Eaton 9SX 8000i

image

Contents

1. Page 18 8 11kVA EU EN 3 Installation 3 7 Rack installation If you ordered other UPS accessories refer to specific user manuals to check the rack installation with the UPS e Prepare EBM for rack mounting This step requires two people The Extended Battery Module is very heavy To ease its rack mounting you can remove the battery pack from the EBM as explained below 1 Remove the center cover of the front panel 2 Remove the four screws to open the front panel 3 Remove the three screws to pull out the metal protection cover of the battery 4 Pull out the plastic handle of the left and right battery packs and slide the packs out slowly on to a flat and stable surface Use two hands to support the battery packs Set them aside for reinstalling after that the EBM is rack mounted 5 Mount the EBM on rack 6 Put back the battery packs screw back the metal protection cover and the front panel then clip the center cover 8 11kVA EU EN Page 19 3 Installation e Rack mounting of UPS EBM and accessory modules Follow steps 1 to 4 for module mounting on the rails The rails and necessary hardware are supplied by EATON Page 20 8 11kVA EU EN 3 Installation 3 8 Installation requirements Recommended protective devices and cable cross sections 1 Recommended upstream protection UPS power rating Upstream circuit breaker 8000VA D curve 50A 110
2. E T N 9SX 8000 9SX 11000 9PX 8000 9PX 11000 9SX EBM 240V 9PX EBM 240V Installation and user manual Copyright O 2012 EATON All rights reserved Service and support Call your local service representative 8 11kVA EU EN Page 2 8 11kVA EU EN SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries The 9SX and 9PX models that are covered in this manual are intended for installation in an environment within 0 to 40 C free of conductive contaminant This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Certification standards e Safety IEC EN 62040 1 Ed 1 2008 UL 1778 4 edition e EMC IEC EN 62040 2 Ed 2 2006 FCC part 15 Class A Performance IEC EN 62040 3 Ed 2 0 2011 IEC 61
3. The following settings are available for configuring Bypass operation Bypass transfer out of tolerance 1 Press any button to activate the menu options then select Settings Output settings and Bypass transfer 2 Select Enabled or Disabled for BP AC NOK and Enter to confirm If Enabled the UPS transfers to Bypass even if Bypass AC source is out of tolerance depending on output mode If Disabled the UPS output is shutdown Interrupt time This setting is displayed to define the break duration during transfer to Bypass only if transfer out of tolerance is enabled 10 ms or 20 ms can be selected Configuring battery settings Automatic battery test Automatic battery tests are done every week in constant charging mode and at each cycle in ABM mode The tests frequency can be modified During the test the UPS transfers to Battery mode and discharges the batteries for 25 seconds under load Battery mode is not displayed and battery low alarm does not activate during a battery test The battery test may be cancelled due to bad conditions or failed Low battery warning During discharge the low battery alarm is activated if the battery capacity goes below 20 This threshold can be modified External battery setting The number of Extended Battery Module is automatically detected or can be set manually in number of EBM or in Ah Deep discharge protection This setting is recommended to avoid damaging the battery Warranty i
4. Dimensions D x W x H mm inch Weight Ib kg 9SXEBM240 680 x 440 x 130 26 8 x 17 3 x 5 1 128 58 9PXEBM240 680 x 440 x 130 26 8 x 17 3 x 5 1 143 65 Table 4 Electrical input Nominal frequency 50 60Hz auto sensing Frequency range 50Hz 40 60Hz before transfer to battery 60Hz 50 70Hz before transfer to battery Bypass voltage range 20 15 of nominal value default Noise filtering MOV for normal and common mode noise Model Default input Selectable input Voltage Voltage Current Voltage range at 100 Load 9SX8KiPM 230V 33 1A 200V 208V 220V 176 276V 9PX8KiPM 230V 240V 250V 9SX11KiPM 230V 45 8A 200V 208V 220V 176 276V 9PX11KiPM 230V 240V 250V Table 5 Electrical input connections Model Input connection Input cable 9SX8KiPM Hardwired Not provided 9PX8KiPM 9SX11KiPM 9PX11KiPM 8 11kVA EU_EN Page 41 9 Specifications Page 42 Table 6 Electrical output All models Normal mode Battery mode Voltage regulation 1 1 Efficiency gt 98 High Efficiency mode gt 91 Frequency regulation gt 94 596 for 8kVA models gt 95 for 11kVA models Sync with line 5 of nominal line frequency outside this range 0 5 of auto selected nominal frequency 0 5 of auto selected nominal frequency Nominal output 200V 208V 220V 230V 240V 250V voltage configurable 8000 11000VA 7200 10000W Frequency 50 or 60Hz autosensing or configurable as a frequ
5. 4 IEC 61000 4 11 for output cable lt 10m 8 11kVA EU_EN 9 Specifications Agency markings CE C Tick cULus Operating temperature 0 to 40 C 32 to 104 F in Online mode with linear derating for altitude Note thermal protection switches load to Bypass in case of overheating Storage temperature 0 to 40 C 32 to 104 F with batteries 15 to 60 C 5 to 140 F without batteries Transit temperature 25 to 55 C 13 to 130 F Relative humidity 0 to 95 no condensing Operating altitude Up to 3 000 meters 9 843 ft above sea level with 10 derating per 1000m Transit altitude Up to 10 000 meters 32 808 ft above sea level Audible noise lt 48 dBA at 1 meter typical for 8kVA models 50 dBA at 1 meter typical for 11kVA models Table 9 Battery EBMs Rack Tower 95 240 240Vdc 20 x 12V 7Ah configuration 9PXEBM240 240Vdc 20 x 12V 9Ah Fuses 63A for 8KVA models 80A for 11kVA models and EBM Type Sealed maintenance free valve regulated lead acid with minimum 3 year float service life at 25 C 77 F Monitoring Advanced monitoring for earlier failure detection and warning Battery port External three pole SBS75G White connector on Power Module for connection to EBM EBM battery 40cm 15 7in cable length Table 10 Communication options Communication bay 1 available independent communication bay for connectivity cards Compatible connec
6. recognition of battery modules Page 9 2 Presentation 2 3 Accessories Part number Description EET Extended Battery Module 9RK Rack kit 9PX Network MS Network card Modbus MS Modbus and network card Relay MS Relay card MBP11Ki HotSwap MBP 11000i SC240RT Supercharger 240VDC TFMR11Ki Transformer 11000i BINTSYS Battery Integration System EBMCBL240 1 8m cable 240V EBM MBP11Ki TFMR11Ki Page 10 00000 OO Input Output terminal blocks Input Output cables for connection to the UPS Bypass terminal blocks for connection to the UPS Normal AC source switch Bypass AC source switch Connector for HotSwap MBP detection Manual Bypass switch 4 16A outlets D Input AC Output DC terminal blocks 2 Connector for battery modules to the UPS and the battery modules Connector for automatic recognition of the Supercharger to the UPS and to the battery modules Input Output terminal blocks 50A output circuit breaker 8 11kVA EU EN 2 Presentation 2 4 Control panel The UPS has a five button graphical LCD It provides useful information about the UPS itself load status events measurements and settings Online mode Fault indicator green indicator red Battery mode Bypass mode indicator orange indicator orange SI SS vaa A N Onl
