Home

BlueWalker VFI 2000CRM LCD

image

Contents

1. el i 7 ill i i i CJ Remove front panel Connect the AC input and Put the front panel back to the re connect battery wires unit Step 3 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords The power cord is supplied in the UPS package G Power Waker Step 4 UPS output connection For socket type outputs simply connect devices to the outlets For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm power cords for 3KVA model c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 5 Communication connection Communication port USB port jaa Par Intelligent slot amp To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS sta
2. 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting voltage 10 O E O PowerWatker a in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable disable when UPS is off Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass voltage range setting Parameter 2 amp 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 200 208 220 230 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage point For 200 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac Default 170Vac For 100 110 115 120 127 VAC models 95 110 setting the low voltage point in parameter 3 from 95Vac to 110Vac Default 95Vac 8 Autonomy limitation setting Parameter 3 Set up backup time on battery mode for general outlets 0 999 setting the backup time in minutes from 0 999 for general outlets on battery mode 0 When setting a
3. is fault UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains The UPS shut down automatically because of overload at the UPS output The UPS shut down automatically because Short circuit occurs on the UPS output A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power 14 G Power Walker Remedy The AC input power is not Check if input power cord connected well firmly connected to the mains The AC input is connected Plug AC input power cord to to the UPS output AC input correctly Check if all batteries are connected well Contact your dealer Contact your dealer UPS is overload Remove excess loads from UPS output Remove excess loads from UPS output Remove excess loads from UPS output first Then shut down the UPS and restart it Remove excess loads from UPS output and restart it Check output wiring and if connected devices are in short circuit status Contact your dealer O _ P PowerWalker Symptom Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value charged least 5 hours and then check capacity If the problem stil
4. Oo B P PowerWalker Online UPS e PowerWalker VFI 1000CRM LCD PowerWalker VFI 2000CRM LCD PowerWalker VFI 3000CRM LCD Manual Uninterruptible Power Supply System Oo G Power Walker Table of Contents Ls Important Safety WarniNO wextsisscctinanscuntedessatininscensedeunediainnauteianeatiasanauibiveiamainnaniedeunesiags 1 Le MAIS POO n E E EA 1 Le PED O arn EEA EE O E E 1 Be Di TISAI a ETE E E EES ENE E SE 1 FEODAU aE AAEE E A A OED 1 1 5 Maintenance service and faults ccccecseseceeevaveueuseeeeavaueusueueaeavaueueusaeavavaveusunesavavanss 2 PAA AIKON ana eUD io O iS 3 2al Rear Danei VOW arsi EN N E A N 3 27 OK LUD ME UPS ooien an o E O R 4 2 3 UPS Tower Rack Installation cccceceeeeeeceeeevaeeeeevevaeseuevaveueevavaesevevaeeeeevavansnuavansneenas 6 Di OPAOS aonair E EE AE E E 7 Migs BUON OPT ALI OO N renee rE EEE EEEN EE EEEE EEEE EE EEES 7 25 ECD u n E A A E E EE 7 23 3 AUdDIE FIONN esner eener O E EEEREN OKETA OAE EEEa 9 IA CD di Day WONrGINGS ING OX orn O a 9 Bae CIS E e PE E A EA E E E E E tet EA AE eee 9 3 6 Operating Mode Description cccccsccsecccecnecececnececeauscesenuecesegueceseguecesenuecnseguecesenanegs 12 3 7 Faults Reference Code s sssesssssnsnnnnnnnnnanannnnnnnnnnnnnnununnnnnnnnnnnnnnunnnnnnnnnnnnnnnnnnnnnnnnne 13 3O NANO MACAO arrine oaa EEEE EEE E ENA EEEE EREA 13 Ae OUNO NOON O aeara ran ect E E E E E EEEE A E EEE EEA NES 14 D Storage ana Maite aC Castanos auanoscapsian
5. PS Press and hold ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm When the UPS is on battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But its not applied to the situations when warnings or errors occur Up key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON Mute button for 5 seconds to enter UPS self testing while in AC mode ECO mode or converter mode Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS UPS will be in standby mode under power normal or transfer to OFF Enter Button Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 Select Button seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode Down key Press this button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute ON Mute Select and Select buttons simultaneously for 5 seconds Then UPS will enter to Button bypass mode This action will be ineffective when the i
