APC SMX3000HV-BNDL uninterruptible power supply (UPS)

image

Contents

1. Green mode Power quality Menu type Audible alarms Display mode Sensitivity Low and high voltage transfer points Low battery warning threshold Automatic self test interval Battery install date Reset energy meter Enter start up wizard Perform firmware update Reset to factory defaults Outlet group configuration delays reboot min return load shedding X X X Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U x scrolling menu x x scrolling menu x x x x scrolling menu x x x x scrolling menu x scrolling menu x scrolling menu x x scrolling menu x x X Main Menu Display Description Standard Option Advanced Option Test amp Diagnostics Logs About UPS self test UPS alarms test UPS calibration test Last 10 transfer events if applicable Last 10 fault events if applicable Model identification Part number Serial number UPS manufacture date Replace battery part number External battery part number Battery install date Replace battery date UPS firmware revision NMC Information part serial version numbers manufacture date MAC address firmware revision if applicable X X X X X X Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Configuration UPS Settings Start up Settings Use the display interface to configure these settings at initial start up The UPS will promp
2. Vac z dNOwd dNOwd su0755a su0754a Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U su0783a Rear panel features continued SmartSlot Use the SmartSlot to install an optional Network Management Card NMC Chassis ground screw The UPS has a ground screw for connecting the ground leads on transient voltage devices Prior to connecting a ground lead disconnect the UPS from AC power Utility power cable Use the power cable supplied to connect the UPS to utility power UPS circuit breaker reset button Press this button to reset the UPS circuit breaker after an overload condition has occurred Controllable Outlet Group 1 Connect critical electronic devices such as a computer monitor modem or other data sensitive devices to these outlets Controllable Outlet Group 2 Connect peripheral electronic devices to these outlets Controllable Outlet Group 3 Connect peripheral electronic devices to these outlets External battery connector Use the external battery cable to connect the UPS to an XLBP XLBPs provide extended runtime during power outages The UPS can support up to 10 external battery packs EPO terminal The Emergency Power Off EPO terminal allows
3. the user to connect the UPS to a central EPO system Serial port To use PowerChute software connect the serial cable supplied to the Serial port Use only interface kits supplied or approved by APC by Schneider Electric Any other serial interface cable will be incompatible with the UPS connector USB port Connect a USB cable from a computer to use power management software Note Serial and USB communication can only be used individually they cannot be used at the same time Installation UPS For UPS installation instructions refer to the Smart UPS X 2000 3000 VA Installation Guide that is supplied with the UPS The guide is also available on the enclosed User Manual CD and the APC by Schneider Electric Web site at www apc com PowerChute network management software For installation instructions refer to the PowerChute software CD supplied with the UPS Installation instructions are also available on the APC by Schneider Electric Web site www apc com External battery pack optional For installation instructions refer to the Smart UPS X 2000 3000 VA External Battery Pack Installation Guide that is supplied with the external battery pack The guide is also available on the enclosed User Manual CD and the APC by Schneider Electric Web site at www apc com Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Operation Connect Equipment CAUTION RISK OF EQUIPMEN
4. using the Advanced menus Normal e Normal e Reduced e Low Select the level of sensitivity to power events that the UPS will tolerate e Normal The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment e Reduced The UPS will tolerate some fluctuations in power e Low The UPS will tolerate more fluctuations in power and will go on battery power less often If the connected load is sensitive to power disturbances set the sensitivity to Normal using the advanced Configuration menu Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Function Factory Default Options Description Low Runtime 150 sec Value set in seconds The UPS will emit an audible alarm when the Warning remaining runtime has reached this level Date of Last Date set at factory Reset this date when the battery module is replaced Battery Replacement Audible Alarm On On Off The UPS will mute all audible alarms if this is set to Off or when any of the display buttons are pressed Display Always on e Always on To conserve energy the display panel illumination Dimmer e Auto dim dims or extinguishes when no events are present Full e Auto off display panel illumination returns when the UPS changes status as a result of an event or if the display panel is touched Auto Self Test On start up and every e Last test 14 days The interval at which the UPS will execute a self test In