7. refer to the specific user manual to check the terminal blocks B connection of the UPS with the MBP r BYPASS AC SOURCE 1 Remove the jumper 2 Insert the Normal AC cable through the cable gland N L2 3 Connect the three cables to the Normal AC source terminal blocks L 4 Insert the Bypass AC cable through the cable gland L1 5 Connect the three cables to the Bypass AC source terminal blocks N L2 6 Insert the Output cable through the cable gland 7 Connect the three cables to the Output terminal blocks OUTPUT NORMAL AC SOURCE 8 Put back and secure the terminal blocks cover with the screws 9 Tighten the cable glands 4 4 Frequency converter connection This type of connection must be carried out by qualified electrical personnel A Before carrying out any connection check that the upstream protection device Normal AC source is open O Off Always connect the ground wire first r BYPASS AC SOURCE 1 Remove the jumper 2 Insert the Normal AC cable through the cable gland N L2 3 Connect the three cables to the Normal AC source terminal blocks Do not connect anything to the Bypass N terminal blocks 4 Insert the Output cable through the cable gland L L1 5 Connect the three cables to the Output terminal blocks N L2 6 Put back and secure the terminal blocks cover with th
8. type and number of batteries or battery packs Contact your service representative to order new batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Do open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic Determine if the battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury Disconnect charging source prior to connecting or disconnecting battery terminals 8 11kVA EU EN Page 35 7 UPS maintenance Replacing the EBM s Al The EBM is heavy Lifting the cabinet into a rack requires a minimum of two people To replace the EBM s 1 Unplug the EBM power cable and battery detection cable from the UPS If additional EBM s are installed unplug the EBM power cable and battery detection cable from each EBM 2 Replace the EBM s See Recycling the used equipment on page 37 fo
9. 000 4 2 ESD level 3 IEC 61000 4 3 Radiated field level 3 IEC 61000 4 4 EFT level 4 IEC 61000 4 5 Fast transients level 4 IEC 61000 4 6 Electromagnetic field level 3 IEC 61000 4 8 Conducted magnetic field level 4 Special symbols gt d P gt UU LA p lt 8 11kVA EU_EN The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol Important instructions that must always be followed Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed as it s explain in this manual For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Information advice help Refer to the user manual of UPS accessories Page 3 SAFETY INSTRUCTIONS Safety of persons RISK OF VOLTAGE BACKFEED The system has its own power source the battery Isolate the UPS and check for hazardous voltage upstream and downstream during lockout tagout operation Terminal blocks may be energized even if the system is disconnected from the AC power source Dangerous voltage levels are present within
10. 00VA D curve 63A 2 poles circuit breaker e N L2 to UPS Normal AC source G N L2 L1 2 Recommended cable cross sections Terminal Wire Terminal wire Minimum input Tightening position function size rating wire size torque L1 Phase 4 25 mm 12 4 AWG 10 mm 8 AWG 105 C 18 Ib in N L2 Neutral Phase 16 mm 6 AWG 90 C Ground Copper wire solid or stranded 8 11kVA EU_EN Page 21 3 Installation 3 9 Installation depending on the system earthing arrangement SEA UPS with common Normal and Bypass AC inputs Main low Bypass AC voltage switchboard MLVS Normal AC Change in SEA between upstream and downstream or galvanic isolation required 2 Bypass AC switchboard D T MLVS Isolation transformer Load Normal AC or Main low Bypass AC voltage 14 a switchboard SE MLVS solation transformer 4 Load Normal AC UPS with separate Normal and Bypass AC inputs Main low PEN Bypass AC voltage st switchboard MLVS Isolation transformer Load Normal AC Change in SEA between upstream and downstream or galvanic isolation required Main low y Bypass voltage 1 switchboard MLVS Isolation Isolation transformer transformer Normal AC gt pf Ny The transformer is not n
11. However Eaton recommends that the batteries charge for 48 hours after long term storage Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use them Contact your service representative 73 When to replace batteries When the battery replacement screen is displayed it is recommended to replace the batteries Contact your service representative to order new batteries p Re REESE ET Battery replacemen 4 years battery Replacement is n recommended Page 34 8 11kVA EU EN 7 UPS maintenance 74 Replacing batteries Li DO NOT DISCONNECT the batteries while the UPS is in Battery mode Batteries can be replaced easily without turning off the UPS or disconnecting the load If you prefer to remove input power to change the batteries see UPS Shutdown on page 26 Consider all warnings cautions and notes before replacing batteries Servicing should be performed by qualified service personnel knowledgeable of batteries and AN required precautions Keep unauthorized personnel away from batteries Batteries can present a risk of electrical shock or burn from high short circuit current Observe the following precautions 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots e When replacing batteries replace with the same
12. The EBM charge to 9096 capacity in less than 3 hours However Eaton recommends that the batteries charge for 48 hours after installation or long term storage Starting the UPS on Battery Before using this feature the UPS must have been powered by utility power with output enabled at least once Battery start can be disabled See Coldstart setting in user settings on page 13 To start the UPS on battery 1 Press the D button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The UPS cycles through Standby mode to Battery mode The indicator illuminates solid The UPS supplies power to your equipment 2 Check the UPS front panel display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting on page 38 Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary UPS shutdown To shut down the UPS 1 Press the D button on the UPS front panel The UPS transfers to Standby mode 2 Set the upstream circuit breaker not provided to the O position Off to switch off the utility power Page 26 8 11kVA EU EN 5 2 5 3 5 Operation Operating modes The Eaton 9SX and 9PX front panel indicates the UPS status through the UPS indicators see page 13 Online mode NG During Online mode the W indicator illuminates solid and the UPS is powered from the utility The UPS
