APC Smart-UPS RT 8000VA 230V
Contents
1. XLJ XLT XLTW yee i 1 H amp L6 20 Q53 gy L6 30 250V 20A 4 250V 30A aje ON cO E f r i Diz Output Circuit Breaker E 8000 10000 VA XLI j oll coll cell ell os eneamenmeans go rei NP l Co Sere re IEC320 C19 E g I e ji e gll 2 9 f 10 A total Go L i p current from four OOOO receptacles BASIC CONNECTORS Serial Port Power management software and interface kits can be used with the UPS Use only interface kits supplied or approved by APC LA Ethernet Port Connect the UPS to the network Located on the Network Management Card O Q The optional Emergency Power Off EPO feature allows connected loads to be immediately de energized from a remote location without switching to battery operation see EPO Option EPO Terminal P The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lead on surge suppression devices such as TVSS Screw telephone and network line protectors When connecting grounding cable disconnect the unit from the utility power outlet is Pe ED ia PES External Battery Pack Connectors Optional external battery packs provide extended runtime during power outages These units support up to 10 external battery packs Refer to the APC Web site www apc com for the information on the external battery pack SURT192XLBP
2. 8 Switch the circuit breakers ON 9 Check line voltages 10 Replace the access panel Installing and Connecting the Batteries and Attaching the Front Bezel e SER SAN WW AN m Y SSA CONNECTING POWER AND EQUIPMENT TO THE UPS 1 Hardwire the UPS see Hardwiring 2 Connect equipment to the UPS cables not included for XLT XLJ XLTW models 3 Turn on all connected equipment To use the UPS as a master on off switch be sure that all connected equipment is switched ON 4 Press the button on the front panel to power up the UPS The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period 5 Configure the Network Management Card optional OPTIONS Refer to the APC Web site www apc com for available accessories Q External Battery Pack SURT192XLBP Q Rail Kit SURTRK2 Q Isolation Transformer Dn Service Bypass Panel CIRCUIT BREAKERS Input Circuit Breaker The UPS is protected from extreme overloads when in ON position 8000 10000 VA The breaker must be on for the UPS to operate XLUXLJ XLT XLTW A Output Circuit Breaker 8000 10000 VA
3. OPERATION FRONT DISPLAY PANEL 085 096 068 Arc 072 051 0 o o 0 048 034 M We e 024 017 0 m x 8 00 O o Batte TM toad a E eiae m Indicator Description Online The UPS is drawing utility power and performing double conversion to supply Az power to connected equipment see Troubleshooting On Battery The UPS is supplying battery power to the connected equipment Bypass The UPS is in bypass mode sending utility power directly to connected equipment N Bypass mode operation is the result of an internal UPS fault an overload condition or a user initiated command either through an accessory or the manual bypass switch Battery operation is not available while the UPS is in bypass mode see Troubleshooting Fault The UPS detects an internal fault see Troubleshooting X Overload The connected loads are drawing more power than the UPS power rating see amp 9 Troubleshooting Replace The battery is disconnected or must be replaced see Troubleshooting Battery x Feature Function Power On Press this button to turn on the UPS Read on for additional capabilities Power Off Press this button to turn off the UPS Feature Function Normal Bypass eu Manually switch connected equipment to bypass mode so that utility power is sent directly to connected equipment Battery operation 1s not a
4. Declaration of Conformity APC 2005 Wwuwiapovoom EC Declaration of Conformity E aa We the undersigned declare under our sole responsibility that the equipment specified below conforms to the following standards and directives Standards to Which Conformity Declared EN55022 EN55024 EN61000 3 2 3 3 4 2 4 3 4 4 4 5 4 6 4 8 4 11 EN60950 1 IEC60950 1 Application of Council Directives 73 23 EEC 89 336 EEC 93 68 EEC Type of Equipment Uninterruptible Power Supply Model Numbers SURT8000XLI SURT8000UXI SURT10000XLI SURT10000UXI Manufacturers American Power Conversion American Power Conversion APC Suzhou UPS Co Ltd Ballybritt Business Park 2nd Street 339 Suhong Zhong Lu Galway Ireland PEZA Cavite Economic Zone Suzhou Industrial Park Rosario Cavite Suzhou Jiangsu 215021 American Power Conversion Philippines P Re China Breaffy Rd i Castlebar American Power Conversion APC Power Infrastructure Co Ltd Co Mayo Ireland Lot 10 Block 16 Phase 4 1678 Ji Xian Road Tong An PEZA Rosario Cavite Xiamen Philippines American Power Conversion m P R China 361100 132 Fairgrounds Rd West Kingston RI 02892 USA American Power Conversion i Lot 3 Block 14 Phase 3 PEZA Rosario Cavit American Power Conversion Philippines AR 1600 Division Rd West Warwick RI 02892 USA APC Brazil LTDA j AI Xingu 850 American Power Conversion Barueri 40 Catamore Blvd Alphaville Sao Paulo East