5. Arc by Schneider Electric a Operation Manual Smart UPS X ee Uninterruptible Power Supply oe Tower Rack Mount 4U Low Voltage SMX2000LV SMX2000LVNC SMX3000LV SMX3000LVNC High Voltage SMX2200HV SMX3000HV SMX3000HVT SMX3000HVNC Overview Product Description The APC by Schneider Electric Smart UPS is a high performance uninterruptible power supply UPS The UPS provides protection for electronic equipment from utility power blackouts brownouts sags and surges small utility power fluctuations and large disturbances The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are fully discharged This user manual is available on the enclosed CD and on the APC by Schneider Electric Web site www apc com Important Safety Messages Read the instructions carefully to become familiar with the equipment before trying to install operate service or maintain it The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure The addition of this symbol to a Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed The following safety messages may appear throughout this man
6. CLUDED OR LIMITED BY APPLICABLE LAW To obtain service under warranty you must obtain a Returned Material Authorization RMA number from customer support Customers with warranty claims issues may access the SEIT worldwide customer support network through the SEIT Web site www ape com Select your country from the country selection drop down menu Open the Support tab at the top of the web page to obtain information for customer support in your region Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase APC by Schneider Electric Worldwide Customer Support Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways e Visit the APC by Schneider Electric Web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests www apc com Corporate Headquarters Connect to localized APC by Schneider Electric Web sites for specific countries each of which provides customer support information Wwww apc com support Global support searching APC by Schneider Electric Knowledge Base and using e support e Contact the APC by Schneider Electric Customer Support Center by telephone or e mail Local country specific centers go to www apc com support contact for contact information For informati
7. NTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF SEIT S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT S SOLE LIABILITY AND PURCHASER S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES IN NO EVENT SHALL SEIT ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES SPECIFICALLY SEIT IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE WHETHER DIRECT OR INDIRECT LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWARE LOSS OF DATA COSTS OF SUBSTITUANTS CLAIMS BY THIRD PARTIES OR OTHERWISE NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT S LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EX
8. T DAMAGE e Adhere to all local and national electrical codes e Wiring should be performed by qualified electrician e Always connect the UPS to a grounded outlet Failure to follow these instructions can result in equipment damage Note The UPS will charge to 90 capacity in the first three hours of normal operation Do not expect full battery runtime capability during this initial charge period 1 Connect equipment to the outlets on the rear panel of the UPS Refer to Switched Outlet Groups on page 12 2 Connect the UPS to the building utility power Connect the UPS to a two pole three wire grounded source only 3 To use the UPS as a MASTER ON OFF switch turn on equipment that is connected to the UPS 4 To turn on the UPS and all connected equipment Press the ON OFF button on the front panel of the UPS 5 Follow the prompts to configure the UPS using the set up wizard the first time the UPS is turned on Refer to Configuration on page 9 and Menu overview on page 6 Network Management Card settings These settings are available only on units that have a Network Management Card NMC e NMC IP Address Mode e NMC Default Gateway Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U 5 Display Interface Online LED UPS Output ON OFF button On Battery LED Fault LED Replace Battery LED Display screen UP DOWN arrow buttons ENTER button m ESCAPE button o