13. abinet are absolutely dry hazard of electric shock The cabinet is heavy see in table 6 on page 42 Use caution to unpack and move the cabinet Unpack the equipment and remove all the packing materials and shipping carton Note Do not lift the UPS or EBM from the front panel Unpacking UPS and Extended Battery Module Discard or recycle the packaging in a responsible manner or store it for future use Place the cabinet in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion Packing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing materials to facilitate sorting 8 11kVA EU EN Page 15 3 Installation 3 3 Checking the accessory kit Verify that the following additional items are included with the UPS 1 2 Tower stands Rack kit for 19 inch enclosures optional 3 Cable glands for Input Output connection Network MS communication card optional 5 RS232 communication cable 6 USB communication cable 7 User manual Safety instructions 9 Software CD ROM f you ordered an optional Extended Battery Module EBM verify that the following additional items are included with the EBM 9 contents 1 Battery power cable attached with battery detection cable 2 Stabilizer bracket 4 screws included 3 Rack kit f
14. ansferring the UPS between 85 202 22 27 5 4 Setting High Efflcleney MOS uocis eset tte dee wr ct ra c eere de lg rod 28 5 5 Configuring Bypass 05 1 24 21 2 04 422082000000000000 28 5 6 Configuring battery settings u uu de edes rei dra kde ga pi a ve e dede eda Rein 28 5 7 Retrieving the Event log oce otii ax reri utter viet Uh ed am ed aad od 29 5 8 Retn vng the Fault log 3 22 Unde te one t W eds 29 6 sasa suwaqa RM 30 6 1 GOMMAUMIGATIOM POMS receipt nacen e Rr RU e beta e EU REIR FER ee edd 30 6 2 Eaton Intelligent Power Software suite 2 2 2 2 2 2 2 22222 00000 33 7 UPS 2 2 004444 34 71 E GUIDING ME CI E secus eater eria EE REE 34 72 Stotingthe egulpFaeht u e ete e edere pete e keen rua 34 73 Whento replace batteries ertet sane LER LORS EO n dag bM ERR d a qu 34 FTA Replacing ibattenes e ege te aa aa ordei Ea W at ode dan 35 75 Replacing the UPS equipped with HotSwap 37 76 Recycling the used equipment 00 000000200 000000000000 37 8 Troubleshooting Era tU RF o usu Nue M enr Rud 38 Typical alarms arndita
15. d Enable or disable the buzzer if an alarm occurs Output voltage 200V 208V 220V 230V 240V 230V 250V Output frequency Frequency converter Disabled Enabled Disabled Frequency settable in frequency converter mode Output mode Industrial Network Industrial Set UPS behavior regarding transfer on Bypass In Out settings Input volt hysteresis Sets input voltage hysteresis 10V from 1 to 10V High Efficiency Enabled Disabled Disabled mode Power the output from Bypass for high efficiency Bypass transfer Transfer if BP AC NOK Enabled Enabled Disabled Allow transfer on Bypass out of tolerance 8 11kVA EU_EN Page 13 2 Presentation Page 14 Submenu Available settings Default settings In Out settings Interrupt time If Bypass transfer is enabled Interrupt time 10ms 20ms Define break duration when transfer on Bypass 10ms Overload prealarm 1096 10296 Load 96 when overload alarm occurs 10296 Redundancy mode Unitary UPS Hot Standby Force slew rate value to 0 5Hz s Unitary UPS On Off settings Cold start Enabled Disabled Authorize the product to start on battery power Enabled Forced reboot Enabled Disabled If mains recover during a shutdown sequence If set to Enabled shutdown sequence will complete and wait 10 seconds prior to restart If set to Di
16. d to avoid accidental load loss Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices The 9SX and 9PX models have one available communication bay for the following connectivity cards Network MS card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connects to Ethernet network In addition a Environmental Monitoring Probe can be attached to obtain humidity temperature smoke alarm and security information Modbus MS card has connection to Modbus protocol in addition to network management Relay MS card has isolated dry contact Form C relay outputs for UPS status Utility failure Battery low UPS alarm OK or on Bypass See on page 21 for the location of the communication bay Network MS card Modbus MS card Relay MS card 8 11kVA EU_EN 6 Communication Installation of the communication cards It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 4 secured by screws 2 Insert the communication card in the slot 3 Secure the card cover with the 2 screws Parallel communication port This slot is used for Parallel operation only on 9PX models 6 2 Eaton Intelligent Power Software suite Each 9SX and 9PX UPS ships with Eaton Intelligent Power Sof
17. e is not connected correctly Check the input connections The Remote Power Off RPO switch is active or the RPO connector is missing If the UPS Status menu displays the Remote Power Off notice inactivate the RPO input Input bad wiring Output bad wiring Led is On Beep continuous Input Output cables are not connected to the correct terminal blocks Connect correctly the Input Output cables MBP disconnected The HotSwap MBP is no more connected to the UPS If the HotSwap MBP is connected to the UPS check that the detection connector is correctly plugged Page 39 8 Troubleshooting 8 2 Silencing the alarm Press the ESC Escape button on the front panel display to silence the alarm Check the alarm condition and perform the applicable action to resolve the condition If the alarm status changes the alarm beeps again overriding the previous alarm silencing 8 3 Service and support If you have any questions or problems with the UPS call your Local Distributor or your local service representative and ask for a UPS technical representative Please have the following information ready when you call for service Model number Serial number Firmware version number Date of failure or problem Symptoms of failure or problem Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA
18. e screws OUTPUT NORMAL AC SOURCE 7 Tighten the cable glands 8 11kVA EU EN Page 25 5 Operation 5 1 UPS startup and shutdown If you ordered HotSwap refer the specific user manual to check the startup sequence of the UPS with the MBP Starting the UPS lil Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm To start the UPS 1 Verify that the EBM are connected to the UPS See Connecting the EBM s on page 17 2 Verify that the UPS terminal blocks are connected to AC source 3 Setthe upstream circuit breaker not provided to the I position On to switch on the utility power The UPS front panel display illuminates and shows EATON logo 4 Verify that the UPS status screen shows b press D to start 5 Press the D button on the UPS front panel for at least 3 seconds The UPS front panel display changes status to UPS starting 6 Check the UPS front panel display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting on page 38 If the N indicator is on do not proceed until all alarms are clear Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 7 Verify that the V indicator illuminates solid indicating that the UPS is operating normally and powering the output The UPS should be in Online mode
19. east expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Eaton 9SX and 9PX you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Providing outstanding performance and reliability the Eaton 9SX and 9PX s unique benefits include True online double conversion technology with high power density utility frequency independence and generator compatibility ABM technology that uses advanced battery management to increase battery service life optimize recharge time and provide a warning before the end of useful battery life Selectable High Efficiency mode of operation Standard communication options one RS 232 communication port one USB communication port and relay output contacts Optional connectivity cards with enhanced communication capabilities Extended runtime with up to twelve Extended Battery Modules EBMs per UPS Firmware that is easily upgradable without a service call Remote On Off control through Remote On Off ROO and Remote Power Off RPO ports Backed by worldwide agency approvals Page 7 2 Presentation 2 1 Standard installations Tower installation Power module D Rack installation Power module Battery module Battery module Descri