5. install a modem if it is displayed Click OK e Select the COM port that is connected to your UPS The port settings are v bits per second 2400 data bits 8 parity none stop bit 1 flow control none e Press ENTER Example for setting the number of external battery packs SURT192XLBP Once the blank terminal window is open follow these steps to enter the number of battery packs e Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User Name is displayed Follow the prompts Type slowly waiting until each character appears on the screen prior to typing the next character Y Y Y Y Network Management Card defaults e User Name apc e Password apc e Press 1 and ENTER to select Device Manager e Select the model by entering the corresponding number then press ENTER e Press 3 and ENTER to select Configuration e Press 1 and ENTER to select Battery e Press 2 and ENTER to change the Battery Settings e Type in the number of external battery packs four battery modules per pack then press ENTER Number of packs 1 internal battery module 2 1 SURTI92XLBP 3 2 SURT192XLBP etc e Press 3 and ENTER to accept the changes e Press ESC multiple times 5 to return to the main menu e Press 4 and ENTER to log out MAINTENANCE SERVICE WARRANTY AND TRANSPORTING Replacing the Battery Module s This UPS has easy to replace hot swappable battery modules Replacement is a saf
6. 20 will pass to connected setting equipment during internal bypass operation Low Bypass Point 30 of output 15 20 25 30 Minimum voltage that the UPS voltage setting will pass to connected equipment during internal bypass operation Output Voltage XLJ models XLJ models Allows the user to select the 200 VAC 200 VAC UPS output voltage while XLT models XLT models on line 208 VAC 200 208 220 230 240 VAC XLTW models XLTW models 220 VAC 200 208 230 240 VAC XLI models XLI models 230 VAC 200 208 220 230 240 VAC Use the voltage setting applicable to your region Output Frequency Automatic Sets the allowable UPS output 50 3 Hz or 0 frequency Whenever possible 60 3 Hz the output frequency tracks the input frequency Number of Battery Number of Connected Defines the number of Packs Batteries four battery connected battery packs for modules per pack proper runtime prediction 10 EPO Emergency Power Off Option The output power can be disabled in an emergency by closing a switch connected to the EPO Adhere to national and local electrical codes when wiring The switch should be connected in a normally open switch contact External voltage is not required the switch is driven by 12V internal supply In closed condition 2mA of current are drawn The EPO switch is internally powered by the UPS for use with non powered switch circuit breakers The EPO circuit is con
7. AND THE UPS S CONNECTED TO UTILITY POWER The UPS is shut down and the battery is discharged from an extended outage None The UPS will return to normal operation when the power is restored and the battery has a sufficient charge BYPASS AND OVERLOAD LEDs ILLUMINATE UPS EMITS A SUSTAINED ALARM TONE The UPS is overloaded The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site www apc com The alarm remains on until the overload is removed Disconnect nonessential equipment from the UPS to eliminate the overload condition 14 PROBLEM AND POSSIBLE CAUSE SOLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory If bypass is the chosen mode of operation ignore the illuminated LED If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS to the normal position FAULT AND OVERLOAD LEDs ILLUMINATE UPS EMITS A SUSTAINED ALARM TONE The UPS has ceased sending power to connected equipment The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site www apc com Disconnect nonessential equipment from the UPS to eliminate the overload condition Press the OFF button then the ON button to restore power to connected equipment FAULT LED ILLUMINATES Internal UPS fault
8. Providence RI 02914 USA 06455 030 Brazil APC India Pvt Ltd 187 3 188 3 Jigani Industrial Area Jigani Bangalore 562106 Karnataka India Importer American Power Conversion A P C b v Ballybritt Business Park Galway Ireland Galway Ireland Ray S Ballard Managing Director Europe Q 5 Jan 05 2 wd La f ez d J 18 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways e Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests e www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information e www apc com support Global support searching APC Knowledge Base and using e support e Contact an APC Customer Support center by telephone or e mail Local country specific centers go to www apc com support contact for information Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support Entire contents copyright 2006 American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC the APC logo Smart UPS and PowerChute are trademarks of American Power Conversion Corporation All other trademarks product names and corpora
