power Supply W Table A 22 8700 W AC Input Power Supply Specifications continued Specification Description 5800 W operation 8700 W operation 5800 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e Tw
44. inental Europe CAB AC10A 90L EU CEE 7 7 10 A 250 VAC Figure A 20 Italy CAB AC10A 90L IT CEI 23 16 7 10 A 250 VAC Figure A 21 Japan North America CAB AC15A 90L US NEMA 5 15 15 A 125 VAC Figure A 22 United Kingdom CAB AC10A 90L UK BS 1363 10 A 250 VAC Figure A 23 1 Plug contains a 13 A fuse Catalyst 6500 Series Switches Installation Guide lt a OL 5781 05 Appendix A Power Supply Specifications 1000 W AC Input Power Supply W 1000 W AC Input Power Supply The 1000 W AC input power supply WS CAC 1000W is supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6509 e Catalyst 6509 NEB The 1000 W power supply shown in Figure A 4 shares the same form factor as the 1300 W 2500 W 3000 W 4000 W and 6000 W AC input power supplies Figure A 4 1000 W AC Input Power Supply AC power connection Cable retention device a g Power switch i Status LEDs Captive installation screw Catalyst 6500 Series Switches Installation Guide OL 5781 05 g ao Appendix A Power Supply Specifications W 1000W AC Input Power Supply 1000 W Power Supply Specifications Table A 5 lists the specifications for the 1000 W AC input power supply Table A 5 1000 W Power Supply Specifications Specification Description AC input type Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500
45. istribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 46 2 eRe IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 44 1 When operating with 100 120VAC you must use two or three AC power cords and the power supply output is limited to either 2800 W 2 inputs or 4200 W 3 inputs 2 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications AC Power Cord Illustrations W AC Power Cord Illustrations This section contains the AC power cord illustrations Note that an AC power cord may be used with several power supplies See the power supply specifications tables for the correct AC power cord illustrations for your power supply Figure A 19 CAB AC10A 90L AU 7a Cordset rating 10 A 250 V Plug SAA AS 3112 Length 8 ft 2 in 2 5 m 113341 Figure A 20 CAB AC10A 90L EU Yee Cordset rating 10 A 250 V Plug CEE 7 7 Length 8 ft 2 in 2 5 m
46. ists the specifications for the AC power cords that are available for the 1400 W AC input power supply These power cords plug into the 1400 W PEM PEM 20A AC not directly into the power supply The table includes references to power cord illustrations amp Note All 1400 W power supply power cords are 14 feet 4 3 meters in length Note All 1400 W power supply power cords have an IEC60320 C19 appliance plug at one end E Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Table A 10 Locale Argentina Australia New Zealand People s Republic of China Continental Europe International Israel Italy Japan North America South Africa Switzerland Switzerland United Kingdom Power Cord Part Number CAB 7513ACR CAB 7513ACA CAB AC16A CH CAB 7513ACE CAB AC 2500W EU CAB AC 2500W INT CAB AC 2500W ISRL CAB 7513ACI CAB 7513AC CAB AC 2500W US 1 CAB AC C6K TWLK CAB 7513ACSA CAB ACS 10 CAB ACS 16 CAB 7513ACU 1400 W Power Supply AC Power Cords Source Plug Type IRAM 2073 SAA AS 3112 GB16C CEE 7 7 CEE 7 7 IEC 309 SI16S3 CEI 23 16 7 NEMA 5 20 NEMA 6 20 NEMA L6 20 IEC 884 1 SEV 1011 SEV 5934 2 Type 23 BS 1363 Cordset Rating 10 A 250 VAC 15 A 250 VAC 16 A 250 VAC 16 A 250 VAC 16 A 250 VAC 16 A 250 VAC 16 A 250 VAC 16 A 250 VAC 20 A 125 VAC 16 A 250 VAC 16 A 250 VAC
47. ive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 16 A maximum at 230 VAC at 2500 W output 16 A maximum at 120 VAC at 1300 W output OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 2500W AC Input and DC Input Power Supplies Table A 11 2500 W Power Supply Specifications continued Specification Description Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC
48. les are powered down and marked as power deny in the show module Status field Equal wattage power supply is inserted with redundancy enabled System log and syslog messages are generated System power equals the power capability of one supply Both supplies provide approximately one half of the total current No change in the module status because the power capability is unchanged Equal wattage power supply is inserted with redundancy disabled System log and syslog messages are generated System power is the combined power capability of both supplies The modules marked as power deny in the show module Status field are brought up if there is sufficient power Catalyst 6500 Series Switches Installation Guide Power Supply Specifications OL 5781 05 Appendix A Power Supply Specifications Table A 26 Configuration Change Power Supply Redundancy W Effects of Power Supply Configuration Changes continued Effect Higher wattage power supply is inserted with redundancy enabled System log and syslog messages are generated The system disables the lower wattage power supply the higher wattage supply powers the system Catalyst operating system For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply Lower wattage power supply is inserted with redundancy enabled System log and syslog messages are gene
49. lies Green Source DC is OK Input voltage is 40 5 VDC or greater Off Source DC voltage falls below 33 VDC is not present or the power supply is turned off Green Power supply fan is operating properly Off Power supply fan failure is detected Red Problem with one or more of the DC output voltages of the power supply Off DC output voltages within acceptable margins Weight AC input 18 5 lb 8 4 kg DC input 21 0 lb 9 5 kg Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 2700 W Power Supply AC Power Cords Table A 12 lists the specifications for the AC power cords that are available for the 2700 W AC input 2700 W AC Input and DC Input Power Supplies power supply The table includes references to power cord illustrations amp Note All 2700 W power supply power cords are 14 feet 4 3 meters in length amp Note All 2700 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 14 2700 W Power Supply AC Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 44 People s Republic of CAB AC16A CH GB16C 16 A 250 VAC Figure A 36 China Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 40 International CAB AC 2500W INT IEC 309
50. ly output e 2800 W operation 25 0 A 3 3 V 120A 12 V 61 29 A 42 V e 4200 W operation 25 0 A 3 3 V 120A 12 V 94 62 A 42 V e 5800 W operation 25 0 A 3 3 V 120A 12 V 132 71 A 42 V e 8700 W operation 25 0 A 3 3 V 120A 12 V 201 75 A 42 V Output holdup time 20 ms minimum Heat dissipation e 11 200 BTU hour 2800 W e 16 800 BTU hour 4200 W e 23 200 BTU hour 5800 W e 34 800 BTU hour 8700 W Catalyst 6500 Series Switches Installation Guide a OL 5781 05 Appendix A Power Supply Specifications 8700 W AC Input Power Supply W Table A 22 8700 W AC Input Power Supply Specifications continued Specification Description Front panel LEDs INPUT OK 1 INPUT OK 2 and INPUT OK 3 220VAC 1 2 and 3 FAN OK OUTPUT FAIL e Green Source voltage is OK Input voltage is 85 VAC or greater e Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off e Green High line AC is present on the respective AC inputs Input voltage is 170 VAC or higher e Off Source AC voltage falls below 170 VAC is not present or the power supply is turned off e Green Power supply fan is operating properly e Off Power supply fan failure is detected e Red One or more of the power supply DC output voltages is out of the normal operating range For 3 3 VDC output 2 7 3 0 VDC min 3 6 3 8
51. lyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has a C20 connector Catalyst 6500 Series Switches Installation Guide OL 5781 05 E Appendix A Power Supply Specifications Hi 4000W AC Input and DC Input Power Supplies 4000 W AC Input and DC Input Power Supplies The 4000 W AC input and DC input power supplies WS CAC 4000W US WS CAC 4000W INT and PWR 4000 DC are supported in the following Catalyst 6500 series switches Catalyst 6506 Catalyst 6506 E Catalyst 6509 Catalyst 6509 E Catalyst 6509 NEB Catalyst 6509 NEB A Catalyst 6513 The 4000 W AC input and DC input power supplies shown in Figure A 14 and Figure A 15 share the same form factor as the 1000 W 1300 W 2500 W and 3000 W power supplies Figure A 14 4000 W AC Input Power Supply 85756 Status LEDs Captive installation screw Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 4000 W AC Input and DC Input Power Supplies W Figure A 15 4000 W DC Input Power Supply 97297 4000 W Power Supply Specifications Table A 17 lists the specifications for the 4000 W AC input and DC input power supplies Table A 17 4000 W AC Input and DC Input Power Supplies Specifi