20. ecessary if x 7 T Normal and Bypass inputs are connected to the same source 7 and wires cross sections and lengths of Normal and Bypass inputs are identical and upstream protection is provided by only one switch with RCD Residual Current Device for Normal and Bypass AC inputs Page 22 8 11kVA EU EN UPS with separate Normal and Bypass AC inputs supplied by separate sources Bypass AC MLVS1 Isolation transformer 3 Installation 8 MLVS2 8 Load Normal AC Bypass AC MLVS1 O T Isolation transformer MLVS2 Normal AC Isolation transformer Load Change in SEA between upstream and downstream or galvanic isolation required Bypass AC MLVS1 AD Isolation transformer Normal AC Frequency converter without Bypass AC input Configuration used when the frequency of example marine requirements the application differs from Normal AC Main low voltage switchboard MLVS gt gt Normal AC Load Hot standby Configuration used to provide N 1 redundancy to critical loads Main low voltage Bypass AC switchboard MLVS Isolation transformer eu Normal AC Lt Normal AC 8 11kVA EU_EN Page 23 4 Power cables connection 4 1 Access to terminal blocks 1 Remove the terminal b
21. ency converter Output overload 100 102 no alarm 102 110 load transfers to Bypass mode after 2 minutes 110 12596 load transfers to Bypass mode after 1 minute 125 150 load transfers to Bypass mode after 10s gt 150 load transfers to Bypass mode after 500ms Output overload 100 125 no alarm Bypass mode 125 150 UPS shuts down after 1 minute gt 15096 UPS shuts down after 1s Voltage waveform Sinewave Harmonic distortion 296 THDV on linear load 596 THDV on non linear load Transfer time Power factor Online mode 0 ms no break High Efficiency mode 10ms maximum due to loss of utility 0 9 Load crest ratio to 1 200 208 250V are derated at 10000VA 9000W 220V is derated at 9900W for 11kVA models Table 7 Electrical output connections Model 9SX8KiPM 9PX8KiPM 9SX11KiPM 9PX11KiPM Output connection Output cable Hardwired Not provided Table 8 Environmental and safety EMC certifications IEC EN 62040 1 2008 IEC EN 62040 2 2006 Cat C2 IEC EN 62040 3 2011 IEC 60950 1 UL 1778 4 CSA 22 2 EMC Emissions CISPR22 Class A AS NZS 22 Class A IEC 61000 3 2 3 12 IEC 61000 3 3 3 11 FCC part 15 Class EMC Immunity IEC 61000 2 2 IEC 61000 4 2 Level 3 IEC 61000 4 3 Level 3 IEC 61000 4 4 Level 4 also on signal ports IEC 61000 4 5 Level 4 Criteria B IEC 61000 4 6 Level 3 IEC 61000 4 8 Level
22. ercentage of battery charge is reached 0 Battery charge mode ABM cycling Constant charge ABM cycling External battery Auto detection Manual EBM set Manual battery set Auto detection Using standard EBM UPS detects automatically the No battery number of EBM connected Deep Disch Yes No Yes protect If set to Yes the UPS automatically prevents battery from deep discharge by adapting end of back up time voltage threshold Warranty void if set to No 8 11kVA EU EN 3 1 i i 3 Installation Inspecting the equipment If any equipment has been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representative Unpacking the cabinet Unpacking the cabinet in a low temperature environment may cause condensation to occur in and on the cabinet Do not install the cabinet until the inside and outside of the c
23. ery e contact normally open e n c contact normally closed The relay output contacts must not be connected to any utility connected circuits AN Reinforced insulation to the utility is required The relay output contacts have a maximum rating of 250 Page 30 8 11kVA EU EN 6 Communication Remote On Off Remote On Off allows remote action of D button to switch On Off the UPS 2 Normally open When contact changes from open to closed the UPS is switched on or stays On When contact changes from closed to open the UPS is switched off or stays Off On Off control via button has priority over the remote control Remote Power Off RPO is used to shutdown the UPS remotely This feature can be used for shutting down the load and the UPS by thermal relay for instance in the event of room over temperature When RPO is activated the UPS shuts down the output and all its power converters immediately The UPS remains on to alarm the fault The RPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from hazardous voltage circuits by reinforced insulation The RPO must not be connected to any utility connected circuits Reinforced insulation to the N utility is required The RPO switch must have a minimum rating of 27 Vdc and 20 mA and be a dedicated latching type switch not tied into any other circuit The RPO signal must
24. he following table describes typical conditions Conditions Possible cause Action Battery mode LED is On 1 beep every 10 seconds A utility failure has occurred and the UPS is in Battery mode The UPS is powering the equipment with battery power Prepare your equipment for shutdown Battery low LED is On 1 beep every 3 seconds The UPS is in Battery mode and the battery is running low This warning is approximate and the actual time to shutdown may vary significantly Depending on the UPS load and number of Extended Battery Modules EBMs the Battery Low warning may occur before the batteries reach 20 capacity No battery LED is On Beep continuous The batteries are disconnected Verify that all batteries are properly connected If the condition persists contact your service representative Battery fault LED is On Beep continuous The battery test is failed due to bad or disconnected batteries or the battery minimum voltage is reached in ABM cycling mode Verify that all batteries are properly connected Start a new battery test if the condition persists contact your service representative The UPS does not provide the expected backup time The batteries need charging or service Apply utility power for 48 hours to charge the batteries If the condition persists contact your service representative Bypass mode LED is on An overl
25. he trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center Do not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Page 37 8 Troubleshooting 8 1 Page 38 The Eaton 9PX and 9SX are designed for durable automatic operation and also alert you whenever potential operating problems may occur Usually the alarms shown by the control panel do not mean that the output power is affected Instead they are preventive alarms intended to alert the user Events are silent status information that are recorded into the Event log Example AC freq in range Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking Some alarms may be announced by a beep every 3 seconds Example Battery low Faults are announced by a continuous beep and red LED recorded into the Fault log and displayed on the LCD with a specific message box Example Out short circuit Use the following troubleshooting chart to determine the UPS alarm condition Typical alarms and faults To check the Event log or Fault log 1 Press any button on the front panel display to activate the menu options 2 Press the I button to select Event log or Fault log 3 Scroll through the listed events or faults T