9. intended for OPERATING 32 to 104 F 0 to 40 C indoor use only Select a STORAGE 5 to 113 F 15 to 45 C charge UPS battery every six months location sturdy enough to handle th ight MAXIMUM andle the weig ELEVATION Do not operate the UPS where OPERATING 10 000 ft 3 000 m there is excessive dust or the STORAGE 50 000 ft 15 000 m temperature and humidity are outside the specified limits HuMIDITY 0 to 95 relative humidity non condensing Ensure the air vents on the front and rear of the UPS are not blocked WEIGHT UPS 244 Ibs 111 kg UPS WITH 284 Ibs 129 kg PACKAGING Hardwiring Wiring must be performed by a qualified electrician 1 SURE Qt Install a utility circuit breaker in accordance with local electrical codes see tables below for input wiring Switch the UPS input circuit breaker see A and utility circuit breakers OFF Remove the access panel see B Remove circular knockouts Run wires through access panel to terminal blocks Wire to ground block first Adhere to all national and local electrical codes See tables and graphics Use appropriate glands to achieve strain relief on the hardwired input and output power cables XLT XLJ AND XLTW MODELS Input Connection Output Connection optional Wire to L1 L2 and Wire to LIA L2A and c System Wiring Voltage Current Extern
10. on The LED is blinking The UPS is running an internal self test 15 Service If the UPS requires service do not return it to the dealer Follow these steps 1 Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems 2 Ifthe problem persists contact APC Customer Support through the APC Web site www apc com Note the model number of the UPS the serial number located on the back of the unit and the date purchased If you call APC Customer Support a technician will ask you to describe the problem and attempt to solve it over the phone If this is not possible the technician will issue a Returned Material Authorization Number RMA Ifthe UPS is under warranty repairs are free Procedures for servicing or returning products may vary internationally Refer to the APC Web site for country specific instructions 3 Pack the UPS in its original packaging If the original packing is not available refer to the APC Web site www apc com for information about obtaining a new set Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transit is not covered under warranty Always DISCONNECT THE BATTERY S before shipping in compliance with U S Department of Transportation DOT and IATA regulations The battery s may remain in the UPS 4 Mark the RMA on the outside of the package 5 Return the UPS b
11. 75 90 percent 5 second delay 5 second delay 30 second delay At Low Battery Never 20 seconds 0 20 60 120 240 480 720 960 seconds 2 5 7 10 12 15 18 20 minutes 0 percent 2 minutes PowerChute software provides automatic unattended shutdown when approximately two minutes of battery runtime remains 0 seconds 0 20 60 120 240 480 720 960 seconds Set the interval at which the UPS will execute a self test Uniquely identify the UPS i e server name or location for network management purposes Specify the percentage to which batteries will be charged following a low battery shutdown before powering connected equipment Mute ongoing alarms or disable all alarms permanently Set the interval between the time when the UPS receives a shutdown command and the actual shutdown The low battery warning beeps become continuous when two minutes of runtime remains Change the warning interval to a higher setting if the operating system requires a longer interval for shutdown Specify the time the UPS will wait after the return of utility power before turn on to avoid branch circuit overloads NOTE SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE NETWORK MANAGEMENT CARD OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE FACTORY USER SELECTABLE FUNCTION DESCRIPTION DEFAULT CHOICES High Bypass Point 10 of 5 10 15 Maximum voltage that the UPS output voltage
12. Arc www apc com User Manual English APC Smart UPS RT 8000 10000 VA 200 240 VAC Tower Rack Mount 6U Uninterruptible Power Supply 990 2689C 04 2006 Introduction The APC Smart UPS RT is a high performance uninterruptible power supply UPS that provides protection for electronic equipment from utility power blackouts brownouts sags and surges The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged INSTALLATION Read the safety information sheet before installation Unpacking Inspect the UPS upon receipt Notify the carrier Literature kit containing and dealer if there is damage XLT XLTW models only Software CD The packaging is recyclable save it for reuse or Smart UPS User Manuals CD dispose of it properly XLI model only Six output power cords Check the package contents UPS with batteries disconnected a Serial cable Product documentation safety and Two front bezels warranty information Network Management Card documentation Removing the Batteries The unit is heavy To lighten the unit remove the batteries Refer to the unpacking instructions on the carton in which the unit is shipped Specifications TEMPERATURE This unit is