52. nector IEC 60320 C15 Ad 113351 Catalyst 6500 Series Switches Installation Guide PAO E OL 5781 05 Appendix A Power Supply Specifications AC Power Cord Illustrations W Figure A 30 CAB 7513ACR E Co P I Cordset rating 10 A 250 V Connector IEC 60320 C19 113352 Figure A 31 CAB 7513ACA Eye Cordset rating 15 A 250 V Plug SAA AS 3112 Length 14 ft 0 in 4 26 m Connector IEC 60320 C19 5 113353 Figure A 32 CAB 7513ACE m7 Za E Cordset rating 16 A 250 V Plug CEE 7 7 Length 14 ft 0 in 4 26 m Connector IEC 60320 C19 113354 Catalyst 6500 Series Switches Installation Guide OL 5781 05 ON Appendix A Power Supply Specifications HE AC Power Cord Illustrations Figure A 33 CAB AC 2500W ISRL gV Om r E Jo Cordset rating 16 A 250 V Plug SI16S3 Figure A 34 0000 Plug CEI 23 16 7 Figure A 35 CAB 7513ACI Length 14 ft 0 in 4 26 m Connector IEC 60320 C19
53. o AC inputs are connected to high line 220 VAC nominal the third AC input is connected to low line 110 VAC nominal e Two AC inputs are connected to high line 220 VAC nominal the third AC input is not connected 8700 W maximum with the following combinations of power cords and source AC voltage applied to the power supply inputs e All three AC inputs are connected to high line 220 VAC nominal System power dissipation 10 360 W Branch circuit requirement AC input Each power supply input should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits should be sized according to local and national codes e All Catalyst 6500 series AC input power supplies require single phase source AC e All AC power supply inputs are fully isolated This means that source AC can be out of phase between multiple AC inputs on the same power supply or different AC power supplies that are installed in the same chassis For the 8700 W power supply this means that power cord 1 can be plugged into phases A B power cord 2 can be plugged into phases B C and power cord 3 can be plugged into phases C A A B or B C OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HI 8700W AC Input Power Supply Table A 22 8700 W AC Input Power Supply Specifications continued Specification Description Power supp
54. ontroller This eliminates the need for you to have access to the supervisor engine console or CLI to control power cycling Table A 23 lists the relay controller box relay type the corresponding power supply terminal block positions and a description of the power cycling operation Catalyst 6500 Series Switches Installation Guide Asa E OL 5781 05 Appendix A Power Supply Specifications Table A 23 External Relay Controller Box Relay Type Power Supply Relay Controller Switch Setting Power Supply Terminal Block Positions Used 8700 W AC Input Power Supply W 8700 W Power Supply Relay Controller Switch Settings and Operation Remote Power Cycling Operation Normally open NO INO RELAY Control wires from the e Power supply cycled from on to off The relay DEFAULT external relay controller power supply is powered off by energizing box attach to terminal the relay relay contacts go from open to block positions 1 and 2 closed for more than 30 seconds e Power supply cycled from off to on The power supply is powered on by de energizing the relay relay contacts go from closed to open for more than 10 seconds Normally closed NC INC RELAY Control wires from the e Power supply cycles from on to off The relay external relay controller power supply is powered off by energizing box attach to terminal the relay relay contacts go from closed to block positions 2 and 3 open for more than 30 seconds e Po
55. operation 25 0 A 3 3 V 5A 5V 12A 12V 65 98 A 42 V Front panel power connector A two pin male Molex connector is located in the lower right corner of the power supply front panel The connector provides 42 VDC at a maximum of 17 A This connector provides power to the WS 6509 NEB UPGRD kit fan assembly through a power harness also provided in the kit A hinged protective flap secured by a captive screw covers the connector when it is not in use Output holdup time 20 ms minimum Heat dissipation 12 046 BTU hour approx Front panel LEDs INPUT OK e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off sSource AC voltage falls below 70 VAC is not present or the power supply is turned off FAN OK e Green Power supply fan is operating properly e Off Power supply fan failure is detected OUTPUT FAIL e Red Problem with one or more of the DC output voltages of the power supply e Off DC output voltages within acceptable margins 42V OK e Green 42 VDC is present at the fan power connector e Off 42 VDC is not present at the fan power connector Weight 15 8 lb 7 2 kg Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 3000 W AC Input Power Supply W 3000 W Power Supply AC Power Cords Table A 16 lists the specifications for the AC power cords that are available for the 3000 W AC input pow