26. ine mode 50 5 0kW 5 5kVA Efficiency 95 Escape Up Down Enter On Off button The following table shows the indicator status and description Indicator Status Description N The UPS is operating normally on Online or on High On ee Green Efficiency mode On The UPS is on Battery mode Orange The UPS is Bypass mode Orange The UPS has an active alarm or fault See trouble On Red shooting on page 38 for additional information 8 11kVA EU EN Page 11 2 Presentation 2 5 Page 12 LCD description After 5 minutes of inactivity the LCD displays the screen saver The LCD backlight automatically dims after 10 minutes of inactivity Press any button to restore the screen Operation status Load equipment status Efficiency information Battery status The following table describes the status information provided by the UPS Note If other indicator appears see troubleshooting on page 38 for additional information Operation status Cause Description Standby mode The UPS is Off Equipment is powered but not protected by the UPS Online mode The UPS is operating normally The UPS is powering and protecting the equipment Battery mode 1 beep every 10 seconds A utility failure has occured and the UPS is on Battery mode The UPS is powering the equipment with the battery power Prepare your equipment f
27. is in Bypass mode Bypass LED should be On Turn the HotSwap MBP switch to the Bypass position the red LED on the HotSwap MBP goes On indicating that the load is now powered directly from utility power Set the Normal AC source and Bypass AC source switches on the HotSwap MBP to the O position and wait for 30s The UPS stops and can now be disconnected To reinstall the UPS APRANdA o Check that the UPS is correctly connected to the HotSwap MBP Set the Normal AC source and Bypass AC source switches on the HotSwap MBP to the I position Press the 1 button to switch On the UPS Select Control then Go to Bypass Turn the HotSwap MBP switch to the Normal position the red LED on the HotSwap MBP goes Off indicating that the load is now powered by the UPS Bypass LED should be On Select Control then Go back normal Check that the UPS is in Online mode the load is now protected by the UPS Online LED should be On 76 Recycling the used equipment Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment 8 11kVA EU EN Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements Do notopen or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic Do not discard the UPS or the UPS batteries in t
28. ll settings to original values Reset average power Clears average power usage measurement Reset cumul power Clears cumulated power usage measurement Dry contacts test Tests dry contact relay outputs Settings Local settings Sets product general parameters In Out settings Sets Output parameters On Off settings Sets On Off conditions Battery settings Sets battery configuration Event log Event filter Selects faults alarms and or events to display Event list Displays the events stored Reset event list Clears events Fault log Fault list Displays the faults stored Reset fault list Clears faults Identification Product type model Part Serial number UPS NMC firmware Com card IPv4 Com card IPv6 Com card MAC Detected accessories Register product Links to Eaton registration website 2 7 User settings The following table displays the options that can be changed by the user Submenu Available settings Default settings Language English Francais Deutsch English Espanol Portugu s User selectable when UPS is Italiano powered for the first time Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages Local settings Date time Format International International US LCD Modify LCD screen brightness and contrast to be adapted to room light conditions Audible alarm Enabled Disabled on battery Enabled Always disable
29. llts co tenter rete Qua a uui uha ege 38 8 2 SIl meinog ii3esalaf tuu 40 Service and SUppOLL uses pro Tae E EAT CY REED na etatens 40 9 SPENN een 41 9 1 Model SBeecilleatlOnis adt e eee eee here eda ac e ai dede deed 41 10 Glossary EE EE 44 Page 5 1 Introduction 1 1 Page 6 Thank you for selecting an EATON product to protect your electrical equipment The 9SX and 9PX range has been designed with the utmost care We recommend that you take the time to read this manual to take full advantage of the many features of your UPS Uninterruptible Power System Before installing your 9SX and 9PX please read the booklet presenting the safety instructions Then follow the indications in this manual To discover the entire range of EATON products and the options available for the 9SX and 9PX range we invite you to visit our web site at www eaton com powerquality or contact your EATON representative Environmental protection EATON has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components e The cardboard we use comprises over 50 of recycled cardboard e Sacks and bags are made of polyethylene e Packing materials are recyclable and bear the appropriate identification sy
30. locks cover one screw 2 Punch the knockouts and insert the cables conduits inside High leakage current AN Earth connection essential before connecting supply 42 Common input sources connection This type of connection must be carried out by qualified electrical personnel Before carrying out any connection check that the upstream protection devices Normal AC source and Bypass AC source are open O Off Always connect the ground wire first If you ordered a HotSwap MBP refer to the specific user manual to check the terminal blocks connection of the UPS with the MBP BYPASS AC SOURCE 1 Make sure the jumper is connected 2 Insert the Normal AC cable through the cable gland 3 Connect the three cables to the Normal AC source terminal blocks 4 Insert the Output cable through the cable gland 5 Connect the three cables to the Output terminal blocks 6 Put back and secure the terminal blocks cover with the screw OUTPUT NORMALAGSOURGE 7 7 Tighten the cable glands Page 24 8 11kVA EU EN 4 Power cables connection 4 3 Separate input source connection This type of connection must be carried out by qualified electrical personnel AN Before carrying out any connection check that the upstream protection devices Normal AC source and Bypass AC source are open O Off Always connect the ground wire first If you ordered a HotSwap MBP