6. UPS system G MLL VW ML 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table Type PowerWalker VFI 1000CRM LCD PowerWalker VFI 1000CRM LCDL PowerWalker VFI 2000CRM LCD PowerWalker VFI 2000CRM LCDL spit PowerWalker VFI 3000CRM LCD PowerWalker VFI 3000CRM LCDL 0 2 1 Rear panel view PowerWalker VFI 1000CRM LCD L PowerWalker VFI 2000CRM LCD L PowerWalker VFI 3000CRM ZZS A E gt n CS mil m e k l d a h 3 Seal lt 1 AC input 5 SNMP intelligent slot option 2 Input circuit breaker 6 External battery connection 3 USB communication port 7 Output receptacles 4 RS 232 communication port 8 Output terminal O G Power Walker 2 2 1 3K Setup the UPS Step 1 External battery connection Only for long run models This UPS is not including batteries Please connect external batteries as below chart m goooon0 5 S 1 m N JON N N S Cooma To external battery Step 2 Connect battery wires For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3
7. XP Vista 2008 7 8 Linux Unix and MAC Power management from SNMP manager and web browser Derate capacity to 80 of capacity in Frequency converter mode or when the output voltage is adjusted to 200 208VAC Product specifications are subject to change without further notice 17
8. dividuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to connect the loads to the UPS system When installing the equipment it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3 5mA 1 4 Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system 1 5 Maintenance service and faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring o
9. ery information BATTERY LEVEL Tunn Indicates the battery is fault AE FAUL BATT FAULT Indicates low battery level and low battery voltage LOW BATT Input amp Battery voltage information a Indicates the input voltage or frequency or battery voltage CO nmin voc Vac Input voltage Vdc battery voltage Hz input frequency 2 D CD n ao A G Power Waker 3 3 Audible Alarm Description Buzzer status Muttedd Battery Mode Sounding every 4 seconds Yes Low Battery Sounding every second Overload e a twice every second Continuously sounding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index mso S ooo C a tate pS Sd comverter wo o e eee C e 3 5 UPS Setting There are three parameters to set up the Q hoon 3 UPS GE aa Parameter 1 It s for program alternatives Refer to below table z Ena Parameter 2 and parameter 3 are the J J setting options or values for each program 01 Output voltage setting Parameter 3 Output voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 200 presents output voltage is 200Vac 208 presents output voltage is 208Vac 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac Default 240 presents output voltage is 240Vac For 100 110 150 120 127 VAC models you may choose the following output voltage 100 presents output voltage
10. is 100Vac QQ PowerWalker 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac Default 127 presents output voltage is 127Vac 02 Frequency Converter enable disable Interface Parameter 2 amp 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default Parameter 2 amp 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz Parameter 3 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable Default 05 ECO voltage range setting Parameter 2 amp 3 Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting range in parameter 3 is from 3V to 12V of the nominal voltage Default 6V LLS Low loss voltage in ECO mode in parameter 2 For 200 208 220
11. l persists consult your dealer Batteries defect Contact your dealer to replace the battery 15 OoOo G Power Walker 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer s Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 40 C 45 C Every 2 months 16 G Power Waker 6 Specifications PowerWalker PowerWalker PowerWalker MODEL VFI 1000CRM LCD L VFI 2000CRM LCD L VFI 3000CRM LCD L j APACITY 2000 VA 1600 W INPUT 160VAC 140VAC 120VAC 110VAC 5 Ambient Temp lt 35 C based on load percentage 100 80 80 70 70 60 60 0 Voltage 175VAC 155VAC 135VAC 125VAC 5 Ambient Temp lt 35 C shi based on load percentage 100 80 80 70 70 60 A 0 300 VAC 5 290 VAC 5 requency Range 40Hz 70 Hz hase Single phase with ground ower Factor 0 99 nominal voltage in
12. nput voltage is out of acceptable range ON Mute Button 3 2 LCD Panel l l HA LOAD LEVEL CD Ga OUTPUT OBSA S reS D Dr eye Ae A e a Lipo n Ci E m E Ep BATTERY LEVEL E LI E A OoOo O PowerWalker Function Remaining backup time information Indicates the remaining backup time in pie chart 7 nt Indicates the remaining backup time in numbers s H hours M minute S second Fault information SAN Indicates that the warning and fault occurs H Indicates the warning and fault codes and the codes are listed in f o details in 3 5 section Mute operation MK Indicates that the UPS alarm is disabled Output amp Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency P gt 4 SB Ca x l Load information sy son 15 00 Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit _SHORT _ Mode operation information Indicates the UPS connects to the mains Indicates the battery is working ii EL Indicates the bypass circuit is working p AE Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is working Indicates the Battery level by 0 25 26 50 51 75 and 76 100 Batt