9. U Troubleshooting Problem and Possible Cause Solution The UPS will not turn on or there is no output The unit has not been turned on Press the ON button once to turn on the UPS The UPS is not connected to utility Be sure the power cable is securely connected to the unit and to the utility power power supply The input circuit breaker has tripped Reduce the load on the UPS Disconnect nonessential equipment and reset the circuit breaker The unit shows very low or no Check the utility power supply to the UPS by plugging in a table lamp If the utility power light is very dim check the utility voltage The battery is not securely connected Be sure that all battery connections are secure There is an internal UPS fault Do not attempt to use the UPS Unplug the UPS and have it serviced immediately The UPS is operating on battery while connected to input utility power The input circuit breaker has tripped Disconnect nonessential equipment and reset the circuit breaker There is very high very low or Move the UPS to a different outlet on a different circuit Test the input distorted input line voltage voltage with the utility voltage display If acceptable to the connected equipment reduce the UPS sensitivity UPS is beeping The UPS is operating normally None The UPS is protecting the connected equipment UPS does not provide expected backup time The UPS battery is weak d
10. a su0343a 9000000 9 Display interface operation Use the UP DOWN arrow buttons to scroll through the main menu options Press ENTER to view the sub menus under each main menu option Press ESCAPE to exit a sub menu and return to a main menu Menu overview The display interface has Standard and Advanced menu screens The preference for Standard or Advanced menu selections is made during initial installation and can be changed at any time through the Configuration menu The Standard menu screens are the most commonly used screens Default settings are included on the Standard menu screens The Advanced menu adds scrolling status screens and additional menus for UPS control and logs Note Actual menu screens may differ by model and firmware revision 6 Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Main Menu Display Description Standard Option Advanced Option Status Some of these options are displayed as scrolling menus Control Configuration Operating mode Efficiency Load power Watts VA Load amperage Load energy meter Battery charge level Battery runtime hours min Battery temperature Battery voltage Number of external battery packs Input voltage and frequency Output voltage and frequency Last transfer reason Last UPS self test result Outlet group status NMC IP address if used UPS control Group outlet control Language Output voltage setting
11. ched Outlet Groups will turn on again after a shutdown Load Shed On Disabled e Shutdown with When the unit switches to battery power the UPS can Battery Delay disconnect power to the Switched Outlet Groups to e Shutdown save runtime immediately e Turn off Configure this delay time use the LOAD SHED TIME immediately WHEN ON BATTERY setting Turn off with delay e Disabled Load Shed Time Disabled Set the value in The amount of time the outlets will function on battery when On Battery seconds power before they will turn off Load Shed On Disabled Shutdown with Configure this time using the LOAD SHED RUNTIME Runtime delay REMAINING setting e Shutdown immediately e Turn off immediately Turn off with delay e Disabled Load Shed On Disabled Set the value in When the remaining runtime reaches this level the Runtime Remaining seconds Switched Outlet Groups will turn off Load Shed on Disabled e Disabled In the event of an overload greater than 105 output Overload e Enabled the Switched Outlet Groups will immediately turn off Network Management Card settings to conserve power for critical loads The Switched Outlet Groups will only turn on again with a manual command These settings are available only on units that have a Network Management Card NMC e NMC IP Address Mode e NMC Default Gateway Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U 13 Emergency Power Off Overview The Emerge
12. cted to the UPS However there is no limit to the number of XLBPs that can be used with the UPS e Refer to Specifications on page 2 for UPS and battery weight Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Specifications For additional specifications refer to the APC by Schneider Electric Web site at www apc com Operating 0 to 40 C 32 to 104 F Temperature ciorage 15 to 45 C 5 to 113 F charge UPS battery every six months Maximum Operating 3 000 m 10 000 ft enn Storage 15 000 m 50 000 ft 0 to 95 relative 0 to 40 C 32 to 104 F Humidity humidity non condensing Battery Maintenance free Battery cartridge weight 23 8 kg 52 4 1b sealed lead acid UPS weight 17 2 kg 38 Ib UPS battery cartridge weight 41 kg 90 4 Ib SMX 120BP chassis weight 13 24 kg 29 2 Ib SMX 120BP chassis battery cartridge weight 47 54 kg 104 8 Ib 2 Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Product Overview Front panel features Oo Display interface panel ups battery cable and connector Battery compartment Bezels mal m Rear panel features SMX2000 120 Vac SMX3000 120 Vac i LI su0756a su0757a SMX2200 SMX3000 230 Vac SMX3000 208