13. Do not attempt to use the UPS Turn the UPS off and have it serviced immediately REPLACE BATTERY LED ILLUMINATES Replace Battery LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected Check that the battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery Failure of a battery self test The UPS emits short beeps for one minute and the Replace Battery LED illuminates The UPS repeats the alarm every five hours Perform the self test procedure after the battery has charged for 24 hours to confirm the Replace Battery condition The alarm stops and the LED clears if the battery passes the self test UPS OPERATES ON BATTERY ALTHOUGH LINE VOLTAGE EXISTS Very high low or distorted line voltage Inexpensive fuel powered generators can distort the voltage Move the UPS to a different line circuit Test the input voltage with the utility voltage display DIAGNOSTIC UTILITY VOLTAGE All five LEDs are illuminated The line voltage is extremely high and should be checked by an electrician There is no LED illumination If the UPS is plugged into a properly functioning utility power outlet the line voltage is extremely low ONLINE LED There is no LED illumination The UPS is running on battery or it is not turned
14. ON Batteries are not connected properly button not pushed UPS not connected to utility power supply Very low or no utility voltage Check that the battery connectors are fully engaged Press the button once to power the UPS and the connected equipment Check that the power cable from the UPS to the utility power supply is securely connected at both ends Check the utility power supply to ensure proper voltage at the receptacle UPS WILL NOT TURN OFF button not pushed Internal UPS fault Press the button once to turn the UPS off Do not attempt to use the UPS Unplug the UPS and have it serviced immediately UPS BEEPS OCCASIONALLY Normal UPS operation when running on battery None The UPS is protecting the connected equipment UPS DOES NOT PROVIDE EXPEC TED BACKUP TIME The UPS battery module s are weak due to a recent outage or are near the end of service life Charge the battery module s Modules require recharging after extended outages and wear faster when put into service often or when operated at elevated temperatures If the battery module s are near the end of service life consider replacing even if the Rep ace Battery LED is not illuminated FRONT PANEL LEDS FLASH SEQ UENTIALLY The UPS has been shut down remotely through software or an optional accessory card None The UPS will restart automatically when utility power returns ALL LEDS ARE OFF
15. SIBILITY OF SUCH DAMAGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise 16 REGULATORY NFORMATION Regulatory Agency Approvals and Radio Frequency Warnings 200 208 220 230 240 V MODELS This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference The user is responsible for correcting the interference Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits Ce cc LISTED 42C2 LR 63938 E95463 TOREJ FRUER DEN Ay TEVE JIR ES BI 2E HI jI WINA VCCI OE KJK JIA ATHE CT lt O ZE EXER CHATS CBR pies BZ TyA kP2 0 BT lt O lk Vl EH TOR 0 ASO IR BR 37 SKIBKEANSTEMHOVET BSMI e T3A031 WEHE RP 38 FIR NI AWE m gt FLEE BENE PRE BIBE aT TE TERRWD P gt R BERDA DR TON BHR 17
16. al Input Circuit Wire Size Full Load Breaker typical typical Nominal SURTS8000XLJ Input amp 200 208 220 240 V 40A 50 A 2 pole 10mm SURT8000XLT Output for Input Wiring only 8 AWG SURT8000XLTW SURTI0000XLJ Input amp 200 208 220 240 V XLJ 50 A 60 A or 63 A 2 pole 16mm SURT10000XLT Output XLT 48 A for Input Wiring only 6 AWG SURTI0000XLTW XLTW 48 A XLI MODELS Input Connections Output Connection optional Single Phase Wire to L1 N and D Wire to L1A N1 and c Three Phase Wire to L1 L2 L3 N and System Wiring Number Voltage Current External Input Wire Size of Full Load Circuit Breaker typical Phases Nominal typical SURT8000XLI Input 1 220 230 240 V 40A 50 A 2 pole 10mm Input 3 380 400 415 V 15 A phase when 50 A 4 pole 10mm Neutral online 40 A on L1 in bypass Output 1 220 230 240 V 40A not required 10mm SURTI10000XLI Input 1 220 230 240 V SOA 63 A 2 pole 16mm Input 3 380 400 415 V 18 A phase when 63 A 4 pole 16mm Neutral online 50 A on LI in bypass Output 1 220 230 240 V SOA not required 16mm2 7 XLI model only For three phase input set the Input Phase Selector switch see C to 3 For single phase input leave switch in default position of 1 XLT XLJ XLTW MODELS OUTPUT XLI MODEL UNA eee iz PIED OUTPUT ee ERERES Hea Aa D sa Ee AW S S e jen