56. power supply power cords are 14 feet 4 3 meters in length amp Note All 2500 W power supply power cords have an IEC60320 C19 appliance connector at one end Table A 12 2500 W Power Supply AC Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Australia New Zealand CAB AC 16A AUS AU208S3 16A 250 VAC Figure A 45 People s Republic of CAB AC16A CH GB16C 16 A 250 VAC Figure A 36 China Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 40 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 41 Israel CAB AC 2500W ISRL S116S3 16 A 250 VAC Figure A 33 Japan North America CAB AC 2500W US1 NEMA 6 20 16 A 250 VAC Figure A 42 200 240VAC operation nonlocking plug Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 43 200 240VAC operation locking plug Japan North America CAB 7513AC NEMA 5 20 20 A 125 VAC Figure A 35 100 120VAC operation Power Distribution Unit CAB C19 CBN IEC 60320 C19 16 A 250 VAC Figure A 46 2 PDU IEC 60320 C20 Switzerland CAB ACS 16 SEV 5934 2 Type 23 16 A 250 VAC Figure A 44 1 The 2500 W power supply operating on 110 VAC delivers 1300 W 2 The PDU power cable is designed for users who power their switch from a PDU The end of the cable that plugs into the Catalyst 6500 series switch chassis has a C19 connector the other end of the cable that plugs into the PDU has
57. r 5 Cable holder cover 11 Tie wrap 6 OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications WE 2700W AC Input and DC Input Power Supplies 2700 W Power Supply Specifications Table A 11 lists the specifications for the 2700 W AC input and DC input power supplies Table A 13 2700 W Power Supply Specifications Specification AC input type Description Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage e Low line 120 VAC nominal 85 VAC min to 132 VAC max e High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current e 16 A maximum at 230 VAC at 2700 W output e 16 A maximum at 120 VAC at 1350 W output Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from pha
58. rated The system disables the lower wattage power supply the higher wattage supply powers the system Catalyst operating system For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply Higher or lower wattage power supply is inserted with redundancy disabled System log and syslog messages are generated System power is increased to the combined power capability of both supplies The modules marked as power deny in the show module Status field are brought up if there is sufficient power Power supply is removed with redundancy enabled System log and syslog messages are generated If the power supplies are of equal wattage there is no change in the module status because the power capability is unchanged If the power supplies are of unequal wattage and the lower wattage supply is removed there is no change in the module status If the power supplies are of unequal wattage and the higher wattage supply is removed the lower wattage power supply must be turned on manually The system had previously turned off the lower wattage power supply Power supply is removed with redundancy disabled System log and syslog messages are generated System power is decreased to the power capability of one supply If there is not enough power for all previously powered up modules some modules are powered down and marked as power deny in the show mod
59. rd Illustrations Figure A 39 CAB 7513ACU mE Cordset rating 13 A 250 V Plug BS 1363 Length 14 ft 0 in 4 26 m 13A replaceable fuse Connector IEC 60320 C19 113359 Figure A 40 CAB AC 2500W EU 7p ae ae Cordset rating 16 A 250 V Plug CEE 7 7 Length 14 ft 0 in 4 26 m Connector IEC 60320 C19 113360 Figure A 41 CAB AC 2500W INT SL qe Cordset rating 16 A 250 V Length 14 ft 0 in 4 26 m Plug IEC 309 M N Connector IEC 60320 C19 113361 Catalyst 6500 Series Switches Installation Guide noa OL 5781 05 Appendix A Power Supply Specifications Figure A 42 CAB AC 2500W US1 ey ra Cordset rating 16 A 250 V Plug NEMA 6 20 Figure A 43 CAB AC C6K TWLK Length 14 ft 0 in 4 26 m Connector IEC 60320 C19 Cordset rating 16 A 250 V Plug NEMA L6 20 Figure A 44 CAB ACS 16 UT Length 14 ft 0 in 4 26 m Connector IEC 60320 C19