13. for two 2 year from the date of purchase The SEIT obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products Repair or replacement of a defective product or parts thereof does not extend the original warranty period This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase Products may be registered online at warranty apc com SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user s or any third person s misuse negligence improper installation testing operation or use of the product contrary to SEIT s recommendations or specifications Further SEIT shall not be liable for defects resulting from 1 unauthorized attempts to repair or modify the product 2 incorrect or inadequate electrical voltage or connection 3 inappropriate on site operation conditions 4 Acts of God 5 exposure to the elements or 6 theft In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered defaced or removed EXCEPT AS SET FORTH ABOVE THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE APPLICABLE TO PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHA
14. gured to shut down after a short delay If equipment has dependent peripherals that must restart or shut down in a specific order such as an ethernet switch that must restart before a connected server connect the devices to separate groups Equipment that needs to reboot independently from other equipment should be connected to a separate group 3 Use the Configuration menus to configure how the Switched Outlet Groups will react in the event of a power outage 12 Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Customize Switched Outlet Groups Use the Control menus to customize the Switched Outlet Groups Function Factory Default Options Description Name String Outlet Groups Outlet Group 1 2 3 Edit these names using an external interface such as the Network Management Card Web interface UPS Name String APC UPS Turn On Delay 0 sec Set the value in The amount of time the Switched Outlet Groups will seconds wait between receiving the command to turn on and the actual startup Turn Off Delay 90 sec Set the value in The amount of time that the Switched Outlet Groups seconds will wait between receiving the command to turn off and the actual shut down Reboot Duration 8 sec Set the value in The amount of time that the Switched Outlet Groups seconds must remain off before it will restart Minimum Return O sec Set the value in The amount of battery runtime that must be available Time seconds before the Swit
15. ncy Power Off EPO option is a safety feature that will immediately disconnect all connected equipment from AC power The UPS will immediately shut down and will not switch to battery power Connect each UPS to the EPO switch In configurations where multiple units are connected in parallel each UPS must be connected to the EPO switch The UPS must be restarted for power to return to connected equipment Press the ON OFF button on the front panel of the UPS 4 CAUTION RISK OF EQUIPMENT DAMAGE OR PERSONNEL INJURY e Adhere to all local and national electrical codes e Wiring should be performed by qualified electrician e Always connect the UPS to a grounded outlet Failure to follow these instructions can result in equipment damage and minor or moderate injury Normally open contacts Normally closed contacts 14 1 Ifthe EPO switch or relay contacts are normally open insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block Use 16 28 AWG wire 2 Secure the wires by tightening the screws If the contacts are closed the UPS will turn OFF and power will be removed from the load 1 Ifthe EPO switch or relay contacts are normally closed insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block Use 16 28 AWG wire 2 Insert a wire jumper between pins 1 and 2 Secure the wires by tightening the three screws at positions 1 2 and 3 If the contacts a
16. ngs at any time using the display interface PowerChute software or a network management card Function Factory Default Options Description High Transfer Low Voltage To avoid unnecessary battery usage set the transfer Point 100 V 108 Vac 108 114 Vac point higher if the utility voltage is chronically high and the connected equipment is known to work under 110 V 116 Vac 116 125 Vac this condition The POWER QUALITY setting will automatically change this setting Fender Wee BoA O Vas Note Use the Advanced Menus to configure this 127 V 134 Vac 134 143 Vac setting High Voltage 200 V 216 Vac 216 228 Vac 208 V 220 Vac 220 235 Vac 220 V 242 Vac 242 254 Vac 230 V 253 Vac 253 265 Vac 240 V 264 Vac 264 276 Vac Low Transfer Low Voltage Set the transfer point lower if the utility voltage is Point 100 V 92 Vac 86 92 Vac chronically low and the connected equipment can tolerate this condition The POWER QUALITY setting 110 V 98 Vac 89 98 Vac will automatically change this setting 120 V 106 Vac 97 106 Vac Note Use the Advanced Menus to configure this setting 127 V 112 Vac 103 112 Vac High Voltage 200 V 184 Vac 172 184 Vac 208 V 184 Vac 169 184 Vac 220 V 198 Vac 186 198 Vac 230 V 207 Vac 195 207 Vac 240 V 216 Vac 204 216 Vac Green Mode Transfer Sensitivity 10 If the UPS input voltage is between the high transfer point and the lower transfer point the UPS will operate in Green Mode Configure this setting