17. e procedure isolated from electrical hazards You may leave the UPS and connected equipment on during the procedure See your dealer or contact APC at the Web site www apc com for information on replacement battery modules The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack s Upon battery disconnection equipment is not protected from power outages Use caution when handling heavy battery modules Refer to Installing and Connecting the Batteries and Attaching the Front Bezel for battery replacement procedure reverse instructions for battery removal e Be sure to deliver the spent battery to a recycling facility or ship it to APC in the bir replacement battery packing material Transporting the UPS Always disconnect the battery module s before shipping the UPS in compliance with U S Department of Transportation DOT and IATA regulations The battery module s may remain in the UPS 1 Shut down and disconnect any equipment attached to the UPS 2 Shut down and disconnect the UPS from the power supply 3 Unplug the battery connectors For shipping instructions contact APC at the Web site www apc com TROUBLESHOOTING Use the table below to solve minor installation and operation problems Refer to the APC Web site www apc com for assistance with complex UPS problems PROBLEM AND POSSIBLE CAUSE SOLUTION UPS WILL NOT TURN
18. sidered a Class 2 circuit UL CSA standards and an SELV circuit IEC standard EPO switch Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV If circuit standard cannot be confirmed use a contact closure switch Use one of the following cable types to connect the UPS to the EPO switch e CL2 Class 2 cable for general use e CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air e CL2R Riser cable for use in a vertical run in a floor to floor shaft e CLEX Limited use cable for use in dwellings and for use in raceways e For installation in Canada Use only CSA certified type ELC extra low voltage control cable e For installation in other countries Use standard low voltage cable in accordance with local regulations Terminal Mode to Configure UPS Parameters Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS Connect the serial cable to the serial port on the back of the UPS 1 Open a terminal program Example HyperTerminal e From the Desktop go to Start gt Programs gt Accessories gt Communication gt HyperTerminal Double click on the HyperTerminal icon e Follow the prompts to choose a name and select an icon Disregard the message must
19. te names are the property of their respective owners and are used for informational purposes only 19
20. ttery Operation The UPS switches to battery operation automatically if the utility power fails While running on battery an alarm beeps four times every 30 seconds Press the button to silence this alarm If the utility power does not return the UPS continues to supply power to the connected equipment until the battery is fully discharged When two minutes of runtime remain the UPS emits a continuous beep If PowerChute or the Network Management Card is not being used files must be manually saved and the computer must be properly shut down before the UPS fully discharges the battery The UPS battery life differs based on usage and environment Refer to the APC Web site www apc com for on battery runtimes USER CONFIGURABLE ITEMS NOTE SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE NETWORK MANAGEMENT CARD OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE EUNGTIGN FACTORY UsER SELECTABLE DESCRIBTION DEFAULT CHOICES Automatic Self Test Every 14 days 336 hours Every 7 days 168 hours Every 14 days 336 hours On Startup Only No Self Test Up to eight characters to UPS ID UPS IDEN define the UPS Date of Last Battery Manufacture Date mm dd yy Reset this date when you replace Replacement the battery modules Minimum Capacity Before Return from Shutdown Alarm Delay After Line Failure Shutdown Delay Duration of Low Battery Warning Synchronized Turn on Delay 0 15 25 35 50 60
21. vailable while the UPS is in bypass mode See Troubleshooting Cold Start This is not a normal condition Supply immediate battery power to the UPS and connected equipment see Troubleshooting Press and hold the button to power up the UPS and connected equipment The UPS will emit two beeps During the second beep release the button Self Test Automatic The UPS performs a self test automatically when turned on and every two weeks thereafter by default During the self test the UPS briefly operates the connected equipment on battery Manual Press and hold the button for a few seconds to initiate the self test Diagnostic Utility Voltage 200v 208V 220V 0236 0245 0256 0217 0226 0238 0199 0207 0219 0180 0189 0200 0161 0170 0181 The UPS has a diagnostic feature that displays the utility voltage Plug the UPS into the normal utility power The UPS starts a self test as part of this procedure The self test does not affect the voltage display Press and hold the button to view the utility voltage bar graph display After a few seconds the five LED Battery Charge aa display on the right of DD dap the front panel shows the utility input voltage 230V 240V Refer to the figure at left for the voltage reading values are not listed on the 0266 0276 UPS 0248 0258 0229 0239 The display indicates the voltage is between the displayed value on the list and es the next higher value O LJ On Ba
22. y insured prepaid carrier to the address given to you by Customer Support Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a Returned Material Authorization RMA number from customer support Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POS