60. rements Depending upon the wattage of the power supply certain switch configurations might require more power than a single power supply can provide Although the power management feature allows you to supply power to all installed modules with two power supplies redundancy is not supported in this configuration Redundant and nonredundant power configurations are summarized in Table A 25 The effects of changing the power supply configurations are summarized in Table A 26 amp Note Table A 25 Power Supply Redundancy If you have two power supplies of For proper load sharing operation in a redundant power supply configuration you must install two modules in the chassis If you fail to install two modules you might receive spurious OUTPUT FAIL indications on the power supply and redundancy is Then Equal wattage Enabled The total power drawn from both supplies is never greater than the capability of one supply If one supply malfunctions the other supply can take over the entire system load Each power supply provides approximately half of the required power to the system Load sharing and redundancy are enabled automatically no software configuration is required OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A W Power Supply Redundancy Table A 25 Power Supply Redundancy continued If you have two power supplies of and redundancy is Then Un
61. s have an IEC60320 C15 appliance plug at one end Table A 6 1000 W AC Input Power Supply Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Argentina CAB 7KACR IRAM 2073 10 A 250 VAC Figure A 24 Australia New Zealand CAB 7KACA SAA AS 3112 15 A 250 VAC Figure A 25 Continental Europe CAB 7KACE CEE 7 7 16 A 250 VAC Figure A 26 Italy CAB 7KACI CEI 23 16 7 10 A 250 VAC Figure A 27 Japan North America CAB 7KAC 15 NEMA 5 15 15 A 125 VAC Figure A 28 United Kingdom CAB 7KACU BS 1363 10 A 250 VAC Figure A 29 1 Plug contains a 13 A fuse Catalyst 6500 Series Switches Installation Guide n12 E OL 5781 05 Appendix A Power Supply Specifications 1300 W AC Input and DC Input Power Supplies W 1300 W AC Input and DC Input Power Supplies The 1300 W AC input power supply WS CAC 1300W and 1300 W DC input power supply WS CDC 1300W are supported in the following Catalyst 6500 series switches e Catalyst 6506 e Catalyst 6509 e Catalyst 6509 NEB The 1300 W power supply see Figure A 5 for the 1300 W AC input power supply and Figure A 6 for the 1300 W DC input power supply shares the same form factor as the 1000 W 2500 W 3000 W 4000 W and 6000 W AC input power supplies Figure A 5 1300 W AC input Power Supply AC power connection Cable retention device Eos g 8 Power switch Status LEDs Captive installa
62. s own dedicated fused branch circuit e For North America 20 A e For International Circuits sized to local and national codes e All AC power supply inputs are fully isolated Source AC can be out of phase between multiple power supplies in the same chassis which means that PS1 can be operating from phase A and PS2 can be operating from phase B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord can be plugged into phase A and power cord 2 can be plugged into phase B AC input frequency 50 60 Hz nominal 3 for full range Power supply output capacity e 1400 W maximum 100 120 VAC e 3000 W maximum 200 240 VAC OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications HI 3000W AC Input Power Supply Table A 15 3000 W Power Supply Specifications continued Specification Description System power dissipation 3520 W total input power or 3 6 KVA high line operation Power supply output e 100 120 VAC operation 25 0 A 3 3 V 5A 5V 12A 12V 27 89 A 42 V e 200 240 VAC
63. se B For high line operation the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B AC input frequency 50 60 Hz nominal 3 for full range Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 2700 W AC Input and DC Input Power Supplies W Table A 13 2700 W Power Supply Specifications continued Specification Description Power supply output capacity e 1350 W maximum 100 120 VAC e 2700 W maximum 200 240 VAC e 1350 W maximum 48 to 60 VDC with one DC input e 2700 W maximum 48 to 60 VDC with two DC inputs System power dissipation e 3 4 KVA high line operation AC input e 3 5 KW DC input DC input voltage 48 VDC to 60 VDC continuous DC input current per DC input e 43 A 40 5 VDC e 37 A 48 VDC e 29A 60 VDC Note For multiple DC input power supplies each DC input must be protected by a dedicated circuit breaker or a fuse The circuit breaker or the fuse must be sized according to the power supply inpu