17. on on how to obtain local customer support contact the APC by Schneider Electric representative or other distributors from whom you purchased your APC by Schneider Electric product J Select models are ENERGY STAR qualified ener For more information go to www apc com site recycle index cfm energy efficiency energy star ENERGY STAR 2013 APC by Schneider Electric APC the APC logo Smart UPS and PowerChute are owned by Schneider Electric Industries S A S or their affiliated companies All other trademarks are property of their respective owners EN 990 4608B 03 2013
18. r country specific instructions 3 Pack the unit in the original packaging whenever possible to avoid damage in transit Never use foam beads for packaging Damage sustained in transit is not covered under warranty a Always DISCONNECT THE UPS BATTERIES before shipping The United States Department of Transportation DOT and the International Air Transport Association IATA regulations require that UPS batteries be disconnected before shipping The internal batteries may remain in the UPS b External Battery Pack products are deenergized when disconnected from the associated UPS product It is not necessary to disconnect the internal batteries for shipping Not all units utilize an external battery pack 4 Write the RMA provided by Customer Support on the outside of the package 5 Return the unit by insured prepaid carrier to the address provided by Customer Support Transport the unit Shut down and disconnect all connected equipment Disconnect the unit from utility power Disconnect all internal and external batteries if applicable PR ere Follow the shipping instructions outlined in the Service section of this manual Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U 17 Two Year Limited Factory Warranty Schneider Electric IT Corporation SEIT warrants its products to be free from defects in materials and workmanship for a period of three 3 years excluding the batteries which are warranted
19. re opened the UPS will turn OFF and power will be removed from the load Note Pin 1 is the power source for the EPO circuit it provides a few milliampere of 24 V power If the normally closed NC EPO configuration is used the EPO switch or relay should be rated for dry circuit applications the rating should be for low voltage and low current applications This normally implies the contacts are gold plated The EPO interface is a Safety Extra Low Voltage SELV circuit Connect the EPO interface only to other SELV circuits The EPO interface monitors circuits that have no determined voltage potential SELV circuits are controlled by a switch or relay properly isolated from utility power To avoid damage to the UPS do not connect the EPO interface to any circuit other than a SELV circuit Use one of the following cable types to connect the UPS to the EPO switch e CL2 Class 2 cable for general use e CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air e CL2R Riser cable for use in a vertical run in a floor to floor shaft e CLEX Limited use cable for use in dwellings and for use in raceways e Installation in Canada Use only CSA certified type ELC extra low voltage control cable e Installation in countries other than Canada and the USA Use standard low voltage cable in accordance with national and local regulations Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4
20. rsists after recharging replace the battery The replacement battery is not Be sure the battery connector is securely connected properly connected The display interface shows a Site Wiring Fault message Site wiring faults detected include If the UPS indicates a site wiring fault have a qualified electrician inspect missing ground hot neutral the building wiring Applicable for 120 Vac models only polarity reversal and overloaded neutral circuit 16 Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U Service and Transport If the unit requires service do not return it to the dealer Follow these steps 1 Review the Troubleshooting section of the manual to eliminate common problems 2 Ifthe problem persists contact APC by Schneider Electric Customer Support through the APC by Schneider Electric Web site www apc com a Note the model number and serial number and the date of purchase The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models b Call APC by Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone If this is not possible the technician will issue a Returned Material Authorization Number RMA c If the unit is under warranty the repairs are free d Service procedures and returns may vary internationally Refer to the APC by Schneider Electric Web site fo