31. mbol S PET Materials Abbreviations Number in S the symbols 7 Polyethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations for the disposal of packing materials End of life EATON will process products at the end of their service life in compliance with local regulations EATON works with companies in charge of collecting and eliminating our products at the end of their service life Product The product is made up of recyclable materials Dismantling and destruction must take place in compliance with all local regulations concerning waste At the end of its service life the product must be transported to a processing center for electrical and electronic waste Battery The product contains lead acid batteries that must be processed according to applicable local regulations concerning batteries The battery may be removed to comply with regulations and in view of correct disposal 8 11kVA EU EN 8 11kVA EU EN The Eaton 95 and 9PX uninterruptible power system UPS protects your sensitive electronic equipment from the most common power problems including power failures power sags power surges brownouts 1 Introduction line noise high voltage spikes frequency variations switching transients and harmonic distortion Power outages can occur when you l
32. monitors and charges the batteries as needed and provides filtered power protection to your equipment Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack environment See user settings on page 13 Battery mode l When the UPS is operating during a power outage the alarm beeps once every ten seconds and the indicator illuminates solid The necessary energy is provided by the battery When the utility power returns the UPS transfers to Online mode operation while the battery recharges If battery capacity becomes low while in Battery mode the audible alarm beeps once every 3 seconds This warning is approximate and the actual time to shutdown may vary significantly Shutdown all applications on the connected equipment because automatic UPS shutdown is imminent When utility power is restored after the UPS shuts down the UPS automatically restarts Bypass mode O In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available and your equipment is not protected however the utility power continues to be passively filtered by the UPS The GO indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for at least 5 seconds and will stay in this mode if three transfers to Bypass occur within 20 minutes The UPS transfers to Bypass mode when the user activates Bypass mode through the front pa
33. nel the UPS detects an internal failure the UPS has an overtemperature condition o the UPS has an overload condition listed in table 6 on page 42 The UPS shuts down after a specified delay for overload conditions listed in table 6 on page 42 The UPS remains on to alarm the fault Standby mode b When the UPS is turned off and remains connected to AC source the UPS is in Standby mode Depending if Bypass Standby setting is enabled the output is powered but not protected The battery recharges when necessary and the communication ports are powered Transferring the UPS between modes From Online or Battery to Bypass mode Press any button to activate the menu options then select Control and Go to Bypass From Bypass to Online or Battery mode Press any button to activate the menu options then select Control and Go back normal 8 11kVA EU EN Page 27 5 Operation 5 4 H 5 5 5 6 Page 28 Setting High Efficiency mode On High Efficiency mode the UPS operates normally on Bypass transfers to Online or Battery mode in less than 10 ms when utility fails and transfers back to Bypass in 5 minutes after utility returns Eaton recommends to use the HE mode only to protect I T equipment To set the High Efficiency mode 1 Press any button to activate the menu options then select Settings Output settings and High Efficiency mode 2 Select Enabled and Enter to confirm Configuring Bypass settings
34. ns will require at least two people unpacking installation in rack system Before and after the installation if the UPS remains de energized for a long period the UPS must be energized for a period of 24 hours at least once every 6 months for a normal storage temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety In case of doubt don t hesitate to contact your EATON representative All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABLE PARTS inside the UPS 8 11kVA EU EN 8 11kVA EU EN Contents T Introductio eee 6 11 Environmental nn 6 2 Presentation u uu u 8 2 1 Standard installations eene KANE 8 2 2 Rea Panel panna eres 9 2 3 erts T 10 2 4 Oo pp 01 PAM l tester tere tih e ce d ca e p rcd 11 2 5 LbOD desernptiornm oett ver P ad EU e V ee DEN 12 26 s qasqa 13 2 7 USGPSStUngs asset en bte estes Patto peste
35. number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units For critical applications immediate replacement may be available Call the Help Desk for the dealer or distributor nearest you Page 40 8 11kVA EU EN Model specifications Table 1 Power Module model list 9 Specifications Model Power Ratings 9SX8KiPM 8000VA 7200W 9PX8KiPM 8000VA 7200W 9SX11KiPM 10000VA 9000W at 200V 208V 250V output 9PX11KiPM 11000VA 9900W at 220V output 11000VA 10000W at 230V 240V output Table 2 Extended Battery Module model list Model Configuration Battery voltage For power ratings 9SXEBM240 Rack Tower 240Vdc 8000 11000VA 9PXEBM240 Rack Tower 240Vdc 8000 11000VA Table 3 Weights and dimensions Model Power Module Dimensions D x W x H mm inch Weight Ib kg 9SX8KiPM 700 x 440 x 130 27 6 x 17 3 x 5 1 42 19 9PX8KiPM 700 x 440 x 130 27 6 x 17 3 x 5 1 42 19 9SX11KiPM 700 x 440 x 130 27 6 x 17 3 x 5 1 46 21 9PX11KiPM 700 x 440 x 130 27 6 x 17 3 x 5 1 46 21 Model EBM
36. oad or a fault has occurred or a command has been received and the UPS is in Bypass mode Equipment is powered but not protected by the UPS Check for one of the following alarms overtemperature overload or UPS failure 8 11kVA EU EN 8 11kVA EU EN 8 Troubleshooting Power overload LED is On Beep continuous UPS overtemperature LED is On 1 beep every 3 seconds Power requirements exceed the UPS capacity greater than 100 of nominal see in table 6 on page 42 for specific output overload ranges The UPS internal temperature is too high or a fan has failed At the warning level the UPS generates the alarm but remains in the current operating state If the temperature rises another 10 C the UPS transfers to Bypass mode or shuts down if Bypass is unusable Remove some of the equipment from the UPS The UPS continues to operate but may switch to Bypass mode or shut down if the load increases The alarm resets when the condition becomes inactive If the UPS transferred to Bypass mode the UPS will return to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflow around the UPS is not restricted Restart the UPS If the condition continues to persist contact your service representative The UPS does not start The input sourc
37. or shutdown End of backup time 1 beep every 3 seconds The UPS is on Battery mode and the battery is running low This warning is approximate and the actual time to shutdown may vary significantly Depending on the UPS load and number of Extended Battery Modules EBMs the Battery Low warning may occur before the battery reaches 20 capacity High Efficiency mode The UPS is operating on High Efficiency mode The UPS is powering and protecting the equipment Bypass mode An overload or a fault has occurred or a command has been received and the UPS is in Bypass mode Equipment is powered but not protected by the UPS 8 11kVA EU EN 2 Presentation 2 6 Display functions Press the Enter button to activate the menu options Use the two middle buttons and W to scroll through the menu structure Press the Enter button to select an option Press the ESC button to cancel or return to the previous menu Main menu Submenu Display information or Menu function Measurements Load W VA A pf Input Bypass V Hz Output Efficiency V Hz 96 Battery 96 min V n DCbus V Average power usage Wh Cumulat power usage Wh since date Control Go to Bypass Transfers the UPS on Bypass mode Start battery test Starts a manual battery test Reset fault state Clears active fault Restore factory set Returns a