64. t 8700 W AC input Both the 6000 W and the 8700 W AC input power supplies are limited to 4000 W when they are installed in the Catalyst 6506 switch chassis E Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications Table A 2 Platform Supported Power Supplies Power Supply Compatibility Matrix i Catalyst 6500 Series Switch Supported Power Supply Configurations continued Restrictions Catalyst 6506 E 2500 W AC input and DC input 3000 W AC input 4000 W AC input and DC input 6000 W AC input 8700 W AC input Catalyst 6509 1000 W AC input 1300 W AC input and DC input 2500 W AC input and DC input 3000 W AC input 4000 W AC input and DC input 6000 W AC input 8700 W AC input Both the 6000 W and the 8700 W AC input power supplies are limited to 4000 W when they are installed in the Catalyst 6506 switch chassis Catalyst 6509 E 2500 W AC input and DC input 3000 W AC input 4000 W AC input and DC input 6000 W AC input 8700 W AC input Catalyst 6509 NEB 1000 W AC input 1300 W AC input and DC input 2500 W AC input and DC input 3000 W AC input 4000 W AC input and DC input 6000 W AC input 8700 W AC input Both the 6000 W and the 8700 W AC input power supplies are limited to 4000 W when they are installed in the Catalyst 6509 NEB switch chassis Catalyst 6509 NEB A 2500 W AC input and DC input 3000 W AC input 4000 W AC input
65. t power rating and any local or national electrical code requirements Power supply output AC supply e 100 120 VAC operation 15 A 1 5 VDC 2 5 A 3 3 VDC 27 49 A 50 VDC e 200 240 VAC operation 15 A 1 5 VDC 2 5 A 3 3 VDC 55 61 A 50 VDC Power supply output DC supply e One DC input operation 15A 41 5 VDC 5A 3 3 VDC 27 49 A 50 VDC e Two DC inputs operation 15A 41 5 VDC 5A 3 3 VDC 55 61 A 50 VDC DC input terminal block Accepts 2 14 AWG copper conductors Actual size of the wire needed is determined by the installer or local electrician Terminal block material rated at 150 C OL 5781 05 Catalyst 6500 Series Switches Installation Guide Appendix A Power Supply Specifications W 2700W AC Input and DC Input Power Supplies Table A 13 2700 W Power Supply Specifications continued Specification Description Output holdup time 20 ms minimum AC input power supply 4 ms DC input power supply Heat dissipation Front panel LEDs INPUT 1 OK INPUT 2 OK DC input power supply only FAN OK OUTPUT FAIL 11 238 BTU hour approx AC input power supply 11 968 BTU hour approx DC input power supply AC input power supplies Green Source AC voltage is OK Input voltage is 85 VAC or greater Off Source AC voltage falls below 70 VAC is not present or the power supply is turned off DC input power supp
66. tarting with the highest numbered port on the module in the highest numbered slot e Modules If additional power savings are needed the system will power down modules in descending order starting with the highest numbered slot Slots containing supervisor engines or Switch Fabric Modules are bypassed and are not powered down This shut down order is fixed and cannot be changed You can change the configuration of the power supplies to redundant or nonredundant at any time If you switch from a redundant to a nonredundant configuration both power supplies are enabled even a power supply that was disabled because it was of a lower wattage than the other power supply If you change from a nonredundant to a redundant configuration both power supplies are initially enabled and if they are of the same wattage they remain enabled If they are of different wattage a syslog message displays and the lower wattage supply is disabled For additional information about the power management feature and individual module power consumption refer to your software configuration guide OL 5781 05 Catalyst 6500 Series Switches Installation Guide a Appendix A Power Supply Specifications W Power Supply Redundancy Catalyst 6500 Series Switches Installation Guide Ka OL 5781 05