21. t for a response to each setting if no response is given the default setting will be used Note The UPS will not turn on until all of these settings have been configured Function Factory Default Options Description Language English e English The language for the display interface e French e German Language options will vary by model and firmware version e Spanish e Italian e Portuguese e Japanese Output Low Voltage 120 Vac e 100 Set the output voltage while the UPS is in Standby mode Voltage 110 e 120 127 High Voltage 230 Vac e 200 e 208 e 220 e 230 e 240 Input Power Good e Good Select the desired utility power input quality Quality e Fair e Good The UPS will go on battery power more often to e Poor provide the cleanest power supply to the connected equipment e Fair The UPS will tolerate some voltage fluctuations e Poor The UPS will tolerate more voltage fluctuations and will go on battery power less often If unsure of the local power quality or the connected equipment is sensitive to voltage fluctuations set the sensitivity level to Good using the Advanced menu Menu Type Standard Standard or The advanced menus include all parameters The Standard Advanced menus display a limited set of menus and options Date UPS manufacture date mm yyyy Enter the current date 90 days Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U 9 General settings Configure these setti
22. terval Setting 14 days there after e Last test 7 days e Turn on 14 days The batteries much be charged to at least 70 e Turn on 7 days capacity to perform the self test e On startup only e Never Reset to No Yes No Restore the UPS factory default settings Factory Default Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U 11 Switched Outlet Groups Note Switched Outlet Groups provide battery backup power to connected equipment Overview The Switched Outlet Groups can be configured to independently turn off turn on shut down go into sleep mode and reboot connected equipment The Switched Outlet Groups can be configured to do the following Turn off Disconnect from power immediately and restart only with a manual command e Turn on Connect to power immediately e Shutdown Disconnect power in sequence and automatically reapply power in sequence when utility power becomes available e Reboot Shut down and restart e Sleep Reboot after a long delay In addition the Switched Outlet Groups can be configured to do the following e Turn on or off in a specified sequence e Automatically turn off or shut down when various conditions occur Use of Switched Outlet Groups 1 Connect critical equipment to a Switched Outlet Group 2 Connect peripheral equipment to the other Switched Outlet Groups During a power outage to conserve battery runtime nonessential equipment can be confi
23. ual to warn of potential hazards A CAUTION CAUTION indicates a potentially hazardous situation which if not avoided can result in equipment damage and minor or moderate injury CAUTION CAUTION indicates a potentially hazardous situation which if not avoided can result in equipment damage Safety and General Information Inspect the package contents upon receipt Notify the carrier and dealer if there is any damage Read the Safety Guide supplied with this unit before installing the UPS e Adhere to all local and national electrical codes e This UPS is intended for indoor use only e Do not operate this UPS in direct sunlight in contact with fluids or where there is excessive dust or humidity e Be sure the air vents on the UPS are not blocked Allow adequate space for proper ventilation e The battery typically lasts for three to five years Environmental factors impact battery life Elevated ambient temperatures poor quality utility power and frequent short duration discharges will shorten battery life e Connect the UPS power cable directly to a wall outlet Do not use surge protectors or extension cords e The batteries are heavy Remove the batteries prior to installing the UPS in a rack e Always install external battery packs XLBPs at the bottom of the rack The UPS must be installed above the XLBPs e The UPS display interface will recognize as many as 10 external battery packs conne
24. ue to a Charge the battery Batteries require recharging after extended outages and recent power outage or is near the end wear out faster when put into service often or when operated at elevated of its service life temperatures If the battery is near the end of its service life consider replacing the battery even if the replace battery LED is not illuminated The UPS is experiencing an overload Check the UPS load display Unplug unnecessary equipment such as condition printers Display interface LEDs flash sequentially The UPS has been shut down remotely None The UPS will restart automatically when utility power is restored through software or an optional accessory card The Fault LED is illuminated the UPS displays a fault message and emits a constant beeping sound Internal UPS fault Do not attempt to use the UPS Turn the UPS off and have it serviced immediately Smart UPS X 2000 2200 3000 Vac XL 120 208 230 240 VA Tower Rack Mount 4U 15 Problem and Possible Cause Solution All LEDs are illuminated and the UPS is plugged into a wall outlet The UPS has shut down and the None The UPS will return to normal operation when the power is restored battery has discharged from an and the battery has a sufficient charge extended outage The Replace Battery LED is illuminated The battery has a weak charge Allow the battery to recharge for at least four hours Then perform a self test If the problem pe