38. or 19 inch enclosures optional EBM Installation manual Discard the EBM user s guide if you are installing the EBM with a new UPS at the same time Use the UPS user s guide to install both the UPS and the EBM If you ordered other UPS accessories refer to specific user manuals to check the packing 8 11kVA EU EN 3 Installation 3 4 Connecting the EBM s A small amount of arcing may occur when connecting an EBM to the UPS This is normal and N will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly 1 Plug the EBM power cable s into the battery connector s Up to 12 EBMs may be connected to the UPS 2 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable 3 Connect the battery detection cable s to the connector of the UPS and of the EBM s If you ordered other UPS accessories refer to specific user manuals to check the connection to the UPS 8 11kVA EU EN Page 17 3 Installation 3 6 Tower installation If you ordered other UPS accessories refer to specific user manuals check the tower installation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its final location 2 Always keep 150 mm of free space behind the UPS rear panel 3 If installing additional cabinets place them next to the UPS in their final location
39. ption Weights Dimensions inch mm Ib kg DxWxH 95 8000 Power Module 42 19 27 6 x 17 3 x 5 1 700 x 440 x 130 95 11000 Power Module 46 21 27 6 x 17 3 x 5 1 700 x 440 x 130 9PX 8000 Power Module 42 19 27 6 x 17 3 x 5 1 700 x 440 x 130 9PX 11000 Power Module 46 21 27 6 x 173 x 5 1 700 x 440 x 130 9SX EBM 240V 128 58 26 8 x 173 x 5 1 680 x 440 x 130 9PX EBM 240V 143 65 26 8 x 173 x 5 1 680 x 440 x 130 Page 8 8 11kVA EU EN 2 2 Rear panels 9SX 8000 Power Module 9SX 11000 Power Module 8 era 3 AS 9PX 11000 Power Module DO 99 1 GEN E GER AN OJOS mud 9SX 9PX EBM 240V Extended Battery Module Ei a LEXY RS 8 11kVA EU EN 0000 ew 2 Presentation RS232 communication port USB communication port Dry relay contacts communication port Connector for ROO Remote On Off control Connectors for automatic recognition of battery module Connector for Parallel operation for 9PX only Connector for RPO Remote Power Off control Slot for optional communication card Connector for battery module Input Output terminal blocks Connector for HotSwap MBP detection Connectors for battery modules to the UPS or to the other battery modules Connectors for automatic
40. r proper disposal A small amount of arcing may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly Plug the EBM cable s into the battery connector s Up to twelve EBMs may be connected to the UPS 4 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable 5 Connect the battery detection cable s to the connector of the UPS and of the EBM s e Testing new batteries To test new batteries 1 Charge the batteries for 48 hours 2 Press any button to activate the menu options 3 Select Control then Start battery test The UPS starts a battery test if the batteries are fully charged the UPS is in Normal mode with no active alarms and the bypass voltage is acceptable During the battery test the UPS transfers to Battery mode and discharges the batteries for 25 seconds The front panel displays Battery test in progress and the percentage of the test completed Page 36 8 11kVA EU EN 75 Replacing the UPS equipped with a HotSwap MBP 7 UPS maintenance The HotSwap MBP allows to service or replace the UPS without interrupting the connected loads Refer to the specific user manual for more information about HotSwap MBP To remove the UPS 1 2 3 4 5 Press any button to activate the menu options Select Control then Go to Bypass Check that the UPS
41. remain active for at least 250 ms for proper operation To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the Remote Power Off function is activated needed Li Leave the RPO connector installed in the RPO port on the UPS even if the RPO function is not RPO connections Internal power supply External power supply eue PRIS e e 1 3 1 3 1 3 1 3 Normally closed Normally open Normally closed Normally open Terminal wire size rating is 0 32 4 mm 22 12 AWG Suggested wire size is 0 82 mm 18 AWG 8 11kVA EU EN Page 31 6 Communication Page 32 Remote control connection and test 1 Check the UPS is shut down and the electrical supply network disconnected 2 Remove RPO connector from the UPS by unfitting the screws 3 Connect a normally closed volt free contact between the two pins of connector Contact open shut down of UPS To return to normal operation deactivate the external remote shut down contact and restart the UPS from the front panel o 1 3 Normally closed 4 Plug the RPO connector into the back of the UPS and fix the screws 5 Connect and restart the UPS according to the previously described procedures 6 Activate the external remote shut down contact to test the function Always test the RPO function before applying your critical loa
42. s aude exe dan cafe v 13 3 Installation u 15 3 1 Inspecting the equipment 00 0 15 32 Unp ckng the Cabinet s Eod ete eerie etae ei edge etd eux uud rene a ERR PETRA eT an 15 3 9 Checking the accessory Kits trc terr a E cart nde de rt 16 3 4 Connecting the EBM S 42 2 4 2 2020 00200000000000000 17 3 5 Connecting other acc ssorles eite Hd e edit dede rae a 17 3 6 lower nstallatiOno iue E tent dee bodes UR ERA sas vg Geer asa asua 18 3 7 EE 19 3 8 Installation requirements 22 21 3 9 Installation depending on the system earthing arrangement 22 4 Power cables connection 24 4 ACCESS to Terminal BIGSRS tue ect Lot ee e le bue 24 4 2 Common input sources 2 1222 7220000001102100 nenn iE rEnnEEnr nnna nt 24 4 3 Separate input source connection 121 2402002000000000 25 4 4 Frequency converter 25 5 Operation u EE a ROO 26 5 UPS startup and 2 24 4242 22 6 eene 26 52 Operating Todes oni pev cnr teta t Uo RU TRY D RP P ted Ge cv 27 5 3 Tr
43. s void if deep discharge protection is disabled 8 11kVA EU EN 5 7 Retrieving the Event log To retrieve the Event log through the display 1 Press any button to activate the menu options then select Event log 2 Scroll through the listed events 5 8 Retrieving the Fault log To retrieve the Fault log through the display 1 Press any button to activate the menu options then select Fault log 2 Scroll through the listed faults 8 11kVA EU EN 5 Operation Page 29 6 Communication 6 1 Communication ports RS232 or USB communication ports The RS232 and USB communication ports cannot operate simultaneously 1 Connect the RS232 16 or USB 2 communication cable to the serial or USB port on the computer 2 Connect the other end of the communication cable 46 or to the RS232 1 or USB 2 communication port on the UPS The UPS can now communicate with EATON power management software Relay output contacts The UPS incorporates four programmable relay outputs each information is available with a close or open contact common Status active information if contact between pin and common is closed Pin 1 not on Bypass Pin 2 load not protected Pin 3 not low battery e Pin 4 not on Battery Pin b user common e Pin 6 on Bypass Pin 7 low battery e Pin 8 load protected e Pin 9 on Batt