67. tion screw Figure A 6 1300 W DC Input Power Supply ooo Terminal ge 5 block gt 5E2565 QQQQOO cover ooosga Qoooo0 o oooooG ise ooooco B ooooo BDD INPUT FAN OUTPUT OK OK FAIL PL Captive installation screw OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications W 1300W AC Input and DC Input Power Supplies 1300 W Power Supply Specifications Table A 7 lists the specifications for the 1300 W AC input and DC input power supplies Table A 7 1300 W AC Input and DC Input Power Supplies Specifications Specification AC input type Description Autoranging input with power factor correction PFC Note Power factor correction is a standard feature on all Catalyst 6500 series AC input power supplies PFC reduces the reactive component in the source AC current allowing higher power factors typically 99 percent or better and lower harmonic current components AC input voltage Low line 120 VAC nominal 85 VAC min to 132 VAC max High line 230 VAC nominal 170 VAC min to 264 VAC max AC input current 16 A 120 VAC 8 A 230 VAC kVA rating 1 625 kVA Branch circuit requirement AC input Each chassis power supply should have its own dedicated fused branch circuit For North America 15 A or 20 A For International Circuits sized to local and national codes All Catalyst 65
68. ule Status field System is booted with power supplies of different wattage installed and redundancy enabled System log and syslog messages are generated The lower wattage supply is disabled Catalyst operating system For Cisco IOS both power supplies come on The total available wattage is the output wattage of the higher wattage power supply System is booted with power supplies of equal or different wattage installed and redundancy disabled System log and syslog messages are generated System power equals the combined power capability of both supplies The system powers up as many modules as the combined capacity allows OL 5781 05 Catalyst 6500 Series Switches Installation Guide A Appendix A Power Supply Specifications Power Supply Redundancy amp Note When running redundant 4000 W power supplies in Catalyst 6506 and Catalyst 6509 non E series systems if you remove the power supply in bay 1 the total system power will be reduced to 2940 W after 300 seconds 5 minutes You can avoid this reduction in the total system power by leaving the 4000 W power supply in bay 1 even in a powered down state If the total system power usage is greater than 2940 W the following scenario will apply if the 4000 W power supply is removed from bay 1 these scenarios are specific to the 4000 W power supply running in redundant mode in either the Catalyst 6506 or Catalyst 6509 non E series systems I
69. upply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B Power supply output capacity 950 W maximum 100 240 VAC DC input voltage 48 VDC to 60 VDC continuous DC input current 38 A 48 VDC 30 A 60 VDC Power supply output AC supply e ISA 415V e 25A 43 3V e 19 15 A 4 50V Power supply output DC supply e ISA 41 5V e 25A 43 3V 19 15 A 50 V Catalyst 6500 Series Switches Installation Guide OL 5781 05 Appendix A Power Supply Specifications 950 W AC Input and DC Input Power Supplies W Table A 3 950 W AC Input and DC Input Power Supplies Specifications continued Item Specification Output holdup time e 20 ms minimum AC input power supply e 4 ms DC input power supply Heat Dissipation Front panel LEDs INPUT OK FAN OK OUTPUT FAIL e 4441 BTU hour approx AC input power supply e 4632 BTU hour approx DC input power supply AC input power supplies e Green Source AC voltage is OK Input voltage is 85 VAC or greater e Off sSource AC voltage falls below 7
70. wer supply cycles from off to on The power supply is powered on by de energizing the relay relay contacts go from open to closed for more than 10 seconds No relay attached NO RELAY Remote power cycling DEFAULT feature not installed OL 5781 05 Catalyst 6500 Series Switches Installation Guide E Appendix A Power Supply Specifications W 8700W AC Input Power Supply 8700 W Power Supply AC Power Cords Table A 24 lists the specifications for the AC power cords that are available for the 8700 W AC input power supply Included in the table are references to illustrations of the power cords Table A 24 8700 W Power Supply AC Power Cords Locale Power Cord Source Plug Type Cordset Rating Power Cord Part Number Reference Illustration Australia New Zealand CAB AC 16A AUS AU20S3 16 A 250 VAC Figure A 45 People s Republic of CAB AC16A CH GB16C 16 A 250 VAC Figure A 36 China Continental Europe CAB AC 2500W EU CEE 7 7 16 A 250 VAC Figure A 40 International CAB AC 2500W INT IEC 309 16 A 250 VAC Figure A 41 Israel CAB AC 2500W ISRL SI16S3 16 A 250 VAC Figure A 33 Japan North America CAB AC 2500W US1 NEMA 6 20 16 A 250 VAC Figure A 42 nonlocking plug 200 240VAC operation Japan North America CAB AC C6K TWLK NEMA L6 20 16 A 250 VAC Figure A 43 locking plug 200 240VAC operation Japan North America CAB 7513AC NEMA 5 20 16 A 125 VAC Figure A 35 100 120VAC operation Power D