13. pn E BATTERY LEVEL Bay _ LOAD LEVEL pe BATTERY LEVEL LOAD LEVEL E gae BATTERY LEVEL Uun G MLL 3 7 Faults Reference Code 14 Z BR Inverter voltage Low 13 x o o 3 8 Warning indicator Icon flashing Low Battery Sounding every second Battery is not connected Sounding every second Over Charge A Cate Sounding every second Battery faut AN Bypass frequency unstable F u EEPROM error EE AN 13 4 Troubleshooting If the UPS system does not operate ea please solve the e by using the table below Symptom No indication and alarm even though the mains is normal The icon Z and flashing on LCD display and alarm is sounding every second Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the icon lt is lighting on LCD display and alarm is continuously sounding The icon A andan on LCD display and alarm iS sounding twice every second Fault py is shown as 43 and The display and alarm is continuously sounding display and alarm is continuously sounding Fault code is shown as 01 02 03 04 11 12 13 41 and 45 on LCD display and alarm is continuously sounding Possible cause cause The external or internal battery is incorrectly connected Battery voltage is too high or the charger is fault Battery voltage is too low or the charger
14. put voltage OUTPUT 200 208 220 230 240VAC 1 Batt Mode 47 53 Hz or 57 63 Hz Synchronized Range 50 Hz 0 25 Hz or 60Hz 0 3 Hz Ambient Temp lt 35 C 105 110 UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal requency Range requency Range Batt Mode 110 130 UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal gt 130 UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal urrent Crest Ratio armonic Distortion C Mode to Batt Mode nverter to Bypass IIO O minl Dbl oO 5 ae lt O oO JJS rel se ee A als O D A Oo oO fed ct O gt lt 3 THD linear load lt 6 THD non linear load Zero 4 ms Typical Pure Sinewave i Qa gt D oe E Time w lt D O 5 3 gJ w ct zZ O Q OM NS EFFICIENCY Numbers S A 6 O Charging Voltage 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 Battery Numbers o 2 3 4 6 8 6 8 Long run Charging Current 1 0A 2 0A 4 0A 6 0 A Model ee eee 27 4VDC 41 0VDC 54 7 VDC 82 1VDC 109 4VDC 82 1VDC 109 4VDC ging g 1 1 1 1 1 1 1 PHYSICAL Standard Model Long run Model Net Weight kg OP OR S Oa O ENVIRONMENT 20 90 RH 0 40 C non condensing Less than 50dBA 1 Meter MANAGEMENT Supports Windows 2000 2003
15. s 0 the backup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled Default 00 Exit setting 3 6 Operating Mode Description Operating mode LCD display ECO mode Frequency Converter mode Battery mode Bypass mode Standby mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second UPS is powered off and no output supply power but still can charge batteries 12 G MLL CU cw 2327 2327 C JU LF C JUa O48 iU 2 Je Loe LOAD LEVEL E Loi BATTERY LEVEL WE Bae _ LOAD LEVEL WX miee EJ rg TE BATTERY LEVEL EZ LOAD LEVEL t BATTERY LEVEL EY _ LOAD LEVEL Ex
16. spaduncnsiapniamsinpaatmaeepniamuns aaatasnapsianopadsacninapniamoinnians 16 O SDECIFICAU ONS siasneinnvesanwvevaesunienaeanseaawesnseananeusnasnesuniaiveaanbsiaiaunneiarandeateranbadanensneaganineegusss 17 Oo G Power Waker 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation Please transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near heater Do not block ventilation holes in the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS system e g laser printers to the UPS output sockets Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any in
17. tus through PC The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 6 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 7 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 eo to the website 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock O G Power Walker 2 3 UPS Tower Rack Installation Rack mount Installation This UPS can be mounted in the 19 rack chassis Please follow below steps to position this UPS Step 1 Tower Installation Step 1 G MLL 3 Operations 3 1 Button operation Turn on the U
18. utlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not dismantle the

Download Pdf Manuals

image

Related Search

Related Contents

Service Manual  BCー-7E/9/320/32ー /325/326シリ一ズヌ寸応  Bedienungsanleitung  [ITA] MATRIX Manuale installazione v1-0 lo  Olympus Pen S 3.5 Operating Instructions  取扱説明書 - no!HAIR (ノーノーヘア)  View PDF - e  Tripp Lite SU2200XLNAFTA User's Manual    FORE-SIGHT ® MC-2000 Series Cerebral Oximeter User Manual  

Copyright © All rights reserved.
Failed to retrieve file