44. sabled shutdown sequence will not complete and restart will occur immediately Enabled Auto restart Enabled Disabled Authorize the product to restart automatically when mains recovers after a complete battery discharge Enabled Auto start Enabled Disabled The UPS automatically starts up as soon as mains power is available no need topress the D button Disabled Energy saving Disabled 100W 1000W If Enabled UPS will shutdown after 5 min of back up time if load is less than threshold Disabled Sleep mode Enabled Disabled If Disabled LCD and communication will turn OFF immediately after UPS is OFF If Enabled LCD and communication stays ON 1h30 min after UPS is OFF Enabled Remote command Enabled Disabled If Enabled shutdown or restart commands from software are authorized Enabled Bypass standby Enabled Disabled Define if output is powered from Bypass in Standby mode Enabled Battery settings Automatic battery test In constant charge mode No test Every day Every week Every month In ABM cycling mode No test Every ABM cycle Every ABM cycle Low battery warning 096 10096 The alarm triggers when the set percentage of battery capacity is reached during back up time 20 Restart bat level 0 100 If set automatic restart will occur only when p
45. t the loads directly to the AC source Transfer of the load to the manual bypass enables UPS maintenance without interrupting the supply of power to the connected loads The normal UPS operating mode in which the AC source supplies the UPS which in turn supplies the connected loads after electronic double conversion Normal source of power for the UPS Contacts supplying information to the user in the form of signals Uninterruptible Power Supply 8 11kVA EU EN
46. th branch circuit overcurrent protection for 50A rating for 8kVA models 70A rating for 11kVA models in accordance with the National Electric Code ANSI NFPA 70 US installations only The upstream circuit breaker must be easily accessible The unit can be disconnected from AC power source by opening this circuit breaker Disconnection and overcurrent protection devices shall be provided by others for permanently connected AC input output circuits Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system For PLUGGABLE EQUIPMENT the socket outlet shall be installed near the equipment and shall be easily accessible Never install the system near liquids or in an excessively damp environment Never let a foreign body penetrate inside the system Never block the ventilation grates of the system Never expose the system to direct sunlight or source of heat If the system must be stored prior to installation storage must be in a dry place The admissible storage temperature range is 15 C to 50 C The system is not for use in a computer room AS DEFINED IN the standard for the Protection of Information Technology Equipment ANSI NFPA 75 US installations only Contact Eaton resellers to order a special battery kit if needed to meet the NE code requirement Special precautions Page 4 All handling operatio
47. the system It should be opened exclusively by qualified service personnel The system must be properly grounded The battery supplied with the system contains small amounts of toxic materials To avoid accidents the directives listed below must be observed servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions when replacing batteries replace with the same type and number of batteries or battery packs do not dispose of batteries in a fire The batteries may explode batteries constitute a danger electrical shock burns The short circuit current may be very high Precautions must be taken for all handling Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Product safety The UPS connection instructions and operation described in the manual must be followed in the indicated order CAUTION To reduce the risk of fire the unit connects only to a circuit provided wi
48. tivity Network MS cards Modbus MS Relay MS Communication ports RS 232 DB9 1200 19200 bps USB 19200 bps Parallel port DB15 only for 9PX models Relay output contacts 4 programmable relay outputs normally open or normally closed Remote On Off 2 pins jumper normally open Remote Power Off 3 pins jumper normally open or normally closed 8 11kVA EU EN Page 43 10 Glossary Page 44 Bypass AC source Frequency converter Low battery warning Backup time Load HE mode Manual bypass Normal double conversion mode Normal AC source Relay contacts UPS Source supplying the bypass line The equipment can be transferred to the by pass line if an overload occurs on the UPS output for maintenance or in the event of a malfunction Operating mode used to convert the AC power frequency between the UPS input and output 50Hz gt 60Hz or 60Hz gt 50Hz This is a battery voltage level indicating that battery power is low and that the user must take action to prevent the imminent break in the supply of power to the load Time during which the load can be supplied by the UPS operating on battery power Devices or equipment connected to the UPS output Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This mode reduces the consumption of electrical power Rotary switch controlled by the user used to connec
49. tware suite To begin installing see the instructions accompanying the Software suite CD Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives you a complete record of critical power events and it notifies you of important UPS or power information If there is a power outage and the 9SX and 9PX UPS battery power becomes low Eaton Software suite can automatically shut down your computer system to protect your data before the UPS shutdown occurs 8 11kVA EU EN Page 33 7 UPS maintenance 71 Equipment care For the best preventive maintenance keep the area around the equipment clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For full battery life keep the equipment at an ambient temperature of 25 C 77 F The batteries are rated for a 3 5 year service life The length of service life varies depending on the frequency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 4 years to keep units running at peak efficiency Inm If the UPS requires any type of transportation verify that the UPS is disconnected and turned off 72 Storing the equipment If you store the equipment for a long period recharge the battery every 6 months by connecting the UPS to utility power The EBM charge to 9096 capacity in less than 3 hours

Download Pdf Manuals

image

Related Search

Related Contents

Fluke 90 Series - uP Board Tester  SmartMetals 063.8100  Operation Manual  IMPORTANTE: Manual de instalación y operación  DL3 User Manual - DataLocker.com  EFFECT 800 PLUS Mattress Replacement System User Manual  BlackBerry Client para Microsoft SharePoint Guía del usuario    Honeywell T7022A User's Manual  Manuel d`utilisation Optoma EP709  